PERFORMANCE WORK STATEMENT (PWS)
Inspection, Maintenance & Servicing of Portable Fire Extinguishers
1.0 INTRODUCTION AND OVERVIEW
1.1 Description of product or service: The contractor shall provide all labor, parts, materials, transportation, equipment, and supplies to perform the required inspections, testing, maintenance, and servicing of U.S. Naval Hospital, Guam (hereinafter referred to as the USNH, Guam) portable fire extinguishers.
1.2 Places of Performance. Except for the recharging, 6-year maintenance, 12-year hydrostatic testing, the contractor will perform work required by this PWS in:
Building 50, USNH, Guam;
*Building 6, Branch Medical Clinic, Naval Base, Guam *Building 1, Branch Dental Clinic, Naval Base, Guam;
Building 61, Training Center, USNH, Guam;
Building 7, Hospital Storage, USNH, Guam;
Building 48, Macerator, USNH, Guam;
Building 55, Support Facility, USNH, Guam;
Building 57, Support Facility, USNH, Guam;
Building 45, Support facility, USNH, Guam;
Warehouse 4/6, USNH, Guam;
Building 70, Gymnasium, USNH, Guam;
Building 23, Central Utility Plant, USNH, Guam;
*Services for both Naval Base Guam Branch Clinics (buildings 6 and 1) will transfer to the new Apra Harbor Medical & Dental Clinic, Building 1792, effective from November 2nd, 2022
See the below embedded word documents for quantity of extinguishers per building.
1.3 Period of Performance: 1 August 2022 through 31 July 2023. Along with the base year, the solicitation and resulting contract will include 3 one-year option periods. The exercise of any option will be at the discretion of the government.
1.4 Applicable Documents: The National Fire Protection Association (NFPA) Standard Number 10.
2.0 PERFORMANCE REQUIREMENT SUMMARY (PRS)
The PRS (below table) lists the performance objectives, the PWS paragraph for each objective, and the performance standards the contractor must meet to successfully perform the objectives. The NFPA Standard Number 10 for portable fire extinguishers governs these performance objectives.
| Performance Objective |
| PWS Paragraph |
| Performance Threshold/Standard |
| Method of Surveillance |
| Annual Inspection, Certification, and Record Keeping |
| Reference 3.1 |
| 100% of the time |
| Customer Complaint |
Six-Year Maintenance (as needed)
| Reference 3.1 |
| 100% of the time |
| Customer Complaint |
12-Year Hydrostatic Testing (as needed)
| Reference 3.1 |
| 100% of the time |
| Customer Complaint |
| Parts and Supplies (as needed) |
| Reference 3.2 |
| 100% of the time |
| Customer Complaint |
Recharge of extinguishers or service calls for 10-pound dry chemical, 20 pound wet chemical, 2.5 and 5 pound fire extinguishers (as needed)
| Reference 3.1 |
| 100% of the time |
| Customer Complaint |
Annual technician certifications
| Reference 3.0 |
| 100% of the time |
| Customer Complaint |
3.0 CONTRACTOR’S RESPONSIBILITIES
Upon contract award, the contractor will conduct a joint on-site visit and walk around of the facilities listed in paragraph 1.2 with the Facility Department representative. The contractor shall record and maintain a list of all extinguishers and any discrepancies. The contractor shall provide a fire extinguisher annual inspection service record once an annual inspection is complete. The contractor will provide any documentation requested by the Contracting Officer within 2 days of the request.
Security Requirements. The contractor is responsible for obtaining the required access to the facilities listed in paragraph through the Naval Base Guam Visitor Control Center.
All refills, tests, repairs, and services performed on the extinguishers must comply with NFPA guidelines and be completed by a certified technician. Hydrostatic testing must be performed by a certified technician and comply with the Department of Transportation requirements. Prospective contractors must include, with their quotations/offer, a valid signed and dated copy of the certification for each technician that will provide the aforementioned services. The prospective contractor shall submit these certifications annually thereafter, before the exercise of any option.
3.1 Task Definition
· Annual on-site inspection (NFPA 10): Fire extinguishers shall be inspected and certified annually. The inspection shall include a check of at least the following items:
a. Location in designated place
b. No obstruction to access or visibility
c. Operating instructions on nameplate legible and facing outward
d. Safety seals and tamper indicators not broken or missing
e. Fullness determined by weighing or “hefting”
f. Examination for obvious physical damage, corrosion, leakage, or clogged nozzle
g. Pressure gauge reading or indicator in the operable range or position
Inspection Record Keeping:
a. Upon completion of Inspection - physical inspection sign tag for certification. Records shall be kept on a tag or label attached to the fire extinguisher, on an inspection checklist maintained on file, or in an electronic method that provides a permanent record.
b. Personnel making inspections shall keep records of all fire extinguishers inspected, including those found to require repairs, testing, replacement, or items/supplies.
· Recharging: All rechargeable-type fire extinguishers shall be recharged after any use or as indicated by inspection or when performing maintenance.
a. The contractor shall pick up and deliver all extinguishers requiring recharging
b. After recharging, a leak test shall be performed on stored-pressure and self-expelling types of fire extinguishers.
c. Each fire extinguisher shall have a tag or label securely attached that indicates the month and year recharging was performed and that identifies the person performing the service.
· 6-Year Maintenance (as Needed):
a. Every 6 years, stored-pressure fire extinguishers that require a 12-year hydrostatic test shall be emptied and subjected to the applicable maintenance procedures. The removal of the agent shall only be done using a listed halon closed recovery system. When the applicable maintenance procedures are performed during a periodic recharging or hydrostatic testing, the 6-year requirement shall begin from that date
b. The contractor shall include on the label the month and year the test was performed, the name of the person who performed the test, and their company.
· 12-Year Hydrostatic Testing (as needed):
c. Hydrostatic testing shall be performed by persons trained in pressure testing procedures and safeguards and who have suitable testing equipment, facilities, and appropriate servicing manual(s) available.
d. The contractor shall ensure that every hydrostatic test includes both an internal and external visual examination of the cylinder.
e. Hydrostatic testing shall be conducted using water or some other non-compressible fluid as the test medium. Air or other gases shall not be used as the sole medium for pressure testing. All air shall be vented prior to hydrostatic testing to prevent violent and dangerous failure of the cylinder
f. The contractor shall maintain a permanent record for each cylinder tested.
g. The contractor shall include on the label the month and year the test was performed, the name of the person who performed the test, and their company.
3.2 Deliverable products and services
· Items and supplies to include safety seals, hoses, and tags, are to be replaced or repaired within 48 hours of a reported discrepancy.
· If any extinguisher is removed for service, the contractor will provide a loaner replacement suitable for the type of hazard being protected and shall be of equal rating.
4.0 DELIVERABLES
Upon validation by the USNH, Guam Naval Hospital Fire Marshall USNH, Guam Safety Representative that all fire extinguishers have been inspected, the contractor shall forward a copy of the annual inspection and record to the Contracting officer.
4.1 Quality Control. The contractor shall submit their quality control plan to the Contracting Officer no later than the 5th day after contract award. The quality control plan must document how their performance will meet the requirements of the contract
4.2 Annual Maintenance Review/Performance Assessment. The U.S. Naval Hospital Safety Department head will escort the contractor during the annual maintenance review checking to make sure all standards of the PWS were met. This review will be conducted from 8:00AM through 2:00PM, Monday through Friday.
image1.emf
NH GUAM FIRE EXTINGUISHER LISTING.docx
BLDG 50 - FIRST FLOOR
Serial number
Location
DEPT
AP875975
1V01 (Left of entrance - inside)
BIOMED
BD532592
1ZA16 (mechanical rm, beside entrance door)
DZSP
BZ220786
1ZA17 (mechanical rm, beside entrance door)
DZSP
BD532599
1ZA18 (electrical rm, beside entrance door)
DZSP
BZ220759
1Y04 (HAZMAT STORAGE, beside entrance door)
DZSP
BZ220758
1Y01 (ACID STORAGE, beside entrance door)
DZSP
AL-469273
1G14/ELEVATOR FAM MED
DZSP
BZ220749
1Y18/BACK ELEVATOR
DZSP
BZ220683
1N05 (in lobby, outside triage rm)
ER
BZ220767
ACROSS 1N14 (admin hallway)
ER
BZ220763
1L15 (across from cast room)
ER
BZ220773
1MC3 (HALLWAY BY ELEVATOR)
ER
F-75296485
MERCY 1
ER
G-09853538
MERCY 1
ER
G-09897547
MERCY 2 (outside compartment)
ER
G-09851039
MERCY 2 (inside near steps)
ER
G-09920548
MERCY 3 (outside compartment)
ER
G-09854034
MERCY 3 (inside near steps)
ER
BD532588
1HS3 (NEXT TO STAIR 3 DOOR)
FAMILY MED
BZ220673
ACROSS 1H35 (NEXT TO STAFF RR)
FAMILY MED
AP875978
1GC3 (R side of entrance/front desk)
FAMILY MED
BZ220792
1GC1 (L side of entrance/front desk)
FAMILY MED
AP875976
1P11
GALLEY
BZ220689
NEAR ENTRANCE OF MESS DECKS
GALLEY
BZ220793
L SIDE BEFORE GALLEY CASHIER ENTRANCE
GALLEY
AD632760(K) 20 LBS
NEAR SALAD BAR
GALLEY
BZ220751
DIET TECH PREP AREA/HAND WASH STATION
GALLEY
AC421343(K) 20 LBS
NEAR DIET TECH COFFEE MACHINE
GALLEY
AD632767 (K) 20 LBS
L SIDE OF FRIDGE GALLEY
GALLEY
BZ220661
DISHWASHING AREA
GALLEY
AC799094 (K) 20 LBS
RIGHT SIDE OF RT FRIDGE GALLEY
GALLEY
BZ220666
1MC2 (ER BACK ENTRANCE NEAR GALLEY)
GALLEY/HALLWAY
AP875977
1E02A (R side, front desk/reception)
INTERNAL MED
BZ220785
1F11 (R side, patient education rm)
INTERNAL MED
AP875974
1R10 (HALLWAY - ACROSS FMD)
LAB
BZ220690
1T01 (BY OFFICERS OFFICE SPACE)
LAB
BZ220770
1TC2 (BY HISTOLOGY)
LAB
BZ220739
1S04 (BY CHEMISTRY ANALYZER)
LAB
BZ220766
1Y14 (EXIT NEAR LOADING DOCK)
MMD
MR931998
1Z01 (STAFF LOUNGE ENTRANCE)
MMD
BZ270756
1Y02 RECEIVING (NEAR RESTROOM)
MMD
BD532609
1X21 (ACROSS MAIL ROOM)
MMD
A99322816 2.5 LBS
RECEIVING (FORKLIFT)
MMD
BZ220696
1Y05 (MED GAS STORAGE RM)
MMD
BZ220676
1ZA05A (hallway)
MORGUE (PAD)
BD532580
1D35 (next to ultrasound room)
OBGYN
BD532583
1C12 (waiting room)
OBGYN
BD532607
1JC1 (hallway)
OMD
AP875973
1AC5 (hallway) across exam rm 2 (1A09)
ORTHO
BD532604
between rooms 1K23 & 1K25
PATIENT ADMIN
DO7345919
1J04 (atrium)
DHCB (TRICARE)
BD532601
ATRIUM (next to water fountain, nearest ER )
PEDIATRICS
BZ220788
1D16 (next to providers office)
PEDIATRICS
BZ220787
left of immunizations
PHARMACY
BZ220740
across from subway
PHARMACY
BZ220670
across pharmacy lounge
PHARMACY
BD532595
1B12 (next to restroom)
PHYS THERAPY
AB935384 5 LBS
1P01 (across MRI) NON-MAGNETIC
RADIOLOGY
AB935385 5 LBS
1O10 (dressing room) NON-MAGNETIC
RADIOLOGY
AB935459 5 LBS
1R20 - (nuclear med) NON-MAGNETIC
RADIOLOGY
AB935458 5 LBS
1O11 (QA) NON-MAGNETIC
RADIOLOGY
AB935392 5 LBS
1Q03 (ultrasound) NON-MAGNETIC
RADIOLOGY
BZ220777
1QC1 (Front Desk/Atrium)
RADIOLOGY
F-97220581
SPARE (5lbs)
FIRE MARSHAL
F-75295624
SPARE (5lbs)
FIRE MARSHAL
Z-237576
SPARE (5lbs)
FIRE MARSHAL
617875
SPARE (5lbs)
FIRE MARSHAL
G-08847384
SPARE (2.5lbs)
FIRE MARSHAL
BLDG 50 - SECOND FLOOR
Serial number
Location
DEPT
BZ220662
Hallway; next to2V32/Biohazard Room
APU
BZ220794
Hallway; next to 2ZA18/Anesthesia work room
APU
27038
Hallway; front of 2V35/Main OR DH
APU
BZ220754
2SC2; APU/PACU Waiting Area
APU
BD532612
Hallway; next to 2V03/Anesthesia DH
APU
BZ220776
2F21 (right side of staff lounge)
AUDIOLOGY/ENT
BZ220747
2F02 (to the R of exam room #2)
AUDIOLOGY/ENT
BD532596
HALLWAY NEAR SUSHI PLACE
CHAPEL SERVICES
BD532605
2K01 (OUTISDE BILLING OFFICE DOOR ON THE LEFT)
CHAPEL SERVICES
BZ220782
2AC3 (NEXT TO VENDING MACHINE)
DENTAL
BZ220783
L of 2B25 (male locker room)
DENTAL/ORAL SURG
BZ220711
2H40 (R side, procedure room)
DERMATOLOGY
BD532593
btwn 2F34 & 2F35 (provider's offices)
GENERAL SURG
BZ220665
2Q08 (HM station)
ICU
BZ220760
2O21 (RN station)
ICU
BZ220715
2PC3 (ICU-ER entry)
ICU (HALL)
BZ220762
2W05 (NEAR SOILED UTILITY RM)
MBU
BZ220645
2X07
MBU
BZ220691
2Z14
MBU
BZ220748
2X01(NURSERY)
MBU
BZ220743
2P14 (NEXT TO COMM RM; ACROSS TRIAGE #1)
MBU
BZ220757
2R05 (NEXT TO LACTATION RM)
MBU (HALL)
BZ220750
2R06 (NEXT TO CASE MGMT OFFICE)
MBU (HALL)
BZ220672
NEXT TO 2K21 (Child Psychologist Room)
MENTAL HEALTH
BZ220753
2JC4 (waiting room)
MENTAL HEALTH
BZ220746
near 2VC5
MAIN OR
BZ220772
near 2Z-A04
MAIN OR
BZ220741
FRONT CHECK OUT (2U06)
MAIN OR
BL836471
near 2T10
MAIN OR
BZ220778
near 2T04
MAIN OR
BZ220693
between 2Z03 & 2Z07
MAIN OR
BZ220761
2L04
MSU
BZ220779
2M10
MSU
BZ220768
2N18
MSU
BZ220744
2PC5
MSU (HALL)
BZ220694
across 2D22 (Nurse's office)
OCC HEALTH
BZ220765
2CC2 (next to OPTOM/OPHTAL front desk/main entrance)
OPHTHAL/OPTOM
BZ532627
Main hallway, next to staff restroom across 2D12
OPTOMETRY
BZ220791
2H16 (across double doors in clinic)
UROLOGY
BZ220774
2GC3 (outside clinic; inbetween UROLOGY & GEN SURG)
UROLOGY
BLDG 50 - 3RD FLOOR
Serial number
Location
DEPT
BZ220667
3A04 (entrance to CMD SUITE)
CMD SUITE
BD532611
btwn 3A05 (copy rm) & 3A07 (CMC office)
CMD SUITE
BD532615
3M01(ROOF ACCESS)
DZSP
BD532610
3M01(North Penthouse, AHU 2-1)
DZSP
BD532597
3MC1 (North Penthouse, Beside Door Exit to Stair #5)
DZSP
BD532617
3M01(North Penthouse, Mezzanine, stairs)
DZSP
BZ220755
3M01 (North Penthouse, AHU 1-10)
DZSP
BD532587
3M01 (North Penthouse, AHU 3-1)
DZSP
BD532616
3MS5 (Exit to Stair 5, 3rd deck landing)
DZSP
BD532606
3U01 (South Penthouse, AHU 2-4)
DZSP
BZ220780
3U01 (South Penthouse, AHU 1-5)
DZSP
BD532602
3UC1 (South Penthouse, AHU 1-11)
DZSP
BD220781
3U01(South Penthouse, AHU 2-11)
DZSP
BD532613
3U01 (South Penthouse, AHU 2-10)
DZSP
D-07345920
3UC1 (South Penthouse, AHU 2-8)
DZSP
BD532586
next to 3G07 (server room)
HRD
BZ220671
btwn rm 3E10 & 3E12
HRD
BZ220771
in hallway btwn 3E03 (XO board room) & 3E05 (PAO office)
HRD
BZ220775
across from 3C14 (CMD SUITE LOUNGE)
HRD
BZ220669
outside 3G14 (LCPO office)
IMD
BZ220745 *6 YR
3G07 (server room)
IMD
BZ220790
3J08 (entrance to QM office - R side)
QM
BD532589
3J06 (near printing room)
STAFF ED
BD532584
3I03 (entrance to SEAT)
STAFF ED
BLDG 61
Serial number
Location
DEPT
SN335507
SECOND FLOOR
PREV MED
BD532591
OUTSIDE KITCHEN
PREV MED
KZ335511
MAIN ENTRANCE
PREV MED
SV915145
PODIUM 1
PREV MED
RW761896
PODIUM 2
PREV MED
KZ335505
CHIEF'S MESS
SEAT
WAREHOUSE 4
Serial number
Location
DEPT
RW762731
WAREHOUSE 4
MORGUE (PAD)
SN291003
MMD SUPPLY/CBRNE ROLL UP DOOR
DZSP
SN335538
BACK EXIT DOOR
DZSP
WAREHOUSE 6
Serial number
Location
DEPT
SH038804
WAREHOUSE 6
MMD
PA480337
WAREHOUSE 6
MMD
AL469287
WAREHOUSE 6 (BTWN A9 & A11)
MMD
KZ335512
WAREHOUSE 6 (BTWN A3 & A4)
MMD
KZ335543
WAREHOUSE 6 (BTWN C1 & C2)
MMD
E63632357 2.5 LBS
WAREHOUSE 6 (FORKLIFT)
MMD
SUPPORT BLDGS
Serial number
Location
DEPT
K-065880
LOX (BLDG 45, beside entrance door)
DZSP
RW761911
FIRE PUMP (BLDG 45)
DZSP
BZ220645
WATER SOFTENER(NEAR CANOPY)
DZSP
SN915189
WATERSOFTENER (ER - BLDG 57)
DZSP
BZ220679
MACERATOR (BLDG 48)
DZSP
BD532582
BLDG 7 (OUTSIDE)
DZSP
WE273869
BLDG 7 (Left of entrance - inside)
DZSP
B65164511
GYM (front entrance) BLDG 70
PRT
KM00578957
GYM (back exit, near locker rooms) BLDG 70
PRT
CUP
Serial number
Location
DEPT
PX109471
SWITCH GEAR RM #109, NORTHSIDE ENTRANCE
DZSP
MR932000
RM 101, CHILLER #1, BESIDE ENTRANCE DOOR
DZSP
XU971659
RM 108 (GENERATOR RM, NORTH WALL) BESIDE DOUBLE DOOR
DZSP
E64061289
RM 108 (GENERATOR RM, SOUTH WALL) BESIDE GENERATOR
DZSP
AV986618
RM 108, GENERATOR RM ENTRANCE
DZSP
Z942657
RM 107 (BOILER/HEATING RM) BACK EXIT DOUBLE DOOR
DZSP
Z942656
RM 107 (BOILER.HEATING RM) BESIDE FRONT ROLL UP DOOR
DZSP
WT298409
RM 107 (TUNNEL)
DZSP
RW761923
RM 104 (PWR SWITCH BOARD) BESIDE BACK EXIT DOUBLE DOOR
DZSP
RW761924
RM 105 (EMERGENCY PWR) BESIDE BACK EXIT DOUBLE DOOR
DZSP
Z942648
RM 101, CHILLER RM, NEXT TO CR NEXT TO PANEL BOX
DZSP
YE823754
SWITCH GEAR RM #109, BACK EXIT DOOR
DZSP
BRANCH MEDICAL CLINIC
Serial number
Location
DEPT
SN26975
M108 (outside xray)
BMC
SN27232
Outside Rm 104 & 105
BMC
SN27017
WAITING RM 128
BMC
SN27005
outside M124
BMC
SN061237
outside M119
BMC
SN761894
GENERATOR
DZSP
SN26993
btwn RM 225 & 226 (hall)
IH
SN27025
btwn RM 220& 221 (hall)
IH
SN27079
RM 217 (office)
IH
SN397464
M208
PREV MED
KZ291012
M201
PREV MED
BRANCH DENTAL CLINIC
Serial number
Location
DEPT
SH038787
BLDG 3 EXTERIOR
BDC
BZ220764
100D
BDC
WE274109
1A
BDC
SN520886
GENERATOR
DZSP
SV915134
BDC
WE273931
BDC
LW128093
BDC
WE274110
110A
BDC
WE274117
BDC
SN739613
001 COMPRESSOR
BDC
NM074688
BLDG 2
BDC
RP426982
BLDG 2
BDC
LW128097
BLDG 3
BDC
NA061198
BLDG 3
BDC
2.5 LBS
5 LBS
5 LBS (NON-METALLIC TYPE)
10 LBS
20 LBS (K TYPE)
TOTAL FIRE EXTINGUISHERS