Plan.pdf
PDF 15 MB Posted
- Solicitation number
- 0000031962
- Issued by
- San Luis Obispo County, San Luis Obispo City, California
About this file
This document is an Advertisement for Bids issued by the California Department of General Services for the Department of State Hospitals, San Luis Obispo County. The project, titled "23-203084. OS. EVSE - ATASCADERO STATE HOSPITAL. 8401," involves the installation and electrical connection of electric vehicle supply equipment (EVSE) infrastructure, including wiring devices and all required associated items for a complete and operational system. The project scope also includes saw cutting, trenching, backfilling, and finishing of the affected lot surface to restore it to original condition. The project is being bid in accordance with Government Code 14838.7 and is open only to Small Business and Micro Business contractors certified through the California Department of General Services, Office of Small Business and DVBE Services. Bids are due by 2:00 PM on the bid opening date, and a mandatory virtual pre-bid site inspection tour will be held on July 22, 2024.
The estimated cost for the project is $240,500, and the term is 60 calendar days. As a condition of contract award, the successful bidder must submit copies of valid Certificates of Reported Compliance for any fleet vehicles used in the completion of the work, as required by the California Air Resources Board In-Use Off-Road Diesel Fueled Fleet Regulations. The contractor and all subcontractors must also abide by all health and safety mandates issued by federal, state, and local governments, as well as those issued by the Department of General Services.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf | ||
| Project_8401_RFBI_02_Response.pdf | ||
| 01-Project_8401_RFBI_1.pdf | ||
| Bid_Package_Document.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Atascadero State Hospital EVCS Installation
100% Construction Drawings
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. ACCESSIBLE ROUTE (A.R.) IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS A BARRIER FREE ACCESS WITHOUT ANY ABRUPT VERTICAL CHANGES EXCEEDING ½” AT 1:2 MAXIMUM SLOPE, EXCEPT THAT LEVEL CHANGES DO NOT EXCEED ¼” VERTICAL (11B-303 & 11B-403.4.). A.R. IS A MINIMUM OF 48” WIDE (11B-403.5.1 EXCEPTION 3) BARRIER-FREE ROUTE WITH SLIP-RESISTANT SURFACE. THE RUNNING SLOPE SHALL BE 5% MAX. IN THE DIRECTION OF TRAFFIC FLOW AND THE CROSS SLOPE SHALL NOT BE STEEPER THAN 1:48 (11B-403.3). PASSING SPACES (11B-403.5.3) OF 60”X60” MIN. ARE LOCATED NOT MORE THAN 200' APART. WALKS WITH CONTINUOUS GRADIENTS HAVE 60” IN LENGTH OF LEVEL AREAS (11B-403.7) NOT MORE THAN 400' APART. A.R. SHALL BE MAINTAINED FREE OF OVERHANGING OBSTRUCTIONS TO 80” MIN.
(11B-307.4) AND FREE OF PROTRUDING OBJECTS (11B-307) GREATER THAN 4” PROJECTION FROM WALL ABOVE 27” AND LESS THAN 80”. OBJECTS PROTRUDING INTO THE A.R. SHALL NOT REDUCE THE CLEAR WIDTH OR MANEUVERING SPACE REQUIRED FOR ACCESSIBLE ROUTES (11B-307.5). THERE IS NO DROP-OFF OVER 4” AT THE EDGE OF WALK OR LANDING UNLESS IDENTIFIED BY A GUARD, A HANDRAIL, OR A WARNING CURB AT LEAST 6” IN HEIGHT ABOVE THE WALK (11B-303.5).
6. DESIGN PROFESSIONAL IN GENERAL RESPONSIBLE CHARGE STATEMENT: THE ACCESSIBLE ROUTE (A.R.) IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS COMPLIANT WITH THE CURRENT APPLICABLE CALIFORNIA BUILDING CODE ACCESSIBILITY PROVISIONS FOR ACCESSIBLE ROUTE REQUIREMENTS FOR THE INSTALLATION OF ELECTRIC VEHICLE CHARGING STATIONS (11B-812.5). AS PART OF THE DESIGN OF THIS PROJECT, THE ACCESSIBLE ROUTE WAS EXAMINED BASED ON APPROXIMATE FIELD MEASUREMENTS AND ANY ELEMENTS, COMPONENTS OR PORTIONS OF THE ACCESSIBLE ROUTE THAT WERE DETERMINED TO BE NONCOMPLIANT 1) HAVE BEEN IDENTIFIED AND 2) THE CORRECTIVE WORK NECESSARY TO BRING THEM INTO COMPLIANCE HAS BEEN INCLUDED WITHIN THE SCOPE OF THIS PROJECT'S WORK THROUGH DETAILS, DRAWINGS AND SPECIFICATIONS INCORPORATED INTO THESE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL FIELD VERIFY ALL SLOPES/GRADES AND DIMENSIONS TO CONFIRM THE CORRECTIVE WORK
NECESSARY.
7. ANY EXISTING NONCOMPLIANT ELEMENTS, COMPONENTS OR PORTIONS OF THE ACCESSIBLE ROUTE THAT WILL NOT BE CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD LIMITATIONS OR A FINDING OF UNREASONABLE
HARDSHIP ARE SO INDICATED IN THESE CONSTRUCTION DOCUMENTS.
8. DURING CONSTRUCTION, IF ACCESSIBLE ROUTE ITEMS WITHIN THE SCOPE OF THE PROJECT REPRESENTED AS CODE COMPLIANT ARE FOUND TO BE NONCONFORMING BEYOND REASONABLE CONSTRUCTION TOLERANCES, THE CONTRACTOR SHALL BRING THESE ITEMS INTO COMPLIANCE WITH THE CBC AS A PART OF THIS PROJECT AND THE FULL
SCOPE OF WORK SHALL BE IDENTIFIED ON THE PROJECT RECORD DRAWINGS.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
BUILDING INFORMATION: BUILDING 506
LOCATION MAP
NOT TO SCALE
PROJECT TEAM
ACCESSIBLE EVCS MOUNTING HEIGHT
INDEX OF DRAWINGS
SCOPE OF WORK
FINISHED FLOOR
4'-0"
MAX.
EVCS CHARGING HANDLE
ELECTRIC VEHICLE CHARGING
STATION (EVCS)
(MAY DIFFER FROM ACTUAL)
R
CALL 811 BEFORE YOU DIG.
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
ACCESSIBILITY NOTE:
ACCESS TO ELECTRIC VEHICLE CHARGING
STATIONS (EVCS) SHALL CONFORM TO THE
LATEST OR THE 2010 ADA ACCESSIBILITY
STANDARDS (CHAPTER 3, SECTION 308 AND 309)
AND 2022 CBC 11B-308 AND 309.
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON ST., SUITE 301,
CORONA, CA. 92879
(951) 340-1977
CONTACT: ED BURTCH
STRUCTURAL ENGINEERCIVIL ENGINEER
PROJECT
LOCATION
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN ARC-FLASH
HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL CONTRACTOR, IN
COMPLIANCE TO THE REQUIREMENTS OF THE LATEST CEC 110.16.
AN ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE
LATEST NFPA 70E - 130.5, SHALL BE PERFORMED BY THE ELECTRICAL
CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD
WARNING LABEL/MARKING TEMPLATE/S SHALL BE SUBMITTED TO THE
EEOR FOR REVIEW AND APPROVAL.
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (17) FUTURE ELECTRIC
VEHICLE CHARGING STATION (EVCS) PORTS WITHIN THE ATASCADERO STATE
HOSPITAL FACILITY.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (2) NEW PANELBOARDS
AND (1) NEW TRANSFORMER AS WELL AS NEW FEEDERS TO THE FUTURE EVCS PORTS
LOCATIONS AS SHOWN ON THESE PLANS. PROJECT INCLUDES STRUCTURAL AND
CIVIL WORK EFFORT/S NECESSARY TO SUPPORT THIS PROJECT. SEE SHEET E1.00
FOR A SUMMARY OF THE FUTURE EVCS PORTS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
CONSTRUCTION TYPE: TYPE V
OCCUPANCY CLASSIFICATION: BUSINESS GROUP B
OCCUPANCY LOAD: 11
ACTUAL BUILDING HEIGHT: ~13'-0", 1 STORY
BUILDING AREA (SQ. FT.) 1,350
AREA OF PROJECT (SQ. FT.) PARKING LOT E: 3,500
GEN. BUILDING: 3,000
TOTAL: 6,000
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: PARKING LOT E: 3,500
GEN. BUILDING: 3,000
TOTAL: 6,000
AREA INCREASED: N/A
HEIGHT INCREASED: N/A
FIRE SPRINKLERS: NO
FIRE ALARM: YES
OTHER FIRE PROTECTION SYSTEMS: NO
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1954
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
EXISTING DSA NUMBER: 02-115909
*NOTE: AREA OF WORK AT GENERATOR BUILDING IS ALL EXTERIOR.
KPFF
140 NEWPORT CENTER DRIVE, SUITE 100
NEWPORT BEACH, CA 92660
(949) 478-8800
CONTANT: ALI KHAMSI
KPFF
18400 VON KARMAN AVE., SUITE 600
IRVINE, CA 92612
(949) 252-1022
CONTACT: CHRISTOPHER DOMINAS
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 20 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 20 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 20 E1.00 SITE PLAN
4 OF 20 E2.00 PARKING LOT E POWER PLAN
5 OF 20 E2.01 GENERATOR BLDG. PARKING LOT POWER PLANS
6 OF 20 E4.00 ELECTRICAL DETAILS
7 OF 20 E4.01 ELECTRICAL DETAILS
8 OF 20 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
9 OF 20 E5.01 SINGLE LINE DIAGRAM & SCHEDULES
10 OF 20 C0.01 TITLE SHEET
11 OF 20 C1.00 COMPOSITE SITE PLAN
12 OF 20 C1.10S EROSION CONTROL AND DEMOLITION PLAN
13 OF 20 C1.30S GRADING AND SITE PLAN
14 OF 20 C1.40N SITE PLAN
15 OF 20 C5.00 DETAILS
16 OF 20 S-001 GENERAL NOTES
17 OF 20 S-002 SPECIAL INSPECTION TABLES
18 OF 20 S-101 PLANS
19 OF 20 S-102 EQUIPMENT ANCHORAGE DETAILS
20 OF 20 S-103 EQUIPMENT ANCHORAGE DETAILS
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
18400 Von Karman Ave., Suite 600
Irvine, CA 92612
O: 949.252.1022
F: 949.252.8082 www.kpff.com
No. 5913
Exp. 12/31/25
BUILDING INFORMATION: BUILDING 506
INDEX OF DRAWINGS
CONSTRUCTION TYPE: TYPE V
OCCUPANCY CLASSIFICATION: BUSINESS GROUP B
OCCUPANCY LOAD: 11
ACTUAL BUILDING HEIGHT: ~13'-0", 1 STORY
BUILDING AREA (SQ. FT.) 1,350
AREA OF PROJECT (SQ. FT.) PARKING LOT E: 3,500
GEN. BUILDING: 3,000
TOTAL: 6,000
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: PARKING LOT E: 3,500
GEN. BUILDING: 3,000
TOTAL: 6,000
AREA INCREASED: N/A
HEIGHT INCREASED: N/A
FIRE SPRINKLERS: NO
FIRE ALARM: YES
OTHER FIRE PROTECTION SYSTEMS: NO
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1954
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
EXISTING DSA NUMBER: 02-115909
*NOTE: AREA OF WORK AT GENERATOR BUILDING IS ALL EXTERIOR.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 21 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 21 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 21 E1.00 SITE PLAN
4 OF 21 E2.00 PARKING LOT E POWER PLAN
5 OF 21 E2.01 GENERATOR BLDG. PARKING LOT POWER PLANS
6 OF 21 E4.00 ELECTRICAL DETAILS
7 OF 21 E4.01 ELECTRICAL DETAILS
8 OF 21 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
9 OF 21 E5.01 SINGLE LINE DIAGRAM & SCHEDULES
10 OF 21 C0.01 TITLE SHEET
11 OF 21 C1.00 COMPOSITE SITE PLAN
12 OF 21 C1.01S PARKING LOT E SITE PLAN
13 OF 21 C1.10S EROSION CONTROL AND DEMOLITION PLAN
14 OF 21 C1.30S GRADING AND SITE PLAN
15 OF 21 C1.40N SITE PLAN
16 OF 21 C5.00 DETAILS
17 OF 21 S-001 GENERAL NOTES
18 OF 21 S-002 SPECIAL INSPECTION TABLES
19 OF 21 S-101 PLANS
20 OF 21 S-102 EQUIPMENT ANCHORAGE DETAILS
21 OF 21 S-103 EQUIPMENT ANCHORAGE DETAILS
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
TEST MARK (For DSA Use Only) Prior to adding document to the Session the Plan Reviewer shall place this test mark off the top edge of the first sheet and change status to "INCORPORATE". If Back-check menu does not show or the color does not change to green, the Plan Reviewer shall fix the back-check menu. For guidance on how to fix the back-check menu, refer to "_DSA EPR Support > Help Desk > Fixing Back Check Menu" DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
05/02/2024
Issue Date: 6/17/2024
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT WALL MOUNTED
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT WALL MOUNTED ELECTRIC
VEHICLE CHARGING STATION
T TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX.
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX.
F
FENCE
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 AMERICA WITH DISABILITIES ACT STANDARDS
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
SAN RAFAEL RD.
SA
N
R
AF
AE
L
R D
BANE ST.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SA
N
R
AF
AE
L
R D
SCALESITE PLAN 11' = 150'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
SITE PLAN
E1.00
EVCS SUMMARY
LOCATIONS SHEET EXISTING EVCS SPACES NEW EVCS SPACES PARKING TYPE
PARKING LOT E E2.00 (0) LEVEL 1 (0) LEVEL 2 (0) LEVEL 1 (8) LEVEL 2 WORKPLACE
GEN. BLDG. PARKING LOT E2.01 (0) LEVEL 1 (0) LEVEL 2 (0) LEVEL 1 (9) LEVEL 2 FLEET
TOTAL NUMBER OF PORTS: (17) LEVEL 2
E2.01
E2.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
T
(E) SWITCHBOARD 'PK-3'
(E) TRANSFORMER
(E) POWER POLE
EV
CHARGING
ONLYEV
CHARGING
ONLYEV
CHARGING
ONLYEV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
PB
PB
(E) CMU RETAINING WALL
3'-0" (TYP.)
1 7(TYP. UON)
2 7
2 7
PB
PANELBOARD 'EV1'108 11
1" PVC CONDUIT
4#6 & 1#8 GRD.
FARTHEST RUN: ~68'-0"
VOLTAGE DROP: 1.12%1" PVC CONDUIT
4#6 & 1#8 GRD.
1" PVC CONDUIT
4#6 & 2#10 GRD.
1" PVC CONDUIT
2#6 & 1#10 GRD.
1 1/2" PVC CONDUIT
8#6 & 2#8 GRD.
1" PVC CONDUIT
4#6 & 1#8 GRD.
2 1/2" PVC CONDUIT
4#4/0 & 1#4 GRD.
EVCS-3
EVCS-4
EVCS-8
EVCS-7
EVCS-6
EVCS-5
EVCS-1
EVCS-2
10EV
CHARGING
ONLY
EV
CHARGING
ONLY
NO
PARKING
SCALEPARKING LOT E POWER PLAN 11/8" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
PARKING LOT E
POWER PLAN
E2.00
R
CALL 811 BEFORE YOU DIG.
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH 7200VA
PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6
+ 1#8 GRD) COILED UP FOR FINAL EVCS
INSTALLATION AT EVCS STUB-UP LOCATION. SEE
DETAIL #1 SHEET E4.00.
SINGLE PORT PEDESTAL TYPE EVCS WITH
7200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (2#6 + 1#10 GRD) COILED UP FOR FINAL
EVCS INSTALLATION AT EVCS STUB-UP
LOCATION. SEE DETAIL #2 SHEET E4.00.
SEE DETAIL #7 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL FOR ROUTING BELOW
ASPHALT. FOR ALL VEHICULAR TRAFFIC
CROSSINGS PROVIDE SCHEDULE 80 PVC
UNDERGROUND CONDUIT.
SEE DETAIL #6 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL FOR ROUTING BELOW
NATIVE SOIL.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
PROVIDE 24" X 24" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANELBOARD
FEEDERS. REFER TO DETAIL #4 ON SHEET E4.01
FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
PROVIDE 30" X 30" X 30" WEATHERPROOF PULL
BOX TO ROUTE CONDUCTORS THROUGH THE
BOTTOM OF THE EXISTING RETAINING WALL AND
UNDERGROUND TO AVOID PENETRATING THE
CONCRETE WALL FOOTING.
PROVIDE 24" X 24" X DEPTH AS REQUIRED
WEATHERPROOF GUTTER TO EXTEND
CONDUCTORS FROM EXISTING SWITCHBOARD
AND ROUTE UNDERGROUND AS SHOWN. BOLT
DOWN TO EXISTING CONCRETE PAD.
NEW ACCESSIBLE ROUTE TO EXISTING BUILDING
506. REFER TO CIVIL DRAWINGS FOR
ADDITIONAL INFORMATION.
NEW NEMA 3R PANELBOARD SURFACE
MOUNTED ON SUPPORTS. REFER TO
STRUCTURAL DRAWINGS FOR MOUNTING
INFORMATION.
PROVIDE 18" X 18" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
GENERAL NOTES:
1. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE REPRESENTATIVE.
2. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
3. PROVIDE MINIMUM OF 3'-0" CLEARANCE BEHIND
ALL PEDESTAL TYPE CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
4. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
5. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND IRRIGATION IMPROVEMENTS
AFFECTED IN WORK.
LEGEND:
EXISTING
CMU BLOCK WALL
NEW
NEW UNDERGROUND
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
PB
(E) DISTRIBUTION
BOARD 'DPA'
PB
(E) GENERATOR
(E) ELECTRIFIED
FENCING
(E) TANK
13(TYP.)
5'-0"
(TYP.)
EVCS-2 EVCS-3 EVCS-4 EVCS-5 EVCS-6 EVCS-7 EVCS-9
1" PVC CONDUIT
4#6 & 1#8 GRD.
(2) 1" PVC CONDUIT
4#6 & 1#8 GRD.
PBPBPB
1" PVC CONDUIT
2#6 & 1#10 GRD.
(3) 1" PVC CONDUIT
4#6 & 1#8 GRD.
T
(1) 1" PVC CONDUIT
2#6 & 1#10 GRD.
(2) 1 1/2" PVC CONDUIT
8#6 & 2#8 GRD.
18'-0"
3'-0"
(TYP.)
EVCS-8
9'-0"
EVCS-1
18'-0" 18'-0"
TRANSFORMER 'T-EV'1198
PANELBOARD 'EV2' 6 8
8 11
1 7 2 7
(TYP. UON)
3(TYP. UON)
5 (TYP. UON)
4 4
FARTHEST RUN: ~85'-0"
VOLTAGE DROP: 1.40%
2'-0"
2'-0"
SCALEGENERATOR BUILDING PARKING LOT POWER PLAN 11/16" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
GENERATOR BLDG.
PARKING LOT
POWER PLANS
E2.01
R
CALL 811 BEFORE YOU DIG.
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH 7200VA
PER PORT. PROVIDE 10'-0" OF FEEDER WIRE (4#6
+ 1#8 GRD) COILED UP FOR FINAL EVCS
INSTALLATION AT EVCS STUB-UP LOCATION. SEE
DETAIL #1 SHEET E4.00.
SINGLE PORT PEDESTAL TYPE EVCS WITH
7200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (2#6 + 1#10 GRD) COILED UP FOR FINAL
EVCS INSTALLATION AT EVCS STUB-UP
LOCATION. SEE DETAIL #2 SHEET E4.00.
SEE DETAIL #7 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL FOR ROUTING BELOW
ASPHALT. FOR ALL VEHICULAR TRAFFIC AND
ELECTRIFIED FENCE CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
SEE DETAIL #6 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL FOR ROUTING BELOW
NATIVE SOIL.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
NEW NEMA 3R PANELBOARD SURFACE
MOUNTED ON SUPPORTS. REFER TO
STRUCTURAL DRAWINGS FOR MOUNTING
INFORMATION.
SEE DETAIL #4 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #1 & #2 SHEET E4.01 FOR
TRANSFORMER GROUND RING AND GROUND
ROD DETAILS.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANELBOARD
FEEDERS. REFER TO DETAIL #4 ON SHEET E4.01
FOR MORE INFORMATION. SEE STRUCTURAL
DRAWINGS FOR MOUNTING INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.01 FOR
MORE INFORMATION.
PROVIDE 17" X 30" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
PROVIDE 13" X 24" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #3
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
GENERAL NOTES:
1. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE REPRESENTATIVE.
2. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
3. PROVIDE MINIMUM OF 3'-0" CLEARANCE BEHIND
ALL PEDESTAL TYPE CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
4. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
5. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND IRRIGATION IMPROVEMENTS
AFFECTED IN WORK.
SCALEENLARGED POWER PLAN 23/16" = 1'-0"
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
PARKING CALCULATION SUMMARY
EXISTING PARKING SPACES:
TOTAL PARKING SPACES: 0
NEW EVCS SPACES:
FLEET EVCS SPACES: 8
VAN ACCESSIBLE EVCS SPACES: N/A
ACCESSIBLE EVCS SPACES: N/A
TOTAL EVCS SPACES: 8
TOTAL PARKING SPACES: 8
NOTES:
1. FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE
GENERAL PUBLIC AND ARE INTENDED FOR USE BY A
DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE FLEET EVCS SHALL
NOT BE REQUIRED TO COMPLY WITH CBC 11B-228.3.2
ACCESS REQUIREMENTS.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 4N.T.S.
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 5N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
6"
MIN.
STEEL COUPLING WITH
THREADED PLUG
FINISH GRADE
PVC CONDUIT
TRANSITION
COUPLING
CONTINUOUS RIGID GALVANIZED
STEEL CONDUIT WRAPPED AROUND
WITH 40 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
CONTINUOUS RIGID
GALVANIZED STEEL
CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
3'-0"
MIN.
FINISH GRADE
PVC CONDUIT
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
PVC COUPLING WITH
THREADED PLUG
PVC CONDUIT
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL (ASPHALT PAVEMENT) 7N.T.S.
12"
24"
MIN.
CONDUIT/S PER PLAN
3" CLEAN SAND
BEDDING
NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS REQUIRED IF SCHEDULE 80 PVC IS USED 2'-0"
BELOW GRADE LEVEL. SEE POWER PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NEW ASPHALT PAVEMENT EXISTING ASPHALT PAVEMENT
EXISTING BASE
CRUSHED AGGREGATE BASE
RECOMPACTED TO 95%
RLATIVE COMPACTION
3"
6"
ELECTRICAL
WARNING TAPE
NATIVE BACKFILL
90% COMPACTION
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL (NATIVE SOIL) 6N.T.S.
12"
GRADE LEVEL
24"
MIN.
ELECTRICAL
WARNING TAPE
CONDUIT/S PER PLANS
3" CLEAN SAND
BEDDING
NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS REQUIRED IF SCHEDULE 80 PVC IS USED 2'-0"
BELOW GRADE LEVEL. SEE POWER PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NATIVE BACKFILL
90% COMPACTION
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 8N.T.S.
SCALE
UNDERGROUND PULLBOX DETAIL 3N.T.S.
GRAVEL
BASE
ELECTRICAL CONDUITS
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
RATED PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
NATIVE BACKFILL
90% COMPACTION
2'-0"
MIN.
GRAVEL
BASE
ELECTRICAL CONDUITS
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
NATIVE BACKFILL
95% COMPACTION
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC RATED
PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
BASE
(TYPICAL)
AC PAVEMENT
(TYPICAL)
2'-0"
MIN.
NATIVE SOIL
APPLICATION
ASPHALT
APPLICATION
NOTE:
REFER TO SHEET NOTES ON SHEET E2.00
FOR SPECIFIC PULLBOX DIMENSIONS.
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
SCALE
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1N.T.S.
NEW CONCRETE EVCS FOOTING.
SEE STRUCTURAL DRAWINGS FOR
MORE INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. PULLBOX PLACEMENT SHOWN HERE IS DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL REFER TO POWER PLANS FOR
SPECIFIC PULLBOX LOCATION.
3. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
FINISH GRADE
1" PVC CONDUIT
4#6 & 1#8 GRD.
DUAL PORT PEDESTAL
EV CHARGING STATION
PROVIDE 3'-0" PVC
CONDUIT STUB-UP
WITH CONDUIT PLUG
AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP
DETAIL #4 ON THIS
SHEET.
UNDERGROUND PULLBOX.
REFER TO DETAIL #3 ON
THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL
SHALL CORRESPOND TO
CHARGER NUMBER. REFER
TO DETAIL #8 ON THIS
SHEET.
SCALE
SINGLE PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 2N.T.S.
4'-0"
MAX.
FRONT
ELEVATION
NEW CONCRETE EVCS FOOTING.
SEE STRUCTURAL DRAWINGS FOR
MORE INFORMATION.
SIDE
ELEVATION
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. PULLBOX PLACEMENT SHOWN HERE IS DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL REFER TO POWER PLANS FOR
SPECIFIC PULLBOX LOCATION.
3. SINGLE PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
FINISH GRADE
1" PVC CONDUIT
2#6 & 1#10 GRD.
UNDERGROUND PULLBOX.
REFER TO DETAIL #3 ON
THIS SHEET.
SINGLE PORT PEDESTAL
EV CHARGING STATION
PROVIDE 3'-0" PVC
CONDUIT STUB-UP
WITH CONDUIT PLUG
AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP
DETAIL #4 ON THIS
SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL
SHALL CORRESPOND TO
CHARGER NUMBER. REFER
TO DETAIL #8 ON THIS
SHEET.
PEDESTAL PLATE
2'-4"
3"
1'-1/2"
1'-1/2"
INCOMING 1"
CONDUIT THRU
3"X3" OPENING
PEDESTAL PLATE
2'-4"
3"
1'-1/2"
1'-1/2"
INCOMING 1"
CONDUIT THRU
3"X3" OPENING
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
DIGITAL MULTI-METER DETAIL 4N.T.S.
SCALE
PANELBOARD DETAIL 3N.T.S.
SCALE
GROUND ROD DETAIL 2N.T.S.
GR
OU
ND
COVER SHALL HAVE CAST
LETTERING "GROUND"
1 CUBIC FT.
MIN. 3/4" GRAVEL
3/4"Ø X 10'-0"L
COPPER GROUND
ROD
PRE-CAST CONCRETE
BOX 10"W x 17"L x 12"D
OPEN BOTTOM
GROUNDING WIRE
CONNECTED TO
EQUIPMENT
GROUND ROD CLAMP
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
GR
OU
ND
GR
OU
ND
PAD MOUNTED
TRANSFORMER
REFER TO STRUCTURAL
SHEETS FOR EQUIPMENT
PAD INFORMATION
GROUNDING ROD
(SEE DETAIL #2 ON
THIS SHEET)
BARE COPPER GROUND
PER PLANS
(TYPICAL)EQUIPMENT GROUNDING
CONNECTION
GROUNDING ROD
(SEE DETAIL #2 ON
THIS SHEET)
SCALE
GROUND RING DETAIL 1N.T.S.
NOTE:
1. THE GROUND RING SHALL BE INSTALLED NOT LESS THAN 30" BELOW FINISH SURFACE
PER NEC 250.53.
VIN
I1 I2 I3 I4
DIGITAL MULTI-METER
WITH NEMA-3R
ENCLOSURE
3/4"C - 3#12
& 1#12 GRD.
TYPICAL
PANELBOARD
CURRENT
TRANSFORMER
(TYP. OF 3)
(TYP. OF 3) 2
NOTES:
PROVIDE DIGITAL MULTI-METER WITH CAPABILITIES
OF MONITORING INCOMING PANELBOARD
FEEDERS. METER SHALL BE CAPABLE OF
MONITORING KHW, MAX PEAK DEMAND AMPS AND
VOLTAGE.
1-AMP IN-LINE FUSES.
TYPICAL ELECTRIC PANEL
(NEMA-3R). MAY DIFFER
FROM ACTUAL.
FINISH GRADEFINISH GRADE
CONCRETE FOOTING. REFER
TO STRUCTURAL DRAWINGS
FOR MORE INFORMATION.
SEE STRUCTURAL DRAWINGS
FOR MOUNTING INFORMATION.
INCOMING AND OUTGOING
CONDUIT/S. SEE POWER
PLANS FOR SIZING AND
QUANTITY. (TYP.)
DIGITAL MULTI-METER.
SEE DETAIL #4 ON THIS
SHEET FOR MORE
INFORMATION.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
ELECTRICAL
DETAILS
E4.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
SINGLE LINE DIAGRAM 1N.T.S.
LEGEND:
EXISTING
NEW
SHEET NOTES:
PROVIDE NEW CIRCUIT BREAKER. SIZE AS
SHOWN. MATCH TO EXISTING MAKE, MODEL AND
AIC RATING.
INCOMING SERVICE FROM
LA DEPT. OF POWER
UTILITY TRANSFORMER
XFMR 'U47730'
112.5KVA
4160V-208Y/120V 3Ø, 4W %Z =5.00%
NEMA-3R
SWITCHBOARD 'PK-3'
600A, 208Y/120V, 3Ø, 4W
NEMA-3R, 65,000 AIC
600A 3P
400A 3P
250A 3P
100A 3P
225A 3P
BLDG.
BLOCKS 2
BLDG.
BLOCKS 1
& RES. 8
CAPT.
(E ) F
E E
D E
R
(E ) F
E E
D E
R
(E ) F
E E
D E
R
(E ) F
E E
D E
R
(E) FEEDER
2 1/2"C - 4#4/0
& 1#4 GRD.
L: ~25'-0"
%V.D.: NEGL.
PANEL
'EV1'
IF=5,863
1,000A BUS
(GENERAL ELECTRIC SPECTRA SERIES)
IF=6,236A
IF=6,076A
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
SINGLE LINE DIAGRAM 1N.T.S.
LEGEND:
EXISTING
NEW
INCOMING
FEEDERS
(E ) F
E E
D E
R
1,600A 3P
SWITCHBOARD 'DPE'
1,600A, 480Y/277V, 3Ø, 4W
NEMA-3R, 65,000 AIC (CUTLER-HAMMER POW-R-LINE C)
30A 3P
225A 3P
100A 3P
TC-3
(E ) F
E E
D E
R
EG-3
(E ) F
E E
D E
R
TSG3
(E ) F
E E
D E
R
225A 3P
225A 3P
TA-3
(E ) F
E E
D E
R
TB-3
(E ) F
E E
D E
R
1,200A 3P
TS-3
(E ) F
E E
D E
R
SHEET NOTES:
PROVIDE NEW CIRCUIT BREAKER. SIZE AS
SHOWN. MATCH TO EXISTING MAKE, MODEL AND
AIC RATING.
SEE DETAILS #1 & #2 SHEET E4.01 FOR
TRANSFORMER GROUND RING AND GROUND
ROD DETAILS.
100A 3P
XFMR 'T-EV'
75KVA
480V-208Y/120V 3Ø, 4W %Z = < 5.00%
NEMA-3R
DISC. SWITCH
200A-3P
WP, NON-FUSED
1 1/2"C - 3#1
& 1#8 GRD.
L: ~210'-0"
%V.D.: 1.05%
1"C-1#4 TO
GROUND ROD
IF=8,391A
PANEL
'EV2'
IF=4,483A
2 1/2"C - 4#4/0
& 1#4 GRD.
L: ~15'-0"
%V.D.: NEGL.
IF=4,656A
225A 3P
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
E. Torres
E.Burtch
As Noted
A ta sc ad er o
S ta te H os pi ta l
E V
C S
In st al la tio n
123-01-02.23
7/18/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 23-S-3370-C
95% CD SubmittalEB6/09/20231
100% CD SubmittalEB7/18/20232
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
TITLE SHEET
C0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
SAN RAFAEL RD.
SA
N
R
AF
AE
L
R D
BANE ST.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SAN RAFAEL RD.
SA
N
R
AF
AE
L
R D
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
COMPOSITE SITE PLAN
C1.00
PROJECT AREA
"SOUTH"
SEE SHEETS
C1.01S C1.10S C1.30S C5.00
PROJECT AREA
"NORTH"
SEE SHEETS
C1.40N
C5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
EV
CHARGING
ONLYEV
CHARGING
ONLYEV
CHARGING
ONLYEV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
NO
PARKING
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
PARKING LOT E SITE
PLAN
C1.01S
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
EROSION CONTROL AND
DEMOLITION PLAN
C1.10S
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
EVCHARGINGONLY
EVCHARGINGONLY
EVCHARGINGONLY
EVCHARGINGONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
PB
PB
PB
NO
PARKING
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
GRADING AND PAVING
PLAN
C1.30S
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
09/27/23
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-3370
EVCHARGINGONLY
EVCHARGINGONLY
EVCHARGINGONLY
EVCHARGINGONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
PB
PB
PB
NO
PARKING
DSA
D E P A R T M E N T O F G E N E R A L S E R V I C E S
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
DSA
DIVISION OF THE STATE ARCHITECT
IDENTIFICATION STAMP
DIV. OF THE STATE ARCHITECT
APP: INC:
REVIEWED FOR
SS FLS ACS
DATE:
03-123860
OUTER PERIMETER ROAD
INNER PERIMETER ROAD
PBPBPB
T
PB
PB
PB
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
El
C am in o
Re al
At as ca de ro
, C A
AG
JP
As Noted
At as ca de ro S ta te
H os pi ta l
EV
C S
In st al la tio n
123-01-02.23
6/09/2023
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD SubmittalJP6/09/20231
140 Newport Center Drive, Suite 100 Newport Beach, CA 92660 O: 949.478.8800 www.kpff.com
100% CD SubmittalJP7/18/20232
SITE PLAN
C1.40N
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .