Plans.pdf
PDF 24 MB Posted
- Attached to
- Project 13836. CDCR EVSE. Contract 25-289268
- Solicitation number
- 0000037478
- Issued by
- Fresno County, Fresno City, California
About this file
This is a construction document set and contract opportunity for the California Department of Corrections and Rehabilitation (CDCR) to install electric vehicle supply equipment (EVSE) infrastructure at Pleasant Valley State Prison in Coalinga, Fresno County, California. The project involves designing and constructing the site and electrical infrastructure necessary to support two electric vehicle charging stations: one single-port Level 3 charger and one dual-port Level 3 charger, totaling three charging ports designated for fleet use only. The scope of work includes site preparation, electrical trenching and conduit installation, concrete pad construction, bollard installation, equipment installation, and restoration of affected surfaces. The project is located at 24863 West Jayne Avenue, Coalinga, CA 93210, on California state property (APN 085-020-35ST). Key technical specifications include a 500 kVA transformer (12 kV to 480Y/277V), a 600-amp distribution panel, two power cabinets rated at 227 full load amps each, underground electrical conduit systems, and grounding infrastructure. The contractor is responsible for furnishing labor, materials, and services for complete system installation and operational testing. No existing parking spaces will be impacted by the project.
Contract 25-289268 (Project Number 13836) is restricted to certified Small Business and Micro Business contractors as set forth under Government Code 14838.7, with bids submitted electronically to jannice.castro@dgs.ca.gov prior to 2:00 p.m. A Class C-10 (Electrician) license is required to bid this project. Contractors must submit valid Certificates of Reported Compliance (CRC) for any fleet vehicles retained by the contractor or subcontractors that are subject to California Air Resources Board In-Use Off-Road Diesel-Fueled Fleet Regulations. The construction documents are dated April 25, 2025, with Fire Marshal approval granted on July 15, 2025. Design consultants include Blair Church & Flynn (electrical and structural), with project oversight by the California Department of General Services and CDCR Project Director Steven Piepenhagen. All work must comply with 2022 California codes including the California Building Code, California Electrical Code, California Fire Code, and applicable Title 24 requirements. The state will provide the electric vehicle charging stations, with final installation and termination to be completed by the current state EVSE vendor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date Signed:
Date Signed:
04-25-2025
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a sa n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n ti .d w g L a y o u t1
B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 000000000013835
Date Signed:
04-25-2025
24863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 03/31/2027EXP 06/30/2026
SHEET INDEX
SHEET NO. TITLE
T1.0 TITLE SHEET
C1.0 OVERALL SITE MAP
C2.0 DEMOLITION PLAN
C3.0 SITE PLAN
C4.0 DETAILS
E1.0 ELECTRICAL CONDUIT PLAN
E2.0 CONDUIT SECTIONS & DETAILS
E2.1 CONDUIT SECTIONS & DETAILS
E3.0 ELECTRICAL SCHEDULE & CIRCUITS
R1.0 REFERENCE DRAWINGS
R1.1 REFERENCE DRAWINGS
R2.0 TITLE 24 DOCUMENTS
TOTAL NUMBER OF SHEETS = 12
PROJECT
LOCATION
W JAYNE AVE
TITLE SHEET
T1.0
PROJECT LOCATION:
PROJECT IS LOCATED AT:
24863 WEST JAYNE AVENUE
COALINGA, CA 93210
APN: 085-020-35ST
SCOPE OF EV IMPROVEMENT WORK:
1. SITE AND ELECTRICAL INFRASTRUCTURE IMPROVEMENTS FOR INSTALLATION OF EV
CHARGERS.
2. IMPACTED EXISTING PARKING = 0 TOTAL SPACES; 0 STANDARD SPACES
3. ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL INSTALLATION OF
THE EVSE, SUCH WORK IS IN THE PERMIT SCOPE AND MAY BE PERFORMED BY OTHERS.
LIST OF CONSULTANTS:
STRUCTURAL: ELECTRICAL:
BRIAN BROOKS
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
DARIO ROMERO
BLAIR CHURCH & FLYNN
451 CLOVIS AVE. STE 200
CLOVIS, CA 93612
(559) 326-1400
PROJECT DIRECTOR:
STEVEN PIEPENHAGEN
DEPARTMENT OF CORRECTIONS
AND REHABILITATION
24863 WEST JAYNE AVENUE
COALINGA, CA 93210
CELL: (279) 945-8547
OWNER/REPRESENTATIVE
INFORMATION:
DEPARTMENT OF CORRECTIONS AND
REHABILITATION
24863 WEST JAYNE AVENUE
COALINGA, CA 93210
EMAIL: STEVEN.PIEPENHAGEN@DGS.CA.GOV
CONTACT: STEVEN PIEPENHAGEN
ANCHORAGE NOTES:
1. ANCHOR SYSTEMS:
A. EPOXY ANCHORS: COMPLYING WITH ICC ESR-2508, OR ICC ESR-3187, OR ICC ESR-3298.
B. MECHANICAL ANCHORS: COMPLYING WITH ICC ESR-4266, OR ICC ESR-2502
2. INSTALLATION: SEE MANUFACTURER'S WRITTEN INSTRUCTIONS AND REFERENCED ICC ES
REPORT.
A. MATERIALS NOT TO BE PENETRATED BY FASTENERS OR ANCHORS: POST-TENSIONED
CONCRETE AND PRECAST CONCRETE, PRESTRESSED CONCRETE UNLESS SPECIFICALLY
DETAILED HEREIN OR AS ACCEPTED IN WRITING BY ARCHITECT (STRUCTURAL ENGINEER).
WHEN INSTALLATION IS PERMITTED, LOCATE PRESTRESSING AND POST-TENSIONED
TENDONS ACCURATELY PRIOR TO INSTALLATION.
B. DRILLING HOLES IN EXISTING CONCRETE FOR ANCHORS: USE NON-PNEUMATIC, ROTARY
HAMMER TOOLS WITH ANSI COMPLIANT NON-REBAR CUTTING DRILL BITS TO DRILL HOLES
TO PROPER TOLERANCE. LOCATE EXISTING REBAR INCLUDING PRESTRESSING AND
POST-TENSIONING TENDONS USING NON-HAZARDOUS, NON-DESTRUCTIVE METHODS
WITH ACCURATE LOCATION TOLERANCES (PLUS OR MINUS ONE INCH PRIOR TO DRILLING
HOLES TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING OR
PRESTRESSING/POST-TENSIONING TENDONS. HOLES SHALL BE THOROUGHLY CLEANED
PER THE MANUFACTURERS WRITTEN RECOMMENDATIONS PRIOR TO INSTALLATION OF
ANCHORS.
C. DELETERIOUS MATERIALS: KEEP ANCHORS, INCLUDING HOLES FOR DRILL AND EPOXY
ANCHORS AND MECHANICAL ANCHORS FREE OF DUST, GREASE, AND OTHER MATERIALS
THAT IMPAIR CHEMICAL AND MECHANICAL BOND.
3. TESTING FOR EXPANSION ANCHORS:
A. SPECIAL INSPECTION: SPECIAL INSPECTOR WILL PERFORM CONTINUOUS SPECIAL
INSPECTION DURING INSTALLATION.
B. TEST QUANTITY: INSPECTOR SHALL TEST 50% OF ANCHORS USED FOR
EQUIPMENT/NON-STRUCTURAL COMPONENT ANCHORAGE.
C. TEST LOADS FOR:
A. 3/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 3/8" EXPANSION ANCHOR: 25 FT-LBS
B. 1/2"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 1/2" EXPANSION ANCHOR: 40 FT-LBS
C. 5/8"Ø (ICC ESR-4266) OR (ICC ESR-2502)
· TORQUE TEST FOR 5/8" EXPANSION ANCHOR: 60 FT-LBS
D. HIGH-STRENGTH EPOXY ADHESIVE COMPLYING WITH ICC ESR-2508, ICC ESR-3298 OR
ICC ESR-3187
D. TESTING METHOD:
A. HYDRAULIC RAM METHOD: THE ANCHORS SHALL BE TESTED BY DIRECT PULL WITH A
HYDRAULIC JACK. DURING THE TEST, THE ANCHORS SHALL HAVE NO OBSERVABLE
MOVEMENT.
B. TORQUE WRENCH METHOD: THE ANCHORS SHALL BE TESTED BY THE USE OF A
CALIBRATED WRENCH. THE APPLICABLE TEST LOAD SHALL BE REACHED WITHIN
ONE-HALF TURN OF THE NUT.
E. FAILED ANCHORS: IF ANY ANCHOR(S) FAIL IN TESTING, TESTING OF REMAINING ANCHORS
OF THE SAME SIZE AND CATEGORY NOT PREVIOUSLY TESTED SHALL BE COMPLETED.
4. POST-INSTALLED ANCHORAGE: CONTRACTOR SHALL INSTALL ANCHORAGE AT ALL LOCATIONS
ILLUSTRATED IN THE CONSTRUCTION DOCUMENTS. POST-INSTALLED ANCHORS SHALL
CONFORM TO CBC REQUIREMENTS, AND BE INSPECTED BY A SPECIAL INSPECTOR.
CONCRETE NOTES:
1. CONCRETE COMPRESSIVE STRENGTH: ALL CONCRETE SHALL ATTAIN A MINIMUM
COMPRESSIVE STRENGTH AS SHOWN IN THE CONCRETE STRENGTH TABLE BELOW AT 28
DAYS, U.N.O. ON PLANS. SEE ALSO SULFATE CONTENT NOTES
2. AGGREGATES IN CONCRETE: SHALL BE NATURAL SAND AND ROCK (150 LB/CU. FT)
CONFORMING TO ASTM C33. AGGREGATE SHALL HAVE PROVEN SHRINKAGE
CHARACTERISTICS OF LESS THAN 0.04% PER ASTM C157. DO NOT CHANGE SOURCE OF
AGGREGATE DURING COURSE OF WORK WITHOUT WRITTEN CONSENT OF ENGINEER.
3. CEMENT: SHALL BE PORTLAND CEMENT CONFORMING TO ASTM C150. CEMENT SHALL BE
TYPE II OR AS REQUIRED TO SATISFY SITE SOIL CONDITIONS. REFER TO TABLE 4 OF ASTM
C150 FOR CONCRETE CEMENT REQUIREMENTS ON SOIL CONTAINING SULFATE. REFER TO
THE CONCRETE STRENGTH TABLE FOR MAXIMUM WATER TO CEMENT RATIO. USE A MINIMUM
OF (6) SACK OF CEMENT FOR EACH CUBIC YARD OF CONCRETE.
CONCRETE STRENGTH
CONDITION
MIN 28-DAY
COMPRESSIVE
STRENGTH,
F'C
CONCRETE
TYPE*
MAXIMUM
AGGREGATE
SIZE
WATER TO
CEMENT
RATIO
MAX
SLUMP**
SLAB ON
GRADE/
CONC PADS
4,000 PSI
NORMAL-WEIGHT
CONCRETE
(NWC)
3/4" 0.50 4"
* MAXIMUM DRY WEIGHT OF LIGHTWEIGHT CONCRETE SHALL BE 115 PCF.
** SLUMP SHALL BE MEASURED PRIOR TO THE ADDITION OF SUPERPLASTICIZER (IF USED.)
REBAR CLEAR COVER IN CONCRETE: THE FOLLOWING MINIMUM CLEAR DISTANCES BETWEEN
REINFORCING STEEL AND FACE OF CONCRETE SHALL BE MAINTAINED UNLESS NOTED OTHER
WISE:
REBAR CLEAR COVER FOR CAST-IN-PLACE CONCRETE
CONDITION COVER
SLAB ON GRADE CENTER OF SLAB OR 2" MIN
4. VIBRATION: VIBRATION OF CONCRETE SHALL BE IN ACCORDANCE WITH GENERAL
PROVISIONS OUTLINED IN PORTLAND CEMENT ASSOCIATION SPECIFICATION ST26.
5. CURING: CONCRETE SHALL BE MAINTAINED AT IN A MOIST CONDITION FOR A MINIMUM OF
FIVE DAYS AFTER IS PLACEMENT. FOR CONCRETE OTHER THAN SLAB ON GRADE, APPROVED
CURING COMPOUNDS MAY BE USED IN LIEU OF MOIST CURING. ONLY IF APPROVED BY THE
ENGINEER OR ARCHITECT.
6. INSPECTIONS, TESTING & QUALITY ASSURANCE: REFER TO SHEET SN1 FOR DEPUTY SPECIAL
INSPECTION, TESTING & STRUCTURAL OBSERVATION REQUIREMENT. A MINIMUM OF ONE
COMPRESSION TEST AT 7 DAYS AND 2 TESTS AT 28 DAYS FOR ALL CONCRETE SAMPLES.
TAKE TEST AT A FREQUENCY OF ONCE EVERY 150 CU. YDS OR 5,000 SQ. FT MINIMUM.
7. DOWELS, INSERTS: SHALL BE TIED IN PLACE PRIOR TO POURING CONCRETE.
8. ANCHOR BOLTS: SHALL BE WEDGE ANCHORS.
9. CONSTRUCTION AND POUR JOINTS: LOCATIONS SHALL BE APPROVED BY ENGINEER PRIOR
TO POURING CONCRETE.
10. FORMWORK: FORMWORK TOLERANCE SHALL BE IN ACCORDANCE WITH THE C.B.C. AND A.C.I
STANDARDS.
11. PIPES IN CONCRETE: PIPES MAY PASS THROUGH STRUCTURAL CONCRETE IN SLEEVES, BUT
SHALL NOT BE EMBEDDED THEREIN. PIPES OR DUCTS EXCEEDING ONE-THIRD THE SLAB OR
WALL THICKNESS SHALL NOT BE PLACED IN THE STRUCTURAL CONCRETE UNLESS
SPECIFICALLY DETAILED.
12. EXPOSED CORNERS: PROVIDE 3/4" CHAMFERS AT ALL EXPOSED CORNERS.
13. DRYPACK OR GROUT: SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI AND BE
COMPOSED OF ONE PART PORTLAND CEMENT TO NOT MORE THAN THREE PARTS SAND.
14. FLY ASH: NOT PERMITTED.
NOTE:
1. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE
WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE
AUTHORITIES HAVING JURISDICTION (AHJ) AND THEIR LATEST ADOPTED EDITIONS (IN
EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING
PUBLICATIONS:
-CALIFORNIA CODE OF REGULATIONS TITLE 24:
· 2022 CALIFORNIA ELECTRICAL CODE (CEC)
· 2022 CALIFORNIA FIRE CODE (CFC)
· 2022 CALIFORNIA BUILDING CODE (CBC)
· 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)
· 2022 CALIFORNIA REFERENCED STANDARDS CODE (CRSC)
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
· AMERICANS WITH DISABILITIES ACT (ADA)
· TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
· APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE
2. PRIOR TO MAKING REVISIONS TO THE EXISTING PHASE SERVICE, VERIFY EXISTING
SEQUENCE OF THE CIRCUITS AND MAKE CERTAIN THAT EVERY ITEM IS THOROUGHLY
PREPARED. PRIOR TO SCHEDULED OUTAGES MAKE CERTAIN THAT EVERY ITEM IS
THOROUGHLY PREPARED, THAT ALL REQUIRED MATERIALS ARE ON-SITE 7 DAYS PRIOR
TO THE SCHEDULED OUTAGE, THAT SPARE MATERIALS ARE AVAILABLE IN THE EVENT
OF DAMAGE OR DEFECTS, AND THAT THE REQUIRED PERSONNEL ARE AVAILABLE TO
COMPLETE THE WORK DURING THE SCHEDULED OUTAGE. DO THE ACTUAL WORK AT AN
OFF-PEAK TIME, OR OVERTIME, AS ARRANGED WITH THE STATE'S PROJECT DIRECTOR
OR AS HEREINAFTER SPECIFIED. ONCE THE WORK IS STARTED, VIGOROUSLY
PROSECUTE IT TO COMPLETION TO KEEP DOWNTIME TO A MINIMUM. ENSURE THAT
EXISTING ELECTRICAL PHASE SEQUENCE (ELECTRICAL PHASE ROTATION) OF THE
SYSTEM IS MAINTAINED. BE PREPARED TO TEMPORARILY SERVE THE EXISTING SERVICE
OR DISCONTINUE THE NECESSARY REVISIONS IN THE EVENT OF AN EMERGENCY OR
OTHER CONDITION WHICH MAKES IT IMPOSSIBLE TO FINISH THE SCHEDULED WORK ON
TIME.
3. NAMEPLATES:
A. PROVIDE NAMEPLATES ON EQUIPMENT, DEVICES, PANELS AND FIELD MOUNTED
INSTRUMENTS (PRESSURE SWITCHES, LIMIT SWITCHES, ETC.) TO IDENTIFY EACH ITEM
WITH ITS RESPECTIVE SERVICE OR FUNCTION. USE BLACK-ON-WHITE LAMINATED
PLASTIC (WHITE LETTERING ON BLACK BACKGROUND), WITH BEVELED EDGES AND
ENGRAVED LETTERING NOT LESS THAN 1/4 INCH HIGH UNLESS OTHERWISE NOTED.
ATTACH WITH 1/4-INCH-LONG NO. 4 PHILLIPS, ROUND HEAD, COARSE THREAD, TYPE
410 STAINLESS STEEL, THREAD-CUTTING SCREWS WITH BLUNT POINT UNLESS
OTHERWISE SPECIFIED. FOR EXTERIOR NAMEPLATES, PROVIDE SILICON SEAL FOR
SCREW PENETRATIONS. FOR CAST IRON ENCLOSURES MOUNT NAMEPLATES WITH
SETON TUFF-BOND #TB2 ADHESIVE.
B. PROVIDE NAMEPLATES FOR INTERNAL DEVICES OF EQUIPMENT (CONTROL RELAYS,
CONTACTORS, TIMERS, TERMINAL BLOCKS, ETC.). MOUNT NAMEPLATES ADJACENT
TO, NOT ON, THE DEVICE.
C. PROVIDE SINGLE, DEDICATED NAMEPLATES FOR DEVICES MOUNTED WITHIN AND ON
EQUIPMENT. PROVIDE AS A MINIMUM A SINGLE DEDICATED NAMEPLATE FOR EACH
DEVICE (RELAY, SWITCH, TERMINAL BLOCK, METER, ETC.). NAMEPLATE SHALL AGREE
WITH IDENTIFICATION ON MANUFACTURER'S DRAWING. ON DEVICES MOUNTED IN
FRONT COMPARTMENT DOORS, PROVIDE EACH DEVICE WITH TWO NAMEPLATES, ONE
ON THE FRONT AND ONE ON THE BACK OF THE FRONT COMPARTMENT DOOR. THE
NAMEPLATES MOUNTED ON THE BACK OF THE DOOR SHALL BE STICK-ON TYPE.
4. FINAL TERMINATION:
A. CONTRACTOR TO PROVIDE FEEDERS COILED IN NEAREST PULL BOX OR JUNCTION
BOX FOR FINAL TERMINATION.
FIRE SAFETY NOTES:
1. FIRE DEPARTMENT ACCESS ROAD SHALL BE MAINTAINED AT ALL TIMES, AND SHALL BE
PROVIDED TO BE WITHIN 100 FEET OF TEMPORARY FIRE DEPARTMENT CONNECTIONS.
(2022 CFC SECTION 3310)
2. FIRE SAFETY DURING DEMOLITION AND CONSTRUCTION SHALL COMPLY WITH CBC
CHAPTER 33 AND CFC CHAPTER 33.
GENERAL CONTRACT NOTES:
1. CONTRACTOR SHALL PROVIDE ALL MATERIALS SUCH AS TOOLS, EQUIPMENT, LABOR, AND
INCIDENTALS REQUIRED INCLUDING THE CONSTRUCTION OF ALL PROPOSED IMPROVEMENTS
SHOWN ON THE PLANS AND AS SPECIFIED BY THE GOVERNING STANDARDS AND/OR THE
CIVIL AND ELECTRICAL ENGINEERS.
2. CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL EXISTING UTILITIES PRIOR TO
CONSTRUCTION OF THE PROPOSED IMPROVEMENTS.
3. IF DAMAGED DURING CONSTRUCTION, THE CONTRACTOR SHALL REPLACE IN KIND ALL
EXISTING STRUCTURES, WALKWAYS, CURB & GUTTER, LANDSCAPING, AND/OR OTHER
IMPROVEMENTS TO AN EXISTING OR BETTER CONDITION.
4. CONTRACTOR SHALL REPLACE ALL EXISTING STRIPING, SIGNAGE AND MARKINGS DAMAGED
DUE TO PROJECT CONSTRUCTION ACTIVITIES. CONTRACTOR TO REMOVE EXISTING
STRIPING BEFORE PLACING PROPOSED STRIPING PATTERNS.
5. ALL WORK SHALL BE CONFINED WITHIN THE EASEMENTS AND/OR CONSTRUCTION LIMITS AS
SHOWN ON THE PLANS.
6. APPROVAL OF THESE PLANS BY THE AUTHORITIES HAVING JURISDICTION DOES NOT
AUTHORIZE ANY WORK TO BE PERFORMED UNTIL A PERMIT OR NOTICE TO PROCEED HAS
BEEN ISSUED.
7. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL NOTIFY ALL UTILITY AUTHORITIES
OR UTILITY COMPANIES HAVING POSSIBLE INTEREST IN THE WORK OF THE CONTRACTOR'S
INTENTION TO EXCAVATE PROXIMATE TO EXISTING FACILITIES AND THE CONTRACTOR SHALL
VERIFY THE LOCATION OF ANY UTILITIES IN THE WORK AREA. THE CONTRACTOR SHALL
NOTIFY UNDERGROUND SERVICE ALERT (U.S.A.) TWO (2) DAYS PRIOR TO BEGINNING ANY
EXCAVATION.
8. THE CONTRACTOR SHALL OBTAIN WRITTEN AUTHORIZATION FROM ANY PROPERTY OWNER
GIVING HIM PERMISSION TO ENTER HIS PROPERTY FOR THE PURPOSE OF CONSTRUCTING
THE IMPROVEMENTS DELINEATED ON THE PLANS AND TRANSITION THERETO.
9. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL BE PROVIDED AS SPECIFIED WITHIN THIS
SET OR APPROVED EQUAL. ALL BILL OF MATERIALS AND/OR EQUIPMENT SHALL MATCH THE
SAME QUALITY AND CAPACITY AS INDICATED HEREIN.
10. CONTRACTOR MUST IMMEDIATELY NOTIFY THE ENGINEER OF RECORD, IDENTIFIED BY THE
PROFESSIONAL ENGINEERING SEAL AND SIGNATURE ON THESE PLANS, OF ANY SITE
CONDITION(S) AND/OR DESIGN INFORMATION THAT PREVENTS THE CONTRACTOR FROM
COMPLYING WITH THE LAWS, REGULATIONS AND/OR BUILDING CODES.
11. ALL CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH DGS STANDARD
CONSTRUCTION SPECIFICATIONS.
12. CHARGING STATIONS SHALL BE PROVIDED BY THE STATE (DEPARTMENT OF GENERAL
SERVICES) AND INSTALLED BY THE CURRENT STATE ELECTRIC VEHICLE CHARGING STATION
VENDOR. ALL FINAL TERMINATIONS AND SPLICING SHALL BE COMPLETED BY THE STATE
VENDOR.
DESIGN CRITERIA:
CALIFORNIA ADMINISTRATIVE CODE (CAC) 2022
CALIFORNIA BUILDING CODE (CBC) 2022
CALIFORNIA ELECTRICAL CODE (CEC) 2022
CALIFORNIA FIRE CODE (CFC) 2022
CALIFORNIA REFERENCED STANDARDS CODE (CRSC) 2022
TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
2020 NATIONAL ELECTRICAL CODE
ARC-FLASH NOTE:
1. ALL NEW ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANELBOARDS SHALL BE
PROVIDED WITH AN ARC-FLASH HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL
CONTRACTOR, IN COMPLIANCE TO THE THE REQUIREMENTS OF THE LATEST CEC 110.16. AN
ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE LATEST NFPA 70E - 130.5,
SHALL BE PERFORMED BY THE ELECTRICAL CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY SHALL BE PERFORMED BY THE ELECTRICAL
CONTRACTOR AND ADHERE TO NFPA 70E-130.5.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD WARNING
LABEL/MARKING TEMPLATE/S SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEER OF
RECORD (EEOR) FOR REVIEW AND APPROVAL.
LOCATION MAP
NOT TO SCALE
L O
S T H
IL
L S R
D
PROPOSED EV CHARGER TABULATION
EV CHARGER NO. OF EVCS(S) NO. OF FLEET PORT(S)
SINGLE (LEVEL 3) 1 1
DUAL (LEVEL 3) 1 2
TOTAL TOTAL EVCS(S) = 2 TOTAL PORT(S) = 3
THE EVCS FOR THIS PROJECT ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR THE USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2
EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH SECTION 11B-228.3.2. THE
EVCS FIR THIS PROJECT ARE NOT DESIGNED TO COMPLY WITH 11B-228.3.2 ACCESS
REQUIREMENTS.
W FIRESTONE AVE
S A
L P
IN
E A
V E
FLOOD ZONE NOTES:
1. PROJECT SITE LOCATED WITHIN FLOOD HAZARD ZONE X; AREAS DETERMINED TO BE
OUTSIDE THE 0.2% ANNUAL CHANCE FLOODPLAIN.
2. FIRM PANEL: 06019C3250H
3. MAP EFFECTIVE DATE; FEBUARY 18, 2009.
4. MAP IS FRESNO COUNTY, CALIFORNIA; PANEL 3250 OF 3525
DESIGN INFORMATION AND PARAMETERS:
1.
BASIC WIND SPEED (100MPH) AND WIND EXPOSURE CATEGORY C.
2. LATITUDE = 35.135131 , LONGITUDE = -120.246235
3. 5, = 0.55, 5D1 = 0.9G, 5S = 1.93G, 5DS = 1.42 G (SITE CLASS D ASSUMED)
UTILITY NOTE:
UTILITY INFORMATION SHOWN HEREON IS BASED ON OBSERVATION OF VISIBLE EVIDENCE BY
A FIELD SURVEY. THE ENGINEER CAN MAKE NO GUARANTEE AS TO THE ACCURACY OR
COMPLETENESS OF THE UNDERGROUND UTILITY FACILITIES SHOWN. PRIOR TO ANY SITE
EXCAVATIONS, THE CONTRACTOR SHALL CONTACT THE OWNER AND UNDERGROUND
SERVICE ALERT (U.S.A.) AND REQUEST THAT THEY IDENTIFY THE LOCATION OF ALL
UNDERGROUND UTILITIES AT THE SITE. SEE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
CDCR - Electric Vehicle Supply Equipment - Pleasant Valley State Prison PN:000000000013836 / Date: 12/12/25
PROJECT LOCATION:
SEE DEMOLITION PLAN ON SHEET
C2.0, SITE PLAN ON SHEET C3.0,
AND ELECTRICAL CONDUIT PLAN
ON SHEET E1.0
NO PARCEL INFORMATION FOUND
EV
A
EV
A
BOBOBOBO
BO
BO
BOBOBOBOBO
BOBO
BOBO
BO
BOBO
TX
PCS
PCS
CONNECTION POINT FROM
SWITCH GEAR 101039035 TO
PROVIDE POWER TO PROPOSED
EVSE CHARGERS SEE SHEETS
E1.0 AND E3.0
OVERALL SITE MAP
C1.0
0 100 300 600 1200
SCALE IN FEET
SCALE: 1"=600'
Date Signed:
Date Signed:
04-25-2025
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a s a n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n s i0
.d w g C
.0
O v e ra ll S it e M a p B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 00000000001383524863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 03/31/2027
C1.0
W JAYNE AVE
OWNER: SETTON
EQUITIES LLC
APN: 073-060-33S
OWNER: GUTAMI
SOLAR LLC
APN: 073-060-55S
OWNER:
ANDERSON
JAMES S
APN: 073-060-12
OWNER: SUTTER AVENUE
COALINGA CA LP
APN: 085-020-08S
OWNER: STATE OF
CALIFORNIA
APN: 085-020-09ST
OWNER: STATE OF CALIFORNIA
APN: 085-020-12ST
OWNER: STATE OF
CALIFORNIA
APN: 085-020-14ST
OWNER: STATE OF
CALIFORNIA
APN: 085-020-13ST
OWNER: FIRESTONE
AVENUE COALINGA CA LP
APN: 085-020-24S
OWNER: NK DEVELOPMENT
APN: 085-020-21S
OWNER: NBINV AF4 LLC
APN: 085-030-55S
OWNER: NBINV AF4 LLC
APN: 085-030-57S
OWNER: FIRESTONE
AVENUE COALINGA CA LP
APN: 085-320-31S
OWNER:
STATE OF
CALIFORNIA
APN: 085-020-16ST
SYMBOL LEGEND:
EXISTING PROPERTY LINE
AREA OF WORK
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
EXISTING
SWITCHBOARD
"N4-T3DP"
EXISTING
SWITCHBOARD
"E1-T1 DP"
EXISTING CUSTOMER OWNED
TRANSFORMER "N1-T1"
EXISTING CUSTOMER OWNED
ELECTRICAL VAULT "N1-MH3"
EXISTING CUSTOMER OWNED
ELECTRICAL VAULT "N1-MH4"
EXISTING CUSTOMER OWNED
TRANSFORMER "E1-T1"
DEMOLITION PLAN
C2.0
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
Date Signed:
Date Signed:
04-25-2025
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a s a n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n ts
.d w g C
.0
D e m o lit io n P la n B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 00000000001383524863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 03/31/2027
DEMOLITION NOTES:
1. THE "LIMIT OF DEMOLITION" SHOWN IS APPROXIMATE AND IS GENERALLY
CONSIDERED TO BE THE MINIMUM REMOVAL REQUIREMENTS. CONTRACTOR MUST
COORDINATE AS NOTED IN THE LEGEND.
2. CONTRACTOR SHALL LEGALLY DISPOSE OF ALL DEMOLISHED MATERIALS OFF SITE.
3. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITY IMPROVEMENTS NOT
SPECIFICALLY DESIGNATED FOR REMOVAL.
4. THE ON-SITE UNDERGROUND UTILITIES SHOWN ON THIS SHEET ARE AT AN
APPROXIMATE LOCATION. THE EXTENT, LOCATIONS AND SIZES ARE UNKNOWN. THE
CONTRACTOR SHALL POTHOLE TO LOCATE AND VERIFY THE UNDERGROUND UTILITY
LINES PRIOR TO REMOVAL.
5. CONTRACTOR TO PROTECT AND PRESERVE IN PLACE ANY FOUND SURVEY
MONUMENTS. ANY MONUMENTS DISTURBED SHALL BE RESET BY A LICENSED
SURVEYOR AND THE APPROPRIATE PAPERWORK FILED WITH THE CITY OR COUNTY.
6. ALL HAZARDOUS MATERIALS ENCOUNTERED DURING SITE DEMOLITION SHALL BE
REMEDIATED AND DISPOSED OF PER STATE AND EPA REQUIREMENTS.
7. CONTRACTOR SHALL CONTACT AND COORDINATE WITH ALL UTILITY AGENCIES PRIOR
TO THE START OF ANY DEMOLITION OR CONSTRUCTION.
8. ANY EXISTING UTILITIES AND/OR IMPROVEMENTS THAT BECOME DAMAGED DURING
CONSTRUCTION SHALL BE COMPLETELY RESTORED TO THE SATISFACTION OF THE
OWNER AND AGENCY HAVING AUTHORITY, AT THE CONTRACTOR'S SOLE EXPENSE.
DEMOLITION LEGEND:
PROTECT EXISTING ASPHALT CONCRETE
PAVEMENT TO REMAIN
PROTECT EXISTING BUILDING TO REMAIN
PROTECT EXISTING UTILITY TO REMAIN
REMOVE AND LAWFULLY DISPOSE OF LANDSCAPE:
340 S.F.
REMOVE EXISTING IMPROVEMENTS AS NECESSARY
TO CONSTRUCT NEW IMPROVEMENTS SHOWN ON
THESE PLANS UNLESS OTHERWISE NOTED ON THE
PLAN. THE REMOVAL OF IMPROVEMENTS MUST BE
COORDINATED WITH ALL PLAN SHEETS.
CONTRACTOR MUST ALSO COORDINATE REMOVAL
OF IMPROVEMENTS WITH UTILITY AGENCIES.
PROTECT ALL IMPROVEMENTS NOT DESIGNATED
FOR REMOVAL. SEE NOTE 1
EXISTING ASPHALT CONCRETE PAVEMENT
EXISTING SYMBOL LEGEND:
ELECTRICAL METER
ELECTRICAL TRANSFORMER
ELECTRICAL VAULT
EXISTING ASPHALT CONCRETE PAVEMENT
EXISTING BUILDING
EXISTING ELECTRICAL LINE
JOINT TRENCH LINE
E
ET
EVA
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
BOBOBOBO
BO
BO
BOBOBOBOBO
BOBO
BOBO
BO
BOBO
EVA
EVA
A C
B
E
TX
CLE
AR
S
PA
CE
REQUIR
ED
CLE
AR
S
PAC
E R
EQ
UIR
ED
C
LE
A R S
P A C E R
E Q U
IR
E D
C L E A R S
P A C E R
E Q U
IR
E D
FR
ONT
BA
CK
REM
OVA
BL
E
REM
OVAB
LE
REM
F
IX
E D
FI
X E D
F
IX
E D
F
IX
E D
F
IX
E D
F
IX
E D
FI
XE
FIX
FIX
ED
PCS
PCS
12'
1 2 3
14' -7"
2'
33'
4'-6"
36'
4'- 6"
'-6
4'-6
F
2'
8'
2'- 8"
4'-3"
24'-2"
3'-8"
29'-4"
7'
SITE & GRADING PLAN
C3.0
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
Date Signed:
Date Signed:
04-25-2025
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a s a n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n s i0
.d w g C
.0
S it e
G ra d in g P la n B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 00000000001383524863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 03/31/2027
CONSTRUCTION LEGEND:
2' WIDE ELECTRICAL UTILITY TRENCH. TRENCH,
BACKFILL AND RESURFACING PER DETAIL [D/E2.0]
FURNISH AND INSTALL FIXED BOLLARDS PER
DETAIL [A/C4.0]
SEE ELECTRICAL CONDUIT PLAN FOR ADDITIONAL
ELECTRICAL IMPROVEMENTS
FURNISH AND INSTALL FIXED FLEET CHARGING
SIGN PER DETAIL [B/C4.0]
CONSTRUCT EQUIPMENT PAD PER DETAIL [C/C4.0]
PROPOSED KEMPOWER POWER CABINET (MODEL
C500). SEE DETAIL [A/R1.1]
PROPOSED KEMPOWER [MODEL C500] SINGLE
CHARGE PORT STYLE CHARGERS TO BE INSTALLED
BY OTHERS. SEE DETAIL [A/R1.0] (SHOWN FOR
REFERENCE ONLY)
PROPOSED KEMPOWER [MODEL STUU5ESL] DUAL
CHARGE PORT STYLE CHARGERS TO BE
INSTALLED. SEE DETAIL [X/Y]
LINEWORK SHOWN FOR REFERENCE ONLY AND
NOT TO BE STRIPED DUE TO STALLS BEING PLACED
IN DIRT.
LIMITS OF CONCRETE IMPROVEMENTS
A
B
C
E
F
PCS
PROPOSED EV CHARGER
EVCS-#
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
POWER SELECT
(FLA)
POWER SHARE
(Y/NA)
CHARGE PORT
TYPE
1 PEDESTAL SINGLE 227 N/A FLEET
2 PEDESTAL DUAL 227 Y FLEET
2 3
NOTES:
- (FLA) STANDS FOR, FULL LOAD AMPS
- (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
FINISH GRADE
2-1/2"Ø DIA. GALVANIZED
STEEL PIPE
REFLECTORIZED SIGN WITH
GREEN TEXT AND BORDER
ON WHITE BACKGROUND
FASTENER: 1/4" DIA. HEX. BOLT W/
LOCK WASHER 1-1/2" FROM TOP
AND BOTTOM OF SIGN
CONCRETE
12"
(M
IN
M
IN
A B O
V E
G R
A D E
IF
I N
A C
IR
C U
L A T
IO
N
P A T H
M
IN
8"
1/2" MINIMUM RADIUSED
CORNERS (TYP)
DETAILS
C4.0
Date Signed:
Date Signed:
04-25-2025
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a sa n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n d t0
.d w g C
.0
D e ta ils B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 00000000001383524863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 03/31/2027
A
C4.0
CDCR STANDARD - FIXED BOLLARD
NOT TO SCALE
B
C4.0
CDCR STANDARD -
EVCS FLEET SIGNAGE
NOT TO SCALE
EQUIPMENT CONCRETE PAD MINIMUM CONCRETE
COMPRESSIVE STRENGTH OF 4,000 PSI REQUIRED
3" CLR.
(TYP)
3" CLR.
(TYP)
C
L R
(M
IN
8'
COMPACT 12" OF NATIVE SOIL MATERIAL TO MINIMUM
95% RELATIVE COMPACTION PER ASTM D1557
SECTION A-A
#4 @ 12" O.C.
BOTH WAYS
3" CLR.
(TYP)
8'
PLAN VIEW
A A
8'
EQUIPMENT CONCRETE PAD MINIMUM CONCRETE
COMPRESSIVE STRENGTH OF 4,000 PSI REQUIRED
3" CLR.
(TYP)
C
L R
(T Y P
(T Y P
C
L R
(T
Y P
1'
(TYP)
#4 @ 12" O.C.
BOTH WAYS
C
C4.0
EQUIPMENT PAD
NOT TO SCALE
1'-6"
MIN. DIA.
FILL PIPE WITH CONCRETE
AND ROUND OFF TOP WITH
GROUT CAP
2" ADHESIVE REFLECTIVE
STRIPE ALL AROUND
FIELD PRIME BOLLARDS
WITH 2 COATS OF
ZINC-RICH PRIMER. PAINT
BOLLARDS WITH 2 COATS
OF INDUSTRIAL YELLOW
ENAMEL
6"Ø STD WT GALVANIZED
STEEL PIPE, GRIND
SMOOTH ALL ROUGH
AREAS AND EDGES
1/4" SLOPE
TOP OF FINISH
GRADE OR
SURFACE MATERIAL
FINISH
GRADE
CONCRETE
ENCASEMENT
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
BOBOBOBO
BO
BO
BOBOBOBOBO
BOBO
BOBO
BO
BOBO
EVA
EVA
1 2 3
'-9"
30'-6"
29'-10"
12' -8"
EVA
EVA
TX
CLE
AR
S
PA
CE
REQUIR
ED
CLE
AR
S
PAC
E R
EQ
UIR
ED
C
LE
A R S
P A C E R
E Q U
IR
E D
C L E A R S
P A C E R
E Q U
IR
E D
FR
ONT
BA
CK
REM
OVA
BL
E
REM
REM
LE
F
IX
E
FI
X E D
F
IX
E D
F
IX
E D
F
IX
E D
F
IX
E D
FI
XE
FIX
FIX
ED
PCS
PCS
(K1)
A
(K2)
(K4, C3)
(K3-K4, C2-C3)
B
C
E
(SATELLITE
PEDESTAL #1)
(P1)
(P2)
(C1)
(SATELLITE PEDESTAL #2)
(K4, C3)
F
G
(K3, C2)
H
I
4'
H
(TYP)
(TYP)
(PCS-2)
(PCS-1)
D
J
(TYP)
ELECTRICAL CONDUIT PLAN
E1.0
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a sa n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n e l0
.d w g E .0
E le c tr ic a l C o n d u it P la n B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 000000000013835
Date Signed:
04-25-2025
24863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 06/30/2026
SCALE IN FEET
0 5 10 20
SCALE: 1"=10'
A
E1.0
CONDUIT SCHEDULE
ELECTRICAL LEGEND:
CONSTRUCT SATELLITE CHARGER CONCRETE PAD AND/OR INSTALL CHARGERS PER DETAILS
[E/E2.0] & [F/E2.0]
FURNISH & INSTALL DISTRIBUTION PANEL "N1T1-EV1DP" PER DETAILS [D/E2.0] AND [B/E3.0]
EXISTING N1-MH3 ELECTRICAL VAULT TO REMAIN, CONTRACTOR TO SPLICE INTO THE
EXISTING FEED AREA LOOP 2 AND PULL NEW WIRE TO THE TRANSFORMER "N1-T8"
SEE DETAIL [D/E2.0] FOR THE FURNISHING AND INSTALLATION OF ABOVE GRADE RMC
CONDUIT. SEE CONDUIT SCHEDULE FOR COUNT AND CONDUIT SIZE
SEE DETAIL [B/E2.0] FOR THE FURNISHING AND INSTALLATION OF BELOW GRADE PVC
CONDUIT (1000V & LESS). SEE CONDUIT SCHEDULE FOR COUNT AND CONDUIT SIZE
FURNISH AND INSTALL CUSTOMER OWNED METER ENCLOSURE PER DETAIL [D/E2.0]
CONSTRUCT POWER UNIT CONCRETE PAD AND/OR INSTALL POWER CABINET PER DETAILS
[A/E2.1] AND [B/E2.1]
FURNISH AND INSTALL EMERGENCY SHUT OFF LABEL FOR THE MAIN EQUIPMENT PER DETAIL
[C/E2.0]
FURNISH AND INSTALL EMERGENCY SHUT OFF LABEL FOR EVCS PER DETAIL [A/E2.0]
FURNISH AND INSTALL TRANSFORMER "N1-T8" PER DETAILS [D/E2.1] AND [C/E3.0]
PROPOSED KEMPOWER POWER CABINET (MODEL C500). SEE DETAIL [A/R1.1]
PROPOSED KEMPOWER [MODEL SU5CSL] SINGLE CHARGE PORT STYLE CHARGERS TO BE
INSTALLED BY OTHERS. SEE DETAIL [A/R1.0] (SHOWN FOR REFERENCE ONLY)
PROPOSED KEMPOWER [MODEL SUU5CSL] SATELLITE DUAL CHARGE PORT STYLE CHARGERS
TO BE INSTALLED. SEE DETAIL [A/R1.0]
PROPOSED DISTRIBUTION PANEL
PROPOSED CUSTOMER OWNED METER
PROPOSED CUSTOMER OWNED PADMOUNT TRANSFORMER
3/4" x 10' COPPER CLAD GROUND ROD, ERICO OR APPROVED EQUAL
ELECTRICAL CONDUIT; SIZE AND COUNT AS NOTED
#2/0 BURIED BARE COPPER GROUND WIRE
A
B
C
D
E
F
G
H
I
J
PCS
TX
FRONT
BACK
ELECTRICAL NOTES:
1. ELECTRICAL UTILITY LINE TO BE PROTECTED IN PLACE WHEN POSSIBLE. IF EXISTING LINES
INTRODUCE EXCESSIVE CONSTRAINTS DURING THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT, REMOVE AND RELOCATE EXISTING LINES AS NEEDED, USING THE PROPOSED
UTILITY TRENCH. IF THE ELECTRICAL LINE CANNOT BE SALVAGED THE CONTRACTOR MUST
LAWFULLY DISPOSE OF THE ELECTRICAL LINE AND REPLACE WITH LIKE-IN-KIND.
2. ALL ELECTRICAL POWER IN CLOSE PROXIMITY TO THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT MUST BE POWERED OFF PRIOR TO THE START OF CONSTRUCTION, TO PREVENT
ANY ELECTRICAL INJURIES.
3. HAND DIG ALL UTILITIES IN CLOSE PROXIMITY TO THE INSTALLATION OF THE ELECTRICAL
EQUIPMENT TO AVOID DAMAGING ANY UTILITY LINE.
4. SEE SINGLE LINE DIAGRAM ON SHEET E3.0.
5. SEE CONDUIT SCHEDULE FOR WIRE SIZE, CONDUIT FILL AND WIRE TAGS.
6. THE METHODS CONTAINED IN CEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH
GROUNDING AND BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING
CONDUCTIVE MATERIALS, ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT
THAT ENCLOSES OR CARRIES ELECTRICAL CONDUCTOR OR EQUIPMENT THAT IS LIKELY TO
BECOME ENERGIZED. SEE CEC 250.4(A)(1) THROUGH (5) FOR FURTHER DESCRIPTION.
7. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION
SHALL BE 6' PER CEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
8. MINIMUM CONDUIT BURIAL DEPTH SHALL BE 24".
9. PER CEC 110.26 "ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED
ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND
MAINTENANCE OF SUCH EQUIPMENT."
10. CONDUIT BODIES, PULL BOXES AND JUNCTION BOXES SHALL BE USED AS NEEDED TO
MAINTAIN LESS THAN 360° OF CONDUIT BENDS BETWEEN PULL POINTS.
11. ALL ABOVE GRADE CONDUIT CONSTRUCTION SHALL FOLLOW CEC 342,
344, 350, OR 358 FOR IMC, RMC, LFMC OR EMT CONSTRUCTION.
12. DC CONDUCTORS FROM PCS UNIT TO SATELLITE TO BE RATED FOR 1000V MINIMUM, 90° C, AND XHHW-2. ALL AC CONDUCTORS (ON THE 480V SIDE OF THE TRANSFORMER) TO BE 600V
MINIMUM, 90° C, THWN-2 OR EQUIVALENT.
13. ALL CIRCUIT BREAKERS THAT ARE OR CAN BE RATED 1200 AMPS OR HIGHER TO ABIDE BY
ARC ENERGY REDUCTION PER CEC/NEC 240.87.
14. GROUND FAULT PROTECTION AND PERFORMANCE TESTING OF EQUIPMENT SHALL BE
PROVIDED FOR ALL APPLICABLE SERVICES PER CEC/NEC 230.95.
15. CONTRACTOR TO INSTALL A JUNCTION BOX AND CONDUIT FROM DISTRIBTUION PANEL
"N1T1-EV1DP" IN ORDER TO ALLOW A CUSTOMER OWNED METER, CT WIRING AND AUX
POWER TO SPARE BREAKER.
16. TYPE 65 KAIC BREAKERS FOR DISTRIBUTION PANEL "N1T1-EV1DP".
17. ALL MEDIUM VOLTAGE CONDUCTORS TO BE RATED FOR 12KV (MINIMUM) 133% MV-105. ALL
ELECTRICAL EQUIPMENT OPERATING AT OVER 1000 VOLTS SHALL BE LISTED FOR
TERMINATION OF ELECTRICAL CONDUCTORS RATED FOR 90° C OR HIGHER.
18. ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL
SAFETY HEALTH ADMINISTRATION.
19. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH
GROUNDING AND BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING
CONDUCTIVE MATERIALS, ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT
THAT ENCLOSES OR CARRIES ELECTRICAL CONDUCTOR OR EQUIPMENT THAT
IS LIKELY TO BECOME ENERGIZED. SEE CEC/NEC 250.4(A)(1) THROUGH (5) FOR FURTHER
DESCRIPTION.
20. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION
SHALL BE 6' PER CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
21. ALL ELECTRICAL EQUIPMENT OPERATING AT 480V SHALL BE LISTED FOR TERMINATION OF
ELECTRICAL CONDUCTORS RATED 75°C OR HIGHER.
22. CONTRACTOR TO ENSURE 12kV TRANSFORMER HAS CLEARANCE THAT ABIDES BY CEC/NEC 110.
23. CONTRACTOR TO VERIFY THE EXISTING LOAD DRAWN BY THE EXISTING PG&E SWITCHGEAR
AND VERIFY THAT THE EXISTING SWITCHBOARD WILL HAVE THE CAPACITY TO SUPPORT THE
PROPOSED LOADS.
24. NEUTRAL AND GROUND NOT TO BE JUMPERED IN DISTRIBUTION PANEL "N1T1-EV1DP".
CONDUIT SCHEDULE
CONDUIT
NUMBER
FROM TO
CONDUCTORS ALL 90°C
THWN-2 OR SIMILAR
UNLESS NOTED
OTHERWISE
CONDUIT SIZE
AND TYPE
COMMENTS
P1
EXISTING ELECTRICAL VAULT
"N1-MH3"
NEW TRANSFORMER "N1-T8"
(3) 1/0 Cu AND
(1) #2 Cu GND
(SEE ELECTRICAL NOTE 17)
(2) 6" PVC
(2) 12 kV CONDUIT RUN FROM
VAULT TO TRANSFORMER
P2 NEW TRANSFORMER "N1-T8"
PROPOSED DISTRIBUTION
PANEL "N1T1-EV1DP"
(4) 350 MCM Cu AND
(1) 2/0 Cu GND
(2) 4" PVC
(2) 480V PARALLEL CONDUIT
RUNS FROM TRANSFORMER
TO PANEL
K1
PROPOSED DISTRIBUTION
PANEL "N1T1-EV1DP"
POWER CABINET
(PCS-1)
(3) 350 MCM CU AND
(1) #4 Cu GND
3" RMC/PVC
DISTRIBUTION PANEL TO
POWER UNIT
K2
PROPOSED DISTRIBUTION
PANEL "N1T1-EV1DP"
POWER CABINET
(PCS-2)
(3) 350 MCM CU AND
(1) #4 Cu GND
3" RMC/PVC
DISTRIBUTION PANEL TO
POWER UNIT
K3
POWER CABINET
(PCS-1)
'EVCS'
SATELLITE PEDESTAL #1
(SATELLITE PORT 1)
(2) 250 MCM CU AND,
(1) #3/0 CU GND
(SEE ELECTRICAL NOTE 12)
3" PVC
DC POWER CONDUCTORS FOR
SATELLITE PEDESTAL
K4
POWER CABINET
(PCS-2)
'EVCS'
SATELLITE PEDESTAL #2
(SATELLITE PORTS 2 AND 3)
(2) 250 MCM CU AND,
(1) #3/0 CU GND
(SEE ELECTRICAL NOTE 12)
3" PVC
DC POWER CONDUCTORS FOR
SATELLITE PEDESTAL
C1
PROPOSED DISTRIBUTION
PANEL "N1T1-EV1DP"
PROPOSED CUSTOMER OWNED
METER ENCLOSURE
EMPTY CONDUIT
(PROVIDE PULL TAPE)
1" RMC
EMPTY CONDUIT FROM PANEL
TO METER ENCLOSURE FOR
CONTROLS
C2
POWER CABINET
(PCS-1)
'EVCS'
SATELLITE PEDESTAL #1
(SATELLITE PORT 1)
(1) SUPERCAT 6/7 SHIELDED
ETHERNET,
(5) #14 CU
3/4" PVC
COMMUNICATION AND
CONTROLS FROM POWER UNIT
TO SATELLITE PEDESTAL
C3
POWER CABINET
(PCS-2)
'EVCS'
SATELLITE PEDESTAL #2
(SATELLITE PORTS 2 AND 3)
(1) SUPERCAT 6/7 SHIELDED
ETHERNET,
(6) #14 CU
3/4" PVC
COMMUNICATION AND
CONTROLS FROM POWER UNIT
TO SATELLITE PEDESTAL
PROPOSED EV CHARGER
EVCS-
WALL/PEDESTAL
MOUNT EVCS
SINGLE/
DUAL EVCS
CHARGE
PORT #
POWER
SELECT
(FLA)
POWER
SHARE
(Y/NA)
CHARGE PORT
TYPE
1 PEDESTAL SINGLE 227 N/A FLEET
2 PEDESTAL DUAL 227 Y FLEET
2 3
NOTES:
- (FLA) STANDS FOR, FULL LOAD AMPS
- (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
M
3'-6" 6"
3'-6"2'-7" 6"
(M
IN
8'
(P3)
1'-6"
(TYP)
PLAN VIEW
SECTION A-A
A
B
A
B
(K1-K2)
2'-1" 1' 11"
1'-5"
8'
M
8 9
15 14 13
17 18
BILL OF MATERIALS (DETAIL [D/E2.0])
REFERENCE
NUMBER
ITEM
DISTRIBUTION PANEL, NEMA TYPE 3R, 480Y/277V, 3Ø,
4W, 600 AMP, 65 KAIC FULLY RATED
MAIN BREAKER, 480 VOLT, 600 AMP TRIP 65 KAIC AT
480V, 3 POLE
BRANCH BREAKER, 480 VOLT, 300 AMP TRIP, 65 KAIC
AT 480V, 3 POLE
4 1" RMC CONDUIT
BRANCH BREAKER, 480 VOLT, 15 AMP TRIP, 65 KAIC
AT 480V, 3 POLE
6 4" PVC BELL
7 3" PVC BELL END
8 2/0 CU CONDUCTOR GRN INSULATION THWN-2
9 4" SCH. 40 PVC, 24" RADIUS MINIMUM
10 3" SCH. 40 PVC, 18" RADIUS MINIMUM
11 3" SCH. 40 PVC
12 4" SCH. 40 PVC
13 ANCHOR BOLT 5/8" WITH 4" EMBEDMENT
14 GALVANIZED NUT, 5/8"
15 GALVANIZED LOCK WASHER, 5/8"
16 CUSTOMER SUPPLIED PADLOCK
17 350 MCM CU CONDUCTOR THWN-2
18 #4 CU CONDUCTOR GRN INSULATION THWN-2
CONCRETE MOUNDING TOP SURFACE (CROWN) TO
SHED WATER
4" GALVANIZED SCH. 40 STEEL POST TO BE FILLED
SOLIDLY WITH CONCRETE AND TO FIELD PRIME
BOLLARDS WITH 2 COATS OF ZINC-RICH PRIMER.
PAINT BOLLARDS WITH 2 COATS OF INDUSTRIAL
YELLOW ENAMEL
21 UNISTRUT STRUT
22 SPRING NUT, 3/8"-16
23 SQUARE WASHER FOR 5/8" BOLT
24 5/8" LOCKING HEX NUT
25 5/8" ALL THREAD
26 4" PIPE CLAMP
27 CUSTOMER OWNED METER WITHIN ENCLOSURE
1 2
9"9" 6"
2' CONDUIT WINDOW
5.5" DIAMETER
(SEE NOTE 6)
PLAN VIEW
1'-5" 1'-5"
(M
IN
"6
(M
IN
4'-10"
2'-2"6" 2'-2"
SECTION A-A
S E E N
O T E
NOTES:
1. MATERIAL FOR SERVICE
CONDUIT SHALL BE LISTED AS
ELECTRICAL CONDUIT.
ACCEPTABLE MATERIAL SHALL
BE PVC RIGID CONDUIT AND
WHEN SPECIFIED, IMC OR
RIGID METALLIC CONDUIT
TAPED OR COATED FOR
DIRECT BURIAL.
2. CONDUIT SWEEP SHALL BE
PVC AND HAVE A MINIMUM
RADIUS AS REQUIRED BY
CEC/NEC CHAPTER 9.
3. MINIMUM CONDUIT COVER
REQUIREMENTS SHALL
FOLLOW CEC/NEC 300.5
UNLESS OTHERWISE
SPECIFIED.
4. EXACT CONDUIT SIZE,
DIRECTION, AND QUANTITY
MAY VARY, REFER TO
ELECTRICAL CONDUIT PLAN
AND CONDUIT SCHEDULE.
5. CHARGER SATELLITE
PROVIDED BY SCE TO BE
INSTALLED BY THE
CONTRACTOR.
6. CONTRACTOR TO ENSURE
THE REQUIRED CONDUITS FIT
WITHIN THE CONDUIT WINDOW
DIMENSIONS PROVIDED.
FINISHED GRADE
EATON RIGID METALLIC
THREADED CONDUIT
COUPLER RC75SA
EATON RIGID METALLIC
THREADED CONDUIT
COUPLER RC300SA
3/4" CHAMFER (TYP)
CONCRETE PAD
EATON CONDUIT PLUG
PLG2M AND PLG8M
SCH. 40 PVC CONDUIT SWEEP,
SEE NOTE 2 & 4 (TYP)
SCH. 40 PVC CONDUIT
(AS NEEDED) (TYP)
SCH. 40 PVC THREADED
MALE ADAPTER (TYP)
SCH. 40 PVC COUPLER (TYP)
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT
(AS NEEDED)
2"
2'
A
(4) HILTI KWIK
BOLT TZ2STUD
ANCHOR WITH 3
3/4 INCHES
EMBEDMENT PER
MANUFACTURER'S
SPECIFICATIONS
A
CONDUIT SECTIONS & DETAILS
E2.0
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a sa n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n d t0
.d w g E .0
C o n d u it S e c ti o n s
D e ta ils B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 000000000013835
Date Signed:
04-25-2025
24863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 06/30/2026
EMERGENCY SHUT-OFF
EVCS-#
LOCATED IN/AT
(PANEL __)
5"
/2
1/4"
(T Y P
1/4"
(T Y P
/8
/4
/4
/4
/4
/4
/4
/4
/8
/4
/4
3/8" 4 3/8" 3/8"
SEE NOTES 1, 4 & 6
SEE NOTES 1, 2, 3 & 5. TEXT TO BE PRINTED
IN THE COLOR WHITE NOT BLACK
SEE NOTE 1
NOTES:
1. ELECTRICAL VEHICLE CHARGING
STATION SHUT-OFF LABEL TO HAVE
WHITE LETTERS ON RED FIELD. WITH
RED AND WHITE DIAGONAL STRIPED
BORDER.
2. EMERGENCY SHUT-OFF LABEL SHALL
READ THE EVCS-# THAT IS CORRELATED
WITH ONE ANOTHER. SEE BELOW FOR
EXAMPLE:
EMERGENCY SHUT-OFF
EVCS-1
LOCATED IN/AT
(PANEL EV)
3. FOR EVCS-# AND LABELING, SEE
ELECTRICAL SCHEDULE & CIRCUITS ON
SHEET E3.0.
4. EMERGENCY SHUT-OFF LABEL TO BE
SELF-ADHESIVE: VINYL, THERMAL,
TRANSFER-PRINTED, 5.5-MIL-THICK,
MULTICOLOR, WEATHER AND
UV-RESISTANT, PRESSURE-SENSITIVE
ADHESIVE LABELS, CONFIGURED FOR
INTENDED USE AND LOCATION.
5. THE TEXT HEIGHT SHALL BE 1/4" HIGH
WITH WHITE LETTERING.
6. EMERGENCY -SHUT-OFF LABEL SHALL
COMPLY WITH THE FOLLOWING
SPECIFICATION:
- SECTION 26 05 53, IDENTIFICATION FOR
ELECTRICAL SYSTEMS
7. PLACE EMERGENCY SHUT-OFF LABEL
ON EACH EVCS CHARGER.
A
E2.0
EMERGENCY SHUT-OFF LABEL
NOT TO SCALE
B
E2.0
TYPICAL ELECTRICAL UTILITY TRENCH
(0 - 1000V AND COMMUNICATIONS)
NOT TO SCALE
F
E2.0
KEMPOWER (SATELLITE) STUB, CAP AND CONCRETE PAD
NOT TO SCALE
E
E2.0
KEMPOWER SATELLITE PEDESTAL INSTALLATION
NOT TO SCALE
D
E2.0
DISTRIBUTION PANEL "N1T1-EV1DP" AND PROPOSED CUSTOMER OWNED METER ENCLOSURE
NOT TO SCALE
C
E2.0
EMERGENCY SHUT-OFF LABEL - ELECTRICAL EQUIPMENT
NOT TO SCALE
EMERGENCY SHUT-OFF
PANEL - #
FOR EVCS CHARGERS
# THROUGH #
5"
/2
1/4"
(T Y P
1/4"
(T Y P
/8
/4
/4
/4
/4
/4
/4
/4
/8
/4
/4
3/8" 4 3/8" 3/8"
SEE NOTES 1, 4 & 6
SEE NOTES 1, 2, 3 & 5. TEXT TO BE PRINTED
IN THE COLOR WHITE NOT BLACK
SEE NOTE 1
NOTES:
1. ELECTRICAL VEHICLE CHARGING
STATION SHUT-OFF LABEL TO HAVE
WHITE LETTERS ON RED FIELD. WITH
RED AND WHITE DIAGONAL STRIPED
BORDER.
2. EMERGENCY SHUT-OFF LABEL SHALL
READ THE PANEL-# THAT IS
CORRELATED WITH THE EVCS
CHARGERS. SEE BELOW FOR EXAMPLE:
EMERGENCY SHUT-OFF
PANEL-#
FOR EVCS CHARGERS
# THROUGH #
3. FOR PANEL ____, EVCS - # AND
LABELING, SEE ELECTRICAL SCHEDULE
& CIRCUITS ON SHEET ___.
4. EMERGENCY SHUT-OFF LABEL TO BE
SELF-ADHESIVE: VINYL, THERMAL,
TRANSFER-PRINTED, 5.5-MIL-THICK,
MULTICOLOR, WEATHER AND
UV-RESISTANT, PRESSURE-SENSITIVE
ADHESIVE LABELS, CONFIGURED FOR
INTENDED USE AND LOCATION.
5. THE TEXT HEIGHT SHALL BE 1/4" HIGH
WITH WHITE LETTERING.
6. EMERGENCY -SHUT-OFF LABEL SHALL
COMPLY WITH THE FOLLOWING
SPECIFICATION:
- SECTION 26 05 53, IDENTIFICATION FOR
ELECTRICAL SYSTEMS
7. PLACE EMERGENCY SHUT-OFF LABEL
ON EACH EVCS CHARGER.
(M
IN
(M
IN
2"
VARIES
(SEE PLAN)
7-INCH OF 3/4-INCH MEDIUM, TYPE B ASPHALT CONCRETE
SAWCUT T-SECTION AND MATCH ADJACENT
ASPHALT CONCRETE
METALLIC WARNING TAPE
95% MINIMUM RELATIVE
COMPACTED NATIVE
BACKFILL UNDER CONCRETE
AND ASPHALT AREAS, PER
ASTM D1557. 90% MINIMUM
RELATIVE COMPACTED
NATIVE BACKFILL UNDER
LANDSCAPE AREAS, PER
ASTM D1556 AND ASTM
D1557. SEE NOTE 3 ELECTRICAL CONDUIT,
SEE ELECTRICAL PLANS
FOR SIZE AND COUNT
(TYP). SEE NOTE 3
24" (MAX) DEPTH, AT LEAST 12" ABOVE
CONDUIT (SEE NOTE 1)
EXISTING ELECTRICAL CONDUIT WHERE
APPLICABLE
EXISTING ELECTRICAL
CONDUIT CROSSING
WHERE APPLICABLE
MINIMUM CONDUIT
BURIAL DEPTH
SHALL BE 24".
RESURFACING
IN CONCRETE AREA
RESURFACING
IN ASPHALT AREA
95% MINIMUM
RELATIVE
COMPACTED NATIVE
MATERIAL IN TOP 2'
OF TRENCH
SAWCUT AND
MATCH
ADJACENT
CONCRETE
6"
(MIN)
CALTRANS
CLASS 3
CONCRETE
EXISTING
CONCRETE
6"
EXISTING ASPHALT CONCRETE PAVEMENT
EXISTING
CURB
6"
SEE NOTE 2
NOTES:
1. PER NEC 300.5 (D)(3), UNDERGROUND
SERVICE CONDUCTORS THAT ARE
NOT ENCASED IN CONCRETE AND
THAT ARE BURIED 450MM (18") OR
MORE BELOW GRADE SHALL HAVE
THEIR LOCATION IDENTIFIED BY A
WARNING RIBBON THAT IS PLACED IN
THE TRENCH AT LEAST 300MM (12")
ABOVE THE UNDERGROUND
INSTALLATION.
2. APPLY SLURRY COAT IN A UNIFORM
THICKNESS IN ACCORDANCE WITH
ASTM D3910 AND ALLOW TO CURE
FOR A MINIMUM OF 5 DAYS. ROLL
SLURRY SEAL TO REMOVE RIDGES
AND PROVIDE A UNIFORM, SMOOTH
SURFACE.
3. DIRECT BURIED UTILITY TRENCH
BACKFILL SHALL COMPLY WITH THE
FOLLOWING SPECIFICATIONS:
- SECTION 31 20 00, EARTH MOVING
- SECTION 26 05 43, UNDERGROUND
DUCTS AND RACEWAYS FOR
ELECTRICAL SYSTEMS
- SECTION 32 12 16, ASPHALT PAVING
- SECTION 03 30 00, CAST-IN-PLACE
CONCRETE
3" CLEAN SAND BEDDING
TO BE PLACED BELOW
AND ABOVE CONDUIT
PER ASTM C33/C33M;
FINE AGGREGATE
LANDSCAPE
RESURFACING
IN LANDSCAPE AREA
TRENCH TRENCH TRENCH
ELECTRICAL NOTES:
1. THE METHODS CONTAINED IN CEC/NEC ARTICLE 250 SHALL BE FOLLOWED TO COMPLY WITH GROUNDING
AND BONDING OF ELECTRICAL SYSTEMS AND NON-CURRENT CARRYING CONDUCTIVE MATERIALS,
ENCLOSURES, OR ITEMS FORMING PART OF ANY SUCH EQUIPMENT THAT ENCLOSES OR CARRIES
ELECTRICAL CONDUCTOR OR EQUIPMENT THAT IS LIKELY TO BECOME ENERGIZED. SEE CEC/NEC
250.4(A)(1) THROUGH (5) FOR FURTHER DESCRIPTION.
2. WHERE TWO OR MORE GROUND RODS ARE TO BE INSTALLED, THE MINIMUM SEPARATION SHALL BE 6' PER
CEC/NEC 250.53 (A)(2), AND (3) RESISTANCE OF ELECTRODES.
3. MINIMUM CONDUIT BURIAL DEPTH SHALL BE 24".
4. PER CEC/NEC 110.26 "ACCESS AND WORKING SPACE SHALL BE PROVIDED AND MAINTAINED ABOUT ALL
ELECTRICAL EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF SUCH
EQUIPMENT."
5. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED FOR TERMINATION OF ELECTRICAL CONDUCTORS RATED
75°C OR HIGHER.
6. ALL ABOVE GRADE CONDUIT CONSTRUCTION SHALL FOLLOW CEC/NEC 342, 344, 350, OR 358 FOR IMC, RMC, LFMC OR EMT CONSTRUCTION.
7. CONTRACTOR TO ENSURE 12kV TRANSFORMER HAS CLEARANCE THAT ABIDES BY CEC-NEC 110.
8. ALL CIRCUIT BREAKERS THAT ARE OR CAN BE RATED 1200 AMPS OR HIGHER TO ABIDE BY ARC ENERGY
REDUCTION PER CEC/NEC 240.87.
9. GROUND FAULT PROTECTION AND PERFORMANCE TESTING OF EQUIPMENT SHALL BE PROVIDED FOR ALL
APPLICABLE SERVICES PER CEC/NEC 230.95.
10. DC CONDUCTOR FROM PCS UNIT TO SATELLITE TO BE RATED FOR 1000V MINIMUM, 90° C, AND XHHW-2. ALL AC CONDUCTORS (ON THE 480V SIDE OF THE TRANSFORMER) TO BE 600V MINIMUM, 90°, THWN-2 OR
EQUIVALENT.
11. ALL MEDIUM VOLTAGE CONDUCTORS TO BE RATED FOR 12kV (MINIMUM) 133% MV-105. ALL ELECTRICAL EQUIPMENT OPERATING AT OVER 1000 VOLTS SHALL BE LISTED FOR TERMINATION OF ELECTRICAL
CONDUCTORS RATED FOR 90° C OR HIGHER.
KEMPOWER SATELLITE
OR APPROVED EQUAL
FINISH GRADE
(SEE NOTES 1 & 2)
CONDUIT FLUSH WITH CONCRETE
SURFACE. PROTECT CONDUCTORS
TO REMAIN.
NOTES:
1. EXACT CONDUIT SIZE, DIRECTION AND
QUANTITY MAY VARY, REFER TO ELECTRICAL
CONDUIT PLAN AND CONDUIT SCHEDULE.
2. CONTRACTOR TO REFER TO INSTALLATION
MANUAL FOR CONDUIT ENTRY, SEPARATION
AND PLACEMENT.
3. REQUIRED SATELLITE TO INSTALL MAY BE
SINGLE OR DUAL. CONTRACTOR TO REFER TO
ELECTRICAL CONDUIT PLAN AND SINGLE LINE
DIAGRAM.
C L E A R
S P A C
E
C L E A R
S P A C
E
(SEE NOTE 3)
3/4" CHAMFER
PROPOSED STUB, CAP
AND CONCRETE PAD
PER DETAIL [F/E2.0]
1'
(4) HILTI KWIK BOLT
TZ2STUD ANCHOR WITH 3
3/4 INCHES EMBEDMENT
PER MANUFACTURER'S
SPECIFICATIONS
2"
2'
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
5'-8"
3" CLR.
(TYP)
C L R
(T
Y P
TRANSFORMER CONCRETE
PAD MINIMUM
COMPREHENSIVE STRENGTH
OF 4,000 PSI REQUIRED
500 KVA, 12KVA-480/277V, Δ ,
65°C, INTERNAL FUSED
PRIMARY LOOP SWITCHES,
LOAD BREAK TERMINATIONS
90"x106"
TRANSFORMER PAD
(1) 5/8"x8' GND
ROD,
COPPERCLAD
(1) CLAMP
APPROX. OUTLINE OF 500kVA
TRANSFORMER. CONTRACTOR
TO CONFIRM FINALIZED LAYOUT
#2/0 BARE COPPER GND
COMPACT 12" OF NATIVE
SOIL MATERIAL TO MINIMUM
95% RELATIVE COMPACTION
PER ASTM D1557
#4 @ 12" O.C. BOTH WAYS
PLAN VIEW SECTION A-A
CONDUIT SECTIONS & DETAILS
E2.1
SHEETSOF
SHEET NO.
SCALE AS NOTED
DATE:
CH. BY:
DR. BY:
REF. & REV.
CONSULTANT
PROJECT LOCATION:
CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION
04-25-2025 12
RF
WH
ELECTRIC VEHICLE CHARGING STATION INFRASTRUCTURE
PLEASANT VALLEY STATE PRISON
CALIFORNIA DEPARTMENT OF GENERAL SERVICES
D ra w in g P -0
\S it e \c d c r P le a sa n t V a lle y S ta te
P ri s o n \c o n s tr u c ti o n D o c u m e n t\ p ro d u c ti o n d ra w in g s \2
P le a s a n t V a lle y S ta te
P ri s o n d t0
.d w g E .1
C o n d u it S e c ti o n s
D e ta ils B
C F .c tb P lo t b y w h a rr is
A p r
:3 p m
PRELIMINARY QC_01
PROJECT #: 000000000013835
Date Signed:
04-25-2025
24863 WEST JAYNE AVENUE, COALINGA, CA 93210
V1
EXP 06/30/2026
(M
IN
1 2
1 2
FINISH GRADE
SCH. 40 PVC COUPLER
SCH. 40 PVC CONDUIT
(AS NEEDED)
SCH. 40 PVC CONDUIT SWEEP,
SEE NOTE 2 & 4 (TYP)
SECTION A-A
NOTES:
1. MATERIAL FOR SERVICE CONDUIT SHALL BE LISTED AS
ELECTRICAL CONDUIT. ACCEPTABLE MATERIAL SHALL BE
PVC RIGID CONDUIT AND WHEN SPECIFIED, IMC OR RIGID
METALLIC CONDUIT TAPED OR COATED FOR DIRECT
BURIAL.
2. CONDUIT SWEEP SHALL BE PVC AND HAVE A MINIMUM
RADIUS AS REQUIRED BY CEC/NEC CHAPTER 9.
3. MINIMUM CONDUIT COVER REQUIREMENTS SHALL
FOLLOW CEC/NEC 300.5 UNLESS OTHERWISE SPECIFIED.
4. EXACT CONDUIT SIZE, DIRECTION, AND QUANTITY MAY
VARY, REFER TO ELECTRICAL CONDUIT PLAN AND
CONDUIT SCHEDULE.
5. CHARGER POWER CABINET PROVIDED BY SCE TO BE
INSTALLED BY THE CONTRACTOR.
6. CONTRACTOR TO ENSURE THE REQUIRED CONDUITS FIT
WITHIN THE CONDUIT WINDOW DIMENSIONS PROVIDED.
SCH. 40 PVC CONDUIT
(AS NEEDED) (TYP)
#4 @ 12" O.C. EACH WAY
SCH. 40 PVC THREADED
MALE ADAPTER (TYP)
SCH. 40 PVC COUPLER (TYP)
3'-2"
RIGID METALLIC
CONDUIT THREADED
PLUG (TYP)
CONCRETE
PAD
RIGID METALLIC THREADED
CONDUIT COUPLER (TYP)
3/4" CHAMFER (TYP)
3"
(TYP)
S E E N
O T E
PLAN VIEW
RECOMMENDED CLEAR SPACE
6" 2'-2" 6"
3'-2"
R E C
O M
M E N
D E D
A A
M
IN
MINIMUM CLEAR SPACE
CONDUIT ENTRY AND
RECOMMENDED CONDUIT
PLACEMENT (TYP)
POWER UNIT TO BE INSTALLED
(IF REQUIRED) OVER FLUSH
CONDUIT, SEE NOTE 6
10"
10"
1'-4"
(4) HILTI KWIK BOLT TZ2STUD ANCHOR
WITH 3 3/4 INCHES EMBEDMENT PER
MANUFACTURER'S SPECIFICATIONS
MINIMUM CLEAR SPACE
1'-6"
(M
IN
(M
IN
#4 AT 12" O.C.
EACH WAY
1 2
1 2
3/4" CHAMFER
FINISH GRADE
(SEE NOTES 1 & 2)
KEMPOWER POWER UNIT
OR APPROVED EQUAL
SECTION A-A
PROPOSED STUB, CAP AND
CONCRETE PAD PER DETAIL [A/E2.1].
NOTES:
1. EXACT CONDUIT SIZE, DIRECTION AND
QUANTITY MAY VARY, REFER TO ELECTRICAL
CONDUIT PLAN AND CONDUIT SCHEDULE.
2. CONTRACTOR TO REFER TO INSTALLATION
MANUAL FOR CONDUIT ENTRY, SEPARATION
AND PLACEMENT.
3. A MINIMUM OF 1 INCH OF CLEARANCE IS
NEEDED BETWEEN PCS UNITS WHEN PLACING
THEM SIDE BY SIDE .
MINIMUM CLEAR SPACE
CONDUIT FLUSH WITH CONCRETE SURFACE.
PROTECT CONDUCTORS TO REMAIN.
(SEE
NOTE 3)
B
E2.1
KEMPOWER POWER UNIT (C501) PEDESTAL INSTALLATION
NOT TO SCALE
A
E2.1
KEMPOWER POWER UNIT (C501) STUB, CAP AND CONCRETE PAD
NOT TO SCALE
C
E2.1
TYPICAL ELECTRICAL HIGH VOLTAGE UTILITY TRENCH
NOT TO SCALE
D
E2.1
500 KVA TRANSFORMER
NOT TO SCALE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/15/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1900
YΔ
12kV 300kVA, 480Y/277V, 3Ø, 4W
EXISTING
CUSTOMER OWNED
TRANSFORMER
"N1-T1"
DISTRIBUTION PANEL "N1T1-EV1DP",
600 AMP BUS, 600 AMP MAIN
480Y/277V, 3Ø, 4W, 65 kAIC MINIMUM
(NEMA 3R)
600A 3P
MAIN
POWER
CABINET
(PCS-1)
(227 FLA)
TO SINGLE PORT
SATELLITE - 1
'EVCS'
1 2
3P 300A
POWER
CABINET
(PCS-2)
(227 FLA)
TO SINGLE PORT
SATELLITES 2-3
'EVCS'
3P 300A
3" U.G. PVC WITH
(3) 350 MCM Cu AND
(1) #4 Cu GND
(TYP FOR PCS-1
THROUGH PCS-2)
TO EXISTING
SWITCHBOARD
"N4-T3DP"
DC: 3" U.G. PVC WITH
(2) 250 MCM CU AND
(1) 3/0 CU GND
(SEE ELECTRICAL NOTE 10)
CONTROLS AND COMMS:
3/4" U.G. PVC WITH
(1) SUPERCAT 6/7 SHIELDED ETHERNET,
(5) #14 CU AND
(NEMA 3R)
CUSTOMER
OWNED METER
WITHIN
ENCLOSURE
(SEE ELECTRICAL
NOTE 13)
1" A.G. RMC WITH
(SEE ELECTRICAL
NOTE 13)
3P 15A
(2) 4" U.G. PVC WITH
(4) 350 MCM Cu AND
(1) 2/0 Cu GND
(IN EACH CONDUIT)
YΔ
12kV 500kVA, 480Y/277V, 3Ø, 4W
PROPOSED CUSTOMER OWNED
FUSED TRANSFORMER "N1-T8"
WITH 75A PRIMARY FUSE
EXISTING CUSTOMER
OWNED ELECTRICAL
VAULT "N1-MH3"
(SEE ELECTRICAL
NOTE 20)
(2) 6" U.G. PVC WITH
(3) 1/0 Cu AND
(1) #2 Cu GND
(IN EACH CONDUIT)
(SEE ELECTRICAL NOTE 15)
FEED FROM AREA
LOOP 2, NORMAL
POWER FEEDER (3)1/0
CU, 15 KV EPR WITH
(1) #2…
This is the start of the file's text. The full file is on GovTribe.