This is a Statement of Work for the modernization of crash alarm systems across three Army airfields operated by Fort Bragg's Directorate of Plans, Training, Mobilization, and Security (DPTMS). The effort encompasses the procurement, installation, and ongoing maintenance of a modernized Primary Crash Alarm System (PCAS), Secondary Crash Alarm System (SCAS), and Airfield Crash Alarm Emergency System to replace the aging FORUM Alert II system currently in place. The three airfields affected are Simmons Army Airfield (SAAF), Mackall Army Airfield (MAAF), and Pope Army Airfield (PAAF), all located in North Carolina.

All work and technical deliverables must conform strictly to the specifications outlined in Section 11.0 (Technical Reference) of the Statement of Work. The contracting action is being conducted by the Department of the Army Materiel Command Mission and Installation Contracting Command. This is a pre-solicitation sources sought notice, indicating that the government is gathering information about contractor capabilities prior to formal competitive solicitation. The specific technical requirements, performance standards, delivery schedules, pricing terms, and other contract details are contained within Section 11.0 of the referenced Statement of Work document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States Army Garrison Directorate of Plans, Training, Mobilization, and Security (DPTMS) Airfield Crash Alarm System Replacement Contract Draft Statement of Work

1.0. INTRODUCTION: The Directorate of Plans, Training, Mobilization, and Security (DPTMS) at Fort Bragg, NC requires the procurement, installation, and ongoing maintenance of a modernized Primary Crash Alarm System (PCAS) / Secondary Crash Alarm System (SCAS) / Airfield Crash Alarm Emergency System. This effort will modernize the aging FORUM Alert II system across three airfields: Simmons Army Airfield (SAAF), Mackall Army Airfield (MAAF), and Pope Army Airfield (PAAF). All work and technical deliverables shall conform in strict accordance with the specifications set forth in Section 11.0 (Technical Reference).

2.0. REQUIRED DELIVERY DATE: Work is to commence within thirty (30) calendar days after contract award. Delivery and Installation must be completed at SAAF, MAAF and PAAF within ninety (90) calendar days after work starts.

3.0. HOURS OF OPERATION: Work may occur between the hours of 7:00 am and 4:30 pm Monday through Friday except on Federal Holidays. The recognized federal holidays include:

New Year’s DayLabor Day
Martin Luther King Jr.’s BirthdayColumbus Day
Washington’s BirthdayVeteran’s Day
Memorial DayThanksgiving Day
Juneteenth DayChristmas Day

Independence Day

4.0 SCOPE: Except for government-furnished property and services explicitly identified herein, the contractor shall provide all personnel, equipment, supplies, transportation, tools, materials, supervision, ongoing network equipment management, routine and emergency maintenance of the system, and other associated items required to execute turnkey equipment installation and support services under this contract. This procurement modernizes the existing FORUM Alert II architecture in accordance with Section 11.0 (Technical References).

4.1 Core System Architecture & Primary Facilities: The Contractor shall install, integrate, and configure a fully operational Crash Alarm Emergency Conferencing System across six (6) primary operational facilities: SAAF Air Traffic Control (ATC) Tower, Simmons Base Operations, MAAF ATC Tower, Mackall Base Operations, PAAF ATC Tower, and Pope Base Operations. Each core system shall deliver integrated primary and secondary emergency conferencing capabilities, comprising: Centralized Crash Alert Voice over Internet Protocol (VoIP) Emergency Notification System (ENS) Server architecture 1U; Uninterruptible Power Supply (UPS), rack-mounted 1U; User interface consoles / Touchscreen Graphical User Interfaces (GUIs) at all six (6) operational facilities; Enterprise fiber network switches; Power-over-Ethernet (PoE) switches deployed to support all required peripheral endpoints; VoIP conference telephones and VoIP Push-to-Talk (PTT) handsets at designated peripheral stations; and Black patch equipment racks or secure wall-mounted equipment cabinets, sized and installed as site conditions dictate. Detailed technical specifications are outlined in Attachment I, Salient Characteristics.

4.2 Peripheral Endpoints & Device Placement: The Contractor shall furnish, position, configure, and verify operational readiness of thirty-seven (37) peripheral VoIP phone stations across the installation, distributed as follows: SAAF - Fifteen (15) locations; MAAF- Eleven (11) locations; PAAF- Eleven (11) locations. All peripheral equipment and station drops shall be placed in designated operating areas and maintained in full working order in compliance with Federal Aviation Administration (FAA) criteria, applicable Army Regulations, Airfield Navigational Aids (NAVAIDS) Maintenance requirements, and the Network Enterprise Center (NEC) regulatory requirements.

4.3 Telecommunications Cabling & Infrastructure Pathway: The Contractor shall be responsible for all premise wiring, data pathways, and patch cabling required for complete end-to-end connectivity except for NEC provided pathways between buildings (peripheral location specific). Station Drops: Provide and route custom-length Category 6/6A patch cables from designated PoE switches to VoIP phone endpoints, customized to building architectural layouts and communications room entry points. Backbone & VoIP ENS Server Integration: Where existing infrastructure is insufficient, the Contractor shall install new horizontal and riser cabling between server rooms, intermediate distribution frames (IDFs), PoE network switches, and peripheral endpoint locations to establish complete, certified network drops. All cabling work shall be labeled, tested, certified, and routed through existing cable trays or new surface raceways conforming to NEC and base telecommunications standards.

5.0. SPECIFIC TASKS:

5.1. GENERAL: The contractor shall provide all personnel, supervision, equipment, tools, materials, transportation, required certifications, specialized training and incidental services necessary to install, test, inspect, maintain and repair all airfield crash alert systems equipment as specified in this Statement of Work (SOW). The Contractor shall perform all work in accordance with applicable manufacturer instructions, installation manuals, approved drawings, site-specific procedures, applicable safety requirements and Government technical requirements. The Contractor shall coordinate all work affecting airfield operations, emergency-response communications, facility access, electrical service, or network connectivity with the Contracting Officer’s Representative (COR) or designated Government representative before beginning work.

5.2. INTEROPERABILITY, CERTIFICATION AND COMPLIANCE

5.2.1. The Airfield Crash Alert System shall be capable of interoperating with the Government’s AudioCodes Mediant 800C1B VESTA System (Software Version 8.5) 911 program and associated emergency communications infrastructure. The Contractor shall provide, install, configure, test and maintain all hardware, software, interfaces, licenses and ancillary equipment necessary to support this interoperability.

5.2.2. The Airfield Crash Alert System shall be capable of interoperating with the National Airspace (NAS) Voice Recording (NVR) System using a digital to analog converter. The recording of all audio traffic of the ENS is required per FAA and DoW regulation.

5.2.3. The contractor shall provide documented evidence that all proposed Airfield Crash Alert System equipment, software, interfaces and associated components requiring Joint Interoperability Test Command (JITC) certification are currently JITC certified for the intended operational use.

5.2.4. The contractor shall ensure that the VoIP ENS system is JITC certified and part of the Defense Information Systems Agency Risk Management Executive (DISA RME) Vendor Security Technical Implementation Guide (STIG) program to maintain Department of War (DoW) cybersecurity compliance.

5.2.5. The contractor shall provide documented evidence that all applicable products are listed on the current Approved Products List (APL) at the time of proposal submission, installation, replacement and system acceptance.

5.2.6. The contractor shall ensure all DoW cybersecurity requirements, Cybersecurity Maturity Model Certification (CMMC) framework and the required CMMC Certification levels are met.

5.3. INSTALLATION AND CONFIGURATION

5.3.1. The contractor shall remove and properly dispose of existing equipment and cabling identified for replacement.

5.3.2. The contractor shall install the crash alarm system control panels, alarm stations, annunciators, communication interfaces, audible alarms, visual indicators, wiring, conduit, junction boxes, power supplies and associated mounting hardware at each peripheral location at MAAF, PAAF, and SAAF.

5.3.3. The contractor shall install equipment in accordance with approved drawings, manufacturer recommendations, applicable electrical standards and Fort Bragg NEC requirements.

5.3.4. The contractor shall label all installed equipment, cabinets, circuits, cables and alarm points using Government-approved nomenclature.

5.3.5. The contractor shall configure alarm zones, activation points, notification sequences, user interfaces, communications pathways and backup functions in accordance with Government-approved operational requirements.

5.3.6. The contractor shall configure the VoIP ENS server to be capable of providing customizable ring tones and variable ring cadences.

5.3.7. The contractor shall configure the VoIP ENS server to have built-in recording manager capability to record all conferences.

5.3.8. The contractor shall ensure that the VoIP ENS server must have high security login policies that are compatible with all the DoW Information Assurance standards.

5.3.9. The contractor shall ensure that the VoIP ENS server must have two-factor Public Key Infrastructure (PKI) based authentication, plus password entry, for an additional authentication factor beyond PKI.

5.3.10. The contractor shall ensure that the VoIP ENS server must have blast notification initiation capability to allow pre-recorded audio announcements (i.e. severe weather warnings) to be broadcast over the Base PA system or other visual notification modes if needed.

5.3.11. The contractor shall ensure that the VoIP ENS server must have softswitch functionality for point-to-point calling between participants.

5.3.12. The contractor shall ensure that the VoIP ENS server must have any number of outbound web service requests when an emergency conference is initiated.

5.3.13. The contractor shall ensure that the VoIP ENS server must have inbound web service initiation of emergency conferences.

5.3.14. The contractor shall ensure that the VoIP ENS server must have participant business hour/off hour feature capability where participants can have different lists of contact phone numbers at different times of the day and different days of the week.

5.3.15. The contractor shall ensure that the VoIP ENS server must have parallel and serial hunt feature capability where, for a participant, multiple contact phone numbers can be tried simultaneously or serially, with programmable retry policy.

5.3.16. The contractor shall configure the VoIP ENS Solution in a redundant architecture with primary and secondary backup servers, and the servers must be configured with redundant internal components. The ENS VoIP system must be capable of supporting multiple emergency notification calls simultaneously without disrupting each other.

5.3.17. The contractor shall configure the redundant VoIP ENS servers to automatically fail-over to the backup server. In the event of a hardware or network failure and the primary unit becomes unavailable the VoIP ENS system will automatically switch over to the redundant standby VoIP ENS server without any intervention by the initiator or system administrator. All end devices must be continually registered to both primary and backup servers.

5.3.18. The contractor shall configure the VoIP ENS server to have an integrated Session Initiation Protocol (SIP) registrar for locally registered SIP users, plus SIP trunking capability. SIP (RFC 3261) must use the register request method to bind a user’s address-of-record to their current physical network contact address. All peripheral VoIP phones (15 at SAAF, 11 at MAAF, 11 at PAAF) and all six (6) touchscreen GUIs must establish and refresh active bindings with the centralized server SIP Registrar.

5.3.19. The contractor shall ensure all endpoints maintain dual registration or automated fail-over profiles between the primary and secondary Servers. If the primary server loses connectivity, endpoints seamlessly re-register with the redundant server within three (3) seconds.

5.3.20. The contractor shall configure SIP registration expiration intervals (Expires header) to not exceed one hundred twenty (120) seconds to verify continuous endpoint connectivity. The system shall incorporate automated, bidirectional keep-alive polling (via SIP OPTIONS or RFC-compliant ping mechanism) occurring at intervals no greater than fifteen (15) seconds. If a peripheral phone fails three (3) consecutive registration or heartbeat cycles, the system shall visually and audibly alert the six (6) Touchscreen GUI operator consoles, specifically identifying the disconnected airfield and facility drop IAW the FAA ARFF in section 11.

5.3.21. The contractor shall configure the UPS to send shutdown signals to the server should the UPS battery life fall below a pre-determined level so the VoIP ENS server can gracefully power off. The VoIP ENS server also must have power recovery capability and automatically restart itself when power is restored.

5.3.22. The contractor shall restore all affected walls, ceilings, floors, equipment racks and work areas to a clean and serviceable condition following installation activities.

5.3.23. The contractor shall maintain continuity of critical crash-alert capability to the maximum extent practicable during installation/replacement actions. When an outage is required, the Contractor shall coordinate the outage to the COR or designated Government representative and provide temporary measures approved by the Government.

5.4. FUNCTIONAL TESTING

5.4.1. The contractor shall work closely with Fort Bragg Air Traffic Control Navigation Aids (NAVAIDS) Personnel and NEC to coordinate complete on-site system assessment and testing to minimize impact on other mission support requirements.

5.4.2. The contractor shall conduct functional testing following installation, repair, configuration changes or scheduled maintenance.

5.4.3. The contractor shall test SIP registration expiration intervals (Expires header) to ensure they do not exceed one hundred twenty (120) seconds to verify continuous endpoint connectivity.

5.4.4. The contractor shall ensure that the system incorporates bidirectional keep-alive polling occurring at intervals no greater than fifteen (15) seconds. If a peripheral phone fails three (3) consecutive registration or heartbeat cycles, the system shall visually and audibly alert the six (6) Touchscreen GUI operator consoles, specifically identifying the disconnected airfield and facility drop.

5.4.5. The contractor shall test and verify the activation of each crash-alert initiation point.

5.4.6. The contractor shall test and verify receipt and display of alarm indications at designated control, dispatch, fire, emergency operations and other Government-designated locations.

5.4.7. The contractor shall test and verify proper operation of audible and visual notification devices.

5.4.8. The contractor shall test to ensure Line Supervision Distinction is present, which forbids silent failure on all airfield crash lines.

5.4.9. The contractor shall test and verify proper routing and transmission of alarm signals through primary and secondary communications paths.

5.4.10. The contractor shall test and verify functionality of backup power, UPS, batteries and automatic transfer of fail-over capabilities. Ensure UPS communication with server, and that power recovery capability and automatic restart after power restoration is operational.

5.4.11. The contractor shall test and verify proper operation of supervisory, trouble and fault indicators.

5.4.12. The contractor shall test and verify the restoration of the system to normal operating condition following alarm activation.

5.4.13. The contractor shall test and verify the interoperability with associated communications, fire protection, emergency notification or monitoring systems when applicable.

5.4.14. The contractor shall coordinate operational testing with the COR or designated Government representative to avoid unnecessary disruption to flying operations, emergency services, and installation activities. The Contractor shall immediately report failed tests, degraded capabilities or unsafe conditions to the COR or designated Government representative.

5.4.15. The contractor shall deliver a complete SIP Dialing & Registration Plan and a Network Acceptance Test Plan (ATP) validating line-break alarms prior to final government acceptance.

5.5. PREVENTATIVE MAINTENANCE

5.5.1. The contractor shall provide parts and labor under 3-year annual support service from the completion of installation and acceptance.

5.5.2. The contractor shall provide onsite technical assistance for issues that cannot be rectified over the phone.

5.5.3. The contractor shall perform preventative maintenance at the manufacturer’s guidance, or the Government approved maintenance schedule.

5.5.3.1. During preventative maintenance, the Contractor shall inspect all crash alert system equipment for physical damage, corrosion, loose connections, water intrusion, contamination and signs of deterioration.

5.5.3.2. The contractor shall clean control panels, cabinets, annunciators, alarm stations and related components.

5.5.3.3. The contractor shall inspect cables, conduit, connectors, terminations, grounding and surge-protection devices.

5.5.3.4. The contractor shall verify the condition and operation of power supplies, batteries, UPS units, chargers and backup power connections.

5.5.3.5. The contractor shall test alarm activation stations, annunciators, audible alarms, visual indicators and communication interfaces.

5.5.3.6. The contractor shall verify software, firmware, configuration settings, time synchronization and event logging.

5.5.3.7. The contractor shall replace consumable items and minor components as required.

5.5.3.8. The contractor shall provide unlimited telephonic technical support to assist local maintenance technicians with troubleshooting problems with the systems.

5.5.3.9. The contractor shall record all maintenance actions, test results, deficiencies, corrective action and parts used. The Contractors shall also identify components approaching end of service life and recommend replacement before failure affects operational availability. A copy of the report shall be provided to the COR or the designated Government representative.

5.6. CORRECTIVE MAINTENANCE AND EMERGENCY SERVICE

5.6.1. The contractor shall provide corrective maintenance for system failures, degraded performance, damage and deficiencies identified by the Government or discovered during scheduled maintenance.

5.6.1.1. Corrective maintenance tasks shall include diagnosing system faults and isolating failed components; repairing or replacing defective equipment, wiring, power supplies, batteries, communications interfaces, alarm devices and related components; restoring the crash alarm system to full operational capability and conducting post-repair functional testing.

5.6.2. The contractor shall document the cause of failure, corrective action taken, parts used, test results and any remaining limitations. A copy of the report shall be provided to the COR or the designated Government representative.

5.6.3. For emergency service calls involving complete or partial loss of crash-alert capability, the contractor shall respond within 1 hour via email or telephone call. If the system cannot be immediately restored, the contractor shall provide interim measures and an estimated time to repair.

5.7. SYSTEM DOCUMENTATION AND RECORDS

5.7.1. The contractor shall maintain current and complete documentation for all work performed under this SOW.

5.7.1.1. Documentation shall include service tickets, maintenance logs, inspection and test reports, installation records, equipment serial numbers, configuration records including alarm-point assignments and communication pathways, drawings, cable schedules, panel layouts and as-built documentation for system modification, list of replaced parts and materials, record of system deficiencies, corrective actions and unresolved issues, manufacture warranty information.

5.8. TRAINING

5.8.1. The contractor shall provide familiarization or operator-level training for designated Government personnel.

5.8.1.1. The training shall address normal operation of crash alert activation and notification equipment; recognition of system alarms, trouble indications, and fault conditions; basic user actions following activation, malfunction or loss of power; procedures for reporting system deficiencies.

5.8.2. The contractor shall provide training materials such as user manuals and system drawings.

6.0 GOVERNMENT FURNISHED SERVICES, FACILITIES and UTILITIES

6.1 The Network Enterprise Center (NEC): Fort Bragg NEC is responsible for the establishment, management, and maintenance of the network infrastructure providing a secure, reliable, and isolated communication path. Providing a Layer 2 connection as a Government-Furnished Service (GFS) from the towers at Simmons Army Airfield, Mackall Army Airfield, and Pope Army Airfield. Extending these connections to multiple locations across each respective airfield to support the crash phone system endpoints. Salient characteristics and parts list are Attachment I of this SOW.

6.2 Air Traffic Control Navigation Aids (NAVAIDs) Branch: DPTMS Airfield Division NAVAIDS Branch is responsible for providing housing that is physically separated from the existing Ft. Bragg NEC network equipment to maintain system integrity and isolation. Existing rack space at all locations will be provided as Government-Furnished Facilities (GFF) except for Pope Base Operations.

7.0 QUALITY ASSURANCE

7.1 The NAVAIDS Chief, Mr. Andrew Connell, is the Government’s technical and final Quality Assurance Evaluator. A projection completion inspection will be conducted jointly between the Government and the Contractor upon completion of work. Receipt of the signed Quality Assurance inspection checklist validates on-site contract completion. The COR will not approve the invoice submission in Wide Area Workflow (WAWF) until this checklist is finalized.

8.0 OCCUPATIONAL SAFETY AND HEALTH ACT AND ENVIRONMENT

8.1 The contractor shall perform work in a safe manner as required by Occupational Safety and Health Act (OSHA) and Health Requirements. The Contractor shall provide a verbal notification to the KO as soon as possible of each occurrence of damage to Government property or an accident resulting in death, injury, occupational disease or adverse environmental impact.

8.2 The contractor shall comply with all local, state and Federal environmental and occupational safety laws, rules and regulations, and compliance with the requirements of the contract shall be immediately brough to the attention of the KO and COR for final resolution. The Contractor shall notify the KO and COR in writing in addition to any verbal notification of such conflicts. The Contractor shall be liable for all fines, penalties and costs which result from violation of or failure to comply with all such local state or Federal laws, rule and regulations. All unsafe acts or conditions fostered by the Contractor or Contractor personnel may be grounds for the KO or COR, to halt all Contractor performance with a commensurate deduction of monies due the Contractor until such unsafe conditions are corrected. The Contractor shall take due caution not to endanger personnel during performance of this contract. Upon discovery of any hazard such as, but not limited to, fire the Contractor shall immediately notify the COR.

9.0 WARRANTY

9.1 The contractor shall guarantee all work performed will be free from defects in workmanship and materials used for a period of three (3) years. Warranty repairs shall be made at the contractor’s expense within one week of being notified of a problem. Differences as to whether the repair shall be covered by warranty will originate with COR and be decided upon by the Contracting Officer (KO).

10.0 INSTALLATION AND FACILITY ACCESS

10.1 Contractor personnel shall comply with all personal identity verification requirements as directed by DoW, Headquarter Department of Army (HQDA) and/or local policy.

10.2 Contractor personnel shall have a valid form of Government issued identification which satisfies the requirement to gain entry onto Fort Bragg. This requirement shall be met for the life of the contract.

10.3 Contractor personnel shall comply with applicable installation, facility, area commander installation and facility access and local security policies and procedures. U.S. Army Fort Bragg – Physical Security Access Control. Personnel shall be aware of and comply with the requirements associated with Installation Access Control (IAC). The Government is not liable for any costs associated with performance delays due solely to a firm’s failure to comply with Installation Access Control System (IACS) processing requirements.

10.4 For contractors that do not require CAC but require access to a DoW facility or installation, contractors and all associated sub-contractors’ employees shall be screened using the National Crime Information Center Interstate Identification Index (NCIC-III) and Terrorist Screening Database (TSDB) (Army Directive 2014-05/AQR 190-13).

10.5 In addition, the contractor shall provide the KO, via the COR, with an Initial Installation Pass Log within three (3) calendar days after contract award. At a minimum the log shall contain the following information: name, address, telephone number, contract number and contracting agency. The log shall be updated as employees are added or removed; submitted within five (5) days after any changes occur, and available at any time upon request by the KO or COR.

10.6 The contractor shall collect installation access passes the same day employment of an individual has expired or has been terminated and shall return them to the issuing office within three (3) business days.

10.7 Upon termination or cancellation of the contract, the contractor shall collect all outstanding installation access passes and return them to the issuing office with three (3) business days.

10.8 In addition to the changes otherwise authorized by the changes clause of this contract, should the Force Protection Condition (FPCON) at any individual facility or installation change, the Government may require changes in contractor security matters or process.

11.0Technical References:
11.1Fort Bragg Network Enterprise Center (NEC) Installation Design Criteria (IDC), July 2024
11.2UFC 3-580-01, Telecommunications Interior Infrastructure Planning and Design
11.3ANSI/TIA-569-E, Telecommunications Pathways and Spaces
11.4ANSI /TIA-607-E, Telecommunications Grounding and Bonding
11.5USAISEC Telecommunications Outside Planning and Design Criteria
11.6AR 95-2 Air Traffic Control, Airfield/Heliport, and Airspace Operations
11.7ATP: 3-04.16 Airfield Operations
11.8AC 150/5210-7E Aircraft Rescue and Fire Fighting (ARFF) Communications
11.9FAA Order JO 7210.3EE Facility Operation and Administration

11.10 TC: 3-04.15 Air Traffic Control Facility Operations, Training, Maintenance, and Standardization

ATTACHMENT I: SALIENT CHARACTERISTICS

Description, Location & Salient Characteristics
Quantity
VoIP Emergency Notification System, 20 SIP Sessions; ConsortAlert software on 1U Dell server with redundant hardware / Equal to or better; 1 (MAAF)
1
VoIP Emergency Notification System: 30 SIP Sessions, ConsortAlert software on 1U Dell server with redundant hardware / Equal to or better; 1 (PAAF, 1 SAAF)
2
Backup VoIP Emergency Notification System: 20 SIP Sessions; ConsortAlert software on 1U Dell server with redundant hardware / Equal to or better; 1 (MAAF)
1
Rack Mount UPS w/ integrated PDU: Rack mount UPS configured for graceful shutdown of VoIP ENS server before DC power drain / Equal to or better 1 (MAAF), 1 (PAAF), 1 (SAAF)
3
User Interface Console/GUI 15.6” (must be touchscreen): All-in-One ConsortAlert console with a “One Touch” GUI / Equal to or better; 2 (MAAF), 2 (PAAF), 2 (SAAF)
6
VoIP Phone: Cisco CP-8841 with MPP / Equal to or better; 11 (MAAF), 11 (PAAF), 15 (SAAF)
37
VoIP PPT handset: Cisco PTT Handset / Equal to or better; 11 (MAAF), 11 (PAAF), 15 (SAAF)
37
PoE Switch: Cisco C9200CX-8P-2X2G-E / Equal to or better; 8 (MAAF), 9 (PAAF), 11 (SAAF)
28
Fiber Switch: Extreme Networks 5420F-24S-4XE / Equal to or better 1 (MAAF), 1 (PAAF), 1 (SAAF)
3
SFP Fiber Module with duplex LC – must be Cisco compliant and TAA Compliant, Cisco / Equal to or better: 16 (MAAF), 18 (PAAF), 22 (SAAF)
56
Spare Kit must include 1 PoE switch, 1 VoIP phone w PTT, 2 SFP, 1 Strobe: ConsortAlert / Equal to or better; 1 (MAAF), 1 (PAAF), 1 (SAAF)
3
Mounting hardware, shelves and cable management: Cabling must be black in color for specific NEC identification, custom-length Category 6/6A patch cables. Shelving must be 1U / equal to or better; 1 (MAAF), 1 (PAAF), 1 (SAAF)
3
Installation must be DoD/JITC certified and must be trained ConsortAlert technicians: Equal to or better; 1 (MAAF), 1 (PAAF), 1 (SAAF)
3
3 Year 24/7 Support Maintenance: Equal to or better; 1 (MAAF), 1 (PAAF), 1 (SAAF)
3

ATTACHMENT 2: ACRONYMS

APL – Approved Products List AR – Army Regulation ATC – Air Traffic Control ATP – Acceptance Test Plan CAC – Common Access Card CMMC – Cybersecurity Maturity Model Certification COR – Contracting Officer’s Representative DISA RME – Defense Information Systems Agency Risk Management Executive DPTMS – Directorate of Plans, Training, Mobilization and Security DoW – Department of War ENS – Emergency Notification System FAA – Federal Aviation Administration FPCON – Force Protection Condition GFF – Government Furnished Facilities GFS – Government Furnished Service GUI – Graphical User Interfaces HQDA – Headquarter Department of Army IAC – Installation Access Control IACS – Installation Access Control System IDF – Intermediate Distribution Frames JITC – Joint Operability Test Command KO – Contracting Officer MAAF – Mackall Army Airfield NAVAIDS – Navigational Aids NC – North Carolina NEC – Network Enterprise Center NICI-III – National Crime Information Center Interstate Identification Index OSHA – Occupational Safety and Health Act PA – Public Address PAAF – Pope Army Airfield PCAS – Primary Crash Alarm System PKI – Public Key Infrastructure PoE – Power-over-Ethernet PTT – Push-to-Talk SAAF – Simmons Army Airfield SCAS – Secondary Crash Alarm System SIP – Session Initiation Protocol SOW – Statement of Work STIG – Security Technical Implementation Guides TSDB – Terrorist Screening Database UPS – Uninterruptible Power Supply VOIP – Voice Over Internet Protocol WAWF – Wide Area Workflow

File details come from the government source that posted it. Updated .