Oliver Middle School Seismic Retrofit - CD - Bid and Permit Set - reduced 250401-01.pdf
PDF 12 MB Posted
- Attached to
- Oliver MS Seismic Retrofit #250304-01
- Solicitation number
- S-P26028-00013192
- Issued by
- Multnomah County, Oregon
About this file
This document is a comprehensive set of construction documents for the Oliver Middle School Seismic Retrofit project, prepared for the Centennial School District in Portland, Oregon. The project involves a voluntary seismic rehabilitation of specific building wings, targeting the central classroom wing, multipurpose room, media center, and front offices. The retrofit is funded by a grant from the Infrastructure Finance Authority, Oregon Business Development Department, through its Seismic Rehabilitation Grant Program. The project is designed to meet structural performance objectives for a Risk Category IV building, specifically aiming to achieve a Life Safety structural performance level and a Hazard-Reduced Non-Structural performance level.
The project's design criteria are based on the American Society of Civil Engineers' "Seismic Rehabilitation of Existing Buildings" (ASCE 41-17) standard, with a focus on improving the building's seismic resistance. The retrofit will involve installing new plywood diaphragms, in-plane and drag members, wood shear walls, and a new seismic gap to isolate the structure from adjacent building parts. The design approach acknowledges that despite the retrofit, some lateral force deficiencies may remain, including roof diaphragms, out-of-plane attachments, vertical lateral resisting elements, foundation elements, and non-structural components. The total project area encompasses approximately 2,979 square feet, which is less than 50 percent of the total building area, and is classified as a Level 2 Alteration under the building code.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Oliver MS Seismic Retrofit - Project Manual 250401-01.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SCOPE:
THE SCOPE OF THIS PROJECT INVOLVES THE VOLUNTARY SEISMIC REHABILITATION OF OLIVER
MIDDLE SCHOOL, SPECIFICALLY TARGETING THE CENTRAL CLASSROOM WING, MULTIPURPOSE
ROOM, MEDIA CENTER, AND FRONT OFFICES. THE CURRENT LATERAL SYSTEM RELIES ON
PLYWOOD-SHEATHED DIAPHRAGMS THROUGHOUT THE BUILDING. EXISTING SHEAR WALLS CONSIST
OF REINFORCED CONCRETE SUPPORTED BY REINFORCED CONCRETE FOOTINGS, WITH A
CONCRETE SLAB-ON-GRADE AT THE MULTIPURPOSE ROOM. THE REMAINING PORTIONS OF THE
BUILDING RELY ON DOUBLE-WYTHE, UNREINFORCED CLAY MASONRY EXTERIOR WALLS AND
REINFORCED CONCRETE MASONRY WALLS FOR LATERAL RESISTANCE.
THE VOLUNTARY SEISMIC STRENGTHENING INCLUDES THE INSTALLATION OF NEW PLYWOOD
DIAPHRAGMS AT THE CEILING OF THE MULTIPURPOSE ROOM. IN-PLANE AND DRAG MEMBERS WILL
BE INTRODUCED TO EFFICIENTLY TRANSFER LOADS TO DESIGNATED SHEAR WALL LOCATIONS.
ADDITIONALLY, NEW WOOD SHEAR WALLS WILL BE ADDED TO REDUCE THE SPANS OF THE EXISTING
DIAGONALLY SHEATHED DIAPHRAGM. HOLD-DOWNS AND FOOTINGS WILL BE INCORPORATED
WHERE NECESSARY. A NEW SEISMIC GAP WILL BE IMPLEMENTED TO ISOLATE THE STRUCTURE
FROM THE ADJACENT, OUT-OF-SCOPE BUILDING PARTS.
AS THIS IS A VOLUNTARY SEISMIC RETROFIT, MATERIAL TESTING WAS NOT CONDUCTED TO MEET THE COMPREHENSIVE CRITERIA OUTLINED IN ASCE 41-17. THE VOLUNTARY SEISMIC REHABILITATION
IS FUNDED BY A GRANT AWARDED TO THE CENTENNIAL SCHOOL DISTRICT BY THE
INFRASTRUCTURE FINANCE AUTHORITY, OREGON BUSINESS DEVELOPMENT DEPARTMENT,
THROUGH ITS SEISMIC REHABILITATION GRANT PROGRAM. THE STANDARD UTILIZED FOR DESIGN IS THE AMERICAN SOCIETY OF CIVIL ENGINEERS' "SEISMIC REHABILITATION OF EXISTING BUILDINGS"
(ASCE 41-17).
THIS PROJECT HAS BEEN VOLUNTARILY DESIGNED TO MEET THE STRUCTURAL PERFORMANCE
OBJECTIVES FOR A RISK CATEGORY IV BUILDING, DESPITE THE STRUCTURE BEING CLASSIFIED AS RISK CATEGORY III. IT IS NOT THE DISTRICT’S INTENT TO UTILIZE THE BUILDING AS A RISK CATEGORY IV STRUCTURE. THE STRUCTURE HAS BEEN EVALUATED TO MEET THE LIFE SAFETY STRUCTURAL
PERFORMANCE AND HAZARD-REDUCED NON-STRUCTURAL PERFORMANCE LEVEL FOR BSE-2E
LOADING, AND THE IMMEDIATE OCCUPANCY STRUCTURAL PERFORMANCE AND POSITION-
RETENTION NON-STRUCTURAL PERFORMANCE LEVEL FOR BSE-1E LOADING.
THE REHABILITATION OBJECTIVES ARE DEFINED AS:
STRUCTURAL PERFORMANCE LEVEL "LIFE SAFETY" REFERS TO A POST-EARTHQUAKE DAMAGE
STATE IN WHICH SIGNIFICANT DAMAGE TO THE STRUCTURE HAS OCCURRED BUT SOME MARGIN
AGAINST EITHER PARTIAL OR TOTAL STRUCTURAL COLLAPSE REMAINS. SOME STRUCTURAL
ELEMENTS AND COMPONENTS ARE SEVERELY DAMAGED BUT THIS HAS NOT RESULTED IN LARGE
FALLING DEBRIS HAZARDS EITHER INSIDE OR OUTSIDE THE BUILDING. INJURIES MAY OCCUR DURING THE EARTHQUAKE; HOWEVER, THE OVERALL RISK OF LIFE-THREATENING INJURY AS A RESULT OF
STRUCTURAL DAMAGE IS EXPECTED TO BE LOW. IT SHOULD BE POSSIBLE TO REPAIR THE
STRUCTURE; HOWEVER, FOR ECONOMIC REASONS THIS MAY NOT BE PRACTICAL. ALTHOUGH THE
DAMAGED STRUCTURE IS NOT AN IMMINENT COLLAPSE RISK, IT WOULD BE PRUDENT TO IMPLEMENT
STRUCTURAL REPAIRS OR INSTALL TEMPORARY BRACING PRIOR TO RE-OCCUPANCY.
STRUCTURAL PERFORMANCE LEVEL 'IMMEDIATE OCCUPANCY' MEANS THE POST-EARTHQUAKE
DAMAGE STATE IN WHICH ONLY VERY LIMITED STRUCTURAL DAMAGE HAS OCCURRED. THE BASIC VERTICAL AND LATERAL FORCE-RESISTING SYSTEMS OF THE RISK OF LIFE-THREATENING INJURY AS
A RESULT OF STRUCTURAL DAMAGE IS VERY LOW, AND ALTHOUGH SOME MINOR STRUCTURAL
REPAIRS MAY BE APPROPRIATE, THESE WOULD GENERALLY NOT BE REQUIRED PRIOR TO
REOCCUPANCY.
THE DESIGN CRITERIA OUTLINED AND DETAILED IN THE CONSTRUCTION DOCUMENTS DO NOT
ADHERE TO THE CITY OF PORTLAND’S SECTION 24.085.020 PARTS I AND K, WHICH DEFINE BSE-1E AS 75% OF BSE-1N AND BSE-2E AS 75% OF BSE-2N. ADDITIONALLY, AS THIS RETROFIT IS VOLUNTARY, THE STATED PERFORMANCE CRITERIA ARE TARGETS. DESPITE THE RETROFIT, THE FOLLOWING
LATERAL FORCE DEFICIENCIES MAY REMAIN:
• ROOF DIAPHRAGMS AND ASSOCIATED DRAG COLLECTORS
• OUT-OF-PLANE ATTACHMENTS AND SUB-DIAPHRAGMS
• ALL VERTICAL LATERAL RESISTING ELEMENTS INCLUDING BUT NOT LIMITED TO WOOD SHEAR
WALLS, CONCRETE SHEAR WALLS, CMU SHEAR WALLS
• ALL FOUNDATION ELEMENTS INCLUDING BUT NOT LIMITED TO BEARING, OVERTURNING AND
SLIDING
• STRONG BACK COLUMNS AT UNDER-REINFORCED CMU WALLS
• ALL NON-STRUCTURAL COMPONENTS FOUND THROUGHOUT THE AREA OF WORK
• SEISMIC ISOLATION JOINTS
A101
A101
1 Ref
X
N
Room name
150 SF
A101 View Name A1.1
1/4" = 1'-0"
ROOM NAME
ROOM NUMBER
ROOM AREA
KEYNOTE TAG
REVISION SET TAG
W1
DOOR NUMBER
WINDOW/GLAZING
TAG
LEVEL HEAD
SHEET REFERENCE
ELEVATION REFERENCE
EXTERIOR
ELEVATION SYMBOL
SHEET REFERENCE
INTERIOR ELEVATION
REFERENCE
INTERIOR
ELEVATION SYMBOL
SHEET REFERENCE
INTERIOR ELEVATION
REFERENCE
BUILDING & WALL
SECTION
SHEET REFERENCE
DRAWING
REFERENCE
DETAIL
REFERENCE
A101
SHEET REFERENCE
DRAWING
REFERENCE
ENLARGED
PLAN
DESIGNATED AREA
PROJECT NORTH
SHEET REFERENCE
VIEW TITLE
DRAWING SCALE
WALL TYPE TAG
STRUCTURAL
KEYNOTE TAG
CEILING TAG
FLOOR
TRANSITION TAG
CENTER LINE
DELTA w// CURRENT
REVISION NUMBER
PREVIOUS REVISION
CEILING MATERIAL
CEILING HEIGHT
ADDITIONAL NOTES
NOTES
ACT
8'-0"
Remarks
EX#
EX#
ME#
ME#
XX#
XX# FLOOR FINISH
BASE FINISH
ADDITIONAL NOTES
WALL FINISHES
FINISH TAG
TR#
FINISH TAG
DISTANCEXX
DRAWING NUMBER
PLUMBING FIXTURE
& RESTROOM
ACCESSORY TAG
1 Ref
R e f
1 Ref
R e f
X
A101
CEILING ASSEMBLY TAG
ROOF ASSEMBLY TAG
F1 FLOOR ASSEMBLY TAG
C1
R1
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:4
:4
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
G0.00
COVER SHEET
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
E T
OLIVER MIDDLE SCHOOL SEISMIC RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
CONSTRUCTION DOCUMENTS | BID AND PERMIT SET
N
PROJECT NOTES ABBREVIATIONS
SYMBOLS LEGEND
1. ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS SHALL BE FIELD
VERIFIED. THE CONTRACTOR SHALL NOTIFY THE PROJECT TEAM OF ANY
SIGNIFICANT DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS.
2. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION
MEANS AND METHODS. RESPONSIBILITY SHALL INCLUDE BUT NOT LIMITED TO
DEMOLITION AND CONSTRUCTION MEANS AND METHODS, TECHNIQUES,
SEQUENCING, AND SAFETY REQUIRED TO COMPLETE CONSTRUCTION.
3. BEFORE STARTING A SECTION OF WORK THE CONTRACTOR SHALL CAREFULLY
EXAMINE PREPARATORY WORK THAT HAS BEEN EXECUTED. ENSURE THAT WORK
AND ADJACENT RELATED WORK WILL FINISH TO PROPER PLANES AND LEVELS.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL MATERIALS AND
WORKMANSHIP IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND
LOCAL CODES.
5. CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL CONTRACT DOCUMENTS, FIELD
CONDITIONS, AND DIMENSIONS FOR ACCURACY AND CONFIRMING THAT WORK IS
BUILDABLE AS SHOWN BEFORE PROCEEDING WITH THE CONSTRUCTION. IF THERE
ARE ANY QUESTIONS, THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING A
CLARIFICATION FROM THE PROJECT TEAM BEFORE PROCEEDING WITH THE WORK
IN QUESTION OR RELATE WORK.
6. THE CONTRACTOR SHALL NOT SCALE DRAWINGS. WRITTEN DIMENSIONS SHALL
ALWAYS GOVERN. CONTRACTOR REQUIRING DIMENSIONS NOT NOTED SHALL
ALWAYS CONTACT THE PROJECT TEAM FOR SUCH INFORMATION PRIOR TO
PRECEDING WITH WORK RELATED TO THOSE DIMENSIONS
7. THE CONTRACTOR SHALL PROTECT, PATCH, AND REPAIR TO MATCH ANY WALLS,
FLOORS, CEILINGS, AND/OR OTHER SURFACES WHICH MAY BE DISTURBED DURING
THE INSTALLATION OF MECHANICAL, ELECTRICAL, PLUMBING OR OTHER OWNER
WORK.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING
REQUIRED FOR PROPER INSTALLATION OF MATERIAL AND EQUIPMENT. PROVIDE
DEMOLITION AND PATCH/REPAIR IN ALL AREAS (WHETHER SPECIFICALLY SHOWN
OR NOT) TO ACCOMMODATE ALL WORK.
9. IF THE CONTRACTOR ENCOUNTERS A CONDITION NOT COVERED IN THE
CONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL NOTIFY AND RESOLVE THE
ISSUE WITH THE PROJECT TEAM BEFORE COMMENCING ANY WORK.
10. ALL PERMITS ASSOCIATED WITH THE PROJECT SHALL BE PAID AND OBTAINED BY
THE CONTRACTOR.
11. GENERAL CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR
JOB CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF PERSONS AND
PROPERTY AND COMPLIANCE WITH OSHA SAFETY STANDARDS.
12. WHEN PORTIONS OF THE WORK ARE PERFORMED BY THE CONTRACTOR ON A
DESIGN-BUILD BASIS, THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE
DESIGN OF SUCH SYSTEMS AND FOR THE SECURING OF ALL ASSOCIATED PERMITS,.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL
DESIGN BUILD SUB CONTRACTORS.
13. CONTRACTOR SHALL AVOID INTERFERENCE AND CONFLICT WITH THE BUILDING'S
NORMAL OPERATION. CONTRACTOR TO COMPLY WITH THE BUILDING RULES AND
REGULATIONS REGARDING SCHEDULING AND USE OF ELEVATORS AND LOADING
DOCKS FOR DELIVERY AND HANDLING OF MATERIALS, EQUIPMENT, AND DEBRIS.
14. ALL KEY NOTES INDICATE NEW ITEMS TYPICALLY UNLESS NOTED OTHERWISE.
15. CONTRACTOR TO REVIEW HAZARDOUS MATERIAL REPORT PROVIDED BY PBS,
DATED SEPTEMBER, 2024, PRIOR TO WORK.
A.B. ANCHOR BOLT
A.C. ASPHALT CONCRETE
A.C.B. ACOUSTICAL BOARD
ACI AMERICAN CONCRETE
INSTITUTE
A.C.P. ACOUSTICAL PANEL
A.C.T. ACOUSTICAL CEILING
TILE
ADD'L. ADDITIONAL
A.D. AREA DRAIN
ADJ. ADJUSTABLE
A.F. ACCESS FLOORING
AGGR. AGGREGATE
A.F.F. ABOVE FINISHED FLOOR
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
ARCH. ARCHITECT
ASCE AMERICAN SOCIETY OF
CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR
TESTING AND MATERIALS
AWS AMERICAN WELDING
SOCIETY
BD. BOARD
BITUM. BITUMINOUS
BKP. BACKING PLATE
BM. BEAM
B.O.D. BASIS OF DESIGN
BOT./B.O. BOTTOM/BOTTOM OF
C.B. CATCH BASIN
CEM. CEMENT
CER. CERAMIC
C.G. CORNER GUARD
C.I. CAST IRON
C.J. CONTROL JOINT
CJP COMPLETE JOINT
PENETRATION
CL CENTERLINE
CLG. CEILING
CLKG. CAULKING
CLO. CLOSET
CLR. CLEAR
CMU CONCRETE MASONRY
UNIT
C.O. CASED OPENING
CONC. CONCRETE
CONN. CONNECTION
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
CPT. CARPET
CTSK. COUNTERSUNK
C.T. CERAMIC TILE
CTR. CENTER
DBA DEFORMED BAR
ANCHOR
D.F. DRINKING FOUNTAIN
D.L. DEAD LOAD
DET. DETAIL
DIA., ⌀ DIAMETER
DISP. DISPENSER
DR. DOOR
DWG. DRAWING
DWR. DRAWER
D.S. DOWNSPOUT
D.S.P. DRY STANDPIPE
(E) EXISTING
E.J. EXPANSION JOINT
ELEC. ELECTRICAL
EL. ELEVATION
EQ. EQUAL
EXPO. EXPOSED
EXP. EXPANSION
EXT. EXTERIOR
F.A. FIRE ALARM
FB. FLAT BAR
F.D. FLOOR DRAIN
FDN. FOUNDATION
FE FIRE EXTINGUISHER
F.H. FLAT HEAD
FIN. FINISH
FLR. FLOOR
F.O.C FACE OF CONCRETE
F.O.F FACE OF FINISH
F.O.S. FACE OF STUDS
F.S. FULL SIZE
FT. FOOT
FTG. FOOTING
FUT. FUTURE
Ga. GAUGE
GALV. GALVANIZED
GL GRID LINE
GLB GLULAM BEAM
G.B. GRAB BAR
GND. GROUND
GYP. GYPSUM
G.W.B. GYPSUM WALL BOARD
H.B. HOSE BIBB
H.C. HOLLOW CORE
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HSS HOLLOW STRUCTURAL
STEEL
IBC INTERNATIONAL
BUILDING CODE
I.D. INSIDE DIAMETER
IN. INCH
INT. INTERIOR
J.B. JUNCTION BOX
J.O.H. JAMB OPENING HEIGHT
J.O.W. JAMB WIDTH
JT. JOINT
K KIPS
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LAM. LAMINATE
LB. POUND
L.L. LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC. LOCATION
LONG. LONGITUDINAL
L.P. LOW POINT
LVF LOW VELOCITY FASTENER
MAX. MAXIMUM
MBMA METAL BUILDING
MANUFACTURERS
ASSOCIATION
M.C. MEDICINE CABINET
M.D.F. MEDIUM DENSITY
FIBERBOARD
M.D.O. MEDIUM DENSITY
OVERLAY
MECH. MECHANICAL
MEMB. MEMBRANE
MFR. MANUFACTURER
MH. MANHOLE
MIN. MINIMUM
MIR. MIRROR
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
M.P. MIDPOINT
MPH MILES PER HOUR
M.S. MACHINE SCREW
MT MAGNETIC PARTICLE
TESTING
MTD. MOUNTED
MUL. MULLION
(N) NEW
N.I.C. NOT IN CONTRACT
NOM. NOMINAL
N.T.S. NOT TO SCALE
OBS. OBSCURE
o.c. ON CENTER
O.C.D. OVERHEAD COILING
DOOR
O.C.G OVERHEAD COILING
GRILLE
O.D. OUTSIDE DIAMETER
O.F.C.I. OWNER FURNISHED
CONTRACTOR
INSTALLED
O.F.D. OVERFLOW DRAIN
O.F.O.I. OWNER FURNISHED
OWNER INSTALLED
OH. OPPOSITE HAND
OPP. OPPOSITE
OWJ OPEN WEB JOIST
PAF POWDER ACTUATED
FASTENER
P/C PRECAST (CONCRETE)
PCF POUNDS PER CUBIC
FOOT
PL PLATE
P.LAM. PLASTIC LAMINATE
PLAS. PLASTER
PLY PLYWOOD
P.C.P. PORTLAND CEMENT
PLASTER
PJP PARTIAL JOINT
PENETRATION
PR. PAIR
PSF POUNDS PER FOOT
PSI POUNDS PER INCH
P/T POST-TENSIONED
P.T. PRESSURE TREATED
PTN. PARTITION
(R) REMOVE
R., RAD. RADIUS
R.C.P. REFLECTED CEILING
PLAN
R.D. ROOF DRAIN
REF. REFERENCE
REINF. REINFORCING
REQ'D. REQUIRED
RL. RELOCATE
R.O. ROUGH OPENING
RWD. REDWOOD
REV. REVERSED
S.A.M. SELF-ADHERED MEMBRANE
S.C. SOLID CORE or SLIP
CRITICAL
S.C.D. SEE CIVIL DRAWINGS
SCHED. SCHEDULE
SHR. SHOWER
SIM. SIMILAR
S.J. SCORE JOINT
S.L.D. SEE LANDSCAPING
DRAWINGS
SLRS SEISMIC LOAD RESISTING
SYSTEM
S.M. SHEET METAL
S.M.D SEE MECHANICAL
DRAWINGS
S.O.G. SLAB ON GRADE
SPEC. SPECIFICATION
SQ. SQUARE
S.S.D. SEE STRUCTURAL
DRAWINGS
S.S. STAINLESS STEEL
SSMA STEEL STUD
MANUFACTURERS
ASSOCIATION
STD. STANDARD
STRUCT. STRUCTURAL
S.T.S. SELF TAPPING SCREW
SUSP. SUSPENDED
SYM. SYMMETRICAL
THRU THROUGH
TYP. TYPICAL
TRD. TREAD
T.B. TOWEL BAR
T.C. TOP OF CURB
T & G TONGUE AND GROOVE
THK. THICK
TJ TRUSS JOIST
T.P. TOP OF PAVEMENT
TRANS. TRANSVERSE
T.W. TOP OF WALL
U.N.O. UNLESS NOTED
OTHERWISE
U.T. ULTRASONIC TESTING
VERT. VERTICAL
V.I.F. VERIFY IN FIELD
V.T.R. VENT THROUGH ROOF
w/ WITH w/o WITHOUT
W.C. WATER CLOSET
WF WIDE FLANGE
W.O. WINDOW OPENING
W.P. WORK POINT
PROJECT TEAM
AERIAL PHOTO
-GENERAL-
G0.00 COVER SHEET
G1.00 CODE SUMMARY
G1.10 AREA & CODE PLAN
G2.10 TYPICAL ADA STANDARDS
G2.20 TYPICAL ADA STANDARDS
-ARCHITECTURAL-
A0.10 ASSEMBLIES & SCHEDULES
A0.20 DOOR AND WINDOW SCHEDULES
A1.10 FLOOR PLAN - OVERALL
A1.20 FLOOR PLAN - AREA C
A1.30 FLOOR PLAN - AREA B
A1.40 ROOF PLAN - OVERALL
A1.50 ROOF PLAN - AREA B
A2.10 REFLECTED CEILING PLAN - OVERALL
A2.20 REFLECTED CEILING PLAN - AREA C
A2.30 REFLECTED CEILING PLAN - AREA B
A4.10 BUILDING SECTIONS
A4.20 BUILDING SECTIONS
A5.00 INTERIOR ELEVATIONS
A6.00 EXTERIOR ELEVATIONS
A7.00 WALL SECTIONS
A8.00 SEISMIC JOINT AXONS
A8.10 SEISMIC JOINT DETAILS
A8.20 SEISMIC JOINT DETAILS
A8.30 DETAILS
A8.40 DETAILS
OWNER:
CENTENNIAL SCHOOL DISTRICT
18135 SE BROOKLYN ST.
PORTLAND, OR 97236
T 503.760.7990
REPRESENTATIVE: SCOTT ROSE
CONTACT: DAN BODELL
R&C MANAGMENT GROUP
T 503.312.5404
ARCHITECTURE:
STAMPING REGISTRANT: ZACH STOKES, PE
CONTACT: DAN SALTEE, AIA
ZCS ENGINEERING & ARCHITECTURE
524 MAIN ST.
OREGON CITY, OR 97045
T 503.659.2205
STRUCTURAL ENGINEERING:
ENGINEER OF RECORD: MATT SMITH, PE, SE
CONTACT: KRISTOFER TONNING, PE, SE
ZCS ENGINEERING & ARCHITECTURE
524 MAIN ST.
OREGON CITY, OR 97045
T 503.659.2205
CIVIL ENGINEERING:
ENGINEER OF RECORD: ZACH STOKES, PE
CONTACT: BLAKE DAVIS, PE
ZCS ENGINEERING & ARCHITECTURE
524 MAIN ST.
OREGON CITY, OR 97045
T 503.659.2205
GENERAL CONTRACTOR:
TBD
PROJECT LOCATION
-DEMOLITION-
D1.10 DEMO FLOOR PLAN - OVERALL
D1.20 DEMO FLOOR PLAN - AREA C
D1.30 DEMO FLOOR PLAN - AREA B
D1.40 DEMO ROOF PLAN - OVERALL
D1.50 DEMO ROOF PLAN - AREA B
D2.10 DEMO REFLECTED CEILING PLAN - OVERALL
D2.20 DEMO REFLECTED CEILING PLAN - AREA C
D2.30 DEMO REFLECTED CEILING PLAN - AREA B
D5.00 DEMO INTERIOR ELEVATIONS
D6.00 DEMO EXTERIOR ELEVATIONS
D9.00 DEMO PHOTOS
D9.10 DEMO PHOTOS
G.C. & SUB-CONTRACTORS TO VERIFY EXISTING CONDITIONS & PROVIDE
CODE REQUIRED MEP DESIGN IN COORDINATION WITH THE ARCHITECTURE
PLANS. FURTHER MODIFICATION MAY BE REQUIRED.
MECHANICAL:
1. DISCONNECT AND REINSTALL HVAC EQUIPMENT ON THE ROOF.
2. DISCONNECT AND REINSTALL WALL MOUNTED RADIANT HEATERS
ALONG WALLS THAT ARE TO BE DEMOLISHED. SEE PLANS FOR
LOCATIONS.
3. UNINSTALL AND MODIFY (E) LOUVER AS REQUIRED FOR NEW
ISOLATION JOINT.
4. PROVIDE FELXIBLE DUCTWORK FOR ALL MECHANICAL SYSTEMS THAT
CROSS THE ISOLATION JOINT.
ELECTRICAL:
1. DISCONNECT AND REINSTALL ALL FIRE ALARMS, LOW VOLTAGE, AND
ANY OTHER WALL MOUNTED ITEMS IN EXISTING LOCATIONS AFTER
STRUCTURAL WORK IS COMPLETED.
2. DISCONNECT AND REINSTALL LIGHT FIXTURES AS DIRECTED ON
PLANS.
3. REPLACE WALL MOUNTED OUTLETS ON AREAS AFFECTED BY
RETROFIT.
4. PROVIDE FLEXIBLE CONDUIT FOR ALL ELECTRICAL SYSTEMS THAT
CROSS THE ISOLATION JOINT.
PLUMBING/FIRE PROTECTION:
1. RECONFIGURE PLUMBING AS REQUIRED IN REINSTALLED SINKS AND
CASEWORK.
2. WATER CURTAIN MODIFICATION REQUIRED FOR ISOLATION JOINT
INSTALLATION.
3. PROVIDE FLEXIBLE PIPING FOR ALL WATER SYSTEMS THAT CROSS
THE ISOLATION JOINT.
4. FIRE SPRINKLER MODIFICATIONS AS REQUIRED FOR SEISMIC
RETROFIT SCOPE OF WORK.
PROJECT SCOPE DESIGN BUILD SCOPE
DEFERRED SUBMITTALS
ZCS SHALL PERFORM GENERAL REVIEW OF ANY DEFERRED SUBMITTAL
DESIGNS PRIOR TO SUBMITTING TO THE AHJ AND PRIOR TO CONSTRUCTION
IMPLEMENTATION FOR GENERAL CONFORMANCE TO THE DESIGN INTENT.
DEFERRED SUBMITTAL ITEMS SHALL NOT BE SPECIALLY FABRICATED OR
INSTALLED UNTIL APPROVED BY THE AHJ AND ZCS.
1. NONE.
VICINITY MAP
N
SHEET INDEX
AREA OF WORK
15840 SE TAYLOR ST
PORTLAND, OR 97233
-CIVIL-
C1.00 CIVIL SITE PLAN
-STRUCTURAL-
S0.10 STRUCTURAL GENERAL NOTES
S0.20 SPECIAL INSPECTIONS AND TESTING
S0.30 SPECIAL INSPECTIONS AND TESTING
S1.10 FOUNDATION PLAN AREA C
S1.20 FOUNDATION PLAN AREA B
S1.30 STAGE AND MEZZANINE FRAMING PLAN
S2.10 ROOF FRAMING PLAN AREA C
S2.20 ROOF FRAMING PLAN AREA B
S3.10 FOUNDATION DETAILS
S3.11 FOUNDATION DETAILS
S4.10 STAGE & MEZZANINE DETAILS
S5.10 ROOF FRAMING DETAILS
S5.11 ROOF FRAMING DETAILS
S5.12 ROOF FRAMING DETAILS
S5.13 ROOF FRAMING DETAILS
S5.14 ROOF FRAMING DETAILS
S5.15 ROOF FRAMING DETAILS
S5.16 ELEVATION
SB1.10 SEISMIC BRACING PLAN AREA B
SB2.10 SEISMIC BRACING PHOTOS
SB3.10 SEISMIC BRACING DETAILS
CHAPTER 24.85 SEISMIC DESIGN REQUIREMENTS FOR EXISTING BUILDINGS
24.85.080 APPLICATION OF OTHER REQUIREMENTS
BUILDING PERMIT APPLICATIONS TO IMPROVE THE SEISMIC CAPABILITY
OF A BUILDING SHALL NOT TRIGGER: ACCESSIBILITY IMPROVEMENTS SO LONG
AS THE SEISMIC IMPROVEMENTS DOES NOT LESSEN ACCESSIBILITY; FIRE LIFE
SAFETY IMPROVEMENTS SO LONG AS THE SEISMIC IMPROVEMENTS DOES NOT
LESSEN THE BUILDINGS FIRE RESISTANCE OR EXITING CAPABILITY;
LANDSCAPE IMPROVEMENTS REQUIRED BY CHAPTER 33; STREET TREE
IMPROVEMENTS REQUIRED BY SECTION 20.40.070.
SOILS SPECIAL INSPECTIONS ARE REQUIRED ON THIS BUILDING PERMIT.
REQUIRED SOILS SPECIAL INSPECTIONS INCLUDE:
1. SHALLOW FOUNDATION SUBGRADE PREPARATION.
24.85.090 FEE REDUCTION
BUILDING PERMIT, PLAN REVIEW, AND FIRE LIFE SAFETY REVIEW FEES
FOR STRUCTURAL WORK RELATED TO SEISMIC STRENGTHENING COVERED BY
THIS CHAPTER WILL BE WAIVED WHEN SUCH FEES TOTAL LESS THAN $2,500,
AND WILL BE REDUCED BY 50 PERCENT WHEN SUCH FEES WOULD TOTAL
$2,500 OR MORE.
CHAPTER 24 CITY CODE
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES
TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND
DEGREE OF OPENING PROTECTION
30 FEET OR GREATER, UNPROTECTED, NONSPRINKLERED HAS NO LIMIT TO THE ALLOWABLE AREA OF
OPENINGS.
CHAPTER 34 EXISTING BUILDINGS
TABLE 3403.4.3.1 PERFORMANCE OBJECTIVES FOR USE IN ASCE 41 FOR COMPLIANCE WITH FULL SEISMIC
FORCES
RISK CATEGORY IV
STRUCTURAL PERFORMANCE LEVEL, BSE-1E IMMEDIATE OCCUPANCY
STRUCTURAL PERFORMANCE LEVEL, BSE-2E LIFE SAFETY
3406 CLASSIFICATION OF WORK
3406.3.1 ALTERATION - LEVEL 2 - SCOPE
"LEVEL 2 ALTERATIONS INCLUDE THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT, AND SHALL APPLY WHERE THE WORK AREA IS EQUAL TO OR LESS THAN 50 PERCENT OF THE BUILDING AREA."
THE WORK AREA IS 2,979 SF, WHICH IS LESS THAN 50 PERCENT OF THE TOTAL BUILDING AREA AND INVOLVES THE RECONFIGURATION OF DOORS, WINDOWS, AND BUILDING SYSTEMS; IT IS THEREFORE A LEVEL 2
ALTERATION.
3408 ALTERATIONS - LEVEL 2
3408.2.4 INTERIOR FINISH
"THE INTERIOR FINISH AND TRIM OF WALLS AND CEILINGS IN EXITS AND CORRIDORS IN ANY WORK AREA
SHALL COMPLY WITH THE REQUIREMENTS OF THIS CODE FOR NEW CONSTRUCTION."
ALL INTERIOR FINISH AND TRIM MATERIALS OF WALLS AND CEILINGS THROUGHOUT THIS PROJECT COMPLY
WITH THE REQUIREMENTS OF THE CODE FOR NEW CONSTRUCTION.
3408.3.4 FIRE ALARM AND DETECTION
"AN APPROVED FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS 3408.3.4.1
THROUGH 3408.3.4.2."
THE EXISTING FIRE ALARM SYSTEM IN THE WORK AREA SHALL BE MAINTAINED.
3408.4.5 EXIT DOORWAYS
3408.4.5.1.1 OCCUPANCY LOAD AND TRAVEL DISTANCE
"IN ANY WORK AREA, ALL ROOMS AND SPACES HAVING AN OCCUPANT LOAD GREATER THAN 50 FEET OR IN WHICH THE TRAVEL DISTANCE TO AN EXIT EXCEEDS 75 FEET SHALL HAVE NOT FEWER THAN TWO EGRESS
DOORWAYS."
3408.4.5.2 DOOR SWING
"IN THE WORK AREA AND IN THE EGRESS PATH FROM ANY WORK AREA TO THE EXIT DISCHARGE, ALL EGRESS DOORS SERVING AN OCCUPANT LOAD GREATER THAN 50 SHALL SWING IN THE DIRECTION OF EXIT TRAVEL."
2022 OREGON STRUCTURAL SPECIALITY CODE REVIEW
ADOPTED CODES
ACCESSIBILITY: 2017 INTERNATIONAL CODE COUNCIL (ICC) A117.1
COMMERCIAL STRUCTURES: 2022 OREGON STRUCTURAL SPECIALTY CODE (OSSC)
ELECTRICAL CODE: 2023 OREGON ELECTRICAL SPECIALTY CODE (OESC)
ENERGY EFFICIENCY: 2021 OREGON ENERGY EFFICIENCY SPECIALTY CODE (OEESC)
FIRE CODE: 2022 OREGON FIRE CODE (OFC)
MECHANICAL CODE: 2022 OREGON MECHANICAL SPECIALTY CODE (OMSC)
PLUMBING CODE: 2023 OREGON PLUMBING SPECIALTY CODE (OPSC)
LOT INFORMATION
ADDRESS 15480 SE TAYLOR ST.
PORTLAND, OR 97233
MAP NUMBER 1S2E01
TAX LOT 00100
BUILDING DATA
YEAR BUILT 1965 AND 1967
BUILDING TYPE V-A
PRIMARY STRUCTURE: 1 HR
EXTERIOR: 1 HR
INTERIOR: 1 HR
FLOOR: 1 HR
ROOF: 1 HR (EXCEPTION B)
EXCEPTION B: EXCEPT IN GROUP F-1, H, M, AND S-1 OCCUPANCIES, FIRE
PROTECTION OF STRUCTURAL MEMBERS IN ROOF CONSTRUCTION
SHALL NOT BE REQUIRED, INCLUDING PROTECTION OF PRIMARY
STRUCTURAL FRAME MEMBERS, ROOF FRAMING AND DECKING WHERE
EVERY PART OF THE ROOF CONSTRUCTION IS 20 FEET OR MORE ABOVE
ANY FLOOR IMMEDIATELY BELOW. FIRE-RETARDANT-TREATED WOOD
MEMBERS SHALL BE ALLOWED TO BE USED FOR SUCH UNPROTECTED
MEMBERS.
(E) BUILDING AREA FIRE AREA 'A': 17,124 SF (OUT OF SCOPE)
FIRE AREA 'B': 16,161 SF
FIRE AREA 'C': 13,823 SF
FIRE AREA 'D': 29,067 SF (FIRST FLOOR)(OUT OF SCOPE)
4,915 SF (SECOND FLOOR)(OUT OF SCOPE)
TOTAL: 81,091 SF (UNCHANGED)
FIRE AREAS ARE DELINEATED ON G1.10 AREA PLAN
ALLOWABLE BUILDING AREA 'E' OCCUPANCY - 18,500 SF
'B' OCCUPANCY - 18,000
FIRE AREA 'A' (E OCCUPANCY): 17,124 SF, OUT OF SCOPE OF WORK
PERIMETER > 30' YARDS = 528.5'/618.5' = 0.85
ALLOWABLE INCREASE = 18,500 + (0.75 x 18,500)
= 32,375 SF
FIRE AREA 'B' (B OCCUPANCY): 16,161 SF
PERIMETER > 30' YARDS = 316.25'/629.25' = 0.5025
ALLOWABLE INCREASE = 18,000 + (0.50 x 18,000)
= 27,000 SF
FIRE AREA 'C' (E OCCUPANCY): 13,823 SF
PERIMETER > 30' YARDS = 428.83'/514.75' = 0.83
ALLOWABLE INCREASE = 18,500 + (0.75 x 18,500)
= 32,375 SF
FIRE AREA 'D' (B OCCUPANCY): 33,982 SF, OUT OF SCOPE OF WORK
PERIMETER > 30' YARDS = 701'/855' = 0.82
ALLOWABLE INCREASE = 18,000 + (0.75 x 18,000) = 31,500
(E) TOTAL BUILDING OCCUPANTS 2,480 (UNCHANGED)
(E) OCCUPANTS IN AREA OF WORK 851 (UNCHANGED)
(E) NUMBER OF STORIES 2 (UNCHANGED)
SECOND STORY LOCATED IN FIRE AREA 'D', NOT IN SCOPE
ALLOWABLE NUMBER OF STORIES 1 PER 2022 OSSC TABLE 504.4 (E OCC., TYPE V-A, NONSPRINKLERED)
(E) BUILDING HEIGHT 35' ± 6" (UNCHANGED)
FIRE SPRINKLER NO (EXCEPT AT STAGE) (UNCHANGED)
EXISTING FIRE SPRINKLER SYSTEM EXISTS TO PROVIDE WATER
CURTAINS TO SEPARATE STRUCTURE INTO FOUR DIFFERENT
BUILDINGS AT THREE LOCATIONS. SPRINKLERS ARE NOT USED TO
SATISFY FM 41 STANDARD Q REQUIREMENTS. THESE STANDARDS
ARE MET THROUGH RATED ASSEMBLIES.
FIRE ALARM YES (UNCHANGED)
OCCUPANCY E (UNCHANGED)
B (UNCHANGED)
S-1 (UNCHANGED)
S-2 (UNCHANGED)
OCCUPANCIES ARE NON-SEPARATED.
EXISTING EGRESS UNCHANGED
(E) FIRE RATINGS DRAWN FROM RECORD DRAWINGS DATED 23 APRIL 2022. SEE CITY REVIEW OF PROJECT
21-092369-REV-01-CO
ENERGY CODE REQUIREMENTS
CLIMATE ZONE 4 - NON RESIDENTIAL
ROOF UNCHANGED
WALL R-20
SLAB ON GRADE EXISTING (UNCHANGED)
DOORS U-0.370 (UNCHANGED)
FENESTRATIONS
FIXED U-0.360 MAX, SHGC 0.360 MAX (UNCHANGED)
OPERABLE U-0.450 MAX, SHGC 0.330 MAX (UNCHANGED)
FM41 STANDARD Q AGREEMENT
ALL CORRIDORS AND STAIRS ENCLOSURES SERVING NOT MORE THAN TWO LEVELS:
1. WALLS AND CEILINGS MUST BE AT LEAST SHEETROCK OR LATH-AND-PLASTER, CONTINUOUS AND
SEALED SMOKETIGHT.
2. ALL WALL/CEILING MATERIALS TO BE AT LEAST FLAMESPREAD CLASS B (FIRETEX/WOOD FIBER
ACOUSTIC BOARD ON CEILINGS MUST BE SEALED WITH APPROVED INTUMESCENT PAINT: OR
REMOVED AND GLUE-SPOTS TREATED)
3. ALL PIPE/DUCT/CONDUIT PENETRATIONS TO BE SEALED SMOKETIGHT.
4. PROVIDE COMBUSTION SMOKE FIRE DAMPERS AT ALL HVAC OPENINGS TO THE CORRIDOR.
5. ALL DOORS TO BE 1 3/4" SOLID CORE OR MINIMUM 20 MINUTE RATED, WITH SMOKE GASKETING.
FRAMES NEED NOT BE RATED IF IN GOOD REPAIR. DOOR RELITES TO BE 1/4" WIRE GLASS WITH STEEL
STOPS.
A. ALL DOORS EXCEPT CLASSROOM DOORS TO BE ON SELF-CLOSERS.
B. CLASSROOM DOORS MAY BE WITHOUT CLOSERS PROVIDED THAT ARE POSTED: "KEEP
THIS DOOR CLOSED WHEN ROOM IS UNOCCUPIED --BY ORDER F THE FIRE MARSHAL.
C. NO CORRIDOR DOORS TO HAVE LOUVERS.
6. CORRIDOR RELITES TO BE 1/4" WIRE GLASS WITH STEEL STOPS, SEALED SMOKETIGHT.
A. TRANSOMS TO BE FIXED SHUT AND SEALED SMOKETIGHT. WIRE-GLASS TRANSOMS
MAY BE TREATED AS CORRIDOR RELITES: PLAIN GLASS TRANSOMS MUST BE
PROTECTED WITH SHEETROCK ON EACH SIDE OF ORIGINAL GLASS OR REPLACED WITH
1 3/4" SOLID CORE DOOR MATERIAL.
7. LIGHTED EXIT SIGNS AND EMERGENCY ILLUMINATION PROVIDING A MINIMUM OF ONE FOOTCANDLE OVER THE ENTIRE EXIT ROUTE SHALL BE TIED TO BATTERY BACK-UP OR AN EMERGENCY GENERATOR.
ALL OTHER PROVISIONS IN STANDARD Q TO NOT APPLY TO THIS PROJECT.
FM41 STANDARD Q COMPLIANCE
ALL CORRIDORS AND STAIRS ENCLOSURES SERVING NOT MORE THAN TWO LEVELS:
1. WALLS AND CEILINGS MUST BE AT LEAST SHEETROCK OR LATH-AND-PLASTER, CONTINUOUS AND
SEALED SMOKETIGHT.
A. ALL CEILINGS TO BE REPLACED IN THE CORRIDOR WILL MAINTAIN A SHEETROCK
SUBSTRATE. ALL RATED ASSEMBLIES THAT ARE TO BE AFFECTED OR DEMOLISHED
BY SCOPE OF WORK WILL PATCHED OR REBUILT WITH THE SAME HOUR RATING.
2. ALL WALL/CEILING MATERIALS TO BE AT LEAST FLAMESPREAD CLASS B (FIRETEX/WOOD FIBER
ACOUSTIC BOARD ON CEILINGS MUST BE SEALED WITH APPROVED INTUMESCENT PAINT: OR
REMOVED AND GLUE-SPOTS TREATED)
A. ALL MATERIAL REPLACED DUE TO SCOPE OF WORK WILL BE A MINIMUM OF CLASS B
FLAMESPREAD. SHEET METAL FLASHING IS CONSIDERED A CLASS 'A' FLAME SPREAD
RATING.
3. ALL PIPE/DUCT/CONDUIT PENETRATIONS TO BE SEALED SMOKETIGHT.
A. ALL PIPES/DUCT/CONDUIT TO BE REMOVED AND REINSTALLED WILL BE SEALED
SMOKETIGHT.
4. ALL DOORS TO BE 1 3/4" SOLID CORE OR MINIMUM 20 MINUTE RATED, WITH SMOKE GASKETING.
FRAMES NEED NOT BE RATED IF IN GOOD REPAIR. DOOR RELITES TO BE 1/4" WIRE GLASS WIT STEEL
STOPS.
A. ALL DOORS EXCEPT CLASSROOM DOORS TO BE ON SELF-CLOSERS.
B. CLASSROOM DOORS MAY BE WITHOUT CLOSERS PROVIDED THAT ARE POSTED: "KEEP
THIS DOOR CLOSED WHEN ROOM IS UNOCCUPIED --BY ORDER F THE FIRE MARSHAL.
C. NO CORRIDOR DOORS TO HAVE LOUVERS.
D. DOORS AND RELITES TO BE REPLACED BY SCOPE OF WORK WILL HAVE A MINIMUM OF
20 MINUTE RATING AND GLASS WILL BE 45 MINUTE RATED WITH STEEL STOPS.
5. CORRIDOR RELITES TO BE 1/4" WIRE GLASS WITH STEEL STOPS, SEALED SMOKETIGHT.
A. TRANSOMS TO BE FIXED SHUT AND SEALED SMOKETIGHT. WIRE-GLASS TRANSOMS
MAY BE TREATED AS CORRIDOR RELITES: PLAIN GLASS TRANSOMS MUST BE
PROTECTED WITH SHEETROCK ON EACH SIDE OF ORIGINAL GLASS OR REPLACED WITH
1 3/4" SOLID CORE DOOR MATERIAL.
a. ALL CORRIDOR RELITES TO BE REPLACED BY SCOPE OF WORK WITH BE A
MINIMUM OF 45 MINUTE RATED.
6. LIGHTED EXIT SIGNS AND EMERGENCY ILLUMINATION PROVIDING A MINIMUM OF ONE FOOTCANDLE
OVER THE ENTIRE EXIT ROUTE SHALL BE TIED TO BATTERY BACK-UP OR AN EMERGENCY GENERATOR.
A. ALL LIGHTED EXIT SIGNS AFFECTED BY SCOPE OF WORK WILL BE INSTALLED WITH A
BATTERY BACK-UP TO MAINTAIN A MINIMUM OF 1 FOOTCANDLE OVER
ALL OTHER PROVISIONS IN STANDARD Q TO NOT APPLY TO THIS PROJECT.
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:3
:4
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
G1.00
CODE SUMMARY
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
E T
UP
EXIT
Room name
X
# occs.
150 sf OLF /sf
# Exit(s)
(E) ILLUMINATED EXIT SIGNAGE
(E) EXIT ACCESS DOORWAY
(E) EGRESS PATH (UNCHANGED)
PROVIDE 1 FOOTCANDLE MIN. ALONG
ENTIRE PATH
OCCUPANCY LOAD VALUE PER ROOM
ROOM OCCUPANT LOAD
(E) 1 HR RATED WALL
(E) 2 HR RATED WALL
(E) AREA SEPARATION WALL - 2 HR RATED
(N) 1 HR RATED WALL
*FIRE WALLS WERE DETERMINED FROM
PROJECT NUMBER 21-092369 PERMITTED
ON 1/10/22
(E) FIRE EXTINGUISHER CABINET
(E) 20 MIN. FIRE RATED DOOR
(E) 90 MIN. FIRE RATED DOOR
(E) 3 HR FIRE RATED DOOR
WORK AREA = 2,979 SF
AREA OUT OF SCOPE
CODE PLAN LEGEND
FEC
20M
90M
3HR
A
C
D
E
F
G
H
L
1 8 112 7 1210 14
E
45 occs.
887 SF
CLASSROOM
20 /sf
1 Exit(s)
212 E
59 occs.
1179 SF
CLASSROOM
20 /sf
2 Exit(s)
210 E
7 occs.
315 SF
PREP
50 /sf
1 Exit(s)
208 E
59 occs.
1176 SF
CLASSROOM
20 /sf
2 Exit(s)
206 E
45 occs.
890 SF
CLASSROOM
20 /sf
1 Exit(s)
204 E
45 occs.
887 SF
CLASSROOM
20 /sf
1 Exit(s)
E
45 occs.
887 SF
CLASSROOM
20 /sf
1 Exit(s)
211 E
45 occs.
891 SF
CLASSROOM
20 /sf
1 Exit(s)
209 E
45 occs.
890 SF
CLASSROOM
20 /sf
1 Exit(s)
207 E
45 occs.
891 SF
CLASSROOM
20 /sf
1 Exit(s)
205 E
45 occs.
891 SF
CLASSROOM
20 /sf
1 Exit(s)
B
5 occs.
678 SF
COUNSELOR
150 /sf
1 Exit(s)
B
1 occs.
97 SF
OFFICE
150 /sf
1 Exit(s)
201B
B
1 occs.
97 SF
OFFICE
150 /sf
1 Exit(s)
201A
E
36 occs.
1790 SF
MEDIA
CENTER
50 /sf
2 Exit(s)
B
2 occs.
212 SF
CONFERENCE
150 /sf
1 Exit(s)
B
3 occs.
368 SF
RECEPTION
150 /sf
3 Exit(s)
002A
E
63 occs.
943 SF
STAGE
15 /sf
4 Exit(s)
048 E
285 occs.
4270 SF
CAFETERIUM
15 /sf
6 Exit(s)
S-2
1 occs.
185 SF
JANITOR
300 /sf
1 Exit(s)
S-2
1 occs.
103 SF
STORAGE B
300 /sf
1 Exit(s)
B
1 occs.
120 SF
MEETING B
150 /sf
1 Exit(s)
B
1 occs.
139 SF
HEALTH
150 /sf
1 Exit(s)
B
1 occs.
89 SF
MDF
150 /sf
1 Exit(s)
B
1 occs.
133 SF
PRINCIPAL
150 /sf
1 Exit(s)
B
1 occs.
103 SF
ASSISTANT
PRINCIPAL
150 /sf
1 Exit(s)
B
1 occs.
106 SF
MEETING A
150 /sf
1 Exit(s)
S-2
1 occs.
44 SF
STORAGE A
300 /sf
1 Exit(s)
B
1 occs.
63 SF
OFFICE
150 /sf
1 Exit(s)
(E) WATER CURTAIN ABOVE
(E) WATER
CURTAIN ABOVE
(E) WATER CURTAIN ABOVE
E X
IT
E X
IT
E
X
IT
EXIT
FEC
FEC
FEC
FEC
90M 90M 90M
20M 20M
20M
20M
20M 20M 20M 20M 20M
20M
20M
OUT OF SCOPE
OUT OF SCOPE
CORRIDOR
CORRIDOR
CORRIDOR
B
133 4 5
K
J
6 9
THE SCOPE OF THIS PROJECT CONSISTS OF THE
VOLUNTARY SEISMIC REHABILITATION OF PORTIONS OF
OLIVER MIDDLE SCHOOL.
THERE ARE NO MODIFICATIONS TO (E) EGRESS
PROPOSED IN THE PROJECT SCOPE.
THE REQUIREMENTS OF SEISMIC REHABILITATION MAY
REQUIRE RELOCATION OF PLUMBING IN ROOF FRAMING
CAVITY FOR THE EXISTING WATER CURTAIN SYSTEM. THIS
SYSTEM IS TO HAVE NO MODIFICATION TO ITS FUNCTION
AND IS TO BE PERFORMED AS PART OF DESIGN-BUILD
SCOPE.
THE REQUIREMENTS OF SEISMIC REHABILITATION WILL
REQUIRE PARTIAL DEMOLITION AND RECONSTRUCTION
OF AN EXISTING 1 HOUR FIRE RATED EXTERIOR WALL
LOCATED SOUTH OF GRIDLINE G, BETWEEN GRIDLINES 7
AND 8. THIS WALL IS TO MAINTAIN A 1 HOUR RATING AND
WILL BE COMPLIANT WITH THE STANDARDS OF CODE FOR
NEW CONSTRUCTION.
LIFE SAFETY NARRATIVE
FIRE AREA 'A' (NOT IN SCOPE) = 17,124 SF
FIRE AREA 'B' = 16,161 SF
FIRE AREA 'C' = 13,823
FIRE AREA 'D' (NOT IN SCOPE) = 33,982
FIRE AREA LEGEND
FIRE AREA 'A'
NOT IN SCOPE
FIRE AREA 'C' FIRE AREA 'B'
FIRE AREA 'D'
NOT IN SCOPE
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:3
:5
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
G1.10
AREA & CODE
PLAN
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
E T
N
G1.10 1/16" = 1'-0"
FIRST FLOOR CODE PLAN2
N
G1.10 1" = 50'-0"
FIRE AREA PLAN1
M
A X
M
IN
12" MAX
1"
1-1/2" MIN. CLR.
STAIR HANDRAIL & EXTENSIONS RAMP HANDRAIL & EXTENSIONS
12" MIN.
CONTINUE TO SLOPE FOR
THE DEPTH OF ONE TREAD
BEYOND THE BOTTOM RISER
NOTES:
1. HANDRAILS SHALL BE PROVIDED ON BOTH SIDES OF STAIRS AND RAMPS.
2. HANDRAILS SHALL BE CONTINUOUS WITHIN FULL LENGTH OF EACH STAIR FLIGHT
OR RAMP RUN. INSIDE HANDRAILS ON SWITCHBACK OR DOGLEG STAIRS OR RAMPS
SHALL BE CONTINUOUS BETWEEN FLIGHT FLIGHTS AND RUNS.
3. HANDRAIL HEIGHT SHALL BE MEASURED VERTICALLY ABOVE NOSINGS, RAMP
SURFACES AND WALKING SURFACES.
4. GRIPPING SURFACES SHALL BE CONTINUOUS, WITHOUT INTERRUPTION BY NEWEL
POSTS, OTHER CONSTRUCTION ELEMENTS, OR OBSTRUCTIONS.
5. HANDRAIL CROSS SECTIONS:
A. CIRCULAR: 1 1/14" MIN. - 2" MAX.
B. NONCIRCULAR PERIMETER: 4" MIN. - 6 1/4" MAX.
C. NONCIRCULAR CROSS SECTION: 2 1/4" MAX.
6. HANDRAIL EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR FLOOR, OR SHALL
BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN OR AN ADJACENT
STAIR FLIGHT.
12" MIN. 12" MIN.
FIXTURES DIM# MOUNTING HEIGHT
B C
D
E
F
G
I
J
K
L
M
N
O
Q R
EXTEND 42" MIN FROM THE SIDE WALL
TOILET 16" MIN - 18" MAX TO CENTER FROM SIDE WALL
URINAL (ADA) 17" TO RIM A.F.F
URINAL 24" TO RIM A.F.F.
SINK (ADA) 34" MAX TO THE HIGHER OF THE RIM OR COUNTER SURFACE
MIRROR 40" MAX TO BOTTOM EDGE OF REFLECTING SURFACE
HORIZONTAL GRAB BAR 33" MIN - 36" MAX HEIGHT A.F.F. TO T.O. GRIPPING SURFACE
VERTICAL GRAB BAR 39" MIN - 41" MAX HEIGHT A.F.F.
18" MIN IN LENGTH
SIDE WALL GRAB BAR 12" MAX FROM REAR WALL
42" MIN IN LENGTH
EXTEND 54" MIN FROM REAR WALL
39" MIN - 41" MAX FROM THE REAR WALL TO CENTERLINE OF BAR
TOILET 17" MIN - 19" MAX TO T.O. SEAT A.F.F.
18" MIN. TO OUTLET OF DISPENSER A.F.F.
1 1/2" MIN. FROM B.O. GRAB BAR
24" MIN - 36" MAX FROM WALL TO OUTLET OF DISPENSER
42" MAX FROM WALL TO OUTLET OF DISPENSER
H
D
J K
N O
G H
E
F
D
A
REAR WALL GRAB BAR A 36" MIN IN LENGTH
6" MAX.
B
C
I
M
L
R
Q
P
REAR WALL GRAB BAR
G
VERTICAL GRAB BAR
SIDE WALL GRAB BAR
SIDE WALL GRAB BAR
VERTICAL GRAB BAR
TOILET PAPER AND
SEAT COVER DISPENSER
TOILET PAPER DISPENSER
TOILET PAPER DISPENSER
S
S
48" MAX A.F.F. TO HIGHEST OPERABLE PARTS OR
44" MAX A.F.F. IF OVER AN OBSTRUCTION W/ A DEPTH OF >20"
ACCESSORY DISPENSERS
P
P
WATER CLOSET CLEARANCE SIZE - SECTION 604.3
AMBULATORY ACCESSIBLE TOILET COMPARTMENT - SECTION 604.10
LAVATORY CLEAR FLOOR SPACE LAVATORY KNEE AND TOE CLEARANCE
M
IN
8" MIN
CLEARANCE
11" MIN KNEE
CLEARANCE
6" MAX TOE
M
IN
M
IN
59" MIN. FLOOR MOUNT
56" MIN. WALL HUNG
NOTE:
THE REQUIRED CLEARANCE AROUND THE
WATER CLOSET SHALL BE PERMITTED TO
OVERLAP THE WATER CLOSET,
ASSOCIATED GRAB BARS, PAPER
DISPENSERS, SANITARY NAPKIN
RECEPTACLES, COAT HOOKS, SHELVES,
ACCESSIBLE ROUTES, CLEAR FLOOR
SPACE AT OTHER FIXTURES AND THE
TURNING SPACE. NO OTHER FIXTURES OR
OBSTRUCTIONS SHALL BE WITHIN THE
REQUIRED WATER CLOSET CLEARANCE
M
IN
48" MIN.
TYPICAL MOUNTING REQUIREMENTS
60" MIN.
DOOR SHALL NOT SWING INTO
THE REQUIRED MINIMUM AREA
OF THE COMPARTMENT
M
IN
4" MAX.
56" MIN.
OR
M A
X
F L
O O
R M
O U
N T
E D
M
IN
W A
L L
H U
N G
M
IN
O R
O R
WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT & DOOR OPENING LOCATION - SECTION 604.9
37" MAX.
35" MIN.
17" MIN. - 19" MAX.
M
IN
M
IN
56" MIN. WALL HUNG (ADULT)
59" MIN. FLOOR MOUNTED (ADULT)
59" MIN. WALL & FLOOR MOUNT (CHILDREN)
T
TBABY CHANGING TABLE 28" MIN - 34" MAX HEIGHT A.F.F.
TOILET PAPER AND
SANITARY NAPKIN
DISPENSER
NOTE:
LETTERS AND NUMBERS ON SIGNS SHALL BE
RAISED 1/32" MIN. AND SHALL BE SANS-SERIF
UPPERCASE CHARACTERS ACCOMPANIED BY
CONTRACTED GRADE 2 BRAILLE WITH A
CONTRASTING BACKGROUND.
PICTOGRAMS SHALL HAVE A
NONGLARE FINISH AND
SHALL CONTRAST WITH
THEIR FIELDS
RESTROOM SIGN LOCATION
GENERAL SIGNAGE REQUIREMENTS
WOMEN
HEIGHT OF
CHARACTERS SHALL BE
5/8" MIN. TO 2" MAX.
BRAILLE SHALL BE
CONTRACTED GRADE II
SIGN SHALL BE PROVIDED
ON LATCH SIDE OF DOOR
RAISED CHARACTERS SHALL
BE 48" MIN. A.F.F. MEASURED
TO BASELINE OF LOWEST
RAISED CHARACTER AND 60"
MAX. A.F.F. TO THE HIGHEST
RAISED CHARACTER
M
IN
F
IE
L
D
STAIR TREADS AND RISERS - SECTION 504
M A
X
M
IN
11" MIN.
TREADS AND RISERS
STAIR NOSINGS - VERTICAL RISER
CURVE OR BEVEL AT LEADING EDGE
1/2" MAX. ROUNDED 1/2" MAX. BEVEL
.0
0°
1 1/2" MAX.
CURVED
CURVED NOSING
BEVELED NOSING
1 1/2" MAX.
BEVELED
30° MAX.
ANGLED RISER
NOTES:
1. ALL STEPS ON A FLIGHT OF STAIRS SHALL HAVE A UNIFORM RISER
HEIGHT AND UNIFORM TREAD DEPTH.
2. OPEN RISERS SHALL NOT BE PERMITTED.
3. NOSINGS WITHIN A STAIRWAY SHALL BE UNIFORM.
4. NOSINGS THAT PROJECT BEYOND RISERS SHALL HAVE THE UNDERSIDE
OF THE LEADING EDGE CURVED OR BEVELED.
5. VISUAL CONTRAST SHALL COMPLY WITH EITHER A OR B:
A. THE LEADING 1" - 2" OF EVERY TREAD AND LANDING, MEASURED
HORIZONTALLY FROM THE LEADING EDGE OF THE NOSING,
SHALL CONSIST OF A SOLID COLOR HAVING VISUAL CONTRAST
OF DARK-ON-LIGHT OR LIGHT-ON-DARK FROM THE REMAINDER
OF THE TREAD. THE CONTRASTING MARKING SHALL BE
DURABLE AND SHALL EXTEND FROM ONE SIDE OF EACH TREAD
TO THE OTHER SIDE OF EACH TREAD.
B. DURABLE DISTINCTIVE WARNING MARKINGS REQUIRED BY THE
ADOPTED BUILDING CODE OR ANSI SAFETY STANDARD.
HANDRAILS - SECTION 505
HANDRAIL CLEARANCE
52" MIN.
M
IN
C H
IL
D
R E
N
A D
U L T
M
A X
M
A X
S T
A N
D
IN
G U
S
C
H
IL
D R
E N
M
IN
M A
X
M
IN
M A
X
S T
A N
D
IN
G U
A
D U
L T
DRINKING FOUNTAINS - SECTION 602
CLEAR FLOOR SPACE
& SPOUT LOCATION
WHEELCHAIR DRINKING FOUNTAIN
SPOUT HEIGHT & LOCATION
5" MAX.
ADULT
15" MIN.
STANDING USE DRINKING FOUNTAIN
SPOUT HEIGHT & LOCATION
NOTE:
WHERE BOTTLE FILLING STATIONS ARE PART OF THE
DRINKING FOUNTAIN FOR PERSONS WHO ARE STANDING,
THE BOTTLE FILLING STATION IS NOT REQUIRED TO
COMPLY WITH THIS SECTION PROVIDED A BOTTLE
FILLING STATION IS LOCATED AT THE DRINKING
FOUNTAIN FOR PERSONS USING WHEELCHAIRS.
DOOR SWINGING IN ON
FRONT WALL OF PARTITION
DOOR SWINGING IN ON
SIDE WALL OF PARTITION
8"
" 1
M
IN
PARTITION
8"
TOE CLEARANCE - PLAN TOE CLEARANCE - ELEVATION
DOOR SWING INTO THE WHEELCHAIR
TOILET COMPARTMENT
URINALS - SECTION 605
13 1/2" MIN.
M A
X
13 1/2" MIN.
WALL HUNG TYPE STALL TYPE
LAVATORIES - SECTION 606
Back wall
Seat wall
Control wall
TRANSFER-TYPE COMPARTMENT CLEARANCES (EXISTING BUILDINGS) - SECTION 608
48" MIN.
M
IN
M
IN
36" MIN.
SIGNAGE, IDENTIFICATION & INTERNATIONAL SYMBOLS OF ACCESSIBILITY - SECTION 703
EXIT
EXIT
FIRE APPLIANCESEXIT SIGNS, LIGHT SWITCHES & OUTLETS
MISCELLANEOUS MOUNTING HEIGHTS
FIRE EXTINGUISHER
OR FIRE HOSE CAB
FIRE ALARM
PULL
ALARM
STROBE
CLOCK
TACK, CHALK, OR
DRY MARKER
BOARD
HOSE
BIBB
SHELF
AND ROD
COAT
HOOKS
CLOSET
ROD
LOW LEVEL
EXIT SIGN
WHERE
REQUIRED
SURFACE-
MOUNTED
ILLUMINATED
EXIT SIGN
3"
9"
M
A X
M
IN
LIGHT SWITCH
M
A X
M
IN
OUTLET
M
A X
M
IN
WITHIN 5 FT OF EACH
EXIT DOORWAY ON
EACH FLOOR
M
IN
M A
X
M
A X
M
IN
M
A X
M
A X
M
A X
M
IN
V A
R
IE
M
A X
M
A X
M
IN
IC
C
A .1
E
X
IS
T
IN
G B
U
IL
D
IN
G
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:3
:5
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
G2.10
TYPICAL ADA
STANDARDS
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
(C)
M
IN
WIDTH
DOOR
UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH
10" MAX.
M
IN
M
A X
10" MAX.
M
A X
>10" - 24" MAX.
M
A X
M
A X
CIRCULAR T-SHAPED OPTION
TURNING SPACE (EXISTING BUILDINGS) - SECTION 304
60" MIN.
OVERLAP OF KNEE AND TOE
M
IN
M
A X
M
A X
20" MAX. >20" - 25" MAX.
M
A X
UNOBSTRUCTED FWD REACH OBSTRUCTED HIGH FORWARD REACH
60" MIN.
M
IN
M
IN
M
IN
MIN.
12" 36" MIN.
MIN.
12"
OVERLAP OF KNEE AND TOE
ARM
PULL SIDE PUSH SIDE PUSH SIDE - DOOR PROVIDED
WITH BOTH CLOSER AND LATCH
M
IN
18" MIN.
M
IN
X
X
M
IN
12" MIN.
MANEUVERING CLEARANCES AT RECESSED DOORS (EXISTING BUILDINGS) - SECTION 404.2.3.5
FRONT APPROACHPOCKET OR HINGE APPROACHSTOP OR LATCH APPROACH
M
IN
M
IN
22" MIN.
M
IN
24" MIN.
MANEUVERING CLEARANCE AT SLIDING AND FOLDING DOORS (EXISTING BUILDINGS) - SECTION 404.2.3.3
FRONT APPROACH, PUSH SIDEHINGE APPROACH, PULL SIDE
HINGE APPROACH, PULL SIDEHINGE APPROACH, PUSH SIDE
LATCH APPROACH, PULL SIDE
(A) (B)
FRONT APPROACH, PULL SIDE
TWO DOORS OR GATES IN A SERIES (EXISTING BUILDINGS) - SECTION 404.2.5
MANEUVERING CLEARANCE AT SWINGING DOORS (EXISTING BUILDINGS) - SECTION 404.2.3
WIDTH
DOOR
M
IN
M
IN
18" MIN.
M
IN
*12" MIN.
*IF BOTH CLOSER
AND LATCH ARE
PROVIDED
36" MIN.
M
IN
M
IN
42" MIN.*4
M
IN
22" MIN.
*48" MIN. IF BOTH
CLOSER AND LATCH
ARE PROVIDED
*4
M
IN
24" MIN.
*54" MIN. IF CLOSER
IS PROVIDED
*4
M
IN
24" MIN.
*48" MIN. IF CLOSER
IS PROVIDED
60" MIN. 48" MIN.
WIDTH
DOOR
LATCH APPROACH, PUSH SIDE
FLOOR SURFACES - SECTION 302
NOTE:
CARPET OR CARPET TILE SHALL HAVE A LOOP,
TEXTURED LOOP, LEVEL CUT PILE, OR LEVEL
CUT/UNCUT PILE TEXTURE. THE PILE SHALL BE 1/2" MAX.
IN HEIGHT. EXPOSED EDGES OF CARPET SHALL BE
FASTENED TO THE FLOOR AND SHALL HAVE TRIM
ALONG THE ENTIRE LENGTH OF THE EXPOSED EDGE.
1/2" MAX.
OPENINGS IN FLOOR SURFACES - SECTION 302.3
1/2" MAX.
LONG DIMENSION
PERPENDICULAR
TO DIRECTION
OF TRAVEL
PREDOMINANT
DIRECTION OF TRAVEL
CHANGES IN LEVEL - SECTION 303
/4
M
A X
VERTICAL CHANGE IN LEVEL BEVELED CHANGE IN LEVEL (A)
/4
/2
M
A X
BEVELED CHANGE IN LEVEL (B)
/2
M
A X
NOTE:
CHANGES IN LEVEL GREATER THAN 1/2" IN HEIGHT
SHALL BE BY RAMP COMPLYING WITH SECTION 405 OR
BY A CURB CAMP COMPLYING WITH SECTION 406
PARALLEL
POSITION OF CLEAR FLOOR SPACE (EXISTING BUILDINGS) - SECTION 305.5
M
IN
48" MIN.
FORWARD
M
IN
30" MIN.
FORWARD APPROACHPARALLEL APPROACH
MANEUVERING CLEARANCE IN AN ALCOVE - SECTION 305.7
60" MIN.
X
36" MIN.
X
KNEE AND TOE CLEARANCE - SECTION 306
8" MIN.
M
IN
M
IN
11" MIN.
M
IN
25" MAX.
M
IN
25" MAX.
17" MIN.
6" MAX.
TOE CLEARANCE - ELEVATION
TOE CLEARANCE - PLAN
KNEE CLEARANCE - ELEVATION
KNEE CLEARANCE - PLAN
x
4" MAX.
X
4" MAX. 4" MAX.
POST
SIGN
M
A X
X > 12"
4" MAX. 4" MAX.
X < 12"
X > 12"
UNLIMITED
POST MOUNTED PROTRUDING OBJECTSLIMITS OF PROTRUDING OBJECTS
PROTRUDING OBJECTS - SECTION 307
NOTE:
PROTRUDING OBJECTS SHALL NOT REDUCE THE
CLEAR WIDTH REQUIRED FOR ACCESSIBLE ROUTES
REDUCED VERTICAL CLEARANCE
M
A X
X
24" MAX. 48" MIN. 24" MAX.
M
IN
M
IN
M
IN
M
IN
CLEAR WIDTH OF AN INTERIOR ACCESSIBLE ROUTE (EXISTING BUILDINGS) - SECTION 403.5
CLEAR WIDTH OF AN ACCESSIBLE ROUTE - INTERIOR
CLEAR WIDTH OF AN ACCESSIBLE ROUTE - EXTERIOR
24" MAX. 48" MIN. 24" MAX.
M
IN
M
IN
M
IN
M
IN
42" MIN.
X < 48"
42" MIN.
M
IN
36" MIN.
X < 48"
36" MIN.
CLEAR WIDTH AT 180-DEGREE TURN
OPTION 2
CLEAR WIDTH AT 180-DEGREE TURN
OPTION 1
M
IN
38" MIN.
60" MIN.
M
IN
M
IN
PASSING SPACE - 60"x60" OPTION
M
IN
PASSING SPACE - T-TURN OPTION
M
IN
M
IN
48" MIN. 36" MIN. 48" MIN.
T-TURN COMPLYING
WITH SECTION 304
CLEAR WIDTH AT 90-DEGREE TURN
REACH RANGES - SECTION 308
SLIDING DOOR
HINGED DOOR
32" MIN.
32" MIN.
CLEAR WIDTH OF DOORWAYS - SECTION 404.2
32" MIN.
FOLDING DOOR DOORWAYS WITHIN DOORS
36" MIN.
60" MIN. 60" MIN.
LANDING RAMP RUN LANDING
AT LEAST AS WIDE
AS RAMP RUN
60" MIN.
LANDING
M
IN
RAMP
RUN
RAMP
RUN
RAMPS - SECTION 405 RAMP EDGE PROTECTION - SECTION 405.9
RAMP
LANDING
10"
/2
M
A X
OR
10"
/2
M
A X
EDGE PROTECTION - LIMITED DROP-OFF EXCEPTION
12" MIN. 12" MIN.
EXTENDED FLOOR SURFACE
CURB
M
IN
C
U R
B
BARRIER
BARRIER PREVENTS PASSAGE
OF 4" SPHERE WITH ANY
PORTION WITHIN 4" OF FLOOR
NOTES:
1. RAMPS SHALL HAVE A RUNNING SLOPE GREATER THAN
1:20 AND NOT STEEPER THAN 1:12.
2. CROSS SLOPE OF RAMP RUNS SHALL NOT BE STEEPER
THAN 1:48.
3. HANDRAILS AND HANDRAIL SUPPORTS THAT ARE
PROVIDED ON THE RAMP RUN SHALL NOT PROJECT INTO
THE REQUIRED CLEAR WIDTH OF THE RAMP RUN.
4. THE RISE FOR ANY RAMP RUN SHALL BE 30" MAX.
5. RAMPS SHALL HAVE LANDINGS AT THE BOTTOM AND TOP
OF EACH RAMP RUN
6. LANDINGS SHALL HAVE A SLOPE NOT STEEPER THAN 1:48.
7. CLEAR WIDTH OF LANDINGS SHALL BE AT LEAST AS WIDE
AS THE WIDEST RAMP RUN LEADING TO THE LANDING.
8. RAMP RUNS WITH A RISE GREATER THAN 6" SHALL HAVE
HANDRAILS.
NOTE:
EDGE PROTECTION SHALL BE PROVIDED ON
EACH SIDE OF RAMP RUNS AND AT EACH SIDE
OF RAMP LANDINGS
M
A X
B A
S E
M
IN
IC
C
A .1
E
X
IS
T
IN
G B
U
IL
D
IN
G
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:3
:5
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
G2.20
TYPICAL ADA
STANDARDS
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
CIVIL SITE PLAN
C1.00
CIVIL SITE PLAN
1"=40'
C1.00
( FEET )
1 INCH = FT
40 20 8040
GENERAL NOTES:
ALL EXISTING PAVING, STRUCTURES, APPURTENANCES, ETC. SHALL BE
PROTECTED THROUGHOUT CONSTRUCTION UNLESS NOTED OTHERWISE.
NO 'STREET TREES' WERE IDENTIFIED WITHIN OR IMMEDIATELY
SURROUNDING THE PROJECT AREA BY THE PORTLAND PARKS AND
RECREATION URBAN FORESTRY 'TREE INVENTORY PROJECT' THEREFORE,
NO STREET TREE PROTECTION IS ANTICIPATED TO BE REQUIRED.
NO WORK IS ANTICIPATED TO BE PERFORMED ADJACENT TO EXISTING
ON-SITE TREES, THEREFORE NO ON-SITE TREE PROTECTION IS
ANTICIPATED TO BE REQUIRED.
CONSTRUCTION NOTES:
1. LIMITS OF SEISMIC RETROFIT WORK ON EXISTING BUILDING. SEE
STRUCTURAL AND ARCHITECTURAL PLANS FOR ALL INFORMATION.
2. EXISTING SITE TREES, TYPICAL. TREE PROTECTION FENCING IS NOT
REQUIRED, BUT CONTRACTOR TO PROTECT TREES FROM DAMAGE AND
MINIMIZE EQUIPMENT COMPACTION OF SOIL IN THE ROOT ZONE.
3. BUILDING TO REMAIN. NO WORK IN THIS AREA.
4. APPROXIMATE LOCATION OF EXTERIOR WALL DEMOLITION AND
RECONSTRUCTION, REFER TO ARCHITECTURAL AND STRUCTURAL
PLANS FOR ALL INFORMATION.
STAGING, ACCESS, EROSION, AND SEDIMENT CONTROL NOTES:
1. LIMITS OF CONTRACTOR LAYDOWN/STAGING AREA. CONTRACTOR TO
PROVIDE TEMPORARY FENCING AND ANY OTHER MEANS NECESSARY
FOR SAFETY AND SECURITY. ADDITIONAL AREAS OF THE PARKING LOT
MAY BE AVAILABLE WHEN SCHOOL IS NOT IN SESSION, COORDINATE
WITH SCHOOL DISTRICT AS NECESSARY.
2. GATE TO ACCESS CONTRACTOR STAGING AREA. CONTRACTOR MAY
ELECT TO REMOVE GATE AND FENCING AS REQUIRED. CONTRACTOR
SHALL REPAIR TO EXISTING CONDITION UPON PROJECT COMPLETION.
CONTRACTOR SHALL MAINTAIN FIRE DEPARTMENT ACCESS TO NORTH
SIDE OF BUILDING FROM PARKING LOT; CONTRACTOR TO COORDINATE
FINAL ACCESS DETAILS WITH FIRE DEPARTMENT PRIOR TO AND DURING
CONSTRUCTION.
3. PARENT DROP-OFF AREA. CONTRACTOR TO ENSURE DROP OFF ROUTE
IS UNOBSTRUCTED DURING STUDENT PICK-UP AND DROP-OFF TIMES.
4. ACCESSIBLE ROUTE TO ACCESSIBLE PARKING AND R.O.W SIDEWALK.
CONTRACTOR TO MAINTAIN REQUIRED ACCESS AND EGRESS ROUTES
DURING CONSTRUCTION.
5. FIRE ACCESS LANE, CONTRACTOR TO KEEP CLEAR AT ALL TIMES.
COORDINATE ANY CLOSURES OR FIRE ACCESS IMPACTS WITH FIRE
DEPARTMENT PRIOR TO IMPACTING FIRE ACCESS ROUTES.
6. PROVIDE INLET PROTECTION AT EXISTING ON-SITE CATCH BASINS.
PROJECT NO:
DRAWN:
CHECKED:
DATE:
O N
E
IN
C H
E Q
U
AL
S
FU
LL
S
C
AL
E
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
E T
01-31-2025
BJD
MRL
P-2887-23
DESCRIPTION DATE:
GENERAL INFORMATION
APPLICANT / OWNER: CENTENNIAL SCHOOL DISTRICT
18135 SE BROOKLYN STREET
PORTLAND, OR 97239
(503) 760-7990
REPRESENTATIVE: SCOTT ROSE
CONTACT: DAN BODELL
R&C MANAGEMENT GROUP
(503) 312-5404
STRUCTURAL ENGINEER: MATT SMITH, PE, SE
ZCS ENGINEERING & ARCHITECTURE
524 MAIN STREET, SUITE 2
OREGON CITY, OR 97045
(503) 659-2205
CIVIL ENGINEER: ZACH STOKES, PE
ZCS ENGINEERING & ARCHITECTURE
524 MAIN STREET, SUITE 2
OREGON CITY, OR 97045
(503) 659-2205
SITE LOCATION: 15840 SE TAYLOR STREET,
PORTLAND, OR 97233
T01S-R02E-S01
TAX LOT: 100
LOT SIZE: ±15.90 ACRES
ZONING: R7 - RESIDENTIAL 7,000
LEGEND
BUILDING - OUT OF RETROFIT SCOPE
EXISTING UNLESS NOTED OTHERWISE
PROPERTY LINE
FENCINGX
SURFACE CONTOUR - MINOR
CURB
PRIVATE SIDEWALK
SITE STRIPING
BUILDING OVERHANG
SURFACE CONTOUR - MAJOR
GRAVEL
EDGE OF PAVEMENT
BOLLARD / POST
TREE - DECIDUOUS
TREE - CONIFER
SANITARY SEWER MANHOLE
POWER/UTILITY POLE
WATER VALVE
FIRE HYDRANT
GUY WIRE
SANITARY SEWER CLEANOUT
STORM DRAIN MANHOLE
CATCH BASIN
WATER METER
GAS VALVE
IRRIGATION VALVE
WATER VAULT
FIRE DEPARTMENT CONNECTION (FDC)
JUNCTION BOX
SITE LIGHT
OLIVER
MIDDLE SCHOOL
BUILDING - LIMITS OF RETROFIT SCOPE
PARKLANE PARK
SE M
A
IN
STR
EET
SE TA
YLO
R
STR
EET
TEMPORARY CONTRACTOR STAGING AREA
CATCH BASIN INLET PROTECTION
'ADA' ACCESS/EGRESS ROUTE
PARKLANE ELEMENTARY SCHOOL
DBH: 6"
DBH: 14"
DBH: 6"
DBH: 6"
DBH: 8"
DBH: 8"
DBH: 14"
DBH: 12"
DBH: 6"
DBH: 6"
DBH: 18" DBH: 16"
DBH: 10"
DBH: 6"
DBH: 22"
DBH: 21"
DBH: 22"
TRACK AND FIELD
2 2
5 6
PARKLANE
CHURCH
PRIVATE RESIDENCE
PRIVATE RESIDENCE
PRIVATE RESIDENCE
PRIVATE RESIDENCE
PRIVATE RESIDENCE RESIDENTIAL
APARTMENTS
AGRICULTURAL LOT
FIRE ACCESS LANE
EXTERIOR WALL DEMOLITION / RECONSTRUCTION
6 6 6
AutoCAD SHX Text 70128
AutoCAD SHX Text 252.54
AutoCAD SHX Text
AC
AutoCAD SHX Text
JB
AutoCAD SHX Text
JB
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text W
AutoCAD SHX Text
EXPIRES: 06-30-26
AutoCAD SHX Text
81129PE
AutoCAD SHX Text
OREGON
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text W
AutoCAD SHX Text
JB
AutoCAD SHX Text S
AutoCAD SHX Text D
UP
UP
UP
UP
A. ALL EXISTING BUILDING COLUMNS, EXTERIOR
WALLS AND STRUCTURAL MEMBERS TO REMAIN,
U.N.O.
B. CONTRACTOR SHALL KEEP CONSTRUCTION AREA
FREE OF DUST AND DEBRIS FOR THE DURATION
OF CONSTRUCTION AND SHALL BE RESPONSIBLE
FOR DISPOSAL OF ALL DEBRIS.
C. FURNISH ALL LABOR AND MATERIALS/EQUIPMENT
TO COMPLETE DEMOLITION AND REMOVAL OF ALL
ITEMS AS INDICATED. PATCH AND REPAIR
INTERIOR SPACE AS REQUIRED UPON
COMPLETION OF DEMOLITION. IF ANY QUESTIONS
ARISE AS TO THE REMOVAL OF ANY MATERIAL,
CLARIFY THE POINT IN QUESTION WITH PROJECT
TEAM BEFORE PROCEEDING.
D. IN PARTITIONS TO BE REMOVED, REMOVE AND
CAP ALL OUTLETS, SWITCHES, WIRES,
THERMOSTATS, ETC., TO THEIR SOURCE.
E. WHERE INTERIOR PARTITIONS, COLUMN FURRING,
FIXTURES, CABINETRY, DOORS AND DOOR
FRAMES, ARE SCHEDULED FOR REMOVAL,
DISPOSE OF ALL DEBRIS AND PATCH FLOOR AND
WALLS AS REQUIRED. PREPARE SURFACES FOR
NEW FINISHES U.N.O. TYPICAL THROUGHOUT
ENTIRE SPACE.
F. REMOVE ALL ABANDONED ELECTRICAL CONDUIT,
CABLING BACKBOARD AND EQUIPMENT, TYPICAL
THROUGHOUT ENTIRE SPACE. AT COMPLETION OF
DEMOLITION WORK, THE CONSTRUCTION AREA(S)
SHALL BE LEFT IN “BROOM CLEAN” CONDITION.
ALL DEBRIS AND MISCELLANEOUS MATERIAL
SHALL BE REMOVED.
G. IN ADDITION TO SPECIFIC DEMOLITION SCOPE
IDENTIFIED, PERFORM MISCELLANEOUS
DEMOLITION AS REQUIRED TO SUPPORT NEW
CONSTRUCTION.
H. RELOCATION OF SMOKE DETECTORS, AND FIRE
ALARM EQUIPMENT, NECESSITATED BY NEW
CONSTRUCTION, SHALL BE ACCOMPLISHED AS A
FIRST PRIORITY, AND PER THE PLANS. NO ACTIVE
SMOKE DETECTOR SHALL BE PERMANENTLY
COVERED OR OTHERWISE REMOVED OR USED
FOR OTHER THAN ITS INTENDED PURPOSE.
REMOVE TEMPORARY COVERS DAILY.
I. REMOVAL OF ANY EQUIPMENT, CABLING
SWITCHES, AND CONDUIT PERTAINING TO
DATA/COMMUNICATIONS AND TELEPHONE SHALL
BE VERIFIED WITH PROJECT TEAM.
J. CONTRACTOR REQUIRED TO PROTECT ANY
FINISHES, CASEWORK, WINDOWS, DOORS, ECT IN
AREAS WHERE WORK IS REQUIRED.
DEMO PLAN GENERAL NOTES
A
C
D
E
F
G
H
L
1 8 112 7 1210 14
CLASSROOM CLASSROOM CLASSROOM CLASSROOM
CLASSROOMCLASSROOMCLASSROOMCLASSROOMCLASSROOM
CLASSROOM
COUNSELOROFFICE
OFFICE
RR
JANITOR
RR STAGE CAFETERIUM
RR STORAGE A
OFFICE
RECEPTION
MEETING A
ASSISTANT
PRINCIPAL
PRINCIPAL
MDF
RR
HEALTH
MEETING B
MEDIA CENTER
CONFERENCE
RR
STORAGE B
AREA C
AREA B
OUT OF SCOPE
OUT OF SCOPE
B
133 4 5
K
J
6 9
M A
T C
H L
IN
E M
A T
C H
L
IN
E
D1.20
D1.30
KEY PLAN
OUT OF SCOPE
OUT OF SCOPE
C B
OVERALL PLAN LEGEND
HATCH INDICATES AREA
OUT OF SCOPE OF WORK
(E) 1 HR RATED WALL
(E) 2 HR RATED WALL
(E) AREA SEPARATION WALL - 2 HR RATED
EXPIRES: 06-30-26
R
D
EG
IS
TE
RE
P
L
ROFESS IONA
81129PE
OREGON
E
RNG
I NE E
Z
S
A . S
J
7 , 2
Y
A C
H
AR
S
TO
K Ee un 2
524 Main Street, Suite 2 Oregon City, OR 97045
503.659.2205
PROJECT NO.
DATE:
DRAWN:
CHECKED:
O N
E
IN
C H
E Q
U A
LS
F
U
LL
S C
A
LE
DESCRIPTION DATE:
/5
/2
:3
:5
P M
A u to d e sk
D o cs
/P
.O liv e r
M S
R e tr o fit /P
A R
C H
R
.r vt
D1.10
DEMO FLOOR
PLAN - OVERALL
P-2887-23
OLIVER MIDDLE
SCHOOL SEISMIC
RETROFIT
CENTENNIAL SCHOOL DISTRICT
15840 SE TAYLOR ST.
PORTLAND, OR 97233
01-31-2025
JAH
DDS
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
B
ID
A
N D
P E
R M
IT
S
E T
D1.10 1/16" = 1'-0"
DEMO FLOOR PLAN OVERALL1
N
A. ALL EXISTING BUILDING COLUMNS, EXTERIOR
WALLS AND STRUCTURAL MEMBERS TO REMAIN,
U.N.O.
B. CONTRACTOR SHALL KEEP CONSTRUCTION AREA
FREE OF DUST…