Plan.pdf
PDF 5 MB Posted
- Attached to
- 24-211137 - EVSE - MOUNT SHASTA - Project 10718
- Solicitation number
- 0000032641
- Issued by
- Shasta County, Siskiyou County, California
About this file
This document is a set of 100% construction drawings for an electrical vehicle supply equipment (EVSE) project at the California Department of Fish and Wildlife (CDFW) facility located at 3 North Old Stage Road in Mt. Shasta, California. The project involves the installation of electrical infrastructure to support the future installation of five Level II EVSE charging stations by the client. The scope of work includes the installation of conduits, wiring, a new electrical panel, transformer, and other equipment. The drawings are dated May 5, 2023 and were submitted for State Fire Marshal review on that date. The plans indicate the project is being managed by the California Department of General Services Real Estate Services Division.
The drawings provide details on the electrical single-line diagram, load schedules, site plan, and installation details for the EVSE equipment pads and electrical infrastructure. The project does not include the procurement or installation of the actual EVSE units, which will be handled by the client. Contractor responsibilities include the required saw cutting, trenching, backfilling, and surface restoration. The drawings indicate this project is intended for use by a designated vehicle or employee fleet, and will not be available for general public use.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf | ||
| Sign-in_Sheet.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2022 Microsoft Corporation © 2022 Maxar ©CNES (2022) Distribution Airbus DS
SITE MAP
VICINITY MAP
G0.0
NONE
CODES AND PREFERENCES SHEET INDEX
SYMBOLS AND ABBREVIATIONS
TITLE 19 CCR PUBLIC SAFETY, DIVISION 1, STATE FIRE MARSHAL REGULATIONS
TITLE 24 CCR, PART 1 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
TITLE 24 CCR, PART 2 2022 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1 AND 2 (2021 IBC, AS AMENDED BY CA)
TITLE 24 CCR, PART 3 2022 CALIFORNIA ELECTRICAL CODE (CEC) (2020 NEC, AS AMENDED BY CA)
TITLE 24 CCR, PART 8 2022 CALIFORNIA HISTORICAL BUILDING CODE
TITLE 24 CCR, PART 9 2022 CALIFORNIA FIRE CODE (CFC) (2021 IFC, AS AMENDED BY CA)
TITLE 24 CCR, PART 10 2022 EXISTING BUILDING CODE
TITLE 24 CCR, PART 11 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CAL GREEN CODE)
TITLE 24 CCR, PART 12 2022 CALIFORNIA REFERENCED STANDARDS CODE (SEE ALSO TITLE 24 CCR-PART 2, CHAPTER 35 -
REFERENCE STANDARDS AND TITLE 24 CCR - PART 9, CHAPTER 47 - REFERENCED STANDARDS)
EVSE DESCRIPTION SCOPE OF WORK
EXISTING EVSE SPACES NEW EVSE SPACES
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(5) LEVEL 2
FLEET WORKPLACE WORKPLACEFLEET
DISCONNECT SWITCH, NON-FUSIBLE, SEE PLANS FOR RATING
EXISTING TO BE REMOVED AND SALVAGED
EXISTING TO BE DEMOLISHED
NEW PLANS-FINAL LOCATION OF RELOCATED EQUIPMENT.
DEMO PLANS-EXISTING TO BE RELOCATED.
EXISTING TO REMAIN
(RS)
(D)
(RL)
(E)
ENCLOSED CIRCUIT BREAKER
GROUND FAULT PROTECTION
GREEN
GREEN
WHITE
WHITE
BLUE
RED
RED
BLACK
BLACK
240V
240Y/120V
POWER WIRE COLOR CODE
SYSTEM
208Y/120V
480Y/277V
PHASE A
BLACK
YELLOW
PHASE B
RED
BROWN
PHASE C
BLUE
ORANGE
NEUTRAL
WHITE
GRAY
GROUND
GREEN
GREEN
ELECTRICAL ABBREVIATIONS
INCOMING ELECTRIC SERVICE
GROUND
DISCONNECT SWITCH, FUSIBLE, SEE PLANS FOR RATING
FUSE
SWITCH
2S, 2W = 2 SPEED, 2 WINDING
RV=REDUCED VOLTAGE STARTING
FULL-VOLTAGE NON-REVERSING UNLESS NOTED
MAGNETIC MOTOR STARTER, NEMA SIZE INDICATED
MCP INDICATES MOTOR CIRCUIT PROTECTOR
3 POLE UNLESS NOTED
CIRCUIT BREAKER,
METERING
Y, SHEET WHERE DETAIL IS DRAWN
DETAIL CALL-OUT: X, DETAIL IDENTIFIER;
WITH EQUIPMENT
CONTROLLER/STARTER FURNISHED
+ 48" UON
+ 18" UON
FLOOR GRADE TO CENTERLINE OF DEVICE
INDICATES HEIGHT FROM FINISHED
SHEET NOTE, SEE NOTE INDICATED
SURFACE MOUNTED PANELBOARD-NEW, EXISTING
POWER DISTRIBUTION SWITCHBOARD
CONDUIT STUB-OUT AND CAPPED
CONDUIT BENDS AWAY FROM OBSERVER
CONDUIT BENDS TOWARD OBSERVER
BELOW GRADE, #4/0 UON
GROUNDING CONDUCTOR 30"
CURVE LINE INDICATES GROUND WIRE
WIRE SIZE OTHER THAN #12
GROUND WIRE
QUANTITY #12 WIRE CURVE LINE INDICATES
CONDUIT EXPOSED 3/4"C-2#12, 1#12G, UON
3/4"C-2#12, 1#12G, UON
CONDUIT UNDER GROUND
CEILING 3/4"C-2#12, 1#12G, UON
CONDUIT CONCEALED IN WALLS OR
PULLBOX
HAND HOLE, 11"Hx17"Lx12"D, UON
ELECTRICAL SYMBOLS - ONE LINE DIAGRAMELECTRICAL SYMBOLS - PLANS
JUNCTION BOX
SINGLE RECEPTACLE 120V, 20A GFCI TYPE
DUPLEX RECEPTACLE
EXISTING AREA LIGHT AND POLE
(AIP)
1"C-2#12, 1#12G
(U)(V"C-W#X,Y#Z)
EXAMPLE: (2)(3/4"C-2#12-1#12G) INDICATES TWO 3/4"
CONDUITS EACH WITH 2#12 AND 1#12G CONDUCTORS
ELECTRICAL SYMBOLS COMMON
SINGLE RUN OF RACEWAY AND CIRCUIT CONDUCTORS.
FIRST NUMBER IS RACEWAY SIZE.
THE FOLLOWING NUMBERS ARE THE CONDUCTOR
QUANTITIES AND SIZES.
A AMPERES
AMPERES INTERRUPTING CAPACITY, SYMMETRICAL
AMERICAN WIRE GAUGE
BARE COPPER
CONDUIT, CONDUCTOR
AICS
AWG
BC
C
CB CIRCUIT BREAKER
CKT CIRCUIT
CNTL CONTROL
CO CONDUIT ONLY
CT CURRENT TRANSFORMER
DTL DETAIL
DWG DRAWING
E EXISTING
G, GND GROUND
GFCI GROUND-FAULT CIRCUIT INTERRUPTER
HH HANDHOLE
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LTG LIGHTING
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
N NEUTRAL
NIC NOT IN CONTRACT
NO. NUMBER
P POLE
PB PUSH BUTTON, PULL BOX
PC PHOTO CELL
PH, Ø PHASE
PVC POLYVINYL CHLORIDE
REQ'D REQUIRED
SMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT
SW SWITCH
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
W WATTS, WIRE
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
NTS NOT TO SCALE
FLUSH MOUNTED PANELBOARD
EXISTING TO BE REMOVED AND REPLACED WITH NEW(RP)
ABOVE FINISHED GRADEAFG
BOLLARD
NEW PLANS: EXISTING TO NEW
INTERCEPTION POINT:
EVSE ELECTRICAL VEHICLE SUPPLY EQUIPMENT
LB FITTING
TEE FITTING
A-1,3
G
#10
PB
J
X
Y
+18"
RV
MCP
30A
M
F
GFP
LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT
(#)# CONDUIT CALLOUT REFERENCE WITH NUMBER OF CONDUITS
SHOWN IN PARENTHESIS.
PROJECT
LOCATION
PROJECT
WORKING AREA
(5 EVSE SPACES)
ELECTRICAL VEHICLE SUPPLY EQUIPMENT (EVSE) INSTALLED ON THIS PROJECT WILL NOT BE AVAILABLE TO THE GENERAL PUBLIC, AND IS INTENDED FOR
USE BY A DESIGNATED VEHICLE OR EMPLOYEE. ELECTRIC VEHICLE CHARGER PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
INSTALL AND ELECTRICALLY CONNECT EVSE INFRASTRUCTURE FOR MAKE READY INSTALLATION AS
SHOWN. CONTRACTOR TO PROVIDE AND INSTALL THE WIRING DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND OPERATIONAL SYSTEM INCLUDING REQUIRED TESTING.
CONTRACTOR SHALL ALSO PROVIDE THE REQUIRED SAW CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE AND RESTORE TO ORIGINAL CONDITION. EVSE CHARGER
PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
(0) LEVEL 1
(0) LEVEL 2
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLMJSV WP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
R
EE
NI
GN
E
LANOISSEFORP
DERETSI
G
ER
STATE OF CALIFORNIA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
POWER TRANSFORMER
FEEDER DESIGNATION SEE
CONDUIT/CONDUCTOR TABLE FOR SIZE
TITLE SHEET
HOMERUN TO PANEL A,
CIRCUIT 1 AND 3
ABANDON IN PLACE. (D) ABOVE GROUND CONDUITS &
CONNECTORS DOWN TO 3" BELOW GROUND LEVEL.
REMOVE AND (D) CONDUCTORS IN UG CONDUITS.
PLUG UG CONDUITS AND ABANDON IN PLACE.
MULTIPLE RUNS OF RACEWAY AND CIRCUIT CONDUCTORS
U = # OF PARALLEL RUNS
V = CONDUIT SIZE
W = # OF PHASE/NEUTRAL CONDUCTORS IN EA. CONDUIT
X = PHASE/NEUTRAL CONDUCTOR SIZE
Y = #OF GROUND CONDUCTORS IN EACH CONDUIT
Z = GROUND CONDUCTOR SIZE
V1
SFM APP #: 23-N-2010-C
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/14/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-2010
Issue Date: 8/27/2024
E0.0
NONE
ELECTRICAL NOTES
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLMJSVWP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
RE
EN
I
GN
E
LANOISSEFORP
DERETSI
GER
STATE OF CALIFORNIA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLM JSV WP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
RE
EN
I
GN
E
LANOISSEFORP
DERETSI
GER
STATE OF CALIFORNIA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
SPECIAL INSPECTIONS REQUIRED
CONCRETE CONSTRUCTION:
STEEL CONSTRUCTION:
CONT PERIODIC N/A
CONT PERIODIC N/A
GENERAL NOTES:
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/14/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
E1.0
NONE
SINGLE LINE DIAGRAM
AND SCHEDULES
480/277V MAIN SWITCHBOARD, NEMA 3R
(E) MSB
PB-EVSE
PANELBOARD, NEMA 1
150A, 120/208V, 3Ø, 4W, 60HZ, 22KAIC
200A BUS, 480/277V, 3Ø, 4W, 60HZ
(E) UTILITY XFMR
EXIST.
LOAD
SINGLE LINE DIAGRAM
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
VOLTAGE DROP CALCULATION
CDFW MT SHASTA
1. OCCUPANCY CLASSIFICATION STORAGE GROUP S
2. BUILDING CONSTRUCTION TYPE TYPE II
3. YEAR BUILT 1978
4. NUMBER OF STORIES 1
5. ACTUAL BUILDING HEIGHT 24'
6. BUILDING AREA IN SQUARE FEET (SPI) 4812
7. PROJECT AREA IN SQUARE FEET (i.e. TENANT IMPROVEMENTS) N/A
8. ALLOWABLE AREA PER C.B.C. N/A
9. AREA AND OR HEIGHT INCREASES N/A
10. FIRE SPRINKLERED (YES OR NO)
TYPE: (WET, DRY, PRE-ACTION, DELUGE)
NO
11. FIRE ALARM (YES OR NO)
TYPE: (MANUAL, AUTOMATIC, ETC.)
YES
AUTOMATIC
12. OTHER FIRE PROTECTION SYSTEMS IF ANY FIRE DETECTION SYSTEM
NOTES:
PB-EVSE PANEL SHALL BE USED FOR 0NLY 240V, 1Ø EVSE CHARGING STATIONS.
ELECTRICAL ION METER TO BE SUBMITTED AND APPROVED BY E.I.R.
MSB MAIN BREAKER TO BE UP-SIZED TO 200A, EXISTING INCOMMING CONDUCTORS
TO BE EVALUATED BY CONTRACTOR AT TIME OF INSTALLATION.
SECTION POSITION DESCRIPTION
LOAD
HP kVA A
1 TROJAN UV 3000
2 TRANSFORMER
3 (BLANK)
4 (BLANK)
5 PB EVSE 31 37.3
ESTIMATED LOAD MSB
TOTAL NEW CONNECTED LOAD 31.0 37.3
TOTAL DEMAND LOAD
AØ BØ CØ
(1) MAXIMUM DEMAND (BASED ON 1 YEAR OF UTILITY DATA)
(kVA)
(A) 0 0 0
(2) NEW CONNECTED LOAD
(kVA) 10.3 10.3 10.3
(A) 37.3 37.3 37.3
(3) TOTAL PROSPECTIVE LOAD
SUM OF (1) AND (2)
(kVA) 10 10 10
(A) 37.3 37.3 37.3
(4) FEEDER EVALUATION (NEC 220.87)
MAXIMUM DEMAND AT 125% PLUS NEW LOAD
(4)=1.25x(1)+(2)
(kVA) 10 10 10
(A) 37.3 37.3 37.3
EXIST. SWITCHBOARD 'MSB'
VERTICAL BUS BRACING
MAIN FUSE RATING
MAIN BREAKER INTR. RATING
MAX FAULT AT MAIN BREAKER
FEEDER SIZE
VERTICAL BUS RATING 200A
VOLTS 480/277V, 3Ø, 3W
TAG
ENCLOSURE TYPE NEMA 3R
LOCATION WAREHOUSE
MSB
200A
CONDUIT/ CABLE SCHEDULE
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLM JSV WP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
R
EE
NI
GN
E
LANOISSEFORP
DERETSI
G
ER
S TAT E OF CALIFORN IA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
200A
70A200A
PANEL SCHEDULE
3P
T-EVSE
45KVA
480-120/208VAC
3Ø,4W,60HZ
DS-EVSE
100A, 600V,3P
PAD LOCKABLE
SAFETY SWITCH (HEAVY DUTY)
INFORMATION ON EXISTING LOADS TO BE UPDATED AFTER UTILITY DATA HAS BEEN
OBTAINED. LOADS WILL BE DETERMINED BASED OFF OF 13 MONTHS OF EXITING
UTILITY DATA.
INSTALL A NEW CIRCUIT BREAKER MATCHING THE EXISTING BREAKER
MANUFACTURER, AND KAIC RATING ON EXISTING MAIN SWITCHBOARD (MSB).
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/14/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
E2.0
AS SHOWN
ELECTRICAL SITE PLAN
Know what's below.
before you dig. Call
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLM JSV WP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
R
EE
NI
GN
E
LANOISSEFORP
DERETSI
G
ER
STATE OF CALIFORNIA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
NEW 45KVA XFMR
NEW POWER POLE
NEW POWER POLE
NEW POWER POLE
EXISTING UTILITY POLE WITH TRANSFORMER
EXISTING 480V 200A PANEL
INSTALL NEW 70A BREAKER TO
FEED EV CHARGING
INFRASTRUCTURE
480 O/H LINE
EVSE OUTPUT CABLE LENGTH AS PER CEC 625.17.
EVSE WITH CABLE DE-ENERGIZING CAPABILITY.
EVSE WITH GROUND FAULT DETECTOR 5 MA.
EVSE EQUIPPED TO AVOID BACK-FEEDING FROM VEHICLE BATTERY TOWARD
POWER WIRES IN CASE OF PRIMARY POWER OUTAGE.
MINIMUM DISTANCE OF 3'-0" IS REQUIRED BETWEEN EVSE CHARGING STATION
AND EDGE OF PERMANENT BOLLARD.
EVSE DUAL PORT PEDESTAL (NIC)(TYP.)
EVSE-3
PB-EVSE-17/19
EVSE-2
PB-EVSE-9/11, 13/15
EVSE-1
PB-EVSE-1/3, 5/7
200 201
200 201
EVSE SINGLE PORT PEDESTAL (NIC)(TYP.)
(2)
NEW 480V DISCONNECT
NEW 225A PANEL
V1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/14/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
3 12" 3 12"
E3.0
NONE
ELECTRICAL DETAILS
3 NORTH OLD STAGE ROAD
MT SHASTA, CA 96067
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
RYAN ALLGOOD
Phone 916 375-4115 Fax 916 376-6216
RYAN.ALLGOOD@DGS.CA.GOV
05/05/23
100% CONSTRUCTION DRAWING
SFM SUBMITTAL
KKHLMJSV WP
EVSE LEVEL II
CDFW MT SHASTA
DEPARTMENT OF
GENERAL SERVICES
RE
EN
I
GN
E
LANOISSEFORP
DERETSI
GER
STATE OF CALIFORNIA
EXP. 9-30-23
No. 23575
ELECTRICAL
JON
ALVAREZ
CROWN CONCRETE
4" DIA GALVANIZED STEEL
PIPE. PRIME AND PAINT
2 COATS INDUSTRIAL
YELLOW ENAMEL
(E) CONCRETE
4' 0"
PERMANENT BOLLARD
3/4" HOLE
1/2" STEEL BASEPLATE
#3 @ 12", 1" CLR
BOTH DIRECTIONS (TYP.)
TOOLED EDGE 1"
EXISTING SLAB
ELECTRICAL EQUIPMENT
EQUIPMENT ANCHOR
PER SPECIFICATION
SECTION
16012 (TYP.)
#3 DOWELS, 3' ON CENTER (TYP.)
4" MIN (TYP. AROUND ALL SIDES)
3" CLR (TYP.)
EPOXY DOWEL INTO
EXISTING CONCRETE
SLAB
2" MIN.
EMBEDMENTROUGHENED
SURFACE (TYP.)
SECTION THROUGH NEW EQUIPMENT PAD ADDED TO
EXISTING SLAB
NOTES:
1. EQUIPMENT BASE TOP SHALL BE LEVEL.
2. PRIOR TO EQUIPMENT BASE INSTALLATION, EXISTING SLAB SURFACE SHALL
BE ROUGHENED.
1' -0
(M
IN
A D
JU
S T T
O B
O
LT
H O
LE
S O F P
A N E
LB
O A R D
(MIN.) 7" WIDER THAN
PANELBOARD
6" 6"
3/4" HOLE
PANELBOARD
P-1000 UNISTRUT
(TYP.)
BLINE
B140HDG
N225 2"x1-
2" HHCS
BLINE
B133HDG
N225 2"x1-
2" HHCS
BLINE
B281HDG
N225 2"x1-
2" HHCS
BLINE
B140HDG
N225 2"x1-
2" HHCS
1" GROUT
EQUIPMENT ANCHOR
PER SPECIFICATION
SECTION
16012 (TYP.)
NOTE:
1. ALL PART NUMBERS ARE SHOWN FOR REFERENCE. CONTRACTOR CAN
PROPOSE APPROVED EQUAL.
OVERHEAD POWER POLE - QUAD
5/8"X10" LONG MACH. BOLT, SQ. HD.
WITH SQ. NUT, H.D. GALV.
2 1/4" SQ. WASHER, 3/16" THICK FOR
5/8" BOLT, H.D. GALV.
PREFORMED DISTRIBUTION - GRIP
DEAD END
600V WIRE, QUAD
CABLE CONNECTOR
CLASS 5, 35 FT. POWER POLE, PENTA
OR CUNAP TREATED DOUGLAS FIR.
PANELBOARD SUPPORT
ELECTRICAL EQUIPMENT PAD
OVER EXISTING SLAB
NOTE:
1. POLE LINE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE STATE OF
CALIFORNIA "RULES FOR OVERHEAD ELECTRIC LINE CONSTRUCTION
GENERAL ORDER NO. 95."
15" MIN.
5 EVSE SERVICE PEDESTAL
NONE
FINISHED GRADE
INSTALL FLUSH WITH
FINISHED PAVED OR
CONCRETE SURFACES.
BTC POWER
DUAL PORT PEDESTAL
NOTES:
1. BTC CHARGER TO BE INSTALLED BY VENDOR.
FRONT VIEW SIDE VIEW
V1
1" EMT CONDUIT
1" EMT WATERPROOF MALE CONNECTOR
1" RIGID COUPLING
1" LFMC
1" LFMC MALE CONNECTOR
1" LFMC MALE CONNECTOR
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
06/14/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-2010
1'- 0"
℄ OF SIGN TO BE CENTERED
AT STALL
(E)
ASPHALT
PAVING
OR
CONCRET
E
5- '0"
EVSEFLEET SIGNAGE6
AUTHORIZED
FLEET
USE
ONLY
| Sheets and Views |
| G0.0 cover sheet-E1.0 |
File details come from the government source that posted it. Updated .