Plans.pdf

PDF 8 MB Posted

Attached to
Project 10447. EVSE. Contract 24-247821
Solicitation number
0000035117
Issued by
Sacramento County, Sacramento City, San Francisco City, West Sacramento City, California

About this file

These construction documents are for an Electric Vehicle Supply Equipment (EVSE) Level II project at the Department of General Services (DGS) Lot 14 Parking Facility located at 1517 13th Street in Sacramento, California. The project involves installing new electric vehicle charging infrastructure, including wall-mounted single and dual chargers, electrical upgrades, parking lot modifications, and associated civil and electrical work. The project is designed to add electric vehicle charging spaces for workplace and fleet use, with detailed plans showing electrical layouts, site plans, grading details, and specific installation requirements. The documents are marked as 100% working drawings and have been submitted for State Fire Marshal and Division of the State Architect review, with project number 000000000010447.

The project appears to be funded through the State of California's Department of General Services, with a focus on improving electric vehicle charging capabilities at a state-owned parking facility. The plans specify technical details such as conduit and conductor specifications, charging station configurations, and mounting requirements for chargers and transformers. Civil details include parking space striping, accessibility considerations, and concrete work specifications. The documents indicate careful planning for electrical infrastructure, including voltage drop calculations, panel schedules, and specific mounting and installation guidelines for the electric vehicle charging equipment.

View the file

Other files

File Type Posted
Bid_Package_Documents.pdf PDF
Project_Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT WORK AREA

- DGS LOT 14 PARKING

FACILITY

SITE MAP

VICINITY MAP

G0.0

NONE

TITLE SHEET

CODES AND PREFERENCES SHEET INDEX

SYMBOLS AND ABBREVIATIONS

EVSE DESCRIPTION

SCOPE OF WORK

EXISTING EVSE SPACES NEW EVSE SPACES

FLEET WORKPLACE WORKPLACEFLEET

PROJECT

LOCATION

SHEET COUNT: 10 SHEETS

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/11/24

100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKM BKM KM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

EXISTING ADA PARKING

COVERED UNDER DSA

#20-116376

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

SFM NUMBER: 24-3703

DSA NUMBER: 02-122929

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

DGS - Electric Vehicle Supply Equipment - Lot 14

PROJECT NUMBER: 000000000010447; 4/14/25

E0.0

NONE

GENERAL NOTES

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

04/24/23

100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKM BKM KM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

RE

EN

IG

NE

LANOISSEFORP

DERETSI

GER

STATE OF CALIFORNIA

EXP. 9-30-23

No. 23575

ELECTRICAL

JON

ALVAREZ

SPECIAL INSPECTIONS REQUIRED

CONCRETE CONSTRUCTION:

STEEL CONSTRUCTION:

CONT PERIODIC N/A

CONT PERIODIC N/A

GENERAL NOTES:

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

06/14/23

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-2021

09/06/24 project number:

000000000010447

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

DSA NUMBER: 02-122929

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

DGS - Electric Vehicle Supply Equipment - Lot 14

PROJECT NUMBER: 000000000010447; 4/14/25

AutoCAD SHX Text: N/A AutoCAD SHX Text: 9 AutoCAD SHX Text: 10 AutoCAD SHX Text: 11 AutoCAD SHX Text: 12 AutoCAD SHX Text: 8 AutoCAD SHX Text: 5 AutoCAD SHX Text: 1 AutoCAD SHX Text: 2 AutoCAD SHX Text: 3 AutoCAD SHX Text: 4 AutoCAD SHX Text: 24 X 36 AutoCAD SHX Text: CAD FILE:

AutoCAD SHX Text: R AutoCAD SHX Text: Q AutoCAD SHX Text: P AutoCAD SHX Text: O AutoCAD SHX Text: N AutoCAD SHX Text: M AutoCAD SHX Text: L AutoCAD SHX Text: K AutoCAD SHX Text: J AutoCAD SHX Text: I AutoCAD SHX Text: H AutoCAD SHX Text: G AutoCAD SHX Text: F AutoCAD SHX Text: E AutoCAD SHX Text: D AutoCAD SHX Text: C AutoCAD SHX Text: B AutoCAD SHX Text: A AutoCAD SHX Text: R AutoCAD SHX Text: Q AutoCAD SHX Text: P AutoCAD SHX Text: O AutoCAD SHX Text: N AutoCAD SHX Text: M AutoCAD SHX Text: L AutoCAD SHX Text: K AutoCAD SHX Text: J AutoCAD SHX Text: I AutoCAD SHX Text: H AutoCAD SHX Text: G AutoCAD SHX Text: F AutoCAD SHX Text: E AutoCAD SHX Text: D AutoCAD SHX Text: C AutoCAD SHX Text: B AutoCAD SHX Text: A AutoCAD SHX Text: 10 AutoCAD SHX Text: 9 AutoCAD SHX Text: 8 AutoCAD SHX Text: 7 AutoCAD SHX Text: 6 AutoCAD SHX Text: 5 AutoCAD SHX Text: 4 AutoCAD SHX Text: 3 AutoCAD SHX Text: 2 AutoCAD SHX Text: 1 AutoCAD SHX Text: 11 AutoCAD SHX Text: 12 AutoCAD SHX Text: 7 AutoCAD SHX Text: 9 AutoCAD SHX Text: 11 AutoCAD SHX Text: 6 AutoCAD SHX Text: 8 AutoCAD SHX Text: 10 AutoCAD SHX Text: 12 AutoCAD SHX Text: Issue AutoCAD SHX Text: Date AutoCAD SHX Text: No.

AutoCAD SHX Text: Description AutoCAD SHX Text: Project AutoCAD SHX Text: Drawn AutoCAD SHX Text: File Date AutoCAD SHX Text: Supervisor AutoCAD SHX Text: Sheet Title AutoCAD SHX Text: Designed AutoCAD SHX Text: Work Order AutoCAD SHX Text: Sheet Number AutoCAD SHX Text: Sheet Scale AutoCAD SHX Text: Reference North AutoCAD SHX Text: DSA Building Number AutoCAD SHX Text: Vault File Number AutoCAD SHX Text: Checked AutoCAD SHX Text: Client Agency AutoCAD SHX Text: Address AutoCAD SHX Text: SPECIAL INSPECTIONS SHALL BE PERFORMED BY AN APPROVED INSPECTOR AGENCY U.N.O. EMPLOYED BY THE OWNER. THE SPECIAL INSPECTOR SHALL BE CERTIFIED BY THE INTERNATIONAL CODE COUNCIL (I.C.C.) TO PERFORM SPECIAL INSPECTION FOR THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION PRIOR TO THE COMPLETION OF THAT PHASE OF THE WORK. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL AND/OR THE ENGINEER. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. THEN, IF UNCORRECTED, TO THE STRUCTURAL ENGINEER AND TO THE BUILDING OFFICIAL. THE INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS TO THE BEST OF THE INSPECTOR'S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS, AS WELL AS THE ADOPTED REGULATIONS, CODES, AND ORDINANCES, AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. IT SHALL BE THE CONTRACTORS'S SOLE RESPONSIBILITY TO PROVIDE AT LEAST 3 WORKING DAYS ADVANCED NOTICE TO THE STATE/STATE'S REPRESENTATIVE WHEN WORK IS READY FOR ANY REQUIRED SPECIAL INSPECTIONS. SHOP INSPECTION OF STEEL CONSTRUCTION IS NOT REQUIRED WHEN THE WORK IF DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT THE SPECIAL INSPECTION. APPROVAL SHALL BE BASED UPON REVIEW OF THE FABRICATOR'S WRITTEN PROCEDURAL AND QUALITY CONTROL MANUALS AND PERIODIC AUDITING OF FABRICATION PRACTICES BY AN APPROVED SPECIAL INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING OFFICIAL STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE WITH APPROVED CONSTRUCTION DOCUMENTS. SPECIAL INSPECTION SHALL BE PROVIDED FOR THE FOLLOWING TYPES OF WORKS PERFORMED IN THE FIELD, OR NOT PERFORMED IN AN APPROVED FABRICATION SHOP AS DEFINED ABOVE, UNLESS NOTED AS "N/A". EVSE INSTRUCTION MANUAL AND TESTING CERTIFICATES SHALL BE AVAILABLE FOR THE INSPECTOR DURING THE COMMISSIONING STAGES. 1. INSPECTION OF POST INSTALLED ANCHORS INSTALLED IN HARDENED INSPECTION OF POST INSTALLED ANCHORS INSTALLED IN HARDENED CONCRETE 1. MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS: A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARD SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS 2. MATERIAL VERIFICATION OF STRUCTURAL STEEL A. FOR STRUCTURAL STEEL, IDENTIFICATION MARKINGS TO CONFORM TO AISC 360 3. MATERIAL VERIFICATION OF WELD FILLER MATERIAL: 4. INSPECTION OF WELDING: 1. SINGLE PASS FILLET WELDS < = 5/16" AutoCAD SHX Text: 1. ALL EQUIPMENT AND PARTS SHALL BE PROVIDED BY CONTRACTOR ALL EQUIPMENT AND PARTS SHALL BE PROVIDED BY CONTRACTOR UNLESS STATED IN THE DRAWINGS OR SPECIFICATION OTHERWISE. 2. PROVIDE CONDUIT SYSTEM TO ENSURE A NEAT AND PROPER FINAL PROVIDE CONDUIT SYSTEM TO ENSURE A NEAT AND PROPER FINAL INSTALLATION, WITH CONDUIT ROUTED TIGHT TO THE STRUCTURE AND PARALLEL OR PERPENDICULAR TO STRUCTURAL MEMBERS. AFTER INSTALLATION IS COMPLETE, PROPERLY CLEAN CONDUIT FITTINGS, J-BOXES, HANDHOLES AND SUPPORT BRACKETS. 3. ELECTRICAL MATERIAL SHALL BE NEW AND LISTED WITH THE ELECTRICAL MATERIAL SHALL BE NEW AND LISTED WITH THE UNDERWRITERS LABORATORIES, INC. (UL), SHALL MEET THEIR REQUIREMENTS, AND SHALL BEAR THEIR LABEL. 4. GROUNDING SHALL BE EXECUTED IN ACCORDANCE WITH APPLICABLE GROUNDING SHALL BE EXECUTED IN ACCORDANCE WITH APPLICABLE CODES. GREEN INSULATED COPPER GROUNDING SHALL BE PROVIDED TO EACH RECEPTACLE, ENCLOSURE, DEVICE, FIXTURE, ETC. FOR THE ENTIRE WORK. THE RACEWAYS SHALL NOT BE USED FOR “EQUIPMENT EQUIPMENT GROUNDING”. . 5. MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE BRACED OR MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE BRACED OR ANCHORED TO RESIST A HORIZONTAL FORCE ACTING IN ANY DIRECTION PER SECTION 1613A OF 2022 CALIFORNIA BUILDING CODE (CBC). 6. WHERE ANCHORAGE DETAILS ARE NOT SHOWN ON THE DRAWINGS, THE WHERE ANCHORAGE DETAILS ARE NOT SHOWN ON THE DRAWINGS, THE FIELD INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STATE IN WRITING. 7. THE CONTRACTOR SHALL TAKE FIELD MEASUREMENTS AND VERIFY FIELD THE CONTRACTOR SHALL TAKE FIELD MEASUREMENTS AND VERIFY FIELD CONDITIONS AND SHALL COMPARE SUCH FIELD MEASUREMENTS, CONDITIONS AND ANY OTHER RELATED INFORMATION KNOWN BY THE CONTRACTOR WITH THE CONTRACT DOCUMENT BEFORE COMMENCING THE WORK. ANY INCONSISTENCIES SHALL BE IMMEDIATELY REPORTED TO THE STATE IN WRITING. 8. ALL ITEMS ARE NEW (N) UNLESS OTHERWISE SHOWN AS EXISTING (E). ALL ITEMS ARE NEW (N) UNLESS OTHERWISE SHOWN AS EXISTING (E). 9. THE CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ANY DAMAGE THE CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ANY DAMAGE DONE TO ITEMS DURING THE CONTRACT PERIOD AND RESTORE FINISHES OF THOSE REMAINING ITEMS TO MATCH EXISTING (E). 10. CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS SHALL BE SEALED WITH SUITABLE SEALANT TO MAINTAIN FIRE SEPARATION RATING. 3M MOLDABLE PUTTY, NELSON OR EQUAL. 11. PROJECT LOCATIONS BUILT PRIOR TO 1980 ARE PRESUMED TO HAVE PROJECT LOCATIONS BUILT PRIOR TO 1980 ARE PRESUMED TO HAVE ASBESTOS CONTAINING MATERIALS. ALL MATERIALS AFFECTED BY THIS PROJECT IN LOCATIONS BUILT PRIOR TO 1980 SHALL BE REMOVED AS ASBESTOS CONTAINING MATERIALS IN ACCORDANCE WITH ALL APPLICABLE LAWS AND REGULATIONS. 12. CONTRACTOR SHALL PROVIDE GROUND PENETRATING RADAR OR OTHER CONTRACTOR SHALL PROVIDE GROUND PENETRATING RADAR OR OTHER TESTING METHODS TO DETERMINE LOCATIONS OF REINFORCING STEEL AND/OR STRUCTURAL TENDONS WHERE CONCRETE CORING IS REQUIRED. CONTRACTOR SHALL AVOID ALL REINFORCING STEEL AND TENDONS WHEN DRILLING. 13. CONTRACTOR SHALL EVALUATE DURING CONSTRUCTION IF PULLBOX'S CONTRACTOR SHALL EVALUATE DURING CONSTRUCTION IF PULLBOX'S ARE REQUIRED AT CONDUIT BENDS TO INCREASE PERFORMANCE OF CABLE PULLING. 14. ALL WORK SHALL BE IN ACCORDANCE WITH THE TECHNICAL ALL WORK SHALL BE IN ACCORDANCE WITH THE TECHNICAL SPECIFICATION INCLUDED AS COMPLEMENTARY DOCUMENT OF BID PACKAGE. 15. CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS BEFORE COMMENCING WORK. EXACT LOCATION, ELEVATION, AND METHOD OF SUPPORTING CONDUITS AND CABLE SHALL BE DETERMINED AT TIME OF INSTALLATION. 16. THE ELECTRICAL DETAIL SHEETS ARE TYPICAL STANDARD DETAILS, AND THE ELECTRICAL DETAIL SHEETS ARE TYPICAL STANDARD DETAILS, AND NOT ALL DETAILS ARE NECESSARILY USED OR APPLY FOR A SITE BID PACKAGE.

E1.0

CONDUIT / CONDUCTOR TABLE

CONDUIT

NO.

CIRCUIT

VOLTAGE

CONDUIT

SIZE

CONDUIT

TYPE

CONDUCTOR

NO./SIZE

CONDUCTOR

TYPE

CONDUCTOR

VOLTAGE

GROUND

NO./SIZE

GROUND

CONDUCTOR

TYPE

NEW T-2 25.0 30.1

NEW T-2 25.0 30.1

NEW T-2 25.0 30.1

18.7 18.7 18.7

68 68 68

PANEL 'PB-2'

NOTES:

(E) DISTRIBUTION PANEL 'DP'

VOLTAGE DROP CALCULATION

SINGLE LINE DIAGRAM

SINGLE LINE DIAGRAM

& SCHEDULES

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/11/24

100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKM BKM KM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

V1 project number:

000000000010447

V1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

DSA NUMBER: 02-122929

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

COMPACTCOMPACT COMPACT

COMPACT COMPACT COMPACT

DRAWING LIMITS

D R

A W

IN

G

L

IM

IT

S

DRAWING LIMITS

D R

A W

IN

G

L

IM

IT

S

N E2.0

AS NOTED

ELECTRICAL PLAN

Know what's below.

before you dig.Call

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/11/24

100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKM BKM KM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

GROUND FLOOR

V1 project number:

000000000010447

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

DSA NUMBER: 02-122929

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

Dn

DRAWING LIMITS

D R

A W

IN

G

L

IM

IT

S

DRAWING LIMITS

D R

A W

IN

G

L

IM

IT

S

N E2.1

AS NOTED

ELECTRICAL PLAN

- 11001

TYPICAL EVSE STATIONS

Know what's below.

before you dig.Call

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105 West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/11/24 100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKMBKMKM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

SECOND FLOOR

V1

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

E3.0

ELECTRICAL DETAILS

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105 West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/11/24 100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKMBKMKM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

EVSE STRIPING

EVSE WORKPLACE SIGNAGE

PERMANENT BOLLARD 4' LONG WHEEL STOP

V1

CONCRETE

CURB

EVSE PER

PLAN

PROPOSED OSHA

SAFETY GREEN 14120

STRIP

MIN. 12" HIGH WHITE LETTERS,

WITHIN 6" OF THE STALL

CENTERLINE AND ALIGNED AT THE

BOTTOM OF THE PARKING STALL

WHEELSTOP PER

PLAN

G G

3' 3'

MIN 3' DISTANCE BETWEEN EVSE

BOLLARD AND WHEELSTOP.

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

Lnd/Srv Home Run

Trash Room

Pump Rm.

Ramp Up Mech.

Rm.

Electrical Room

Storage

Break Room

Open Office

Trans Vest.

Office

Office

Storage Conference Room

Office

Vest.

Toilet

Arcade

Conference Room

Office

Open Office

COMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACT COMPACT

COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

NO

PARKING

COMPACT

1''=20'

N

OVERALL SITE PLAN

C1.0 Know what's below.

before you dig.Call

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105 West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/06/24 100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKMBKMKM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

CIVIL

LEGEND

CIVIL

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

Storage

Arcade

ELE

CTR

IC

VEH

ICLE

S

ONL

Y

COMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACTCOMPACT

Storage

Arcade

COMPACTCOMPACTCOMPACTCOMPACT

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHA

RGI

NG

ONL

Y

NO

PARKING

COMPACT

Storage

Arcade

COMPACTCOMPACTCOMPACTCOMPACTCOMPACT

1"=10'

N

½” ¼”

LEGEND

DEMOLITION, SITE AND

GRADING PLAN

C2.0 Know what's below.

before you dig.Call

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105 West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/06/24 100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKMBKMKM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

CIVIL

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

9' min12' min

5' min

' m in fu ll re qu ire d le ng th o f ch ar gi ng s pa ce

EV

CHARGING

ONLY

NO

PARKING

EV

CHARGING

ONLY

LC

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

NO

PARKING

SINGLE STRIPE SCENARIO

PARKING STALL STRIPE THICKNESS TO MATCH EXISTING

WIDTH PER CITY STANDARDS AND SPECIFICATIONS

AS SHOWN

CIVIL DETAILS

C3.0 Know what's below.

before you dig.Call

1517 13TH STREET

SACRAMENTO, CA 95814

State of California

Department of General Services Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105 West Sacramento, California 95605

Ryan Allgood Phone 916 375-4115 Fax 916 376-6216 ryan.allgood@dgs.ca.gov

09/06/24 100% WORKING DRAWINGS

SFM SUBMITTAL

KMBKMBKMKM

EVSE LEVEL II

DGS - 1517 13TH STREET

DEPARTMENT OF

GENERAL SERVICES

CIVIL

3' 3'

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

X-X

VII. REINFORCING STEEL:

1. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60.

2. REINFORCING STEEL FOR CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS SHALL HAVE THE

FOLLOWING CONCRETE COVER, SEE ACI 117 FOR TOLERANCES.

A. CONCRETE EXPOSED TO EARTH OR IN CONTACT WITH GROUND:

a. CAST AGAINST AND PERMANENTLY IN CONTACT WITH EARTH 3"

b. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#5 AND SMALLER) 1-1/2"

c. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#6 AND LARGER) 2"

B. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:

a. SLABS, JOISTS AND WALLS (#11 AND SMALLER) 3/4"

b. SLABS, JOISTS AND WALLS (#14 AND LARGER) 1-1/2"

c. BEAMS, COLUMNS AND PEDESTALS 1-1/2"

3. BAR SPLICES MAY BE DELETED AND CONTINUOUS REINFORCING USED AT CONTRACTORS OPTION. BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN FRAMED BEAMS AND SLABS SPLICE TOP

BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS.

4. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH ACI 318 AND THE

'MANUAL OF STANDARD PRACTICE' BY CRSI AS MODIFIED BY THE CONTRACT DOCUMENTS.

5. FIELD BENDING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT SEOR APPROVAL. ALL

REINFORCING BENDS SHALL BE MADE COLD.

IV. REINFORCED CONCRETE:

1. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318 AND ACI 301 WITH MODIFICATIONS AS NOTED

ON THE CONTRACT DOCUMENTS.

2. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND BEAR THE WET SEAL OF A CIVIL ENGINEER LICENSED IN THE STATE OF THE PROJECT AND BE PROVIDED TO THE SEOR FOR REVIEW. EACH MIX DESIGN SHALL BEAR THE NAME OF THE PROJECT AND THE SPECIFIC USE.

3. CONCRETE MODULUS OF ELASTICITY SHALL MEET THE MINIMUM PROVIDED IN ACI 318 SECTION 19.2.2 FOR THE 28-DAY STRENGTH SPECIFIED BELOW. TEST SHALL BE IN ACCORDANCE WITH ASTM C469.

4. CONCRETE SHALL HAVE THE FOLLOWING ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS.

LOCATION STRENGTH, f'c CONCRETE TYPE

A. FOUNDATIONS 4,000 PSI* NORMAL WEIGHT

* INDICATES FOOTING DESIGNED FOR F'c = 2,500 PSI THEREFORE SPECIAL INSPECTIONS NOT

REQUIRED

1. PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR II. CONCRETE EXPOSED TO SOILS

CONTAINING CORROSIVE ELEMENTS (SULFATES) SHALL COMPLY WITH CBC 1904.1.

2. FLY ASH MAY BE USED AS A SUBSTITUTE FOR PORTLAND CEMENT. WEIGHT OF FLY ASH SHALL NOT EXCEED 15% OF CEMENT WEIGHT. FLY ASH SHALL CONFORM TO ASTM C618 CLASS F AND LOSS OF

IGNITION SHALL BE LIMITED TO 2%.

3. MIXING OPERATIONS SHALL CONFORM TO ASTM C94.

4. ALL CONCRETE NOT IN CONTACT WITH EARTH TO HAVE FINISH AS SPECIFIED BY ARCHITECT OR AS

COVERED IN PROJECT SPECIFICATIONS. UNLESS OTHERWISE NOTED, NON-ARCHITECTURAL

CONCRETE COLUMNS AND WALLS SHALL HAVE 3/4”CHAMFERED CORNERS.

5. AGGREGATE FOR NORMALWEIGHT CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS

OF ASTM C33 AND PROJECT SPECIFICATIONS.

6. ALL CONCRETE SHALL BE REINFORCED. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT AS REQUIRED BY ACI-318 IN ELEMENTS WHERE NO REINFORCEMENT IS INDICATED ON THE DRAWINGS.

7. DRY PACK OR GROUT UNDER BASE PLATES AND SILL PLATES SHALL BE 7000 PSI MIN AT 28 DAYS.

8. CONCRETE PLACEMENT SHALL CONFORM TO ACI 304 AND PROJECT SPECIFICATIONS. SANDBLAST ALL

CONCRETE SURFACES WHICH NEW CONCRETE WILL BE PLACED AGAINST.

9. TWO HOURS MUST ELAPSE BETWEEN END OF COLUMN OR WALL POURS AND THE BEGINNING OF

FLOOR POURS.

10. ALL REINFORCEMENT, ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SECURELY HELD IN PLACE WHILE CONCRETE IS POURED. ADDITIONAL BARS TO BE PROVIDED BY THE CONTRACTOR FOR

SUPPORT AS NEEDED.

11. MECHANICAL, ELECTRICAL AND PLUMBING OPENINGS AND SLEEVES ARE SHOWN INDICATIVELY AND

SMALL OPENINGS AND SLEEVES ARE NOT SHOWN. SEE SLAB EDGE, MECHANICAL, ELECTRICAL,

PLUMBING AND OTHER TRADES FOR SIZE AND LOCATION OF ALL SLAB AND WALL OPENINGS AND SLEEVES. CONTRACTOR TO DEVELOP AND SUBMIT A SINGLE COORDINATION DRAWING COMBINING ALL TRADES INDICATING ALL SLAB OPENINGS AND SLEEVES PRIOR TO POURING CONCRETE FOR REVIEW

BY STRUCTURAL ENGINEER.

12. ALL PIPE AND CONDUIT OPENINGS SHALL BE SLEEVED AND CAST IN PLACE UNLESS OTHERWISE

NOTED. DO NOT SAWCUT, CORE OR CORE DRILL STRUCTURAL CONCRETE WITHOUT EXPLICIT

DIRECTION FROM THE STRUCTURAL ENGINEER. DRILL BITS THAT CAN CUT OR DAMAGE REINFORCING

ARE NOT PERMITTED TO BE USED ON STRUCTURAL CONCRETE.

13. CONDUITS AND PIPES SHALL NOT BE PERMITTED IN STRUCTURAL CONCRETE ELEMENTS UNLESS SPECIFICALLY REVIEWED BY THE STRUCTURAL ENGINEER. ALL CONDUITS TO BE EMBEDDED IN THE

STRUCTURAL CONCRETE SHALL BE SUBMITTED FOR STRUCTURAL REVIEW ON A SINGLE

COORDINATED CONDUIT DRAWING COMBINING ALL TRADES DEVELOPED AND COORDINATED BY THE

CONTRACTOR. COORDINATED CONDUITS/PIPES MUST BE PLACED IN ONE LAYER AVOIDING

CROSSOVER AND SPACED AT THE GREATER OF 3" OR 3 DIAMETERS. DRAWINGS SHALL SHOW STUB-UP LOCATIONS, BEND RADIUS AND DETAILS OF CONDUIT/PIPE INSTALLATION. ALL CONDUITS AND PIPES

SHALL BE INSTALLED PER THE REQUIREMENTS OF ACI 318 SECTIONS 20.7 AND 26.8.2.

A. ELECTRICAL CONDUIT SHALL BE RIGID STEEL CONDUIT OR FLEXIBLE PLASTIC CONDUIT. ALUMINUM

CONDUIT IS PROHIBITED. CONDUIT OUTSIDE DIAMETER SHALL NOT EXCEED 2" OR 1/6 SLAB

THICKNESS, WHICHEVER IS LESSER. CONDUIT SHALL BE FIRMLY CHAIRED AND TIED TO PREVENT

DISPLACEMENT DURING POURING.

II. DESIGN LOADS:

1. DEAD LOAD: EQUIPMENT SELF WEIGHT.

2. WIND LOAD

A. ULTIMATE DESIGN BASIC WIND SPEED V(ult) = 94 MPH

B. WIND IMPORTANCE FACTOR = 1.00

C. WIND EXPOSURE CATEGORY = C

3. SEISMIC LOAD

A. SITE CLASS = D (DEFAULT)

B. RISK CATEGORY = II

C. SEISMIC IMPORTANCE FACTOR = 1.00

D. MAPPED SPECTRAL RESPONSE

a. SHORT PERIOD SS = 0.57 g

b. 1-SECOND PERIOD S1 = 0.25 g

E. DESIGN SPECTRAL RESPONSE (5% DAMPED)

a. SHORT PERIOD SDS = 0.51 g

I. GENERAL NOTES:

1. ALL STRUCTURAL WORK SHALL CONFORM TO THE DRAWINGS, THE PROJECT SPECIFICATIONS, ALL

DRAWING NOTES, AND THE 2021 CALIFORNIA BUILDING CODE (CBC).

2. ALL APPLICABLE REFERENCE STANDARDS, AS MODIFIED BY THE BUILDING CODE, INCLUDE:

A. ASCE/SEI 7-16: MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

B. ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

C. AISC 360-16: SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS

D. ACI 117-10: STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE

CONSTRUCTION AND MATERIAL

E. AISI SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL

MEMBERS, 2016

3. THE SCOPE OF WORK IS NOT SOLELY DEFINED BY THESE DOCUMENTS.

4. TYPICAL DETAILS APPLY THROUGHOUT THE PROJECT, EVEN IF NOT SPECIFICALLY REFERENCED IN PLANS OR DETAILS. DETAILS OF CONSTRUCTION NOT FULLY SHOWN OR NOTED ON THE DRAWINGS NOR CALLED OUT IN THE SPECIFICATIONS SHALL BE OF THE SAME SIZE AND CHARACTER AS FOR

SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.

5. ALL FORCES INDICATED IN THE STRUCTURAL DRAWINGS ARE SERVICE LOADS AS DEFINED BY ASCE-7, UNLESS NOTED OTHERWISE.

6. DO NOT USE SCALED DIMENSIONS; USE ONLY WRITTEN DIMENSIONS. WHERE NO DIMENSION IS

PROVIDED, CONSULT THE ARCHITECT FOR CLARIFICATIONS BEFORE PROCEEDING WITH WORK.

7. SEE ARCHITECTURAL DRAWINGS FOR SITE POSITIONING AND PROJECT DATUM, REFERENCE IS (0'-0")

AS SHOWN ON ARCHITECTURAL DRAWINGS.

8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONDITIONS OF THE JOB SITE

INCLUDING SAFETY OF PERSONS AND PROPERTY AND THE MEANS AND METHODS OF CONSTRUCTION.

9. STRUCTURAL ELEMENTS SHALL BE CENTERED ABOUT GRIDLINES OR DIMENSION LINES, UNLESS

OTHERWISE NOTED.

10. THE CONTRACTOR SHALL PROVIDE ENGINEERED DESIGNS OF TEMPORARY SHORING AND BRACING AND MAKE SAFE ALL FLOORS, ROOFS, WALLS, EXCAVATIONS AND ADJACENT PROPERTY AS PROJECT

CONDITIONS AND LOCAL BUILDING CODE REQUIRE.

11. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC. REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT

SHOWN ON PLAN. DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE ARCHITECT

IMMEDIATELY.

12. OPENINGS SHALL NOT BE MADE IN ANY STRUCTURAL MEMBER UNLESS SPECIFICALLY SHOWN ON THE

STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.

13. DEFICIENT WORK AND WORK NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AS IDENTIFIED

BY THE ARCHITECT OR INSPECTOR SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE.

CONTRACTOR SHALL COMPENSATE OWNER FOR SERVICES ARISING FROM DEFICIENT WORK.

14. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY REQUIRED DEWATERING OF THE SITE

DURING CONSTRUCTION.

15. THE CONTRACTOR SHALL PREPARE ENGINEERED DESIGN AND SHALL BE RESPONSIBLE FOR

CONFIRMING ADEQUACY OF AS BUILT STRUCTURE FOR ALL SURCHARGE LOADS RESULTING FROM

COMPACTION AS WELL AS CRANES TRUCKS, BULLDOZERS OR ANY OTHER CONSTRUCTION

EQUIPMENT. ENGINEERED DESIGNS SHALL BE PREPARED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION AND SUBMITTED TO ENGINEER OF RECORD FOR REVIEW.

16. THE STRUCTURAL COMPONENTS BY THEMSELVES ARE A NON-SELF-SUPPORTING STRUCTURE.

LATERAL FORCES DUE TO WIND, EARTHQUAKE, OR SOIL ARE CARRIED BY THE ROOF AND FLOOR DIAPHRAGMS TO THE LATERAL SYSTEM. CERTAIN ELEMENTS SHOWN ON THE STRUCTURAL DRAWINGS

(SUCH AS BRACING, ROOF AND FLOOR SLABS, AND CONCRETE IN COMPOSITE COLUMNS) ARE

REQUIRED FOR OVERALL OR LOCAL STABILITY OF OTHER ELEMENTS (SUCH AS BEAMS, COLUMNS, AND WALLS). IF DUE TO SEQUENCING OF CONSTRUCTION, THESE STABILITY ELEMENTS ARE NOT IN PLACE, THE CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION WHERE THE PROJECT IS LOCATED, WHO SHALL INVESTIGATE WHERE TEMPORARY

SHORING/BRACING IS REQUIRED AND SHALL DESIGN THIS TEMPORARY SHORING/BRACING. THE

CONTRACTOR SHALL PROVIDE THIS SHORING/BRACING UNTIL THE REQUIRED STRUCTURAL ELEMENTS AND THEIR CONNECTIONS HAVE BEEN INSTALLED AND REACH THEIR FINAL DESIGN STRENGTHS.

17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT WHEN PLACED ON FRAMED FLOORS OR ROOFS.

THE CONSTRUCTION MATERIAL LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.

CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING WHERE STRUCTURE IS NOT COMPLETE OR HAS

NOT ATTAINED DESIGN STRENGTH.

18. BUILDING TOLERANCES: STANDARD TOLERANCES SHALL BE BASED ON THE REQUIREMENTS OF THE AISC CODE OF STANDARD PRACTICE AND ACI 117, STANDARD SPECIFICATIONS FOR TOLERANCES FOR

CONCRETE CONSTRUCTION AND MATERIALS.

III. FOUNDATIONS:

1. FOUNDATION DESIGN CRITERIA ARE BASED ON CODE MINIMUM VALUES AS SPECIFIED IN CHAPTER 18

"SOILS AND FOUNDATIONS" OF THE 2021 CALIFORNIA BUILDING CODE (CBC).

2. FOOTINGS ARE DESIGNED BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 1,500 PSF.

3. LATERAL BEARING PRESSURE FOR FOOTING DESIGN IS 100 PSF.

4. SOIL PREPARATION OF THE SITE SHALL FOLLOW THE RECOMMENDATIONS DESCRIBED IN CHAPTER 18 OF 2021 CBC. THIS INCLUDES REMOVAL OF EXISTING STRUCTURES/UTILITIES, REMOVAL OF EXISTING FILL WHERE DEEMED NECESSARY, PREPARATION OF THE SUBGRADE & COMPACTION, EXCAVATIONS

FOR NEW FOUNDATIONS & SLABS, AND BACKFILLING TO RETAINING WALLS.

5. FOUNDATIONS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED FILL MATERIAL 12 INHES IN DEPTH WITH THE IN-PLACE DRY DENSITY NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT

OPTIMUM MOISTURE CONTENT DETERMINED IN ACCORDANCE WITH ASTM D1557.

6. LOCATION OF ALL UNDERGROUND UTILITIES SHALL BE VERIFIED PRIOR TO CONSTRUCTION OF FOUNDATION TO AVOID ANY INTERFERENCE. CONTRACTOR SHALL EXPOSE EXISTING UTILITY LINES IN THE IMMEDIATE AREA TO DETERMINE THEIR EXACT INVERT ELEVATION, SIZE AND LOCATION RELATIVE TO THE FOUNDATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY INTERFERENCE WITH PILES, FOOTINGS OR FOUNDATION WALLS.

7. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER, AND SEEPAGE. WATER SHALL NOT BE ALLOWED TO STAND IN TRENCHES OR FORMS BEFORE OR AFTER CONCRETE IS PLACED, AND SHALL BE PUMPED OUT. IF BOTTOMS OF TRENCHES

BECOME SOFTENED DUE TO RAIN OR OTHER WATER BEFORE FOUNDATIONS ARE CAST, THE

CONTRACTOR SHALL, AT THEIR OWN EXPENSE, EXCAVATE THE SOFTENED MATERIAL AND REPLACE

WITH CONCRETE.

8. CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED TO SAFELY AND ADEQUATELY RETAIN THE EARTH BANKS AND ANY EXISTING

STRUCTURE.

9. EXCAVATIONS FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO

PLACING OF CONCRETE AND REINFORCING. CONTRACTOR SHALL NOTIFY THE GEOTECHNICAL

ENGINEER WHEN THE EXCAVATIONS ARE READY FOR INSPECTION. THE GEOTECHNICAL ENGINEER

SHALL SUBMIT A LETTER OF COMPLIANCE TO THE OWNER.

10. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING

WALLS BEFORE CONCRETE OR MASONRY HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR

SHALL BRACE OR PROTECT ALL BUILDING WALLS BELOW GRADE FROM LATERAL LOADS UNTIL

ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL DESIGN STRENGTH.

CONTRACTOR SHALL PROVIDE FOR DESIGNS, PERMITS AND INSTALLATION OF BRACING AND

PROTECTION.

VIII. ANCHOR RODS:

1. ANCHOR RODS SHALL BE ASTM F1554 GRADE 36 WITH CLASS 1A THREADS, UNLESS NOTED

OTHERWISE. FURNISH ANCHOR RODS PREFABRICATED WITH MATCHING DOUBLE HEAVY HEX NUTS

JAMMED AT THE END EMBEDDED IN CONCRETE. FURNISH HARDENED PLATE WASHERS, LOCK

WASHERS, AND MATCHING HEAVY HEX NUTS FOR SECURING THE BASE PLATE TO THE ANCHOR RODS.

A RIGID STEEL TEMPLATE SHALL BE USED TO LOCATE ANCHOR RODS WHILE PLACING CONCRETE.

2. HOOKED ANCHOR RODS SHALL NOT BE USED EXCEPT WHERE NOTED.

3. ANCHOR RODS SHALL HAVE SUFFICIENT LENGTH TO PROVIDE THE MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, MEASURED FROM THE FACE OF THE CONCRETE TO THE NEAR FACE OF THE DOUBLE NUT, WITH ADEQUATE EXTENSION AS REQUIRED TO RECEIVE THE BASE PLATE WITH FULL THREAD

PROJECTION FOR NUT INSTALLATION.

4. ANCHOR ROD INSTALLATION SHALL BE COORDINATED WITH REINFORCING AND FRAMEWORK.

5. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER EVALUATION BY THE CONTRACTOR'S ERECTION

ENGINEER.

6. AFTER BASE INSTALLATION, ANCHOR ROD NUTS SHALL BE INSTALLED TO A SNUG-TIGHT CONDITION.

7. NO HEATING OR BENDING OF THE ANCHOR RODS IS PERMITTED. HOLES IN THE BASE

MATERIAL SHALL NOT BE ENLARGED BY BURNING.

VI. MECHANICAL AND ADHESIVE ANCHORS:

1. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE:

A. "SET-XP”BY SIMPSON STRONG TIE (ICC ESR-2508)

B. "HIT-HY 200 V3" BY HILTI, INC. (ICC ESR-3814) EQUIPMENT ANCHORAGE UON

C. "PURE110+BY DEWALT (ICC ESR-3298)

2. EXPANSION ANCHORS INSTALLED INTO CONCRETE:

A. "STRONG-BOLT 2" BY SIMPSON STRONG-TIE (ICC ESR-3037)

B. "KWIK BOLT TZ2 (KB-TZ2)”BY HILTI, INC. (ICC ESR-4266)

C. "POWER-STUD+SD2" BY DEWALT (ICC ESR-2502)

3. ADHESIVE ANCHORS: ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS AND ANSI B18.22.1

TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS ASTM A193 GRADE B7

THREADED RODS TO USE ASTM A 563 GRADE DH HEAVY HEX NUTS AND ASTM F 436 WASHERS.

4. ADHESIVE DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.

5. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC-ES REPORT AND MANUFACTURERS

RECOMMENDATIONS.

6. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS PER ICC-ES REPORT &

MANUFACTURERS RECOMMENDATIONS.

7. CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL

ASSEMBLIES ATTACHED WITH MECHANICAL OR ADHESIVE ANCHORS.

8. PRIOR TO ALL DRILLING OR CORING, THE CONTRACTOR SHALL (1) VERIFY THE EXISTING CONCRETE OR MASONRY THICKNESS TO PREVENT DAMAGE TO THE OPPOSITE FACE OF CONCRETE AND MAINTAIN 1 -1 /2 ”CLEAR COVER U.N.O., AND (2) IDENTIFY EXISTING REINFORCING LOCATIONS BY PACHOMETER, PROBING, CHIPPING, ETC. TO AVOID DAMAGE EXISTING REINFORCING.

9. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH, WHICHEVER IS

LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE

ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS

NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION.

10. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION TO SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER

(AAI) CERTIFIED THROUGH ACI/CRSI OR EQUIVALENT (ACI 318-14 17.8.2.2).

11. ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-14 17.1.2).

SETTING INFORMATION SYM. UNITS

NOMINAL ANCHOR DIAMTER (IN.)

INSTALLATION TORQUE

CARBON STEEL

INSTALLATION TORQUE

STAINLESS STEEL

TINST

TINST

FT-LB

(Nm)

FT-LB

(Nm)

1/4 3/8 1/2 5/8 3/4

(5)

(41)

(68)

(54)

(149)

(8)

(41)

(54)

(81)

(169)

SLAB STEP/ DEPRESSION

SLOPE UP

SLOPE DOWN

RIDGE

VALLEY

REVISION NUMBER

ELEVATION

SECTION MARK

ELEVATION MARK

GRID BUBBLE

S301

S201

SLAB THICKNESS

CHANGE

DETAIL MARK

S501

THE INSPECTOR SHALL OBSERVE THESE FUNCTIONS ON A RANDOM BASIS.

OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS.

OBSERVE

THESE INSPECTIONS SHALL BE PERFORMED FOR EACH CONNECTION OR MEMBER,

AND COMPLETED PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.

PERFORM

SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT CONTINUOUSLY

WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED

CONTINUOUS

SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT

WHERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF

WORK.

PERIODIC

A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN APPROVED AGENCY AND

APPROVED BY THE BUILDING OFFICIAL AS HAVING THE COMPETENCE NECESSARY TO

INSPECT A PARTICULAR TYPE OF CONSTRUCTION REQUIRING SPECIAL INSPECTION.

SPECIAL

INSPECTOR

INSPECTION OF CONSTRUCTION REQUIRING THE EXPERTISE OF AN APPROVED

SPECIAL INSPECTOR IN ORDER TO ENSURE COMPLIANCE WITH THE BUILDING CODE

AND THE APPROVED CONSTRUCTION DOCUMENTS.

SPECIAL

INSPECTION

DEFINITIONS

REFERENCES

CODES/STANDARDS

SPECIAL INSPECTION AND TEST REQUIREMENTS

TYPE REQUIRED INSPECTIONS AND/OR TESTSFREQUENCY

INDICATES SPECIAL INSPECTION OF ITEM IS REQUIRED FOR THE WORK DEFINED IN

THE CONSTRUCTION DOCUMENTS FOR THIS PROJECT.

INSPECTION AND TESTING REQUIREMENTS ON THIS SHEET ARE IN ACCORDANCE

WITH SECTION 1705 OF THE 2021 CALIFORNIA BUILDING CODE (CBC). AND HAVE BEEN

IDENTIFIED AS A STATEMENT OF SPECIAL INSPECTIONS AS REQUIRED BY CBC

SECTION 1704.3. THE OWNER OR THE OWNER'S AUTHORIZED AGENT, OTHER THAN

THE CONTRACTOR, SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO

PROVIDE THE SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION AS

REQUIRED BY CBC SECTION 1705 AND IDENTIFY THE APPROVED AGENCIES TO THE

BUILDING OFFICIAL. THESE SPECIAL INSPECTIONS AND TESTS ARE IN ADDITION TO

THE INSPECTIONS BY THE BUILDING OFFICIAL THAT ARE IDENTIFIED IN CBC SECTION

110. SPECIAL INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE WITH CBC SECTION

1704.2.1, AND ALL OTHER APPLICABLE SECTIONS AND STANDARDS.

SPECIAL INSPECTIONS AND TESTS INDICATED ON THIS SHEET ARE FOR THE

STRUCTURAL WORK, SEE OTHER DISCIPLINES DRAWINGS AND SPECIFICATIONS FOR

REQUIRED NONSTRUCTURAL SPECIAL INSPECTIONS AND TESTS.

STATEMENT OF SPECIAL INSPECTIONS

CONCRETE CBC 1705.3

4. ANCHORS POST-INSTALLED

IN HARDENED CONCRETE

MEMBERS

INSPECT ALL OTHER MECHANICAL OR ADHESIVE ANCHORS THAT ARE NOT ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS - SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI318: 17.8.2 OR OTHER QUALIFICATION PROCEDURES.

PERIODIC ACI 318: 17.8.2

GENERAL NOTES ABBREVIATIONS

Issue

Project

Supervisor Designed Drawn

Sheet Title

Sheet Scale

Sheet Number

A x

B C D E F G H I J K L M N O

AB C D E F G H I J K L M N O

File Date

V3

PROFESSIONAL STAMP

Work OrderDSA Building Number

Vault File Number

Address

Checked

N/A

Client Agency

S---001

MRP JH DK

Stantec Consulting Services Inc.

801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775

GENERAL NOTES

AD

# POUND

& AND

@ AT

AB ANCHOR BOLT

ACS ALL COMMON SIDES

ADDL ADDITIONAL

AESS ARCHITECTURALLY EXPOSED

STRUCTURAL STEEL

ALT ALTERNATE

ARCH,

ARCH'L

ARCHITECT, ARCHITECTURAL

BL BRICKLEDGE

BLDG BUILDING

BLKG BLOCKING

BM BEAM

BN BOUNDARY NAILING

BO BOTTOM OF

BOB BOTTOM OF BEAM

BOD BOTTOM OF DECK

BOS BOTTOM OF STEEL

BOT, BOTT BOTTOM

BP BASE PLATE

BRBF BUCKLING RESTRAINED BRACED

FRAME

BRG BEARING

BTWN BETWEEN

C CHANNEL

CB CONCRETE BEAM

CC CARRIED COLUMN

CEN CENTER

CFMF COLD-FORMED METAL FRAMING

CIP CAST IN PLACE

CJ CONTROL JOINT

CJP COMPLETE JOINT PENETRATION

CL CENTERLINE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONN CONNECT, CONNECTION

CONT CONTINUOUS

CTR CENTERED

CWI CERTIFIED WELDING INSPECTOR

D, DIA DIAMETER

DBA DEFORMED BAR ANCHOR

DBL DOUBLE

DEF DEFORMED, DEFINITION

DEFL DEFLECTION

DET, DTL DETAIL

DIAG DIAGONAL

DN DOWN

DWG DRAWING

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

EMB EMBED

EN EDGE NAILING

EOR ENGINEER OF RECORD

EOS EDGE OF SLAB

EQ EQUAL

EQ SPA EQUAL SPACE

ES EACH SIDE

EW EACH WAY

EXIST, (E) EXISTING

EXT EXTERIOR

FD FLOOR DRAIN

FDN, FNDN FOUNDATION

FF EL FINISH FLOOR ELEVATION

FN FIELD NAILING

FOA FACE OF ANGLE

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FT FEET

FTG FOOTING

Fy YIELD STRESS

GA GAGE, GUAGE

GALV GALVANIZED

GB GRADE BEAM

GLB GLUED-LAMINATED BEAM

GT GIRDER TRUSS

H, HORIZ HORIZONTAL

HC HOLLOW CORE

HI HIGH

HK HOOK

HSS HOLLOW STRUCTURAL STEEL

IN INCHES

INFO INFORMATION

INT INTERIOR

JST JOIST

JT JOINT

K KIPS

KB KNEE BRACE

L ANGLE

LB POUND

LF LINEAR FOOT

LG LENGTH

LLBB LONG LEG BACK TO BACK

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LO LOW

LT WT LIGHTWEIGHT

LVL LEVEL

MAX MAXIMUM

MC MOMENT CONNECTION

MCJ MASONRY CONTROL JOINT

MECH MECHANICAL

MEZZ MEZZANINE

MFR,

MANUF

MANUFACTURER

MID MIDDLE

MIL MILLIMETER

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTL METAL

N NORTH

NA NOT APPLICABLE

NDT NON-DESTRUCTIVE TESTING

NEW, (N) NEW

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NWC NORMAL WEIGHT CONCRETE

OC ON CENTER

OH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OWSJ OPEN WEB STEEL JOIST

PERP PERPENDICULAR

PJP PARTIAL JOINT PENETRATION

PL PLATE

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

R RADIUS

REF REFER, REFERENCE

REINF REINFORCED, REINFORCEMENT

REM REMAINDER

REQ'D REQUIRED

REQ'MTS,

REQMTS

REQUIREMENTS

REV REVISION

SAD SEE ARCHITECTURAL DRAWINGS

SC SLIP CRITICAL

SCHED SCHEDULE

SCJ SAWN CONTROL JOINT

SECT SECTION

SF SQUARE FEET

SHT SHEET

SHTG SHEATHING

SIM SIMILAR

SOG SLAB ON GRADE

SPA SPACES, SPACING

SQ SQUARE

SSH SHORT SLOTTED HOLE

STD STANDARD

STL STEEL

STRUCT STRUCTURE, STRUCTURAL

SUPP SUPPORT

T&B TOP AND BOTTOM

TEMP TEMPORARY

THK THICK

TO TOP OF

TOC TOP OF CONCRETE

TOF TOP OF FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF STEEL

TOSC TOP OF STRUCTURAL CONCRETE

TOSL TOP OF SLAB

TOT TOTAL

TOW TOP OF WALL

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

V, VERT VERTICAL

VIF VERIFY IN FIELD

W WIDE FLANGE

W/ WITH

W/O WITHOUT

WB WIND BRACE

WBBP WIND BRACE BASEPLATE

WHSS WELDED HEADED STEEL STUD

WP WORKING POINT, WORK POINT

WRT WITH RESPECT TO

WT WEIGHT

WWR WELDED-WIRE REINFORCEMENT

YD YARD

SYMBOLS

DGS - LOT 14

1517 13TH ST

SACRAMENTO, CA 95814

V1

No. Date Description

09-30-622426

9-10-24 project number:

000000000010447

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

DSA NUMBER: 02-122929

09-30-26

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

7 3/4"

4"

1/ 5"

1' 1/ 2"

1' 1"

1'

1/ 2"

3/ 4"

MOUNTING HOLES, PER MFR (4) TOT

P1000 EXTEND

3" MIN PAST

EACH ANCHOR

TYP

1/4" DIA HHCS &

SPRING NUT

TYP

(2) 1/2" DIA

HILTI KB-TZ2

TYP

EQUIP BY

OTHERS

(E) CMU WALL

1' 1"

3' 1/

1' 1/ 2"

1 3/16"

1 5/8"

3 3/4"

94 LBS

11 1/2"

NOTES:

1. ALL STRUTS SHALL BE UNISTRUT

2. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED

3. CMU ASSUMED TO BE SOLID GROUTED, ALERT SEOR IF HOLLOW BLOCKS

ARE DISCOVERED

2" EMB

C

LR3"

TYP

3" CLR

2'

0"

TRANFORMER BY

OTHERS

FINISHED GRADE

SUBGRADE PER

GENERAL NOTES

(4) #5 EA WAY

TOP & BOT

WT = 1025 LBS

NOTE:

1. FOOTING MAY BE FLUSH WITH ADJACENT PAVING AS REQUIRED.

PAVING PER NOTE 1

.7

1/2" DIA AB @ MFR LOCATION (4) MIN

TYP

CONTRACTOR'S ALT: 1/2" DIA

THREADED ROD W/ HITLI HIT-HY 200

V3 ADHESIVE (ICC ESR - 4868)

W/ 8" EMB

1' -0 M

IN

TY

P

8" E

M B

TYP

6" MIN

EQ EQ

31.3" x 24"

(2) 3/8" DIA MB PER

BRACKET

FLOOR MOUNTING

KIT 7400FM PER MFR

(2) PER SIDE

7 3/4"

4"

1/ 5"

1' 1/ 2"

1'

1"

1'

1/ 2"

3/ 4"

MOUNTING HOLES, PER MFR (4) TOT

P1000 EXTEND

3" MIN PAST

EACH ANCHOR

TYP

1/4" DIA HHCS &

SPRING NUT

TYP

(2) 1/2" DIA

HILTI KB-TZ2

TYP

EQUIP

(E) CMU WALL

1' 1"

3' 1/

1' 1/ 2"

1 3/16"

1 5/8"

3 3/4"

111 LBS

11 1/2"

NOTES:

1. ALL STRUTS SHALL BE UNISTRUT

2. ALL EXPOSED STEEL SHALL BE HOT DIPPED GALVANIZED

3. CMU ASSUMED TO BE SOLID GROUTED, ALERT SEOR IF HOLLOW BLOCKS

ARE DISCOVERED

Issue

Project

Supervisor Designed Drawn

Sheet Title

Sheet Scale

Sheet Number

A x

B C D E F G H I J K L M N O

AB C D E F G H I J K L M N O

File Date

V3

PROFESSIONAL STAMP

Work OrderDSA Building Number

Vault File Number

Address

Checked

N/A

Client Agency

S---002

MRP JH DK

Stantec Consulting Services Inc.

801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775

DETAILS

AD

DGS - LOT 14

1517 13TH ST

SACRAMENTO, CA 95814

V1

No. Date Description

NTSS---002

2 SINGLE WALL MOUNTED CHARGER

NTSS---002

5 TRANSFORMER FOUNDATION & ANCHORAGE

NTSS---002

4 DUAL WALL MOUNTED CHARGER

09-30-622426

9-10-24 project number:

000000000010447

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

10/09/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-3703

DSA NUMBER: 02-122929

09-30-26

DSA

D E P A R T M E N T O F G E N E R A L S E R V I C E S

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

DSA

DIVISION OF THE STATE ARCHITECT

IDENTIFICATION STAMP

DIV. OF THE STATE ARCHITECT

APP: INC:

REVIEWED FOR

SS FLS ACS

DATE:

02-122929

02/03/2025

File details come from the government source that posted it. Updated .