Park County Office Standby Power Plans.pdf
PDF 14 MB Posted
- Attached to
- Park County Office Standby Power
- Solicitation number
- FAC2025-003
- Issued by
- Pitkin County, Colorado
About this file
The document is a set of electrical engineering plans for the Park County Office Building Standby Power Addition project located at 856 Costello Avenue in Fairplay, Colorado. The comprehensive plan set includes detailed electrical site plans, one-line diagrams, electrical symbol legends, and conduit routing elevations for installing a new standby power system. The project involves adding a new 800 amp service disconnect, routing new conduits and feeders, and integrating an existing diesel generator located at 911 Clark Street to provide backup power for the county office building. The plans are designed by MEP Engineering Inc. and are dated October 30, 2024, with the project number 24191, and are marked "For Bidding" stage.
The electrical plans show a complex installation requiring directional boring for conduit placement, surface-mounted conduit routing, and careful coordination with existing electrical infrastructure. The one-line diagrams detail the electrical distribution, including main distribution panels, transfer switches, and generator connections. The site plan reveals the spatial relationships between the existing building, utility transformer, and proposed electrical improvements. Drawing notes emphasize the importance of field verification, utility coordination, and precise routing to avoid existing structural elements and infrastructure. The plans also include accessibility and code compliance annotations, indicating careful attention to regulatory requirements for the electrical system upgrade.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB FAC2025-003 Park County Office Standby Power.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARK COUNTY OFFICE BUILDING
STANDBY POWER ADDITION
856 COSTELLO AVENUE, FAIRPLAY, COLORADO 80440
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E001
COVER PAGE
SYMBOL DESCRIPTION
LINETYPES and LINEWEIGHTS
NOTES and TAGS
CIRCUITING POWER SYMBOLS
ABBREVIATIONS
ELECTRICAL SYMBOLS LEGEND
ALL SYMBOLS INDICATED IN THE LEGEND MAY NOT NECESSARILY BE USED ON PLANS.
CIRCUITING DESIGNATION -
OPEN 277/480V., SOLID 120/208V.
CIRCUITING - RUN CONCEALED IN WALL
OR CEILING
CIRCUITING - RUN CONCEALED IN FLOOR
OR GRADE
CONDUIT RISER - TURNED UP, TURNED
DOWN
CIRCUITING - CONTINUED AS DESIGNATED
CIRCUITING - END CAP
GRADE - LARGER DASHED AND BOLD
NEW CIRCUITING - UNDER FLOOR OR
NEW CIRCUITING - CONTINUOUS AND BOLD
EXISTING CIRCUITING - CONTINUOUS AND
THIN
DEMOLITION CIRCUITING - LARGER
DASHED AND THIN
NEW AND RELOCATED DEVICES AND
FIXTURES - CONTINUOUS AND BOLD
EXISTING DEVICES AND FIXTURES
- CONTINUOUS AND THIN
- SMALLER DASHED AND THIN
DEMOLITION DEVICES AND FIXTURES
REVISION DELTA
DRAWING NOTE
MECHANICAL EQUIPMENT
KITCHEN EQUIPMENT
TELECOMMUNICATION SYMBOLS
JUNCTION BOX; J-BOX WITH BLANK COVER
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
HALF SWITCHED DUPLEX RECEPTACLE
DEDICATED DUPLEX RECEPTACLE
CEILING MOUNTED DUPLEX RECEPTACLE
CLG. MOUNTED FOURPLEX RECEPTACLE
FOURPLEX RECEPTACLE
DEDICATED FOURPLEX RECEPTACLE
SPECIAL RECEPTACLE - SEE DRAWING NOTES
FLOOR MOUNTED POWER FLOOR BOX DEVICE
FLOOR COMBINATION PWR/DATA FLOOR BOX
NON FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
VARIABLE FREQUENCY DRIVE
MOTOR
ONE, TWO, and THREE BUTTON PUSH SWITCH
POWER POLE
TIME CLOCK
CONTACTOR
METER
PANEL BOARD
CLOCK
PULLBOX
CURRENT TRANSFORMER
TRANSFORMER
DESCRIPTIONSYMBOL
SWITCHES
SWITCH, SINGLE POLE
SWITCH, DOUBLE POLE
SWITCH, THREE WAY
SWITCH, FOUR WAY
SWITCH, DIMMER
SWITCH, KEYED
SWITCH, WITH PILOT LIGHT
SWITCH, THERMAL OVERLOAD
SWITCH, VARIABLE SPEED CONTROL
SWITCH, WITH TYPE S FUSE HOLDER
(INCLUDE FUSE)
CEILING MOUNTED FIRE HORN/STROBE
SYMBOL DESCRIPTION
FIRE ALARM SYMBOLS
CEILING MOUNTED STROBE
CEILING MOUNTED FIRE SPEAKER
REMOTE INDICATOR LAMP
MANUAL PULL STATION
FLOW SWITCHFS
TS TAMPER SWITCH
WALL MOUNTED STROBE
WALL MOUNTED FIRE HORN
WALL MOUNTED FIRE HORN/STROBE
MAGNETIC DOOR HOLD OPEN
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
DUCT DETECTOR
FIRE SMOKE DAMPER
HEAT DETECTOR
SMOKE DETECTOR
FIREFIGHTER'S PHONE JACK / WALL PHONE
MISCELLANEOUS SYMBOLS
CARD READER, DOUBLE GANG BOX,
REMOTE TEST SWITCH
MUSIC OR PAGING SPEAKER, DOUBLE GANG,
EPO
BELL
SECURITY CAMERA, DOUBLE GANG BOX,
TRANSFORMER
NON-FUSED DISCONNECT
FUSED DISCONNECT SWITCH
PULL BOX
CURRENT TRANSFORMER
ONE LINE DIAGRAM SYMBOLS
DESCRIPTIONSYMBOL
PANEL BOARD
PAD MOUNTED
TRANSFORMER
TRANSFER SWITCH
TRANSFORMER BANK
OVERHEAD POLE MOUNTED
GENERATOR
METER
DESCRIPTIONSYMBOL
FUSED DISCONNECT SWITCH
WITHIN SWITCHBOARD
WITHIN SWITCHBOARD
SPARE SWITCH
SPACE WITHIN SWITCHBOARD
CIRCUIT BREAKER
SERVICE WEATHER HEAD
CURRENT TRANSFORMER
GROUNDING CONNECTION
MOTOR
SWITCH
FLOOR DATA OUTLET - SEE DRAWING NOTES
1" CONDUIT STUB TO ACCESSIBLE CEILING
DATA OUTLET, DOUBLE GANG BOX,
1" CONDUIT STUB TO ACCESSIBLE CEILING
TELEPHONE/DATA OUTLET, DOUBLE GANG BOX,
1" CONDUIT STUB TO ACCESSIBLE CEILING
TELEPHONE OUTLET, DOUBLE GANG BOX,
FLOOR TELEPHONE/DATA OUTLET - SEE
CABLE TV OUTLET, DOUBLE GANG BOX,
WALL SECURITY MOTION SENSOR,DOUBLE GANG,
CLG. SECURITY MOTION SENSOR, DOUBLE GANG,
FF
INTERCOM PUSH BUTTON, DOUBLE GANG BOX
MICROPHONE JACK
COMBINATION CLOCK/SPEAKER BOX
PS PRESSURE SWITCH
ENCLOSURE
SWITCH, LOW VOLTAGE - SEE DRAWING NOTES
3/4" CONDUIT STUB TO ACCESSIBLE CEILING
3/4" CONDUIT STUB TO ACCESSIBLE CEILING
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
3/4" CONDUIT STUB TO ACCESSIBLE CEILING
TWO-WAY COMMUNICATION STATION
1" CONDUIT STUB TO ACCESSIBLE CEILING
LIGHTING CONTROL NOTE
DRAWING NOTES
GROUND BAR
COMBINATION DUPLEX RECEPT / USB OUTLETUSB
FIRE ALARM GRAPHIC MAP
PHOTOCELL
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
THERMOSTAT, LINE VOLTAGE
GB GROUND BAR
LTG SCENE CONTROLLER-SEE DRAWING NOTES
PA
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
EMERGENCY POWER OFF PUSH BUTTON
DOOR BUZZER
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
DOOR CONTACT, - SEE DRAWING NOTES
1/2" CONDUIT STUB TO ACCESSIBLE CEILING
LIGHTING CONTROL SENSORS
a,b
D
WALL VACANCY SENSOR, DUAL TECH,
SINGLE ZONE, INTEGRAL OVERRIDE SWITCH
WALL VACANCY SENSOR, DUAL TECH,
SINGLE ZONE, INTEGRAL OVR SWITCH, DIMMING
WALL VACANCY SENSOR, DUAL TECH,
DUAL ZONE, INTEGRAL OVERRIDE SWITCH,
a,b
CEILING VACANCY SENSOR, DUAL TECH,
SINGLE ZONE, POWER PACK;
CEILING VACANCY SENSOR, DUAL TECH,
DUAL ZONE, 2P POWER PACK;
LV OVERRIDE SWITCHES
LV OVERRIDE SWITCHES
WP CEILING VACANCY SENSOR, SINGLE ZONE,
EXTERIOR RATED, EXTENDED RANGE, PIR
INTERIOR DAYLIGHT SENSOR
A,AMP AMPERE
AC ABOVE COUNTER
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CT CURRENT TRANSFORMER
CU COPPER
CLG CEILING (CEILING MOUNTED)
CWP COLD WATER PIPE
(D) EXISTING TO BE DEMOLISHED
Db DECIBEL
(E) EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EPO EMERGENCY POWER OFF
EM EMERGENCY POWER CIRCUIT
FA FIRE ALARM
FC FOOTCANDLES
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
G,GND GROUND
HP HORSEPOWER
IG ISOLATED GROUND DEVICE
LV LOW VOLTAGE
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MV MEDIUM VOLTAGE
MW MICROWAVE
(N) NEW
N NEUTRAL
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
NEC NATIONAL ELECTRIC CODE
NF NON FUSED
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
(PART) PARTIAL CIRCUIT
REF REFRIGERATOR
(RL) EXISTING TO BE RELOCATED
RTS REMOTE TEST SWITCH
TBB TELEPHONE PLYWOOD BACKBOARD
UC UNDER COUNTER
UG UNDER GROUND
WP WEATHERPROOF - NEMA 3R
XP EXPLOSION PROOF
DC
B
S
T
P
S
MIC
AI
M
B
M
S
RTS
CR
M
B P
TC
FT
H S
PANEL
"LA"
T C
B P
FRN-R
100A
100/3
100/3
F T
T F
FRN-R
100A
100/3
SPARE
100/3
SPACE
100/3
M
G
M
LV
CS
F
MAP
ANN
FACP
DH
F
F
F
F
SC
SU
V
TO
P
K D
GB
C
TC
PP
M
VFD
CJ
D
OS
a,b
VS
VS
VS
VS
VS
CODE ANALYSIS
Park County Office Building (Phase II) Fairplay, CO
Applicable Codes: 2018 IBC
2018 IBC – International Building Code 2018 IECC – International Energy Conservation Code 2018 IFC – International Fire Code 2018 IFGC – International Fuel Gas Code 2018 IMC – International Mechanical Code 2018 IPC – International Plumbing Code 2023 NEC – National Electric Code ANSI A117.1 (Accessible and Usable Facilities) Town of Fairplay Unified Development Code
The building size of 22,895 GSF (2 stories),the A-3, B and S-1 occupancies and a building construction type of Type II-B.
TOPIC
Occupancy Classification
Fire Walls
Construction Type
Allowable Height and Building Areas
Area modifications with Automatic Sprinkler System and Open Space Width (min. 30')
IBC REFERENCE
Section 302.1
Section 706.4
Table 503
Table 503
Section 506.1
Section 506.2
REQUIREMENT
Group A-3, B, S-1 footnote a.- in Type II or V construction, walls shall be permitted to have a 2-hour fire-resistance rating.
Type IIB
Based on A-3, most restrictive 2 stories maximum 9,500 SF (per story)
Aa = At + [ At x lf ] + [At x ls] Aa = 9,500 + [ 9,500 x 0.75 ] + 9,500 x 2 Aa = 35,625 (Per Story) Maximum Allowed lf = [ F / P - 0.25 ] W / 30 lf = [ 800 / 800 - 0.25 ] 30 / 30 lf = 0.75
GENERAL INFORMATION:
Allowable Areas for Openings
Elevator Lobby
Fire Alarm and Detection Systems
Exit Doorway Arrangement
Stairway Area of Refuge
Minimum Clear Height
Stairway Clear Width
Exit Access Travel Distance
Corridor Fire-Resistance Required
Minimum Egress Width
Minimum Number of Exits
Exit Access Stairways
Fire Extinguisher, Portable
Section 705.8.1 exception 1.1
Section 713.14.1 exception 4
Section 907.2.1
Section 1015.2.1 exception 2
Section 1007.3 exception 2
Section 1003.2
Section 1007.3 exception 1
Table 1016.2
Table 1018.1
Section 1018.2
Table 1021.2
Section 1020.1 exception 4
Section 906.3
Building has fire separation of more than 15' at the first floor. Unlimited protection openings are permitted.
Not required for a building with less than three floors (2 story building)
Manual Fire Alarm boxes are not required where an automatic sprinkler system and notification appliances are installed.
Minimum distance between exit doors not to exceed one-third diagonal dimension of area served because fully sprinklered.
Area of refuge not required at unenclosed stairways because fully sprinklered.
90" for means of egress.
48" clear width at exit stairways not required because fully sprinklered.
A-3 = 250' fully sprinklered
Fully sprinklered, no rated corridors
44" Minimum
2 Exits Required First Story
Fully sprinklered building with interior egress stairway serving only the first and second story not required to be enclosed
Maximum Travel Distance to fire extinguisher for Class A Hazards is 75'-0".
Occupancy Load "A-3" 183 "B" 159 "S-1" 11 Total 353
Plumbing Fixtures Table 2902.1
WC Count
"A-3"
"B"
"S-1"
Male Female Male Female Male Female Male Female
92 (1 per 125) = 1 92 (1 per 65) = 2 80 (1 per 25 first 50) + 1 per 50 remaining = 3 80 (1 per 25 first 50) + 1 per 50 remaining = 3 6 (1 per 100) = 1 6 (1 per 100) = 1 1 + 3 + 1 = 5 2 + 3 + 1 = 6
Total Required
Total Provided
Lavatory Count
"A-3"
"B"
"S-1"
Male Female Male Female Male Female Male Female
92 (1 per 200) = 1 92(1 per 200) = 1 80 (1 per 40 first 80) + 1 per 80 remaining = 3 80 (1 per 40 first 80) + 1 per 80 remaining = 3 6 (1 per 100) = 1 6 (1 per 100) = 1 1 + 3 + 1 = 5 1 + 3 + 1 = 5
Unisex Toilet
Drinking Fountains "A-3" "B" "S-1"
183 (1 per 500) = 1 159 (1 per 100) = 2 11 (1 per 1,000) = 1 Totals 1 + 2 + 1 = 4 4 4
7 total
Service Sinks "A-3" "B" "S-1"
183 (1 service sink) = 1 159 (1 service sink) = 1 11 (1 service sink) = 1 Totals 1 + 1 + 1 = 3 3 1
Showers 0 0
Notes:
1. Individual room occupancy calculations figured per Table 1004.1.1 "Maximum Floor Area Allowances Per Occupant" for individual spaces. Spaces are then groups for occupancy listed is the general use occupancy for plumbing fixtures calculations per [P] Table 2902.1 "Minimum Number of Required Plumbing Fixtures".
2. Urinal substitution does not exceed 67% of the water closet requirement (IPC Section 419.2).
Accessible Parking Spaces
Accessible Lockers
Accessible Toilet and Bathing Facilities
Accessible Signage
Table 1106.1
Section 1109.9
Section 1109.2
Section 1110
Of the 151 spaces provided (between 150 and 200), 6 are required to be accessible (1 of which shall be van-accessible).
At least 5% of lockers must be accessible.
1 of each fixture type shall be accessible for each men and women within the new toilet rooms.
Required.
SHEET INDEX
E001 - COVER SHEET
E002 - CODE ANALYSIS AND LEGEND
E003 - ONE-LINE DIAGRAM
E004 - ONE-LINE DIAGRAM
E-100 - ELECTRICAL SITE PLAN
E-112 - ELECTRICAL FLOOR PLAN
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E002
CODE ANALYSIS AND
LEGEND
300 KVA,
UTILITY TRANSFORMER
BY XCEL ENERGY
208/120V., 3Ø, 4W
T F
M
PANEL
"MP1"
T C
M
N
G
PANEL
"P1E"
PANEL
"P1W"
PANEL
"P2E"
PANEL
"P2W"
PANEL
"LP"
MDP 208/120V, 3Ø, 4W, 1000A BUS, 65KAIC
UTILITY
PRIMARY
BY
XCEL
ENERGY
800AMP CT CABINET
WITH CT'S
GFP
SPACE
60/3 800/3
400/3 100/3 100/3 100/3 200/3 50/3 100/3
6 2 2 2 5 3 2
BLDG STEELCOLD WATER PIPE
CONCRETE
ENCASED
ELECTRODE
8 109
5 (4-250KCMIL AL; 1 #4 AL GND) 2-1/2" C
[2(4-250 KCMIL AL; 2 #1 AL GND)] IN SINGLE 4" C
FEEDER SCHEDULE
(4 #1/0 AL; 1#6 GND) 2" C
(1 #4 GND) 3/4" C
(5 #3AL) 1-1/4" C
3 [(4-400 KCMIL AL) 3" C]
(1 3/0 GND) 3/4" C
ROOF
UPPER LEVEL
LOWER LEVEL
ELEVATOR
ELEVATOR
CONTROLLER
100A3P
DISCONNECT
SPD
1"C
XCEL ENERGY METER
N.T.S.SCALE:
ONE-LINE DIAGRAM - 856 CASTELLO
(3 #8 AL; 1#8 AL GND) 3/4" C
(1 #6 GND) 3/4" C
PANEL
"MP2"
400/3
NEW 800A 120/208V, 3Ø,
4W, 4-POLE AUTOMATIC
TRANSFER SWITCH
65,000A AIC RATING
G 200/3
40/3
400/3
400/3
EXISTING 250KW / 312.5KVA
120/208V, 3Ø, 4W
CUMMINS DIESEL GENERATOR
LOCATED AT 911 CLARK ST.
DRAWING NOTES
1. DISCONNECT N-G BOND AT MAIN SWITCHGEAR. CONNECT NEW N-G CONNECTION AT MAIN DISCONNECT
BACK TO EXISTING GROUNDING ELECTRODE SYSTEM.
2. ROUTE SURFACE MOUNTED CONDUIT FROM SERVICE DISCONNECT ALONG WALL TO ELECTRICAL ROOM.
PENETRATE EXTERIOR WALL VIA PULL BOX AND EXTEND TO NEW TRANSFER SWITCH LOCATION.
3. ROUTE SURFACE MOUNTED CONDUIT UP FROM BORE LOCATION TO PULL BOX ADJACENT TO NORMAL
POWER FEED AND EXTEND TO NEW TRANSFER SWITCH LOCATION.
EXISTING FEEDER
TO BE REMOVED
11 3[(4-400 KCMIL AL; 1#3/0 SSBJ)3"C]
12 3[(4-400 KCMIL AL; 1#1/0 GND)3"C]
EXISTING FEEDER
TO BE REMOVED
CONTRACTOR TO COORDINATE ADDITION OF 400A 3-POLE BREAKER WITH
GENERATOR MANUFACTURER. IT IS UNLIKELY AN ADDITIONAL BREAKER CAN BE
ADDED TO THE EXISTING GENERATOR OUTPUT BREAKER CONFIGURATION.
CONTRACTOR TO INCLUDE COSTS TO INVESTIGATE MULTIPLE SOLUTIONS.
FIRST SOLUTION WOULD ENTAIL TAPPING OFF THE GENERATOR BUSSING TO AN
ENCLOSED, NEMA-3R, 400 AMP CIRCUIT BREAKER MOUNTED ADJACENT TO THE
GENERATOR ON A UNISTRUT RACK. LOCATE BREAKER TO MAINTAIN
GENERATOR ACCESS. ALTERNATIVELY CONTRACTOR TO PROVIDE PRICING TO
PROVIDE 600 AMP NEMA-3R PANELBOARD WITH 200/3 BREAKER AND 400/3
BREAKER. TAP GENERATOR BUSSING WITH 2[4-350 KCMIL; 1#1 GND)2-1/2"C]
RECONNECT EXISTING 200/3 FEED TO NEW PANELBOARD AND CONNECT NEW
400/3 FEED SERVING NEW STANDBY POWER FEED TO 856 COSTELLO AVENUE.
G 200/3
40/3
400/3
400/3EXISTING 250KW / 312.5KVA
120/208V, 3Ø, 4W
CUMMINS DIESEL GENERATOR
LOCATED AT 911 CLARK ST.
PANEL
"GEN"
200/3
RECONNECT TO EXISTING
200AMP STANDBY POWER
FEEDER
NEW STANDBY POWER
CONNECTION TO 856
COSTELLO
N.T.S.SCALE:
ALTERNATE GENERATOR STANDBY CONNECTION
2[(4-350 KCMIL; 1 #1 GND)2-1/2"C
REMOVE EXISTING 200/3 BREAKER TO
ALLOW TAP CONNECTION.
X ISC #1
ISC #2 X
X
ISC #3 X
ISC #4
NOTE: ALL FEEDERS ARE COPPER UNLESS OTHERWISE NOTED.
14 (1) 2"C FOR CONTROLS
2[(4-250 KCMIL AL; 1 #1 AL GND)2-1/2"C]
KRP-C
800A
800/3
G N
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E003
ONE LINE DIAGRAM
N.T.S.SCALE:
ONE-LINE DIAGRAM - 911 CLARK ST.
1 3 [(4 #350 KCMIL THWN CU) 3" C]
5 (CONTROL CABLE PER MANUFACTURER'S REQUIREMENTS) 1"C.
6 (4 #4 THWN CU & #8 CU GRD) 1 1/2"C.
FEEDER SCHEDULE
(4 #6 THWN CU & #10 CU GRD) 1 1/4"C.
2 [(4 #3/0 THWN CU & #3 CU GRD) 2 1/2"C]
2 [(4 #3/0 THWN CU & #3 CU GRD) 2 1/2"C.]
(4 #1/0 THWN CU & #6 CU GRD) 2"C.
PAD MOUNT
TRANSFORMER
T F
M T
C
UTILITY PRIMARY
BY XCEL ENERGY
CT CABINET
NEMA 3R
XCEL
ENERGY
METER
(4 #1 THWN CU & #8 CU GRD) 2"C.
(4 #1/0 THWN CU & #6 CU GRD) 2"C.
(3 #1 THWN CU & #8 CU GRD) 1 1/2"C.
(4 #3/0 THWN CU & #6 CU GRD) 2 1/2"C.
12 (3 #1/0 THWN CU & #6 CU GRD) 2"C.
13 (4 #1/0 THWN CU, 1 #4/0 THWN CU NEUTRAL, 1 #6
GRD & #6 CU ISOLATED GRD) 2 1/2"C.
14 (#6 CU GRD) 3/4"C.
15 (#3/0 CU GRD) 3/4"C.
16 1 1/4"C.
17 1"C.
MDP - "A" 120/208 VOLT, 3Ø, 4 WIRE 800A MCB,
NEMA 3R 42,000 AIC
MCB
800/3
40/3SPD
INTERNALLY
MOUNTED
N
G
COLD WATER PIPE
14 14 15 15 15 15
BLDG STEEL
TWO - 3/4" x 10'-0"
COPPER GROUND RODS
REFERENCE GROUND
BAR (DATA)
UFFER GROUND 40'-0" BARE
3/0 COPPER IN FOOTER
60/3 60/3 125/3 100/3 150/3400/3 400/3
2 3
6 6 7 8 9
(4) 100/3
SPACES
SDP - "B" 120/208V, 3Ø, 4 WIRE
400A MLO 42,000 AIC
PANEL
"LPA"
PANEL
"RPA"
PANEL
"RPB"
PANEL
"RPC"
PANEL
"M"
SERIES RATED
FULLY RATED
100/3
MCB
TO MAIN
TELEPHONE
SWITCH
G
LOWER LEVEL
PANEL
"LSA"
BUSSMANN
COORDINATION
PANEL
#250DQDAA
40/3400/3
DIESEL CUMMINS
NEMA 3R ENCLOSURE
SILENT RACK
LIFE SAFETY ATS
60A, 4 POLE
EQUIPMENT ATS
400A, 4 POLE
REMOTE
ANNUNCIATOR
(#3/0 CU GRD) 3/4"C. TO
SERVICE GROUND
RPA-4 BATTERY
PAD HEATER
RPA-6,8 (2 #8 & GRD) 1"C.
208V JACKET HEATER
125/3
SPD
(4) 100/3
SPACES
125/3
200/3
90/3
UPS
A
UPS
B
PANEL
"UPSA"
PANEL
"UPSB"
125/3
MCB
125/3
MCB
30 KW 30 KW
EITHER UPS CAN CARRY 100% OF UPS
LOAD IF OTHER IS DOWN FOR SERVICE. A/B
SWITCHING FROM UPS UNITS
PANEL
"EMA"
PANEL
"CRAC"
WP
INTERNALLY
MOUNTED
PANEL "EM" 120/208V, 3Ø, 4W
400A MLO AIC = 22,000
EXISTING ONE-LINE DIAGRAM SHOWN FOR REFERENCE ONLY. NO WORK THIS CONTRACT.
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E004
ONE LINE DIAGRAM
SCALE: 1" = 10'-0"
ELECTRICAL SITE PLAN
DRAWING NOTES
1. CONTRACTOR TO LOCATE EXISTING 4" SPARE CONDUIT UNDER GRAVEL YARD AREA AND EXTEND TO
NEW TRANSFER SWITCH LOCATION. UTILIZE DIRECTIONAL BORING TO AVOID SAW CUT AND PATCH OF EXISTING PARKING AREA. PROVIDE MINIMUM 24"X36"X24"D POLYMER CONCRETE BOX WITH TIER 22 COVER. SIZE BOX AS NEEDED TO MEET NEC 314 REQUIREMENTS FOR STRAIGHT PULL, ANGLED OR U-PULL OF CONDUCTORS BASED ON MEANS AND METHODS USED IN THE INSTALLATION IF CONDUIT
AND CONDUCTORS. HUBBELL ARMORCAST A600 SERIES OR EQUAL.
2. CONTRACTOR TO PROVIDE NEW SERVICE DISCONNECT ADJACENT TO EXISTING CT CABINET. ROUTE CONDUIT FROM CT CABINET INTO NEW SERVICE DISCONNECT AND FROM NEW SERVICE DISCONNECT
SURFACE MOUNTED ALONG WALL TO ELECTRICAL ROOM LOCATION. PULL NEW FEEDERS CT TO
DISCONNECT AND FROM DISCONNECT TO TRANSFER SWITCH LOCATED IN THE SAME ELECTRICAL
ROOM AS MAIN SWITCHGEAR.
3. CONTRACTOR TO PROVIDE NEW 2" CONDUIT FROM GENERATOR LOCATION TO NEW TRANSFER SWITCH LOCATION FOR CONTROL WIRING. COORDINATE TRENCHING/BORING OF CONDUIT WITH OWNERSHIP
PRIOR TO ROUGH-IN.
4. EXTEND CONDUIT AND ROUTE NEW FEEDERS AND CONTROL WIRING FROM TO FINAL CIRCUIT
BREAKER/CONTROLS TERMINATION BLOCK WITHIN GENERATOR ENCLOSURE.
5. LOCATION OF 400/3 ENCLOSED CIRCUIT BREAKER IN NEMA R3 ENCLOSURE UNITSTRUT MOUNTED AT 48" A.F.G. ADJACENT TO EXISTING GENERATOR & EXISTING 4" CONDUIT. REFER TO NOTE ON ONE-LINE
DIAGRAM E003. FIELD ADJUST LOCATION TO MAINTAIN GENERATOR ACCESS.
T F
T C
M
NEW 800 AMP
NEMA 3R SERVICE
DISCONNECT
1 EXISTING CUMMINS
DIESEL GENERATOR
EXISTING SPARE
4" CONDUIT
B P
DIRECTIONAL BORE 4"
CONDUIT, MINIMUM OF 24"
BELOW PARKING LOT
PAVING FOR FEEDER.
DIRECTIONAL BORE 2"
CONDUIT, MINIMUM OF 24"
BELOW PARKING LOT
PAVING FOR CONTROLS.
TO ATS,
RE: E101
DEPTH OF CONDUIT BORE
WILL BE DEEPER IN THIS
AREA REFER TO SHEET
E102 FOR CONDUIT
ELEVATION DIAGRAM.
EXISTING UTILITY
TRANSFORMER
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E100
ELECTRICAL
SITE PLAN
AutoCAD SHX Text E102
AutoCAD SHX Text
DRAWING NOTES
1. RELOCATE EXISTING FIRE ALARM DOCUMENTS CABINET TO OTHER SIDE OF FIRE ALARM
CONTROL PANEL TO ALLOW ROOM FOR NEW AUTOMATIC TRANSFER SWITCH.
2. FIELD COORDINATE WALL PENETRATION LOCATIONS AND PULL BOX LOCATIONS ON EXTERIOR WALL.
COORDINATE ROUTING OF CONDUIT FROM PULL BOXES ABOVE EXISTING PANELS TO NEW ATS
LOCATION.
1/8" = 1'-0"SCALE:
LOWER LEVEL AREA 2 POWER PLAN
N.T.S.SCALE:
KEY PLAN
ATS
T C
M
NEW 800A SERVICE DISCONNECT
ON UNISTRUT RACK RE: DIAGRAM
THIS SHEET.
SURFACE MOUNTED CONDUIT ROUTED ABOVE
DOOR ON UNISRUT RACK. STANDOFF WALL TO
AVOID STRUCTURAL COLUMN AND EXTERNAL
STORMWATER DOWNSPOUT. RE PHOTOS THIS
SHEET & CONDUIT ELEVATION SHEET E102. N.T.S.SCALE:
PROPOSED SERVICE DISCONNECT CONFIGURATION
EXTEND DOWNSPOUT AND SPLASHBLOCK
PAST NEW ELECTRICAL SERVICE
DISCONNECT.
PROPOSED SURFACE MOUNTED CONDUIT ALONG EXTERIOR WALL
ROUTE CONDUIT TO AVOID DOWNSPOUTS AND PLATFORM
SUPPORT BEAMS. ROUTE UNDER PLATFORM WALKWAY TO OTHER
SIDE OF DOOR. PENETRATE WALL ABOVE ELECTRICAL PANELS
AND EXTEND TO NEW AUTOMATIC TRANSFER SWITCH LOCATION.
NEMA 3R PULLBOXES SURFACE MOUNTED.
REFER TO CONDUIT ELEVATION SHEET E102.
EXISTING CT CABINET
& METER
CONDUIT TO JOG STANDING OFF WALL TO AVOID
EXISTING STEEL BEAM, ROUTE UNDER PLATFORM,
ABOVE DOOR.
CONDUIT TO JOG STANDING OFF WALL TO AVOID
EXISTING STEEL BEAM, PENETRATE ALUMINUM
SIDING ON RIGHT SIDE OF WALKWAY AND CONTINUE
ON TO PULLBOX ON OUTSIDE WALL OF ELECTRICAL
ROOM.
CONDUIT FROM SERVICE DISCONNECT MOUNTED
TO WALL ABOVE EXISTING CONDENSING UNITS.
ROUTE CONDUIT TO AVOID DOWNSPOUTS AND
PLATFORM SUPPORT BEAMS.
N.T.S.SCALE:
PROPOSED CONDUIT ROUTING
DOCUMENT CABINET(RL)
GENERAL NOTES
PHOTOS AND ROUTING/MOUNTING DIAGRAMS PROVIDED TO SHOW DESIGN INTENT. CONTRACTOR SHALL VISIT SITE TO REVIEW EXISTING CONDITIONS AS THEY MAY VARY FROM WHAT IS DEPECTED. FIELD VERIFY ALL SIZES AND DIMENSIONS, AND EXISTING GRADING AND ELEVATIONS. CALL 811 AND HAVE EXISTING UTILITIES LOCATED AND MARKED PRIOR TO DIGGING. COORDINATE FINAL ROUTING AND BUILDING PENETRATIONS WITH OWNER PRIOR TO ROUGH-IN. COORDINATE POWER OUTAGES WITH OWNER 14 DAYS IN
ADVANCE.
UNISTRUT ANCHOR
BASEPLATE
UNISTRUT MOUNTING
RACK
800A SERVICE
DISCONNECT
NONESCALE:
DISCONNECT MOUNTING DIAGRAM
CONCONCRETE
FOOTER
CONDUIT TO EXISTING
CT CABINET
GRADE
CONDUIT TO NEW
ATS IN ELECTRICAL
ROOM
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E101
ENLARGED POWER PLAN
GENERAL NOTES
CONDUIT ROUTING ELEVATION PROVIDED TO SHOW DESIGN INTENT. ARCHITECTURAL ELEVATION IS FROM ORIGINAL CONSTRUCTION DOCUMENTS AND COULD VARY FROM EXISTING FIELD CONDITIONS. CONTRACTOR SHALL VISIT SITE TO REVIEW EXISTING CONDITIONS AS THEY MAY VARY FROM WHAT IS DEPECTED. FIELD VERIFY ALL SIZES AND DIMENSIONS, AND EXISTING GRADING AND ELEVATIONS. CALL 811 AND HAVE EXISTING UTILITIES LOCATED AND MARKED PRIOR TO DIGGING. COORDINATE FINAL ROUTING AND BUILDING PENETRATIONS WITH OWNER PRIOR TO ROUGH-IN. COORDINATE POWER OUTAGES WITH OWNER 14 DAYS IN
ADVANCE.
N.T.S.SCALE:
CONDUIT ROUTING ELEVATION
N.T.S.SCALE:
KEY PLAN
SERVICE DISCONNECT
ON UNISTRUT. RE: E101
EXISTING CONDENSORS
EXISTING LIGHT
EXTERIOR PULLBOXES
COORDINATE EXACT LOCATIONS
AND PENETRATIONS WITH EXISTING
EQUIPMENT AND CONDUIT IN THE
ELECTRICAL ROOM.
ROUTE CONDUIT AROUND
DRAIN PIPE
ROUTE CONDUIT SUPPORT
BEAMS
CUT SMALL OPENING IN EXISTING
METAL SIDING TO ROUTE CONDUIT
THROUGH
POWER AND CONTROLS CONDUIT
FROM GENERATOR BORED
UNDERGROUND. RE: ELECTRICAL
SITE PLAN E100.
DESIGNED BY: CHECKED BY:
PROJECT #:
ISSUE DATE#
PARK COUNTY
OFFICE BUILDING
STANDBY POWER
24191
856 CASTELLO AVE
FAIRPLAY, CO 80440
RCC RCC
FOR BIDDING 10-30-241
E102
CONDUIT ROUTING
ELEVATION
| Sheets and Views |
| 24191 - E001-E001 |
| 24191 - E002-E002 |
| 24191 - E003-E003 |
| 24191 - E004-E004 |
| 24191 - E100-E100 |
| 24191 - E101-E101 |
| 24191 - E102-E102 |