P01 SOW - Purchase Boiler Safety Valves.docx

DOCX document 32 KB Posted

Attached to
4820--Kunkle (BNOE) Steam-Rated Boiler Safety Valves for the Minneapolis VA Health Care System
Solicitation number
36C26326Q0376
Issued by

About this file

This is a Statement of Work (SOW) for the Minneapolis Veterans Affairs Health Care System to procure eight Kunkle (BNOE) steam-rated boiler safety valves. The contractor must supply three Model 300LNM01-AS valves (160 orifice, 4" inlet x 6" outlet, set to 160 PSI), three Model 300LMK01-AS valves (150 orifice, 3" inlet x 4" outlet, set to 155 PSI), one Model 300LMK01-AS valve (150 orifice, 3" inlet x 4" outlet, set to 160 PSI), and one Model 300LLJ01-AS valve (150 orifice, 2" inlet x 4" outlet, set to 155 PSI). All valves must be steam-rated with cast steel or forged bodies, bolted yoke design, stainless steel nozzles, exposed carbon steel springs rated to 750°F, and 300# inlet and 150# outlet flanges meeting ANSI B16.5 specifications. Each valve must be factory-set and tested to its specified pressure.

The contractor shall provide a one-year warranty from the purchase date and must include the Veterans Affairs Purchase Order Number on all shipping labels and packing lists. Deliveries are accepted Monday through Friday between 7:00 am and 3:00 pm at the Minneapolis VA Health Care System, One Veterans Drive, Minneapolis, Minnesota 55417, excluding federal holidays. Contractors must submit cut sheets detailing all valve specifications with their official offer. This procurement is for materials only with delivery to the hospital loading dock; no security requirements apply.

View the file

Other files

File Type Posted
36C26326Q0376.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

Minneapolis Veteran Affairs Health Care System “Purchase Boiler Safety Valves”

1. Scope:

a. Contractor will provide and ship eight Kunkle (BNOE) steam-rated boiler safety valves to the Minneapolis Veterans Affairs Hospital.

Qty
Model
Orifice size
Connection Size
Variation
Valve Service
Spring Material
Set Pressure
3
300LNM01-AS 160
N
4" inlet x 6” outlet
Standard
Steam ASME section I
Carbon Steel (to 750°F)
160
3
300LMK01-AS 150
M
3" inlet x 4” outlet
Standard
Steam ASME section I
Carbon Steel (to 750°F)
155
1
300LMK01-AS 150
M
3" inlet x 4” outlet
Standard
Steam ASME section I
Carbon Steel (to 750°F)
160
1
300LLJ01-AS 150
L
2½" inlet x 4” outlet
Standard
Steam ASME section I
Carbon Steel (to 750°F)
155

b. Boiler Safety Valves shall meet the following salient characteristics:

· Safety Valves must meet specification listed above.

· Valve must be rated for Steam.

· Body must be Cast steel or forged.

· Bolted Yoke design.

· Stainless Steel Nozzle

· Exposed steel spring that is capable of 750° F.

· Safety Valve Flanges shall be 300# inlet and 150# outlet.

· Each Safety valve shall be factory set and tested to specified pressures listed above.

· Inlet and outlet flanges must meet ANSI B16.5 specifications.

c. Contractor shall provide a 1-year warranty for each valve from the date of purchase.

d. Contractor shall include the Veteran Affairs issued Purchase Order Number on the shipping label or packing list. Without the Purchase order number, the item may not be properly received. Delay in payment or failure to be paid may be the result.

2. Delivery Hours:

a. Monday through Friday from 7:00 am – 3:00 pm. Deliveries are not accepted on the federal holidays listed below:

Observed Federal Holidays:

New Year’s DayMartin Luther King Birthday
Washington’s BirthdayMemorial Day
JuneteenthIndependence Day
Labor DayColumbus Day
Veteran’s DayThanksgiving Day

Christmas Day

3. Delivery Address:

Veteran Affairs Health Care System Attn: Eric Hartung One Veterans Drive Minneapolis, MN 55417

4. Submittals:

a. Contractors shall submit a cut sheet listing all specifications of safety valves listed in their official offer.

5. References:

· Veteran Affairs Boiler Safety Alert Message – Replace cast iron safety valves.

6. Security:

a. Not required. This procurement is for materials only. Items will be delivered to the Minneapolis Veterans Affairs Hospital loading dock.

END