Plans 27-36 18124.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ 171 200000000138 2
- Issued by
- Benzie County, Michigan
About this file
This document consists of electrical construction plans for the Holly Recreation Area Wastewater System Improvements project under the State of Michigan, Department of Natural Resources, Parks and Recreation Division. The project (DTMB File Number 751/18124.CDP) encompasses Phase 500 (Bids and Construction) and includes detailed electrical specifications and site plans for wastewater system improvements at a recreation area facility. The plans specify work for three primary locations: the sanitation station/equalization tank pump station, the west restroom building pump station, and the east restroom building pump station. The project requires installation of control panels, pumping systems with variable frequency drives, flow metering equipment, electrical service upgrades, and generator with automatic transfer switch capabilities (noted as Bid Alternate No. 2). Multiple submersible pumps ranging from 2 to 12 horsepower are specified across the facilities, along with associated conduit, wiring, and control systems complying with the National Electrical Code and NFPA standards.
The electrical plans detail comprehensive wiring requirements, equipment pad specifications, and hazardous location classifications for confined spaces such as equalization tanks and wet wells. Equipment specifications include NEMA 4X stainless steel enclosures for control panels, surge protective devices with minimum 80 kVA/phase ratings, intrinsically safe relays and barriers for hazardous areas, and uninterruptible power supplies. The plans establish minimum conductor sizing requirements (#12 for power, #14 for control, #16 twisted shielded pair for analog signals), conduit specifications ranging from 3/4 inches to 3 inches, and grounding electrode systems with maximum 5-ohm resistance. Bid Alternate No. 2 addresses the optional provision of a 100 kilowatt diesel standby generator with automatic transfer switch, with a manual 2-pole 400-ampere transfer switch as the base requirement if the generator option is not selected. The document includes detailed diagrams, material schedules, installation details, and comprehensive notes for coordination with utility providers including Consumers Energy for electrical service connections.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Specs 18124.pdf | ||
| Plans 1-7 18124.pdf | ||
| Addendum 1 18124.pdf | ||
| Plans 18-26 18124.pdf | ||
| Plans 8-17 18124.pdf | ||
| Advertisement 18124.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Reviewer
Designer
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
W G
L A
Y O
U T
E
D
T
E
T
I M
E
M
U
S E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a t e o f
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a n d
R c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E001
TCD
TCD
JAC
GENERAL NOTES
DEMOLITION NOTES
AutoCAD SHX Text
1. THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND NFPA 820 SHALL BE CONSIDERED CLASS I, DIVISION 1 HAZARDOUS LOCATIONS: A. INSIDE EQUALIZATION TANK. B. INSIDE WET WELLS. 2. THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND THE FOLLOWING LOCATIONS, IN ACCORDANCE WITH NEC AND NFPA 820 SHALL CONSIDERED CLASS I, DIVISION 2 HAZARDOUS LOCATIONS: A. INSIDE FLOW METER MANHOLE. B. INSIDE CONTROL VALVE MANHOLES. 3. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCALLY ADOPTED CODES. 4. COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL SERVICE TO NEW EQUALIZATION TANK AREA. 5. PROVIDE CONDUIT SEAL-OFF FITTINGS IN ALL CONDUIT RUNS PROVIDE CONDUIT SEAL-OFF FITTINGS IN ALL CONDUIT RUNS THAT ENTER/LEAVE HAZARDOUS LOCATIONS. ALL WORK IN HAZARDOUS AREAS SHALL BE IN ACCORDANCE WITH ARTICLE 500 OF THE NATIONAL ELECTRICAL CODE. 6. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS. 7. ALL WIRING SHALL BE INSTALLED IN CONDUIT; MINIMUM ALL WIRING SHALL BE INSTALLED IN CONDUIT; MINIMUM CONDUIT SIZE IS 3/4" . MINIMUM CONDUCTOR SIZES FORPOWER WIRING IS #12, FOR CONTROL WIRING IS #14, AND FOR ANALOG SIGNAL WIRING IS #16TSP (TWISTED SHIELDED PAIR). 8. PROVIDE EQUIPMENT PADS. REFERENCE SHEET E603 FOR PROVIDE EQUIPMENT PADS. REFERENCE SHEET E603 FOR EQUIPMENT PAD DETAIL. COORDINATE LOCATIONS WITH CIVIL. 9. GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 GROUNDING SHALL BE IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRIC CODE. 10. ALL MOUNTING HARDWARE SHALL BE 316 STAINLESS STEEL.ALL MOUNTING HARDWARE SHALL BE 316 STAINLESS STEEL.
AutoCAD SHX Text
GENERAL ELECTRICAL ABBREVIATIONS
AutoCAD SHX Text
AMPERES
AutoCAD SHX Text
A, AMP
AutoCAD SHX Text
KNOCKOUT
AutoCAD SHX Text
KO
AutoCAD SHX Text
ALTERNATING CURRENT
AutoCAD SHX Text
AC
AutoCAD SHX Text
KILOVOLT AMPERE
AutoCAD SHX Text
KVA
AutoCAD SHX Text
ACOUSTICAL CEILING PANEL
AutoCAD SHX Text
ACP
AutoCAD SHX Text
KILOWATT
AutoCAD SHX Text
KW
AutoCAD SHX Text
AMERICANS WITH DISABILITIES ACT
AutoCAD SHX Text
ADA
AutoCAD SHX Text
KILOWATT-HOUR
AutoCAD SHX Text
KWHR
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
LIGHT-EMITTING DIODE
AutoCAD SHX Text
LED
AutoCAD SHX Text
AUTHORITY HAVING JURISDICTION
AutoCAD SHX Text
AHJ
AutoCAD SHX Text
LIGHT SWITCH OR LIMIT SWITCH
AutoCAD SHX Text
LS
AutoCAD SHX Text
AMPERE-INTERRUPTING CURRENT
AutoCAD SHX Text
AIC
AutoCAD SHX Text
LIGHT OR LEVEL TRANSDUCER
AutoCAD SHX Text
LT
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text
AL
AutoCAD SHX Text
LIQUID-TIGHT FLEXIBLE METAL CONDUIT
AutoCAD SHX Text
LTFMC
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
LTG
AutoCAD SHX Text
AUTOMATIC TELLER MACHINE
AutoCAD SHX Text
ATM
AutoCAD SHX Text
LOW VOLTAGE
AutoCAD SHX Text
LV
AutoCAD SHX Text
AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text
ATS
AutoCAD SHX Text
METER
AutoCAD SHX Text M
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
BRKR
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MANUF
AutoCAD SHX Text
CONDUIT OR CELSIUS
AutoCAD SHX Text C
AutoCAD SHX Text
MINIMUM CIRCUIT AMPACITY
AutoCAD SHX Text
MCA
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
CB
AutoCAD SHX Text
MAIN CIRCUIT BREAKER
AutoCAD SHX Text
MCB
AutoCAD SHX Text
CABLE TELEVISION
AutoCAD SHX Text
CATV
AutoCAD SHX Text
MOTOR CONTROL CENTER
AutoCAD SHX Text
MCC
AutoCAD SHX Text
CAST-IN-PLACE
AutoCAD SHX Text
CIP
AutoCAD SHX Text
MOTOR CIRCUIT PROTECTOR
AutoCAD SHX Text
MCP
AutoCAD SHX Text
CONTROL JOINT
AutoCAD SHX Text
CJ
AutoCAD SHX Text
MANHOLE
AutoCAD SHX Text
MH
AutoCAD SHX Text
CIRCUIT
AutoCAD SHX Text
CKT
AutoCAD SHX Text
MAIN LUGS ONLY
AutoCAD SHX Text
MLO
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CLG
AutoCAD SHX Text
MOUNT
AutoCAD SHX Text
MT
AutoCAD SHX Text
CONSTRUCTION MANAGER
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
MTD
AutoCAD SHX Text
CONCRETE MASONRY UNIT
AutoCAD SHX Text
MEDIUM VOLTAGE
AutoCAD SHX Text
MV
AutoCAD SHX Text
COAXIAL
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
N, NEUT
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
NORMALLY CLOSED
AutoCAD SHX Text
NC
AutoCAD SHX Text
CONTROL PANEL
AutoCAD SHX Text
NIGHT LIGHT
AutoCAD SHX Text
NL
AutoCAD SHX Text
CURRENT TRANSFORMER
AutoCAD SHX Text
NORMALLY OPEN
AutoCAD SHX Text
NO
AutoCAD SHX Text
COPPER
AutoCAD SHX Text
NOMINAL
AutoCAD SHX Text
NOM
AutoCAD SHX Text
COMMISSIONING
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
COMMISSIONING AGENT
AutoCAD SHX Text
OUTSIDE DIAMETER
AutoCAD SHX Text
OD
AutoCAD SHX Text
BUILDING MANAGEMENT SYSTEM
AutoCAD SHX Text
OVERHEAD
AutoCAD SHX Text
OH
AutoCAD SHX Text
DECIBEL
AutoCAD SHX Text
OVERHEAD DOOR
AutoCAD SHX Text
OHD
AutoCAD SHX Text
DIRECT CURRENT
AutoCAD SHX Text
OVERLOAD
AutoCAD SHX Text
OL
AutoCAD SHX Text
DEMOLISH
AutoCAD SHX Text
PUBLIC ADDRESS
AutoCAD SHX Text
PA
AutoCAD SHX Text
DEMOLISH OR DEMOLITION
AutoCAD SHX Text
PULL BOX OR PUSHBUTTON
AutoCAD SHX Text
PB
AutoCAD SHX Text
DRINKING FOUNTAIN
AutoCAD SHX Text
POWER FACTOR CORRECTION
AutoCAD SHX Text
PFC
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
PH
AutoCAD SHX Text
DOUBLE POLE DOUBLE THROW
AutoCAD SHX Text
PANEL OR PANELBOARD
AutoCAD SHX Text
PNL
AutoCAD SHX Text
DOUBLE POLE SINGLE THROW
AutoCAD SHX Text
POTENTIAL TRANSFORMER
AutoCAD SHX Text
PT
AutoCAD SHX Text
ELECTRICAL CONTRACTOR
AutoCAD SHX Text
PAN-TILT-ZOOM
AutoCAD SHX Text
PTZ
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
POWER
AutoCAD SHX Text
PWR
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
REFLECTED CEILING PLAN
AutoCAD SHX Text
RCP
AutoCAD SHX Text
ELEVATOR OR ELEVATION
AutoCAD SHX Text
REINFORCING BAR
AutoCAD SHX Text
REBAR
AutoCAD SHX Text
EMERGENCY
AutoCAD SHX Text
RECEPTACLE
AutoCAD SHX Text
RECEPT
AutoCAD SHX Text
ELECTRICAL METALLIC TUBING
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
RM
AutoCAD SHX Text
ENCLOSURE
AutoCAD SHX Text
RIGID NON-METALLIC CONDUIT
AutoCAD SHX Text
RNMC
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
RIGHT-OF-WAY
AutoCAD SHX Text
ROW
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
RIGID METALLIC CONDUIT
AutoCAD SHX Text
RMC
AutoCAD SHX Text
ELECTRIC WATER HEATER
AutoCAD SHX Text
SECONDARY
AutoCAD SHX Text
SEC
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
SINGLE POLE DOUBLE THROW
AutoCAD SHX Text
SPDT
AutoCAD SHX Text
FUSE OR FAHRENHEIT
AutoCAD SHX Text
SPECIFICATIONS
AutoCAD SHX Text
SPECS
AutoCAD SHX Text
FIRE ALARM
AutoCAD SHX Text
SINGLE POLE SINGLE THROW
AutoCAD SHX Text
SPST
AutoCAD SHX Text
FIRE ALARM ANNUNCIATOR PANEL
AutoCAD SHX Text
SQUARE
AutoCAD SHX Text
SQ
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
SS
AutoCAD SHX Text
FIXTURES, FURNISHINGS & EQUIPMENT
AutoCAD SHX Text
SOLENOID VALVE
AutoCAD SHX Text
SV
AutoCAD SHX Text
FIXTURE
AutoCAD SHX Text
SWITCHBOARD
AutoCAD SHX Text
SWBD
AutoCAD SHX Text
FULL LOAD AMPERES
AutoCAD SHX Text
SWITCHGEAR
AutoCAD SHX Text
SWGR
AutoCAD SHX Text
FACTORY MUTUAL
AutoCAD SHX Text
TEMPERATURE CONTROLS CONTRACTOR
AutoCAD SHX Text
TCC
AutoCAD SHX Text
FLEXIBLE METAL CONDUIT
AutoCAD SHX Text
TEMPERATURE CONTROL PANEL
AutoCAD SHX Text
TCP
AutoCAD SHX Text
FIBER OPTIC
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text
TRANS
AutoCAD SHX Text
FIRE RETARDANT
AutoCAD SHX Text
TIME SWITCH
AutoCAD SHX Text
TS
AutoCAD SHX Text
GENERAL CONTRACTOR
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
TYP
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
UNDERWRITERS LABORATORIES
AutoCAD SHX Text
UL
AutoCAD SHX Text
GROUND FAULT CIRCUIT INTERRUPTER
AutoCAD SHX Text
UNLESS NOTED OTHERWISE
AutoCAD SHX Text
UNO
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
UNINTERRUPTIBLE POWER SUPPLY
AutoCAD SHX Text
UPS
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
VOLTS
AutoCAD SHX Text V
AutoCAD SHX Text
GYPSUM BOARD
AutoCAD SHX Text
VOLT-AMPERE
AutoCAD SHX Text
VA
AutoCAD SHX Text
HANDHOLE
AutoCAD SHX Text
VOLTS-ALTERNATING CURRENT
AutoCAD SHX Text
VAC
AutoCAD SHX Text
HAND-OFF-AUTO
AutoCAD SHX Text
VOLTS-DIRECT CURRENT
AutoCAD SHX Text
VDC
AutoCAD SHX Text
HORSE POWER
AutoCAD SHX Text
VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
HIGH VOLTAGE
AutoCAD SHX Text
WATTS
AutoCAD SHX Text W
AutoCAD SHX Text
INSIDE DIAMETER
AutoCAD SHX Text
WATER HEATER
AutoCAD SHX Text
WH
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
WP
AutoCAD SHX Text
CM
AutoCAD SHX Text
CMU
AutoCAD SHX Text
COAX
AutoCAD SHX Text
CONC
AutoCAD SHX Text
CP
AutoCAD SHX Text
CT
AutoCAD SHX Text
CU
AutoCAD SHX Text Cx
AutoCAD SHX Text CxA
AutoCAD SHX Text
BMS
AutoCAD SHX Text
DB
AutoCAD SHX Text
DC
AutoCAD SHX Text
DEM
AutoCAD SHX Text
DEMO
AutoCAD SHX Text
DF
AutoCAD SHX Text
DISC
AutoCAD SHX Text
DPDT
AutoCAD SHX Text
DPST
AutoCAD SHX Text
EC
AutoCAD SHX Text
EJ
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
ELEV
AutoCAD SHX Text
EM
AutoCAD SHX Text
EMT
AutoCAD SHX Text
ENCL
AutoCAD SHX Text
ETR
AutoCAD SHX Text
EWC
AutoCAD SHX Text
EWH
AutoCAD SHX Text
EXIST
AutoCAD SHX Text F
AutoCAD SHX Text
FA
AutoCAD SHX Text
FAAP
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FF&E
AutoCAD SHX Text
FIXT
AutoCAD SHX Text
FLA
AutoCAD SHX Text
FM
AutoCAD SHX Text
FMC
AutoCAD SHX Text
FO
AutoCAD SHX Text
FRT
AutoCAD SHX Text
GC
AutoCAD SHX Text
GEN
AutoCAD SHX Text
GFCI
AutoCAD SHX Text
GFI
AutoCAD SHX Text
GND
AutoCAD SHX Text
GYP BD
AutoCAD SHX Text
HH
AutoCAD SHX Text
HOA
AutoCAD SHX Text
HP
AutoCAD SHX Text
ID
AutoCAD SHX Text
JB
AutoCAD SHX Text
HV
AutoCAD SHX Text
NATIONAL ELECTRICAL CODE
AutoCAD SHX Text
NEC
AutoCAD SHX Text
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
AutoCAD SHX Text
NEMA
AutoCAD SHX Text
SURGE PROTECTION DEVICE
AutoCAD SHX Text
SPD
AutoCAD SHX Text %%uNOTES
AutoCAD SHX Text
ELECTRICAL SYMBOL LEGEND
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
MANUFACTURER / CATALOG NO.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
GFI
AutoCAD SHX Text
WP
AutoCAD SHX Text
ZPX/Y
AutoCAD SHX Text X
AutoCAD SHX Text N
AutoCAD SHX Text X
AutoCAD SHX Text N
AutoCAD SHX Text 1.
AutoCAD SHX Text
DUPLEX RECEPTACLE
AutoCAD SHX Text
HUBBELL #HBL5362I
AutoCAD SHX Text
MOUNT AT 18" AFF; NOTE 1
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
WEATHERPROOF WHILE-IN-USE DUPLEX RECEPTACLE
AutoCAD SHX Text
HUBBELL #GFR5362SGI
AutoCAD SHX Text
HUBBELL #GFR5362SGI WITH WP26EH
AutoCAD SHX Text
MOUNT AT 18" AFF, UNO; NOTE 1
AutoCAD SHX Text
MOUNT AT 18" ABOVE GRADE, UNO; NOTE 2
AutoCAD SHX Text
MOUNT AT 18" AFF, UNO; NOTE 1
AutoCAD SHX Text
NONFUSIBLE DISCONNECT SWITCH
AutoCAD SHX Text
FUSIBLE DISCONNECT SWITCH
AutoCAD SHX Text
MOTOR STARTER
AutoCAD SHX Text
COMBINATION MOTOR STARTER-DISCONNECT
AutoCAD SHX Text
SPECIAL CONNECTION AS NOTED
AutoCAD SHX Text
PANELBOARD (480Y/277V) (480V)
AutoCAD SHX Text
PANELBOARD (240/120V) OR (208Y/120V)
AutoCAD SHX Text
SINGLE PHASE MOTOR CONNECTION
AutoCAD SHX Text
THREE PHASE MOTOR CONNECTION
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
CONDUIT UNDER FLOOR
AutoCAD SHX Text
CONDUIT ABOVE FLOOR
AutoCAD SHX Text
SURFACE OR RECESSED LUMINAIRE
AutoCAD SHX Text
WALL MOUNTED LUMINAIRE
AutoCAD SHX Text
SURFACE OR RECESSED FLUORESCENT LUMINAIRE
AutoCAD SHX Text
SEE SPECIFICATIONS
AutoCAD SHX Text
SEE SPECIFICATIONS
AutoCAD SHX Text
SEE SPECIFICATIONS
AutoCAD SHX Text
SEE SPECIFICATIONS
AutoCAD SHX Text
AutoCAD SHX Text
SEE PANELBOARD SCHEDULE
AutoCAD SHX Text
SEE PANELBOARD SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SEE SPECIFICATIONS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SEE LUMINAIRE SCHEDULE
AutoCAD SHX Text
SEE LUMINAIRE SCHEDULE
AutoCAD SHX Text
SEE LUMINAIRE SCHEDULE
AutoCAD SHX Text
SIZE AS NOTED
AutoCAD SHX Text Z=No. POLES; X=SWITCH SIZE; Y=FUSE SIZE; MOUNT AT 5'-0" AFF, UNO
AutoCAD SHX Text N=STARTER SIZE; X=STARTER TYPE, (RV: REDUCED VOLTAGE; BLANK: FULL VOLTAGE); MOUNT AT 5'-0" AFF, UNO
AutoCAD SHX Text N=STARTER SIZE; X=STARTER TYPE, (RV: REDUCED VOLTAGE; BLANK: FULL VOLTAGE); MOUNT AT 5'-0" AFF, UNO
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SITE LUMINAIRE AND POLE
AutoCAD SHX Text
SEE LUMINAIRE SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text
UNO = UNLESS NOTED OTHERWISE SSP = STAINLESS STEEL PLATE
AutoCAD SHX Text PART NUMBER SPECIFIED IS FOR DRY LOCATION ONLY. PROVIDE DEVICE RATED FOR THE ENVIRONMENT RECEPTACLE SHALL BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC.SHALL BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC. BE LISTED AS WEATHER-RESISTANT TO COMPLY WITH THE 2008 NEC.
AutoCAD SHX Text 2.
AutoCAD SHX Text
WIRING DEVICES - RECEPTACLE SCHEDULE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MANUFACTURE
AutoCAD SHX Text
CATALOG NO.
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DUPLEX RECEPTACLE
AutoCAD SHX Text
HUBBELL
AutoCAD SHX Text
HBL5362I
AutoCAD SHX Text
MOUNT AT 18" AFF, UNO
AutoCAD SHX Text
GFCI DUPLEX RECEPTACLE
AutoCAD SHX Text
HUBBELL
AutoCAD SHX Text
MOUNT AT 18" AFF, UNO
AutoCAD SHX Text WEATHERPROOF, GFCI DUPLEX RECEPTACLE WITH WEATHERPROOF WHILE-IN-USE, EXTRA DUTY COVER
AutoCAD SHX Text
HUBBELL
AutoCAD SHX Text
MOUNT AT 36" AFF, UNO
AutoCAD SHX Text
GFR5362SGI
AutoCAD SHX Text
GFR5362SGI, WP26EH
AutoCAD SHX Text
GFI
AutoCAD SHX Text
WP
AutoCAD SHX Text
1. FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT OF WORK AND INCLUDE ALL COSTS ASSOCIATED WITH DEMOLITION IN BASE BID. 2. COORDINATE DEMOLITION WORK WITH OTHER TRADES. COORDINATE DEMOLITION WORK WITH OTHER TRADES. DISCONNECT AND REMOVE ALL CONDUIT, WIRING, AND DEVICES ASSOCIATED WITH EQUIPMENT BEING REMOVED. EXPOSED CONDUIT AND DEVICES SHALL BE DISCONNECTED AND REMOVED; CONCEALED CONDUIT CAN BE ABANDONED IN PLACE. ALL WIRING SHALL BE COMPLETELY REMOVED BACK TO ITS SOURCE.
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E002
TCD
TCD
JAC
KEY NOTES
SANITATION STATION
ELECTRICAL SITE PLAN
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
UTILITY TRANSFORMER PAN
AutoCAD SHX Text
PUMP CONTROL PANEL CIRCUIT BREAKER
AutoCAD SHX Text
MIXER MOTOR STARTERS (FUTURE)
AutoCAD SHX Text
ATS
AutoCAD SHX Text
MCB
AutoCAD SHX Text
UTILITY METER
AutoCAD SHX Text
120V CIRCUITS (SEPARATE CONDUITS FOR BLOCK HEATER, BATTERY CHARGER, ETC.)
AutoCAD SHX Text
PUMP CONTROL PANEL
AutoCAD SHX Text
MIXER TERMINATION BOX (FUTURE)
AutoCAD SHX Text
MIXER TERMINATION BOX (FUTURE)
AutoCAD SHX Text V-2
AutoCAD SHX Text V-4
AutoCAD SHX Text
MX-1 (FUTURE)
AutoCAD SHX Text
BL-1
AutoCAD SHX Text
COORDINATE CONDUIT STUB-UP LOCATION WITH BLOWER ENCLOSURE
AutoCAD SHX Text P-1
AutoCAD SHX Text P-2
AutoCAD SHX Text
LE-3 LSH-3 LSL-3
AutoCAD SHX Text
MX-2 (FUTURE)
AutoCAD SHX Text
PUMP/LEVEL TERMINATION BOX
AutoCAD SHX Text V-5
AutoCAD SHX Text
VALVE VAULT
AutoCAD SHX Text
FE-1
AutoCAD SHX Text
FLOW METER MANHOLE
AutoCAD SHX Text V-1
AutoCAD SHX Text V-3
AutoCAD SHX Text
MANHOLE (MH-1)
AutoCAD SHX Text
MANHOLE (MH-2)
AutoCAD SHX Text
GENERATOR PAD
AutoCAD SHX Text
UTILITY TRANSFORMER
AutoCAD SHX Text
EQUIPMENT PANEL
AutoCAD SHX Text
GENERATOR REMOTE E-STOP PUSHBUTTON
AutoCAD SHX Text
1. UTILITY TRANSFORMER PROVIDED BY CONSUMERS ENERGY; UTILITY TRANSFORMER PROVIDED BY CONSUMERS ENERGY; PROVIDE CONCRETE PAD, SEE DETAIL ON SHEET E603. 2. INSTALL A 5" PVC CONDUIT WITH NYLON PULL CORD FOR INSTALL A 5" PVC CONDUIT WITH NYLON PULL CORD FOR USE BY CONSUMERS ENERGY FOR INSTALLATION OF PRIMARY CABLING (COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH CONSUMERS ENERGY). 3. BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC PROVIDE GENERATOR AND AUTOMATIC TRANSFER SWITCH (ATS). 4. PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL TRANSFER SWITCH (MTS) IF BID ALTERNATE NO. 2 IS NOT PROVIDED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = 30'
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E003
TCD
TCD
JAC
KEY NOTES
WEST RESTROOM BUILDING
ELECTRICAL SITE PLAN
AutoCAD SHX Text
3" WTR.
AutoCAD SHX Text
2" WTR.
AutoCAD SHX Text
WEST RESTROOM BUILDING
AutoCAD SHX Text
EXISTING WEST CAMPGROUND POWER DISTRIBUTION PANEL (WC-PDP)
AutoCAD SHX Text
EXISTING UTILITY TRANSFORMER
AutoCAD SHX Text
EQUIPMENT PAD
AutoCAD SHX Text
3#3,#8G,1-1/4"C FOR POWER
AutoCAD SHX Text
EXISTING SEPTIC TANKS 2-3000 GALLON
AutoCAD SHX Text
NEW PUMP STATION WET WELL
AutoCAD SHX Text
NEW PUMP STATION VALVE VAULT
AutoCAD SHX Text
CONTROL PANEL (CP-WRPS)
AutoCAD SHX Text
1. PROVIDE 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE PROVIDE 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE LABELED 6 IN EXISTING PANEL WC-PDP. MATCH EXISTING CIRCUIT BREAKER MANUFACTURE, TYPE, AND INTERRUPT RATING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = 10'
AutoCAD SHX Text
NORTH
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E004
TCD
TCD
JAC
EAST RESTROOM BUILDING
ELECTRICAL SITE PLAN
KEY NOTES
AutoCAD SHX Text
2" WTR.
AutoCAD SHX Text
UG ELEC
AutoCAD SHX Text
EAST RESTROOM BUILDING
AutoCAD SHX Text
EXISTING EAST CAMPGROUND POWER DISTRIBUTION PANEL (EC-PDP)
AutoCAD SHX Text
EXISTING UTILITY TRANSFORMER
AutoCAD SHX Text
EXISTING SEPTIC TANK 1,000 GALLONS
AutoCAD SHX Text
EXISTING SEPTIC TANK 3,200 GALLONS
AutoCAD SHX Text
EXISTING SEPTIC TANK 3,200 GALLONS
AutoCAD SHX Text
NEW PUMP STATION VALVE VAULT
AutoCAD SHX Text
NEW PUMP STATION WET WELL
AutoCAD SHX Text
REMOVE EXISTING CONTROL PANEL (CP-ERPS)
AutoCAD SHX Text
3#3,#8G,1-1/4"C FOR POWER
AutoCAD SHX Text
NEW CONTROL PANEL (CP-ERPS)
AutoCAD SHX Text
EQUIPMENT PAD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1" = 10'
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
1. WIRE TO EXISTING 2-POLE 150AF, 100AT CIRCUIT BREAKER WIRE TO EXISTING 2-POLE 150AF, 100AT CIRCUIT BREAKER IN SPACE LABELED 12 IN EXISTING PANEL EC-PDP.
AutoCAD SHX Text
INPUT/OUTPUT LIST AND WIRING SCHEDULE
DESCRIPTION I/O TYPE
DESTINATION WIRING
CONDUIT
SIZE
SIGNAL
TYPE
REMARKS
FROM TO #16TSP #14 #12
CP-EQPS
VAVLE CV-1 IN REMOTE DI VALVE CV-1 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL
VALVE CV-1 OPENED DI VALVE CV-1
CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE CV-1 CLOSED DI VALVE CV-1 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE CV-1 OPEN DO VALVE CV-1 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE CV-1 CLOSED DO VALVE CV-1
CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
VAVLE V-1 IN REMOTE DI VALVE V-1 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL
VALVE V-1 OPENED DI VALVE V-1 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-1 CLOSED DI VALVE V-1 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-1 OPEN DO VALVE V-1
CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-1 CLOSED DO VALVE V-1 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VAVLE V-2 IN REMOTE DI VALVE V-2 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL
VALVE V-2 OPENED DI VALVE V-2
CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-2 CLOSED DI VALVE V-2 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-2 OPEN DO VALVE V-2 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-2 CLOSED DO VALVE V-2 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VAVLE V-3 IN REMOTE DI VALVE V-3 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL
VALVE V-3 OPENED DI VALVE V-3 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-3 CLOSED DI VALVE V-3 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-3 OPEN DO VALVE V-3 CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-3 CLOSED DO VALVE V-3 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VAVLE V-4 IN REMOTE DI VALVE V-4 CP-EQPS - 10 2 1" 120 VAC 120VAC FOR ACTUATOR FROM CONTROL PANEL
VALVE V-4 OPENED DI VALVE V-4
CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-4 CLOSED DI VALVE V-4 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-4 OPEN DO VALVE V-4 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
VALVE V-4 CLOSED DO VALVE V-4 CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
GENERATOR ALARM DI STANDBY GENERATOR
CP-EQPS
- 4 - 3/4" 120 VAC -
GENERATOR RUNNING DI STANDBY GENERATOR CP-EQPS - - - - 120 VAC
COMBINE SIMILAR SIGNALS
ATS ON GENERATOR DI ATS CP-EQPS - 4 - 3/4" 120 VAC -
ATS ON NORMAL DI ATS
CP-EQPS
- - - - 120 VAC
COMBINE SIMILAR SIGNALS
EQ TANK FLOW - FE-1 FIT-1 - - - 3/4" - MAUFACTURES CABLE
EQ TANK FLOW AI FIT-1 CP-EQPS 1 - - 3/4" 4-20mA 120VAC FOR TRANSMITTER FROM CONTROL PANEL
EQ TANK LEVEL AI LT-3 CP-EQPS 1 - - 3/4" 4-20mA MAUFACTURES CABLE
EQ TANK LOW LEVEL (FLOAT)
DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
EQ TANK HIGH LEVEL (FLOAT)
DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-1 RUNNING DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-1 IN REMOTE DI - 2 - - 120 VAC
WIRING INTERNAL TO CP-EQPS
PUMP P-1 VFD FAULT DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-1 START/STOP CALL DO - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-1 VFD SPEED CONTROL AO 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS
PUMP P-1 VFD SPEED FEEDBACK AI 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS
PUMP P-1 HIGH TEMPERATURE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-1 SEAL LEAK DETECTED DI 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-2 RUNNING DI - 2 - - 120 VAC
WIRING INTERNAL TO CP-EQPS
PUMP P-2 IN REMOTE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-2 VFD FAULT DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-2 START/STOP CALL DO - 2 - - 120 VAC
WIRING INTERNAL TO CP-EQPS
PUMP P-2 VFD SPEED CONTROL AO 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS
PUMP P-2 VFD SPEED FEEDBACK AI 1 - - - 4-20mA WIRING INTERNAL TO CP-EQPS
PUMP P-2 HIGH TEMPERATURE DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
PUMP P-2 SEAL LEAK DETECTED DI - 2 - - 120 VAC
WIRING INTERNAL TO CP-EQPS
CONTROL PANELPOWER ON DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
SURGE PROTECTIVE DEVICE (SPD) FAULT
DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
UPS FAULT DI - 2 - - 120 VAC
WIRING INTERNAL TO CP-EQPS
UPS LOW BATTERY DI - 2 - - 120 VAC WIRING INTERNAL TO CP-EQPS
Reviewer
Designer
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E401
TCD
TCD
JAC
GENERAL NOTES
CONTROL PANEL CP-EQPS RISER DIAGRAM
KEY NOTES
CONTROL PANEL CP-EQPS ONE LINE DIAGRAM
EQ TANK PUMP STATION ONE LINE DIAGRAM
AutoCAD SHX Text
1. COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL COORDINATE WITH ELECTRIC UTILITY FOR NEW ELECTRICAL SERVICE. 2. THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA 4X STAINLESS STEEL ENCLOSURE; SURGE PROTECTIVE DEVICE; 1 POWER; LOAD CENTER FOR DISTRIBUTING POWER;POWER SUPPLIES; INTERIOR LIGHT (INTERLOCKED WITH PANEL DOOR); THERMOSTATICALLY CONTROLLED ANTI-CONDENSATION HEATER; VENTILATION FAN, ETC. 3. EQ TANK PUMP STATION CONTROL PANEL SHALL INCLUDE AN EQ TANK PUMP STATION CONTROL PANEL SHALL INCLUDE AN INTEGRAL SURGE PROTECTIVE DEVICE (SPD). SPD SHALL PROVIDE L-N, L-G, L-L, AND N-G PROTECTION.
AutoCAD SHX Text
EQ TANK PUMP STATION CONTROL PANEL (CP-EQPS)
AutoCAD SHX Text
EQ TANK
AutoCAD SHX Text
AutoCAD SHX Text
MFR'S CABLE, 3/4"C
AutoCAD SHX Text
AutoCAD SHX Text
FLOAT SWITCH CABLE
AutoCAD SHX Text
PUMP/LEVEL TERMINATION BOX
AutoCAD SHX Text 2"C
AutoCAD SHX Text
LSH-3
AutoCAD SHX Text
LSL-3
AutoCAD SHX Text 3/4"C
AutoCAD SHX Text
LEVEL TRANSDUCER
AutoCAD SHX Text
AutoCAD SHX Text
PUMP POWER; SEE ONE LINE DIAGRAM
AutoCAD SHX Text 2"C
AutoCAD SHX Text
AutoCAD SHX Text
ALARM LIGHT
AutoCAD SHX Text 3/4"C
AutoCAD SHX Text
AutoCAD SHX Text
LE-3
AutoCAD SHX Text P-2
AutoCAD SHX Text P-1
AutoCAD SHX Text
3-250 KCMIL,#4G,3"C
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
1. SEE PUMP CONTROL PANEL WIRING DIAGRAM ON SHEET SEE PUMP CONTROL PANEL WIRING DIAGRAM ON SHEET E601. 2. COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH LEVEL PROBE MANUFACTURER. 3. CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% MAXIMUM CONDUCTOR FILL PERMITTED BY NEC FOR CONDUIT SEALS. CONTRACTOR SHALL ADJUST CONDUIT SIZES BASED ON ACTUAL CABLE SIZE. 4. PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. 5. SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS 80kA/PHASE. 6. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. 7. HIGH TEMP AND SEAL LEAK SENSOR WIRING RUNS VIA PUMP HIGH TEMP AND SEAL LEAK SENSOR WIRING RUNS VIA PUMP CABLE; SPLICE WIRING IN PUMP/LEVEL TERMINATION BOX AT WET WELL AND PROVIDE 4#14 IN 3/4" CONDUIT FROM PUMP/LEVEL TERMINATION BOX TO PUMP CONTROL PANEL. 8. FLOAT SWITCH WIRING RUNS VIA FLOAT SWITCH CABLE; FLOAT SWITCH WIRING RUNS VIA FLOAT SWITCH CABLE; SPLICE WIRING IN PUMP/LEVEL TERMINATION BOX AT WET WELL AND PROVIDE 2#14 (FOR EACH FLOAT SWITCH) IN 3/4" CONDUIT FROM PUMP/LEVEL TERMINATION BOX TO PUMP CONTROL PANEL. 9. PUMP CONTROL PANEL SHALL BE UL LABELED FOR PUMP CONTROL PANEL SHALL BE UL LABELED FOR AVAILABLE FAULT CURRENT. 10. CIRCUIT BREAKER AND LOAD CENTER TO BE SIZED BY CIRCUIT BREAKER AND LOAD CENTER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS. PROVIDE WIRING AND BRANCH CIRCUIT BREAKERS SIZED IN ACCORDANCE WITH NEC. 11. LOCATION OF PUMP/LEVEL TERMINATION BOX AND CONDUIT LOCATION OF PUMP/LEVEL TERMINATION BOX AND CONDUIT RUNS TO BE FINALIZED AT TIME OF INSTALLATION. 12. PROVIDE 2" CONDUIT FROM ATS TO GENERATOR CONTROL PROVIDE 2" CONDUIT FROM ATS TO GENERATOR CONTROL PANEL. PROVIDE GENERATOR START-STOP AND STATUS CABLING. 13. PROVIDE 4#12,#12G IN 1" CONDUIT FROM PUMP CONTROL PROVIDE 4#12,#12G IN 1" CONDUIT FROM PUMP CONTROL PANEL TO GENERATOR CONTROL PANEL FOR POWER FOR GENERATOR BLOCK HEATER AND BATTERY CHARGER. TERMINATE WIRING IN PANELS AS INDICATED ON THE MANUFACTURER'S WIRING SCHEMATICS. 14. BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC BID ALTERNATE NO. 2: PROVIDE GENERATOR AND AUTOMATIC : PROVIDE GENERATOR AND AUTOMATIC TRANSFER SWITCH (ATS). 15. PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL PROVIDE NEMA 4X (316 SS) 2-POLE 400A MANUAL TRANSFER SWITCH (MTS) IF BID ALTERNATE NO. 2 IS NOT PROVIDED.
AutoCAD SHX Text
AutoCAD SHX Text
TO WIREWAY
AutoCAD SHX Text
EQ TANK METER VAULT
AutoCAD SHX Text
MFR'S CABLES, 1"C
AutoCAD SHX Text
FE-1
AutoCAD SHX Text
(COORDINATE WIRING)
AutoCAD SHX Text
SEAL OFF FITTING (TYP.)
AutoCAD SHX Text
CP-EQPS 10K AIC RATING NEMA 4X, 316 SS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P-1
AutoCAD SHX Text
12 HP
AutoCAD SHX Text
32.0 FLA (3 )
AutoCAD SHX Text
55.4 FLA (1 )
AutoCAD SHX Text 3#3,#8G,1-1/4"C
AutoCAD SHX Text 2P200
AutoCAD SHX Text
CB
AutoCAD SHX Text
SPD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LINE
AutoCAD SHX Text
PUMP CABLE (TYPICAL)
AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE SUSPENDED CABLE DETAIL, ON SHEET E604 (TYPICAL)
AutoCAD SHX Text
PUMP/LEVEL TERMINATION BOX
AutoCAD SHX Text
CB
AutoCAD SHX Text
CP-ESPS
AutoCAD SHX Text
CB
AutoCAD SHX Text
LINE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
VFD
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
MCP
AutoCAD SHX Text
MCP
AutoCAD SHX Text 2P200
AutoCAD SHX Text
SIZE 1
AutoCAD SHX Text
MX-2
AutoCAD SHX Text
2 HP
AutoCAD SHX Text
12.0 FLA (1 )
AutoCAD SHX Text
MX-1
AutoCAD SHX Text
2 HP
AutoCAD SHX Text
12.0 FLA (1 )
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
AUTOMATIC TRANSFER SWITCH - 2 POLE 400A 120/240V-1 NEMA 3R
AutoCAD SHX Text
STANDBY GENERATOR 100 KW DIESEL 120/240V-1 -3W
AutoCAD SHX Text
3-350 KCMIL,#4G,3"C
AutoCAD SHX Text
3-350 KCMIL,#4G,3"C
AutoCAD SHX Text 2P300
AutoCAD SHX Text
MAIN CIRCUIT BREAKER (SERVICE ENTRANCE RATED)
AutoCAD SHX Text
3-350 KCMIL,3"C
AutoCAD SHX Text
NEMA 4X (316SS)
AutoCAD SHX Text P
AutoCAD SHX Text B
AutoCAD SHX Text P
AutoCAD SHX Text B
AutoCAD SHX Text
SEAL-OFF FITTING (TYPICAL)
AutoCAD SHX Text
PUMP CABLE (TYPICAL)
AutoCAD SHX Text
PULL BOX (TYPICAL)
AutoCAD SHX Text
TO NEW UTILITY TRANSFORMER 120/240V-1 -3W
AutoCAD SHX Text M
AutoCAD SHX Text
NEW UTILITY METER
AutoCAD SHX Text
3-350 KCMIL,#4G,3"C
AutoCAD SHX Text
3-250 KCMIL,#4G,3"C
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
120/240V-1 -3WFROM WIREWAY
AutoCAD SHX Text
3-250 KCMIL,#4G,3"C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
POWER DISTRIBUTION BLOCKS (TYPICAL)
AutoCAD SHX Text
WIREWAY NEMA 4X (316 SS)
AutoCAD SHX Text
TO CONTROL CIRCUIT
AutoCAD SHX Text 2#10,#10G,3/4"C
AutoCAD SHX Text 2P300
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text 2#12,#12G,10#14,1"C
AutoCAD SHX Text
TO VALVE V-5
AutoCAD SHX Text
TO VALVE V-4
AutoCAD SHX Text 2#12,#12G,10#14,1"C
AutoCAD SHX Text
TO VALVE V-3
AutoCAD SHX Text 2#12,#12G,10#14,1"C
AutoCAD SHX Text
TO VALVE V-2
AutoCAD SHX Text 2#12,#12G,10#14,1"C
AutoCAD SHX Text
TO BLOWER BL-1
AutoCAD SHX Text 2#12,#12G,3/4"C
AutoCAD SHX Text
TO GENERATOR
AutoCAD SHX Text 4#12,2#12G,1"C
AutoCAD SHX Text P-2
AutoCAD SHX Text
12 HP
AutoCAD SHX Text
32.0 FLA (3 )
AutoCAD SHX Text
55.4 FLA (1 )
AutoCAD SHX Text
TO VALVE V-1
AutoCAD SHX Text 2#12,#12G,10#14,1"C
AutoCAD SHX Text
NEMA 4X (316 SS)
AutoCAD SHX Text
NEMA 4X (316 SS)
AutoCAD SHX Text
SIZE 1
AutoCAD SHX Text
NEMA 4X (316 SS)
AutoCAD SHX Text
(FUTURE)
AutoCAD SHX Text
(FUTURE)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E402
TCD
TCD
JAC
GENERAL NOTES
KEY NOTES
EAST RESTROOM BUILDING
PUMP STATION RISER DIAGRAM
WEST RESTROOM BUILDING
PUMP STATION RISER DIAGRAM
EAST RESTROOM BUILDING
PUMP STATION ONE LINE DIAGRAM
WEST RESTROOM BUILDING
PUMP STATION ONE LINE DIAGRAM
AutoCAD SHX Text
1. THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA THE PUMP STATION CONTROL PANEL SHALL INCLUDE A NEMA 4X STAINLESS STEEL ENCLOSURE; SURGE PROTECTIVE DEVICE; LOAD CENTER FOR DISTRIBUTING POWER; POWER SUPPLIES; INTERIOR LIGHT (INTERLOCKED WITH PANEL DOOR); THERMOSTATICALLY CONTROLLED ANTI-CONDENSATION HEATER; VENTILATION FAN, ETC. 2. FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT FIELD VERIFY EXISTING CONDITIONS TO DETERMINE EXTENT OF WORK AND INCLUDE ALL COSTS ASSOCIATED WITH DEMOLITION IN BASE BID. 3. COORDINATE DEMOLITION WORK WITH OTHER TRADES. COORDINATE DEMOLITION WORK WITH OTHER TRADES. DISCONNECT AND REMOVE ALL CONDUIT, WIRING, AND DEVICES ASSOCIATED WITH EQUIPMENT BEING REMOVED. EXPOSED CONDUIT AND DEVICES SHALL BE DISCONNECTED AND REMOVED; CONCEALED CONDUIT CAN BE ABANDONED IN PLACE. ALL WIRING SHALL BE COMPLETELY REMOVED BACK TO ITS SOURCE. 4. PUMP STATION CONTROL PANEL SHALL INCLUDE AN PUMP STATION CONTROL PANEL SHALL INCLUDE AN INTEGRAL SURGE PROTECTIVE DEVICE (SPD). SPD SHALL PROVIDE L-N, L-G, L-L, AND N-G PROTECTION.
AutoCAD SHX Text
1. COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH COORDINATE EXACT CONDUIT SIZE REQUIREMENTS WITH LEVEL PROBE MANUFACTURER. 2. CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% CONDUIT SIZES INDICATED DO NOT TAKE INTO ACCOUNT 25% MAXIMUM CONDUCTOR FILL PERMITTED BY NEC FOR CONDUIT SEALS. CONTRACTOR SHALL ADJUST CONDUIT SIZES BASED ON ACTUAL CABLE SIZE. 3. PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE PROVIDE WIRE AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. 4. SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS SURGE PROTECTION DEVICE (SPD) MINIMUM RATING IS 80kA/PHASE. 5. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. PROVIDE NAMEPLATE TO IDENTIFY COLOR CODING OF WIRING. 6. PUMP CONTROL PANEL SHALL BE UL LABELED FOR PUMP CONTROL PANEL SHALL BE UL LABELED FOR AVAILABLE FAULT CURRENT.
AutoCAD SHX Text
AutoCAD SHX Text
NEW 120/240V-1PH-3W FROM PDP-WC CIRCUIT 6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text
CB
AutoCAD SHX Text
AutoCAD SHX Text
SEAL-OFF FITTING (TYPICAL)
AutoCAD SHX Text
PUMP CABLE (TYPICAL)
AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE CONDUIT SEAL-OFF AND SUSPENDED CABLE DETAIL, ON SHEET E602 (TYPICAL)
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
CP-ERPS 10K AIC RATING NEMA 4X, 316 SS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P-5
AutoCAD SHX Text
5 HP
AutoCAD SHX Text
15.2 FLA (3 )
AutoCAD SHX Text
26.3 FLA (1 )
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text
CB
AutoCAD SHX Text
SPD
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SEAL-OFF FITTING (TYPICAL)
AutoCAD SHX Text
PUMP CABLE (TYPICAL)
AutoCAD SHX Text PROVIDE HEAVY DUTY SUPPORT GRIP AT CONDUIT TERMINATION POINT, SEE CONDUIT SEAL-OFF AND SUSPENDED CABLE DETAIL, ON SHEET E602 (TYPICAL)
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text
CB
AutoCAD SHX Text
TO CONTROL CIRCUIT
AutoCAD SHX Text
CB
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text 3#3,#8G,1-1/4"C
AutoCAD SHX Text
EAST RESTROOM BUILDING PUMP STATION CONTROL PANEL (CP-ERPS)
AutoCAD SHX Text
AutoCAD SHX Text
ALARM LIGHT
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
PUMP STATION WETWELL
AutoCAD SHX Text
AutoCAD SHX Text
FLOAT SWITCH CABLE
AutoCAD SHX Text
LSH-1
AutoCAD SHX Text
LSL-1
AutoCAD SHX Text
LEVEL TRANSDUCER
AutoCAD SHX Text
SEAL OFF FITTING (TYP.)
AutoCAD SHX Text
ALARM LIGHT
AutoCAD SHX Text
LE-1
AutoCAD SHX Text P-6
AutoCAD SHX Text P-5
AutoCAD SHX Text
TO PDP-WC CIRCUIT 6
AutoCAD SHX Text
MFR'S CABLES, 3/4"C
AutoCAD SHX Text
MFR'S CABLE, 3/4"C
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text 3#3,#8G,1-1/4"C
AutoCAD SHX Text
PUMP STATION WETWELL
AutoCAD SHX Text
AutoCAD SHX Text
FLOAT SWITCH CABLE
AutoCAD SHX Text
LSH-2
AutoCAD SHX Text
LSL-2
AutoCAD SHX Text
LEVEL TRANSDUCER
AutoCAD SHX Text
SEAL OFF FITTING (TYP.)
AutoCAD SHX Text
LE-2
AutoCAD SHX Text P-4
AutoCAD SHX Text P-3
AutoCAD SHX Text
MFR'S CABLES, 3/4"C
AutoCAD SHX Text
MFR'S CABLE, 3/4"C
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text
PUMP CABLE, 1"C
AutoCAD SHX Text
CP-WRPS 10K AIC RATING NEMA 4X, 316 SS
AutoCAD SHX Text
WEST RESTROOM BUILDING PUMP STATION CONTROL PANEL (CP-WRPS)
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
EXISTING 120/240V-1PH-3W FROM PDP-EC CIRCUIT 12
AutoCAD SHX Text 3#3,#8G,1-1/4"C
AutoCAD SHX Text
TO PDP-EC CIRCUIT 12
AutoCAD SHX Text 3#3,#8G,1-1/4"C
AutoCAD SHX Text
LINE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
LINE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
SPD
AutoCAD SHX Text
AutoCAD SHX Text
TO CONTROL CIRCUIT
AutoCAD SHX Text
LINE
AutoCAD SHX Text
VFD
AutoCAD SHX Text
LINE
AutoCAD SHX Text
VFD
AutoCAD SHX Text P-6
AutoCAD SHX Text
5 HP
AutoCAD SHX Text
15.2 FLA (3 )
AutoCAD SHX Text
26.3 FLA (1 )
AutoCAD SHX Text P-3
AutoCAD SHX Text
5 HP
AutoCAD SHX Text
15.2 FLA (3 )
AutoCAD SHX Text
26.3 FLA (1 )
AutoCAD SHX Text P-4
AutoCAD SHX Text
5 HP
AutoCAD SHX Text
15.2 FLA (3 )
26.3 FLA (1 )
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E601
TCD
TCD
JAC
GENERAL NOTES
SUBMERSIBLE PUMP P-1 VFD WIRING DIAGRAM
EQ TANK PUMP STATION CONTROL PANEL WIRING DIAGRAM
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text THE FOLLOWING DEVICES SHALL BE PROVIDED IN THE PUMP CONTROL PANEL BUT ARE NOT SHOWN FOR CLARITY: 120VAC TRANSIENT VOLTAGE SURGE SUPPRESSER, 24VDC POWER SUPPLIES, INTRINSICALLY SAFE BARRIERS, GFI CONVENIENCE RECEPTACLE, INTERIOR LIGHT, COOLING FAN, CONDENSATE HEATER, THERMOSTAT(S) AND OTHER DEVICES LISTED IN THE SPEC. DRY CONTACTS FOR THE FOLLOWING SIGNALS SHALL BE WIRED TO A TERMINAL STRIP TO INTERFACE WITH THE SCADA MISSION RTU. ALARMS: EQ TANK LOW LEVEL (CR1) [DISCRETE] EQ TANK HIGH LEVEL (CR2) [DISCRETE] PUMP P-1 VFD FAULT (CRF) [DISCRETE] PUMP P-1 HIGH TEMP SHUTDOWN (CR4) [DISCRETE] PUMP P-1 SEAL LEAK DETECTED (CR5) [DISCRETE] PUMP P-2 VFD FAULT (CRF) [DISCRETE] PUMP P-2 HIGH TEMP SHUTDOWN (CR6) [DISCRETE] PUMP P-2 SEAL LEAK DETECTED (CR7) [DISCRETE STATUS: PUMP P-1 RUN STATUS (CRR) [DISCRETE] PUMP P-2 RUN STATUS (CRR) [DISCRETE] SPD STATUS [DISCRETE] ALL WIRING TO/FROM THIS PANEL AND OTHER ENCLOSURES/EQUIPMENT SHALL BE INSTALLED IN CONDUIT. MINIMUM CONDUCTOR SIZE FOR POWER IS #12, FOR CONTROL IS #14. CIRCUIT BREAKER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS INCLUDED IN SUBMERSIBLE PUMP CONTROL PACKAGE. PROVIDE WIRING AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH NEC. CIRCUIT BREAKER AND FUSE SIZES SHALL BE DETERMINED BY CONTROL PANEL FABRICATOR. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CONTROL POWER ON
AutoCAD SHX Text
LOW LEVEL FLOAT SWITCH LSL-3
AutoCAD SHX Text
ISR-1
AutoCAD SHX Text
HIGH LEVEL FLOAT SWITCH LSH-3
AutoCAD SHX Text
ISR-2
AutoCAD SHX Text
CR1
AutoCAD SHX Text
ISR-1
AutoCAD SHX Text
INTRINSICALLY SAFE RELAY (TYPICAL)
AutoCAD SHX Text
CR2
AutoCAD SHX Text
ISR-2
AutoCAD SHX Text
CR3
AutoCAD SHX Text
CR1
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR3
AutoCAD SHX Text
EQ TANK LOW LEVEL
AutoCAD SHX Text
EQ TANK HIGH LEVEL
AutoCAD SHX Text
OVERRIDE PUMP CONTROL
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR4
AutoCAD SHX Text
CR5
AutoCAD SHX Text
PUMP P-1 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-1 SEAL LEAK DETECTED
AutoCAD SHX Text
PUMP P-1 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-1 SEAL LEAK DETECTED
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR6
AutoCAD SHX Text
CR7
AutoCAD SHX Text
PUMP P-2 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-2 SEAL LEAK DETECTED
AutoCAD SHX Text
PUMP P-2 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-2 SEAL LEAK DETECTED
AutoCAD SHX Text
CONTACTS SHOWN IN ALARM STATE
AutoCAD SHX Text
CONTACT SHOWN IN NORMAL STATE
AutoCAD SHX Text
P-1 HIGH TEMP AND SEAL LEAK SENSORS
AutoCAD SHX Text
P-2 HIGH TEMP AND SEAL LEAK SENSORS
AutoCAD SHX Text
P-1 HIGH TEMP AND SEAL LEAK RELAY
AutoCAD SHX Text
P-2 HIGH TEMP AND SEAL LEAK RELAY
AutoCAD SHX Text
(CONTINUES ABOVE)
AutoCAD SHX Text
(CONTINUED FROM BELOW)
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
COMPACTLOGIX PLC
AutoCAD SHX Text WET WELL LEVEL FROM LEVEL TRANSDUCER (LE-3) (#16TSP,3/4"C; 4-20mA)
AutoCAD SHX Text
CR9
AutoCAD SHX Text
CR9
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR8
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR1
AutoCAD SHX Text
CR8
AutoCAD SHX Text
WET WELL LOW LEVEL
AutoCAD SHX Text
WET WELL HIGH LEVEL
AutoCAD SHX Text
ALARM BEACON
AutoCAD SHX Text R
AutoCAD SHX Text
CR10
AutoCAD SHX Text
TEST
AutoCAD SHX Text
CR8
AutoCAD SHX Text
CR9
AutoCAD SHX Text
CR10
AutoCAD SHX Text
CRF (FROM P-1 VFD)
AutoCAD SHX Text
CRF (FROM P-2 VFD)
AutoCAD SHX Text SPEED CONTROL LOOPED TO VFDs (#16TSP, 4-20mA)
AutoCAD SHX Text
PLC-AUTO (TO P-1 VFD)
AutoCAD SHX Text
CR5 (TO P-2 VFD)
AutoCAD SHX Text
(TYPICAL FOR P-2)
AutoCAD SHX Text
CR10
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
PLC-AUTO (TO P-2 VFD)
AutoCAD SHX Text
CR1 (TO PLC)
AutoCAD SHX Text
CR2 (TO PLC)
AutoCAD SHX Text
CR3 (TO P-1 VFD)
AutoCAD SHX Text
CR4 (TO P-1 VFD)
AutoCAD SHX Text
CR6 (TO P-1 VFD)
AutoCAD SHX Text
CB
AutoCAD SHX Text
UPS
AutoCAD SHX Text W
AutoCAD SHX Text
CRP
AutoCAD SHX Text
CRP (TO PLC)
AutoCAD SHX Text
CONTROL POWER ON
AutoCAD SHX Text
CR5 (TO PLC)
AutoCAD SHX Text
CR4 (TO PLC)
AutoCAD SHX Text
CR7 (TO PLC)
AutoCAD SHX Text
CR6 (TO PLC)
AutoCAD SHX Text
SPD FAILURE (TO PLC)
AutoCAD SHX Text
UPS FAULT (TO PLC)
AutoCAD SHX Text
UPS LOW BATTERY (TO PLC)
AutoCAD SHX Text
CB
AutoCAD SHX Text
DS
AutoCAD SHX Text
CONTROL PANEL LIGHT
AutoCAD SHX Text
LED
AutoCAD SHX Text
PANELVIEW PLUS
AutoCAD SHX Text
PANELVIEW PLUS
AutoCAD SHX Text
CB
AutoCAD SHX Text
ENCLOSURE AIR CIRCULATION FAN
AutoCAD SHX Text
TS
AutoCAD SHX Text
CB
AutoCAD SHX Text
TS
AutoCAD SHX Text
ENCLOSURE HEATER
AutoCAD SHX Text
GFCI DUPLEX RECEPTACLE
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
MISSION RTU
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR1
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
CRF
AutoCAD SHX Text
AutoCAD SHX Text
HIGH LEVEL
AutoCAD SHX Text
LOW LEVEL
AutoCAD SHX Text
PUMP 1 TROUBLE
AutoCAD SHX Text
PUMP 2 TROUBLE
AutoCAD SHX Text
CR4
AutoCAD SHX Text
CR5
AutoCAD SHX Text C
AutoCAD SHX Text
CRF
AutoCAD SHX Text
CR6
AutoCAD SHX Text
CR7
AutoCAD SHX Text
24 VDC POWER SUPPLY
AutoCAD SHX Text
CB
AutoCAD SHX Text
CR7 (TO P-2 VFD)
AutoCAD SHX Text
CR1 (TO RTU)
AutoCAD SHX Text
CR2 (TO RTU)
AutoCAD SHX Text
SPD FAILURE (TO RTU)
AutoCAD SHX Text
PUMP P-2 SEAL LEAK DETECTED
AutoCAD SHX Text
CR7 (TO RTU)
AutoCAD SHX Text
PUMP P-2 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
CR6 (TO RTU)
AutoCAD SHX Text
PUMP P-1 SEAL LEAK DETECTED
AutoCAD SHX Text
CR5 (TO RTU)
AutoCAD SHX Text
PUMP P-1 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
CR4 (TO RTUI)
AutoCAD SHX Text
CR3 (TO P-2 VFD)
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text
MISSION RTU
AutoCAD SHX Text
MISSION SYSTEM
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
GENERATOR CONTROL POWER
AutoCAD SHX Text
GENERATOR BLOCK HEATER
AutoCAD SHX Text
CB
AutoCAD SHX Text
CB
AutoCAD SHX Text
BLOWER BL-1
AutoCAD SHX Text
CB
AutoCAD SHX Text
POWER FOR VALVE V-1
AutoCAD SHX Text
CB
AutoCAD SHX Text
POWER FOR VALVE V-2
AutoCAD SHX Text
CB
AutoCAD SHX Text
POWER FOR VALVE V-3
AutoCAD SHX Text
CB
AutoCAD SHX Text
POWER FOR VALVE V-4
AutoCAD SHX Text
CB
AutoCAD SHX Text
POWER FOR VALVE V-5
AutoCAD SHX Text
OOX
AutoCAD SHX Text
XOO
AutoCAD SHX Text
CB
AutoCAD SHX Text
IN AUTO (TO PC)
AutoCAD SHX Text
OOX
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text
VFD
AutoCAD SHX Text 4-20mA SPEED CONTROL (FROM PLC)
AutoCAD SHX Text 4-20mA SPEED FEEDBACK (TO PLC)
AutoCAD SHX Text
HUMAN MACHINE INTERFACE
AutoCAD SHX Text
LINE REACTOR
AutoCAD SHX Text
CRF
AutoCAD SHX Text
FAN
AutoCAD SHX Text
CRR
AutoCAD SHX Text
ETM
AutoCAD SHX Text
FAULT
AutoCAD SHX Text
CRF
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CRR
AutoCAD SHX Text
RUNNING
AutoCAD SHX Text
THERMOSTAT (INSIDE VFD ENCLOSURE)
AutoCAD SHX Text
CR4 OR CR6 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
CR5 OR CR7 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
SHUTDOWN PUMP IN HAND AND AUTO MODES AND ENERGIZE CRF
AutoCAD SHX Text
SHUTDOWN PUMP IN AUTO MODE ONLY AND ENERGIZE CRF
AutoCAD SHX Text
PLC-AUTO (FROM PLC)
AutoCAD SHX Text
CR3 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
OPERATE AT 100% SPEED
AutoCAD SHX Text OPERATE AT SPEED BASED ON 4-20mA SPEED CONTROL INPUT
AutoCAD SHX Text
CRR RUN STATUS (TO PLC)
AutoCAD SHX Text
CRF FAULT STATUS (TO PLC)
AutoCAD SHX Text
CRR (FROM VFD-2)
AutoCAD SHX Text
PUMP P-1
AutoCAD SHX Text L1
AutoCAD SHX Text L2
AutoCAD SHX Text
CRR RUN STATUS (TO RTU)
AutoCAD SHX Text
CRF FAULT STATUS (TO RTU)
AutoCAD SHX Text L1
AutoCAD SHX Text L2
AutoCAD SHX Text L3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TO PUMP CONTROLLER
AutoCAD SHX Text N
AutoCAD SHX Text
(CONTINUES ABOVE)
AutoCAD SHX Text
(CONTINUES ABOVE)
AutoCAD SHX Text Y
AutoCAD SHX Text R
AutoCAD SHX Text
(CONTINUED FROM BELOW)
AutoCAD SHX Text
(CONTINUED FROM BELOW)
AutoCAD SHX Text L1
N
Drawn By
Hard copy is intended to be
24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2020
A l l R i g h t s R e s e r v e d
P L O
T
I N
F O
Z
C
A D
C
D E
D
Y O
U T
E
T
E
M
E
E
R
T
D W
Y E
R
R E V I S I O N S
NRT
191527
S t a
M i c h i g a n
D e p a r t m e n t o f
N a t u r a l
R e s o u r c e s
P a r k s a c r e a t i o n
D i v i s i o n
H o l l y
R e c r e a t i o n
A r e a
W a s t e w a t e r
S y s t e m
I m p r o v e m e n t s
DTMB File Number
751/18124.CDP
1/30/2020
PHASE 500
BIDS AND CONSTRUCTION
E602
TCD
TCD
JAC
GENERAL NOTES
SUBMERSIBLE PUMP P-5 VFD WIRING DIAGRAM
PUMP STATION CONTROL PANEL WIRING DIAGRAM
WEST RESTROOM BUILDING
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text THE FOLLOWING DEVICES SHALL BE PROVIDED IN THE PUMP CONTROL PANEL BUT ARE NOT SHOWN FOR CLARITY: 120VAC TRANSIENT VOLTAGE SURGE SUPPRESSER, 24VDC POWER SUPPLIES, INTRINSICALLY SAFE BARRIERS, GFI CONVENIENCE RECEPTACLE, INTERIOR LIGHT, COOLING FAN, CONDENSATE HEATER, THERMOSTAT(S) AND OTHER DEVICES LISTED IN THE SPEC. DRY CONTACTS FOR THE FOLLOWING SIGNALS SHALL BE WIRED TO A TERMINAL STRIP TO INTERFACE WITH THE SCADA MISSION RTU. ALARMS: WET WELL LOW LEVEL (CR1) [DISCRETE] WET WELL HIGH LEVEL (CR2) [DISCRETE] PUMP P-5 VFD FAULT (CRF) [DISCRETE] PUMP P-5 HIGH TEMP SHUTDOWN (CR4) [DISCRETE] PUMP P-5 SEAL LEAK DETECTED (CR5) [DISCRETE] PUMP P-6 VFD FAULT (CRF) [DISCRETE] PUMP P-6 HIGH TEMP SHUTDOWN (CR6) [DISCRETE] PUMP P-6 SEAL LEAK DETECTED (CR7) [DISCRETE STATUS: PUMP P-5 RUN STATUS (CRR) [DISCRETE] PUMP P-6 RUN STATUS (CRR) [DISCRETE] SPD STATUS [DISCRETE] ALL WIRING TO/FROM THIS PANEL AND OTHER ENCLOSURES/EQUIPMENT SHALL BE INSTALLED IN CONDUIT. MINIMUM CONDUCTOR SIZE FOR POWER IS #12, FOR CONTROL IS #14. CIRCUIT BREAKER TO BE SIZED BY CONTROL PANEL MANUFACTURER AS REQUIRED FOR LOADS INCLUDED IN SUBMERSIBLE PUMP CONTROL PACKAGE. PROVIDE WIRING AND CIRCUIT BREAKER SIZED IN ACCORDANCE WITH NEC. CIRCUIT BREAKER AND FUSE SIZES SHALL BE DETERMINED BY CONTROL PANEL FABRICATOR. PROVIDE INTRINSICALLY SAFE RELAYS OR BARRIERS ON ALL CIRCUITS THAT RUN TO HAZARDOUS LOCATIONS.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text
OOX
AutoCAD SHX Text
XOO
AutoCAD SHX Text
CB
AutoCAD SHX Text
IN AUTO (TO PC)
AutoCAD SHX Text
OOX
AutoCAD SHX Text H
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text
VFD
AutoCAD SHX Text FUTURE 4-20mA SPEED CONTROL (FROM PC)
AutoCAD SHX Text FUTURE 4-20mA SPEED FEEDBACK (TO PC)
AutoCAD SHX Text
HUMAN MACHINE INTERFACE
AutoCAD SHX Text
LINE REACTOR
AutoCAD SHX Text
CRF
AutoCAD SHX Text
FAN
AutoCAD SHX Text
CRR
AutoCAD SHX Text
ETM
AutoCAD SHX Text
FAULT
AutoCAD SHX Text
CRF
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CRR
AutoCAD SHX Text
RUNNING
AutoCAD SHX Text
THERMOSTAT (INSIDE VFD ENCLOSURE)
AutoCAD SHX Text
CR4 OR CR6 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
CR5 OR CR7 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
SHUTDOWN PUMP IN HAND AND AUTO MODES AND ENERGIZE CRF
AutoCAD SHX Text
SHUTDOWN PUMP IN AUTO MODE ONLY AND ENERGIZE CRF
AutoCAD SHX Text
PLC-AUTO (FROM PC)
AutoCAD SHX Text
CR3 (FROM PUMP CONTROL PANEL)
AutoCAD SHX Text
OPERATE AT 100% SPEED
AutoCAD SHX Text OPERATE AT SPEED BASED ON 4-20mA SPEED CONTROL INPUT
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CONTROL POWER ON
AutoCAD SHX Text
LOW LEVEL FLOAT SWITCH LSL-1
AutoCAD SHX Text
ISR-1
AutoCAD SHX Text
HIGH LEVEL FLOAT SWITCH LSH-1
AutoCAD SHX Text
ISR-2
AutoCAD SHX Text
INTRINSICALLY SAFE RELAY (TYPICAL)
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR4
AutoCAD SHX Text
CR5
AutoCAD SHX Text
PUMP P-1 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-1 SEAL LEAK DETECTED
AutoCAD SHX Text
PUMP P-1 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-1 SEAL LEAK DETECTED
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR6
AutoCAD SHX Text
CR7
AutoCAD SHX Text
PUMP P-2 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-2 SEAL LEAK DETECTED
AutoCAD SHX Text
PUMP P-2 HIGH TEMP SHUTDOWN
AutoCAD SHX Text
PUMP P-2 SEAL LEAK DETECTED
AutoCAD SHX Text
CONTACTS SHOWN IN ALARM STATE
AutoCAD SHX Text
CONTACT SHOWN IN NORMAL STATE
AutoCAD SHX Text
P-1 HIGH TEMP AND SEAL LEAK SENSORS
AutoCAD SHX Text
P-2 HIGH TEMP AND SEAL LEAK SENSORS
AutoCAD SHX Text
P-1 HIGH TEMP AND SEAL LEAK RELAY
AutoCAD SHX Text
P-2 HIGH TEMP AND SEAL LEAK RELAY
AutoCAD SHX Text
(CONTINUES ABOVE)
AutoCAD SHX Text
(CONTINUED FROM BELOW)
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
PUMP CONTROLLER (PC)
AutoCAD SHX Text WET WELL LEVEL FROM LEVEL TRANSDUCER (LE-1) (#16TSP,3/4"C; 4-20mA)
AutoCAD SHX Text
CR9
AutoCAD SHX Text
CR9
AutoCAD SHX Text
CR2
AutoCAD SHX Text
CR8
AutoCAD SHX Text
RESET
AutoCAD SHX Text
CR1
AutoCAD SHX Text
CR8
AutoCAD SHX Text
WET WELL LOW LEVEL
AutoCAD SHX Text
WET…