This is a Salient Characteristics specification document for a mobile water treatment trailer requirement with a place of performance at WBAMC and a scheduled delivery date of 5/7/2026. The requirement is for one water treatment trailer designed to support mobile sterilization units by providing separate means of treating supply water to meet specific temperature and quality standards for cold water, hot water, and reverse osmosis (RO) final rinse applications.

The trailer must be a complete turnkey system capable of fitting inside a 52-foot tractor trailer with wood flooring and include the following major components: a 60 gpm RO unit with 1a membranes and eight replacement filters; a 2,000-gallon water storage tank; a multibag filter housing with 40-inch filters rated at 0.1 micron absolute (100 filters) and 0.5 micron absolute (100 filters); a 7.5 HP vertical distribution pump with a 10 HP 460V variable frequency drive; a 44-gallon stainless steel bladder tank; a 1-inch globe valve for water blending; water quality monitoring equipment including a GF Signet 9950 TDS meter; a water softening system; four 120V electric heaters; two 120-gallon electric water heaters maintaining 120-140 degrees Fahrenheit; and a 2 gpm recirculating pump. The contractor must provide site visit services to assess existing utilities and available space, complete turnkey installation with interconnection of all equipment to sterilization units, a maintenance plan with on-call personnel support, and monthly water testing. The supplied water must meet strict quality parameters including sediment filtration of 0-5 microns, specific hardness, dissolved solids, alkalinity, pH, conductivity, silica, chloride, and trace metal concentrations for both cold and hot water supplies, with water maintained colorless in appearance.

View the file

Other files

File Type Posted
Sources Sought Notice _Sterilization Units WBAMC.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet3

Salient Characteristics
Palce of Performance: WBAMC Loading DockDate:5/7/2026
Requirement POC:Quantity: 1
Description: Water treatment TrailerRP#:
Summary: Mobile Sterilization trailers will need a seperate means of treating their supply water do to the special requirements needed for the cold water, hot water, and RO for final rinse.
#Description of Minimum Requirement
and/or ObjectiveMinimum RequirementObjective
160 gpm RO unit160 gpm RO unit. Permeate should be able to drain to nearby trench drain. Use
1aRO membranes8Replacement RO Filters
22000 Gal Water storage tank12000 gal Water storage tank
3Chemical Injection Quill1Chemical Injection Quill
4Multibag Filter Housing1Housing to use 40 inch filters for prefiltering water of sediment and particles.
4aBag filters100.1 Micron Absolute rating
4bFilters100.5 micron Absolute 40-inch filters
57.5 HP Water Pump17.5 HP vertical distribution pump
6VFD110 HP 460 V
7Bladder tank144 Gallon stainless steel vessel w/ bladder
8Globe valve11" for blending water to meet Water quality requirement of sterilization equipment.
9TDS meter1GF Signet 9950 to measure TDS in mg/l
10Water softner system1Water softner to soften water going to RO and water Heaters.
11Electric Heaters4120 v electric heaters
12120 Gal Electric Water Heaters2Hot water supply. Must be able to keep the hot water between 120-140 degrees Faranheit.
132 gpm Recirculating pump1For recirculating hot water
14ContainmentN/AEquipment should fit inside of a 52' tractor trailer with a wood flooring so holes can be made for routing pipe.
15MaintenanceN/AMaintenance plan should be provided to maintain the individual equipment and the structure. Maintence plan to include on-call personel.
16InstallationN/AMust include turnkey installation of equipment. Must include connection of equiopment to each other and to the mobile sterilization unit(s).
17Site VisitN/AMust include site visit to see availability of exsisting utilites and availble space.
18Monthly water testingN/AMonthly water test to test cold water and hot water supply.
18aMin Sediment FiltrationMIN-MAXCold Water: 0-5 Micron

Hot Water: 0-5 Micron 18b Total Hardness as CaCo3 MIN-MAX Cold Water: 50-170 ppm CaCo3 Hot Water: 0-17 ppm CaCo3 18c Total Dissovled Solids MIN-MAX Cold Water: 100-170 ppm Hot Water: 50-250 ppm 18d Total Alkalinity as CaCo3 MIN-MAX Cold Water: 70-180 ppm Hot Water: 50-180 ppm 18e pH MIN-MAX Cold Water: 6.5-8.5 Hot Water: 6.5-9.5 18f Conductivity MIN-MAX Cold Water: 0-1000 umhos/cm Hot Water: 40-500 umhos/cm 18g Total Silica MIN-MAX Cold Water: 0-50 ppm Hot Water: 0.1-2.5ppm 18h Chloride MIN-MAX Cold Water: 0-10 ppm Hot Water: 0-10 ppm 18i Cu-Copper MIN-MAX Cold Water: 0-0.1 ppm Hot Water: 0-0.1 ppm 18j Fe-Iron MIN-MAX Cold Water: 0-0.1 ppm Hot Water: 0-0.1 ppm 18k Zn-Zinc MIN-MAX Cold Water: 0-0.1 ppm Hot Water: 0-0.1 ppm 18l Al-Aluminium MIN-MAX Cold Water: 0-0.1 ppm Hot Water: 0-0.1 ppm 18m Mn-Manganese MIN-MAX Cold Water: 0-0.1 ppm Hot Water: 0-0.1 ppm 18n Color/Clarity N/A Water must be colorless

Sheet2

Cold UtilityHot Utility
SpecificationUnitsminmaxminmax
Min Sediment FiltrationMicron0505
Total Hardness as CaCo3ppm CaCo350170017
Total Dissovled Solidsppm10050050250
Total Alkalinity as CaCo3ppm7018050180
pH6.58.56.59.5
Conductivityumhos/cm0100040500
Total Silicappm0500.12.5
Chlorideppm010010
Cu-Copperppm00.100.1
Fe-Ironppm00.100.1
Zn-Zincppm00.100.1
Al-Aluminiumppm00.100.1
Mn-Manganeseppm00.100.1
Color/ClarityWater should be colorless