This is a solicitation for project number 652-CSI-204 to provide a new addition to house two new MRIs at a VA medical center. The project includes demolishing existing structures and preparing the site for construction. The single story addition will be approximately 2,785 square feet and utilize exterior construction to match the existing facility. Interior finishes will also match standard materials, colors and patterns used elsewhere in the facility. The scope includes relocating an existing MRI trailer and associated services. All work must be performed in accordance with provided drawings, specifications and a statement of work. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6 is the agency issuing this solicitation.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HHL
HL-1
SUPPLY AIR
SPS
SP-1
HT
H-2
PSH
PRESSURE SWITCH TO
DISABLE FAN WHEN HIGH
PRESSURE LIMIT SETPOINT IS
REACHED
ZC
HC-1
L P
S
LPR
H
SD
DUCT
DETECTOR BY
DIV. 28
A F
T E
R F
IL
T
E R
DPT
TT
T-5
SUPPLY FAN
(500-1Y-SF-2)
STS
SF
HS
CS
IT-2
VFD
SPD
SF
ALA
SF
A F
M D
FT
AF-3
TT
T-3
TT
T-4
D X
C O
O L
CC
CC-1
P R
E H
E A
T
TT
T-2
P R
E F
IL
T
E R
DPT
F
IL
T E
R
DPT
OUTSIDE
AIR IN
STS
EF
HS
CS
IT-1
VFD
SPD
EF
ALA
EF
TT
T-2
A F
M D
FT
AF-2
RELIEF AIR
OUT
TT
T-1
NEW GLOBAL
SENSOR
RETURN FAN
(500-1Y-RF-2)
DPT-3
DPT-2
DPT-1
DIFFERENTIAL
PRESSURE
TRANSMITTER (TYP.)
SEE STEAM HUMIDIFIER
CONTROLS ON M-504
H W
R
H W
S
ZC
V-1
CONDENSING
UNIT
PROVIDE 10
ADDITIONAL POINTS
THROUGH BACNET
AS SELECTED BY THE
VA
SST
CU-1
CS
CU-1
ALA
CU-1
V-1
A F
M D
FT
AF-1
D C
W
D-1 D-2
RETURN
AIR IN
HT
H-1
ZC
D-1
ZC
D-2
D-3
ZC
D-3
1. GENERAL FAN AND TEMPERATURE CONTROL
1.1. FAN OPERATION: AHU SUPPLY FAN (SF-2) AND RETURN FAN (RF-2) SHALL BE INTERLOCKED TO OPERATE AT THE SAME
TIME. INTERLOCK AREA EXHAUST FANS WITH 500-1Y-AHU-2.
1.2. OPERATION: OUTDOOR AIR AND RELIEF AIR DAMPERS SHALL MODULATE OPEN. SUPPLY AND EXHAUST FAN SHALL OPERATE ON TIME SCHEDULE. ADJUST FAN SPEED THROUGH THE VARIABLE FREQUENCY DRIVE TO MEET THE
AIRFLOW QUANTITIES SHOWN ON THE DRAWINGS.
1.3. DISCHARGE SUPPLY AIR TEMPERATURE SETPOINT SHALL BE SET FOR 55˚F (ADJ).
1.4. TEMPERATURE OF OUTDOOR AIR SHALL BE MONITORED BY A TEMPERATURE SENSOR (T-1).
1.4.1. IF THE LEAVING TEMPERATURE (T-3) IS 5 DEGREES F (ADJ) BELOW THE DISCHARGE AIR SETPOINT TEMPERATURE, THE HEATING HOT WATER VALVE V-1 SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. THE HEATING HOT WATER VALVE, V-1 SHALL MODULATE TOWARD CLOSE IF THE
LEAVING TEMPERATURE (T-3) RISES TO THE DISCHARGE AIR TEMPERATURE SETPOINT.
1.4.2. IF THE LEAVING TEMPERATURE IS MORE THAN 2 DEGREES ABOVE SETPOINT FOR 20 MINUTES, THE
MECHANICAL COOLING (CC) SHALL BE ENERGIZED TO OPERATE THROUGH THE CONDENSING
UNIT MANUFACTURER’S CONTROLS TO MAINTAIN DISCHARGE AIR SETPOINT. COOLING SHALL BE
DE-ENERGIZED IF THE LEAVING TEMPERATURE DROPS ONE DEGREE BELOW THE DISCHARGE AIR
TEMPERATURE SETPOINT.
1.5. OPERATION: IN UNOCCUPIED MODE, ENERGIZE SUPPLY AND RETURN FANS AND APPLICABLE COIL TO MAINTAIN
65 DEGREES F (ADJ) TO 78 DEGREES F (ADJ) .
1.6 AIRFLOW MEASURING STATIONS (AF-1, AF-2, AND AF-3) ON THE OUTDOOR AIR, RETURN AIR, AND SUPPLY AIR STREAMS, RESPECTIVELY, SHALL MONITOR AND REPORT TO THE BAS THE SUPPLY AND EXHAUST AIRFLOW
AMOUNTS IN CFM
2. ECONOMIZER:
2.1. A COMPARATIVE TEMPERATURE ECONOMIZER STRATEGY SHALL BE UTILIZED. THE OUTDOOR AIR DAMPER SHALL MODULATE OPEN AND THE RETURN AIR DAMPER SHALL MODULATE CLOSED WHEN OA ENTHALPY IS LESS THAN
RETURN AIR ENTHALPY IN COOLING MODE.
3. SAFETY CONTROL/PROTECTION:
3.1 DUCT DETECTOR SHALL BE FURNISHED BY FIRE ALARM CONTRACTOR. THE DUCT DETECTOR SHALL DE-ENERGIZE THE SUPPLY FAN SF-1 (INCLUDING INTERLOCKS), SIGNAL FIRE ALARM PANEL AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE PRODUCTS OF COMBUSTION. HARD WIRE DUCT DETECTOR TO SF-1 CONTACTOR OR FIRE ALARM
INPUTS ON VFD.
3.2 PRESSURE PROTECTION: A HIGH PRESSURE TRANSMITTER LOCATED AT THE SUPPLY FAN DISCHARGE SHALL
DE-ENERGIZE THE SUPPLY AIR FAN IF ITS SETPOINT, 5” WG ( ADJUSTABLE), IS REACHED.
4. ALARMS:
4.1 ALARM FOR DIRTY FILTER WHEN PRESSURE DROP EXCEEDS 0.5” WG ABOVE INITIAL PRESSURE DROP.
4.2 ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS BELOW 45°F IN HEATING MODE.
4.3 ALARM IF AHU SUPPLY OR RETURN AIR FAN FAILS TO START OR FAILS DURING OPERATION.
4.4 ALARM IF UNIT DISCHARGE STATIC PRESSURE EXCEEDS 5” WG.
4.5 ALARM UPON SMOKE DETECTOR ACTIVATION.
5. GRAPHICS AND MONITORING:
5.1 BAS FRONT END SYSTEM SHALL INCLUDE GRAPHICS SHOWING ALL HVAC SYSTEMS, ALARMS AND OTHER POINTS SHOWN ON THE DRAWINGS AND INCLUDED IN THE SPECIFICATIONS AND IN ACCORDANCE WITH VA REQUIREMENTS.
VFDS SHALL REPORT OPERATIONAL AND ALARM CONDITIONS TO THE BAS.
6. DDC PANELS:
6.1 PROVIDE NETWORK AREA CONTROL PANELS WITH LCD READOUT AND KEYPAD IN ACCORDANCE WITH THE SPECS TO BE LOCATED AS SHOWN ON THE DRAWINGS TO SERVE AHU, TERMINAL BOXES, AND OTHER EQUIPMENT.
SYSTEM:
MODULAR ROOFTOP AIR HANDLER
POINT
LEGEND
SYSTEM
OUTPUTS
BINARY ANA-
LOG
BINARY ANALOG
SYSTEM INPUTS SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
ALARM
PROCESSING
PAGE:
SYSTEM COMPONENT:
RETURN AIR TEMPERATURE
RETURN AIR FLOW (CFM)
PRE-HEAT TEMPERATURE
COOLING COIL TEMPERATURE
DISCHARGE STATIC PRESSURE
SUPPLY AIRFLOW (CFM)
RETURN FAN STATUS
SUPPLY FAN STATUS
STATIC PRESSURE HIGH LIMIT
SUPPLY FAN VSMC ALARM
RETURN FAN VSMC ALARM
DUCT DETECTOR
RETURN FAN VSMC
SUPPLY FAN VSMC
OUTSIDE AIR DAMPER
RELIEF AIR DAMPER
PREHEAT COIL VALVE
COOLING
RETURN FAN START/STOP
SUPPLY FAN START/STOP
AIRFLOW MONITORING - OA
AIRFLOW MONITORING - SA
AI-1
AI-3
AI-3
AI-4
AI-5
BI-1
BI-2
BI-3
BI-4
BI-5
BI-6
AO-1
AO-2
AO-3
AO-4
AO-6
AO-7
BO-1
BO-2
FT-1
FT-3
T-2
AF-2
T-3
T-4
SP-1
AF-3
STS-RF
STS-SF
SP-1
ALA-SF
ALA-RF
SD
SPD-RF
SPD-SF
D-1
D-2
V-1
CC-1
SST-RF
SST-SF
AF-1
AF-3
P O
IN
T
ID
A B
B R
E V
IA
T
IO
N
P R
IO
R
IT
Y
/A D
D A
LT
E
R
-- -- -- -- -- -- --E
LE
C T R
IC
D
E V
IC
E
S T A
R T /S
T O
P
O P
E N
/C
LO
S E
S P
E E
D C
O M
M A
N D
V A
LV
E
P O
S
IT
IO
N
D A
M P
E R
P O
S
IT
IO
N
S T A
T U
S A
LA
R
M P
R E
S S
U R
E
H
IG
H H
U M
ID
IT
Y
H
IG
H S
T A
T
IC
P R
E S
S U
R E
LO
W
T E
M P
E R
A T U
R E
T E
M P
E R
A T U
R E
T
P R
E S
S U
R E
P O
S
IT
IO
N
F
LO
W P
E R
C E
N T
S T A
T
IC
P R
E S
S U
R E
C A
R B
O N
M O
N O
X
ID
E
H U
M
ID
IT
Y
V A
C U
U M
LO
C
A L
A
LA
R M
P A
N E
L
A R
E A
A
LA
R M
P A
N E
L
M A
S T E
R A
LA
R
M P
A N
E L
H
IG
H L
IM
IT
LO
W
L
IM
IT
S C
H E
D U
LE
S
T A
R T /S
T O
P
F U
N C
T
IO
N D
U T Y C
Y C
LE
T E
M P
. E C
O N
O M
IZ
E
R
E N
T H
A
LP
Y E
C O
N O
M
IZ
E R
T E
M P
E R
A T U
R E
R E
S E
T
D E
M A
N D
L
IM
IT
IN
G
T E
M P
E R
A T U
R E
O V
E R
R
ID
E
S T A
T
IC
P R
E S
S U
R E
R E
S E
T
P R
E S
S U
R E
/V O
L.
C
O N
T R
O L
F A
IL
U
R E
M O
D E
S P
A C
E T
E M
P . C
O N
T R
O L
F U
LL
C
O M
M U
N
IC
A T
IO
N
T R
E N
D
IN
G
REMARKS
FULL COMMUNICATION
FULL COMMUNICATION
AI-7
AI-8
PREFILTER PRESSURE DIFFERENTIAL
AFTER FILTER PRESSURE DIFFERENTIAL
AI-9
AI-12
DPT-1
DPT-2
OUTSIDE AIR TEMPERATURE
AI-13
T-1
CONDENSING UNIT STATUS BI-7
B
B
CONDENSING UNIT ALARM BI-8 ALA-CU
ROOM PRESSURE MONITOR DECON/ANTE BI-9 -
ROOM PRESSURE MONITOR DECON/CLEAN PREP BI-10 -
BI-11 -PROVIDE 3 BI POINTS FROM CONDENSING UNIT
BACNET COMMUNICATION AS SELECTED BY
THE VA
BI-12 -
BI-13 -
CONDENSING UNIT START/STOP BO-3 SST-CU
B
B
AI-14 -
AI-15 -
AI-16 -
AI-17 -
AI-18
PROVIDE 7 AI POINTS FROM CONDENSING UNIT
BACNET COMMUNICATION AS SELECTED BY THE
VA
AI-10
STS-CU B
B
B
LEGEND:
B - BACNET AVAILABLE POINT
- TCC POINT
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
NOTES:
1. MULTIPLE CONTROLLERS SHALL BE USED FOR OBTAINING POINTS. COORDINATE CONTROLLERS PRIOR TO SUBMITTALS.
2. ALL POINTS SHALL APPEAR ON GRAPHICS.
AI-2
DISCHARGE AIR TEMPERATURE T-5
OUTSIDE AIRFLOW (CFM) AI-11 AF-1
AIRFLOW MONITORING - RA FT-2 AF-2
RETURN AIR DAMPER AO-5 D-3
CONTROL DIAGRAM ABBREVIATIONS
AF AIR FLOW MONITORING
AFMD AIR FLOW MEASURING DEVICE
AI ANALOG INPUT
ALA ALARM
AO ANALOG OUTPUT
BI BINARY INPUT
BO BINARY OUTPUT
CS CURRENT SENSOR
D DAMPER
DPT DIFFERENTIAL PRESSURE TRANSDUCER
FT FLOW TRANSMITTER
H HUMIDITY
HL HUMIDITY LIMIT
RF RETURN FAN
SD SMOKE DETECTOR (BY DIV. 28)
SF SUPPLY FAN
SP STATIC PRESSURE
SPD SPEED
SPS STATIC PRESSURE SENSOR
SST STATUS
TT TEMPERATURE TRANSMITTER
V VALVE
EXISTING ENGINEERING
CONTROL CENTER
EXISTING
NETWORK
BACNET
BUILDING
CONTROLLER
(JACE)
BACNET
BUILDING
CONTROLLER
(B-BC)
BACNET
BUILDING
CONTROLLER
(B-BC)
EXISTING
GLOBAL
CONTROLLER
B-
AAC
B-
AAC
B-
AAC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
B-
ASC
EXISTIN
G B-ASC
EXISTIN
G B-ASC
EXISTIN
G B-ASC
EXISTIN
G B-ASC
EXISTIN
G B-ASC
EXISTIN
G B-ASC
EXISTING CONTROL
SYSTEM TO REMAIN
EXISTING CONTROLLER
PROTOCOL
CONTROL SYSTEM CONFIGURATION
EXISTING ECC TO REMAIN. EXISTING
CONTROL SYSTEM SOFTWARE TO CO-
EXIST ON ECC. INSTALL NEW BACNET
CONTROLS ON CURRENT PROJECT,
EXISTING CONTROL SYSTEM TO REMAIN,
RE-USE EXISTING COMMUNICATION
NETWORK.
MSTP COMMUNICATION
(TYPICAL)
EXISTING COMMUNICATION
NETWORK
NOTES:
1. REUSE EXISTING BACNET COMMUNICATION NETWORK.
2. EXISTING CONTROLLERS TO REMAIN.
3. INSTALL MULTIPLE BUILDING CONTROLLERS AS REQUIRED.
NEW BUILDING CONTROLLERS TO HAVE LCD DISPLAY AND
KEYPAD.
4. INSTALL NEW CONTROLLERS (B-AAC, B-ASC) AS REQUIRED.
5. UPDATE EXISTING GRAPHICS TO INCLUDE NEW DEVICES AND
RELATED POINTS.
PROVIDE NEW BUILDING
CONTROLLER
POINT NAME:
DISCHARGE AIR TEMPERATURE (T-5)
OUTSIDE AIR TEMPERATURE (T-1)
SPACE HUMIDITY (H-1)
HARDWARE POINTS
AI AO
X
X
X
X
BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
X
X
X
X
X
X
X W/ TEMPERATURE RESET
HUMIDIFIER START/STOP (SST-H)
SUPPLY AIR HUMIDITY (H-2) X XX
SUPPLY AIR HUMIDITY HIGH LIMIT (HL-1) X XX
STEAM HUMIDIFIERS SEQUENCE:
SPACE AIR HUMIDITY SHALL BE MONITORED. ON A CALL FOR HUMIDIFICATION AND IF
OUTDOOR TEMPERATURE IS BELOW 50°F, HUMIDIFIER SHALL ENABLE TO MAINTAIN THE
SPACE AIR HUMIDITY SET POINT TO 30% (ADJUSTABLE). THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR DUCT 8 FEET AWAY FROM THE HUMIDIFIER SHALL DISABLE
THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE BMS, IF THE SUPPLY AIR HUMIDITY
EXCEEDS 90% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE AIRFLOW BEFORE
HUMIDITY CONTROLS ARE ACTIVATED.
ZC
PC
H
SUPPLY AIR
TAP WATER
STEAM CONDENSATE
HHL
8'-0" MIN.
HT
H-2
AFS
STEAM SUPPLY TO DISPERSION TUBE
HUMIDIFER
BACNET CONTROLLER
STEAM DISPERSION
TUBE AHU
H-1
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7 /2
:5
:0
A
M
M-504
MECHANICAL CONTROLS
9 10SMH
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 OCTOBER 7, 2020
BID DOCUMENTS
652-CSI-20419-088
SPG
SCALE: N.T.S.
AIR HANDLING UNIT (AHU) SCHEMATIC
SCALE: N.T.S.
AIR HANDLING UNIT (AHU) SEQUENCE OF OPERATION AND POINTS LIST
SCALE: N.T.S.
BACNET SYSTEM ARCHITECTURE
SCALE: N.T.S.
STEAM HUMIDIFIER POINTS LIST
SCALE: N.T.S.
STEAM HUMIDIFIER CONTROLS
F
R P
O
SS
E
OI LNA
GNE
IN
E R
E
N
SILAS PERRY GEORGE
M O
C O
M
OHL
EA T
W
I N
A
V F
I G
I R
Lic. No. 0402056110
DocuSign Envelope ID: 9AC413A8-6793-4109-90C2-2F2A5DEDE49E
10/7/2020
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/7 /2
:5
:0
A
M
M-601
MECHANICAL SCHEDULES
10 10SMH
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 OCTOBER 7, 2020
BID DOCUMENTS
652-CSI-20419-088
SPG
FAN SCHEDULE
MARK LOCATION BUILDING/AREA SERVED SERVICE AIRFLOW TYPE DRIVE HP (W) VOLT PHASE
SPEED
CONTROL REMARKS
500-1Y-SF-2 INSIDE AHU MRI EXPANSION 500-1Y-AHU-2 3500 CFM DUAL PLENUM DIRECT 5 HP 480 3 VARIABLE
500-1Y-RF-2 INSIDE AHU MRI EXPANSION 500-1Y-AHU-2 3500 CFM DUAL PLENUM DIRECT 2 HP 480 3 VARIABLE
500-1Y-EF-4 ABOVE CEILING MRI EXPANSION GENERAL EXHAUST 230 CFM INLINE CENTRIFUGAL CABINET DIRECT (109 W) 120 1 CONSTANT
500-1Y-EF-5 ROOF MRI 3 EMERGENCY EXHAUST 810 CFM DOWNBLAST CENTRIFUGAL DIRECT (172 W) 120 1 CONSTANT 1,2,3,4
500-1Y-EF-6 ROOF MRI 4 EMERGENCY EXHAUST 740 CFM DOWNBLAST CENTRIFUGAL DIRECT 0.141 HP 120 1 CONSTANT 1,2,3,4
STEAM HUMIDIFIER SCHEDULE
HUMIDIFIER
MARK LOCATION
SYSTEM AIR
HANDLING AIRFLOW
# OF
MANIFOLDS SOURCE
STEAM TRAP
REMARKS
PRESSURE
ENT VALVE
PRESSURE ENT
HUMIDIFIER
FLOW
(LBS/HR)
CAPACITY
(LBS/H)R
500-1Y-SH-2 INSIDE AHU 500-1Y-AH-2 3500 2 ELECTRIC
HUMIDIFIER
15 psi 7 psi 18
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE MODULAR OUTDOOR UNIT DX COOLING COIL, HOT WATER HEATING COIL, STEAM HUMIDIFIER AND PLENUM FANS.
3. PROVIDE SLEEVED UV-C LIGHTS DOWNSTREAM OF COOLING COIL WITH VIEWING WINDOW AND DOOR INTERLOCK SWITCH.
4. PROVIDE WITH SINGLE POINT 480V POWER CONNECTION AND INTERNAL TRANSFORMERS FOR CONTROLS, LIGHTS AND SERVICE RECEPTACLES.
5. BALANCE AIRFLOWS PER THE FLOOR PLANS. SCHEDULED AIRFLOWS ARE NOMINAL FOR SIZING EQUIPMENT.
6. BASIS OF DESIGN IS TRANE PERFORMANCE CLIMATE CHANGER CSAA008.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH STANDARD DISCONNECT, BACKDRAFT DAMPER, 13.5" ROOF CURB WITH DAMPER TRAY, ALUMINUM BIRD SCREEN AND FAN SPEED CONTROLLER.
3. PROVIDE CONTROLLER AS REQUIRED TO INTEGRATE INTO EXISTING JOHNSON CONTROLS BUILDING AUTOMATION SYSTEM.
4. BASIS OF DESIGN IS LOREN COOK.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH 24V POWER FROM CONTROL CIRCUIT LOCATED IN ROOM 1Y-113.
3. PIPE RUNOUT SIZE 3/4".
AIR DEVICE SCHEDULE (EXHAUST)
DIFFUSER
MARK TYPE Min Flow Max Flow MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL
EG-23 EGG CRATE 60 100 0.09 in-wg CEILING 24x24 6"Ø 13 No WHITE ALUMINUM
EG-24 EGG CRATE 0.09 in-wg CEILING 24x24 No WHITE
AIR DEVICE SCHEDULE (RETURN)
DIFFUSER
MARK TYPE Max Flow Min Flow MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE MAX NC
DAMPER
DIFFUSER FINISH MATERIAL REMARKS
RG-9 EGG CRATE 555 210 0.08 in-wg CEILING 12x12 10x10 20 No STEEL
RG-12 EGG CRATE 555 210 0.08 in-wg CEILING 24x24 10X10 20 Yes ALUMINUM
RG-23 EGG CRATE 250 170 0.09 in-wg CEILING 24x24 10"Ø 14 No ALUMINUM
RG-24 EGG CRATE 400 240 0.09 in-wg CEILING 24x24 12"Ø 12 No STEEL
AIR DEVICE SCHEDULE (SUPPLY)
DIFFUSER
MARK TYPE
AIRFLOW
MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE DAMPER FINISH MATERIAL REMARKSMIN. MAX.
SQUARE CONE 136 230 0.07 in-wg CEILING 24x24 -- No WHITE STEEL
SD-11 LOUVERED FACE 80 180 0.08 in-wg CEILING 24x24 6"Ø No WHITE ALUMINUM 1, 2
SD-12 LOUVERED FACE 140 280 0.08 in-wg CEILING 24x24 8"Ø No WHITE ALUMINUM 1, 2
SD-13 LOUVERED FACE 220 380 0.07 in-wg CEILING 24x24 10"Ø No WHITE ALUMINUM 1, 2
SD-14 LOUVERED FACE 315 550 0.08 in-wg CEILING 24x24 12"Ø No WHITE ALUMINUM 1, 2
SD-31 LOUVERED FACE 80 180 0.10 in-wg CEILING 12x12 6"Ø No WHITE ALUMINUM 1, 2
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE DAMPER IN BRANCH DUCT AS SHOWN ON PLANS.
VALVE SCHEDULE
MARK
SYSTEM AND/OR
SERVICE TYPE SIZE FLOW REMARKS
500-1Y-V-TU-1 3-WAY FLOATING VALVE 3/4" -3/4" -3/4" 4.0 GPM
500-1Y-V-TU-2 2-WAY FLOATING VALVE 3/4" -3/4" 1.6 GPM
500-1Y-V-TU-3 2-WAY FLOATING VALVE 3/4" -3/4" 4.3 GPM
500-1Y-V-TU-4 2-WAY FLOATING VALVE 3/4" -3/4" 2.4 GPM
V-AH-2 3-WAY FLOATING VALVE 1 1/2" -1 1/2" -1 1/2" 7.6 GPM
SINGLE DUCT AIR TERMINAL SCHEDULE
MARK ROOM SERVED
SYSTEM AIR
HANDLING VAV SIZE
AIRFLOW CONTROL
TYPE
CONTROL
SEQUENCE
HOT WATER HEATING COIL
REMARKSAIRFLOW MIN REHEAT ROWS EAT LAT EWT LWT FLOW
500-1Y-2-TU-1 1Y-156 AHU-MRI 10 in 920 740 740 CAV 5°F DEADBAND 1 55 °F 95 °F 180 °F 160 °F 4.00 GPM
500-1Y-2-TU-2 1Y-151D AHU-MRI 6 in 375 300 300 CAV 5°F DEADBAND 1 55 °F 95 °F 180 °F 160 °F 1.60 GPM
500-1Y-2-TU-3 1Y-158 AHU-MRI 10 in 1000 810 810 CAV 5°F DEADBAND 1 55 °F 95 °F 180 °F 160 °F 4.34 GPM
500-1Y-2-TU-4 1Y-150,151,152,153,154 AHU-MRI 8 in 590 500 500 CAV 5°F DEADBAND 1 55 °F 95 °F 180 °F 160 °F 2.40 GPM
ELECTRIC STEAM HUMIDIFIER SCHEDULE
MARK LOCATION
SYSTEM AIR
HANDLING AIRFLOW
# OF
MANIFOLDS SOURCE
STEAM
KW VOLT PHASE MCA MOCP REMARKS
FLOW
(LBS/HR)
MRI-SH-1 1Y-113 500-1Y-AH-2 3500 1 TAP WATER 18 6 277 1 21.7 30 1
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATION.
AIR HANDLING UNIT SCHEDULE
MARK LOCATION BUILDING SERVED TYPE
AIRFLOW
SUPPLY FAN
MARK
RETURN OR
RELIEF FAN
MARK PREFILTER MARK
AFTERFILTER
MARK
FINAL FILTER
MARK
PREHEAT COIL
MARK
COOLING COIL
MARK REHEAT COIL
HUMIDIFIER
MARK REMARKSSUPPLY MIN OA RETURN
500-1Y-AH-2 INSIDE AHU MRI EXPANSION MODULAR ROOFTOP 3500 CFM 550 CFM 2950 CFM 500-1Y-SF-2 500-1Y-RF-2 500-1Y-PF-2-1
500-1Y-PF-2-2
500-1Y-AF-2-1 N/A 500-1Y-PHC-2 500-1Y-CC-2 N/A 500-1Y-SH-2
HYDRONIC PUMP SCHEDULE
MARK LOCATION BLDG SERVED SYSTEM TYPE
CIRCULATING FLUID
MIN % EFF
ELECTRICAL MOTOR
PHASE PHASE
ELECTRICAL MOTOR
REMARKSFLUID FLOW HEAD
NPSH
AVAILABLE TEMPERATURE
NOMINAL
POWER (HP) PHASE VOLT R.P.M.
SPEED
CONTROL
500-1Y-HWP-1 1Y-133 MRI EXPANSION HEATING HOT WATER SMALL FLEX INLINE PUMP 0 GPM 0 ftH2O 0.0 ftH2O -460 °F 2 HP 480 0
500-1Y-HWP-2 1Y-133 MRI EXPANSION HEATING HOT WATER SMALL FLEX INLINE PUMP 0 GPM 0 ftH2O 0.0 ftH2O -460 °F 2 HP 480 0
DX COOLING COIL SCHEDULE
MARK LOCATION BUILDING SERVED
SYSTEM AIR
HANDLING AIRFLOW
MAX FACE
VELOCITY APD
EAT LAT CAPACITY
REMARKSDB WB DB WB
TOTAL
(BTU/H)
SENSIBLE
(BTU/H)
500-1Y-CC-2 INSIDE AHU MRI EXPANSION 500-1Y-AH-2 3500 CFM 462 FPM 0.53 in-wg 80 °F 67 °F 55 °F 54 °F 142,052 95,988
HEATING HOT WATER COIL SCHEDULE
MARK LOCATION BUILDING SERVED
SYSTEM AIR
HANDLING AIRFLOW
MAX FACE
VELOCITY APD EAT LAT
CAPACITY
(BTU/H)
WATER
REMARKSFLOW EWT LWT
WPD
(FT HD)
500-1Y-PHC-2 INSIDE AHU MRI EXPANSION 500-1Y-AH-2 3500 500 FPM 0.10 in-wg 45 °F 65 °F 77,200 7.72 GPM 180 °F 160 °F 0.93
DUCTLESS SPLIT CONDENSING UNIT SCHEDULE
MARK COMPRESSOR TYPE POWER MCA MOCP REMARKS
500-1Y-OU-1 DC INVERTER-DRIVEN TWIN ROTARY 208, 1, 60 14 15
500-1Y-OU-2 DC INVERTER-DRIVEN TWIN ROTARY 208, 1, 60 13 20
500-1Y-OU-3 DC INVERTER-DRIVEN TWIN ROTARY 208, 1, 60 13 20
DUCTLESS SPLIT INDOOR UNIT SCHEDULE
TAG LOCATION TYPE AIRFLOW CAPACITY EAT DB
500-1Y-IU-1 1Y-159 WALL MOUNTED UNIT 320-370-425 18,000.0 Btu/h 75 °F
500-1Y-IU-2 1Y-155 WALL MOUNTED UNIT 320-370-425 18,000.0 Btu/h 75 °F
500-1Y-IU-3 1Y-162 WALL MOUNTED UNIT 320-355-390 12,000.0 Btu/h 75 °F
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH STANDARD WALL THERMOSTAT AND FILTER ALONG WITH CONDENSATE PUMP.
3. INDOOR UNIT POWERED THROUGH CONDENSING UNIT.
CONDENSING UNIT SCHEDULE
MARK LOCATION SYSTEM SERVED
COOLING CAPACITY
RANGE (BTU) COMPRESSOR TYPE POWER MCA MOCP REMARKS
500-1Y-CU-2 GRADE OUTSIDE 500-1Y-AH-2 150,000 DUAL SCROLL / DUAL CIRCUITS 480/3 26 35
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. BASIS OF DESIGN IS TRANE TTA150.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
EXPANSION TANK SCHEDULE
MARK LOCATION SYSTEM TYPE
APPROX.
SYSTEM
VOLUME
SYSTEM TEMPERATURE
RANGE
INITIAL
PRESSURE IN
TANK
MAX
OPERATING
PRESSURE
FILL PRESSURE AT TANK TANK
VOLUME
ACCEPTANCE
VOLUME
PIPE SIZE TO
TANK REMARKSMIN TEMP MAX TEMP RELIEF VALVE AT TANK
500-1Y-ET-1 1Y-133 HEATING HOT WATER HORIZONTAL DIAPHRAGM 230 gal 125 °F 180 °F 15.8 psi 125.0 psi 18.0 psi 18.0 psi 44.4 gal 22.6 gal 3/4"
AIR SEPARATOR SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE TYPE SIZE FLOW WPD
BUILT-IN
STRAINER
REQUIRED REMARKS
500-1Y-AS-1 1Y-133 HOT WATER TANGENTIAL 2" 60.0 GPM 1 ftH2O Yes
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATION.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATION.
F
R P
O
SS
E
OI LNA
GNE
IN
E R
E
N
SILAS PERRY GEORGE
M O
C O
M
OHL
EA T
W
I N
A
V F
I G
I R
Lic. No. 0402056110
DocuSign Envelope ID: 9AC413A8-6793-4109-90C2-2F2A5DEDE49E
10/7/2020
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL
ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING
HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT
DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST
COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S
SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED
(MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED
THIRD PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE
GOVERNMENT, SHALL BE PROVIDED.
19. COMPRESSION COUPLINGS AND CONNECTIONS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
ELECTRICAL SYMBOL LEGEND
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION BONDING PLATE
LIGHTING SYMBOL LEGEND
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER, 0-10V DIMMING
D: LINE VOLTAGE DIMMER, 0-10V DIMMING
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
OS
OS
LS
---PC EXTERIOR PHOTOCELL
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)
48"CR
ES
DC
RX
48" EMERGENCY PUSH BUTTON
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
S
NURSE CALL PATIENT STATION WITH PILLOW SPEAKER (GET WELL)
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
P
NURSE CALL PATIENT BED INTERFACE RECEPTACLE
B NURSE CALL CODE BLUE STATION
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)
D
NURSE CALL DUTY STATION
M
NURSE CALL MASTER STATION/CONSOLE
NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)
IC
INTERCOM WITH CAMERA
IC
INTERCOM MASTER WITH PUSH TO RELEASE DOORM
NURSE CALL WIRELESS ANTENNASNW
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
NURSE CALL EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
NCE
MATV
CCTV
LADDER CABLE TARY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
HEADWALL
18"
HEADWALL
/40"
40",72"
18"
60"
CEILING
CEILING
6' TO TOP
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
S
C
NURSE CALL STAFF TERMINAL
NURSE CALL PATIENT STATION WITH CALL CORD.
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
60"
HEADWALL
W WIRELESS PENDANT
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
ABOVE
DOOR
NURSE CALL DOME LIGHT
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
N
M
PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)
88" MOTION DETECTOR
MD
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
AREA OF REFUGE PANEL6' TO TOP
AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP
AOF
AOFA
IC AREA OF REFUGE INTERCOM48"
AREA OF REFUGE STROBE LIGHTCEILINGSL
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
N
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
48"
CEILING
CEILING
TELEMETRY ANTENNA - 2-4 PRCEILING
ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR
GENERAL TECHNOLOGY NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE
CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI
STANDARDS, AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607B OR 607A - GROUNDING AND BONDING
REQUIREMENTS FOR TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR
TELECOMMUNICATIONS PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY
AMERICAN ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS
NOTED OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6 COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6 KEYSTONE JACK WIRED PER T568A OR T568B AS
DIRECTED BY THE VA COR.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606A OR 606B EDITION AS WELL AS THE
STANDARDS SET FORTH BY THE VA HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569.B PARAGRAPH 4.5.6.2.
21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING
AND EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
23. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
24. DEVICES PLACE IN INTERCOMMUNICATION ROOM ROOM TO BE MOUNTED ON FIRE RETARDANT PLYWOOD.
GENERAL ELECTRICAL DEMOLITION NOTES
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE. MATERIALS DEEMED NOT SALVAGEABLE
SHALL BE REMOVED FROM THE PREMISES.
B. THE CONTRACTOR WILL BE HELD TO HAVE EXAMINED THE PREMISES AND SATISFIED HIMSELF AS TO EXISTING CONDITIONS UNDER WHICH HE WILL BE OBLIGED TO PERFORM HIS WORK. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE
CONTRACTOR SHALL COOPERATE WITH OTHER TRADES.
C. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES CONTINUATION THROUGH THE
AREA.
D. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
E. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND NEW
CONSTRUCTION.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING TO
REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY OWNER'S REPRESENTATIVE.
G. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
H. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
I. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT OF
FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR OWNER'S
REPRESENTATIVE.
J. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS
NOTED OTHERWISE.
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2 :5
P
M
E-001
ELECTRICAL GENERAL NOTES AND
SYMBOL LEGENDS
1 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
DocuSign Envelope ID: 98DCF9C5-99FD-4ED7-B6A5-2F60D4B88C55
11/10/202011/10/2020
GENERAL FIRE ALARM NOTES
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.
C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.
D. NFPA 70 NATIONAL ELECTRICAL CODE.
E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
G. NFPA 101 LIFE SAFETY CODE.
H. VA FIRE PROTECTION DESIGN MANUAL.
I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE
ALARM DEVICES. COORDINATE WITH COR.
9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE
LOCATION WITH THE SPRINKLER CONTRACTOR.
10. CONNECT ALL ELECTROMAGNETIC DOOR HOLD OPEN DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE
WITH THE DOOR HARDWARE CONTRACTOR.
11. PROVIDE RELAY CONTROL MODULES FOR PACS, COORDINATE WITH PHYSICAL ACCESS CONTROL SYSTEM
(PACS), CONTRACTOR AND COR.
12. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42"
(1.07M) AND NOT MORE THEN 48" (1.22M) FROM FINISH FLOOR.
13. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.
14. MATCH EXISTING FIRE ALARM SYSTEM RESPONSE. COORDINATE WITH COR AND FIRE ALARM SYSTEM
VENDOR/ MAINTAINANCE COMPANY
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM PULL SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM SMOKE DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
P
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM HEAT DETECTOR
48"
90"
90"
90"
FIRE ALARM PANEL
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
FLOW SWITCH
FAP
NAC
FAAP
TAMPER SWITCH
POST INDICATOR VALVEPIV
REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS
F FIRE ALARM BELL90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
F
S
HD
DUCT SMOKE DETECTOR *
AREA SMOKE DETECTOR *
DOOR RELEASE SMOKE DETECTOR *
ELEVATOR SMOKE DETECTOR *
MANUAL PULL STATION
ELEVATOR MACHINE ROOM HEAT DETECTOR
GENERATOR ROOM HEAT DETECTOR
SPRINKLER WATERFLOW/PRESSURE SWITCH
WATER CONTROL VALVE TAMPER
FIRE PUMP (ANY ALARM CONDITION REQUIRED
BY (NFPA 20)
HIGH/LOW PRESSURE DRY-PIPE SPRINKLER
SYSTEM
KITCHEN HOOD SUPPRESSION SYSTEM
GAS EXTINGUISHING SYSTEMS
DRY-PIPE VALVE ROOM TEMPERATURE ALARM
DEDICATED FIRE WATER STORAGE TANK LOW LEVEL
DEDICATED FIRE WATER STORAGE TANK LOW
TEMPERATURE
* WHILE NFPA 101 DOES NOT REQUIRE SOME DETECTORS TO NOTIFY BUILDING OCCUPANTS, VA REQUIRES ALL SMOKE DETECTORS, OTHER THAN DUCT SMOKE DETECTORS, TO NOTIFY BUILDING OCCUPANTS AS REQUIRED BY THE LIFE SAFETY CODE OR ITS REFERENCES.
** THOSE DOORS THAT ARE REQUIRED TO BE TIED TO THE FIRE ALARM SYSTEM SUCH AS DELAYED EGRESS AND ACCESS CONTROLLED DOORS.
a - DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
FIRE ALARM SYSTEM INPUT/OUTPUT MATRIX
OUTPUT
INPUT DEVICE
S
O U
N D
G E
N E
R A
L
B U
IL
D
IN
G
A L A
R M
F O
R
T
H E
R H
IG
H
R
IS
E
(N
N -H
E A
L T
H C
A R
S
E
S E
C T
IO
N
.2
.1
N
O T
IF
Y
N E
C E
S S
A
Y
A F
F F
O R
R E
S P
O N
F
R
H E
A L T
H C
A R
E A
N D
H
IG
H
R
IS
E B
U
IL
D
IN
G
L Y
A
L A
R M
S
IG
N
M
Y B
E D
IF
F
E R
E N
T
IF
F E
R E
N T
F L O
O R
S
N
O T
IF
Y
F
IR
P A
R T
M E
N T
IN
IT
IA
U P
E R
V
IS
O R
Y S
IG
N
A
-H
O U
R M
A N
N
P
IN
T
F O
R I M
M E
D
IA
S
P O
N S
E
C
L O
S E
A S
S O
C
IA
M O
K E
B A
R R
IE
R
D O
O
T H
E F
L O
O R
C
L O
S E
D A
M P
E R
S
N P
R O
X
IM
A T
E
T E
C T
O R
S
H U
T D
O W
N
IR
N D
L E
R S
E R
V E
D B
Y
E D
E T
E C
T O
R
R
E C
A L L E
L E
V A
T O
R
X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X Xa
X
X
X
L L
ELECTRICAL ABBREVIATIONS LIST
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VETERANS AFFAIRS
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OIT OFFICE OF INFORMATION
TECHNOLOGY
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX, (E) EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLA FULL LOAD AMPS
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSBD MAIN SWITCHBOARD
MT MOUNT
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2 :5
P
M
E-002
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
2 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
REF.
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F5 3/
G
F5 3/
G
F5 3/
G
F53/30G F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
F53/30G
24/36
24/36
24/24
24/3
/2
24/24
24/36
/2
24/24
24/36
24/24
24/
24/24
24/3
/2
24/24
24/24
24/
24/24
24/3
24/24
/2
/2
24/36
24/24
48" HIGH WALL
E.J.COVER
PLATE
E.J.
COVER
PLATE E.J.
COVER
PLATE
NUCLEAR MEDICINE
E.J.
COVER
PLATE
E. J. COVER PLATE
E.J. COVER
PLATE
PLATE
E.J. COVER
E.J. COVER
PLATE
CHAIRS
DAILY LOGS
PSYCHIATRIC DAY TREATMENT
(INPATIENT
PHARMACY)
ORTHOPAEDIC DENTAL RENOVATION AREA
E.J.
COVER
PLATE
COVER
E.J. PLATE
E.J.
CARE
COMMUNITY
CARE
COMMUNITY
WOMENS
CLINIC
STATION
TUG DOCK
DISCHARGE BOX
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
COOK
CHILL
FRIDGECOFFE
R
EF
U C R
BLK
BLK
BLK
TRANSPORT
CORE NO. 1
SHELVING
FIRE ARM
LOCKERS
VAULT
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
LOW COUNTER
COUNTER
FC
FCFC
FC
FC
FC
FC
FC
FC
FC
F.C.
FC
STORE
IV
NIC
2DRB
STORE
IV
5 6 7 81 2 3 4
FECFEC
FEC
FEC
FC
COPY STAND
FILES FILES
FAX
FLAT FILE
PAPER ST
TABLE
PLOTTER
PRINT PRINT PRINT
PLOTTER
COPY STAND
SCREEN
CUTTER
FILES FILES
DN
INDUSTRIAL
STAIR
DN UP
UP
UP
DN
DN
UP
DN
1W-118
1E-100A
1E-100
1E-100B
1E-100C
1E-103
1E-1041E-1051E-107
1E-108
1E-106
1E-109
CIX-4
DT-1
P4
P-10
P-9
DT-3
TOILET
OFFICE
WORKER
SOCIAL
PSYCHIATRIST
CLINICAL TEAMPSYCHIATRIST
LCSW
OFFICE
OFFICE
STAIR
RECEIVING
DISPATCH
OFFICE
CLINICAL
PSYCHOLOGIST
CLINICAL
TRAUMATIC
STRESS
DISORDER
POST
CORRIDOR
STORAGE
BOOTH
BOOTH
BOOTH BOOTHBOOTHBOOTH
CLOSET
CLOSET
P. TUBE
OFFICE
OFFICE
1B-105
OFFICE
OFFICE
1B-223
OFFICE
1B-246
OFFICE
PAT ADVOC
1B-222
PAT ADVOC
1B-221
1W-100B
1W-100C
MALE
PATIENT
TOILET
1S-136
FEMALE
PATIENT
TOILET
1S-135
MENS
LOCKER RM
1S-126
UNISEX
TOILET
1T-101
OFFICE
1T-100
OFFICE
1X-116
WAITING
ROOM
1X-118
BREAK ROOM
1X-117
CLERKS
TRAINING 1X-110
OFFICE
1X-119
EXAM RM
1X-121
EXAM RM
1X-122
RECEPTION
1X-120
STORAGE
1X-124
1X-123
1X-128
OFFICE
1X-112
1X-113
TOILET
1X-114
1X-126
CHIEF
PROSTHETICS
1X-115
1X-127
GRAPHIC
ALCOVE
1X-110C
ORTHOTICS
LAB
1X-109
SHOE
SHOP
1X-111
1X-129
CHIEF MENTAL
HEALTH
SVC
1E-130
CORRIDOR
C1E-4
CORRIDOR
C1E-6
CORRIDOR
C1E-3
CORRIDOR
C1E-2
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
SALLY PORT
CORRIDOR
C1D-1
CORRIDOR
CORRIDOR
C1D-11
CORRIDOR
C1D-3
CORRIDOR
C1D-5
CORRIDOR
C1D-4
CORRIDOR
C1D-8
CORRIDOR
C1D-6
SECRETARY
1E-131
PHYSICIAN
1E-128
ADMINISTRATIVE
OFFICE
1E-129
STORAGE
1E-132
CONFERENCE RM
1E-122
GROUP RM
1E-121
GROUP RM
1E-120
GROUP RM
1E-119
RECREATIONAL
THERAPY
1E-118
PSYCHIATRIC
TRAINING
OFFICE
1E-117
OFFICE
1E-157
RECREATION
THERAPY
1E-152
TOILET
1E-153
SOCIAL
WORKER
1E-149
SOCIAL
WORKER/
STUDENTS
1E-150
REHAB
TECHNICIAN
1E-148
RECREATION
THERAPIST
1E-147
UNISEX
TOILET
1E-146
HAC
1E-143
OCCUPATIONAL
THERAPIST
1E-144
OFFICE
1E-142
OFFICE
1E-140
COUNSELOR
SUPERVISOR
1E-141
PSYCHOLOGIST
1E-137
OFFICE
1E-133
OFFICE
1E-134
COUNSELOR
1E-138
PSYCHOLOGY
TECHNICIAN
1E-135
SUICIDE
PREVENTION
CASE MANAGER
1E-139
STAFF
LOUNGE
1E-126
ELEC
CLOSET
1E-145
MEDICATION
1E-151A
STAFF
TOILET
1E-125UNISEX
TOILET
1E-124
MEDICATION
DISPENSING
1E-151
NURSE
STATION
C1E-5
UNISEX
TOILET
1E-155
OFFICE
1E-154
STORAGE
1E-154B
WAITING
1E-116
OFFICE
1E-154C
CLINICAL
PSYCOLOGIST
1E-115
SOCIAL
WORKER
1E-114
OFFICE
1E-156
OFFICE
1E-159COUNSELOR
1E-113
LOCAL
RECOVERY
CO-ORDR
1E-160
CLINICAL
SOCIAL WORKER
1E-112
DAY ROOM
1E-158
NURSE MGR
1F-188A
TOILET
1F-188
BEDROOM 1
1F-185
BEDROOM 2
1F-184
TOILET
1F-185A
TOILET
1F-182
BEDROOM 3
1F-179
TOILET
1F-180
BEDROOM 4
1F-177
TOILET
1F-178
SECLUSION-2
1F-176
SECLUSION-1
1F-175
MEDICATION
1F-174 TOILET
1F-173
BEDROOM 5&6
1F-171
TOILET
1F-172
BEDROOM 7
1F-169
BEDROOM 8
1F-167
TOILET
1F-170
TOILET
1F-168
BEDROOM 9
1F-165
TOILET
1F-166
BEDROOM 10&11
1F-163
TOILET
1F-164
SOILED LINEN/
UTILITY
1F-162
BEDROOM 12&13
1F-140
TOILET
1F-141
GROUP RM
1F-138TOILET
1F-139
PATIENT
CROSS
1F-142
PC/GROUP
1F-143
ELECTRICAL
1F-144
TOILET
1F-145
BREAK RM
1F-146
CHARTING
1F-150
STAFF TOILET
1F-147
LAUNDRY
1F-149
CLEAN LINEN
1F-148
MED
1F-152
CLEAN
LINEN
1F-151
NURSE
1F-153
DAY ROOM
1F-156
CLOSET
1F-136
BREAK ROOM
1F-134
TOILET
1F-135
BEDROOM 14
1F-132
TOILET
1F-133
BEDROOM 15
1F-130
TOILET
1F-131
BEDROOM 16
1F-128
TOILET
1F-129
BEDROOM 17
1F-126
TOILET
1F-127
BEDROOM 18
1F-124
TOILET
1F-125
BEDROOM 19
1F-122
TOILET
1F-123
BEDROOM 20
1F-120
TOILET
1F-121
BEDROOM 21
1F-118
TOILET
1F-119
BEDROOM 22
1F-116
TOILET
1F-117
BEDROOM 23
1F-114
TOILET
1F-115
CONFERENCE
RM
1F-112
TOILET
1F-113
CORRIDOR
1F-110
CLEAN EQUIPMENT
1F-159
TOILET
1F-157
VESTIBULE
1F-158
ELECTRICAL
SVC BAY
1F-187
MECHANICAL
SVC BAY-D
1F-186
VISITOR
1F-109A
OFFICE
1F-108
OFFICE
1F-107
OPMH
GROUP RM
1D-115
VISITOR
1F-109B
STORAGE
1F-105
STORAGE
1F-105
NURSE MGR
1D-102
OFFICE
1D-104SOILED
LINEN
1D-103
TRASH
1D-101
OFFICE
1D-100
OFFICE
1D-112
STORAGE
1D-111
TOILET
1D-110
OFFICE
1D-109
1D-104 TOILET
1D-106
OFFICE
1D-105
OFFICE
1D-107
OMPH
PHYSICIAN
1D-114
STORAGE
1D-108
CONFERENCE
1D-113
ELECTRICAL
SVC BAY
1D-154
COPY/WORK
RM
1D-147
ADMIN
STORAGE
1D-147A
SECRETARY
1D-150
CHIEF OF
PSYCHIATRIC
SVC
1D-151
ADMIN
OFFICER
1D-152
MECH
SVC
BAY-W
1D-153
MALE
TOILET
1D-155
FEMALE
TOILET
1D-156
C & L
DIRECTOR
1D-158
RESIDENT
C & L 1D-157
CHECK IN
OFFICE
1D-159
CHECK-IN
1D-160
SLEEP LAB
DIRECTOR
1D-161
ADMINISTRATIVE
CONFERENCE
RM
1D-162
OMPH
PHYSICIAN
1D-163
DAY RM
1E-111
FEMALE
TOILET
1D-149
FEMALE
LOCKER
1D-148
NURSE
PRACTITIONER
OUT PATIENT
MHSC
1D-132
FEMALE
TOILET
1C-101
OPMH
WAITING
1D-146
SOCIAL
WORKER
1D-133
MENTAL HEALTH
CLINIC NURSE
1D-135
RECEPTION
1D-145
WORK
RM
1D-144
OPMH
PHYSICIAN
1D-137
SOCIAL
WORKER
1D-139
INPT
DIRECTOR
1D-141
OFFICE
CWT
1D-143
UNISEX
STAFF
TOILET
1D-119
OPMH
RESIDENT
1D-118
OPMH
PHYSICIAN
1D-117
PSYCHOLOGIST
1D-116
FEMALE
TOILET
1D-122
SOCIAL
ACTIVITIES
RM
1D-120
OPMH
KITCHEN
1D-121
PSYCHOLOGIST
1D-142
PSYCHOLOGIST
1D-140
CLINICAL
SOCIAL
WORKER
1D-138
OPMH
PHYSICIAN
1D-136
SOCIAL
WORKER
1D-134
HAC
1D-131
SOCIAL
WORKER
1D-130
PSYCHOLOGIST
1D-128
NEURO
PSYCHOLOGIST
1D-126
OUT PATIENT
INPT
MENTAL HEALTH
CLINIC
1D-126A
PSYCHIATRIC
CLINICAL NURSE
SPECIALIST
1D-124
ASSOCIATE
CHIEF
PSYCHOLOGY
1D-129
PSYCHOLOGY
SVC
1D-129A
COPY RM
1D-127
TEST…