Park County Office Standby Power
Solicitation number
FAC2025-003
Issued by
Pitkin County, Colorado

About this file

The document is a set of electrical engineering plans for the Park County Office Building Standby Power Addition project located at 856 Costello Avenue in Fairplay, Colorado. The comprehensive plan set includes detailed electrical site plans, one-line diagrams, electrical symbol legends, and conduit routing elevations for installing a new standby power system. The project involves adding a new 800 amp service disconnect, routing new conduits and feeders, and integrating an existing diesel generator located at 911 Clark Street to provide backup power for the county office building. The plans are designed by MEP Engineering Inc. and are dated October 30, 2024, with the project number 24191, and are marked "For Bidding" stage.

The electrical plans show a complex installation requiring directional boring for conduit placement, surface-mounted conduit routing, and careful coordination with existing electrical infrastructure. The one-line diagrams detail the electrical distribution, including main distribution panels, transfer switches, and generator connections. The site plan reveals the spatial relationships between the existing building, utility transformer, and proposed electrical improvements. Drawing notes emphasize the importance of field verification, utility coordination, and precise routing to avoid existing structural elements and infrastructure. The plans also include accessibility and code compliance annotations, indicating careful attention to regulatory requirements for the electrical system upgrade.

View the file

Other files

File Type Posted
IFB FAC2025-003 Park County Office Standby Power.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PARK COUNTY OFFICE BUILDING

STANDBY POWER ADDITION

856 COSTELLO AVENUE, FAIRPLAY, COLORADO 80440

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E001

COVER PAGE

SYMBOL DESCRIPTION

LINETYPES and LINEWEIGHTS

NOTES and TAGS

CIRCUITING POWER SYMBOLS

ABBREVIATIONS

ELECTRICAL SYMBOLS LEGEND

ALL SYMBOLS INDICATED IN THE LEGEND MAY NOT NECESSARILY BE USED ON PLANS.

CIRCUITING DESIGNATION -

OPEN 277/480V., SOLID 120/208V.

CIRCUITING - RUN CONCEALED IN WALL

OR CEILING

CIRCUITING - RUN CONCEALED IN FLOOR

OR GRADE

CONDUIT RISER - TURNED UP, TURNED

DOWN

CIRCUITING - CONTINUED AS DESIGNATED

CIRCUITING - END CAP

GRADE - LARGER DASHED AND BOLD

NEW CIRCUITING - UNDER FLOOR OR

NEW CIRCUITING - CONTINUOUS AND BOLD

EXISTING CIRCUITING - CONTINUOUS AND

THIN

DEMOLITION CIRCUITING - LARGER

DASHED AND THIN

NEW AND RELOCATED DEVICES AND

FIXTURES - CONTINUOUS AND BOLD

EXISTING DEVICES AND FIXTURES

- CONTINUOUS AND THIN

- SMALLER DASHED AND THIN

DEMOLITION DEVICES AND FIXTURES

REVISION DELTA

DRAWING NOTE

MECHANICAL EQUIPMENT

KITCHEN EQUIPMENT

TELECOMMUNICATION SYMBOLS

JUNCTION BOX; J-BOX WITH BLANK COVER

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

HALF SWITCHED DUPLEX RECEPTACLE

DEDICATED DUPLEX RECEPTACLE

CEILING MOUNTED DUPLEX RECEPTACLE

CLG. MOUNTED FOURPLEX RECEPTACLE

FOURPLEX RECEPTACLE

DEDICATED FOURPLEX RECEPTACLE

SPECIAL RECEPTACLE - SEE DRAWING NOTES

FLOOR MOUNTED POWER FLOOR BOX DEVICE

FLOOR COMBINATION PWR/DATA FLOOR BOX

NON FUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

VARIABLE FREQUENCY DRIVE

MOTOR

ONE, TWO, and THREE BUTTON PUSH SWITCH

POWER POLE

TIME CLOCK

CONTACTOR

METER

PANEL BOARD

CLOCK

PULLBOX

CURRENT TRANSFORMER

TRANSFORMER

DESCRIPTIONSYMBOL

SWITCHES

SWITCH, SINGLE POLE

SWITCH, DOUBLE POLE

SWITCH, THREE WAY

SWITCH, FOUR WAY

SWITCH, DIMMER

SWITCH, KEYED

SWITCH, WITH PILOT LIGHT

SWITCH, THERMAL OVERLOAD

SWITCH, VARIABLE SPEED CONTROL

SWITCH, WITH TYPE S FUSE HOLDER

(INCLUDE FUSE)

CEILING MOUNTED FIRE HORN/STROBE

SYMBOL DESCRIPTION

FIRE ALARM SYMBOLS

CEILING MOUNTED STROBE

CEILING MOUNTED FIRE SPEAKER

REMOTE INDICATOR LAMP

MANUAL PULL STATION

FLOW SWITCHFS

TS TAMPER SWITCH

WALL MOUNTED STROBE

WALL MOUNTED FIRE HORN

WALL MOUNTED FIRE HORN/STROBE

MAGNETIC DOOR HOLD OPEN

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

DUCT DETECTOR

FIRE SMOKE DAMPER

HEAT DETECTOR

SMOKE DETECTOR

FIREFIGHTER'S PHONE JACK / WALL PHONE

MISCELLANEOUS SYMBOLS

CARD READER, DOUBLE GANG BOX,

REMOTE TEST SWITCH

MUSIC OR PAGING SPEAKER, DOUBLE GANG,

EPO

BELL

SECURITY CAMERA, DOUBLE GANG BOX,

TRANSFORMER

NON-FUSED DISCONNECT

FUSED DISCONNECT SWITCH

PULL BOX

CURRENT TRANSFORMER

ONE LINE DIAGRAM SYMBOLS

DESCRIPTIONSYMBOL

PANEL BOARD

PAD MOUNTED

TRANSFORMER

TRANSFER SWITCH

TRANSFORMER BANK

OVERHEAD POLE MOUNTED

GENERATOR

METER

DESCRIPTIONSYMBOL

FUSED DISCONNECT SWITCH

WITHIN SWITCHBOARD

WITHIN SWITCHBOARD

SPARE SWITCH

SPACE WITHIN SWITCHBOARD

CIRCUIT BREAKER

SERVICE WEATHER HEAD

CURRENT TRANSFORMER

GROUNDING CONNECTION

MOTOR

SWITCH

FLOOR DATA OUTLET - SEE DRAWING NOTES

1" CONDUIT STUB TO ACCESSIBLE CEILING

DATA OUTLET, DOUBLE GANG BOX,

1" CONDUIT STUB TO ACCESSIBLE CEILING

TELEPHONE/DATA OUTLET, DOUBLE GANG BOX,

1" CONDUIT STUB TO ACCESSIBLE CEILING

TELEPHONE OUTLET, DOUBLE GANG BOX,

FLOOR TELEPHONE/DATA OUTLET - SEE

CABLE TV OUTLET, DOUBLE GANG BOX,

WALL SECURITY MOTION SENSOR,DOUBLE GANG,

CLG. SECURITY MOTION SENSOR, DOUBLE GANG,

FF

INTERCOM PUSH BUTTON, DOUBLE GANG BOX

MICROPHONE JACK

COMBINATION CLOCK/SPEAKER BOX

PS PRESSURE SWITCH

ENCLOSURE

SWITCH, LOW VOLTAGE - SEE DRAWING NOTES

3/4" CONDUIT STUB TO ACCESSIBLE CEILING

3/4" CONDUIT STUB TO ACCESSIBLE CEILING

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

3/4" CONDUIT STUB TO ACCESSIBLE CEILING

TWO-WAY COMMUNICATION STATION

1" CONDUIT STUB TO ACCESSIBLE CEILING

LIGHTING CONTROL NOTE

DRAWING NOTES

GROUND BAR

COMBINATION DUPLEX RECEPT / USB OUTLETUSB

FIRE ALARM GRAPHIC MAP

PHOTOCELL

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

THERMOSTAT, LINE VOLTAGE

GB GROUND BAR

LTG SCENE CONTROLLER-SEE DRAWING NOTES

PA

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

EMERGENCY POWER OFF PUSH BUTTON

DOOR BUZZER

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

DOOR CONTACT, - SEE DRAWING NOTES

1/2" CONDUIT STUB TO ACCESSIBLE CEILING

LIGHTING CONTROL SENSORS

a,b

D

WALL VACANCY SENSOR, DUAL TECH,

SINGLE ZONE, INTEGRAL OVERRIDE SWITCH

WALL VACANCY SENSOR, DUAL TECH,

SINGLE ZONE, INTEGRAL OVR SWITCH, DIMMING

WALL VACANCY SENSOR, DUAL TECH,

DUAL ZONE, INTEGRAL OVERRIDE SWITCH,

a,b

CEILING VACANCY SENSOR, DUAL TECH,

SINGLE ZONE, POWER PACK;

CEILING VACANCY SENSOR, DUAL TECH,

DUAL ZONE, 2P POWER PACK;

LV OVERRIDE SWITCHES

LV OVERRIDE SWITCHES

WP CEILING VACANCY SENSOR, SINGLE ZONE,

EXTERIOR RATED, EXTENDED RANGE, PIR

INTERIOR DAYLIGHT SENSOR

A,AMP AMPERE

AC ABOVE COUNTER

AFCI ARC FAULT CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AL ALUMINUM

BLDG BUILDING

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CT CURRENT TRANSFORMER

CU COPPER

CLG CEILING (CEILING MOUNTED)

CWP COLD WATER PIPE

(D) EXISTING TO BE DEMOLISHED

Db DECIBEL

(E) EXISTING TO REMAIN

EC ELECTRICAL CONTRACTOR

EPO EMERGENCY POWER OFF

EM EMERGENCY POWER CIRCUIT

FA FIRE ALARM

FC FOOTCANDLES

GC GENERAL CONTRACTOR

GD GARBAGE DISPOSAL

GFCI GROUND FAULT CIRCUIT INTERRUPTER

G,GND GROUND

HP HORSEPOWER

IG ISOLATED GROUND DEVICE

LV LOW VOLTAGE

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MFR MANUFACTURER

MLO MAIN LUGS ONLY

MV MEDIUM VOLTAGE

MW MICROWAVE

(N) NEW

N NEUTRAL

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

NEC NATIONAL ELECTRIC CODE

NF NON FUSED

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NTS NOT TO SCALE

(PART) PARTIAL CIRCUIT

REF REFRIGERATOR

(RL) EXISTING TO BE RELOCATED

RTS REMOTE TEST SWITCH

TBB TELEPHONE PLYWOOD BACKBOARD

UC UNDER COUNTER

UG UNDER GROUND

WP WEATHERPROOF - NEMA 3R

XP EXPLOSION PROOF

DC

B

S

T

P

S

MIC

AI

M

B

M

S

RTS

CR

M

B P

TC

FT

H S

PANEL

"LA"

T C

B P

FRN-R

100A

100/3

100/3

F T

T F

FRN-R

100A

100/3

SPARE

100/3

SPACE

100/3

M

G

M

LV

CS

F

MAP

ANN

FACP

DH

F

F

F

F

SC

SU

V

TO

P

K D

GB

C

TC

PP

M

VFD

CJ

D

OS

a,b

VS

VS

VS

VS

VS

CODE ANALYSIS

Park County Office Building (Phase II) Fairplay, CO

Applicable Codes: 2018 IBC

2018 IBC – International Building Code 2018 IECC – International Energy Conservation Code 2018 IFC – International Fire Code 2018 IFGC – International Fuel Gas Code 2018 IMC – International Mechanical Code 2018 IPC – International Plumbing Code 2023 NEC – National Electric Code ANSI A117.1 (Accessible and Usable Facilities) Town of Fairplay Unified Development Code

The building size of 22,895 GSF (2 stories),the A-3, B and S-1 occupancies and a building construction type of Type II-B.

TOPIC

Occupancy Classification

Fire Walls

Construction Type

Allowable Height and Building Areas

Area modifications with Automatic Sprinkler System and Open Space Width (min. 30')

IBC REFERENCE

Section 302.1

Section 706.4

Table 503

Table 503

Section 506.1

Section 506.2

REQUIREMENT

Group A-3, B, S-1 footnote a.- in Type II or V construction, walls shall be permitted to have a 2-hour fire-resistance rating.

Type IIB

Based on A-3, most restrictive 2 stories maximum 9,500 SF (per story)

Aa = At + [ At x lf ] + [At x ls] Aa = 9,500 + [ 9,500 x 0.75 ] + 9,500 x 2 Aa = 35,625 (Per Story) Maximum Allowed lf = [ F / P - 0.25 ] W / 30 lf = [ 800 / 800 - 0.25 ] 30 / 30 lf = 0.75

GENERAL INFORMATION:

Allowable Areas for Openings

Elevator Lobby

Fire Alarm and Detection Systems

Exit Doorway Arrangement

Stairway Area of Refuge

Minimum Clear Height

Stairway Clear Width

Exit Access Travel Distance

Corridor Fire-Resistance Required

Minimum Egress Width

Minimum Number of Exits

Exit Access Stairways

Fire Extinguisher, Portable

Section 705.8.1 exception 1.1

Section 713.14.1 exception 4

Section 907.2.1

Section 1015.2.1 exception 2

Section 1007.3 exception 2

Section 1003.2

Section 1007.3 exception 1

Table 1016.2

Table 1018.1

Section 1018.2

Table 1021.2

Section 1020.1 exception 4

Section 906.3

Building has fire separation of more than 15' at the first floor. Unlimited protection openings are permitted.

Not required for a building with less than three floors (2 story building)

Manual Fire Alarm boxes are not required where an automatic sprinkler system and notification appliances are installed.

Minimum distance between exit doors not to exceed one-third diagonal dimension of area served because fully sprinklered.

Area of refuge not required at unenclosed stairways because fully sprinklered.

90" for means of egress.

48" clear width at exit stairways not required because fully sprinklered.

A-3 = 250' fully sprinklered

Fully sprinklered, no rated corridors

44" Minimum

2 Exits Required First Story

Fully sprinklered building with interior egress stairway serving only the first and second story not required to be enclosed

Maximum Travel Distance to fire extinguisher for Class A Hazards is 75'-0".

Occupancy Load "A-3" 183 "B" 159 "S-1" 11 Total 353

Plumbing Fixtures Table 2902.1

WC Count

"A-3"

"B"

"S-1"

Male Female Male Female Male Female Male Female

92 (1 per 125) = 1 92 (1 per 65) = 2 80 (1 per 25 first 50) + 1 per 50 remaining = 3 80 (1 per 25 first 50) + 1 per 50 remaining = 3 6 (1 per 100) = 1 6 (1 per 100) = 1 1 + 3 + 1 = 5 2 + 3 + 1 = 6

Total Required

Total Provided

Lavatory Count

"A-3"

"B"

"S-1"

Male Female Male Female Male Female Male Female

92 (1 per 200) = 1 92(1 per 200) = 1 80 (1 per 40 first 80) + 1 per 80 remaining = 3 80 (1 per 40 first 80) + 1 per 80 remaining = 3 6 (1 per 100) = 1 6 (1 per 100) = 1 1 + 3 + 1 = 5 1 + 3 + 1 = 5

Unisex Toilet

Drinking Fountains "A-3" "B" "S-1"

183 (1 per 500) = 1 159 (1 per 100) = 2 11 (1 per 1,000) = 1 Totals 1 + 2 + 1 = 4 4 4

7 total

Service Sinks "A-3" "B" "S-1"

183 (1 service sink) = 1 159 (1 service sink) = 1 11 (1 service sink) = 1 Totals 1 + 1 + 1 = 3 3 1

Showers 0 0

Notes:

1. Individual room occupancy calculations figured per Table 1004.1.1 "Maximum Floor Area Allowances Per Occupant" for individual spaces. Spaces are then groups for occupancy listed is the general use occupancy for plumbing fixtures calculations per [P] Table 2902.1 "Minimum Number of Required Plumbing Fixtures".

2. Urinal substitution does not exceed 67% of the water closet requirement (IPC Section 419.2).

Accessible Parking Spaces

Accessible Lockers

Accessible Toilet and Bathing Facilities

Accessible Signage

Table 1106.1

Section 1109.9

Section 1109.2

Section 1110

Of the 151 spaces provided (between 150 and 200), 6 are required to be accessible (1 of which shall be van-accessible).

At least 5% of lockers must be accessible.

1 of each fixture type shall be accessible for each men and women within the new toilet rooms.

Required.

SHEET INDEX

E001 - COVER SHEET

E002 - CODE ANALYSIS AND LEGEND

E003 - ONE-LINE DIAGRAM

E004 - ONE-LINE DIAGRAM

E-100 - ELECTRICAL SITE PLAN

E-112 - ELECTRICAL FLOOR PLAN

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E002

CODE ANALYSIS AND

LEGEND

300 KVA,

UTILITY TRANSFORMER

BY XCEL ENERGY

208/120V., 3Ø, 4W

T F

M

PANEL

"MP1"

T C

M

N

G

PANEL

"P1E"

PANEL

"P1W"

PANEL

"P2E"

PANEL

"P2W"

PANEL

"LP"

MDP 208/120V, 3Ø, 4W, 1000A BUS, 65KAIC

UTILITY

PRIMARY

BY

XCEL

ENERGY

800AMP CT CABINET

WITH CT'S

GFP

SPACE

60/3 800/3

400/3 100/3 100/3 100/3 200/3 50/3 100/3

6 2 2 2 5 3 2

BLDG STEELCOLD WATER PIPE

CONCRETE

ENCASED

ELECTRODE

8 109

5 (4-250KCMIL AL; 1 #4 AL GND) 2-1/2" C

[2(4-250 KCMIL AL; 2 #1 AL GND)] IN SINGLE 4" C

FEEDER SCHEDULE

(4 #1/0 AL; 1#6 GND) 2" C

(1 #4 GND) 3/4" C

(5 #3AL) 1-1/4" C

3 [(4-400 KCMIL AL) 3" C]

(1 3/0 GND) 3/4" C

ROOF

UPPER LEVEL

LOWER LEVEL

ELEVATOR

ELEVATOR

CONTROLLER

100A3P

DISCONNECT

SPD

1"C

XCEL ENERGY METER

N.T.S.SCALE:

ONE-LINE DIAGRAM - 856 CASTELLO

(3 #8 AL; 1#8 AL GND) 3/4" C

(1 #6 GND) 3/4" C

PANEL

"MP2"

400/3

NEW 800A 120/208V, 3Ø,

4W, 4-POLE AUTOMATIC

TRANSFER SWITCH

65,000A AIC RATING

G 200/3

40/3

400/3

400/3

EXISTING 250KW / 312.5KVA

120/208V, 3Ø, 4W

CUMMINS DIESEL GENERATOR

LOCATED AT 911 CLARK ST.

DRAWING NOTES

1. DISCONNECT N-G BOND AT MAIN SWITCHGEAR. CONNECT NEW N-G CONNECTION AT MAIN DISCONNECT

BACK TO EXISTING GROUNDING ELECTRODE SYSTEM.

2. ROUTE SURFACE MOUNTED CONDUIT FROM SERVICE DISCONNECT ALONG WALL TO ELECTRICAL ROOM.

PENETRATE EXTERIOR WALL VIA PULL BOX AND EXTEND TO NEW TRANSFER SWITCH LOCATION.

3. ROUTE SURFACE MOUNTED CONDUIT UP FROM BORE LOCATION TO PULL BOX ADJACENT TO NORMAL

POWER FEED AND EXTEND TO NEW TRANSFER SWITCH LOCATION.

EXISTING FEEDER

TO BE REMOVED

11 3[(4-400 KCMIL AL; 1#3/0 SSBJ)3"C]

12 3[(4-400 KCMIL AL; 1#1/0 GND)3"C]

EXISTING FEEDER

TO BE REMOVED

CONTRACTOR TO COORDINATE ADDITION OF 400A 3-POLE BREAKER WITH

GENERATOR MANUFACTURER. IT IS UNLIKELY AN ADDITIONAL BREAKER CAN BE

ADDED TO THE EXISTING GENERATOR OUTPUT BREAKER CONFIGURATION.

CONTRACTOR TO INCLUDE COSTS TO INVESTIGATE MULTIPLE SOLUTIONS.

FIRST SOLUTION WOULD ENTAIL TAPPING OFF THE GENERATOR BUSSING TO AN

ENCLOSED, NEMA-3R, 400 AMP CIRCUIT BREAKER MOUNTED ADJACENT TO THE

GENERATOR ON A UNISTRUT RACK. LOCATE BREAKER TO MAINTAIN

GENERATOR ACCESS. ALTERNATIVELY CONTRACTOR TO PROVIDE PRICING TO

PROVIDE 600 AMP NEMA-3R PANELBOARD WITH 200/3 BREAKER AND 400/3

BREAKER. TAP GENERATOR BUSSING WITH 2[4-350 KCMIL; 1#1 GND)2-1/2"C]

RECONNECT EXISTING 200/3 FEED TO NEW PANELBOARD AND CONNECT NEW

400/3 FEED SERVING NEW STANDBY POWER FEED TO 856 COSTELLO AVENUE.

G 200/3

40/3

400/3

400/3EXISTING 250KW / 312.5KVA

120/208V, 3Ø, 4W

CUMMINS DIESEL GENERATOR

LOCATED AT 911 CLARK ST.

PANEL

"GEN"

200/3

RECONNECT TO EXISTING

200AMP STANDBY POWER

FEEDER

NEW STANDBY POWER

CONNECTION TO 856

COSTELLO

N.T.S.SCALE:

ALTERNATE GENERATOR STANDBY CONNECTION

2[(4-350 KCMIL; 1 #1 GND)2-1/2"C

REMOVE EXISTING 200/3 BREAKER TO

ALLOW TAP CONNECTION.

X ISC #1

ISC #2 X

X

ISC #3 X

ISC #4

NOTE: ALL FEEDERS ARE COPPER UNLESS OTHERWISE NOTED.

14 (1) 2"C FOR CONTROLS

2[(4-250 KCMIL AL; 1 #1 AL GND)2-1/2"C]

KRP-C

800A

800/3

G N

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E003

ONE LINE DIAGRAM

N.T.S.SCALE:

ONE-LINE DIAGRAM - 911 CLARK ST.

1 3 [(4 #350 KCMIL THWN CU) 3" C]

5 (CONTROL CABLE PER MANUFACTURER'S REQUIREMENTS) 1"C.

6 (4 #4 THWN CU & #8 CU GRD) 1 1/2"C.

FEEDER SCHEDULE

(4 #6 THWN CU & #10 CU GRD) 1 1/4"C.

2 [(4 #3/0 THWN CU & #3 CU GRD) 2 1/2"C]

2 [(4 #3/0 THWN CU & #3 CU GRD) 2 1/2"C.]

(4 #1/0 THWN CU & #6 CU GRD) 2"C.

PAD MOUNT

TRANSFORMER

T F

M T

C

UTILITY PRIMARY

BY XCEL ENERGY

CT CABINET

NEMA 3R

XCEL

ENERGY

METER

(4 #1 THWN CU & #8 CU GRD) 2"C.

(4 #1/0 THWN CU & #6 CU GRD) 2"C.

(3 #1 THWN CU & #8 CU GRD) 1 1/2"C.

(4 #3/0 THWN CU & #6 CU GRD) 2 1/2"C.

12 (3 #1/0 THWN CU & #6 CU GRD) 2"C.

13 (4 #1/0 THWN CU, 1 #4/0 THWN CU NEUTRAL, 1 #6

GRD & #6 CU ISOLATED GRD) 2 1/2"C.

14 (#6 CU GRD) 3/4"C.

15 (#3/0 CU GRD) 3/4"C.

16 1 1/4"C.

17 1"C.

MDP - "A" 120/208 VOLT, 3Ø, 4 WIRE 800A MCB,

NEMA 3R 42,000 AIC

MCB

800/3

40/3SPD

INTERNALLY

MOUNTED

N

G

COLD WATER PIPE

14 14 15 15 15 15

BLDG STEEL

TWO - 3/4" x 10'-0"

COPPER GROUND RODS

REFERENCE GROUND

BAR (DATA)

UFFER GROUND 40'-0" BARE

3/0 COPPER IN FOOTER

60/3 60/3 125/3 100/3 150/3400/3 400/3

2 3

6 6 7 8 9

(4) 100/3

SPACES

SDP - "B" 120/208V, 3Ø, 4 WIRE

400A MLO 42,000 AIC

PANEL

"LPA"

PANEL

"RPA"

PANEL

"RPB"

PANEL

"RPC"

PANEL

"M"

SERIES RATED

FULLY RATED

100/3

MCB

TO MAIN

TELEPHONE

SWITCH

G

LOWER LEVEL

PANEL

"LSA"

BUSSMANN

COORDINATION

PANEL

#250DQDAA

40/3400/3

DIESEL CUMMINS

NEMA 3R ENCLOSURE

SILENT RACK

LIFE SAFETY ATS

60A, 4 POLE

EQUIPMENT ATS

400A, 4 POLE

REMOTE

ANNUNCIATOR

(#3/0 CU GRD) 3/4"C. TO

SERVICE GROUND

RPA-4 BATTERY

PAD HEATER

RPA-6,8 (2 #8 & GRD) 1"C.

208V JACKET HEATER

125/3

SPD

(4) 100/3

SPACES

125/3

200/3

90/3

UPS

A

UPS

B

PANEL

"UPSA"

PANEL

"UPSB"

125/3

MCB

125/3

MCB

30 KW 30 KW

EITHER UPS CAN CARRY 100% OF UPS

LOAD IF OTHER IS DOWN FOR SERVICE. A/B

SWITCHING FROM UPS UNITS

PANEL

"EMA"

PANEL

"CRAC"

WP

INTERNALLY

MOUNTED

PANEL "EM" 120/208V, 3Ø, 4W

400A MLO AIC = 22,000

EXISTING ONE-LINE DIAGRAM SHOWN FOR REFERENCE ONLY. NO WORK THIS CONTRACT.

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E004

ONE LINE DIAGRAM

SCALE: 1" = 10'-0"

ELECTRICAL SITE PLAN

DRAWING NOTES

1. CONTRACTOR TO LOCATE EXISTING 4" SPARE CONDUIT UNDER GRAVEL YARD AREA AND EXTEND TO

NEW TRANSFER SWITCH LOCATION. UTILIZE DIRECTIONAL BORING TO AVOID SAW CUT AND PATCH OF EXISTING PARKING AREA. PROVIDE MINIMUM 24"X36"X24"D POLYMER CONCRETE BOX WITH TIER 22 COVER. SIZE BOX AS NEEDED TO MEET NEC 314 REQUIREMENTS FOR STRAIGHT PULL, ANGLED OR U-PULL OF CONDUCTORS BASED ON MEANS AND METHODS USED IN THE INSTALLATION IF CONDUIT

AND CONDUCTORS. HUBBELL ARMORCAST A600 SERIES OR EQUAL.

2. CONTRACTOR TO PROVIDE NEW SERVICE DISCONNECT ADJACENT TO EXISTING CT CABINET. ROUTE CONDUIT FROM CT CABINET INTO NEW SERVICE DISCONNECT AND FROM NEW SERVICE DISCONNECT

SURFACE MOUNTED ALONG WALL TO ELECTRICAL ROOM LOCATION. PULL NEW FEEDERS CT TO

DISCONNECT AND FROM DISCONNECT TO TRANSFER SWITCH LOCATED IN THE SAME ELECTRICAL

ROOM AS MAIN SWITCHGEAR.

3. CONTRACTOR TO PROVIDE NEW 2" CONDUIT FROM GENERATOR LOCATION TO NEW TRANSFER SWITCH LOCATION FOR CONTROL WIRING. COORDINATE TRENCHING/BORING OF CONDUIT WITH OWNERSHIP

PRIOR TO ROUGH-IN.

4. EXTEND CONDUIT AND ROUTE NEW FEEDERS AND CONTROL WIRING FROM TO FINAL CIRCUIT

BREAKER/CONTROLS TERMINATION BLOCK WITHIN GENERATOR ENCLOSURE.

5. LOCATION OF 400/3 ENCLOSED CIRCUIT BREAKER IN NEMA R3 ENCLOSURE UNITSTRUT MOUNTED AT 48" A.F.G. ADJACENT TO EXISTING GENERATOR & EXISTING 4" CONDUIT. REFER TO NOTE ON ONE-LINE

DIAGRAM E003. FIELD ADJUST LOCATION TO MAINTAIN GENERATOR ACCESS.

T F

T C

M

NEW 800 AMP

NEMA 3R SERVICE

DISCONNECT

1 EXISTING CUMMINS

DIESEL GENERATOR

EXISTING SPARE

4" CONDUIT

B P

DIRECTIONAL BORE 4"

CONDUIT, MINIMUM OF 24"

BELOW PARKING LOT

PAVING FOR FEEDER.

DIRECTIONAL BORE 2"

CONDUIT, MINIMUM OF 24"

BELOW PARKING LOT

PAVING FOR CONTROLS.

TO ATS,

RE: E101

DEPTH OF CONDUIT BORE

WILL BE DEEPER IN THIS

AREA REFER TO SHEET

E102 FOR CONDUIT

ELEVATION DIAGRAM.

EXISTING UTILITY

TRANSFORMER

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E100

ELECTRICAL

SITE PLAN

AutoCAD SHX Text E102

AutoCAD SHX Text

DRAWING NOTES

1. RELOCATE EXISTING FIRE ALARM DOCUMENTS CABINET TO OTHER SIDE OF FIRE ALARM

CONTROL PANEL TO ALLOW ROOM FOR NEW AUTOMATIC TRANSFER SWITCH.

2. FIELD COORDINATE WALL PENETRATION LOCATIONS AND PULL BOX LOCATIONS ON EXTERIOR WALL.

COORDINATE ROUTING OF CONDUIT FROM PULL BOXES ABOVE EXISTING PANELS TO NEW ATS

LOCATION.

1/8" = 1'-0"SCALE:

LOWER LEVEL AREA 2 POWER PLAN

N.T.S.SCALE:

KEY PLAN

ATS

T C

M

NEW 800A SERVICE DISCONNECT

ON UNISTRUT RACK RE: DIAGRAM

THIS SHEET.

SURFACE MOUNTED CONDUIT ROUTED ABOVE

DOOR ON UNISRUT RACK. STANDOFF WALL TO

AVOID STRUCTURAL COLUMN AND EXTERNAL

STORMWATER DOWNSPOUT. RE PHOTOS THIS

SHEET & CONDUIT ELEVATION SHEET E102. N.T.S.SCALE:

PROPOSED SERVICE DISCONNECT CONFIGURATION

EXTEND DOWNSPOUT AND SPLASHBLOCK

PAST NEW ELECTRICAL SERVICE

DISCONNECT.

PROPOSED SURFACE MOUNTED CONDUIT ALONG EXTERIOR WALL

ROUTE CONDUIT TO AVOID DOWNSPOUTS AND PLATFORM

SUPPORT BEAMS. ROUTE UNDER PLATFORM WALKWAY TO OTHER

SIDE OF DOOR. PENETRATE WALL ABOVE ELECTRICAL PANELS

AND EXTEND TO NEW AUTOMATIC TRANSFER SWITCH LOCATION.

NEMA 3R PULLBOXES SURFACE MOUNTED.

REFER TO CONDUIT ELEVATION SHEET E102.

EXISTING CT CABINET

& METER

CONDUIT TO JOG STANDING OFF WALL TO AVOID

EXISTING STEEL BEAM, ROUTE UNDER PLATFORM,

ABOVE DOOR.

CONDUIT TO JOG STANDING OFF WALL TO AVOID

EXISTING STEEL BEAM, PENETRATE ALUMINUM

SIDING ON RIGHT SIDE OF WALKWAY AND CONTINUE

ON TO PULLBOX ON OUTSIDE WALL OF ELECTRICAL

ROOM.

CONDUIT FROM SERVICE DISCONNECT MOUNTED

TO WALL ABOVE EXISTING CONDENSING UNITS.

ROUTE CONDUIT TO AVOID DOWNSPOUTS AND

PLATFORM SUPPORT BEAMS.

N.T.S.SCALE:

PROPOSED CONDUIT ROUTING

DOCUMENT CABINET(RL)

GENERAL NOTES

PHOTOS AND ROUTING/MOUNTING DIAGRAMS PROVIDED TO SHOW DESIGN INTENT. CONTRACTOR SHALL VISIT SITE TO REVIEW EXISTING CONDITIONS AS THEY MAY VARY FROM WHAT IS DEPECTED. FIELD VERIFY ALL SIZES AND DIMENSIONS, AND EXISTING GRADING AND ELEVATIONS. CALL 811 AND HAVE EXISTING UTILITIES LOCATED AND MARKED PRIOR TO DIGGING. COORDINATE FINAL ROUTING AND BUILDING PENETRATIONS WITH OWNER PRIOR TO ROUGH-IN. COORDINATE POWER OUTAGES WITH OWNER 14 DAYS IN

ADVANCE.

UNISTRUT ANCHOR

BASEPLATE

UNISTRUT MOUNTING

RACK

800A SERVICE

DISCONNECT

NONESCALE:

DISCONNECT MOUNTING DIAGRAM

CONCONCRETE

FOOTER

CONDUIT TO EXISTING

CT CABINET

GRADE

CONDUIT TO NEW

ATS IN ELECTRICAL

ROOM

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E101

ENLARGED POWER PLAN

GENERAL NOTES

CONDUIT ROUTING ELEVATION PROVIDED TO SHOW DESIGN INTENT. ARCHITECTURAL ELEVATION IS FROM ORIGINAL CONSTRUCTION DOCUMENTS AND COULD VARY FROM EXISTING FIELD CONDITIONS. CONTRACTOR SHALL VISIT SITE TO REVIEW EXISTING CONDITIONS AS THEY MAY VARY FROM WHAT IS DEPECTED. FIELD VERIFY ALL SIZES AND DIMENSIONS, AND EXISTING GRADING AND ELEVATIONS. CALL 811 AND HAVE EXISTING UTILITIES LOCATED AND MARKED PRIOR TO DIGGING. COORDINATE FINAL ROUTING AND BUILDING PENETRATIONS WITH OWNER PRIOR TO ROUGH-IN. COORDINATE POWER OUTAGES WITH OWNER 14 DAYS IN

ADVANCE.

N.T.S.SCALE:

CONDUIT ROUTING ELEVATION

N.T.S.SCALE:

KEY PLAN

SERVICE DISCONNECT

ON UNISTRUT. RE: E101

EXISTING CONDENSORS

EXISTING LIGHT

EXTERIOR PULLBOXES

COORDINATE EXACT LOCATIONS

AND PENETRATIONS WITH EXISTING

EQUIPMENT AND CONDUIT IN THE

ELECTRICAL ROOM.

ROUTE CONDUIT AROUND

DRAIN PIPE

ROUTE CONDUIT SUPPORT

BEAMS

CUT SMALL OPENING IN EXISTING

METAL SIDING TO ROUTE CONDUIT

THROUGH

POWER AND CONTROLS CONDUIT

FROM GENERATOR BORED

UNDERGROUND. RE: ELECTRICAL

SITE PLAN E100.

DESIGNED BY: CHECKED BY:

PROJECT #:

ISSUE DATE#

PARK COUNTY

OFFICE BUILDING

STANDBY POWER

24191

856 CASTELLO AVE

FAIRPLAY, CO 80440

RCC RCC

FOR BIDDING 10-30-241

E102

CONDUIT ROUTING

ELEVATION

Sheets and Views
24191 - E001-E001
24191 - E002-E002
24191 - E003-E003
24191 - E004-E004
24191 - E100-E100
24191 - E101-E101
24191 - E102-E102