Plans 27-36 18124.pdf

PDF 4 MB Posted

Attached to
751/18124. CDP Holly Rec. Area Wastewater System Improvements
Solicitation number
RFQ 171 200000000138 2
Issued by
Benzie County, Michigan

About this file

This document consists of electrical construction plans for the Holly Recreation Area Wastewater System Improvements project under the State of Michigan, Department of Natural Resources, Parks and Recreation Division. The project (DTMB File Number 751/18124.CDP) encompasses Phase 500 (Bids and Construction) and includes detailed electrical specifications and site plans for wastewater system improvements at a recreation area facility. The plans specify work for three primary locations: the sanitation station/equalization tank pump station, the west restroom building pump station, and the east restroom building pump station. The project requires installation of control panels, pumping systems with variable frequency drives, flow metering equipment, electrical service upgrades, and generator with automatic transfer switch capabilities (noted as Bid Alternate No. 2). Multiple submersible pumps ranging from 2 to 12 horsepower are specified across the facilities, along with associated conduit, wiring, and control systems complying with the National Electrical Code and NFPA standards.

The electrical plans detail comprehensive wiring requirements, equipment pad specifications, and hazardous location classifications for confined spaces such as equalization tanks and wet wells. Equipment specifications include NEMA 4X stainless steel enclosures for control panels, surge protective devices with minimum 80 kVA/phase ratings, intrinsically safe relays and barriers for hazardous areas, and uninterruptible power supplies. The plans establish minimum conductor sizing requirements (#12 for power, #14 for control, #16 twisted shielded pair for analog signals), conduit specifications ranging from 3/4 inches to 3 inches, and grounding electrode systems with maximum 5-ohm resistance. Bid Alternate No. 2 addresses the optional provision of a 100 kilowatt diesel standby generator with automatic transfer switch, with a manual 2-pole 400-ampere transfer switch as the base requirement if the generator option is not selected. The document includes detailed diagrams, material schedules, installation details, and comprehensive notes for coordination with utility providers including Consumers Energy for electrical service connections.

View the file

Other files

File Type Posted
Specs 18124.pdf PDF
Plans 1-7 18124.pdf PDF
Addendum 1 18124.pdf PDF
Plans 18-26 18124.pdf PDF
Plans 8-17 18124.pdf PDF
Advertisement 18124.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Reviewer

Designer

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

W G

L A

Y O

U T

E

D

T

E

T

I M

E

M

U

S E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a t e o f

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a n d

R c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E001

TCD

TCD

JAC

GENERAL NOTES

DEMOLITION NOTES

AutoCAD SHX Text

1. THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND NFPA 820 SHALL BE CONSIDERED CLASS I, DIVISION 1 HAZARDOUS LOCATIONS: A. INSIDE EQUALIZATION TANK. B. INSIDE WET WELLS. 2. THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND NFPA 820 SHALL CONSIDERED CLASS I, DIVISION 2 HAZARDOUS LOCATIONS: A. INSIDE FLOW METER MANHOLE. B. INSIDE CONTROL VALVE MANHOLES. 3. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCALLY ADOPTED CODES. 4. COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL SERVICE TO NEW EQUALIZATION TANK AREA. 5. PROVIDE CONDUIT SEAL-OFF FITTINGS IN ALL CONDUIT RUNS PROVIDE CONDUIT SEAL-OFF FITTINGS IN ALL CONDUIT RUNS THAT ENTER/LEAVE HAZARDOUS LOCATIONS. ALL WORK IN HAZARDOUS AREAS SHALL BE IN ACCORDANCE WITH ARTICLE 500 OF THE NATIONAL ELECTRICAL CODE. 6. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS. 7. ALL WIRING SHALL BE INSTALLED IN CONDUIT; MINIMUM ALL WIRING SHALL BE INSTALLED IN CONDUIT; MINIMUM CONDUIT SIZE IS 3/4" . MINIMUM CONDUCTOR SIZES FORPOWER WIRING IS #12, FOR CONTROL WIRING IS #14, AND FOR ANALOG SIGNAL WIRING IS #16TSP (TWISTED SHIELDED PAIR). 8. PROVIDE EQUIPMENT PADS. REFERENCE SHEET E603 FOR PROVIDE EQUIPMENT PADS. REFERENCE SHEET E603 FOR EQUIPMENT PAD DETAIL. COORDINATE LOCATIONS WITH CIVIL. 9. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE. 10. ALL MOUNTING HARDWARE SHALL BE 316 STAINLESS STEEL.ALL MOUNTING HARDWARE SHALL BE 316 STAINLESS STEEL.

AutoCAD SHX Text

GENERAL ELECTRICAL ABBREVIATIONS

AutoCAD SHX Text

AMPERES

AutoCAD SHX Text

A, AMP

AutoCAD SHX Text

KNOCKOUT

AutoCAD SHX Text

KO

AutoCAD SHX Text

ALTERNATING CURRENT

AutoCAD SHX Text

AC

AutoCAD SHX Text

KILOVOLT AMPERE

AutoCAD SHX Text

KVA

AutoCAD SHX Text

ACOUSTICAL CEILING PANEL

AutoCAD SHX Text

ACP

AutoCAD SHX Text

KILOWATT

AutoCAD SHX Text

KW

AutoCAD SHX Text

AMERICANS WITH DISABILITIES ACT

AutoCAD SHX Text

ADA

AutoCAD SHX Text

KILOWATT-HOUR

AutoCAD SHX Text

KWHR

AutoCAD SHX Text

ABOVE FINISHED FLOOR

AutoCAD SHX Text

AFF

AutoCAD SHX Text

LIGHT-EMITTING DIODE

AutoCAD SHX Text

LED

AutoCAD SHX Text

AUTHORITY HAVING JURISDICTION

AutoCAD SHX Text

AHJ

AutoCAD SHX Text

LIGHT SWITCH OR LIMIT SWITCH

AutoCAD SHX Text

LS

AutoCAD SHX Text

AMPERE-INTERRUPTING CURRENT

AutoCAD SHX Text

AIC

AutoCAD SHX Text

LIGHT OR LEVEL TRANSDUCER

AutoCAD SHX Text

LT

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

AL

AutoCAD SHX Text

LIQUID-TIGHT FLEXIBLE METAL CONDUIT

AutoCAD SHX Text

LTFMC

AutoCAD SHX Text

LIGHTING

AutoCAD SHX Text

LTG

AutoCAD SHX Text

AUTOMATIC TELLER MACHINE

AutoCAD SHX Text

ATM

AutoCAD SHX Text

LOW VOLTAGE

AutoCAD SHX Text

LV

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH

AutoCAD SHX Text

ATS

AutoCAD SHX Text

METER

AutoCAD SHX Text M

AutoCAD SHX Text

CIRCUIT BREAKER

AutoCAD SHX Text

BRKR

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

MANUF

AutoCAD SHX Text

CONDUIT OR CELSIUS

AutoCAD SHX Text C

AutoCAD SHX Text

MINIMUM CIRCUIT AMPACITY

AutoCAD SHX Text

MCA

AutoCAD SHX Text

CIRCUIT BREAKER

AutoCAD SHX Text

CB

AutoCAD SHX Text

MAIN CIRCUIT BREAKER

AutoCAD SHX Text

MCB

AutoCAD SHX Text

CABLE TELEVISION

AutoCAD SHX Text

CATV

AutoCAD SHX Text

MOTOR CONTROL CENTER

AutoCAD SHX Text

MCC

AutoCAD SHX Text

CAST-IN-PLACE

AutoCAD SHX Text

CIP

AutoCAD SHX Text

MOTOR CIRCUIT PROTECTOR

AutoCAD SHX Text

MCP

AutoCAD SHX Text

CONTROL JOINT

AutoCAD SHX Text

CJ

AutoCAD SHX Text

MANHOLE

AutoCAD SHX Text

MH

AutoCAD SHX Text

CIRCUIT

AutoCAD SHX Text

CKT

AutoCAD SHX Text

MAIN LUGS ONLY

AutoCAD SHX Text

MLO

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

CLG

AutoCAD SHX Text

MOUNT

AutoCAD SHX Text

MT

AutoCAD SHX Text

CONSTRUCTION MANAGER

AutoCAD SHX Text

MOUNTED

AutoCAD SHX Text

MTD

AutoCAD SHX Text

CONCRETE MASONRY UNIT

AutoCAD SHX Text

MEDIUM VOLTAGE

AutoCAD SHX Text

MV

AutoCAD SHX Text

COAXIAL

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

N, NEUT

AutoCAD SHX Text

CONCRETE

AutoCAD SHX Text

NORMALLY CLOSED

AutoCAD SHX Text

NC

AutoCAD SHX Text

CONTROL PANEL

AutoCAD SHX Text

NIGHT LIGHT

AutoCAD SHX Text

NL

AutoCAD SHX Text

CURRENT TRANSFORMER

AutoCAD SHX Text

NORMALLY OPEN

AutoCAD SHX Text

NO

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

NOMINAL

AutoCAD SHX Text

NOM

AutoCAD SHX Text

COMMISSIONING

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

NTS

AutoCAD SHX Text

COMMISSIONING AGENT

AutoCAD SHX Text

OUTSIDE DIAMETER

AutoCAD SHX Text

OD

AutoCAD SHX Text

BUILDING MANAGEMENT SYSTEM

AutoCAD SHX Text

OVERHEAD

AutoCAD SHX Text

OH

AutoCAD SHX Text

DECIBEL

AutoCAD SHX Text

OVERHEAD DOOR

AutoCAD SHX Text

OHD

AutoCAD SHX Text

DIRECT CURRENT

AutoCAD SHX Text

OVERLOAD

AutoCAD SHX Text

OL

AutoCAD SHX Text

DEMOLISH

AutoCAD SHX Text

PUBLIC ADDRESS

AutoCAD SHX Text

PA

AutoCAD SHX Text

DEMOLISH OR DEMOLITION

AutoCAD SHX Text

PULL BOX OR PUSHBUTTON

AutoCAD SHX Text

PB

AutoCAD SHX Text

DRINKING FOUNTAIN

AutoCAD SHX Text

POWER FACTOR CORRECTION

AutoCAD SHX Text

PFC

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

PH

AutoCAD SHX Text

DOUBLE POLE DOUBLE THROW

AutoCAD SHX Text

PANEL OR PANELBOARD

AutoCAD SHX Text

PNL

AutoCAD SHX Text

DOUBLE POLE SINGLE THROW

AutoCAD SHX Text

POTENTIAL TRANSFORMER

AutoCAD SHX Text

PT

AutoCAD SHX Text

ELECTRICAL CONTRACTOR

AutoCAD SHX Text

PAN-TILT-ZOOM

AutoCAD SHX Text

PTZ

AutoCAD SHX Text

EXPANSION JOINT

AutoCAD SHX Text

POWER

AutoCAD SHX Text

PWR

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

REFLECTED CEILING PLAN

AutoCAD SHX Text

RCP

AutoCAD SHX Text

ELEVATOR OR ELEVATION

AutoCAD SHX Text

REINFORCING BAR

AutoCAD SHX Text

REBAR

AutoCAD SHX Text

EMERGENCY

AutoCAD SHX Text

RECEPTACLE

AutoCAD SHX Text

RECEPT

AutoCAD SHX Text

ELECTRICAL METALLIC TUBING

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

RM

AutoCAD SHX Text

ENCLOSURE

AutoCAD SHX Text

RIGID NON-METALLIC CONDUIT

AutoCAD SHX Text

RNMC

AutoCAD SHX Text

EXISTING TO REMAIN

AutoCAD SHX Text

RIGHT-OF-WAY

AutoCAD SHX Text

ROW

AutoCAD SHX Text

ELECTRIC WATER COOLER

AutoCAD SHX Text

RIGID METALLIC CONDUIT

AutoCAD SHX Text

RMC

AutoCAD SHX Text

ELECTRIC WATER HEATER

AutoCAD SHX Text

SECONDARY

AutoCAD SHX Text

SEC

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

SINGLE POLE DOUBLE THROW

AutoCAD SHX Text

SPDT

AutoCAD SHX Text

FUSE OR FAHRENHEIT

AutoCAD SHX Text

SPECIFICATIONS

AutoCAD SHX Text

SPECS

AutoCAD SHX Text

FIRE ALARM

AutoCAD SHX Text

SINGLE POLE SINGLE THROW

AutoCAD SHX Text

SPST

AutoCAD SHX Text

FIRE ALARM ANNUNCIATOR PANEL

AutoCAD SHX Text

SQUARE

AutoCAD SHX Text

SQ

AutoCAD SHX Text

FIRE ALARM CONTROL PANEL

AutoCAD SHX Text

STAINLESS STEEL

AutoCAD SHX Text

SS

AutoCAD SHX Text

FIXTURES, FURNISHINGS & EQUIPMENT

AutoCAD SHX Text

SOLENOID VALVE

AutoCAD SHX Text

SV

AutoCAD SHX Text

FIXTURE

AutoCAD SHX Text

SWITCHBOARD

AutoCAD SHX Text

SWBD

AutoCAD SHX Text

FULL LOAD AMPERES

AutoCAD SHX Text

SWITCHGEAR

AutoCAD SHX Text

SWGR

AutoCAD SHX Text

FACTORY MUTUAL

AutoCAD SHX Text

TEMPERATURE CONTROLS CONTRACTOR

AutoCAD SHX Text

TCC

AutoCAD SHX Text

FLEXIBLE METAL CONDUIT

AutoCAD SHX Text

TEMPERATURE CONTROL PANEL

AutoCAD SHX Text

TCP

AutoCAD SHX Text

FIBER OPTIC

AutoCAD SHX Text

TRANSFORMER

AutoCAD SHX Text

TRANS

AutoCAD SHX Text

FIRE RETARDANT

AutoCAD SHX Text

TIME SWITCH

AutoCAD SHX Text

TS

AutoCAD SHX Text

GENERAL CONTRACTOR

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text

TYP

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

UNDERWRITERS LABORATORIES

AutoCAD SHX Text

UL

AutoCAD SHX Text

GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text

UNLESS NOTED OTHERWISE

AutoCAD SHX Text

UNO

AutoCAD SHX Text

GROUND FAULT INTERRUPTER

AutoCAD SHX Text

UNINTERRUPTIBLE POWER SUPPLY

AutoCAD SHX Text

UPS

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

VOLTS

AutoCAD SHX Text V

AutoCAD SHX Text

GYPSUM BOARD

AutoCAD SHX Text

VOLT-AMPERE

AutoCAD SHX Text

VA

AutoCAD SHX Text

HANDHOLE

AutoCAD SHX Text

VOLTS-ALTERNATING CURRENT

AutoCAD SHX Text

VAC

AutoCAD SHX Text

HAND-OFF-AUTO

AutoCAD SHX Text

VOLTS-DIRECT CURRENT

AutoCAD SHX Text

VDC

AutoCAD SHX Text

HORSE POWER

AutoCAD SHX Text

VARIABLE FREQUENCY DRIVE

AutoCAD SHX Text

VFD

AutoCAD SHX Text

HIGH VOLTAGE

AutoCAD SHX Text

WATTS

AutoCAD SHX Text W

AutoCAD SHX Text

INSIDE DIAMETER

AutoCAD SHX Text

WATER HEATER

AutoCAD SHX Text

WH

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text

WEATHERPROOF

AutoCAD SHX Text

WP

AutoCAD SHX Text

CM

AutoCAD SHX Text

CMU

AutoCAD SHX Text

COAX

AutoCAD SHX Text

CONC

AutoCAD SHX Text

CP

AutoCAD SHX Text

CT

AutoCAD SHX Text

CU

AutoCAD SHX Text Cx

AutoCAD SHX Text CxA

AutoCAD SHX Text

BMS

AutoCAD SHX Text

DB

AutoCAD SHX Text

DC

AutoCAD SHX Text

DEM

AutoCAD SHX Text

DEMO

AutoCAD SHX Text

DF

AutoCAD SHX Text

DISC

AutoCAD SHX Text

DPDT

AutoCAD SHX Text

DPST

AutoCAD SHX Text

EC

AutoCAD SHX Text

EJ

AutoCAD SHX Text

ELEC

AutoCAD SHX Text

ELEV

AutoCAD SHX Text

EM

AutoCAD SHX Text

EMT

AutoCAD SHX Text

ENCL

AutoCAD SHX Text

ETR

AutoCAD SHX Text

EWC

AutoCAD SHX Text

EWH

AutoCAD SHX Text

EXIST

AutoCAD SHX Text F

AutoCAD SHX Text

FA

AutoCAD SHX Text

FAAP

AutoCAD SHX Text

FACP

AutoCAD SHX Text

FF&E

AutoCAD SHX Text

FIXT

AutoCAD SHX Text

FLA

AutoCAD SHX Text

FM

AutoCAD SHX Text

FMC

AutoCAD SHX Text

FO

AutoCAD SHX Text

FRT

AutoCAD SHX Text

GC

AutoCAD SHX Text

GEN

AutoCAD SHX Text

GFCI

AutoCAD SHX Text

GFI

AutoCAD SHX Text

GND

AutoCAD SHX Text

GYP BD

AutoCAD SHX Text

HH

AutoCAD SHX Text

HOA

AutoCAD SHX Text

HP

AutoCAD SHX Text

ID

AutoCAD SHX Text

JB

AutoCAD SHX Text

HV

AutoCAD SHX Text

NATIONAL ELECTRICAL CODE

AutoCAD SHX Text

NEC

AutoCAD SHX Text

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

AutoCAD SHX Text

NEMA

AutoCAD SHX Text

SURGE PROTECTION DEVICE

AutoCAD SHX Text

SPD

AutoCAD SHX Text %%uNOTES

AutoCAD SHX Text

ELECTRICAL SYMBOL LEGEND

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

MANUFACTURER / CATALOG NO.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

GFI

AutoCAD SHX Text

WP

AutoCAD SHX Text

ZPX/Y

AutoCAD SHX Text X

AutoCAD SHX Text N

AutoCAD SHX Text X

AutoCAD SHX Text N

AutoCAD SHX Text 1.

AutoCAD SHX Text

DUPLEX RECEPTACLE

AutoCAD SHX Text

HUBBELL #HBL5362I

AutoCAD SHX Text

MOUNT AT 18" AFF; NOTE 1

AutoCAD SHX Text

GROUND FAULT INTERRUPTER

AutoCAD SHX Text

WEATHERPROOF WHILE-IN-USE DUPLEX RECEPTACLE

AutoCAD SHX Text

HUBBELL #GFR5362SGI

AutoCAD SHX Text

HUBBELL #GFR5362SGI WITH WP26EH

AutoCAD SHX Text

MOUNT AT 18" AFF, UNO; NOTE 1

AutoCAD SHX Text

MOUNT AT 18" ABOVE GRADE, UNO; NOTE 2

AutoCAD SHX Text

MOUNT AT 18" AFF, UNO; NOTE 1

AutoCAD SHX Text

NONFUSIBLE DISCONNECT SWITCH

AutoCAD SHX Text

FUSIBLE DISCONNECT SWITCH

AutoCAD SHX Text

MOTOR STARTER

AutoCAD SHX Text

COMBINATION MOTOR STARTER-DISCONNECT

AutoCAD SHX Text

SPECIAL CONNECTION AS NOTED

AutoCAD SHX Text

PANELBOARD (480Y/277V) (480V)

AutoCAD SHX Text

PANELBOARD (240/120V) OR (208Y/120V)

AutoCAD SHX Text

SINGLE PHASE MOTOR CONNECTION

AutoCAD SHX Text

THREE PHASE MOTOR CONNECTION

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text

CONDUIT UNDER FLOOR

AutoCAD SHX Text

CONDUIT ABOVE FLOOR

AutoCAD SHX Text

SURFACE OR RECESSED LUMINAIRE

AutoCAD SHX Text

WALL MOUNTED LUMINAIRE

AutoCAD SHX Text

SURFACE OR RECESSED FLUORESCENT LUMINAIRE

AutoCAD SHX Text

SEE SPECIFICATIONS

AutoCAD SHX Text

SEE SPECIFICATIONS

AutoCAD SHX Text

SEE SPECIFICATIONS

AutoCAD SHX Text

SEE SPECIFICATIONS

AutoCAD SHX Text

AutoCAD SHX Text

SEE PANELBOARD SCHEDULE

AutoCAD SHX Text

SEE PANELBOARD SCHEDULE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SEE SPECIFICATIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SEE LUMINAIRE SCHEDULE

AutoCAD SHX Text

SEE LUMINAIRE SCHEDULE

AutoCAD SHX Text

SEE LUMINAIRE SCHEDULE

AutoCAD SHX Text

SIZE AS NOTED

AutoCAD SHX Text Z=No. POLES; X=SWITCH SIZE; Y=FUSE SIZE; MOUNT AT 5'-0" AFF, UNO

AutoCAD SHX Text N=STARTER SIZE; X=STARTER TYPE, (RV: REDUCED VOLTAGE; BLANK: FULL VOLTAGE); MOUNT AT 5'-0" AFF, UNO

AutoCAD SHX Text N=STARTER SIZE; X=STARTER TYPE, (RV: REDUCED VOLTAGE; BLANK: FULL VOLTAGE); MOUNT AT 5'-0" AFF, UNO

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SITE LUMINAIRE AND POLE

AutoCAD SHX Text

SEE LUMINAIRE SCHEDULE

AutoCAD SHX Text

AutoCAD SHX Text

UNO = UNLESS NOTED OTHERWISE SSP = STAINLESS STEEL PLATE

AutoCAD SHX Text PART NUMBER SPECIFIED IS FOR DRY LOCATION ONLY. PROVIDE DEVICE RATED FOR THE ENVIRONMENT RECEPTACLE SHALL BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC.SHALL BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC. BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC.

AutoCAD SHX Text 2.

AutoCAD SHX Text

WIRING DEVICES - RECEPTACLE SCHEDULE

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

MANUFACTURE

AutoCAD SHX Text

CATALOG NO.

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DUPLEX RECEPTACLE

AutoCAD SHX Text

HUBBELL

AutoCAD SHX Text

HBL5362I

AutoCAD SHX Text

MOUNT AT 18" AFF, UNO

AutoCAD SHX Text

GFCI DUPLEX RECEPTACLE

AutoCAD SHX Text

HUBBELL

AutoCAD SHX Text

MOUNT AT 18" AFF, UNO

AutoCAD SHX Text WEATHERPROOF, GFCI DUPLEX RECEPTACLE WITH WEATHERPROOF WHILE-IN-USE, EXTRA DUTY COVER

AutoCAD SHX Text

HUBBELL

AutoCAD SHX Text

MOUNT AT 36" AFF, UNO

AutoCAD SHX Text

GFR5362SGI

AutoCAD SHX Text

GFR5362SGI, WP26EH

AutoCAD SHX Text

GFI

AutoCAD SHX Text

WP

AutoCAD SHX Text

1. FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT OF WORK AND INCLUDE ALL COSTS ASSOCIATED WITH DEMOLITION IN BASE BID. 2. COORDINATE DEMOLITION WORK WITH OTHER TRADES. COORDINATE DEMOLITION WORK WITH OTHER TRADES. DISCONNECT AND REMOVE ALL CONDUIT, WIRING, AND DEVICES ASSOCIATED WITH EQUIPMENT BEING REMOVED. EXPOSED CONDUIT AND DEVICES SHALL BE DISCONNECTED AND REMOVED; CONCEALED CONDUIT CAN BE ABANDONED IN PLACE. ALL WIRING SHALL BE COMPLETELY REMOVED BACK TO ITS SOURCE.

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E002

TCD

TCD

JAC

KEY NOTES

SANITATION STATION

ELECTRICAL SITE PLAN

AutoCAD SHX Text

GENERATOR

AutoCAD SHX Text

UTILITY TRANSFORMER PAN

AutoCAD SHX Text

PUMP CONTROL PANEL CIRCUIT BREAKER

AutoCAD SHX Text

MIXER MOTOR STARTERS (FUTURE)

AutoCAD SHX Text

ATS

AutoCAD SHX Text

MCB

AutoCAD SHX Text

UTILITY METER

AutoCAD SHX Text

120V CIRCUITS (SEPARATE CONDUITS FOR BLOCK HEATER, BATTERY CHARGER, ETC.)

AutoCAD SHX Text

PUMP CONTROL PANEL

AutoCAD SHX Text

MIXER TERMINATION BOX (FUTURE)

AutoCAD SHX Text

MIXER TERMINATION BOX (FUTURE)

AutoCAD SHX Text V-2

AutoCAD SHX Text V-4

AutoCAD SHX Text

MX-1 (FUTURE)

AutoCAD SHX Text

BL-1

AutoCAD SHX Text

COORDINATE CONDUIT STUB-UP LOCATION WITH BLOWER ENCLOSURE

AutoCAD SHX Text P-1

AutoCAD SHX Text P-2

AutoCAD SHX Text

LE-3 LSH-3 LSL-3

AutoCAD SHX Text

MX-2 (FUTURE)

AutoCAD SHX Text

PUMP/LEVEL TERMINATION BOX

AutoCAD SHX Text V-5

AutoCAD SHX Text

VALVE VAULT

AutoCAD SHX Text

FE-1

AutoCAD SHX Text

FLOW METER MANHOLE

AutoCAD SHX Text V-1

AutoCAD SHX Text V-3

AutoCAD SHX Text

MANHOLE (MH-1)

AutoCAD SHX Text

MANHOLE (MH-2)

AutoCAD SHX Text

GENERATOR PAD

AutoCAD SHX Text

UTILITY TRANSFORMER

AutoCAD SHX Text

EQUIPMENT PANEL

AutoCAD SHX Text

GENERATOR REMOTE E-STOP PUSHBUTTON

AutoCAD SHX Text

1. UTILITY TRANSFORMER PROVIDED BY CONSUMERS ENERGY; UTILITY TRANSFORMER PROVIDED BY CONSUMERS ENERGY; PROVIDE CONCRETE PAD, SEE DETAIL ON SHEET E603. 2. INSTALL A 5" PVC CONDUIT WITH NYLON PULL CORD FOR INSTALL A 5" PVC CONDUIT WITH NYLON PULL CORD FOR USE BY CONSUMERS ENERGY FOR INSTALLATION OF PRIMARY CABLING (COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH CONSUMERS ENERGY). 3. BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC PROVIDE GENERATOR AND AUTOMATIC TRANSFER SWITCH (ATS). 4. PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL TRANSFER SWITCH (MTS) IF BID ALTERNATE NO. 2 IS NOT PROVIDED.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1" = 30'

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E003

TCD

TCD

JAC

KEY NOTES

WEST RESTROOM BUILDING

ELECTRICAL SITE PLAN

AutoCAD SHX Text

3" WTR.

AutoCAD SHX Text

2" WTR.

AutoCAD SHX Text

WEST RESTROOM BUILDING

AutoCAD SHX Text

EXISTING WEST CAMPGROUND POWER DISTRIBUTION PANEL (WC-PDP)

AutoCAD SHX Text

EXISTING UTILITY TRANSFORMER

AutoCAD SHX Text

EQUIPMENT PAD

AutoCAD SHX Text

3#3,#8G,1-1/4"C FOR POWER

AutoCAD SHX Text

EXISTING SEPTIC TANKS 2-3000 GALLON

AutoCAD SHX Text

NEW PUMP STATION WET WELL

AutoCAD SHX Text

NEW PUMP STATION VALVE VAULT

AutoCAD SHX Text

CONTROL PANEL (CP-WRPS)

AutoCAD SHX Text

1. PROVIDE 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE PROVIDE 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE LABELED 6 IN EXISTING PANEL WC-PDP. MATCH EXISTING CIRCUIT BREAKER MANUFACTURE, TYPE, AND INTERRUPT RATING.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1" = 10'

AutoCAD SHX Text

NORTH

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E004

TCD

TCD

JAC

EAST RESTROOM BUILDING

ELECTRICAL SITE PLAN

KEY NOTES

AutoCAD SHX Text

2" WTR.

AutoCAD SHX Text

UG ELEC

AutoCAD SHX Text

EAST RESTROOM BUILDING

AutoCAD SHX Text

EXISTING EAST CAMPGROUND POWER DISTRIBUTION PANEL (EC-PDP)

AutoCAD SHX Text

EXISTING UTILITY TRANSFORMER

AutoCAD SHX Text

EXISTING SEPTIC TANK 1,000 GALLONS

AutoCAD SHX Text

EXISTING SEPTIC TANK 3,200 GALLONS

AutoCAD SHX Text

EXISTING SEPTIC TANK 3,200 GALLONS

AutoCAD SHX Text

NEW PUMP STATION VALVE VAULT

AutoCAD SHX Text

NEW PUMP STATION WET WELL

AutoCAD SHX Text

REMOVE EXISTING CONTROL PANEL (CP-ERPS)

AutoCAD SHX Text

3#3,#8G,1-1/4"C FOR POWER

AutoCAD SHX Text

NEW CONTROL PANEL (CP-ERPS)

AutoCAD SHX Text

EQUIPMENT PAD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1" = 10'

AutoCAD SHX Text

NORTH

AutoCAD SHX Text

1. WIRE TO EXISTING 2-POLE 150AF, 100AT CIRCUIT BREAKER WIRE TO EXISTING 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE LABELED 12 IN EXISTING PANEL EC-PDP.

AutoCAD SHX Text

INPUT/OUTPUT LIST AND WIRING SCHEDULE

DESCRIPTION I/O TYPE

DESTINATION WIRING

CONDUIT

SIZE

SIGNAL

TYPE

REMARKS

FROM TO #16TSP #14 #12

CP-EQPS

VAVLE CV-1 IN REMOTE DI VALVE CV-1 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL

VALVE CV-1 OPENED DI VALVE CV-1

CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE CV-1 CLOSED DI VALVE CV-1 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE CV-1 OPEN DO VALVE CV-1 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE CV-1 CLOSED DO VALVE CV-1

CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

VAVLE V-1 IN REMOTE DI VALVE V-1 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL

VALVE V-1 OPENED DI VALVE V-1 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-1 CLOSED DI VALVE V-1 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-1 OPEN DO VALVE V-1

CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-1 CLOSED DO VALVE V-1 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VAVLE V-2 IN REMOTE DI VALVE V-2 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL

VALVE V-2 OPENED DI VALVE V-2

CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-2 CLOSED DI VALVE V-2 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-2 OPEN DO VALVE V-2 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-2 CLOSED DO VALVE V-2 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VAVLE V-3 IN REMOTE DI VALVE V-3 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL

VALVE V-3 OPENED DI VALVE V-3 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-3 CLOSED DI VALVE V-3 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-3 OPEN DO VALVE V-3 CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-3 CLOSED DO VALVE V-3 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VAVLE V-4 IN REMOTE DI VALVE V-4 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL

VALVE V-4 OPENED DI VALVE V-4

CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-4 CLOSED DI VALVE V-4 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-4 OPEN DO VALVE V-4 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

VALVE V-4 CLOSED DO VALVE V-4 CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

GENERATOR ALARM DI STANDBY GENERATOR

CP-EQPS

- 4 - 3/4" 120 VAC -

GENERATOR RUNNING DI STANDBY GENERATOR CP-EQPS - - - - 120 VAC

COMBINE SIMILAR SIGNALS

ATS ON GENERATOR DI ATS CP-EQPS - 4 - 3/4" 120 VAC -

ATS ON NORMAL DI ATS

CP-EQPS

- - - - 120 VAC

COMBINE SIMILAR SIGNALS

EQ TANK FLOW - FE-1 FIT-1 - - - 3/4" - MAUFACTURES CABLE

EQ TANK FLOW AI FIT-1 CP-EQPS 1 - - 3/4" 4-20mA 120VAC FOR TRANSMITTER FROM CONTROL PANEL

EQ TANK LEVEL AI LT-3 CP-EQPS 1 - - 3/4" 4-20mA MAUFACTURES CABLE

EQ TANK LOW LEVEL (FLOAT)

DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

EQ TANK HIGH LEVEL (FLOAT)

DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-1 RUNNING DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-1 IN REMOTE DI - 2 - - 120 VAC

WIRING INTERNAL TO CP-EQPS

PUMP P-1 VFD FAULT DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-1 START/STOP CALL DO - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-1 VFD SPEED CONTROL AO 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS

PUMP P-1 VFD SPEED FEEDBACK AI 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS

PUMP P-1 HIGH TEMPERATURE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-1 SEAL LEAK DETECTED DI 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-2 RUNNING DI - 2 - - 120 VAC

WIRING INTERNAL TO CP-EQPS

PUMP P-2 IN REMOTE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-2 VFD FAULT DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-2 START/STOP CALL DO - 2 - - 120 VAC

WIRING INTERNAL TO CP-EQPS

PUMP P-2 VFD SPEED CONTROL AO 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS

PUMP P-2 VFD SPEED FEEDBACK AI 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS

PUMP P-2 HIGH TEMPERATURE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

PUMP P-2 SEAL LEAK DETECTED DI - 2 - - 120 VAC

WIRING INTERNAL TO CP-EQPS

CONTROL PANELPOWER ON DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

SURGE PROTECTIVE DEVICE (SPD) FAULT

DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

UPS FAULT DI - 2 - - 120 VAC

WIRING INTERNAL TO CP-EQPS

UPS LOW BATTERY DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS

Reviewer

Designer

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E401

TCD

TCD

JAC

GENERAL NOTES

CONTROL PANEL CP-EQPS RISER DIAGRAM

KEY NOTES

CONTROL PANEL CP-EQPS ONE LINE DIAGRAM

EQ TANK PUMP STATION ONE LINE DIAGRAM

AutoCAD SHX Text

1. COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL SERVICE. 2. THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA 4X STAINLESS STEEL ENCLOSURE; SURGE PROTECTIVE DEVICE; 1 POWER; LOAD CENTER FOR DISTRIBUTING POWER;POWER SUPPLIES; INTERIOR LIGHT (INTERLOCKED WITH PANEL DOOR); THERMOSTATICALLY CONTROLLED ANTI-CONDENSATION HEATER; VENTILATION FAN, ETC. 3. EQ TANK PUMP STATION CONTROL PANEL SHALL INCLUDE AN EQ TANK PUMP STATION CONTROL PANEL SHALL INCLUDE AN INTEGRAL SURGE PROTECTIVE DEVICE (SPD). SPD SHALL PROVIDE L-N, L-G, L-L, AND N-G PROTECTION.

AutoCAD SHX Text

EQ TANK PUMP STATION CONTROL PANEL (CP-EQPS)

AutoCAD SHX Text

EQ TANK

AutoCAD SHX Text

AutoCAD SHX Text

MFR'S CABLE, 3/4"C

AutoCAD SHX Text

AutoCAD SHX Text

FLOAT SWITCH CABLE

AutoCAD SHX Text

PUMP/LEVEL TERMINATION BOX

AutoCAD SHX Text 2"C

AutoCAD SHX Text

LSH-3

AutoCAD SHX Text

LSL-3

AutoCAD SHX Text 3/4"C

AutoCAD SHX Text

LEVEL TRANSDUCER

AutoCAD SHX Text

AutoCAD SHX Text

PUMP POWER; SEE ONE LINE DIAGRAM

AutoCAD SHX Text 2"C

AutoCAD SHX Text

AutoCAD SHX Text

ALARM LIGHT

AutoCAD SHX Text 3/4"C

AutoCAD SHX Text

AutoCAD SHX Text

LE-3

AutoCAD SHX Text P-2

AutoCAD SHX Text P-1

AutoCAD SHX Text

3-250 KCMIL,#4G,3"C

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

1. SEE PUMP CONTROL PANEL WIRING DIAGRAM ON SHEET SEE PUMP CONTROL PANEL WIRING DIAGRAM ON SHEET E601. 2. COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH LEVEL PROBE MANUFACTURER. 3. CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% MAXIMUM CONDUCTOR FILL PERMITTED BY NEC FOR CONDUIT SEALS. CONTRACTOR SHALL ADJUST CONDUIT SIZES BASED ON ACTUAL CABLE SIZE. 4. PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. 5. SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS 80kA/PHASE. 6. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. 7. HIGH TEMP AND SEAL LEAK SENSOR WIRING RUNS VIA PUMP HIGH TEMP AND SEAL LEAK SENSOR WIRING RUNS VIA PUMP CABLE; SPLICE WIRING IN PUMP/LEVEL TERMINATION BOX AT WET WELL AND PROVIDE 4#14 IN 3/4" CONDUIT FROM PUMP/LEVEL TERMINATION BOX TO PUMP CONTROL PANEL. 8. FLOAT SWITCH WIRING RUNS VIA FLOAT SWITCH CABLE; FLOAT SWITCH WIRING RUNS VIA FLOAT SWITCH CABLE; SPLICE WIRING IN PUMP/LEVEL TERMINATION BOX AT WET WELL AND PROVIDE 2#14 (FOR EACH FLOAT SWITCH) IN 3/4" CONDUIT FROM PUMP/LEVEL TERMINATION BOX TO PUMP CONTROL PANEL. 9. PUMP CONTROL PANEL SHALL BE UL LABELED FOR PUMP CONTROL PANEL SHALL BE UL LABELED FOR AVAILABLE FAULT CURRENT. 10. CIRCUIT BREAKER AND LOAD CENTER TO BE SIZED BY CIRCUIT BREAKER AND LOAD CENTER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS. PROVIDE WIRING AND BRANCH CIRCUIT BREAKERS SIZED IN ACCORDANCE WITH NEC. 11. LOCATION OF PUMP/LEVEL TERMINATION BOX AND CONDUIT LOCATION OF PUMP/LEVEL TERMINATION BOX AND CONDUIT RUNS TO BE FINALIZED AT TIME OF INSTALLATION. 12. PROVIDE 2" CONDUIT FROM ATS TO GENERATOR CONTROL PROVIDE 2" CONDUIT FROM ATS TO GENERATOR CONTROL PANEL. PROVIDE GENERATOR START-STOP AND STATUS CABLING. 13. PROVIDE 4#12,#12G IN 1" CONDUIT FROM PUMP CONTROL PROVIDE 4#12,#12G IN 1" CONDUIT FROM PUMP CONTROL PANEL TO GENERATOR CONTROL PANEL FOR POWER FOR GENERATOR BLOCK HEATER AND BATTERY CHARGER. TERMINATE WIRING IN PANELS AS INDICATED ON THE MANUFACTURER'S WIRING SCHEMATICS. 14. BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC : PROVIDE GENERATOR AND AUTOMATIC TRANSFER SWITCH (ATS). 15. PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL TRANSFER SWITCH (MTS) IF BID ALTERNATE NO. 2 IS NOT PROVIDED.

AutoCAD SHX Text

AutoCAD SHX Text

TO WIREWAY

AutoCAD SHX Text

EQ TANK METER VAULT

AutoCAD SHX Text

MFR'S CABLES, 1"C

AutoCAD SHX Text

FE-1

AutoCAD SHX Text

(COORDINATE WIRING)

AutoCAD SHX Text

SEAL OFF FITTING (TYP.)

AutoCAD SHX Text

CP-EQPS 10K AIC RATING NEMA 4X, 316 SS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-1

AutoCAD SHX Text

12 HP

AutoCAD SHX Text

32.0 FLA (3 )

AutoCAD SHX Text

55.4 FLA (1 )

AutoCAD SHX Text 3#3,#8G,1-1/4"C

AutoCAD SHX Text 2P200

AutoCAD SHX Text

CB

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LINE

AutoCAD SHX Text

PUMP CABLE (TYPICAL)

AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE SUSPENDED CABLE DETAIL, ON SHEET E604 (TYPICAL)

AutoCAD SHX Text

PUMP/LEVEL TERMINATION BOX

AutoCAD SHX Text

CB

AutoCAD SHX Text

CP-ESPS

AutoCAD SHX Text

CB

AutoCAD SHX Text

LINE

AutoCAD SHX Text

VFD

AutoCAD SHX Text

VFD

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

MCP

AutoCAD SHX Text

MCP

AutoCAD SHX Text 2P200

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

MX-2

AutoCAD SHX Text

2 HP

AutoCAD SHX Text

12.0 FLA (1 )

AutoCAD SHX Text

MX-1

AutoCAD SHX Text

2 HP

AutoCAD SHX Text

12.0 FLA (1 )

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text

AUTOMATIC TRANSFER SWITCH - 2 POLE 400A 120/240V-1 NEMA 3R

AutoCAD SHX Text

STANDBY GENERATOR 100 KW DIESEL 120/240V-1 -3W

AutoCAD SHX Text

3-350 KCMIL,#4G,3"C

AutoCAD SHX Text

3-350 KCMIL,#4G,3"C

AutoCAD SHX Text 2P300

AutoCAD SHX Text

MAIN CIRCUIT BREAKER (SERVICE ENTRANCE RATED)

AutoCAD SHX Text

3-350 KCMIL,3"C

AutoCAD SHX Text

NEMA 4X (316SS)

AutoCAD SHX Text P

AutoCAD SHX Text B

AutoCAD SHX Text P

AutoCAD SHX Text B

AutoCAD SHX Text

SEAL-OFF FITTING (TYPICAL)

AutoCAD SHX Text

PUMP CABLE (TYPICAL)

AutoCAD SHX Text

PULL BOX (TYPICAL)

AutoCAD SHX Text

TO NEW UTILITY TRANSFORMER 120/240V-1 -3W

AutoCAD SHX Text M

AutoCAD SHX Text

NEW UTILITY METER

AutoCAD SHX Text

3-350 KCMIL,#4G,3"C

AutoCAD SHX Text

3-250 KCMIL,#4G,3"C

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

120/240V-1 -3WFROM WIREWAY

AutoCAD SHX Text

3-250 KCMIL,#4G,3"C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

POWER DISTRIBUTION BLOCKS (TYPICAL)

AutoCAD SHX Text

WIREWAY NEMA 4X (316 SS)

AutoCAD SHX Text

TO CONTROL CIRCUIT

AutoCAD SHX Text 2#10,#10G,3/4"C

AutoCAD SHX Text 2P300

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text 2#12,#12G,10#14,1"C

AutoCAD SHX Text

TO VALVE V-5

AutoCAD SHX Text

TO VALVE V-4

AutoCAD SHX Text 2#12,#12G,10#14,1"C

AutoCAD SHX Text

TO VALVE V-3

AutoCAD SHX Text 2#12,#12G,10#14,1"C

AutoCAD SHX Text

TO VALVE V-2

AutoCAD SHX Text 2#12,#12G,10#14,1"C

AutoCAD SHX Text

TO BLOWER BL-1

AutoCAD SHX Text 2#12,#12G,3/4"C

AutoCAD SHX Text

TO GENERATOR

AutoCAD SHX Text 4#12,2#12G,1"C

AutoCAD SHX Text P-2

AutoCAD SHX Text

12 HP

AutoCAD SHX Text

32.0 FLA (3 )

AutoCAD SHX Text

55.4 FLA (1 )

AutoCAD SHX Text

TO VALVE V-1

AutoCAD SHX Text 2#12,#12G,10#14,1"C

AutoCAD SHX Text

NEMA 4X (316 SS)

AutoCAD SHX Text

NEMA 4X (316 SS)

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

NEMA 4X (316 SS)

AutoCAD SHX Text

(FUTURE)

AutoCAD SHX Text

(FUTURE)

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E402

TCD

TCD

JAC

GENERAL NOTES

KEY NOTES

EAST RESTROOM BUILDING

PUMP STATION RISER DIAGRAM

WEST RESTROOM BUILDING

PUMP STATION RISER DIAGRAM

EAST RESTROOM BUILDING

PUMP STATION ONE LINE DIAGRAM

WEST RESTROOM BUILDING

PUMP STATION ONE LINE DIAGRAM

AutoCAD SHX Text

1. THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA 4X STAINLESS STEEL ENCLOSURE; SURGE PROTECTIVE DEVICE; LOAD CENTER FOR DISTRIBUTING POWER; POWER SUPPLIES; INTERIOR LIGHT (INTERLOCKED WITH PANEL DOOR); THERMOSTATICALLY CONTROLLED ANTI-CONDENSATION HEATER; VENTILATION FAN, ETC. 2. FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT OF WORK AND INCLUDE ALL COSTS ASSOCIATED WITH DEMOLITION IN BASE BID. 3. COORDINATE DEMOLITION WORK WITH OTHER TRADES. COORDINATE DEMOLITION WORK WITH OTHER TRADES. DISCONNECT AND REMOVE ALL CONDUIT, WIRING, AND DEVICES ASSOCIATED WITH EQUIPMENT BEING REMOVED. EXPOSED CONDUIT AND DEVICES SHALL BE DISCONNECTED AND REMOVED; CONCEALED CONDUIT CAN BE ABANDONED IN PLACE. ALL WIRING SHALL BE COMPLETELY REMOVED BACK TO ITS SOURCE. 4. PUMP STATION CONTROL PANEL SHALL INCLUDE AN PUMP STATION CONTROL PANEL SHALL INCLUDE AN INTEGRAL SURGE PROTECTIVE DEVICE (SPD). SPD SHALL PROVIDE L-N, L-G, L-L, AND N-G PROTECTION.

AutoCAD SHX Text

1. COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH LEVEL PROBE MANUFACTURER. 2. CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% MAXIMUM CONDUCTOR FILL PERMITTED BY NEC FOR CONDUIT SEALS. CONTRACTOR SHALL ADJUST CONDUIT SIZES BASED ON ACTUAL CABLE SIZE. 3. PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. 4. SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS 80kA/PHASE. 5. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. 6. PUMP CONTROL PANEL SHALL BE UL LABELED FOR PUMP CONTROL PANEL SHALL BE UL LABELED FOR AVAILABLE FAULT CURRENT.

AutoCAD SHX Text

AutoCAD SHX Text

NEW 120/240V-1PH-3W FROM PDP-WC CIRCUIT 6

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text

CB

AutoCAD SHX Text

AutoCAD SHX Text

SEAL-OFF FITTING (TYPICAL)

AutoCAD SHX Text

PUMP CABLE (TYPICAL)

AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE CONDUIT SEAL-OFF AND SUSPENDED CABLE DETAIL, ON SHEET E602 (TYPICAL)

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text

CP-ERPS 10K AIC RATING NEMA 4X, 316 SS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text P-5

AutoCAD SHX Text

5 HP

AutoCAD SHX Text

15.2 FLA (3 )

AutoCAD SHX Text

26.3 FLA (1 )

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text

CB

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SEAL-OFF FITTING (TYPICAL)

AutoCAD SHX Text

PUMP CABLE (TYPICAL)

AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE CONDUIT SEAL-OFF AND SUSPENDED CABLE DETAIL, ON SHEET E602 (TYPICAL)

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text

CB

AutoCAD SHX Text

TO CONTROL CIRCUIT

AutoCAD SHX Text

CB

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text 3#3,#8G,1-1/4"C

AutoCAD SHX Text

EAST RESTROOM BUILDING PUMP STATION CONTROL PANEL (CP-ERPS)

AutoCAD SHX Text

AutoCAD SHX Text

ALARM LIGHT

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

PUMP STATION WETWELL

AutoCAD SHX Text

AutoCAD SHX Text

FLOAT SWITCH CABLE

AutoCAD SHX Text

LSH-1

AutoCAD SHX Text

LSL-1

AutoCAD SHX Text

LEVEL TRANSDUCER

AutoCAD SHX Text

SEAL OFF FITTING (TYP.)

AutoCAD SHX Text

ALARM LIGHT

AutoCAD SHX Text

LE-1

AutoCAD SHX Text P-6

AutoCAD SHX Text P-5

AutoCAD SHX Text

TO PDP-WC CIRCUIT 6

AutoCAD SHX Text

MFR'S CABLES, 3/4"C

AutoCAD SHX Text

MFR'S CABLE, 3/4"C

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text 3#3,#8G,1-1/4"C

AutoCAD SHX Text

PUMP STATION WETWELL

AutoCAD SHX Text

AutoCAD SHX Text

FLOAT SWITCH CABLE

AutoCAD SHX Text

LSH-2

AutoCAD SHX Text

LSL-2

AutoCAD SHX Text

LEVEL TRANSDUCER

AutoCAD SHX Text

SEAL OFF FITTING (TYP.)

AutoCAD SHX Text

LE-2

AutoCAD SHX Text P-4

AutoCAD SHX Text P-3

AutoCAD SHX Text

MFR'S CABLES, 3/4"C

AutoCAD SHX Text

MFR'S CABLE, 3/4"C

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text

PUMP CABLE, 1"C

AutoCAD SHX Text

CP-WRPS 10K AIC RATING NEMA 4X, 316 SS

AutoCAD SHX Text

WEST RESTROOM BUILDING PUMP STATION CONTROL PANEL (CP-WRPS)

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

EXISTING 120/240V-1PH-3W FROM PDP-EC CIRCUIT 12

AutoCAD SHX Text 3#3,#8G,1-1/4"C

AutoCAD SHX Text

TO PDP-EC CIRCUIT 12

AutoCAD SHX Text 3#3,#8G,1-1/4"C

AutoCAD SHX Text

LINE

AutoCAD SHX Text

VFD

AutoCAD SHX Text

LINE

AutoCAD SHX Text

VFD

AutoCAD SHX Text

SPD

AutoCAD SHX Text

AutoCAD SHX Text

TO CONTROL CIRCUIT

AutoCAD SHX Text

LINE

AutoCAD SHX Text

VFD

AutoCAD SHX Text

LINE

AutoCAD SHX Text

VFD

AutoCAD SHX Text P-6

AutoCAD SHX Text

5 HP

AutoCAD SHX Text

15.2 FLA (3 )

AutoCAD SHX Text

26.3 FLA (1 )

AutoCAD SHX Text P-3

AutoCAD SHX Text

5 HP

AutoCAD SHX Text

15.2 FLA (3 )

AutoCAD SHX Text

26.3 FLA (1 )

AutoCAD SHX Text P-4

AutoCAD SHX Text

5 HP

AutoCAD SHX Text

15.2 FLA (3 )

26.3 FLA (1 )

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E601

TCD

TCD

JAC

GENERAL NOTES

SUBMERSIBLE PUMP P-1 VFD WIRING DIAGRAM

EQ TANK PUMP STATION CONTROL PANEL WIRING DIAGRAM

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text THE FOLLOWING DEVICES SHALL BE PROVIDED IN THE PUMP CONTROL PANEL BUT ARE NOT SHOWN FOR CLARITY: 120VAC TRANSIENT VOLTAGE SURGE SUPPRESSER, 24VDC POWER SUPPLIES, INTRINSICALLY SAFE BARRIERS, GFI CONVENIENCE RECEPTACLE, INTERIOR LIGHT, COOLING FAN, CONDENSATE HEATER, THERMOSTAT(S) AND OTHER DEVICES LISTED IN THE SPEC. DRY CONTACTS FOR THE FOLLOWING SIGNALS SHALL BE WIRED TO A TERMINAL STRIP TO INTERFACE WITH THE SCADA MISSION RTU. ALARMS: EQ TANK LOW LEVEL (CR1) [DISCRETE] EQ TANK HIGH LEVEL (CR2) [DISCRETE] PUMP P-1 VFD FAULT (CRF) [DISCRETE] PUMP P-1 HIGH TEMP SHUTDOWN (CR4) [DISCRETE] PUMP P-1 SEAL LEAK DETECTED (CR5) [DISCRETE] PUMP P-2 VFD FAULT (CRF) [DISCRETE] PUMP P-2 HIGH TEMP SHUTDOWN (CR6) [DISCRETE] PUMP P-2 SEAL LEAK DETECTED (CR7) [DISCRETE STATUS: PUMP P-1 RUN STATUS (CRR) [DISCRETE] PUMP P-2 RUN STATUS (CRR) [DISCRETE] SPD STATUS [DISCRETE] ALL WIRING TO/FROM THIS PANEL AND OTHER ENCLOSURES/EQUIPMENT SHALL BE INSTALLED IN CONDUIT. MINIMUM CONDUCTOR SIZE FOR POWER IS #12, FOR CONTROL IS #14. CIRCUIT BREAKER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS INCLUDED IN SUBMERSIBLE PUMP CONTROL PACKAGE. PROVIDE WIRING AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH NEC. CIRCUIT BREAKER AND FUSE SIZES SHALL BE DETERMINED BY CONTROL PANEL FABRICATOR. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CONTROL POWER ON

AutoCAD SHX Text

LOW LEVEL FLOAT SWITCH LSL-3

AutoCAD SHX Text

ISR-1

AutoCAD SHX Text

HIGH LEVEL FLOAT SWITCH LSH-3

AutoCAD SHX Text

ISR-2

AutoCAD SHX Text

CR1

AutoCAD SHX Text

ISR-1

AutoCAD SHX Text

INTRINSICALLY SAFE RELAY (TYPICAL)

AutoCAD SHX Text

CR2

AutoCAD SHX Text

ISR-2

AutoCAD SHX Text

CR3

AutoCAD SHX Text

CR1

AutoCAD SHX Text

CR2

AutoCAD SHX Text

CR3

AutoCAD SHX Text

EQ TANK LOW LEVEL

AutoCAD SHX Text

EQ TANK HIGH LEVEL

AutoCAD SHX Text

OVERRIDE PUMP CONTROL

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR4

AutoCAD SHX Text

CR5

AutoCAD SHX Text

PUMP P-1 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-1 SEAL LEAK DETECTED

AutoCAD SHX Text

PUMP P-1 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-1 SEAL LEAK DETECTED

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR6

AutoCAD SHX Text

CR7

AutoCAD SHX Text

PUMP P-2 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-2 SEAL LEAK DETECTED

AutoCAD SHX Text

PUMP P-2 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-2 SEAL LEAK DETECTED

AutoCAD SHX Text

CONTACTS SHOWN IN ALARM STATE

AutoCAD SHX Text

CONTACT SHOWN IN NORMAL STATE

AutoCAD SHX Text

P-1 HIGH TEMP AND SEAL LEAK SENSORS

AutoCAD SHX Text

P-2 HIGH TEMP AND SEAL LEAK SENSORS

AutoCAD SHX Text

P-1 HIGH TEMP AND SEAL LEAK RELAY

AutoCAD SHX Text

P-2 HIGH TEMP AND SEAL LEAK RELAY

AutoCAD SHX Text

(CONTINUES ABOVE)

AutoCAD SHX Text

(CONTINUED FROM BELOW)

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

COMPACTLOGIX PLC

AutoCAD SHX Text WET WELL LEVEL FROM LEVEL TRANSDUCER (LE-3) (#16TSP,3/4"C; 4-20mA)

AutoCAD SHX Text

CR9

AutoCAD SHX Text

CR9

AutoCAD SHX Text

CR2

AutoCAD SHX Text

CR8

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR1

AutoCAD SHX Text

CR8

AutoCAD SHX Text

WET WELL LOW LEVEL

AutoCAD SHX Text

WET WELL HIGH LEVEL

AutoCAD SHX Text

ALARM BEACON

AutoCAD SHX Text R

AutoCAD SHX Text

CR10

AutoCAD SHX Text

TEST

AutoCAD SHX Text

CR8

AutoCAD SHX Text

CR9

AutoCAD SHX Text

CR10

AutoCAD SHX Text

CRF (FROM P-1 VFD)

AutoCAD SHX Text

CRF (FROM P-2 VFD)

AutoCAD SHX Text SPEED CONTROL LOOPED TO VFDs (#16TSP, 4-20mA)

AutoCAD SHX Text

PLC-AUTO (TO P-1 VFD)

AutoCAD SHX Text

CR5 (TO P-2 VFD)

AutoCAD SHX Text

(TYPICAL FOR P-2)

AutoCAD SHX Text

CR10

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

PLC-AUTO (TO P-2 VFD)

AutoCAD SHX Text

CR1 (TO PLC)

AutoCAD SHX Text

CR2 (TO PLC)

AutoCAD SHX Text

CR3 (TO P-1 VFD)

AutoCAD SHX Text

CR4 (TO P-1 VFD)

AutoCAD SHX Text

CR6 (TO P-1 VFD)

AutoCAD SHX Text

CB

AutoCAD SHX Text

UPS

AutoCAD SHX Text W

AutoCAD SHX Text

CRP

AutoCAD SHX Text

CRP (TO PLC)

AutoCAD SHX Text

CONTROL POWER ON

AutoCAD SHX Text

CR5 (TO PLC)

AutoCAD SHX Text

CR4 (TO PLC)

AutoCAD SHX Text

CR7 (TO PLC)

AutoCAD SHX Text

CR6 (TO PLC)

AutoCAD SHX Text

SPD FAILURE (TO PLC)

AutoCAD SHX Text

UPS FAULT (TO PLC)

AutoCAD SHX Text

UPS LOW BATTERY (TO PLC)

AutoCAD SHX Text

CB

AutoCAD SHX Text

DS

AutoCAD SHX Text

CONTROL PANEL LIGHT

AutoCAD SHX Text

LED

AutoCAD SHX Text

PANELVIEW PLUS

AutoCAD SHX Text

PANELVIEW PLUS

AutoCAD SHX Text

CB

AutoCAD SHX Text

ENCLOSURE AIR CIRCULATION FAN

AutoCAD SHX Text

TS

AutoCAD SHX Text

CB

AutoCAD SHX Text

TS

AutoCAD SHX Text

ENCLOSURE HEATER

AutoCAD SHX Text

GFCI DUPLEX RECEPTACLE

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

MISSION RTU

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

CR2

AutoCAD SHX Text

CR1

AutoCAD SHX Text

AutoCAD SHX Text C

AutoCAD SHX Text

CRF

AutoCAD SHX Text

AutoCAD SHX Text

HIGH LEVEL

AutoCAD SHX Text

LOW LEVEL

AutoCAD SHX Text

PUMP 1 TROUBLE

AutoCAD SHX Text

PUMP 2 TROUBLE

AutoCAD SHX Text

CR4

AutoCAD SHX Text

CR5

AutoCAD SHX Text C

AutoCAD SHX Text

CRF

AutoCAD SHX Text

CR6

AutoCAD SHX Text

CR7

AutoCAD SHX Text

24 VDC POWER SUPPLY

AutoCAD SHX Text

CB

AutoCAD SHX Text

CR7 (TO P-2 VFD)

AutoCAD SHX Text

CR1 (TO RTU)

AutoCAD SHX Text

CR2 (TO RTU)

AutoCAD SHX Text

SPD FAILURE (TO RTU)

AutoCAD SHX Text

PUMP P-2 SEAL LEAK DETECTED

AutoCAD SHX Text

CR7 (TO RTU)

AutoCAD SHX Text

PUMP P-2 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

CR6 (TO RTU)

AutoCAD SHX Text

PUMP P-1 SEAL LEAK DETECTED

AutoCAD SHX Text

CR5 (TO RTU)

AutoCAD SHX Text

PUMP P-1 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

CR4 (TO RTUI)

AutoCAD SHX Text

CR3 (TO P-2 VFD)

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text

MISSION RTU

AutoCAD SHX Text

MISSION SYSTEM

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

GENERATOR CONTROL POWER

AutoCAD SHX Text

GENERATOR BLOCK HEATER

AutoCAD SHX Text

CB

AutoCAD SHX Text

CB

AutoCAD SHX Text

BLOWER BL-1

AutoCAD SHX Text

CB

AutoCAD SHX Text

POWER FOR VALVE V-1

AutoCAD SHX Text

CB

AutoCAD SHX Text

POWER FOR VALVE V-2

AutoCAD SHX Text

CB

AutoCAD SHX Text

POWER FOR VALVE V-3

AutoCAD SHX Text

CB

AutoCAD SHX Text

POWER FOR VALVE V-4

AutoCAD SHX Text

CB

AutoCAD SHX Text

POWER FOR VALVE V-5

AutoCAD SHX Text

OOX

AutoCAD SHX Text

XOO

AutoCAD SHX Text

CB

AutoCAD SHX Text

IN AUTO (TO PC)

AutoCAD SHX Text

OOX

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text

VFD

AutoCAD SHX Text 4-20mA SPEED CONTROL (FROM PLC)

AutoCAD SHX Text 4-20mA SPEED FEEDBACK (TO PLC)

AutoCAD SHX Text

HUMAN MACHINE INTERFACE

AutoCAD SHX Text

LINE REACTOR

AutoCAD SHX Text

CRF

AutoCAD SHX Text

FAN

AutoCAD SHX Text

CRR

AutoCAD SHX Text

ETM

AutoCAD SHX Text

FAULT

AutoCAD SHX Text

CRF

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CRR

AutoCAD SHX Text

RUNNING

AutoCAD SHX Text

THERMOSTAT (INSIDE VFD ENCLOSURE)

AutoCAD SHX Text

CR4 OR CR6 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

CR5 OR CR7 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

SHUTDOWN PUMP IN HAND AND AUTO MODES AND ENERGIZE CRF

AutoCAD SHX Text

SHUTDOWN PUMP IN AUTO MODE ONLY AND ENERGIZE CRF

AutoCAD SHX Text

PLC-AUTO (FROM PLC)

AutoCAD SHX Text

CR3 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

OPERATE AT 100% SPEED

AutoCAD SHX Text OPERATE AT SPEED BASED ON 4-20mA SPEED CONTROL INPUT

AutoCAD SHX Text

CRR RUN STATUS (TO PLC)

AutoCAD SHX Text

CRF FAULT STATUS (TO PLC)

AutoCAD SHX Text

CRR (FROM VFD-2)

AutoCAD SHX Text

PUMP P-1

AutoCAD SHX Text L1

AutoCAD SHX Text L2

AutoCAD SHX Text

CRR RUN STATUS (TO RTU)

AutoCAD SHX Text

CRF FAULT STATUS (TO RTU)

AutoCAD SHX Text L1

AutoCAD SHX Text L2

AutoCAD SHX Text L3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TO PUMP CONTROLLER

AutoCAD SHX Text N

AutoCAD SHX Text

(CONTINUES ABOVE)

AutoCAD SHX Text

(CONTINUES ABOVE)

AutoCAD SHX Text Y

AutoCAD SHX Text R

AutoCAD SHX Text

(CONTINUED FROM BELOW)

AutoCAD SHX Text

(CONTINUED FROM BELOW)

AutoCAD SHX Text L1

N

Drawn By

Hard copy is intended to be

24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.

Manager

PROJECT NO.

SHEET NO.

© C o p y r i g h t 2020

A l l R i g h t s R e s e r v e d

P L O

T

I N

F O

Z

C

A D

C

D E

D

Y O

U T

E

T

E

M

E

E

R

T

D W

Y E

R

R E V I S I O N S

NRT

191527

S t a

M i c h i g a n

D e p a r t m e n t o f

N a t u r a l

R e s o u r c e s

P a r k s a c r e a t i o n

D i v i s i o n

H o l l y

R e c r e a t i o n

A r e a

W a s t e w a t e r

S y s t e m

I m p r o v e m e n t s

DTMB File Number

751/18124.CDP

1/30/2020

PHASE 500

BIDS AND CONSTRUCTION

E602

TCD

TCD

JAC

GENERAL NOTES

SUBMERSIBLE PUMP P-5 VFD WIRING DIAGRAM

PUMP STATION CONTROL PANEL WIRING DIAGRAM

WEST RESTROOM BUILDING

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text THE FOLLOWING DEVICES SHALL BE PROVIDED IN THE PUMP CONTROL PANEL BUT ARE NOT SHOWN FOR CLARITY: 120VAC TRANSIENT VOLTAGE SURGE SUPPRESSER, 24VDC POWER SUPPLIES, INTRINSICALLY SAFE BARRIERS, GFI CONVENIENCE RECEPTACLE, INTERIOR LIGHT, COOLING FAN, CONDENSATE HEATER, THERMOSTAT(S) AND OTHER DEVICES LISTED IN THE SPEC. DRY CONTACTS FOR THE FOLLOWING SIGNALS SHALL BE WIRED TO A TERMINAL STRIP TO INTERFACE WITH THE SCADA MISSION RTU. ALARMS: WET WELL LOW LEVEL (CR1) [DISCRETE] WET WELL HIGH LEVEL (CR2) [DISCRETE] PUMP P-5 VFD FAULT (CRF) [DISCRETE] PUMP P-5 HIGH TEMP SHUTDOWN (CR4) [DISCRETE] PUMP P-5 SEAL LEAK DETECTED (CR5) [DISCRETE] PUMP P-6 VFD FAULT (CRF) [DISCRETE] PUMP P-6 HIGH TEMP SHUTDOWN (CR6) [DISCRETE] PUMP P-6 SEAL LEAK DETECTED (CR7) [DISCRETE STATUS: PUMP P-5 RUN STATUS (CRR) [DISCRETE] PUMP P-6 RUN STATUS (CRR) [DISCRETE] SPD STATUS [DISCRETE] ALL WIRING TO/FROM THIS PANEL AND OTHER ENCLOSURES/EQUIPMENT SHALL BE INSTALLED IN CONDUIT. MINIMUM CONDUCTOR SIZE FOR POWER IS #12, FOR CONTROL IS #14. CIRCUIT BREAKER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS INCLUDED IN SUBMERSIBLE PUMP CONTROL PACKAGE. PROVIDE WIRING AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH NEC. CIRCUIT BREAKER AND FUSE SIZES SHALL BE DETERMINED BY CONTROL PANEL FABRICATOR. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS.

AutoCAD SHX Text 3.

AutoCAD SHX Text 4.

AutoCAD SHX Text 5.

AutoCAD SHX Text 6.

AutoCAD SHX Text

OOX

AutoCAD SHX Text

XOO

AutoCAD SHX Text

CB

AutoCAD SHX Text

IN AUTO (TO PC)

AutoCAD SHX Text

OOX

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text

VFD

AutoCAD SHX Text FUTURE 4-20mA SPEED CONTROL (FROM PC)

AutoCAD SHX Text FUTURE 4-20mA SPEED FEEDBACK (TO PC)

AutoCAD SHX Text

HUMAN MACHINE INTERFACE

AutoCAD SHX Text

LINE REACTOR

AutoCAD SHX Text

CRF

AutoCAD SHX Text

FAN

AutoCAD SHX Text

CRR

AutoCAD SHX Text

ETM

AutoCAD SHX Text

FAULT

AutoCAD SHX Text

CRF

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CRR

AutoCAD SHX Text

RUNNING

AutoCAD SHX Text

THERMOSTAT (INSIDE VFD ENCLOSURE)

AutoCAD SHX Text

CR4 OR CR6 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

CR5 OR CR7 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

SHUTDOWN PUMP IN HAND AND AUTO MODES AND ENERGIZE CRF

AutoCAD SHX Text

SHUTDOWN PUMP IN AUTO MODE ONLY AND ENERGIZE CRF

AutoCAD SHX Text

PLC-AUTO (FROM PC)

AutoCAD SHX Text

CR3 (FROM PUMP CONTROL PANEL)

AutoCAD SHX Text

OPERATE AT 100% SPEED

AutoCAD SHX Text OPERATE AT SPEED BASED ON 4-20mA SPEED CONTROL INPUT

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CONTROL POWER ON

AutoCAD SHX Text

LOW LEVEL FLOAT SWITCH LSL-1

AutoCAD SHX Text

ISR-1

AutoCAD SHX Text

HIGH LEVEL FLOAT SWITCH LSH-1

AutoCAD SHX Text

ISR-2

AutoCAD SHX Text

INTRINSICALLY SAFE RELAY (TYPICAL)

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR4

AutoCAD SHX Text

CR5

AutoCAD SHX Text

PUMP P-1 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-1 SEAL LEAK DETECTED

AutoCAD SHX Text

PUMP P-1 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-1 SEAL LEAK DETECTED

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR6

AutoCAD SHX Text

CR7

AutoCAD SHX Text

PUMP P-2 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-2 SEAL LEAK DETECTED

AutoCAD SHX Text

PUMP P-2 HIGH TEMP SHUTDOWN

AutoCAD SHX Text

PUMP P-2 SEAL LEAK DETECTED

AutoCAD SHX Text

CONTACTS SHOWN IN ALARM STATE

AutoCAD SHX Text

CONTACT SHOWN IN NORMAL STATE

AutoCAD SHX Text

P-1 HIGH TEMP AND SEAL LEAK SENSORS

AutoCAD SHX Text

P-2 HIGH TEMP AND SEAL LEAK SENSORS

AutoCAD SHX Text

P-1 HIGH TEMP AND SEAL LEAK RELAY

AutoCAD SHX Text

P-2 HIGH TEMP AND SEAL LEAK RELAY

AutoCAD SHX Text

(CONTINUES ABOVE)

AutoCAD SHX Text

(CONTINUED FROM BELOW)

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

PUMP CONTROLLER (PC)

AutoCAD SHX Text WET WELL LEVEL FROM LEVEL TRANSDUCER (LE-1) (#16TSP,3/4"C; 4-20mA)

AutoCAD SHX Text

CR9

AutoCAD SHX Text

CR9

AutoCAD SHX Text

CR2

AutoCAD SHX Text

CR8

AutoCAD SHX Text

RESET

AutoCAD SHX Text

CR1

AutoCAD SHX Text

CR8

AutoCAD SHX Text

WET WELL LOW LEVEL

AutoCAD SHX Text

WET…

This is the start of the file's text. The full file is on GovTribe.