Plan.pdf
PDF 4 MB Posted
- Attached to
- DOT D7 - EVSE - VENTURA FIELD OFFICE - PN
- Solicitation number
- 0000040351
- Issued by
- Ventura County, California
About this file
This is a construction plan document for the California Department of Transportation (Caltrans) District 7 Ventura Field Office Electric Vehicle Supply Equipment (EVSE) installation project, prepared by Goss Engineering, Inc. in coordination with the California Department of General Services (DGS) Office of Sustainability. The project involves the installation of infrastructure to support two Level 2 electric vehicle charging stations within a parking lot at the Ventura Field Office, a 2,300 square foot building constructed in 1967. The scope of work includes the replacement of an existing lighting and power distribution panelboard, installation of new electrical feeders and underground conduit to supply power to two dual-port pedestal-mounted charging stations designated for fleet vehicles only, installation of concrete bollards, new parking signage, removal and replacement of parking lot striping, and all associated civil and structural work. The project requires compliance with the 2022 California Building Code, 2022 California Electrical Code, 2022 California Fire Code, and applicable NFPA standards. Major deliverables include third-party testing of new feeder conductors, arc-flash hazard analysis and labeling per NFPA 70E, short-circuit studies per IEEE 399, and final arc-flash assessment studies per IEEE 1584 standards.
The contract is available for bid only to Small Business and Micro Business contractors certified through the California Department of General Services, and requires a C-10 electrical contractor license as a condition of bidding. Contractors must submit valid Certificates of Reported Compliance (CRCs) for any fleet vehicles subject to California Air Resources Board In-Use Off-Road Diesel-Fueled Fleet Regulations. The electrical contractor is responsible for maintaining all equipment in a safe manner, providing necessary barriers and safety measures during construction, performing special inspections for concrete work and post-installed anchors, and ensuring coordination with other trades and the site owner representative. A minimum of 72 hours' notice is required prior to any circuit shutdown or facility disruption, and contractors are required to call 811 before digging for underground utilities. The project drawings are 100% construction documents dated November 25, 2024, with State Fire Marshal approval issued March 23, 2025, and final approval through September 11, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (2) ELECTRIC VEHICLE
CHARGING STATION (EVCS) PORTS WITHIN THE VENTURA FIELD OFFICE. SEE EVCS
NOTE ON THIS SHEET.
THE ELECTRIC VEHICLE SUPPLY EQUIPMENT IS MADE UP OF (1) REPLACED
PANELBOARD AS WELL AS NEW FEEDERS TO THE EVCS PORTS LOCATIONS AS SHOWN
ON THESE PLANS. PROJECT INCLUDES STRUCTURAL AND CIVIL WORK EFFORT/S
NECESSARY TO SUPPORT THIS PROJECT. SEE SHEET E1.00 FOR A SUMMARY OF THE
EVCS PORTS.
ALL EVSE INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSPECTION OF THE EVSE, SUCH WORK IS WITHIN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 11 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 11 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 11 E1.00 SITE PLAN
4 OF 11 E2.00 POWER PLAN
5 OF 11 E4.00 ELECTRICAL DETAILS
6 OF 11 E5.00 SINGLE LINE DIAGRAM & SCHEDULES
7 OF 11 C1.00 SITE IMPROVEMENT PLAN
8 OF 11 S0.01 GENERAL NOTES
9 OF 11 S0.02 SPECIAL INSPECTIONS
10 OF 11 S2.00 PARKING LOT EQUIPMENT SUPPORT PLAN
11 OF 11 S4.00 STRUCTURAL DETAILS
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA FIRE
CODE, 2022 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE OWNER OF THE CONDITIONS. THE OWNER WILL, AFTER CONSULTATION WITH
THE OWNER'S REPRESENTATIVE, DETERMINE A FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIME WITH OWNER. MINIMUM 72-HOURS NOTICE IS REQUIRED
BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION OF FACILITY PERSONNEL FUNCTIONING.
GENERAL NOTES
BUILDING INFORMATION
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION
(EVCS) SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT STATE ELECTRIC
VEHICLE CHARGING STATION VENDOR. ALL
FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
CONSTRUCTION TYPE: V-B
OCCUPANCY CLASSIFICATION: B
OCCUPANCY LOAD: 15
ACTUAL BUILDING HEIGHT: 12 FT.
BUILDING AREA (SQ. FT.) 2,300 SQ. FT.
AREA OF PROJECT (SQ. FT.) 1,000 SQ. FT.
SEPARATED OR NON-SEPARATED USE: NON-SEPARATED
ALLOWABLE AREA: 9,000 SQ. FT.
AREA INCREASED: NONE
HEIGHT INCREASED: NONE
FIRE SPRINKLERS: NO
FIRE ALARM: NO
OTHER FIRE PROTECTION SYSTEMS: FIRE EXTINGISHER
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1967
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: NO
PROJECT TEAM
PROJECT DIRECTOR
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON STREET, SUITE 301,
CORONA, CA 92879
(951) 340-1977
CONTACT: ED BURTCH
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(279) 782-3872
CONTACT: ANN WATSON
PROJECT
LOCATION
Caltrans District 7 Ventura Field Office
EVSE Installation
100% Construction Drawings
COMMERCIAL DEVELOPMENT RESOURCES
695 TOWN CENTER DRIVE, SUITE 110,
COSTA MESA, CA 92626
(949) 610-8997
CONTACT: AARON M. ALBERTSON
MRP PLANNING CO.
130 CENTENNIAL WAY, UNIT C,
TUSTIN, CA 92780
(714) 923-8946
CONTACT: MIKE PAAR
ARC-FLASH NOTE:
ALL NEW ELECTRICAL SWITCHBOARDS, PANELBOARDS,
EQUIPMENT/DEVICES AND SUCH, SHALL BE PROVIDED WITH AN ARC-FLASH
HAZARD WARNING LABEL/MARKING BY THE ELECTRICAL CONTRACTOR, IN
COMPLIANCE TO THE REQUIREMENTS OF THE LATEST CEC 110.16.
AN ARC-FLASH ASSESSMENT STUDY WHICH SHALL ADHERE WITH THE
LATEST NFPA 70E - 130.5, SHALL BE PERFORMED BY THE ELECTRICAL
CONTRACTOR.
THE ARC-FLASH ASSESSMENT STUDY AND THE ARC-FLASH HAZARD
WARNING LABEL/MARKING TEMPLATE/S SHALL BE SUBMITTED TO THE
EEOR FOR REVIEW AND APPROVAL.
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013973
BUILDING INFORMATION NOTE:
INFORMATION PROVIDED IS FOR THE VENTURA FIELD OFFICE. THE EVSE
WORK SHALL CONNECT INTO AN EXISTING ELECTRICAL PANELBOARD.
OSFM PERMIT NUMBER: 24-S-4517
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T H
C
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
PROJECT NUMBER: 000000000013973; 09/11/26
http://www.gossengineering.com
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
T
TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
ELECTRICAL GENERAL NOTES
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2022 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2021 INTERNATIONAL BUILDING CODE)
2022 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2020 NATIONAL ELECTRIC CODE)
2022 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2021 INTERNATIONAL FIRE CODE)
2022 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2022 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2022 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2019 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2022 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2022 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH STUDIES SHALL BE PROVIDED FOR LOW VOLTAGE (480 V, 208 V, 120 V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THE STUDY SHALL INCLUDE ALL PORTIONS OF THE ELECTRICAL DISTRIBUTION SYSTEM (WITHIN THE PROJECT SCOPE OR AS DEFINED BY THE EEOR) SUPPLIED BY NORMAL AND ALTERNATE SOURCES OF POWER. THIS INCLUDES SWITCHGEAR, SWITCHBOARDS, PANEL BOARDS, MOTOR CONTROL CENTERS, TRANSFORMERS, GENERATORS AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THE ANALYSIS WILL INCLUDE CREATION OF ARC-FLASH HAZARD WARNING LABELS. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS. THE CONTRACTOR WILL SUBMIT TO THE EEOR FOR APPROVAL AND INSTALL THE LABELS. PROVIDE A CURRENT, UP-TO-DATE SHORT CIRCUIT CURRENT STUDY. IF ONE DOES NOT EXIST, THEN PERFORM A SHORT CIRCUIT STUDY IN ACCORDANCE WITH IEEE 399 STANDARD (BROWN BOOK), “IEEE RECOMMENDED PRACTICE FOR INDUSTRIAL AND COMMERCIAL POWER SYSTEM ANALYSIS,” BASED UPON THE POSITIVE AND ZERO SEQUENCE SOURCE IMPEDANCE SUPPLIED BY THE LOCAL ENERGY PROVIDER. ALL STUDIES SHALL BE SUBMITTED TO THE EEOR FOR REVIEW AND APPROVAL.
10. PERFORM AN ARC FLASH HAZARD ANALYSIS AFTER THE SHORT CIRCUIT AND PROTECTIVE DEVICE COORDINATION STUDIES HAVE BEEN COMPLETED BASED UPON IEEE 1584 STANDARD, “IEEE GUIDE FOR PERFORMING ARC FLASH HAZARD CALCULATIONS.” THE ANALYSIS SHALL BE CALCULATED BY MEANS OF THE
SKM POWER TOOLS FOR WINDOWS COMPUTER SOFTWARE PACKAGE. PERTINENT DATA, RATIONALE
EMPLOYED, AND ASSUMPTIONS IN DEVELOPING THE CALCULATIONS SHALL BE INCORPORATED IN THE INTRODUCTORY REMARKS OF THE STUDY. THE ANALYSIS SHALL BE IN ACCORDANCE WITH APPLICABLE NFPA 70E, OSHA 29-CFR, PART 1910 SUBPART S AND IEEE 1584 STANDARDS. INCIDENT ENERGIES AND HAZARD CATEGORIES MUST BE CALCULATED. THE USE OF THE NFPA “TABLE METHOD” IS UNACCEPTABLE. BASED ON THE RESULTS OF THE INCIDENT ENERGY STUDY, THE SELECTED VENDOR SHALL PRODUCE AND INSTALL A WARNING LABEL (ORANGE <40 CAL/CM2) OR DANGER LABEL (RED > 40 CAL/CM2) APPROXIMATELY 4” X 6” (BRADY MULTI-COLOR OR EQUIVALENT) FOR EVERY POINT IN THE SYSTEM AS SPECIFIED SYSTEM EQUIPMENT SHOWN ON THE ONE-LINE DIAGRAM. LABELS WILL BE IN ACCORDANCE WITH ANSI Z535.4-2002 LISTING ITEMS 1-8 ABOVE. ALSO, INCLUDE THE BUS NAME, SYSTEM OPERATING VOLTAGE, AND DATE OF ISSUE. THE LABEL MUST
BE READABLE IN BOTH INDOOR AND OUTDOOR ENVIRONMENTS FOR AT LEAST 3 YEARS.
a. DETERMINE THE FOLLOWING:
· ARC HAZARD BOUNDARY (INCHES)
· WORKING DISTANCE (INCHES)
· ARC FLASH INCIDENT ENERGY AT THE WORKING DISTANCE (CALORIES/CM2)
· PPE CATEGORY AND DESCRIPTION INCLUDING THE GLOVE RATING
· VOLTAGE RATING OF THE EQUIPMENT
· LIMITED APPROACH DISTANCE (INCHES)
· RESTRICTED APPROACH DISTANCE (INCHES)
· PROHIBITED APPROACH DISTANCE (INCHES)
b. PRODUCE ARC FLASH EVALUATION SUMMARY SHEETS LISTING THE FOLLOWING ADDITIONAL ITEMS.
· BUS NAME
· UPSTREAM PROTECTIVE DEVICE NAMES, TYPE AND SETTINGS
· BUS LINE-TO-LINE VOLTAGE
· BUS BOLTED FAULT
· PROTECTIVE DEVICE BOLTED FAULT CURRENT
· ARCING FAULT CURRENT
· PROTECTIVE DEVICE TRIP / DELAY TIME
· BREAKER OPENING TIME
· SOLIDLY GROUNDED COLUMN
· EQUIPMENT TYPE
· GAP
· ARC FLASH BOUNDARY
· WORKING DISTANCE
· INCIDENT ENERGY
· REQUIRED PROTECTIVE FIRE RATED CLOTHING TYPE AND CLASS
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
T
(E) ASPHALT
PAVEMENT
(E) 20'-0" MANUAL
ROLLING GATE
WITH PADLOCK
(E) 20'-0" MANUAL
SWING GATE WITH
PADLOCK
(E) UNPAVED AREA
(E) UNPAVED AREA
(E) FENCE
(E) FRONT BUILDING
ENTRANCE
(E) REAR BUILDING
ENTRANCE
(E) PEDESTRIAN
GATE
(E) CMU
BLOCK WALL
(E) FENCE
UNOBSTRUCTED FIRE
APPARATUS ACCESS ROAD
RADIUS: 20'-0"
RADIUS: 20'-0"
20'-0"
20'-0"
20'-0"
SCALE
SITE PLAN 1
3/32" = 1'-0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
SITE PLAN
E1.00
E2.00
EVCS SUMMARY
LOCATION PARKING TYPE SHEET EXISTING EVCS SPACES NEW EVCS SPACES
PARKING LOT
*FLEET E2.00 (0) LEVEL 2 (2) LEVEL 2
TOTAL FLEET PORTS: (2) LEVEL 2
* NOTE:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH CBC
11B-228.3.2 ACCESS REQUIREMENTS.
SCOPE OF
WORK
SHEET NOTES:
PROVIDE KNOX BOX OR KNOX PADLOCK THAT
COMPLIES WITH CFC SECTION 506 AND INSTALL
NEAR GATE. CONTRACTOR SHALL COORDINATE
WITH LOCAL FIRE DEPARTMENT TO ENSURE
KNOX BOX OR PADLOCK IS KEYED AS REQUIRED.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON EXISTING DRAWINGS AND A FIELD
VISIT OF THE ELECTRICAL SYSTEM. IN CASE OF
ANY DISCREPANCIES WITH EXISTING FIELD
CONDITIONS, ELECTRICAL CONTRACTOR SHALL
VERIFY THE EXACT DIFFERENCES AND NOTIFY
THE ELECTRICAL ENGINEER FOR POSSIBLE
REVISION TO THESE DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
PB
18'-0"
(TYP.)
9'-0"
(TYP.)
3'-0"
(TYP.)
4'-0"
EVCS-11 2
1 1/4"C - 2#2
& 1#8 GRD.
PB
1" 1/4C - 2#2
& 1#8 GRD.
(E) CONCRETE
SIDEWALK
(E) ASPHALT
PAVEMENT
10 (TYP.)
LIGHTING & POWER
DIST. PANELBOARD
9 (TYP.)
(E) CMU
BLOCK WALL
(E) ANTENNA
(E) SCE METER &
SERVICE DISCONNECT
(E) 30kVA TRANSFORMER
(E) SAFETY SWITCH
(E) MAIN DISTRIBUTION
PANELBOARD
(E) ROOF
OVERHANG
(E) TREE
8"
3'-0" CLEAR
WORKING
SPACE
SCALE
POWER PLAN 1
1/8"=1'=0"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T
HC
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
POWER PLAN
E2.00
SHEET NOTES:
DUAL PORT PEDESTAL TYPE EVCS WITH
14,400VA AND POWER SHARE CAPABILITIES.
PROVIDE 10'-0" OF FEEDER WIRE (2#2 + 1#8 GRD)
COILED UP AT EVCS STUB-UP LOCATION FOR
FINAL EVCS INSTALLATION. PROVIDE MULE TAPE
ROUTED THROUGH CONDUIT FROM THE
PANELBOARD TO EVCS STUB-UP. SEE DETAIL #1
ON SHEET E4.00.
SEE DETAIL #2 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #4
SHEET E4.00 FOR UNDERGROUND PULL-BOX
DETAIL.
SEE DETAIL #3 SHEET E4.00 FOR UNDERGROUND
CONDUIT BURIAL DETAIL THROUGH NATIVE SOIL.
DEMOLISH AND REPLACE EXISTING LIGHTING &
POWER DISTRIBUTION PANEL WITH NEW
RECESSED PANELBOARD. SEE SINGLE LINE
DIAGRAM #1 SHEET E5.00 FOR MORE
INFORMATION.
ROUTE CONDUIT BELOW FLOOR SPACE.
WALL PENETRATION THROUGH NON-RATED
WOOD FRAME WALL. PROVIDE WEATHER PROOF
CAULKING AND PAINT TO MATCH EXISTING
SURFACE.
PROVIDE 10" X 10" X 10" NEMA-3R SURFACE
MOUNTED PULLBOX.
NEW 4" DIA. CONCRETE BOLLARDS. PROVIDE
3'-0" SPACING BETWEEN POSTS. REFER TO CIVIL
DRAWINGS FOR MORE INFORMATION.
REMOVE EXISTING PARKING STRIPING AND
PROVIDE NEW. REFER TO CIVIL DRAWINGS FOR
MORE INFORMATION.
NEW SIGNAGE AND POST. REFER TO CIVIL
DRAWINGS FOR SIGN INFORMATION AND
STRUCTURAL DRAWINGS FOR FOOTING
INFORMATION.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON EXISTING DRAWINGS AND A FIELD
VISIT OF THE ELECTRICAL SYSTEM. IN CASE OF
ANY DISCREPANCIES WITH EXISTING FIELD
CONDITIONS, ELECTRICAL CONTRACTOR SHALL
VERIFY THE EXACT DIFFERENCES AND NOTIFY
THE ELECTRICAL ENGINEER FOR POSSIBLE
REVISION TO THESE DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE SITE'S REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS FOR
SERVICING. CONTRACTOR SHALL FIELD VERIFY
ALL DISTANCES PRIOR TO BID.
5. EXISTING VEGETATION SHALL BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND IRRIGATION IMPROVEMENTS
AFFECTED IN WORK.
PROPOSED EV CHARGERS
EVCS #
WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS
CHARGE PORT #
POWER SELECT
(FLA)
VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL 60 208V-1PH Y FLEET
NOTES:
· (1) DUAL PORT EVCS SHALL SERVE (2) FLEET PARKING STALLS
· (FLA) STANDS FOR FULL LOAD AMPS
· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
1 2
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
SCALE
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 1
N.T.S.
NEW CONCRETE EVCS
FOOTING. SEE STRUCTURAL
DRAWINGS FOR MORE
INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
FINISH GRADE
DUAL PORT PEDESTAL
EV CHARGING STATION
(14,400VA PER PORT)
PROVIDE 1'-6" PVC CONDUIT
STUB-UP WITH CONDUIT
PLUG AND GROUNDING
BUSHING. REFER TO
CONDUIT STUB UP DETAIL #2
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL SHALL
CORRESPOND TO CHARGER NUMBER.
REFER TO DETAIL #5 ON THIS SHEET.
NOTE:
1. FOR PEDESTAL TYPE EVCS INFORMATION - REFER TO INSTALLATION INSTRUCTIONS PER MANUFACTURER.
2. DUAL PORT CHARGING STATION SHALL BE PROVIDED AND INSTALLED BY CURRENT STATE VENDOR. CONTRACTOR SHALL
PROVIDE INFRASTRUCTURE NECESSARY TO SUPPORT THE CHARGER AS SHOWN ON THESE DRAWINGS.
3. PROVIDE MULE TAPE FROM EVCS STUB-UP BACK TO THE LIGHTING & POWER DIST. PANELBOARD.
4. PERMANENT DISCONNECTING THAT COMPLY WITH CEC 110.25 MEANS SHALL BE PROVIDED AT THE PANELBOARD. REFER
TO PANEL SCHEDULE NOTE #1 ON DETAIL #3 SHEET E5.00 FOR MORE INFORMATION.
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 2
N.T.S.
1'-6"
MIN.
FINISH GRADE
PVC CONDUIT
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PROVIDE BUSHING
WHEN PULLING
CONDUCTORS
PVC COUPLING WITH
THREADED PLUG
PVC CONDUIT
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 5
N.T.S.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
NOTE:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
SCALE
UNDERGROUND PULLBOX DETAIL 4
N.T.S.
GRAVEL
BASE
ELECTRICAL
CONDUIT(S)
(IN/OUT)
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
12" DEEP REINFORCED
CONCRETE NON-TRAFFIC
PULLBOX
(EXTEND AS REQUIRED)
FINISH GRADE
COMPACTED
BACKFILL
(TYPICAL)
ELECTRICAL
CONDUIT(S)
(IN/OUT)
2'-0"
MIN.
NOTE:
REFER TO SHEET NOTES ON POWER
PLANS FOR SPECIFIC PULLBOX
DIMENSIONS.
1'-0"
GRADE LEVEL
2'-0"
MIN.
ELECTRICAL
WARNING TAPE
3" CLEAN SAND
BEDDING
NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS REQUIRED IF SCHEDULE 80 PVC IS USED 2'-0"
BELOW GRADE LEVEL. SEE POWER PLAN FOR MORE INFORMATION
1" MIN. SPACING. SHALL BE EQUAL
TO THE LARGEST CONDUIT SIZE
FOR MULTIPLE CONDUIT RUNS.
3" CLEAN SAND
BEDDING
NATIVE BACKFILL
90% COMPACTION
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL (NATIVE SOIL) 3
N.T.S.
CONDUIT/S PER PLAN
1 1/4" PVC CONDUIT
2#2 & 1#8 GRD.
WITH MULE TAPE BACK
TO PANELBOARD
2"
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T H
C
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
ELECTRICAL
DETAILS
E4.00
1/02/2025DATE OF SIGNING:
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
SCALE
SINGLE LINE DIAGRAM - RECONSTRUCTION 2
N.T.S.
INCOMING SERVICE FROM
SOUTHERN CALIFORNIA
EDISON
M
(E) 30kVA TRANSFORMER 240V-208Y/120V, 3Ø, 4W %Z =5.00%
NEMA-2
LIGHTING
& POWER
DIST. PNL
(E) SAFETY SWITCH
100A-3P
SCALE
SINGLE LINE DIAGRAM 3
N.T.S.
SCALE
SINGLE LINE DIAGRAM - DEMOLITION 1
N.T.S.
DEMOLITION NOTES:
DISCONNECT ALL EXISTING CONNECTIONS AND
PROTECT IN PLACE. DEMOLISH EXISTING
PANELBOARD.
LEGEND:
EXISTING
DEMOLITION
LEGEND:
EXISTING
NEW
(E F E E D
E R
(E F E E D
E R
(E) FEEDER
(E)
DEMOLITION NOTES:
PROVIDE NEW RECESSED 42 CIRCUIT
PANELBOARD AND RECONNECT EXISTING
LOADS. EXTEND CONDUCTORS AND CONDUITS
AS NEEDED.
PROVIDE ARC FLASH LABEL.
(E) SCE METER
AND SERVICE
DISCONNECT
100A-3P
150A-3P
(E) MAIN DISTRIBUTION
PANELBOARD
150A, 240V, 3Ø, 3W
(E F E E D
E R
INCOMING SERVICE FROM
SOUTHERN CALIFORNIA
EDISON
M
(E) 30kVA TRANSFORMER 240V-208Y/120V, 3Ø, 4W %Z =5.00%
NEMA-2
LIGHTING
& POWER
DIST. PNL
(E) SAFETY SWITCH
100A-3P
(E F E E D
(E F E E D
(E) FEEDER
(E)
(E) SCE METER
AND SERVICE
DISCONNECT
100A-3P
150A-3P
(E) MAIN DISTRIBUTION
PANELBOARD
150A, 240V, 3Ø, 3W
(E F E E D
1 2
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
E. Torres
E. Burtch
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
11/25/2024
V2
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
R E
NG
A
E
S
No. E17083
T
E
ET
S
AT
L
CE A
F
RIC
L
ORN
I
E
PR
RAET
RE
D D.D
OF ONA
B R
L
SSI
N E
R E
IW
D
U
T H
C
E
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD SubmittalEB07/19/20241
100% CD SubmittalEB11/25/20242
1/02/2025DATE OF SIGNING:
SINGLE LINE
DIAGRAM &
SCHEDULES
E5.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
CREW
ROOM
STORAGE
WOMEN'S
MEN'S
CREW
ROOM
SUPERVISOR'S
OFFICE
JANITOR
LUNCH
ROOM
RECORD
ROOM
FRONT
OFFICE
RECORD
ROOM
UTILITY
CLOSET
EX.
TRAILER
EV
FLEET
ONLY
EV
FLEET
ONLY
PB
PB
EXISTING
BUILDING
(N.A.P)
EX. ASHPAHLT
PAVEMENT
.0
9.0'
.0
3.0'
EX. ANTENNA
EX. CONCRETE
SIDEWALK
EX. 30kVA
TRANSFORMER
EX. SAFETY
SWITCH
EX. MAIN
DISTRIBUTION
PANELROAD
EX. SCE METER &
SERVICE DISCONNECT
EX. TREE
EX. ROOF
OVERHANG
EX. CMU
BLOCK WALL
22 1
4 4
6 6
9.0'
REFER TO SEPARATE
PLAN PREPARED BY
GOSS ENGINEERING
REFER TO SEPARATE
PLAN PREPARED BY
GOSS ENGINEERING
R
CALL 811 BEFORE YOU DIG.
CONSTRUCTION NOTES:
INSTALL UNDERGROUND CONDUIT PER SEPARATE PLAN PREPARED BY GOSS
ENGINEERING.
INSTALL WHEELSTOP PER DETAIL 3, THIS SHEET.
INSTALL BOLLARDS PER DETAIL 1, THIS SHEET.
INSTALL 4" WIDE GREEN PAINT STRIPE TO MATCH FEDERAL STD. 595B COLOR 14090
INSTALL EV PARKING SIGNAGE PER DETAIL 2, THIS SHEET.
INSTALL WHITE "EV FLEET ONLY" LETTERING
GENERAL NOTES:
1. ELECTRICAL VEHICLE CHARGING STATION/S (EVCS) SHALL BE PROVIDED,
INSTALLED AND CONNECTED BY STATE VENDOR.
2. PROVIDE MINIMUM OF 1'-0" CLEARANCE BEHIND ALL PEDESTRAL MOUNTED
CHARGES FOR SERVICING. CONTRACTOR SHALL FIELD VERIFY ALL DISTANCES
PRIOR TO BID.
3. EXISTING VEGETATION TO BE REMOVED, PROTECTED AND RESTORED AFTER
CONSTRUCTION.
4. REMOVE AND REPLACE IN-GROUND LANDSCAPING AND IRRIGATION
IMPROVEMENTS AFFECTED IN WORK.
EXISTING CONCRETE
EXISTING WALL
PROPOSED UNDERGROUND
ELECTRICAL CONDUIT
LEGEND
AUTHORIZED
ELECTRIC
FLEET
VEHICLES
ONLY
GREEN BACKGROUND WITH WHITE
LETTERING
FINISH GRADE
NOTE/S:
1. SIGNAGE TO BE FURNISHED AND INSTALLED BY CONTRACTOR.
CONTRACTOR TO PROVIDE SUBMITTAL CONFIRMING SIGNAGE
PRIOR TO ORDERING.
2. SIGNAGE SHALL BE 80" MIN. ABOVE GROUND SURFACE MEASURED
TO THE BOTTOM OF THE LOWEST SIGN WHEN LOCATED WITHIN A
WALKABLE CIRCULATION PATH.
80" MIN.
1.5'
1.0'
1"
PROVIDE DIAMOND GRADE
ALUMINUM REFLECTIVE SIGN WITH
GRAPHIC
CONCRETE FOOTING PER
STRUCTURAL DRAWINGS
NOT TO SCALE
2 EV PARKING SIGNAGE DETAIL
4.0'
3.0'4.0'
MIN.
1.25'
CONCRETE CAP
FIELD PRIME STEEL BOLLARDS WITH
2 COATS OF ZINC-RICH PRIMER.
PAINT BOLLARDS WITH 2 COATS OF
INDUSTRIAL YELLOW ENAMEL.
4" SCHEDULE 40 STEEL CONCRETE
FILLED MINIMUM 4" DIAMETER
CONCRETE
NOT TO SCALE
1BOLLARD DETAIL
9"
2- #3 REBARS
TOP OF PAVEMENT
#5 REBAR W/ 1'-6" EMBED INTO PAVING
4'-0"
EPOXY TO A.C. PAVEMENT
PRECAST CONC. BUMPER
NOT TO SCALE
CONCRETE WHEELSTOP DETAIL
SITE IMPROVEMENT
PLAN
C1.00
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate #
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
GUILLERMO SANCHEZ
AARON ALBERTSON
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e
E V S E I n s ta lla ti o n
24083
11/13/2024
V2
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 24-S-4517-C
95% CD Submittal--07/19/20241
100% CD Submittal--11/13/20242
1/02/2025DATE OF SIGNING:
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
BLDG. DEPT.B.D.
EQUIPMENT
EQUAL
EDGE NAILING
ELEVATION
EACH WAY
EACH SIDE
EACH FACE
DRAWING
DOWNSPOUT
DOUGLAS FIR
DITTO
DIMENSION
DIAMETER
COUNTERSUNK
CONSTRUCTION
CONTINUOUS
CONCRETE
COLUMN
CLEAR
CEILING
CAST IN PLACE
CAST IRON
BOTTOM
BLOCKING
BOUNDARY NAILING
DR.
E.N.
EQUIP.
EQ.
EL.
E.W.
E.S.
E.F.
EA.
DWG.
D.S.
D.F.
EACH
COL.
DO.
DIM.
DIAM.
CTSK.
CONST.
CONT.
CONC.
DOOR
CLR.
CLG.
C.I.P.
C.I.
BOT.
BLKG.
BM.
B.N.
BEAM
NOT IN CONTRACT
LOW HYD. ELECT.
PL.
P.L.
PARTN.
O.C.
N.T.S.
N.I.C.
MISC.
MIN.
MAX.
PROPERTY LINE
PLATE
PARTITION
ON CENTER
NOT TO SCALE
MISCELLANEOUS
MINIMUM
MAXIMUM
M.B.
LTWT.
LHE
LG.
INTR.
HORIZ.
HT.
HGR.
GYP.
GLB
GA.
GALV.
F.L.
FLR.
HORIZONTAL
MACHINE BOLT
LIGHTWEIGHT
INTERIOR
LONG
HEIGHT
HANGER
GYPSUM
GLU-LAM BEAM
GALVANIZED
FLOW LINE
GAUGE
FLOOR
TOP OF FRAMINGT.O.F.
TOP OF STEEL
WIRE MESH
WITH/OUT
VERTICAL
TYPICAL
TOP OF WALL
TAPERED STL. GIRDER
TOP OF PAVING
TOP OF LEDGER
W/O
W.W.M.
WD. WOOD
VERT.
W/
TYP.
T.W.
TSG
T.O.S.
T.O.P.
T.O.L.
WITH
TOP & BOTTOM
TOP OF CURVE
TONGUE & GROOVE
TOP OF BEAM
STRUCTURAL
STANDARD
STAGGERED
SPECIFICATIONS
SIMILAR
SELECT STRUCTURAL
STEELSTL
T & G T & B
THK.
T.O.C.
T.O.B.
T.
STR.
THICK
TOP
STAG.
SPECS.
STD.
SIM.
SHT.
S.S.
RO.
SHEET
ROUGH OPENING
ARCHITECTURAL
ALUMINUM
ALTERNATE
AGGREGATE
ANCHOR BOLT
ARCHL.
ALUM.
ALT.
AGG.
A.B.
FACE OF MASONRY
F.G F.F.
FIN.
F.O.S.
F.O.M.
EXTR.
(E)
FINISH GRADE
FINISH FLOOR
FINISH
FACE OF STUD
EXTERIOR
EXISTING
REINFORCE(D)
PRESSURE TREATED
LBS / SQ. IN.
PLYWOOD
REINF.
RFTR.
P.S.I.
P.T.
RAD.
PLY.
RAFTER
RADIUS
NEW(N) -
OSB ORIENTED STRAND BOARD-
BTW. BETWEEN-
FTG. FOOTING-
DEEPDP.
SHEAR WALL LENGTHS.W.L. -
CONCRETE MASONRY UNITSC.M.U. -
REQUIREDREQ'D -
ADDITIONALADD'L -
SHEET METAL SCREWSSMS -
CENTEREDCNT'D -
BLOCKBLK. -
VERIFY IN FIELDV.I.F. -
TOP OF DECKT.O.D. -
LSV LONG SIDE VERT.-
LSH LONG SIDE HORIZ.-
& - AND Ø - DIAMETER
L - ANGLE d - PENNY (NAIL GRADE)
@ - AT - PROPERTY LINE
- CENTERLINE # - POUND(LBS) OR NUMBER
P L C L
K.P. KING POST-
UNLESS NOTED OTHERWISEU.N.O. -
REFERENCERE: -
ABBREVIATIONS:
STRUCTURAL SYMBOLS:
DESIGN CRITERIA
WIND
DESIGN WIND SPEED, V = 93 MPH
RISK CATEGORY = II
WIND EXPOSURE = C
INTERNAL PRESSURE COEFFICIENT = ± 0.18
EARTHQUAKE
RISK CATEGORY = II
SEISMIC IMPORTANCE FACTOR, Ie = 1.0
SS = 1.954
S1 = 0.735
SDS = 1.564
SD1 = 0.833
SITE CLASS = D (DEFAULT)
SEISMIC DESIGN CATEGORY = B
RESPONSE MODIFICATION COEFFICIENT, RP = 2.5
COMPONENT AMPLIFICATION FACTOR - aP = 1.0
ANALYSIS PROCEDURE USED =
EQUIVALENT LATERAL
FORCE PROCEDURE
EFFECTIVEEFF. -
GENERAL:
1. ALL STRUCTURAL ELEMENTS, WORKMANSHIP AND MATERIALS SHALL CONFORM TO
THE LATEST REQUIREMENTS OF THE 2022 CALIFORNIA BUILDING CODE (C.B.C.) AND
ALL OTHER APPLICABLE CODES AND ORDINANCES.
2. GENERAL CONTRACTOR SHALL VERIFY ALL GRADES, DIMENSIONS AND CONDITIONS
PRIOR TO BIDDING AND COMMENCING CONSTRUCTION AND NOTIFY THE ARCHITECT
OR ENGINEER OF ANY DISCREPANCIES OR INCONSISTENCIES. DIMENSIONS SHALL
NOT BE SCALED FROM THE DRAWINGS OR DETAILS. ANY WORK PERFORMED PRIOR
TO AND/OR IN CONFLICT WITH SUCH CLARIFICATION SHALL BE CORRECTED BY THE
CONTRACTOR AT THEIR EXPENSE AND AT NO ADDITIONAL COST TO THE OWNER OR
DESIGN TEAM OF RECORD.
4. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE AND DO NOT INDICATE THE WAYS AND MEANS OF CONSTRUCTION. THE
STRUCTURE SHOWN ON THESE DRAWINGS IS STRUCTURALLY SOUND ONLY IN THE
COMPLETED FORM. GENERAL CONTRACTOR SHALL PROVIDE ALL MEASURES
NECESSARY TO PROTECT THE STRUCTURE, WORKMAN AND OTHER PERSONS
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT TO BE LIMITED
TO, BRACING, SHORING FOR CONSTRUCTION EQUIPMENT AND SHORING FOR THE
STRUCTURE.
5. ANY DISCREPANCIES BETWEEN SPECIFICATIONS, GENERAL NOTES, STRUCTURAL
PLANS AND DETAILS SHALL BE BROUGHT TO THE ATTENTION TO THE ARCHITECT OR
ENGINEER BY THE GENERAL CONTRACTOR PRIOR TO COMMENCING ANY WORK.
3. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION AND COORDINATION
WITH ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE
SPRINKLER DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION
OF ALL WORK, INCLUDING THAT OF ALL SUBTRADES.
7. ANY REFERENCES TO THE WORDS APPROVED, OR APPROVAL IN THESE DOCUMENTS
SHALL BE HERE DEFINED TO MEAN GENERAL ACCEPTANCE OR REVIEW AND SHALL
NOT RELIEVE THE CONTRACTOR AND/OR HIS SUBCONTRACTORS OF ANY LIABILITY IN
FURNISHING THE REQUIRED MATERIALS OR LABOR SPECIFICATION.
8. ALL MATERIALS SHALL BE FURNISHED AS SHOWN HEREIN UNLESS ALTERNATES ARE
APPROVED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CHANGES
NECESSARY & SHALL COORDINATE ALL DETAILS AND OBTAIN WRITTEN APPROVAL BY
THE ARCHITECT, OWNER, AND STRUCTURAL ENGINEER OF RECORD. COSTS OF
ADDITIONAL DESIGN WORK NECESSITATED BY SELECTION OF AN OPTION OR DUE TO
ERRORS OR OMISSIONS IN CONSTRUCTION, SHALL BE BORNE BY THE CONTRACTOR.
6. ANY DISCREPANCIES BETWEEN ARCHITECTURAL AND STRUCTURAL DRAWINGS
AND/OR FIELD CONDITIONS MUST BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER OF RECORD PRIOR TO SUBMITTAL OF BID AND
CONSTRUCTION. ANY DISCREPANCIES BETWEEN DRAWINGS THAT RESULT IN
ADDITIONAL COST AFTER THE BID SHALL BE THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO REVIEW
DRAWINGS CAREFULLY DURING THE BID PROCESS. DO NOT PROCEED WITH ANY
WORK UNTIL DISCREPANCIES OR ANY OUTSTANDING ITEMS AND/OR QUESTIONS
HAVE BEEN RESOLVED.
9. CONNECTIONS OF ALL ITEMS SUPPORTED BY THE STRUCTURE ARE THE
RESPONSIBILITY OF THE DISCIPLINES WHO MAKE THESE ATTACHMENTS. REVIEW
AND COORDINATE ALL THE REQUIREMENTS AND THE ARCHITECTS PROJECT
SPECIFICATIONS AS APPLICABLE.
10. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING
UTILITIES WHETHER INDICATED ON CONTRACT DRAWINGS OR NOT, AND TO PROTECT
THEM FROM DAMAGE. REPAIR AND REPLACE OF SAID WORK SHALL BE AT THE
EXPENSE OF THE CONTRACTOR.
11. ALL MANUFACTURED PRODUCTS MUST BE INSTALLED PER MANUFACTURER'S
RECOMMENDATION.
12. REQUIRED SHOP DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL
ENGINEER OF RECORD FOR REVIEW FOR ALL FABRICATED MATERIALS AND WILL
BE REVIEWED AS TO THEIR GENERAL CONFORMANCE TO THE DESIGN CONCEPT.
ARCHITECT AND CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLIANCE AND
DIMENSIONS. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND COMPLIANCE
CERTIFICATES TO THE BUILDING DEPARTMENT WHEN REQUIRED. SHOP DRAWINGS
SHALL NOT BE REPRODUCTIONS OF CONTRACT DOCUMENTS.
13. VIBRATIONAL EFFECTS OF MECHANICAL AND/OR ANY OTHER EQUIPMENT HAVE NOT
BEEN CONSIDERED BY THE STRUCTURAL ENGINEER.
FOUNDATION:
1. DESIGN SOIL BEARING PRESSURE OF 1500 PSF (ASSUMED) AT A DEPTH OF 18"
(ASSUMED) BELOW LOWEST ADJACENT COMPACTED SUBGRADE FOR CONTINUOUS
FOOTINGS AND FOR ISOLATED PADS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING NECESSARY TO
SUPPORT CUT AND/OR FILL SECTIONS DURING EXCAVATION, AND FOR FORMING
AND PLACEMENT OF CONCRETE.
3. BACK FILL AGAINST WALLS SHALL BE PLACED EVENLY AGAINST BOTH SIDES OF
WALLS UNTIL THE LOWER GRADE IS REACHED.
4. FOUNDATION WALLS THAT RETAIN EARTH SHALL BE BRACED AGAINST BACKFILLING
PRESSURES UNTIL FLOOR SLABS AT TOP AND BOTTOM ARE IN PLACE.
5. A 15 MIL VAPOR RETARDER SHALL BE PROVIDED UNDER ALL INTERIOR FLOOR
SLABS OVER SUB-GRADE.
CONCRETE:
1. ALL CONCRETE MATERIALS, CONSTRUCTION AND WORKMANSHIP SHALL
CONFORM TO THE LATEST EDITION OF THE ACI 301 "SPECIFICATIONS FOR
STRUCTURAL CONCRETE" AND ACI 318 "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE".
3. CONCRETE MIXES SHALL BE DESIGNED BY A RECOGNIZED TESTING LABORATORY.
ALL CONCRETE MIX DESIGNS BEARING THE SEAL AND SIGNATURE OF A LICENSED
CIVIL ENGINEER SHALL BE SUBMITTED TO THE ENGINEER OF RECORD FOR REVIEW
AND APPROVAL.
7. IN COLD WEATHER, THE TEMPERATURE OF THE CONCRETE WHEN DELIVERED AT
THE SITE SHALL BE AT LEAST 50 DEGREES FAHRENHEIT.
2. THE MINIMUM COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS
EXCEPT AS NOTED ON PLANS OR SOILS REPORT SHALL BE:
10. SLAB ON GRADE SHALL BE POURED ON FIRM, MOISTENED, COMPACT EARTH.
REFER TO SOILS ENGINEERS RECOMMENDATIONS WHEN SOILS REPORT IS
AVAILABLE. CONSTRUCTION OR CRACK-CONTROL JOINTS SHALL BE SPACED A
MAXIMUM OF 12' APART AND ALIGNED WITH COLUMN CENTERS WHERE OCCURS.
8. CONCRETE CURING SHALL COMPLY WITH ACI-308. RE: ARCHITECTURAL FOR FINISH.
11. GROUT SHALL CONSIST OF 1 PART CEMENT, TO NOT MORE THAN 3 PARTS SAND
AND NOT LESS THAN 1 PART NOR MORE THAN 2 PARTS PEA GRAVEL BASED ON
DRY LOOSE VOLUMES. GROUT SHALL BE OF FLUID CONSISTENCY. APPROVED
ADMIXTURES MAY BE ADDED TO GROUT MIX. GROUT SHALL ATTAIN A MINIMUM
ULTIMATE COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS.
12. DRYPACK SHALL OBTAIN A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF
3000 PSI AT 28 DAYS. DRYPACK SHALL CONSIST OF 1 PART CEMENT, 4 PARTS
SAND, AND NOT LESS THAN 1/4 PART OR MORE THAN 1/2 PART LIME PUTTY OR
DRY HYDRATED LIME.
4. MAXIMUM SLUMP AT PLACEMENT SHALL BE 5 INCHES, UNLESS WATER REDUCING
ADMIXTURE IS USED IN THE CONCRETE MIX.
5. WATER REDUCING ADMIXTURE CONFORMING TO ASTM C494 MAYBE USED.
6. CONCRETE SHRINKAGE SHALL NOT EXCEED 0.05% AS DETERMINED BY ASTM C157.
9. PRIOR TO PLACEMENT OF CONCRETE, REINFORCING STEEL, ANCHORS BOLTS,
HOLDOWNS, EMBED PLATES AND OTHER EMBEDMENTS SHALL BE FIRMLY SECURED
IN POSITION.
13. WHERE NEW CONCRETE IS POURED AGAINST EXISTING CONCRETE, ROUGHEN
THE EXISTING SURFACE TO 14 INCH AMPLITUDE.
14. MAINTAIN CONCRETE ABOVE 50 DEGREES FAHRENHEIT AND IN A MOIST
CONDITION FOR A MINIMUM OF 7 DAYS AFTER PLACEMENT UNLESS OTHERWISE
ACCEPTED BY ENGINEER OF RECORD.
3,000 3,000
2" 1"
SULFATE EXPOSURE
SLAB ON
GRADE
FOUNDATION
MAX. WATER TO CEMENT RATIO 0.5 0.55
PER SOILS REPORT
PORTLAND CEMENT TYPE
(RE: ASTM C-50)
II II
MIN. COMPRESSIVE STRENGTH
MAXIMUM SIZE AGGREGATE
(RE: ASTM C-33)
4,000
1"
BEAMS &
COLUMNS
0.5
II
REINFORCING STEEL & EMBEDS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #18 BAR 2"
#5 BAR, W31 OR D31 WIRE AND SMALLER 1 1/2"
#11 BAR AND SMALLER 3/4"
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS 1 1/2"
1. ALL REINFORCING STEEL NO. 4 OR LARGER SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A615, GRADE 60 AND NO. 3 OR SMALLER, SHALL CONFORM
TO ASTM A615, GRADE 40 U.N.O.. ALL REINFORCING SHALL BEAR MILL STOCK
IDENTIFICATION.
10. CLEAR COVERAGE OF CONCRETE OVER REINFORCING BARS SHALL BE AS SHOWN IN
DETAILS AND PER CHART BELOW:
3. BARS SHALL BE CLEAN OF RUST, MUD, OIL, GREASE OR OTHER COATING MATERIAL
LIKELY TO IMPAIR BONDING.
4. GRADE 60 REINFORCING BARS SHALL NOT BE BENT WITHOUT THE APPROVAL OF THE
ENGINEER.
5. ALL REINFORCEMENT MUST BE CONTINUOUS EXCEPT AS DETAILED. ALL SPLICE AND
LAP LOCATIONS SHALL BE VERIFIED WITH THE ENGINEER.
6. ALL WELDED REINFORCING STEEL SHALL CONFORM TO ASTMA706, GRADE 60.
REINFORCING STEEL WELDING SHALL CONFORM TO AWS D1.4. WELDING SHALL BE
PERFORMED BY A CERTIFIED WELDER USING LOW HYDROGEN E70XX ELECTRODES.
ALL FIELD WELDING SHALL BE CONTINUOUSLY INSPECTED BY A REGISTERED DEPUTY
INSPECTOR. NO WELDING SHALL BE DONE AT THE BEND IN A BAR.
8. WELDED WIRE MESH SHALL CONFORM TO ASTM A185 GRADE 65 FOR PLAIN WIRE
AND ASTM A497 GRADE 75 FOR DEFORMED BAR.
CONDITION
2. ALL REINFORCING STEEL, ANCHOR BOLTS AND OTHER EMBEDMENTS SHALL BE
TIED IN PLACE PRIOR OR SECURELY FASTENED TO FORMS PRIOR TO FOUNDATION
EXCAVATION INSPECTION OR POURING CONCRETE.
9. ALL ANCHOR BOLTS SHALL HAVE A STANDARD HEAD AT EMBEDDED END &
SHALL CONFORM TO ASTM F1554. MINIMUM EMBEDMENT OF ANCHOR BOLTS
SHALL BE 7" IN FOOTINGS, 5 1/2" IN MASONRY WALLS, AND 4 1/2" INTO
VERTICAL CONCRETE SURFACES.
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH
EARTH, SLAB, WALLS, JOISTS:
CONCRETE
COVER
SPECIFICATION ICC#
EPOXY
MANUFACTURER LARR# CONCRETE MASONRY
DEWALT PURE 110+ ESR-3298
HILTI HIT-RE 500 V3 ESR-3814 X
X
NOTE: SPECIAL INSPECTION REQUIRED FOR ALL POST INSTALLED ANCHORAGE
HILTI
SIMPSON
HILTI
ESR-3027
ESR-4266KB-TZ2
KWIK 'HUS' EZ
ESR-4266
TITEN 'HD' ESR-2713
X
X
X
X-U - SHOT DRIVIN HILTI ESR-2269 X X
HILTI X-GN - GAS DRIVIN ESR-1752 X X
25675
25662
POST INSTALLED ANCHORAGE SCHEDULE
MECHANICAL ANCHORS
SHOT / GAS DRIVIN PINS
SIMPSON STRONG BOLT-2 ESR-3037 XESR-3037
SET-3G ESR-4844
X
ESR-4844
HILTI HD1-P TZ ESR-4236 X
ESR-3814
ESR-3298
ESR-3027
ESR-4236
ESR-2713
SIMPSON AT-XP IAPMO ER-281 XIAPMO ER-281
SIMPSON X
SIMPSON STRONG BOLT-2 ER-240 X
SIMPSON TITEN 'HD' ESR-1056 X
HILTI KB-TZ2 ESR-4561 XESR-4561
ER-240
ESR-1056
HILTI HIT-HY 200-A V3 ESR-4868 XESR-4868
SIMPSON SET-3G ESR-4057 ESR-4057
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
S o u th
G a rd e n S tr e e t, V e n tu ra C A
J.BISCOCHO
S.NAGARAJAN
As Noted
C a lt ra n s D is tr ic t
V e n tu ra F ie ld
O ff ic e E V S E I n s ta lla ti o n
124-01-02.59
07/19/2024
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CSFM APPLICATION NUMBER: 00-0-0000-C
95% CD Submittalmrp07/19/20241
100% CD Submittalmrp11/13/20242
S0.01
GENERAL NOTES
S6349S I
V A
R A
M
NAG
A R
A J
A N
R E G I S T E R
E D
PR
OFESSIONA
L E
N G I N E E R
S T
RUCTUR
A
L
S T
A
T E
OF CAL I F
O
R
N I A
(#) 24-115(p) 714 - 923 - 8946
130 centennial way #F tustin, ca m:r:p planning co.m:r:p planning co.
s t r u c t u r a l en g i n eer i n g www.mrpplanningco.com
24-S-4517-C
V2
1/02/2025DATE OF SIGNING:
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/23/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-4517
DOT D7 - Electric Vehicle Supply Equipment - Ventura Field Office
PROJECT NUMBER: 000000000013973; 09/11/26
http://www.mrpplanningco.com
STATEMENT OF SPECIAL INSPECTIONS, 2022 CBC
PROJECT:
LOCATION:
THIS STATEMENT OF SPECIAL INSPECTIONS IS SUBMITTED IN FULFILLMENT OF THE
REQUIREMENTS OF CBC SECTIONS 1704 AND 1705. INCLUDED ARE:
SCHEDULE OF SPECIAL INSPECTIONS AND TESTS APPLICABLE TO THIS PROJECT.
X SPECIAL INSPECTIONS PER SECTIONS 1704 AND 1705
X SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE
LIST OF THE TESTING AGENCIES AND OTHER SPECIAL INSPECTORS THAT WILL BE RETAINED
TO CONDUCT THE TEST AND INSPECTIONS.
SPECIAL INSPECTIONS AND TESTING WILL BE PERFORMED IN ACCORDANCE WITH THE APPROVED
PLANS AND SPECIFICATIONS, THIS STATEMENT AND CBC SECTIONS 1704, 1705, 1707, AND 1708.
THE SCHEDULE OF SPECIAL INSPECTIONS SUMMARIZES THE SPECIAL INSPECTIONS AND TEST
REQUIRED. SPECIAL INSPECTORS WILL REFER TO THE APPROVED PLANS AND SPECIFICATIONS
FOR DETAILED SPECIAL INSPECTION REQUIREMENTS. ANY ADDITIONAL TESTS AND INSPECTIONS
REQUIRED BY THE APPROVED PLANS AND SPECIFICATIONS WILL ALSO BE PERFORMED.
INTERIM REPORTS WILL BE SUBMITTED TO THE BUILDING OFFICIAL AND THE REGISTERED DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE IN ACCORDANCE WITH CBC SECTION 1704.2.4.
A FINAL REPORT OF SPECIAL INSPECTIONS DOCUMENTING REQUIRED SPECIAL INSPECTIONS
TESTING AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE
SUBMITTED PRIOR TO ISSUANCE OF A CERTIFICATE OF USE AND OCCUPANCY (SECTION 1704.1.2.).
THE FINAL REPORT WILL DOCUMENT:
REQUIRED SPECIAL INSPECTIONS.
CORRECTION OF DISCREPANCIES NOTED IN INSPECTIONS.
THE OWNER RECOGNIZES HIS OR HER OBLIGATION TO ENSURE THAT THE CONSTRUCTION COMPLIES
WITH THE APPROVED PERMIT DOCUMENTS AND TO IMPLEMENT THIS PROGRAM OF SPECIAL
INSPECTIONS. IN PARTIAL FULFILLMENT OF THESE OBLIGATIONS, THE OWNER WILL RETAIN AND
DIRECTLY PAY FOR THE SPECIAL INSPECTIONS AS REQUIRED IN CBC SECTION 1704.2.
THIS PLAN HAS BEEN DEVELOPED WITH THE UNDERSTANDING THAT THE BUILDING OFFICIAL WILL
REVIEW AND APPROVE THE QUALIFICATIONS OF THE SPECIAL INSPECTORS WHO WILL
PERFORM THE INSPECTIONS.
MONITOR SPECIAL INSPECTION ACTIVITIES ON THE JOB SITE TO ASSURE THAT THE SPECIAL
INSPECTORS ARE QUALIFIED AND ARE PERFORMING THEIR DUTIES AS CALLED FOR IN THIS
STATEMENT OF SPECIAL INSPECTION.
REVIEW SUBMITTED INSPECTION REPORTS.
PERFORM INSPECTIONS AS REQUIRED BY THE UNIVERSITY.
PREPARED BY:
REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
SIVARAM NAGARAJAN
SIGNATURE DATE
OWNER'S AUTHORIZATION:
OWNER
SIGNATURE DATE
BUILDING OFFICIAL'S ACCEPTANCE:
BUILDING OFFICIAL
SIGNATURE DATE
SCHEDULE OF INSPECTION, TESTING AGENCIES, AND INSPECTORS
RESPONSIBILITY FIRM ADDRESS, TELEPHONE, E-MAIL
TBD
NOTATION USED IN TABLE:
COLUMN HEADER:
C INDICATES CONTINUOUS INSPECTION IS REQUIRED
P
BOX ENTRIES:
X
VERIFICATION AND INSPECTION C NOTESP
TABLE 1705.3 - CONCRETE
1. INSPECTION OF REINFORCING STEEL INCLUDING
PRESTRESSING TENDONS AND PLACEMENT.
X
2. INSPECTION OF REINFORCING STEEL WELDING IN
ACCORDANCE WITH TABLE 1705.2.2 ITEM 2b
3. INSPECT BOLTS TO BE INSTALLED IN CONCRETE
PRIOR TO AND DURING PLACEMENT OF CONCRETE
WHERE ALLOWABLE LOADS HAVE BEEN INCREASED
X
4. VERIFYING USE OF REQUIRED DESIGN MIX. X
5. AT TIME FRESH CONCRETE IS SAMPLED TO
FAB…
This is the start of the file's text. The full file is on GovTribe.