SHEET INDEX
GI001
SHEET
NO. DRAWING TITLE
GENERAL
GI002
ARCHITECTURAL
SHEET
NO.
COVER SHEET
NOTES, ABBREVIATIONS AND LEGEND
PENTHOUSE LIFE SAFETY PLANLS101
REPLACE AIR HANDLERS IN BUILDING 1
PROJECT NUMBER: 657A5-22-103
BID DOCUMENTS
MARION VA MEDICAL CENTER
2401 W MAIN ST, MARION, IL 62959
PENTHOUSE DEMO FLOOR, ROOF AND REFLECTED CEILING PLANAD101
FIRE PROTECTION
FIRE PROTECTION ABBREVIATIONS AND NOTESF-001
FIRE PROTECTION PARTIAL ROOF PLAN & PENTHOUSEF-101
PLUMBING
PLUMBING ABBREVIATIONS, LEGENDS, & NOTESP-001
MECHANICAL
MECHANICAL LEGEND, ABBREVIATIONS, AND NOTESM001
MECHANICAL NOTESM002
PENTHOUSE AND ROOF MECHANICAL PHASING PLANM003
ELECTRICAL
PLUMBING PARTIAL THIRD & ROOF/ PENTHOUSE PLANSP-101
ELECTRICAL GENERAL NOTES AND ABBREVIATIONSE001
LOCATION MAP
NOT TO SCALE
AREA MAP
NOT TO SCALE
TRUE
NORTH
TRUE
NORTH
PLAN
NORTH
PLAN
NORTH
PROJECT LOCATION PROJECT LOCATION
ELECTRICAL SYMBOLSE002
MECHANICAL NEW WORK PLANM101
HVAC DETAILSM501
MECHANICAL PIPING DETAILSM502
MECHANICAL PIPING DETAILSM503
MECHANICAL EQUIPMENT DETAILM504
PENTHOUSE FLOOR , ROOF AND REFLECTED CEILING PLANAE101
PENTHOUSE EXTERIOR ELEVATIONS AND BUILDING SECTIONSAE201
TEMPORARY AHU SITE LOCATION PLANAS101
WALL SECTIONS AND DETAILSAE301
STRUCTURAL
STRUCTURAL NOTESS001
PENTHOUSE DEMO AND NEW PENTHOUSE FRAMING PLANSS101
PLATFORM ROOF FRAMING PLANS102
FRAMING ELEVATIONSS201
STEEL DETAILSS501
STEEL DETAILSS502
PENTHOUSE DUCT AND PIPING DEMOLITION PLANSMD101
SECTIONS - MECHANICAL NEW WORK PLANM401
ISOMETRIC MECHANICAL PLAN - NEW PENTHOUSE 401 - NEW WORKM402
STEAM TO HOT WATER HEAT EXCHANGER MAKE-UP WATER SCHEMATICSM505
MECHANICAL SCHEDULESM601
VA STATION GENERAL CONTROL NOTES AND LEGENDM800
CONTROL SCHEMATIC, SEQUENCE OF CONTROL, AND CONTROL POINT – MECHANICALM801
CONTROL SCHEMATIC, SEQUENCE OF CONTROL, AND CONTROL POINT – MECHANICALM802
ELECTRICAL PENTHOUSE DEMO PLANED101
ELECTRICAL DETAILSE501
ELECTRICAL DETAILSE502
ELECTRICAL SCHEDULESE601
PLUMBING ENLARGED THIRD FLOOR PLANSP-401
PLUMBING ENLARGED PENTHOUSE PLANSP-402
PLUMBING DETAILSP-501
SIESMIC BRACING DETAILSP-502
SCHEDULES AND DETAILSAE601
ELECTRICAL PENTHOUSE PLANE101
STRUCTURAL DETAILSS503
PLAN DETAILSAE401
THIRD FLOOR REFLECTED CEILING PLANAE102
SIGNATURE BLOCK
CHIEF OF ENGINEERING
ENERGY ENGINEER
FACILITY PLANNER
SAFETY
VA POLICE
INFECTION PREVENTION
ENVIRONMENTAL MANAGEMENT
INFORMATION SECURITY OFFICER
PRIVACY OFFICER
OFFICE OF INFORMATION TECHNOLOGY
ASSOCIATE DIRECTOR, PATIENT CARE
CHIEF OF STAFF
ASSOCIATE DIRECTOR
FACILITY DIRECTOR
M & O SUPERVISOR
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PA SJ/KB
REPLACE AIR HANDLERS IN BUILDING 1 675A5-22-103
VAMC MARION, IL
03-07-2025REVISIONS:
COVER SHEET
GI001
ARCHITECTURAL ABBREVIATIONSARCHITECTURAL LEGEND
GENERAL ARCHITECTURAL NOTES
GENERAL PROJECT NOTES
A
A301
A201
A401
ROOM
NAME
+ 0'-6"
AIR CONDITIONING
ACOUSTICAL CEILING TILE
ABOVE FINISH FLOOR
ALUMINUM
BATT INSULATION
BOTTOM OF
CEMENTITIOUS BACKER BOARD
CEMENTITIOUS CRYSTALLINE WATERPROOFING
COLD-FORMED METAL FRAMING
CORNER GUARD
CENTERLINE
CONCRETE MASONRY UNIT
CASED OPENING
COMMUNICATION
CONCRETE
SEALED CONCRETE
CONTINUOUS
CONTRACTING OFFICER'S REPRESENTATIVE
CERAMIC TILE
CERAMIC TILE BASE
CARPET
DIAMETER
EXPANSION JOINT
ELECTRICAL
EPOXY FLOORING
EXPOSED STRUCTURE
ET CETERA
EXISTING
EXPOSED
FACTORY FINISH
FLOOR DRAIN
FIRE EXTINGUISHER CABINET
FIRE HOSE CABINET
FINISHED FLOOR
FINISH
FLOOR
FACE OF
FIELD VERIFY
FABRIC WALLCOVERING
GAGE
GRANITE
GYPSUM (WALL) BOARD
HANDICAPPED
HOLLOW METAL
HANDRAIL
HEATING VENTILATION AND AIR-CONDITIONING
MATERIAL
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
MASONRY OPENING
METAL
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
PLASTER
PLASTIC LAMINATE
PORCELAIN TILE
PAIR
PAINT
QUARRY TILE
RESILIENT BASE
REFRIGERATOR
REQUIRED
RESINOUS FLOORING
RESINOUS EPOXY WALL-CEILING
ROUGH OPENING
RUBBER FLOORING
RECESSED PAPER HOLDER
SEALED HIGH BUILD GLAZED COATING
SOLID CORE WOOD
SIMILAR
SPECIAL FACED
STAINLESS STEEL
STEEL
SUBSTRATE
SHEET VINYL
SOLID VINYL TILE
TELEPHONE
TOP OF
TYPICAL
UNLESS NOTED OTHERWISE
VINYL COMPOSITION TILE
VINYL WALL COVERING
WALL COVERING
WALL PROTECTION
WOOD
WELDED SEAM SHEET FLOORING
AC
AT
AFF
AL
BATT
BO
CBB
CCW
CFMF
CG
C
CMU
CO
COMM
CONC
SCONC
CONT
COR
CT
CTB
CP
DIA
EJ
ELEC
EPY
ES
ETC
EXIST
EXP
FAC FIN
FD
FEC
FHC
FF
FIN
FLR
FO
FV
FWC
GA
GRA
GYP BD/GWB
HC
HM
HR
HVAC
MATL
MAX
MECH
MFR
MIN
MO
MTL
NIC
NTS
OC
OH
PLS
PL
PT
PR
P
QT
RB
REF
REQ'D
RES
RES-W
RO
RF
RPH
SC
SCW
SIM
SP
SS
STL
SUBS
SV
SVT
TELE
TO
TYP
UNO
VCT
VWC
WC
WP
WD
WSF
L
ROOM NAME AND NUMBER
DOOR NUMBER
KEY NOTE
DETAIL CALLOUT
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
SECTION CALLOUT
VERTICAL ELEVATION
COLUMN CENTERLINE DESIGNATION
DEMOLITION KEY NOTE
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
INTERIOR ELEVATION CALLOUT
DETAIL NUMBER
SHEET WHERE DETAIL IS DRAWN
CARD READERCR
HIGH-PRESSURE LAMINATEHPL
LUXURY VINYL TILELVT
EDGE OF DECKEOD
DOWNSPOUTDS
CONTROL JOINTCJ
DRINKING FOUNTAINDF
FIRE RETARDANT TREATEDFRT
EXTERIOR INSULATION FINISHING SYSTEMEIFS
WATER RESISTANTWR
J1
SECTION CUT
HEAD/JAMB/SILL DETAIL NUMBER
EQUALEQ
CARPET TILECPT
REFLECTED CEILING PLANRCP
SOLID SURFACE MATERIALSSM
ALUMINUM COMPOSITE METAL PANELSACMP
A. DIMENSIONS, UNLESS OTHERWISE INDICATED, ARE TO:
• FACE OF EXISTING WALL SURFACE
• FACE OF MASONRY
• FACE OF WALL STUDS
• TOP OF SLAB
• TOP OF MASONRY
• ALIGN WALLS WITH EXISTING WHERE NOT OTHERWISE INDICATED.
B. COORDINATE WITH ALL DISCIPLINES DRAWINGS FOR ADDITIONAL REQUIREMENTS.
COORDINATE OPENINGS IN SLABS, ROOF, AND WALLS. WHERE HOLES IN EXISTING WALLS
AND SLABS ARE CREATED FOR PENETRATIONS, COORDINATE SIZE AND LOCATION. PATCH
HOLES CAUSED BY THE REMOVAL OF EQUIPMENT, PIPING, CONDUIT, DUCT, GRILLES, ETC.
WITH MATERIALS MATCHING EXISTING SLAB OR WALL IN STRUCTURE, MATERIAL,
THICKNESS, ALIGNMENT, GRADES, AND QUALITY.
C. COORDINATE AND PROVIDE GALVANIZED METAL BACKER PLATE OR SOLID FIRE
RETARDANT TREATED WOOD BLOCKING FOR WALL-MOUNTED ITEMS. COORDINATE
LOCATIONS WITH COR FOR GOVERNMENT PROVIDED/CONTRACTOR INSTALLED
EQUIPMENT.
D. `PROVIDE' IS DEFINED AS PROVIDING MATERIALS, DELIVERY, STORAGE, HANDLING,
INSTALLATION, ADJUSTMENT, AND CLEANING FOR THE ITEM INDICATED.
E. SEAL PIPE PENETRATIONS THROUGH SLABS, MASONRY, SMOKE RATED PARTITIONS AND
FIRE-RATED PARTITIONS WITH THE APPROPRIATE FIRESTOP TO MAINTAIN THE RATING OF
THE WALL OR SLAB. SUBMIT CUT SHEETS AND SPECIFICATIONS TO THE COR FOR
APPROVAL PRIOR TO INSTALLATION. PROVIDE UL LISTED ASSEMBLIES.
F. SKIM COAT ALL DAMAGED EXISTING WALL SURFACES THAT REQUIRE PAINTING.
G. REMOVED MATERIALS WHICH ARE INDICATED TO BE TURNED OVER TO THE COR SHALL BE
DELIVERED BY THE CONTRACTOR TO A PLACE INDICATED BY THE COR .
H. REMOVE COMPLETELY ALL MATERIALS AS INDICATED ON THE DRAWINGS AND AS
REQUIRED FOR CONSTRUCTION. EDGES AND FACES OF DEMOLISHED AREAS SHALL BE
REPAIRED TO ACCEPT NEAT INSTALLATION OF CONSTRUCTION OR FINISHES. WHERE
EXISTING MATERIALS ARE TO BE REPLACED (WALLS, INSULATION, FLOORING, ETC.)
EXISTING MATERIALS, ADHESIVES, ETC. SHALL BE REMOVED AND EXPOSED SURFACES
SHALL BE PREPARED AS INDICATED OR SPECIFIED PRIOR TO INSTALLATION OF
MATERIALS.
I. PREVENT DAMAGE TO MATERIALS AND FINISHES TO REMAIN. REPAIR DAMAGES FROM
CONSTRUCTION ACTIVITIES TO EXISTING ITEMS TO REMAIN, AT NO ADDITIONAL COST
WHERE SUCH EXPOSED MATERIALS OR FINISHES TO REMAIN ARE DAMAGED.
A. THE CONTRACTOR SHALL BE PREPARED TO STOP ANY WORK AND CLEAN UP THE WORK AREA
AS DIRECTED IN MEDICAL SITUATIONS REQUIRING SUCH ACTION.
B. THE CONTRACTOR SHALL NOT ORDER OR INSTALL ANY MATERIALS OR EQUIPMENT UNTIL
SUBMITTALS FOR SUCH HAVE BEEN APPROVED.
C. ALL TOOLS AND MATERIALS USED IN THIS PROJECT SHALL BE PROPERLY SECURED AT ALL
TIMES BY THE CONTRACTOR TO REDUCE THE POSSIBILITY OF ANY OF THESE TOOLS BEING A
HAZARD TO PATIENTS, VISITORS AND STAFF.
D. THE CONTRACTOR WILL BE RESPONSIBLE FOR ACQUIRING I.D. BADGES FOR EACH MEMBER OF
HIS WORK FORCE. VALID FORMS OF I.D. ARE REQUIRED TO RECEIVE BADGES. COORDINATE
WITH COR.
E. THE CONTRACTOR, AT HIS EXPENSE, WILL BE RESPONSIBLE FOR TRAINING EACH MEMBER OF
HIS WORK FORCE ON VA POLICIES FOR ON-SITE WORK BEFORE ANY MEMBER WILL BE
ALLOWED TO PERFORM WORK ON VA PREMISES.
F. ABSOLUTELY NO VA TOOLS, MATERIALS OR EQUIPMENT WILL BE LOANED OR GIVEN BY THE VA
TO ANY MEMBER OF THE CONTRACTOR'S WORK FORCE AT ANY TIME.
G. ANY SMOKE DETECTORS HAVING ANY POTENTIAL FOR EXPOSURE TO CONSTRUCTION SMOKE,
DUST AND DEBRIS SHALL BE SUITABLY PROTECTED TO PREVENT ACCIDENTAL ALARM DURING
CONSTRUCTION. ALL SUCH ACTION MUST BE FIRST COORDINATED AN CLEARED WITH THE COR
AND THE VA SAFETY OFFICER. ALL FUNCTIONAL FIRE ALARM DEVICES SHALL BE ACTIVE
WHENEVER THE CONTRACTOR'S FORCES ARE NOT PRESENT IN THE WORK AREA.
H. THE CONTRACTOR MUST PROVIDE WRITTEN FIRE SAFETY CHECKLIST AT THE END OF EVERY
WORK DAY TO THE COR CERTIFYING THAT ALL WORK AREAS HAVE BEEN SURVEYED AND
FOUND TO BE SECURE, SAFE AND FREE OF ANY FLAMMABLE LIQUIDS.
I. CONTRACTOR SHALL COORDINATE ONLY WITH THE COR AND CONTRACTING OFFICER.
J. SEE SPECIFICATIONS SECTIONS 01 00 00 AND 01 35 26 FOR INTERIM LIFE SAFETY MEASURES.
K. ALL FINISH COLORS TO BE SELECTED BY COR/ VA INTERIOR DESIGNER WHERE NOT
OTHERWISE INDICATED. CONTRACTOR SHALL SUBMIT COLORS FROM THE MANUFACTURER'S
FULL RANGE OF COLORS.
L. PROVIDE 24"X24" ACCESS PANELS IN HARD CEILINGS WHERE DUCTS AND DAMPERS OR OTHER
PIPES REQUIRE ACCESS AS REQUIRED. COORDINATE EXACT LOCATIONS WITH THE COR.
M. THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING VA EQUIPMENT WITHOUT
AUTHORIZATION FROM VAMC ENGINEERING SERVICE UNLESS AN EMERGENCY SITUATION
OCCURS.
N. CONTRACTOR SHALL MAINTAIN ALL FIRE-RATED ASSEMBLIES WITHIN THE PROJECT AREA
DURING PERFORMANCE OF THE WORK.
O. CONTRACTOR SHALL PROVIDE AND MAINTAIN ALL REQUIRED EXIT LIGHTING AND SIGNAGE
REQUIRED FOR EGRESS WITHIN AND ADJACENT TO THE PROJECT AREA DURING
PERFORMANCE OF THE WORK.
P. INDICATED EXISTING CONDITIONS ARE BASED UPON LIMITED FIELD INVESTIGATION AND DID
NOT INCLUDE DESTRUCTIVE INVESTIGATION OR TESTING. CONTRACTOR SHALL VERIFY ALL
EXISTING CONDITIONS INCLUDING DIMENSIONS OF THE INSTALLED CONSTRUCTION PRIOR TO
COMMENCING WITH THE WORK. IF DISCREPANCIES ARE DISCOVERED, THE CONTRACTOR
SHALL NOTIFY THE COR FOR INTERPRETATION AND DIRECTION PRIOR TO PROCEEDING WITH
THE WORK.
Q. COORDINATE WORK WITH EQUIPMENT SUPPLIER/ INSTALLER CONTRACTED SEPARATELY WITH
THE GOVERNMENT.
ACCESSIBILITY REQUIREMENTS
FRONT APPROACHES
HINGE-SIDE APPROACHES
LATCH-SIDE APPROACHES
USE EITHER
OPTION 1 OR
OPTION 2
ALL DOOR ASSEMBLIES SHALL BE CONSTRUCTED TO MEET THE
INDICATED MINIMUM CLEARANCES AS APPLICABLE.
1'-0" IF DOOR HAS BOTH
A CLOSER AND A
LATCH
5' -0
1'-6"
3' -6
4'-6"
4' -0
O P
TI
O
N
5' -0
OPTION 1
3'-0"
O P
TI
O
N
4' -6
OPTION 2
3'-6"
2'-0"
4' -0
2'-0"
3' -6
4' -0
4' -6
W / C
LO
S
E R
4' -0
W / C
LO
S
E R
W /C
LO
S
E R
A N
D L
A
TC
H
ALL WORK SHALL COMPLY WITH FEDERAL ABA,
LOCAL, AND STATE ACCESSIBILITY CODES AND
REQUIREMENTS.
DOOR LOCATIONS
TYPICAL DETAILS
TYP DOOR LOCATION
SEE DOOR SCHEDULE
4"
TYP
TYPICAL SIGNAGE MOUTING HEIGHTS
A
5' -0
4' -9
EQ EQ
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PA SJ/KB
REPLACE AIR HANDLERS IN BUILDING 1 675A5-22-103
VAMC MARION, IL
03-07-2025REVISIONS:
NOTES, ABBREVIATIONS AND LEGENDS
GI002
DESIGN CODES:
1.1 BUILDING CODE: 2021 INTERNATIONAL BUILDING CODE AS AMENDED BY
A.VA H-18-8 SEISMIC DESIGN REQUIREMENTS
B.NATIONAL LOADING STANDARD: ASCE 7-16 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
C. ACI 318-19 BUILDING CODE REQUIREMENTS FOR STURCTURAL CONCRETE
D.STEEL: AISC 360-16 - SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS
DESIGN LOADS:
1.1 DESIGN LOADS ARE AS FOLLOWS:
A.ROOF:
1. DEAD LOADS:
a. PLATFORM & EXISTING ROOF: SELF WEIGHT OF MATERIALS
b. EQUIPMENT ON PLATFORM: SEE BELOW
2. LIVE LOADS:
a. PLATFORM: 60 PSF
b. EXISTING ROOF: 20 PSF
3. COLLATERAL LOADS:
a. PLATFORM & EXISTING ROOF: 10 PSF
4. RAIN LOADS:
a. N/A: NO ACCUMULATION
5. FLOOD LOADS:
a. N/A: NOT IN FLOOD HAZARD AREA
6. SNOW LOADS:
a. GROUND SNOW LOAD = 15 PSF
B.WIND LOADS:
1. DESIGN WIND SPEED = Vult 116 MPH
2. WIND EXPOSURE = B
3. RISK CATEGORY = IV
C.EARTHQUAKE LOADS:
1. OCCUPANCY CATEGORY = IV
2. SPECTRAL RESPONSE COEFFICIENT
a. Ss = 0.770 g
b. S1 = 0.262 9
3. SPECTRAL RESPONSE ACCELERATION
a. Sds = 0.612 g
b. Sd1 = 0.367 g
4. SEISMIC DESIGN CATEGORY = D
5. SITE CLASS = D
1.2 DEFLECTION CRITERIA: REFER TO TABLE 1604.3 FOR DEFLECTION LIMITS.
UNIT IDENTIFIER
L(IN) W(IN) H(IN)
MAX DIMENSIONS
MAX WEIGHT(LB)
AHU-3 408 90 78 11,631
GENERAL STRUCTURAL NOTES:
1.1 ELEVATIONS AS SHOWN ON THE STRUCTURAL DRAWINGS ARE ELEVATIONS RELATIVE TO THE FINISH EXISTING
FLOOR ELEVATION UNLESS NOTED OTHERWISE
1.2 WHERE A DETAIL, TYPICAL DETAIL, SECTION, TYPICAL SECTION OR NOTE IS SHOWN FOR ONE CONDITION, IT SHALL
APPLY FOR ALL SIMILAR OR LIKE CONDITIONS UNLESS OTHERWISE NOTED.
1.3 THE STRUCTURAL DESIGN OF THE STRUCTURE IS BASED ON THE FULL INTERACTION OF ALL ITS COMPONENT PARTS, WITH NO PROVISION MADE FOR CONDITIONS OCCURRING DURING CONSTRUCTION. THEREFORE, CONTRACTOR SHALL PROVIDE ADEQUATE BRACING AND TEMPORARY SHORING DURING CONSTRUCTION.
1.4 CONTRACTOR IS RESPONSIBLE FOR ALL JOB SITE SAFETY INCLUDING THE SAFE RIGGING, LIFTING AND SETTING OF
EQUIPMENT IN ACCORDANCE WITH APPLICABLE STANDARDS.
1.5 FURNISH AND INSTALL ALL NECESSARY ATTACHMENTS, ANCHORAGES AND ACCESSORIES TO PROVIDE A COMPLETE STRUCTURALLY SOUND STRUCTURE WITH A CONTINUOUS LOAD PATH. BRING ANY DISCONTINUITIES TO THE
ATTENTION OF THE STRUCTURAL ENGINEER IMMEDIATELY.
1.6 FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF FABRICATION OR CONSTRUCTION. BRING ANY DISCREPANCIES ALONG WITH DETAILED FIELD SKETCHES OF AS-BUILT CONDITIONS TO THE ATTENTION OF THE
STRUCTURAL ENGINEER IMMEDIATELY.
1.7 COORDINATE AND VERIFY ALL DIMENSIONS AND DETAILS WITH THE EXISTING, CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS. NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY OF
ANY DISCREPANCIES.
SHOP DRAWINGS
2.1 STRUCTURAL DRAWINGS INDICATE TYPICAL AND CERTAIN SPECIFIC CONDITIONS ONLY. SHOP DRAWINGS SHALL
DETAIL ALL CONDITIONS IN ACCORDANCE WITH SPECIFIED STANDARDS AND THE SPECIFIC REQUIREMENTS OF THIS
PROJECT AS INDICATED ON THE DRAWINGS.
2.2 CONTRACTOR SHALL PROVIDE A MINIMUM OF ONE HARD COPY AND LEGIBLE PDF FOR EACH STRUCTURAL
COMPONENT FOR REVIEW PRIOR TO FABRICATION.
2.3 PHOTOCOPY REPRODUCTIONS OF THE CONTRACT DOCUMENTS WILL BE REJECTED AND CONTRACTOR WILL BE
RESPONSIBLE FOR ANY ASSOCIATED DELAYS.
2.4 SUBMITTALS FOR VENDOR DESIGNED COMPONENTS SHALL BE ACCOMPANIED BY DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT. IN ADDITION, THESE SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT SUPERVISION OF THE STRUCTURAL
ENGINEER SEALING THIS WORK.
2.5 REVIEW OF SUBMITTALS INCLUDING SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR OF THE SOLE RESPONSIBILITY FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF THOSE SUBMITTALS.
2.6 SUBMITTALS SHALL BE REVIEWED BY THE CONTRACTOR, PRIOR TO SUBMISSION FOR ENGINEER'S REVIEW, FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS AND AS-BUILT CONDITIONS. ANY DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS SHALL BE CLEARLY NOTED ALONG WITH REASONS FOR THE DEVIATION.
2.7 ALLOW A MINIMUM OF TWO CALENDAR WEEKS (14 DAYS) FROM RECEIPT OF SUBMITTALS AT THE ENGINEERS OFFICE FOR REVIEW. ALLOW TIME IN THE CONSTRUCTION SCHEDULE FOR SHIPPING AND PROCESSING TIME IN ADDITION TO
SUCH REVIEWS.
SPECIAL INSPECTIONS:
1.1 SPECIAL INSPECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH CHAPTER 17 OF THE BUILDING CODE REFERENCED ABOVE AND AS DEFINED IN THE SPECIFICATIONS. A QUALIFIED SPECIAL INSPECTOR APPROVED BY
THE GOVERNMENT SHALL MAKE SPECIAL INSPECTIONS.
1.2 INSPECTION REPORTS SHALL BE FURNISHED TO THE GOVERNMENT, ARCHITECT, AND STRUCTURAL ENGINEER.
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR, AND, IF NOT CORRECTED, SHALL BE
REPORTED TO THE GOVERNMENT, ARCHITECT, AND STRUCTURAL ENGINEER.
EQUIPMENT NOTES:
1.1 EQUIPMENT COORDINATION
A.THE CONTRACTOR SHALL COORDINATE DIMENSIONAL AND UTILITY REQUIREMENTS OF ACTUAL EQUIPMENT
PURCHASED WITH PROVISIONS SHOWN ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING ANY CHANGES NECESSARY TO MAKE SUCH COORDINATION WITHOUT ADDITIONAL COST
TO THE GOVERNMENT.
1.2 EQUIPMENT ANCHORAGE
A.THE CONTRACTOR SHALL ENGINEER, FURNISH AND INSTALL NECESSARY ANCHORAGE AND VIBRATION ISOLATION
FOR ALL EQUIPMENT AND CURBS TO RESIST ALL LOADING INCLUDING BUT NOT LIMITED VIBRATORY, WIND AND
EARTHQUAKE LOADS AT NO ADDITIONAL COST TO THE GOVERNMENT.
B.THE CONTRACTOR SHALL PREPARE AND SUBMIT ANCHORAGE DETAILS AND SUPPORTING CALCULATIONS PREPARED AND SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT FOR ALL MOUNTED EQUIPMENT, AND ASSOCIATED CURBS, FOR REVIEW AND APPROVAL PRIOR TO FABRICATION AND
INSTALLATION.
1.3 EQUIPMENT STRUCTURAL SUPPORT
A.THE STRUCTURAL DESIGN DEPICTED ON THESE DRAWINGS IS BASED ON THE EQUIPMENT DIMENSIONS AND
WEIGHTS OUTLINED ABOVE. IN THE EVENT THE CONTRACTOR SELECTS EQUIPMENT WITH WEIGHT GREATER THAN THAT DEPICTED IN THE TABLE SHOWN ON THIS SHEET, OR DIMENSIONS MORE THAN 10% GREATER OR LESS THAN THOSE DEPICTED IN THE TABLE SHOWN ON THIS SHEET, THE CONTRACTOR SHALL HAVE THE AFFECTED SUPPORTING STRUCTURE (NEW AND EXISTING) EVALUATED AND REINFORCED AS NECESSARY BY A STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROJECT, AND SUBMIT SEALED CALCULATIONS AND DRAWINGS FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF FABRICATION. COSTS ASSOCIATED WITH ENGINEERING ANALYSIS, DESIGN AND CONSTRUCTION OF REPAIRS SHALL BE BORN BY THE CONTRACTOR AT NO ADDITIONAL
COST TO THE GOVERNMENT.
STRUCTURAL STEEL NOTES:
1.1 GENERAL
A.GENERAL REQUIREMENTS
1. DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE MANUAL OF
STEEL CONSTRUCTION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, INC.
B.SUBMITTALS
1. SHOP DRAWINGS: ERECTION AND FABRICATION DRAWINGS. SHOP DRAWINGS SHALL NOT CONTAIN
REPRODUCTIONS OF THE CONTRACT DRAWINGS. MEMBER SUBSTITUTION AND DEVIATIONS FROM THE CONTRACT DRAWINGS SHALL BE CLEARLY IDENTIFIED WITH AN EXPLANATION FOR THE PROPOSED DEVIATION.
C.DELIVERY, STORAGE AND HANDLING
1. PROTECT FROM CORROSION, DEFORMATION, AND OTHER TYPES OF DAMAGE. STORE ITEMS IN AN ENCLOSED
AREA FREE FROM CONTACT WITH SOIL AND WEATHER. REMOVE AND REPLACE DAMAGED ITEMS WITH NEW
ITEMS.
1.2 PRODUCTS
A.MATERIALS:
1. ALL WIDE FLANGE W'S & WT'S SHALL BE IN CONFORMANCE WITH ASTM A 992, LATEST ADOPTED EDITION, UNO.
2. ALL OTHER SHAPES, PLATES AND BARS SHALL BE IN CONFORMANCE WITH ASTM A 36, LATEST ADOPTED EDITION, UNO.
3. ALL SQUARE, RECTANGULAR AND ROUND TUBING SHALL BE IN CONFORMANCE WITH ASTM A 500, LATEST
ADOPTED EDITION, GRADE B.
4. ALL ROUND PIPE SHALL BE IN CONFORMANCE WITH ASTM A 53, LATEST ADOPTED EDITION, GRADE B.
5. BOLTS SHALL CONFORM TO F 1852 (A 325) TYPE 1 LOAD INDICATOR BOLTS, UNO.
6. THREADED RODS SHALL COMPLY WITH ASTM A 36, LATEST ADOPTED EDITION, UNO.
7. HARDENED STEEL WASHERS SHALL COMPLY WITH ASTM F 436.
8. HEAVY HEX NUTS SHALL COMPLY WITH ASTM A 563.
9. GROUT (WHERE SHOWN OR REQUIRED) SHALL BE NON-SHRINK, NON-METALLIC FACTORY PREMIXED GROUT
HAVING A COMPRESSIVE STRENGTH OF 6800PSI AT 28 DAYS.
B.FABRICATION
1. ALL NATURAL AND FABRICATED CAMBER SHALL BE INSTALLED UPWARD.
2. THE MINIMUM THICKNESS OF GUSSET AND FIN PLATES SHALL BE 3/8 IN.
3. BOLTED CONNECTIONS:
a. ALL OTHERS MAY BE CONSIDERED AS "BEARING" TYPE N.
b. THE MINIMUM NUMBER OF BOLTS IN STRUCTURAL STEEL CONNECTIONS SHALL BE AS FOLLOWS:
1) A MINIMUM OF TWO BOLTS PER CONNECTION SHALL BE USED, UNO.
C.FINISH (ROOF TOP EQUIPMENT SUPPORT)
1. SURFACE PREPARATION:
a. UNLESS NOTED OTHERWISE, SHOP CLEAN THE SURFACE OF ALL STRUCTURAL STEEL IN ACCORDANCE WITH
THE REQUIREMENTS OF SSPC-SP2
2. PRIMER:
a. UNLESS NOTED OTHERWISE SHOP PAINT WITH A MINIMUM OF 1.0 MILS OF THE FABRICATORS STANDARD RUST
INHIBITIVE PRIMER.
b. BLOCK OUT PRIMER AT THE FOLLOWING LOCATIONS:
1) STEEL AT SLIP CRITICAL CONNECTIONS.
2) STEEL TO BE EMBEDDED IN CONCRETE.
3) STEEL TO RECEIVE SPRAY-ON FIRE PROOFING.
4) STEEL TO RECEIVE GALVANIZED FINISH.
3. FINISH COATING:
a. HOT DIPPED GALVANIZED: ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER SHALL BE HOT-
DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153.
D.FINISH (ALL OTHER STEEL)
1. SURFACE PREPARATION:
a. UNLESS NOTED OTHERWISE, SHOP CLEAN THE SURFACE OF ALL STRUCTURAL STEEL IN ACCORDANCE WITH
THE REQUIREMENTS OF SSPC-SP2.
2. PRIMER:
a. UNLESS NOTED OTHERWISE SHOP PAINT WITH A MINIMUM OF 1.0 MILS OF THE RUST INHIBITIVE PRIMER.
3. FINISH COATING
a. PAINT AS DIRECTED BY THE ARCHITECT
b. STANDARD COLORS AS SELECTED BY THE GOVERNMENT
1.3 PART 3 EXECUTION
A.EXAMINATION
1. PRIOR TO STRUCTURAL STEEL ERECTION, ERECTOR SHALL INSPECT EXISTING CONSTRUCTION FOR CORRECT SIZE, LAYOUT AND ALIGNMENT. ANY INCONSISTENCIES DEEMED DETRIMENTAL TO THE ERECTION OF STEEL
SHALL BE REPORTED AND REPAIRED PRIOR TO INSTALLATION.
B. INSTALLATION
1. WELDED CONNECTIONS SHALL BE MADE WITH E70XX ELECTRODES IN ACCORDANCE WITH AWS D1.1, STRUCTURAL WELDING CODE BY THE AMERICAN WELDING SOCIETY, AND SHALL BE PERFORMED BY CERTIFIED
WELDERS. WELDER CERTIFICATION SHALL BE AVAILABLE ON SITE FOR INSPECTION.
C.FIELD QUALITY CONTROL
1. TOLERANCES
a. MAXIMUM VARIATION FROM PLUMB: 1/4" (6 MM) PER STORY, NON-CUMULATIVE.
b. MAXIMUM OFFSET FROM TRUE ALIGNMENT
2. WELDED CONNECTIONS:
a. ALL WELDS SHALL BE VISUALLY EXAMINED.
b. 15% OF ALL WELDS SHALL BE TESTED IN ACCORDANCE WITH THE FOLLOWING METHODS:
1) TESTED BY THE LIQUID PENETRANT METHOD IN ACCORDANCE WITH ASTM E 165 OR THE MAGNETIC PARTICLE
METHOD IN ACCORDANCE WITH ASTM E 709.
D.REPAIR
1. PROTECTIVE COATINGS DAMAGED DURING THE TRANSPORTATION, ERECTION AND FIELD WELDING PROCESSES
SHALL BE REPAIRED IN THE FIELD TO MATCH THE SHOP APPLIED COATING.
E.CLEANING AND PROTECTION
1. CLEAN AFTER INSTALLATION EXPOSED PREFINISHED ITEMS IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS.
2. PROTECT INSTALLED ITEMS FROM DAMAGE CAUSED BY SUBSEQUENT CONSTRUCTION.
BAR GRATING NOTES:
1.1 PART 1 GENERAL
A.GENERAL REQUIREMENTS: FABRICATE AND INSTALL BAR GRATING AND STAIR TREADS IN ACCORDANCE WITH:
1. ANSI/NAAMM METAL BAR GRATING MANUAL MBG 531 (ALUMINUM AND LIGHT DUTY STEEL AND STAINLESS STEEL
GRATING)
B.SUBMITTALS
1. FIELD MEASURE EXISTING CONDITIONS PRIOR TO THE PREPARATION OF SHOP DRAWINGS AND FABRICATION.
2. PRODUCT DATA AND SHOP AND SETTING DRAWINGS SHALL DEMONSTRATE COMPLIANCE WITH THE LOADING
CRITERIA, THE REQUIREMENTS CONTAINED HEREIN AND THE GRATING AND TREADS, INCLUDING FASTENERS, SPECIFIED ON THE DRAWINGS.
C.QUALITY ASSURANCE
1. MANUFACTURER QUALIFICATIONS: A COMPANY SPECIALIZING IN THE MANUFACTURING OF METAL BAR GRATINGS
WITH NOT LESS THAN 5 YEARS DOCUMENTED EXPERIENCE.
2. INSTALLER QUALIFICATIONS: A COMPANY SPECIALIZING IN THE INSTALLATION OF METAL BAR GRATINGS WITH
NOT LESS THAN 5 YEARS DOCUMENTED EXPERIENCE.
3. WELDERS SHALL BE CERTIFIED IN ACCORDANCE WITH AWS D1.1/D1.1M FOR THE TYPE OF WELDING AND
POSITION UTILIZED ON THIS PORTION OF WORK. IF WELDERS CERTIFICATION IF MORE THAN ONE-YEAR OLD, WELDER SHALL BE ABLE TO DOCUMENT THAT THE WELDER HAS BEEN ENGAGED IN WELDING SINCE THE DATE OF
CERTIFICATION WITH NO BREAK IN SERVICE GREATER THAN 6 MONTHS.
D.DELIVERY, STORAGE AND HANDLING
1. PROTECT FROM CORROSION, DEFORMATION, AND OTHER TYPES OF DAMAGE. STORE ITEMS IN AN ENCLOSED
AREA FREE FROM CONTACT WITH SOIL AND WEATHER. REMOVE AND REPLACE DAMAGED ITEMS WITH NEW
ITEMS.
1.2 PART 2 PRODUCTS
A.MATERIALS
1. STEEL GRATING:
a. BEARING, CROSS AND CONNECTING BARS OF RECTANGULAR SECTION SHALL COMPLY WITH ASTM A 1011/A
1011M, LATEST ADOPTED EDITION, COMMERCIAL SERIES (TYPE 2) FOR HOT ROLLED CARBON SHEET AND STRIP
STEEL.
b. TOP SURFACE OF BEARING BARS SHALL HAVE THE FOLLOWING FINISH:
1) SERRATED
c. CROSS BARS MADE OF WIRE ROD SHALL COMPLY WITH ASTM A 510/A510M, LATEST ADOPTED EDITION, FOR
CARBON STEEL WIRE RODS AND COARSE ROUND WIRE.
d. STAIR TREAD NOSING SHALL HAVE THE FOLLOWING FINISH:
1) ABRASIVE
e. FABRICATION:
1) PROVIDE 1/4" CLEARANCE AT ALL SIDES TO PERMIT EASY REMOVAL OF GRATING.
2) FABRICATE SECTIONS NOT TO EXCEED 25 SF (2.3M2) IN AREA AND 200 LBS (90 KG) IN WEIGHT.
3) FABRICATE SECTIONS OF GRATING WITH END-BANDING BARS.
4) FINISH GRATING PENETRATIONS WITH EDGE BANDING.
f. FINISHES:
1) GALVANIZED GRATING SHALL HAVE ALL EXPOSED SURFACES ZINC-COATED BY THE HOT DIP PROCESS AFTER
FABRICATION, WITH A COATING OF NOT LESS THAN 1.8 OZ/SF (550 G/M2) OF COATED SURFACE.
2. FASTENERS:
a. REMOVABLE PANELS
1) STAINLESS STEEL SADDLE CLIPS WITH 1/4" STAINLESS STEEL FASTENERS.
1.3 PART 3 EXECUTION
A.EXAMINATION
1. PRIOR TO GRATING INSTALLATION, INSTALLER SHALL INSPECT SUPPORTS FOR CORRECT SIZE, LAYOUT AND ALIGNMENT. ANY INCONSISTENCIES DEEMED DETRIMENTAL TO GRATING PLACEMENT SHALL BE REPORTED AND
REPAIRED PRIOR TO INSTALLATION.
B. INSTALLATION
1. INSTALL AND SECURE GRATING IN ACCORDANCE WITH APPROVED SHOP DRAWINGS AND STANDARD
INSTALLATION CLEARANCES IN ACCORDANCE WITH ANSI/NAAMM METAL BAR GRATING MANUAL.
2. CUTTING, FITTING AND PLACEMENT
a. PERFORM ALL CUTTING AND FITTING REQUIRED FOR INSTALLATION. GRATING SHALL BE PLACED SUCH THAT
CROSS BARS ALIGN.
b. WHEREVER GRATING IS PIERCED BY PIPES, DUCTS AND STRUCTURAL MEMBERS, CUT OPENINGS NEATLY AND ACCURATELY TO SIZE AND WELD RECTANGULAR BAND BAR OF THE SAME HEIGHT AND MATERIAL AS THE
BEARING BARS.
c. CUTOUTS FOR CIRCULAR OBSTRUCTIONS ARE TO BE AT LEAST 2" LARGER IN DIAMETER THAN THE
OBSTRUCTION.
d. UTILIZE STANDARD PANEL WIDTHS WHEREVER POSSIBLE.
3. GRATING ANCHORAGE
a. MECHANICALLY ANCHOR GRATING TO SUBSTRATE AT A SPACING NOT TO EXCEED 24 INCHES (600 MM) ON CENTER. A MINIMUM OF TWO FASTENERS PER PANEL SHALL BE USED AT EACH SUPPORT, WITH A MINIMUM OF FOUR FASTENERS PER PANEL. LOCATE FASTENERS 6" FROM EACH SIDE OF THE PANEL. REMOVABLE GRATING PANELS SHALL BE FASTENED TO SUPPORT MEMBERS WITH U-SHAPE CLIPS, OR BY CLIPS THAT WILL NOT
CREATE A TRIPPING HAZARD.
C.FIELD QUALITY CONTROL
1. INSTALLATION TOLERANCES SHALL BE IN ACCORDANCE WITH THE METAL BAR GRATING MANUAL.
D.REPAIR
1. TOUCH-UP DAMAGED AND ABRADED GRATING WITH ZINC COATING AS RECOMMENDED BY THE GRATING
MANUFACTURER.
E.CLEANING AND PROTECTION
1. CLEAN AFTER INSTALLATION EXPOSED PREFINISHED ITEMS IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS.
F. PROTECT INSTALLED ITEMS FROM DAMAGE CAUSED BY SUBSEQUENT CONSTRUCTION.
POST-INSTALLED ANCHORS:
1.1 POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLING POST- INSTALLED ANCHORS IN PLACE OF MISSING OR MISPLACED CAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN IN PLACING POST-INSTALLED ANCHORS TO AVOID CONFLICTS WITH EXISTING REBAR. HOLES SHALL BE DRILLED AND CLEANED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTIONS. SUBSTITUTION REQUESTS, FOR PRODUCTS OTHER THAN THOSE SPECIFIED BELOW, SHALL BE SUBMITTED BY THE CONTRACTOR TO THE ENGINEER- OF-RECORD ALONG WITH CALCULATIONS THAT ARE PREPARED & SEALED BY A REGISTERED PROFESSIONAL ENGINEER. THE CALCULATIONS SHALL DEMONSTRATE THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERTINENT EQUIVALENT PERFORMANCE VALUES (MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGN PROCEDURE AND/OR STANDARD(S) AS REQUIRED BY THE BUILDING CODE.
1.2 CONCRETE ANCHORS
A.ADHESIVE ANCHORS FOR USE IN CRACKED AND UNCRACKED CONCRETE SHALL HAVE BEEN TESTED IN
ACCORDANCE WITH ACI 318 APPENDIX D.
B.ALL POST INSTALLED ANCHORS THAT ARE NOT PROPERLY INSPECTED IN ACCORDANCE WITH THE APPROPRIATE
ICC ESR CODE REPORT SHALL BE CONSIDERED TO HAVE ZERO CAPACITY AND CORRECTED BY THE CONTRACTOR
AND INSPECTED DURING INSTALLATION AT NO COST TO THE GOVERNMENT.
C.ALL POST-INSTALLED ANCHORS SHALL BE DESIGNED, DETAILED, INSTALLED, AND INSPECTED WITH THE
APPROPRIATE ICC ESR CODE REPORT.
D.PRE-APPROVED ANCHOR MANUFACTURER
1. HILTI HY200 W/ HAS STD ROD IN ACCORDANCE WITH ICC ESR #3187
2. ADD HILTI KWIK BOLT TZ ANCHOR IN ACCORDANCE WITH ICC ESR #1917
LOCATION ZONE
EFFECTIVE
WIND AREA (SF)
ULTIMATE DESIGN WIND
PRESSURE
(PSF)
ROOF
WALLS
5 5 a = 4'-10" a a h a a
-44.2,+16.0
-37.4,+16.0
-34.5,+16.0
-25.4,+16.0
-25.4,+16.0
-25.4,+16.0
-58.3,+16.0
-49.6,+16.0
-45.8,+16.0
-58.3,+16.0
-49.6,+16.0
-45.8,+16.0
-27.5, +25.4
-24.9, +22.8
-23.8,+21.6
1'
6h 6h
.2 h
1'
-33.8,+25.4
-28.6,+22.8
-26.4,+21.6 h = 48'-10"
GENERAL STRUCTURAL NOTES: (CTD)
EXISTING CONDITIONS
3.1 AS WITH ANY WORK AFFECTING EXISTING CONSTRUCTION, UNFORESEEN CONDITIONS ARE UNAVOIDABLE WITHOUT
DEMOLISHING OTHERWISE SERVICEABLE CONSTRUCTION, DISRUPTING OCCUPIED OPERATIONS AND INCURRING SIGNIFICANT COST FOR CLOSE UP EXAMINATION AND NON-DESTRUCTIVE TESTING DURING THE DESIGN STAGE.
3.2 WITH THE PASSAGE OF TIME SINCE THE CREATION OF AS-BUILT DRAWINGS AND/OR THE DESIGNERS SURVEY, BOTH CONCEALED AND VISIBLE CONDITIONS MAY HAVE CHANGED DUE TO ALTERATIONS, ADDITIONS, RENOVATIONS AND
DETERIORATION.
3.3 PRIOR TO THE COMMENCEMENT OF ANY WORK IN PREPARATION OF CONSTRUCTION RELATED ACTIVITIES, INCLUDING BUT NOT LIMITED TO SHOP DRAWING PREPARATION, ALL EMBEDDED AND CONCEALED ITEMS LIKELY TO BE ENCOUNTERED DURING CONSTRUCTION SHALL BE LOCATED AND MARKED ON THE SURFACE. THIS WORK SHALL BE ACCOMPLISHED BY DESTRUCTIVE AND/OR NON-DESTRUCTIVE MEANS WITHOUT IMPAIRING THE STRUCTURAL INTEGRITY OF THE ASSOCIATED MEMBERS. SHORING AS REQUIRED SHALL BE DESIGNED BY A PROFESSIONAL STRUCTURAL ENGINEER, LICENSED IN THE STATE OF THE PROJECT, AND FURNISHED AND INSTALLED AT NO
ADDITIONAL COST.
3.4 EXISTING CONDITIONS THAT INTERFERE OR OTHERWISE AFFECT THE DESIGN, CONSTRUCTION OR SERVICEABILITY OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER, INCLUDING PLAN AND SECTION SKETCHES PREPARED BY A LICENSED SURVEYOR, IMMEDIATELY FOR RESOLUTION. THE CONTRACTOR SHALL ALLOW TWO CALENDAR WEEKS IN THE SCHEDULE FOR DESIGN RESOLUTION OF THE INTERFERENCE AFTER ALL INFORMATION ABOUT THE INTERFERENCE, INCLUDING SIZE, LOCATION AND FUNCTION OF THE EMBEDMENT, HAS
BEEN RECEIVED BY THE STRUCTURAL ENGINEER.
STEEL ROOF DECKING NOTES
1.1 ROOF DECK SHALL BE AS SPECIFIED ON THE PLANS IN ACCORDANCE WITH THE STEEL DECK
INSTITUTE. DECK SHALL HAVE A GALVANIZED FACTORY FINISH. TOUCH UP IN FIELD IN
ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS.
1.2 ROOF DECKING SHALL BEAR A MINIMUM OF 1 ½" ON SUPPORTS AND SHALL BE LAPPED A
MINIMUM OF 2".
1.3 ROOF DECKING SHALL BE FASTENED TO COLD FORMED STEEL TRUSSES WITH # 12 SELF
TAPPING SCREWS AT A MAXIMUM SPACING OF 6" O.C. (36/4 PATTERN) AT ENDS OF SHEETS
AND AT INTERMEDIATE SUPPORTS FOR A DISTANCE OF 3'-0" FROM THE EXTERIOR OF THE
BUILDING AND A MAXIMUM OF 6" O.C. (36/4 PATTERN) AT ALL OTHER INTERMEDIATE
SUPPORTS. FASTENERS SHALL BE INSTALLED WITH A MINIMUM EDGE DISTANCE OF 1".
1.4 ROOF DECKING SIDE LAPS SHALL BE FASTENED WITH (3) #10 TEK SELF DRILLING SELF
TAPPING SCREW PER SPAN. BUTTON PUNCH SIDE LAPS ARE NOT PERMISSIBLE.
REINFORCED CONCRETE NOTES
1.01 CONCRETE DESIGN IS IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE, ACI 318.
1.02 CONCRETE WORK SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH THE FIELD REFERENCE MANUAL: STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE ACI 301 WITH SELECTED ACI AND ASTM
REFERENCES (SP-15 )
1.03 SUBMIT REINFORCING STEEL SHOP DRAWINGS AND RECEIVE APPROVAL PRIOR TO FABRICATION OF SAME.
1.04 ALL CONCRETE SHALL BE NORMAL WEIGHT (145PCF) AND HAVE A MINIMUM 28-DAY COMPRESSIVE STRENGTH
AS FOLLOWS UNLESS NOTED OTHERWISE:
A. F'c = 4000 PSI
1.05 CONCRETE MIX DESIGN SUBMITTAL REQUIREMENTS:
A. CEMENT: AMOUNT PER CUBIC YARD AND SUPPLIER.
B. FLYASH: AMOUNT PER CUBIC YARD, SUPPLIER, A HISTORY OF SUCCESSFUL USE OF FLYASH CONCRETE IN
SIMILAR APPLICATIONS.
C. AGGREGATE: AMOUNT PER CUBIC YARD, TYPE AND COMPOSITE GRADATION ANALYSIS INCLUDING BOTH
COARSE AND FINE.
D. WATER: AMOUNT PER CUBIC YARD AND WATER/CEMENT RATIO.
E. ADMIXTURES: TYPE, AMOUNT PER CUBIC YARD, PRODUCT DATA INDICATING ASTM COMPLIANCE AND
CHLORIDE ION CONTENT.
F. COMPRESSIVE TESTS OF PAST USAGE OF THE SUBMITTED MIX DESIGN INDICATING THE SAME MIX DESIGN
CODE.
1.06 WHEN STRENGTH DATA FROM FIELD EXPERIENCE OR TRIAL MIXTURES ARE NOT AVAILABLE, CONCRETE MIX
DESIGN SHALL COMPLY WITH THE FOLLOWING:
A. 3000 PSI NORMAL WEIGHT CONCRETE SHALL BE BASED ON A MAXIMUM AGGREGATE SIZE OF 1 IN., MAXIMUM WATER/CEMENT RATIO OF 0.58 FOR NON-AIR-ENTRAINED, CONCRETE AND A MAXIMUM SLUMP OF 4IN.
B. THE MAXIMUM SLUMPS SPECIFIED ABOVE SHALL NOT BE EXCEEDED PRIOR TO THE ADDITION OF WATER
REDUCING ADMIXTURES REGARDLESS OF THE EXISTENCE OF TEST DATA.
C. AIR ENTRAINED CONCRETE SHALL BE USED FOR EXTERIOR EXPOSED CONCRETE IN ACCORDANCE WITH THE
FOLLOWING:
1. SEVERE FREEZING EXPOSURE (F3) BASED ON THE MAXIMUM NOMINAL AGGREGATE SIZE:
a. 3/4": 6 % + 1-1/2%
b. 1": 6 % + 1-1/2%
c. 1-1/2": 5.5 % + 1-1/2%
2. MODERATE FREEZING EXPOSURE (F2) BASED ON THE MAXIMUM NOMINAL AGGREGATE SIZE:
a. 3/4": 5 % + 1-1/2%
b. 1": 4.5 % + 1-1/2%
c. 1-1/2": 4.5 % + 1-1/2%
3. MILD FREEZING EXPOSURE (F0 AND F1) BASED ON THE MAXIMUM NOMINAL AGGREGATE SIZE:
a. 3/4": 3.5 % + 1-1/2%
b. 1": 3 % + 1-1/2%
c. 1-1/2": 2.5 % + 1-1/2%
E. NORMAL WEIGHT AGGREGATE SHALL COMPLY WITH ASTM C 33.
F. AGGREGATE FOR FLATWORK SHALL BE WELL GRADED INCLUDING FINE, INTERMEDIATE AND COARSE
AGGREGATE UNLESS OTHERWISE SPECIFIED.
G. WHEN PERMITTED, THE WEIGHT OF CLASS C FLYASH SHALL NOT EXCEED 25% OF THE WEIGHT OF CEMENT
PLUS POZZOLAN.
1.08 CONCRETE SHALL BE TESTED IN ACCORDANCE WITH ACI 301 AND THE SPECIFICATIONS, WHEN PROVIDED, FOR
COMPLIANCE WITH THE CONTRACT DOCUMENTS. AT A MINIMUM, CONCRETE SPECIMENS SHALL BE TAKEN FOR EACH MIX DESIGN PLACED IN A DAY. CONCRETE TEST REPORTS SHALL BE AVAILABLE ON SITE FOR INSPECTION.
1.09 ALL STEEL REINFORCEMENT SHALL CONFORM WITH THE FOLLOWING:
A. DEFORMED BARS SHALL CONFORM WITH ASTM A 615 GRADE 60.
B. DEFORMED BARS THAT WILL BE WELDED SHALL CONFORM TO ASTM A 706 GRADE 60. WELDING SHALL BE
IN ACCORDANCE WITH AWS D1.4 STRUCTURAL WELDING CODE.
REINFORCED CONCRETE NOTES (CTD.):
1.10 PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE. SPLICE ONLY AS SHOWN OR APPROVED.
STAGGER SPLICES WHERE POSSIBLE. DOWELS SHALL MATCH SIZE AND SPACING OF THE SPECIFIED REINFORCEMENT AND SHALL BE LAPPED WITH TENSION SPLICES. UNLESS OTHERWISE NOTED, ALL REINFORCING SHALL BE CONTACT LAP SPLICED WITH A CLASS B SPLICE IN ACCORDANCE WITH ACI 318-19. FOR BARS WITH A MINIMUM COVER AND SPACING GREATER THAN 2.0DB AND 3.0DB (DB = BAR DIAMETER) RESPECTIVELY, THE MINIMUM SPLICE LENGTH, EXPRESSED IN BAR DIAMETERS, SHALL NOT BE LESS THAN SPECIFIED IN THE REBAR SPLICE SCHEDULE. SPLICE LENGTHS SHALL BE INCREASED BY A FACTOR OF 1.3 FOR TOP REINFORCEMENT AND WHEN LIGHTWEIGHT CONCRETE IS USED. LAP WELDED WIRE FABRIC (WWF) ONE
SPACE PLUS 2 IN. ON ALL SIDES AT SPLICES.
1.11 ALL DOWELS AND TERMINATING BARS SHALL HAVE A STANDARD 90-DEG HOOK UNO.
1.12 ALL HORIZONTAL REINFORCING SHALL BE CONTINUOUS AROUND CORNERS, THROUGH CONTROL JOINTS, AND
THROUGH CONSTRUCTION JOINTS UNO.
1.13 CONCRETE COVER AT REINFORCEMENT:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH -3 IN.
B. FORMED CONCRETE EXPOSED TO WEATHER OR EARTH:
1. (#5 AND SMALLER) -1½ ".
2. (#6 TO #18) -2".
3. ALL OTHER -1 ½".
1.14 MINIMUM CONCRETE COVER FOR REINFORCEMENT
A. SLABS: 2 IN.
B. WALLS: 2 IN.
1.15 CONCRETE SHALL RECEIVE THE FOLLOWING FINISHES:
A. EXTERIOR SLABS - BROOM FINISH IN DIRECTION OF SLOPE.
B. ALL OTHER CONCRETE - STEEL TROWEL FINISH
1.16 ALL CONCRETE SHALL BE CONSOLIDATED BY VIBRATION, SPADING, RODDING, OR FORKING SO THAT THE CONCRETE IS THOROUGHLY WORKED AROUND THE REINFORCEMENT, AROUND EMBEDDED ITEMS, AND INTO CORNERS OF FORMS, ELIMINATING ALL AIR OR STONE POCKETS WHICH MAY CAUSE HONEYCOMBING, PITTING, OR PLANES OF WEAKNESS.IF VIBRATORS, OF ADEQUATE SIZE, ARE USED THEY SHALL BE INSERTED AND WITHDRAWN AT POINTS APPROXIMATELY 18 INCHES APART. AT EACH INSERTION, THE DURATION SHALL BE SUFFICIENT TO CONSOLIDATE THE CONCRETE BUT NOT SUFFICIENT TO CAUSE SEGREGATION (GENERALLY
FROM 5 TO 15 SECONDS).
1.17 MAINTAIN CONCRETE AFTER PLACEMENT WITH MINIMAL MOISTURE LOSS AT RELATIVELY CONSTANT TEMPERATURE FOR THE PERIOD NECESSARY FOR HYDRATION OF CEMENT AND HARDENING OF CONCRETE (NOT LESS THAN 7 DAYS). COMPLY WITH THE REQUIREMENTS OF ACI 308 - STANDARD PRACTICE FOR CURING CONCRETE; AMERICAN CONCRETE INSTITUTE. A COMBINATION CURING AND SEALING COMPOUND SHALL BE APPLIED AFTER THE CONCRETE HAS BEEN FINISHED OR THE FORMS REMOVED. COMPOUND SHALL BE IN ACCORDANCE WITH ASTM C309, LATEST ADOPTED EDITION, TYPE I, CLASS B. (W.R. MEADOWS CS-309).
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Revisions:
STRUCTURAL NOTES REPLACE AIR HANDLERS IN BUILDING 1
VAMC MARION, IL
S001
675A5-22-103
03-07-2025
BID DOCUMENTS
DCASLW
PLAN
NORTH
TRUE
NORTH
KEY PLAN
NTS
PROJECT AREA
I J K L M
I.3
R E
F 1'
8"
R E
F
R E
F
R E
F
REF
3' - 9"
REF
8' - 9"
REF
9' - 0"
REF
4' - 9"
REF
12' - 3"
EXISTIN
G P
ENTHOUSE
STRUCTURE TO BE D
EMOLISHED
EXIST STEEL COLUMN
TO BE DEMOLISHED
(E
W
X
(E
W
X
(E) - W10X22
(E
W
X
(E
W
X
(E) - W10X19
(E
W
X
(E
W
X
(E) - W12X30
SHORE EXISTING STEEL
BEAM PRIOR TO
COLUMN REMOVAL
(E) - W10X22
R E
F
/2
EXISTING POST TO
BE DEMOLISHED
EXISTING POST TO
BE DEMOLISHED
DENOTES EXISTING PENTHOUSE STRUCTURE TO BE
DEMOLISHED
DENOTES EXIST STEEL BEAM TO BE DEMOLISHED
DENOTES EXISTING STEEL BEAM
DENOTES EXISTING CONCRETE FRAMING BELOW
DENOTES CONCRETE DEMOLITION BETWEEN EXIST PAN
JOISTS. FIELD VERIFY EXTENT OF DEMOLITION.
1. SHORING DESIGN AND CONSTRUCTION SHALL BE BY THE CONTRACTOR
AND SUBMITTED FOR REVIEW PRIOR TO COMMENCING WORK
2. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
4. NEW ROOF SLAB CORE PENETRATIONS SHALL BE ALLOWED FOR PIPING
PROVIDED PENETRATIONS DO NOT DAMAGE EXISTING CONCRETE BEAMS
OR PAN JOIST WEBS. PROVIDE A MINIMUM 18" SPACING BETWEEN
PENETRATIONS AND MAXIMUM CORE DIAMETER OF 12". COORDINATE
PENETRATION LOCATIONS WITH MECHANICAL ELECTRICAL AND PLUMBING
DRAWINGS AND EXISTING CONDITIONS PRIOR TO COMMENCING WORK.
I J K L M
I.3
REF
12' - 6"
REF
9' - 0"
REF
4' - 9"
REF
12' - 3"
R E
F 1'
8"
R E
F
R E
F
R E
F
R E
F
/2
E X
IS
T
C O
N C
R E
TE
J
O
IS
T
(E
R
B x2
(E
R
B 8x
(E
R B
8x
(E
R
B 8x
(E
R B
8x
(E
R
B 8x
(E
R
B x2
(E
R
B x2
(E
R
B 8x
(E
R
B 8x
(E) - 17 1/2 x 12
(E) - 12 x 12
(E) - 12 x 12
(E) - 12 x 12
(E) - 12 x 12
(E) - 12 x 12
REF
3' - 9"
HSS4X4X5/16
HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4HSS4X4X1/4
HSS4X4X1/4
HSS4X4X5/16
S501
4 TYP
(E) - W10X22
(E
W
X
(E
W
X
S503
S503
S503
S503
SIM
S201
DENOTES NEW METAL STUD WALL
DENOTES EXISTING CONCRETE FRAMING BELOW
1. T/STL PENTHOUSE PLATFORM = +2'- 3" FROM EXISTING ROOF
2. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL
FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS
PRIOR TO SUBMISSION OF SHOP DRAWINGS
4. (E)-XxXX DENOTES EXISTING STRUCTURAL MEMBER
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Revisions:
PENTHOUSE DEMO AND NEW
PENTHOUSE FRAMING PLANS
REPLACE AIR HANDLERS IN BUILDING 1
VAMC MARION, IL
S101
675A5-22-103
03-07-2025
BID DOCUMENTS
DCASLW
3/16" = 1'-0"S101
EXISTING PENTHOUSE AND
ROOF FRAMING DEMOLITION PLAN
EXIST. PENTHOUSE DEMO PLAN LEGEND EXIST. PENTHOUSE DEMO PLAN NOTES
3/16" = 1'-0"S101
2 PENTHOUSE PLATFORM FRAMING PLAN
PENTHOUSE PLATFORM
FRAMING PLAN LEGEND
PENTHOUSE PLATFORM
FRAMING PLAN NOTES
I J K L M
REF
12' - 6"
REF
9' - 0"
REF
4' - 9"
REF
12' - 3"
R E
F
R E
F
R E
F
/2
3N16 STEEL
ROOF DECK
W12X14
W12X14
E O
D 1'
0"
SLOPE
I.3
EQ EQ EQ
W12X14
W12X14
E X
TE
N
S
IO
N
4' -0
O
.C . M
A X
K
W
/ R
TO
P
C H
O R
D
E X
TE
N
S
IO
N
4' -0
O
.C . M
A X
K
W
/ R
TO
P
C H
O R
D
E X
TE
N
S
IO
N
4' -0
O
.C . M
A X
K
W
/ R
TO
P
C H
O R
D
W
X
W
X
W
X
W
X
W
X
W
X
S201
S201
S201
S201
E O
D
3/ 4"
EOD
2' - 9"
EOD
1' - 0"
T/ S
TL
+1 4'
-6
/8
T/ S
TL
+1 4'
-2
/1 6"
HSS6X2X1/4 LSH TYP
S501
TYP
S501
S501
S501
S502
TYP
S502
TYP
S502
S502
TOP CHORD EXTENSION TYP
S502
S502
S201
TYP
KEY PLAN
NTS
PROJECT AREA
I J K L M
REF
12' - 6"
REF
9' - 0"
REF
4' - 9"
REF
12' - 3"
R E
F 1'
8"
R E
F
R E
F
R E
F
R E
F
/2
W10X22
W
X
W10X22
W
X
W10X26
I.3
REF
3' - 9"
S201
S201
S201
S201
W
X
W
X
W10X22
W10X19
W8X10
W8X10
W8X10
W8X10
W8X10
W8X10
W8X10
W10X19
W10X19
W10X19
W10X19
W10X19
W
X
W8X10
W8X10
W8X10
W8X10
W8X10
W8X10
W8X10
W
X
W
X
W10X22
W
X
W
X
W
X
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
HSS4X4X1/4
6'
0"
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
E Q
W
X
W
X
W
X
REF
7' - 2 1/4"
REF
5' - 0"
H S
S 8X
6X 3/
L
S V
H S
S 8X
6X 3/
L
S V
H S
S 8X
6X 3/
L
S V
HSS8X4X3/8 LSV @
COLUMN LINES TYP UNO
L2X2X1/4 TYP UNO
L4x4x3/8 TYP
S501
S501
TYP.
TYP.
L4x4x1/4 HORIZONTAL
BRACE TYP
S501
S502
S502
S501
1' - 9"
1' - 9 1/2"
W8X10
W8X10 W8X10
W8X10
W8X10
W8X10
W8X10
W8X10 W8X10
W8X10
W8X10
W8X10
2'
3/
8"
1'
1"
1'
9"
5'
7"
2'
8"
2'
9"
2'
2"
1'
9"
2'
2"
2'
2"
5'
5"
1'
- 1
1"
(E) - W10X22
(E
W
X
(E
W
X
(E) - W10X22
(E) - W8X24
(E) - W8X24
(E) - W8X24
S201
HSS6X2X1/4
HSS6X2X1/4
HSS6X2X1/4
HSS6X2X1/4
S503
STAIR, SEE ARCH.
S501
TYP
SEE NOTE 6
SEE NOTE 6
DENOTES NEW GALVANIZED STEEL GRATING
DENOTES BRACED FRAME
BEAM
DENOTES SPAN DIRECTION OF W19-4(1x3/16) GRATING
DENOTES NEW HORIZONTAL BRACING
DENOTES MOMENT CONNECTION. SEE DETAILS.
DENOTES SPLIT LOCATIONS, SEE NOTE 4X' - X" *
1. T/STL PENTHOUSE PLATFORM = +2'- 3" FROM EXISTING ROOF
2. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY
3. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
4. COORDINATE AHU SPLIT SECTION DIMENSIONS WITH ACTUAL EQUIPMENT
PROVIDED.
5. (E)-XxXX DENOTES EXISTING STRUCTURAL MEMBER
6. PROVIDE L2x2x1/4 FRAME AS REQUIRED AT FLOOR DRAIN. WELD END OF
ANGLES TO FLOOR BEAMS WITH 3/16 ALL AROUND FILLET WELDS.
OPENING WIDTH JAMB SIZE HEAD/SILL SIZE JAMB TOP CONNECTOR JAMB BASE CONNECTOR
LIGHT GAUGE FRAMED OPENING SCHEDULE FOR BLAST LOADING
(REQUIREMENTS FOR MISSION CRITICAL PROTECTED)
NOTES:
1. SIZES SHOWN ARE FOR BLAST LOADING ONLY. LIGHT GAUGE VENDOR SHALL DESIGN ALL LIGHT GAUGE
FOR ALL OTHER CODE PRESCRIBED LOADS AND DEFLECTIONS AS SHOWN ON THE DRAWINGS.
2. ALL MEMBERS AND CONNECTORS SHOWN SHALL BE 50 KSI.
3. CONNECTORS AND ANCHORS SHOWN ARE DESIGN BASIS.
4. BASE CONNECTOR SHALL HAVE (1) 1/2" DIAMETER x 3 5/8" EMBED HILTI KWIK BOLT TZ ANCHOR AT EACH
CONNECTOR TO CONCRETE AND (6) #12 SELF-DRILLING SCREWS TO THE JAMB. IN CONDITIONS WHERE EXISTING ELEVATED CONCRETE BASE DOES NOT PROVIDE 6" THICKNESS PROVIDE THROUGH BOLT SAME SIZE AS NOTED ABOVE THROUGH THE CONCRETE WITH 3/8" x 3" SQUARE PLATE ON THE UNDER SIDE OF
CONCRETE. DOUBLE NUT THROUGH BOLT.
5. TOP CONNECTOR SHALL BE CONNECTED TO THE STUD WITH (4) #12 SELF DRILLING SCREWS. ATTACH CONNECTOR TO STEEL FRAMEWORK WITH (3) 0.157" DIAMETER POWDER DRIVEN FASTENERS WITH A
MINIMUM SPACING OF 1" AND MINIMUM EDGE DISTANCE OF 1/2".
6. BUILT UP STUDS SHALL NOT BE BACK TO BACK. ADD TRACK, SAME GAUGE AS STUD, AS REQUIRED TO
BUILD UP MEMBER AND PROVIDE FLAT SURFACE FOR ROUGH OPENING.
7. MEMBERS ARE DESIGNED BASED ON VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL FOR
MISSION CRITICAL PROTECTED FACILITIES, 2023 EDITION.
8. PROVIDE A MINIMUM OF 3" EDGE DISTANCE TO POST INSTALLED ANCHOR NOTED IN NOTE 3 ABOVE.
WALL HEIGHT STUD SIZE STUD SPACING
TOP CONNECTOR
TO STEEL
BASE CONNECTOR TO
CONCRETE
LIGHT GAUGE WALL FRAMING SCHEDULE FOR BLAST LOADING
(REQUIREMENTS FOR MISSION CRITICAL PROTECTED)
STUDS AT METAL WALL PANEL LOCATIONS
UP to 15'-0" (2) VERTICLIP SL600-68 (1) STIFFCLIP CL600-118(2) 600S200-97 1'-0"
NOTES:
1. SIZES SHOWN ARE FOR BLAST LOADING ONLY. LIGHT GAUGE VENDOR SHALL DESIGN ALL LIGHT
GAUGE FOR ALL OTHER CODE PRESCRIBED LOADS AND DEFLECTIONS AS SHOWN ON THE DRAWINGS.
2. ALL MEMBERS AND CONNECTORS SHOWN SHALL BE 50 KSI.
3. CONNECTOR AND ANCHOR TYPE SHOWN ARE DESIGN BASIS.
4. STUD BASE CONNECTORS BELOW PLATFORM LEVEL SHALL HAVE (1) 1/2" DIAMETER x 3 5/8" EMBED HILTI
KWIK BOLT TZ ANCHOR TO CONCRETE AND (6) #12 SDS TO STUD. IN CONDITIONS WHERE EXISTING ELEVATED CONCRETE BASE DOES NOT PROVIDE 6" THICKNESS PROVIDE THROUGH BOLT SAME SIZE AS NOTED ABOVE THROUGH THE CONCRETE WITH 3/8" x 3" SQUARE PLATE ON THE UNDER SIDE OF
CONCRETE. DOUBLE NUT THROUGH BOLT.
5. ALL STUD TOP CONNECTORS SHALL BE CONNECTED TO THE STUD WITH (4) #12 SELF DRILLING SCREWS. ATTACH CONNECTOR TO STEEL FRAMEWORK WITH (2) 0.157" DIAMETER POWDER DRIVEN
FASTENERS WITH A MINIMUM SPACING OF 1" AND MINIMUM EDGE DISTANCE OF 1/2".
6. BASE CONNECTOR AT STUDS NOT ATTACHED TO CONCRETE SHALL BE CONNECTED TO THE STUD WITH
(6) #12 SELF DRILLING SCREWS AND ATTACHED TO STEEL FRAMEWORK WITH (3) 0.157" DIAMETER POWDER DRIVEN FASTENERS WITH A MINIMUM SPACING OF 1" AND MINIMUM EDGE DISTANCE OF 1/2"
7. MEMBERS ARE DESIGNED BASED ON VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL FOR
MISSION CRITICAL PROTECTED FACILITIES, 2023 EDITION.
8. BUILT UP STUDS SHALL NOT BE BACK TO BACK. ADD TRACK, SAME GAUGE AS STUD, AS REQUIRED TO
BUILD UP MEMBER INTO BOX SHAPE.
UP TO 6'-0" (4) 600S250-97 (2) 600S200-97 (2) VERTICLIP SL600-68 (2) STIFFCLIP CL600-118
(2) VERTICLIP SLB600-68
AT BYPASS STUD
CONDITIONS
BASE CONNECTOR TO STEEL
(1) STIFFCLIP CL600-118
PLAN
NORTH
TRUE
NORTH
1. (X'-X") INDICATES T/STL ELEVATION RELATIVE TO 0'-0".
2. COORDINATE T/STL WITH JOIST SEAT DEPTH REQUIRED.
3. PROVIDE UPLIFT BRIDGING AT FIRST BOTTOM CHORD PANEL POINT.
4. DO NOT PRIME STEEL THAT WILL RECEIVE SPRAY-ON FIRE PROOFING
5. REF. DENOTES FOR REFERENCE ONLY, CONTRACTOR SHALL FIELD VERIFY
6. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO
SUBMISSION OF SHOP DRAWINGS
BRACED FRAME
BEAM
EDGE OF DECK
JOIST BRIDGING
SLOPE ARROW WITH SLOPE (1/4" PER FT MIN.)
DENOTES DECK SPAN DIRECTION & DECK DESCRIPTION
DENOTES BOTTOM FLANGE BRACE
DENOTES 250 LB JOIST POINT LOAD
SLOPE
3/16" = 1'-0"S102
2 PENTHOUSE ROOF FRAMING PLAN
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Revisions:
PLATFORM ROOF FRAMING
PLAN
REPLACE AIR HANDLERS IN BUILDING 1
VAMC MARION, IL
S102
675A5-22-103
03-07-2025
BID DOCUMENTS
DCASLW
3/16" = 1'-0"S102
1 PENTHOUSE PLATFORM FRAMING PLAN
PENTHOUSE PLATFORM
FRAMING PLAN LEGEND
PENTHOUSE PLATFORM
FRAMING PLAN NOTES
PENTHOUSE ROOF FRAMING PLAN NOTES PENTHOUSE ROOF FRAMING PLAN LEGEND
K I.3
REF
17' - 9"
S502
S502
OPP. HAND
HSS4X4X1/4
W12X14
W10X22
H S
S 4X
4X 5/
16 H S
S 4X
4X 1/
(E) - W10X22
S503
H S
S 4X
4X 1/
T=C=9.1K
T/STL
SEE PLAN
KI.3
REF
17' - 9"
S502
S502
TYP
W12X14
HSS
4X
4X 1/
HSS4X4X1/4
W10X22
H S
S 4X
4X 5/
H S
S 4X
4X 1/
HSS4X4X1/4
HSS
4X
4X 1/
T= C=6
.3 K
T=C=7.0K
T/STL
SEE PLAN
S502
5 TYP
4 5
REF
20' - 0"
S502
S502
TYP
W12X26
HSS4X
4X
1/
4 HSS4X4X1/4
W12X14
H S
S 4X
4X 5/
H S
S 4X
4X 1/
T= C=5
.7 K
T=C=5.7K
T/STL
SEE PLAN
S501
REF
20' - 2 1/2"
S502
S502
TYP
W12X14
H S
S 4X
4X 1/
W12X26
H S
S 4X
4X 1/
HSS4X
4X
1/
HSS4X4X1/4
T= C=4
.8 K
T=C=4.8K
T/STL
SEE PLAN
S501
HSS6X4X1/4
H S
S 6X
2X 1/
H S
S 6X
2X 1/
H S
S 6X
2X 1/
HSS6X4X1/4
H S
S 6X
2X 1/
HSS6X6X1/4
H S
S 6X
2X 1/
S5023
S502
S502
S502
HSS8X6X3/8 LSV HSS8X6X3/8 LSV
HSS8X4X3/8
LSH
LSH
SEE NOTE 1
8' - 6" 2' - 4 1/4" 10 3/4"
SEE NOTE 1
9' - 4"
S E
E N
O
TE
4'
6"
EQ EQ
TYP.
TYP.
TYP.
S502
S502
6 TYP. TYP.
TYP.
T/STL
SEE PLAN
S E
E N
O
TE
8'
1/
4"
S E
E N
O
TE
3'
1/
4"
NOTE 1:
COORDINATE WITH ACTUAL
LOUVER AND DOOR PROVIDED
3380 Trickum Road
Woodstock, GA. 30188 770-517-5507 voice 770-517-5508 fax
Bldg. 500, Ste. 100 www.ieiusa.com
INCORPORATED
INNOVATIVE
ENGINEERING
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved: Project Director
Project Title:
1 2 3 4 5 6 7 8 9
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Revisions:
FRAMING ELEVATIONS REPLACE AIR HANDLERS IN BUILDING 1
VAMC MARION, IL
S201
675A5-22-103
03-07-2025
BID DOCUMENTS
DCASLW
3/8" = 1'-0"S201
1 BRACE ELEVATION ALONG GRID LINE "5"
3/8" = 1'-0"S201
2 BRACE ELEVATION ALONG GRID LINE "2"
3/8" = 1'-0"S201
4 BRACE ELEVATION ALONG GRID LINE "K"
3/8" = 1'-0"S201
5 BRACE ELEVATION ALONG GRID LINE "I.3"
3/8" = 1'-0"S201
3 FRAMING ELEVATION ALONG GRID LINE "K"
R 1/ 2"
TYP
1/2" TYP
T O
N E
A R
E S
T 1/
4" k
R O
U N
D E
D U
P bf
T O
N E
A R
E S
T 1/
4" k, R O
U N
D E
D U
P
ROUND UP TO NEAREST 1/4"
(b /2 + 1/2") f
STEEL BEAM,
SEE PLAN
DOUBLE ANGLES
(5/16" THICKNESS
MIN.)
3" MAX.
3" S
P A
C E
S
3" M
A X
CL
3/4" dia ASTM A-325 BOLTS TYP.
(2) REQUIRED AT W8 AND W10 MEMBERS,
(3) AT W12 MEMBERS
HORIZONTAL
BRACE, SEE PLAN
3/16
TOP FLANGE OF
WIDE FLANGE BEAM
WIDE FLANGE BEAM
1/
2"
1/ 2"
1/4'' CAP PLATE AT
TOP OF COLUMN
STEEL COLUMN,
SEE PLAN
3/8"x4"x0'-9" PLATE
LONG SIDE VERTICAL
(3) 3/4''Ø A325 BOLTS
1/2"
3" 3"
2 1/2"
T/ STL
SEE PLAN
CL
3/16
1/8
1 1/2"
1/
2"
3"
3"
STEEL COLUMN,
SEE PLAN
1/4
13/16'' DIA. HOLE FOR 1/2"
ANCHOR BOLTS
3/4"x10"x10" BASE
PLATE, U.N.O.
CL
CL
NOTES:
1. USE (4) 1/2" DIA.x2 3/4" EMBED HILTI HY200
ANCHOR TYP. U.N.O.
2. PROVIDE 1 1/2" NON-SHRINK GROUT
UNDER BASEPLATE.
EXISTING
CONCRETE
COLUMN BELOW
1/4'' CAP PLATE AT TOP
OF COLUMN
HSS COLUMN,
SEE PLAN
3/8"x4"x0'-9" PL.
(3) 3/4''Ø ASTM A-325 BOLTS
1/8''
1/2"
3" 3"
T/ STL
SEE PLAN
CL
2 1/2"
BEAM,
SEE PLAN BEAM,
SEE PLAN
3/16
TYP.
HSS COLUMN,
SEE PLAN
3/8"x4"x0'-9" PL.
3/4"Ø ASTM A-325 BOLTS TYP.
(2) REQUIRED AT W8 AND W10 MEMBERS,
(3) AT W12 MEMBERS
1/2"
3" 3"
T/ STL
SEE PLAN
CL
2 1/2"
BEAM,
SEE PLAN BEAM,
SEE PLAN
3/16
TYP.
K
JOIST SEE
PLAN
BEAM SEE
PLAN
METAL
WALL STUD
GRATING
SEE PLAN BEAM, SEE
PLAN
BEAM SEE
PLAN
EXISTING CONCRETE
PAN JOINT/SLAB AND
ROOF BEAM
EXISTING PAN JOIST AND
SLAB SEE PLANEXISTING
CONCRETE
COLUMN
COLUMN
SEE PLAN
BEAM, SEE
PLAN
1/4
TYP
2L4x4x1/4x6"
LONG TYP
3/16
TYP
3/16
TYP
2' - 9"
2' - 0"
1/4"x3x0'-3" CONT
BENT PLATE
1/4
TYP
3/16
TYP
I.3
JOIST SEE
PLAN
BEAM SEE
PLAN
WALL
STUD SEE
SCHEDULE
GRATING
SEE PLAN
BEAM SEE
PLAN
BEAM SEE
PLAN
BRACING
SEE PLAN
EXISTING
CONCRETE
PARAPET AND
ROOF BEAM
EXISTING PAN JOIST AND
SLAB SEE PLAN
EXISTING
CONCRETE
COLUMN
WALL
STUD SEE
SCHEDULE
C4x5.4 @ EVERY
OTHER…