09-Elec BD changes highlighted 201112.pdf
PDF 3 MB Posted
- Attached to
- Y1DB--New 4th MRI Addition Project 652-CSI-204
- Solicitation number
- 36C24621R0021
About this file
This solicitation is for project 652-CSI-204 to provide a new addition at the Hunter Holmes McGuire VA Medical Center in Richmond, Virginia. The scope of work includes demolishing existing structures and completely preparing the site for a new single story, approximately 2,785 square foot addition to house two new MRIs adjacent to an existing MRI suite. Interior finishes will match standard facility materials, colors, and patterns. The project also includes relocating an existing MRI trailer and associated services. The solicitation is seeking bids for all labor, materials, supervision, and equipment to complete the project in accordance with provided drawings, specifications, and statement of work issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
F S
1/2W 15cd
S
1.4
2.1 3
C'
B'
A'
PANEL 'PCLB'
PANEL 'LCLB'PANEL 'ECLCLB'
PORTABLE MRI
TO BE DISCONNECTED
AND RELOCATED.
150A ECB
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:2 :3
P
M
ED101
FIRST FLOOR ELECTRICAL
DEMOLITION PLAN
4 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
FIRST FLOOR PARTIAL PLAN ELECTRICAL DEMOLITION
1 DISCONNECT, REMOVE AND RETAIN THE MRI
SERVICE RECEPTACLE, SAFETY DISCONNECT
SWITCH, FIRE ALARM BOX AND RECEPTACLE
AND COMMUNICATION DEVICES FOR THE
RELOCATED MRI. DISASSEMBLE AND
REMOVE THE UNISTRUT ASSEMBLY, RETAIN
FOR NEW WORK. DEMOLISH CONDUIT AND
WIRING BACK TO LAST OPERABLE DEVICE OR
PANELBOARD.
2 EXISTING 150A ENCLOSED CIRCUIT BREAKER
TO BE RETAINED. REMOVE DOWNSTREAM
CONDUCTORS AND CONDUIT.
3 DEMOLISH EXISTING RECEPTACLES.
REMOVE CONDUIT AND WIRING BACK TO
ALLOW FOR WALL REMOVAL. PROVIDE
JUNCTION BOX IN A LOCATION THAT WILL BE
ACCESSIBLE AFTER NEW WALLS AND
CEILINGS ARE INSTALLED AND RETAIN
CIRCUIT FOR EXTENSION TO NEW DEVICES.
4 DEMOLISH EXISTING FIRE ALARM
NOTIFICATION DEVICES. REMOVE WIRING
BACK TO LAST OPERABLE DEVICE. REMOVE
CONDUIT BACK TO ALLOW FOR WALL
REMOVAL FOR EXTENSION TO NEW DEVICES
IN NEW WORK.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. DEMOLITION SHALL INCLUDE BUT NOT BE LIMITED
TO THESE DEVICES OR SYSTEMS SHOWN. FIELD
VERIFY EXISTING CONDITIONS. COORDINATE WITH
ARCHITECTURAL, MECHANICAL AND PLUMBING.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Callout Note #1 edited for clarity, devices and unistrut assembly to be retained and reused.
ggossett Callout Revision, the 150A flush mounted enclosed circuit breaker will be retained and reused, not demolished.
F
FS
1/2W 75cd
F
S 1/2W 75cd
F
15cd
FS
1/2W 75cd
F
15cd
F
15cd
F 30cd
F
15cd
F
15cd
W
CR
DC
ES
RX
J
W
W
W
S
S
S
S
S
S S
S
M, 2PM, 2P
J
J
AC
GFI
GFI
WP
AC
GFI
M, 2P
GFI
WP
80"
DC
S
N 1
N 1
N 1
N 1
N 1
E
S
N 1 N 1
F 15cd
E
E
E
E
M, 2P, 3R
E
M, 2P
E
M
M, 2P, 3R
DC
ES
RX
CR
W
S
IC
M
S
DRESS
1Y-152
DRESS
1Y-153
TLT
1Y-154
CORRIDOR
C1Y-4
MRI 2
1Y-156
MRI 1
1Y-158
EQUIPMENT 1
1Y-159
EQUIPMENT 2
1Y-155
1.4 2 2.1 3
C'
B'
A'
2EXISTING
PANEL 'ECLCLB'
EXISTING
PANEL 'PCLB'
500-1Y-CU-2
EXISTING
PANEL 'LCLA'
EXISTING
PANEL 'ECLCL'
EXISTING
PANEL 'PCLA'
500-1Y-OU-1
500-1Y-OU-2
MRI-SH-1
BAY 3
1Y-151C
STORAGE
1Y-150
PREP
1Y-151
BAY 1
1Y-151A
BAY 2
1Y-151B
CORRIDOR
C1Y-1B
IV
1Y-110
CORRIDOR
C1Y-1
IT ROOM
1Y-107_____
EP101
CONTROL ROOM
1Y-151D
EP101
TO PDCL
500-1Y-OU-3
(SEE EP104)
SOLA MRI
MAIN PANEL
VIDA MRI
MAIN PANEL
CHILLER -1
CHILLER 2
PANEL 'P1EDA'
PANEL
'L1-1EDA'
PANEL
'SL1-1EDA'
PANEL
'MCC-P1EDA'
'LCLA'- 20
'ECLCL'- 15
'ECLCL'- 34
'LCLA'- 22
'ECLCL'- 13
'LCLA'- 30
'LCLA'- 26
E-401
E-401
EXISTING
PANEL 'LCLB'
150A ECB
60/3P/35AF/3R
3-8 AWG,
1-10 AWG EG,
IN 1" C.
'PCLA'- 32,34,36
500-1Y-EF-4
'LCLA'- 15
'ECLCL'- 16,18
'ECLCL'- 41
'PCLA'- 20
'LCLA'- 17
'LCLA'- 25,27
'ECLCL'- 14
'ECLCLB'- 22
'ECLCLB'- 24
'ECLCL'- 17
'LCLA'- 29,31
'SL1-1EDA'- 2'LCLA'- 41
E-501
'LCLA'- 24
250A ECB 4
IT ROOM
1Y-107
2-10 AWG,
10 AWG EG,
IN 3/4"C.
(6-30R)
1920 20
2123 22
'ECLCL'- 38
'ECLCL'- 36
'ECLCL'- 40,42
'ECLCL'- 19
'ECLCL'- 21
'ECLCL'- 20
C'
CONTROL ROOM
1Y-151D
M
E-401
_____ 2
E-401
'ECLCLB'- 18
'ECLCLB'- 12
'ECLCLB'- 10
'ECLCLB'- 8 'ECLCLB'- 14
'ECLCLB'- 16
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:5 :0
P
M
EP101
FIRST FLOOR ELECTRICAL PLAN - MRI
SUITE
5 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
0 4 8 16
NORTH
TRUE
Scale: 1/8" = 1'-0"
FIRST FLOOR PARTIAL PLAN ELECTRICAL - MRI SUITE
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A. ALL 120 VOLT 20 AMP BRANCH CIRCUIT
CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG
IN 3/4" CONDUIT, UNLESS NOTED OTHERWISE.
a. RUNS LESS THAN 150' SHALL BE MINIMUM
2-12 AWG, 1-12 AWG EG IN 3/4" C.
b. RUNS BETWEEN 150'-250' SHALL BE
MINIMUM 2-10 AWG, 1-10 AWG EG IN 3/4" C.
c. RUNS GREATER THAN 250' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4" C.
B. ALL FIXTURES, DEVICES, AND ANY RELATED
RACEWAYS OR WIRING WITH THE MRI SUITES
SHALL CONSIST OF NON-FERROUS MATERIALS.
FIXTURES AND DEVICES SHOULD BE RATED FOR
MRI APPLICATIONS.
C. REFERENCE SHEET E-401 FOR CONDUIT ROUTING
INFORMATION.
D. EXTEND EXISTING PUBLIC ADDRESS SYSTEM TO
NEW SPEAKERS.
E. EXISTING DOOR CONTROL AND INTERCOM FOR
ACCESS TO MRI SUITE IS TO BE MAINTAINED AND
EXTENDED TO CONTROL ROOM (1Y-151D).
Scale: 1/4" = 1'-0"
ELECTRICAL PLAN - IT ROOM
Scale: 1/4" = 1'-0"
ENLARGED PLAN ELECTRICAL CONTROL ROOM
0 2 4 8
NORTH
TRUE
0 2 4 8
NORTH
TRUE
1 MRI MAIN PANELS. SEE SHEET E-401 FOR
RACEWAY PLANS. REFER TO PARTIAL RISER
DIAGRAM - MRI SUITES ON SHEET E-601 FOR
ADDITIONAL INFORMATION.
2 UTILIZE EXISTING 150A ENCLOSED CIRCUIT
BREAKER FOR SOLA MRI MAIN PANEL.
3 REPLACE EXISTING 54 POLE PANEL
INTERIORS WITH NEW 42 POLE INTERIORS
WITH FEED THRU LUGS.
4 PROVIDE NEW 250A/3P FLUSH-MOUNTED
ENCLOSED CIRCUIT BREAKER FOR VIDA MRI
MAIN PANEL.
5 MRI CHILLER BRANCH CIRCUIT. FROM
CRAWL SPACE, PENETRATE THE EXISTING
BUILDING WALL. PROVIDE SLEEVE AND
CONDUIT WITH WATERPROOF SEAL AT THE
PENETRATION. ROUTE CONDUIT BELOW
GRADE IN 1-WAY CONCRETE ENCASED
DUCTBANK TO THE MRI CHILLERS, WITH PULL
BOXES AS SHOWN. SEE SHEET EP104 FOR
ROUTE THROUGH THE CRAWL SPACE
6 ROUTE DUCTBANK OUTSIDE OF PERIMETER
FENCING, COORDINATE EXACT LOCATION
WITH CIVIL PLANS. SEE DUCTBANK
CONSTRUCTION DETAIL ON E-501.
7 PROVIDE 11"W X 21"L X 12"H TIER 8
FIBERGLASS PULLBOX WITH STRAIGHT
WALLS AND OPEN BOTTOM. MOUNT SUCH
THAT THE LID IS FLUSH WITH FINISHED
GRADE.
8 MED GAS ALARM PANEL CONNECTION.
EXTEND CIRCUIT FROM EXISTING MED GAS
ALARM PANEL.
9 EXISTING MED GAS ALARM PANEL TO
REMAIN.
10 DOOR OPERATOR CONNECTION. EXTEND
EXISTING CIRCUIT TO NEW DOORS.
COORDINATE WITH DOOR INSTALLER.
11 NEW TELECOMMUNICATIONS CABLING
ABOVE ACCESSIBLE CEILING SPACE TO BE
SUSPENDED ON J-HOOKS 5' ON CENTER.
12 PROVIDE WALL MOUNTED 24 PORT FIBER
OPTIC PATCH PANEL.
13 APPROXIMATE LOCATION OF EXISTING DATA
RACK IN INTERSTITIAL SPACE.
14 EXISTING HYDRONIC PUMPS TO BE
REPLACED. DISCONNECT EXISTING PUMPS
AND REMOVING WIRING BACK TO
STARTER/DISCONNECT SWITCH. PROVIDE
NEW WIRING IN KIND AND CONNECT TO NEW
PUMPS. REMOVE AND REPLACE FUSES WITH
DUAL-ELEMENT, 6 AMPS.
15 APPROXIMATE LOCATION OF EXISTING
NURSE CALL EQUIPMENT CABINETS. FIELD
VERIFY.
16 EXISTING FIRE ALARM PANEL, EDWARDS
EST3.
17 PROVIDE 3-4" FIRE/SMOKE UL LISTED SLEEVE
ASSEMBLY.
18 PROVIDE NEW FLOOR-MOUNTED IT RACK.
SEE DETAIL 7 ON E-502.
19 PROVIDE NEW TGB.
20 PROVIDE 3/4" FIRE RETARDANT PLYWOOD
BACKBOARD.
21 PACS CONTROLLER.
22 DOOR INTERCOM EQUIPMENT. COORDINATE
EXACT LOCATION WITH COR PRIOR TO
ROUGH-IN.
23 COORDINATE EXACT LOCATION OF IT ROOM
CAMERA WITH OIT.
24 LADDER TYPE CABLE TRAY. SEE DETAILS ON
SHEET E-503.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Callout Revision, utilize existing 150A ECB, in lieu of demolishing and replacing with 250A ECB.
ggossett Highlight ggossett Callout Revision, to accommodate feed thru lugs, the guts of this panel will be replaced.
ggossett Highlight ggossett Callout Revision, new 250A ECB will be fed from PCLA. Metering indicates PCLA has more capacity than PCLB.
ggossett Highlight ggossett Highlight ggossett Callout Revised, concrete encasement of conduit to MRI chillers.
ggossett
The route and provisions of the underground circuit was revised
EE
E
E
GFI
WP
E
E
1.4 2 2.1 3
C'
B'
A'
500-1Y-EF-5 500-1Y-EF-6
500-1Y-AH-2
'ECLCLB'- 29
'ECLCLB'- 29
500-1Y-GRV-3
500-1Y-RF-2
3-10 AWG,
10 AWG EG,
IN 3/4" C.
500-1Y-SF-2
3-10 AWG,
10 AWG EG,
IN 3/4" C.
STRUCTURAL
COLUMN
BELOW
TYPICALCRYOGEN
EXHAUST
CRYOGEN
EXHAUST
THRU ROOF
PENETRATION
TYPICAL
5 5
PCLA - 1,3,5
PCLA - 2,4,6
'LCLA'- 28
'LCLA'- 33
'LCLA'- 32
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2 :4
P
M
EP102
ROOF POWER PLAN
6 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
0 2 4 8
NORTH
PLAN
Scale: 1/4" = 1'-0"
ROOF POWER PLAN
1 LIGHTNING PROTECTION AIR TERMINAL
(TYP.). SEE DETAIL ON SHEET E-501 FOR
MORE INFORMATION.
2 MAIN LIGHTNING PROTECTION SYSTEM ROOF
CONDUCTOR. AROUND THE ROOF
PERIMETER, THE MAIN CONDUCTOR SHALL
BE ROUTED ON THE PARAPET, CENTERED AS
MUCH AS POSSIBLE. ON THE FLAT ROOF,
THE MAIN CONDUCTOR SHALL BE ROUTED AT
RIGHT ANGLES TO THE BUILDING
STRUCTURE. REFER TO SPECIFICATIONS
FOR SUPPORTS AND SECUREMENT
INTERVALS.
3 DISCONNECT SWITCH FOR EXHAUST FAN IS
PROVIDED WITH EQUIPMENT. COORDINATE
EXACT LOCATION OF TERMINATION POINT
WITH MECHANICAL CONTRACTOR
4 CONNECT ROOF MOUNTED EQUIPMENT TO
THE LIGHTNING PROTECTION SYSTEM WITH
BONDING PLATE PER THE SPECIFICATIONS.
5 PROVIDE DOWN CONDUCTOR FROM THE
MAIN ROOF CONDUCTOR TO THRU-ROOF
ASSEMBLY AND MAKE CONNECTION TO
STRUCTURAL STEEL COLUMN BELOW ROOF.
BOND COLUMN AT ITS BASE AND EXTEND
DOWN CONDUCTOR TO BURIED GROUND
RING.
6 GRAVITY RELIEF VENT, NO ELECTRICAL
POWER CONNECTION REQUIRED.
7 EXISTING ROOFTOP EQUIPMENT TO REMAIN,
NOT IN SCOPE.
8 THE EXISTING GROUND RING SHALL BE CUT
TO ALLOW FOR CONSTRUCTION OF MRI
ADDITION. CONNECT NEW GROUND RING TO
THE EXISTING LOOP.
9 CONNECT THE MAIN CONDUCTOR TO THE
EXISTING LIGHTNING PROTECTION SYSTEM
ON THE EXISTING ROOF.
10 AIR HANDLING UNIT FAN CONNECTIONS.
COORDINATE TERMINATION LOCATIONS WITH
APPROVED EQUIPMENT SHOP DRAWINGS
AND THE MECHANICAL CONTRACTOR PRIOR
TO ROUGH-IN.
11 AIR HANDLING UNIT SERVICE RECEPTACLE
AND LIGHTS CONNECTION.
12 AIR HANDLING UNIT UV LIGHTS CONNECTION.
A. PROVIDE UL MASTER LABEL FOR REVISED
LIGHTNING PROTECTION SYSTEM. CONNECT TO
EXISTING LIGHTNING PROTECTION SYSTEM.
B. VERIFY EXISTING SYSTEM INSTALLER WITH THE
VA. COORDINATE NEW WORK WITH COR.
C. CONNECT LIGHTING PROTECTION SYSTEM TO
EXISTING GROUND LOOP IF EXTANT. VERIFY IN
FIELD.
TYPICAL
ggossett Text Box Updates to the roof plan include:
* noted connection to existing lightning protection system on adjacent roof;
* noted tie in to existing buried ground loop conductor;
* showed and noted additional items on roof requiring bonding to the lightning protection system, such as roof drains and cryogen exhaust stacks;
* notes for down conductor routing added for clarity.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight
COOK
CHILL
COOK
CHILL
COOK
CHILL
FC
1T-1481T-152A
SERVING LINE STORAGE
1T-147
CORRIDORCORRIDOR
C1V-3
DRESSING RM
1T-144
STAFF
TOILET
1T-143
ELECTRICAL
SVC BAY
1V-101
MECHANICAL
SVC BAY-S
1V-100
MECHANICAL
SVC BAY-R
CORRIDOR
C1V-2
OFFICE
1T-146 SCI
MATERIAL
STORAGE
1T-145
HAC
1V-157
CORRIDOR
C1V-1
OFFICE
1V-155
SOCIAL
WORKER
1V-102
EXAM RM
1V-154
SCI PA
OFFICE
1V-103
EXAM RM
1V-151
SCI PA
OFFICE
1V-104
EXAM RM
1V-105
EXAM RM
1V-105A
CORRIDOR
C1V-9
DAY RM
1V-156
2 BED RM
1V-153
2 BED RM
1V-152
4 BED RM
1V-149
PATIENT
TOILET
1V-150
STORAGE
1T-147
PP
FC
LOCOMOTOR
TRAINING LAB
1V-139
OFFICE/LAB
1V-137
TOILET
1V-138
OFFICE
1V-135 OFFICE
1V-132
SHOWER
1V-134
ELECTRICAL
OFFICE
1V-136
STAFF
TOILET
1V-133
PATIENT
TOILET
1V-131
4 BED RM
1V-130
OFFICE
1V-129
SHOWER
1V-124
TOILET
1V-123
1 BED RM
1V-122
1V-121
1 BED RM
1V-119
TOILET
1V-120
1V-118
SELF CARE
TOILET/SHOWER
AREA
1V-125
TOILET
1V-128
TOILET
1V-127
TOILET
1V-126
CORRIDOR
C1V-6
UU
W
WW
2019181716
J
GFI
WP
F S 1/2W 15cd
JJ
J
ELECTRICAL
SVC BAY
1V-101
RELOCATED
UNISTRUT
ASSEMBLY
UNISTRUT
FRAMING
ANCHOR TO
GRADE
RELOCATED
RECEPTACLE
FOR MOBILE
MRI TRAILER
SINGLE GANG WEATHERPROOF
WHILE IN USE ENCLOSURE FOR DUPLEX
SERVICE RECEPTACLE
WEATHERPROOF WHILE IN USE
ENCLOSURE FOR
TELEPHONE/DATA OUTLET
SERVICING MOBILE MRI TRAILER
FROM
DISCONNECT
SWITCH
FROM WALL
MOUNTED PULL BOX
RELOCATED FIRE ALARM
CONNECTION
FINISHED GRADE
RELOCATED
DISCONNECT
SWITCH MOUNTED
ON UNISTRUT
FROM
CRAWLSPACE
TO MOBILE MRI
ELEVATION
CONDUIT BODY WITH THRU
WALL PENETRATION FROM
FIRE ALARM SYSTEM
ABOVE INTERIOR
ACCESSIBLE CEILING.
FINISHED GRADE
4-INCH SQUARE
WEATHERPROOF
BOXES
480V
FIRE
120V
TELE/
DATA
EP103
RELOCATED
PORTABLE MRI
200A/3P
150AF
3R
EP103
EP103
EXISTING
PANEL 'PD1S'
EXISTING
PANEL 'L1SA'
EXISTING
PANEL 'P1SA'
T1S
EXISTING
PANEL 'LD1S'
EXISTING
PANEL 'ECP1S'
EXISTING
PANEL 'ECL1S'
EXISTING
PANEL 'ESP1S'
EXISTING
PANEL 'ESL1S'
EXISTING
PANEL 'EEP1S'
EXISTING
PANEL 'EEL1S'
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:0 :2
P
M
EP103
FIRST FLOOR ELECTRICAL PLAN -
MOBILE MRI
7 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
Scale: 1/8" = 1'-0"
FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI
Scale: 1/4" = 1'-0"
ENLARGED PLAN ELECTRICAL SVC BAY (1V-101)
0 4 8 16
NORTH
PLAN
0 2 4 8
NORTH
PLAN
1 RELOCATED MRI. SEE CIVIL/SITE PLANS FOR
LOCATION. EXTERNAL NEW SERVICES AS
REQUIRED.
2 TO ECPDOQ IN TRANSFORMER VAULT NO. 5.
3 REFER TO PARTIAL ONE-LINE DIAGRAM ON
SHEET E-601 FOR CONDUIT AND CONDUCTOR
SIZING.
4 EXISTING 200A/3P DISCONNECT AND SERVICE
TO REMAIN.
5 RELOCATE DISCONNECT SWITCH FOR
PORTABLE MRI. MOUNT TO EXTERIOR OF
BUILDING.
6 1-1/2"C FOR TELEPHONE/DATA CABLING TO IT
ROOM.
7 ROUTE NEW SERVICES DOWN AND THROUGH
CRAWL SPACE.
8 AT EXISTING PANEL 'ECL1S', USE EXISTING
SPARE CIRCUIT BREAKER(S) FOR NEW MRI
TRAILER RECEPTACLES. RUN NEW 1"C FROM
PANEL TO NEW MOBILE MRI LOCATION VIA
CRAWLSPACE.
9 REINSTALL UNISTRUT ASSEMBLY AND
DEVICES FROM PREVIOUS PORTABLE MRI
LOCATION.
10 FIELD VERIFY FA ANNUNCIATOR CIRCUIT AT
EXISTING CORRIDOR. EXTEND FA
ANUNCIATOR CIRCUIT TO MRI TRAILER.
ROUTE WITH DATA/IT SERVICES TO SERVICE
RACK (3/4" C)
11 CONNECT COPPER UTP CABLE TO SPARE
PORTS IN PATCH PANEL. COORDINATE WITH
COR AND OIT. PROVIDE UPDATING LABLING.
CONTINUATION
Scale: N.T.S.
MOBILE MRI UNISTRUT
N
KEY PLAN
SCALE: NO SCALE
Scale: N.T.S.
EXTERIOR WALL ELEVATION
AREA OF WORK
ggossett Rectangle ggossett Highlight ggossett Callout Added remaining panels in the electrical room to the enlarged plan for clarity and completeness.
ggossett Highlight ggossett Callout Revised mobile MRI connections to be fed from Critical branch power sources.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett
Elevation view added to clarify design intent.
C G
CGCG
CG
C G
LVD
O S
OS
OS
LV LVD
LV
LV
LVD
OS
VS
OS
OS
OS
OS
PC
1 1.4 2 2.1 3
C'
B'
A'
DRESS
1Y-152
DRESS
1Y-153
TLT
1Y-154
CORRIDOR
C1Y-4
MRI 1
1Y-158
EQUIPMENT 1
1Y-159
EQUIPMENT 2
1Y-155
D D D
D
D
D
D
D
D
D
D
D
D
D
D
B B
B
E E
D
D
D
E E
ETR
X
B
J
J
Jd e
EM
NL
EM
NL
J
J a b
X f
Jc
EM
NL
EM
NL
D
EM
NL
CORRIDOR
C1Y-1B
MRI 2
1Y-156
C
C
C C
C
C
C
C
S S
Z Z
CORRIDOR
C1Y-1
IT ROOM
1Y-107
IV
1Y-110
STORAGE
1Y-150
BAY 3
1Y-151C
BAY 2
1Y-151B
BAY 1
1Y-151A
PREP
1Y-151
BB
B B B
A A AA A A
RCD
RCD
EM
EM
RC
D
D D
D
D
D D
D a b c g b b b a a a a a a a aaaa g g g b b b eee d d d e e e e e e e e h h h h d e f
F F F F
F
F
F
F F F F
F F F F
F
F
F
FFFF
RCD2
'ECLCLB'- 15
'ECLCLB'- 20
'ECLCLB'- 19
CONTROL ROOM
1Y-151D
'ECLCLB'- 13'ECLCLB'- 17
i j i j i j j j j j j i,j
2 2
LUMINAIRE SCHEDULE
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION
MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.
GENERAL NOTES:
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/1
/2
:2 :4
P
M
EL101
FIRST FLOOR LIGHTING PLAN - MRI
SUITE
9 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
Scale: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN - MRI SUITE 0 4 8 16
NORTH
PLAN
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
1 ARCHITECTURAL LED CEILING ASSEMBLY.
PROVIDED BY GENERAL TRADES AND
INSTALLED BY ELECTRICAL CONTRACTOR.
PROVIDE JUNCTION BOX WITH RACEWAY TO
ABOVE CEILING AREA OUTSIDE THE MRI
SUITE. COORDINATE WIRING REQUIREMENTS
(2-12 AWG, 1-12 AWG G, IN 3/4") WITH
VENDOR/SUPPLIER. COORDINATE WITH
ARCHITECTURAL DRAWNGS.
2 EMERGENCY LIGHT FIXTURE SHALL BE
CONNECTED AHEAD OF ANY LOCAL
CONTROLS, SEE SHEET NOTE C.
3 JUNCTION BOXES ABOVE CEILING FOR LED
DRIVERS AND RELATED COMPONENTS FOR
MRI RATED FIXTURES. COORDINATE WITH
MANUFACTURERS PRODUCT SUBMITTALS.
4 EXTERIOR LIGHTING SHALL BE CONTROLLED
BY PHOTOCELL AND PROGRAMMED FOR
DUSK TO DAWN OPERATION.
TYPE DESCRIPTION MOUNTING LAMP BALLAST/DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
A 4" SQUARE RECESSED DOWNLIGHT, MRI RATED RECESSED LED;
3500K; 80
CRI; 1500
LUMENS
0-10V DIMMABLE
LED DRIVER
120 V 13 W KENALL MRIDL4S DCFW 13L
35K8 FW RIMRI4 24V
DIM1
B ARCHITECTURAL RECESSED 6" NON-FERROUS
DOWNLIGHT WITH ANTI-MICROBIAL MATTE
WHITE TRIM AND DIFFUSE LENS.
RECESSED
FLANGE
LED;
3500K; 80
CRI; 1668
LUMENS
REMOTE
ELECTRONIC
120 V 23 W KENALL MRIDL6-NF-DCFW-2
3L-35K8-M-CSS-T-RI
MRI6-24V-DIM1
C RECESSED LENSED DOWNLIGHT 6" DIAM, LED
DOWNLING, WIDE BEAM DISTRIBUTION, CLEAR
SPECULAR DEFLECTOR, MINIMUM 1500 LUMEN
RATED OUTPUT 80 CRI, 3500K DEG K. INTEGRAL
ELECTRONIC DRIVER ASSEMBLY, 0-10V
DIMMING.
RECESSED LED;
3500K; 80
CRI; 1500
LUMENS
INTEGRAL
ELECTRONIC
120 V 18 W EATON/COOPER
METALLUX
HALO PD610ED101
PD6MA8301VCWF
ACUITY BRANDS
PHILLIPS LIGHTING
HUBBEL LIGHTING.
D ARCHITECTURAL RECESSED LENSED GRID
TROFFER (DIRECT/INDIRECT), RIGID DIE
FORMED STEEL HOUSING, PAINTED AFTER
FABRICATION. HIGH REFLECTANCE REFLECTOR,
ACRYLIC FROSTED CENTER BASKET LENS
ASSEMBLY. ELECTRONIC LED DRIVER 0-10V
DIMMING CAPABILITY, RATED 4988 LUMENS AT
3500K.
RECESSED
GRID
LED; 3400
LUMENS;
80 CRI;
3500K
INTEGRAL
ELECTRONIC
120 V 41 W EATON/COOPER
METALLUX
22CZLD5-34
UNV-L835CD1PAF
ACUITY BRANDS,
PHILLIPS LIGHTING,
HUBBELL LIGHTING.
E ARCHITECTURAL RECESSED LENSED GRID
TROFFER (DIRECT/INDIRECT), RIGID DIE
FORMED STEEL HOUSING, PAINTED AFTER
FABRICATION. HIGH REFLECTANCE REFLECTOR,
ACRYLIC FROSTED CENTER BASKET LENS
ASSEMBLY. ELECTRONIC LED DRIVER 0-10V
DIMMING CAPABILITY, RATED 4988 LUMENS AT
3500K.
RECESSED
GRID
LED; 4988
LUMENS;
80 CRI;
3500K
INTEGRAL
ELECTRONIC
120 V 41 W EATON/COOPER
METALLUX
24CZLD5-50
UNV-L835CD1PAF
ACUITY BRANDS,
PHILLIPS LIGHTING,
HUBBELL LIGHTING.
F 6.5"W X 6.25"H X 48"L STRAIGHT COVE(LENSED)
LED DESIGNED FOR MRI APPLICATIONS. NON
FERROUS ASSEMBLY RECESSED IN CEILING
TILE/GRID. MINIMUM LUMEN OUT 4000LUMENS
PER 4' SECTION. PROVIDE ACRYLIC
LENS/LOUVER. 120/277V LED ELECTRONIC
DRIVER CAPABLE OF 0-10V DIMMING. PROVIDE
FOR CONTINOUS ROW CONNECTION.
RECESSED
GRID
LED; 80
CRI; 3500K
REMOTE
ELECTRONIC,
0-10V DIMMING
120 V 69 W PDC LIGHTING PDC#3-07-000088
S MRI NONMAGNETIC SINGLE POD CEILING
MOUNT LIGHT
WALL
MOUNT AT
9' 6"
HALOGEN
BULB
INTEGRAL TO UNIT 120 V 105 W MRI EQUIP EX-1002
X LED EXIT SIGN. WHITE HOUSING WITH (RED)
EDGE LIT PANEL.
UNIVERSAL LED --- 120 V 5 W EATON/COOPER
METALLUX
SURELITES EUR60R
LITHONIA ACUITY
BRANDS
PHILLIPS LIGHTING
HUBBELL LIGHTING
Z SURFACE MOUNTED LED WRAP FIXTURE, STEEL
HOUSING WITH POWDER COAT FINISH. WHITE
ACRYLIC DIFFUSER.
30" RD LED;4700
LUMEN; 80
CRI; 3500K
INTEGRAL
ELECTRONIC,
0-10V DIMMING
120 V 43 W EATON/COOPER 4CWPLD4040PC
A. ALL 120 VOLT 20 AMP BRANCH CIRCUIT
CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG EG
IN 3/4" CONDUIT, UNLESS NOTED OTHERWISE.
a. RUNS LESS THAN 150' SHALL BE MINIMUM
2-12 AWG, 1-12 AWG EG IN 3/4" C.
b. RUNS BETWEEN 150'-250' SHALL BE
MINIMUM 2-10 AWG, 1-10 AWG EG IN 3/4"
C.
c. RUNS GREATER THAN 250' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4" C.
B. ALL FIXTURES, DEVICES, AND ANY RELATED
RACEWAYS OR WIRING WITHIN THE MRI SUITES
SHALL CONSIST ON NON FERROUS MATERIALS.
FIXTURES AND DEVICES SHOULD BE RATED FOR
MRI APPLICATIONS.
C. ALL INTERIOR UN-SWITCHED EXIT SIGNS,
EMERGENCY NIGHT LIGHTS (EM NL) AND
EMERGENCY LIGHTING UNITS SHALL BE
CIRCUITED FROM LIFE SAFETY EMERGENCY
LIGHTING CIRCUIT 'SL1-1EDA'-1, BUT AHEAD OF
ANY SWITCHING.
D. LOCATION AND QUANTITY OF OCCUPANCY
SENSORS AND LIGHT LEVEL SENSORS ARE
APPROXIMATE. CONTRACTOR SHALL FOLLOW
MANUFACTURER'S RECOMMENDED PLACEMENT
AND INSTALL PER MANUFACTURER'S
INSTRUCTIONS.
E. CONTRACTOR SHALL VERIFY COMPATIBILITY OF
ALL LIGHTING CONTROLS WITH THE LED
DRIVERS TO BE CONTROLLED.
F. COORDINATE ALL TIME DELAY, AUTO DIM,
PRESET DIMMING LEVELS, SENSOR SENSITIVITY
AND OTHER CONFIGURATIONS WITH THE VA.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight ggossett
Added exterior lighting controls
CEILING HANGER
WIRE, TYP.
WIRE TIE OR
SCREW BAR
HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
ARCHITECTURAL
CEILING GRID RECESSED CAN
LUMINAIRE
RECESSED CAN
LUMINAIRE
ARCHITECTURAL CEILING GRID
ACOUSTICAL
CEILING TILE
(TYP)
LUMINAIRE
BAR HANGERS
LUMINAIRE SUSPENSION
WIRE REFER TO
SPECIFICATION SECTION 26
51 00
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
FIXTURE WHIP FROM
JUNCTION BOX (6'
[1829MM] LONG MAX
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE. REFER TO
SPECIFICATION SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING
TILE, TYP.
ARCHITECTURAL
CEILING GRID
1/4" SCREW
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
FIXTURE WHIP FROM JUNCTION
BOX (6' [1829MM] LONG MAX)
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
LUMINAIRE MANUFACTURER'S
EARTHQUAKE CLIP, (4) PER
FIXTURE AT CORNERES. ATTACH
WITH SHEET METAL SCREW
FIXTURE WHIP
FROM JUNCTION
BOX
(6FT. LONG MAX.)
LUMINAIRE. REFER TO
SCHEDULE
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER
TO SCHEDULE
ACOUSTICAL CEILING
TILE (TYP)
3 TWIST
MINIMUM (TYP)
LUMINAIRE
SUSPENSION WIRES
(#10 MIN)
ATTACHED TO
STRUCTURE
(TYP EA. CORNER)
3/8" MIN GALVANIZED
THREADED ROD, TYP.
LOCKING SQUARE
WASHER & LOCKNUT
NOTES
1. METAL CHANNEL STRUT SUPPORT LONGER THAN 36"
SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 0533, RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT
CONDITIONS.
3. FOR TRAPEZE INSTALLATION IN SEISMIC AREAS REFER TO
SPECIFICATION SECTION 10 05 41, SEISMIC RESTRAINT
REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
CONDUIT CLAMP
SIZE AS REQUIRED
WASHER
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
LENGTH AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED
STEEL
MOUNTING
CHANNEL
AIR TERMINAL
NOTES:
1. SEE PLATE E-001 FOR LEGEND.
2. ALL SPLICES BELOW GRADE SHALL BE THE
EXOTHERMIC WELD TYPE.
3. AIR TERMINALS SHALL EXTEND NO LESS THAN 10
INCHES ABOVE THE OBJECT OR AREA THEY ARE TO
PROTECT.
4. ALL METAL EQUIPMENT ON THE ROOF SHALL BE
BONDED TO THE LIGHTNING PROTECTION SYSTEM.
5. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH
ROUND BASE AND VERTICAL TUBE WITH NEOPRENE
SEAL. FLASHING SHALL BE THE PRODUCT OF THE
MANUFACTURER OF THE LIGHTNING PROTECTION
SYSTEM. A MEMBRANE FLASHING SHALL BE PROVIDED
OVER THE THRU ROOF FLASHING.
MAIN CONDUCTOR
CLIP CABLE SUPPORT
SEALING WASHER
L E
N G
T H
P
E R
S P
E C
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 12" [308 mm] ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHING SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE
PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
CONDUIT CLAMP.
SIZE AS
REQUIRED
LOCKING
SQUARE
WASHER &
LOCKNUT
3/8" MIN.
GALVANIZE
D
THREADED
ROD, TYP.
STEEL
EXPANSION
ANCHOR
BATT INSULATION
CONDUIT TYP.
SEAL-OFF FITTING TYP.
STAINLESS CLAMP, TYP.
PREFABRICATED FORMED
0.06" THICK ALUMINUM
FLASHING ROUND COLLAR
WITH MIN. 3" WIDE FLANGE.
ATTACH TO ROOF PER
MANUFACTURER'S
INSTRUCTIONS.
MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF
ROOF BY ROOFING
CONTRACTOR. PRIME FLANGE
BEFORE STRIPPING.
ROOF
WATER CUT-OFF
MASTIC COMPATIBLE
WITH ROOF
MEMBRANE
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
ROOF MEMBRANE
SEALANT AT
PENETRATION TO
MEMBRANE JUNCTURE
BY ROOFING
CONTRACTOR
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS &
WEATHER-PROOF PRESSURE
SEAL TO COLLAR
LOCKING
SQUARE
WASHER
LOCKNUT
3/8" MIN GALVANIZED
THREADED ROD,
TYP.
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
CONDUIT CLAMP.
SIZE AS
REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
UV-INHIBITED
POLYCARBONATE OR
HIGH-DENSITY
POLYPROPYLENE PLASTIC
BLOCK, LENGTH AS
REQUIRED
LIGHTING
ZONE (a)
DAYLIGHTING
ZONE
RCD
(AS NEEDED)
SEQUENCE OF OPERATION:
• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN
ROOM
• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE
CLOSEST TO WINDOWS
• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED
OTHERWISE BY THE VA
• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23
LINE VOLTAGE CIRCUIT
LVDS
OS OS
LS
LOW VOLTAGE
OCCUPANCY
SENSOR
LOW VOLTAGE LIGHT LEVEL
SENSOR (AS NEEDED)
LIGHTING CONTROLLER
WITH 1 RELAYS AND 1
CHANNEL OF 0-10V
DIMMING
LOW VOLTAGE
DIMMER SWITCHES
(AS NEEDED)
LIGHTING
ZONE (a)
LIGHTING
ZONE (b)
RCD2
(AS NEEDED)
SEQUENCE OF OPERATION:
• OCCUPANCY SENSOR CONTROLS ALL LUMINAIRES WITHIN
ROOM
• LIGHT LEVEL SENSOR CONTROLS DIMMING OF LIGHTING ZONE
CLOSEST TO WINDOWS
• ALL ZONES SET TO MANUAL ON-AUTO OFF UNLESS DIRECTED
OTHERWISE BY THE VA
• LIGHTING CONTROL DEVICE MUST COMPLY WITH NEC 700.23
LINE VOLTAGE CIRCUIT
b1 a,b b
LVDS S
a
LVD
OS OS
LS
LOW VOLTAGE
OCCUPANCY
SENSOR
LOW VOLTAGE LIGHT LEVEL
SENSOR (AS NEEDED)
LIGHTING
CONTROLLER WITH 2
RELAYS AND
2 CHANNELS OF
0-10V DIMMING
LOW VOLTAGE
DIMMER SWITCHES
(AS NEEDED)
DAYLIGHTING
ZONE (b1)
FINISHED
GRADE
HANDHOLE,
OPEN BOTTOM,
TYPICAL
PVC
CONDUIT,
CONCRETE-
ENCASED
CRAWL SPACE
FROM PANEL
PDCL
EXISTING BLDG NEW
MRI
ADDITION
TO MRI
CHILLERS
DUCT BANK NOTES:
1. CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS
SPECIFIED.
2. PROVIDE REINFORCING RODS ON TOP AND BOTTOM
OF DUCTS WHEN CROSSING OR PLACED IN
ROADWAYS.
3. MINIMUM COVER TOP OF ENVELOPE SHALL BE 24"
[610mm].
3"
[76mm]
[7 m m
[7 m m ]3"
[76mm]
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2 :2
P
M
E-501
ELECTRICAL DETAILS
11 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
Scale: N.T.S.
DOWNLIGHT MOUNTING - LAY-IN CEILING
Scale: N.T.S.
EXIT SIGN MOUNTING - LAY-IN CEILING
Scale: N.T.S.
LUMINAIRE MOUNTING - LAY-IN CEILING
Scale: N.T.S.
CONDUIT TRAPEZE MOUNTING
Scale: N.T.S.
LIGHTNING PROTECTION AIR TERMINAL
Scale: N.T.S.
CONDUIT ROOF PENETRATION
Scale: N.T.S.
ROOF CONDUIT SUPPORT
Scale: N.T.S.
SINGLE RELAY ROOM CONTROLLER DIAGRAM
Scale: N.T.S.
DUAL RELAY ROOM CONTROLLER DIAGRAM
Scale: N.T.S.
HANDHOLE SECTION DETAIL
Scale: N.T.S.
DUCTBANK CONSTRUCTION
ggossett Rectangle ggossett Callout Added detail for buried MRI chiller circuits.
ggossett Rectangle ggossett
Detail added to clarify design intent
150NG
250NG
TO EPO
SEE SIEMENS DRAWINGS.
100NG
150NG
100A/3P
150A/3P
250G
CHILLER-1
250G
CHILLER-2
250G
EPC
GPA
PULL
BOX
PULL
BOX
E
E
TO EPO
250A/3P
ECB
EXISTING
PANEL
'ECLDOC'
208/120V
400A MCB
CRITICAL
EXISTING
PANEL 'LDCL'
208/120V
EXISTING
PANEL 'PDCL'
480/277V
EXISTING
PANEL 'PCLB'
480/277V
400A MLO
EXISTING
PANEL 'LCLB'
208/120V
100A MLO
EXISTING
PANEL
'ECLCLB'
208/120V
CRITICAL
EXISTING
4-500 MCM,
1-1/0 AWG EG,
IN 4" C.
EXISTING
4-2 AWG,
1-6 AWG EG,
IN 1-1/4"C
FIRST FLOOR (CARDIAC CATH LAB)
VIDA MRI
MAIN PANEL
250A MCB
SHUNT TRIP
EXISTING
PANEL 'PCLA'
480/277V
400A MLO
EXISTING
PANEL 'LCLA'
208/120V
100A MLO
EXISTING
PANEL 'ECLCL'
208/120V
225A MLO
EXISTING
4-500 MCM
XF-TCC
EXISTING
150A/3P
ECB
SOLA MRI
MAIN PANEL
150A MCB
SHUNT TRIP
(E) 150NG400NG
1. (EX) INDICATES EXISTING FEEDERS. VERIFY IN FIELD. RECORD ON AS-BUILT DOCUMENTATION.
NOTES:
1200NG 1200A - EXISTING TO BE FIELD VERIFIED.
800NG 800A - EXISTING TO BE FIELD VERIFIED.
400NG 400A 380A 3-500 KCMIL, 1-500 KCMIL NEUTRAL, 1-3 AWG EGC, IN 4" C
400G 400A 380A 3-500 KCMIL, 1-3 AWG EGC, IN 3-1/2" C
400N 400A 380A 3-500 KCMIL, 1-500 KCMIL NEUTRAL, IN 3-1/2" C
300NG 300A 310A 3-350 KCMIL, 1-350 KCMIL NEUTRAL, 1-4 AWG EGC, IN 3" C
300G 300A 310A 3-350 KCMIL, 1-2 AWG EGC, IN 3" C
300N 300A 310A 3-350 KCMIL, 1-350 KCMIL NEUTRAL, IN 3" C
250NG 250A 255A 3-250 KCMIL, 1-250 KCMIL NEUTRAL, 1-4 AWG EGC, IN 3" C
250G 250A 255A 3-250 KCMIL, 1-2 AWG EGC, IN 2-1/2" C
250N 250A 255A 3-250 KCMIL, 1-250 KCMIL NEUTRAL, IN 2-1/2" C
225NG 225A 230A 3-4/0 AWG, 1-4/0 AWG NEUTRAL, 1-2 AWG EGC, IN 3" C
225G 225A 230A 3-4/0 AWG, 1-2 AWG EGC, IN 2-1/2" C
225N 225A 230A 3-4/0 AWG, 1-4/0 AWG NEUTRAL, IN 2-1/2" C
200NG 200A 200A 3-3/0 AWG, 1-3/0 AWG NEUTRAL, 1-6 AWG EGC, IN 2-1/2" C
200G 200A 200A 3-3/0 AWG, 1-4 AWG EGC, IN 2" C
200N 200A 200A 3-3/0 AWG, 1-3/0 AWG NEUTRAL, IN 2" C
150NG 150A 150A 3-1/0 AWG, 1-1/0 AWG NEUTRAL, 1-6 AWG EGC, IN 2" C
150G 150A 150A 3-1/0 AWG, 1-6 AWG EGC, IN 2" C
150N 150A 150A 3-1/0 AWG, 1-1/0 AWG NEUTRAL, IN 2" C
100NG 100A 100A 3-3 AWG, 1-3 AWG NEUTRAL, 1-8 AWG EGC, IN 1-1/4" C
100G 100A 100A 3-3 AWG, 1-8 AWG EGC, IN 1-1/4" C
100N 100A 100A 3-3 AWG, 1-3 AWG NEUTRAL, IN 1-1/4" C
60NG 60A 65A 3-6 AWG, 1-6 AWG NEUTRAL, 1-10 AWG EGC, IN 1" C
60G 60A 65A 3-6 AWG, 1-8 AWG EGC, IN 1" C
60N 60A 65A 3-6 AWG, 1-6 AWG NEUTRAL, IN 1" C
TAG BREAKER SIZE 75°C AMPACITY CONDUCTOR SIZE (CU)
ELECTRICAL EQUIPMENT FEEDER SCHEDULE
30NG 30A 35A 3-10 AWG, 1-10 AWG NEUTRAL, 1-10 AWG EGC, IN 3/4" C
30G 30A 35A 3-10 AWG, 1-8 AWG EGC, IN 3/4" C
30N 30A 35A 3-10 AWG, 1-10 AWG NEUTRAL, IN 3/4" C
20NG 20A 25A 3-12 AWG, 1-12 AWG NEUTRAL, 1-12 AWG EGC, IN 3/4" C
20G 20A 25A 3-12 AWG, 1-8 AWG EGC, IN 3/4" C
20N 20A 25A 3-12 AWG, 1-12 AWG NEUTRAL, IN 3/4" C
100G(2) 100A(2) 100A(2) 2 SETS OF 3-3 AWG, 1-8 AWG EGC; COMBINED IN 2" C
GFI
WALL
MOUNTED
DISCONNECT
SWITCH,
NEMA 3R
RELOCATED
MOBILE MRI
RECEPTACLE
2-10 AWG,
1-10 AWG
EG, IN 3/4" C.
200NG
FIRST FLOOR
CRAWL SPACE
INSIDE OUTSIDE
AREA W ELECTRICAL SERVICE BAY
1-S-W ROOM 1V-101
EXISTING
PANEL 'ECL1S'
208/120V
50A MLO
CRITICAL
GRADE
EXISTING
PANEL
'ECPDOQ'
480/277V 400A
CRITICAL
LOWER LEVEL
TRANSFORMER VAULT NO. 5
AREA "U"
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0 :2
P
M
E-601
ONE-LINE DIAGRAM
14 15JDM
NEW 4TH MRI ADDITION
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD.
RICHMOND, VA 23249 NOVEMBER 10, 2020
BID DOCUMENTS
652-CSI-20419-088
GG
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
Scale: N.T.S.
POWER RISER DIAGRAM - MRI SUITES
1 UTILIZE EXISTING SPARE CIRCUIT
BREAKERS. SEE PANEL SCHEDULE.
2 REMOVE PANEL INTERIORS AND REPLACE
WITH 400A, 42-POLE INTERIORS, SQUARE D
#NF442L4, WITH FEED-THRU LUG KIT,
#NF400FTL. RECONNECT EXISTING FEEDER
CONDUCTORS TO MAIN LUGS, AND PROVIDE
NEW FEED THRU CONDUCTORS AS SHOWN
TO 250A ENCLOSED CIRCUIT BREAKER.
3 REPLACE EXISTING TRIP UNITS IN BREAKERS
FEEDING PANELS 'PCLA' AND 'PCLB' WITH
400A TRIP UNITS, GE #SRPG400A.
4 EXISTING ENCLOSED CIRCUIT BREAKER.
5 PROVIDE 150A/3P CIRCUIT BREAKER IN
PANEL 'ECPDOQ' TO MATCH EXISTING.
Scale: N.T.S.
PARTIAL RISER DIAGRAM - MOBILE MRI
A. MAIN SERVICE PANELS FOR MRI EQUIPMENT
SHALL HAVE OCP DEVICES WITH SHUNT TRIP.
COORDINATE WITH VENDORS INSTALLATION
DRAWINGS AND EPO SWITCHES.
B. LIGHTER LINEWEIGHT INDICATES EXISTING TO
REMAIN, VERIFY IN FIELD. HEAVIER LINEWEIGHT
INDICATES NEW WORK.
ggossett Highlight ggossett Highlight ggossett Callout Mobile MRI sources revised to Critical branch power.
ggossett Highlight ggossett Highlight ggossett Highlight ggossett Highlight
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| Sheets |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| Sheets |
| E-601 - ONE-LINE DIAGRAM |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-401 - ELECTRICAL RACEWAY PLAN |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-501 - ELECTRICAL DETAILS |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-502 - ELECTRICAL DETAILS |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-503 - ELECTRICAL DETAILS |
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES AND SYMBOL LEGENDS |
| E-002 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| E-401 - ELECTRICAL RACEWAY PLAN |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-503 - ELECTRICAL DETAILS |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| ED101 - FIRST FLOOR ELECTRICAL DEMOLITION PLAN |
| EL101 - FIRST FLOOR LIGHTING PLAN - MRI SUITE |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
| EP102 - ROOF POWER PLAN |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| EP104 - PARTIAL BASEMENT ELECTRICAL PLAN |
| ES101 - FIRST FLOOR ELECTRICAL PLAN - OVERALL |
| E-601 - ONE-LINE DIAGRAM |
| Sheets |
| E-601 - ONE-LINE DIAGRAM |
| EP103 - FIRST FLOOR ELECTRICAL PLAN - MOBILE MRI |
| E-602 - ELECTRICAL SCHEDULES |
| Sheets |
| E-601 - ONE-LINE DIAGRAM |
| E-602 - ELECTRICAL SCHEDULES |
| EP101 - FIRST FLOOR ELECTRICAL PLAN - MRI SUITE |
File details come from the government source that posted it. Updated .