SCOPE OF WORK

1. PROJECT DATA:

TITLE: FCA - Correct Electrical System Deficiencies

BUILDING/FACILITY: VAMC Wichita, 5500 E Kellogg Wichita, KS

67218 PROJECT NUMBER: Project # 589A7-20-111

COTR: Andrew Chavez (316-685-2221 X57929)

REQUESTOR: Andrew Chavez

CONTRACTOR: TBD

CONSTRUCTION DURATION: 122 calendar Days

2. GENERAL SCOPE:

A. The contractor shall provide labor, material and supervision to replace, construct, demo, or repair the following:

I.The following is electrical equipment requiring replacement or repair. ▪ Repair and replace panel boards ML11, EE7981, Square D 208/3/4. MSR PNL-001 and MSR PNL-002. Electrical equipment is located at building 11, Engineering Compound. Both panelboards in this vault should be replaced due to their age and missing parts and obsolete bolt lock switches.

II.▪ Replace SWITCHGEAR 53, 15 KV Switch Lineup (5 enclosures), located at the Building 11 shop area. The

Switchgear has deteriorated due to age and weathering. The switches stick partially closed or do not open all the way, unsafe to operate due to defective operating mechanisms.

III.▪ Replace SWITCHGEAR 55, 15 KV Switch Lineup (6 enclosures), located at the Building 26/3 area. The Switchgear has deteriorated due to age and weathering. The switches stick partially closed or do not open all the way, unsafe to operate due to defective operating mechanisms. Contractor shall field investigate equipment for detail and verification for a complete design.

IV.▪ Replace ground wire mounting, unsecured on C-Phase, and the ground wire is dangling. SWITCHGEAR 49 Main

Building 1 Area, Westinghouse 15KV WLI 600 AMP, Main Selector switch.

V.▪ Repair Square D, 750 KVA, EE N/A, MSR XFR-024, Primary Cable Stress cone connecting to H2 (Transformer

Bushing Terminal) taped end is cracked. Location is at building 29.

VI.▪ Replace electrical panels in Building 34, room 112-34. Panels to be replaced are normal power panels EE44711 &

EE44712, emergency Power panels EE44708 & EE709. Panels are beyond useful life and are broken beyond repair.

END OF SCOPE OF WORK