SCOPE Attachment 1 NWWW40002300088.pdf
PDF 5 MB Posted
- Solicitation number
- NWWW40002300088SRG
About this file
This document package provides construction drawings, specifications, and calculations for foundation retrofits for various National Oceanic and Atmospheric Administration weather tower sites in Hawaii. The drawings depict existing and proposed concrete foundations and anchorage details for 30-foot tilt-down sensor towers. The specifications establish requirements for concrete mix designs, reinforcement, formwork, and other structural elements. Accompanying calculations demonstrate the capacity of proposed anchor bolts, epoxy anchors, and concrete foundations to resist gravity, wind, and seismic loads according to building code standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 23-00088 amd 0002 SAM.GOV sbc surveyor.docx | DOCX document | |
| RFQ (3) ATTACHEMENT 637074366514600000 NWWW40002300088SRG.pdf | ||
| 23-00088 amd 0001 SAM.GOV sbc surveyor.docx | DOCX document | |
| RFQ (4) ATTACHEMENT HSOIS - South Point NWWW40002300088SRG.pdf | ||
| RFQ (1) posting verbiage NWWW40002300088.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW Attachment 1
HSOIS DCP requirements and typical photos
Figure 1. Typical HSOIS DCP (side view).
Figure 2. Typical HSOIS DCP (front view).
SOW Attachment 2
30-ft tilt-down tower “hinged sensor pole” drawings and specifications
SOW Attachment 3
Typical foundation plans and details for 30-ft tilt-down tower
ST
R
U C
TU
R
A L
G
EN
ER
A
L N
O
TE
S
P A R T N E R S
ENGINEERING
FO
U
N D
A
TI
O N
R
ET
R O
FI
T
D
ES
IG
N
F O
R
V A
R
IO
U S
LO
C
A
TI
O N
S, H
A W
A I'I
TM
K
: V A
R
IO
U S
N O
A A
N W
S
F
O O
T H
IN
G
ED
S
EN
SO
R P
O
LE
M
ET
EO
R
O
LO
G
IC
A L
TO
W
ER
S
S01
STRUCTURAL GENERAL NOTES CONCRETE NOTES REINFORCING STEEL NOTES
ANCHORS
FOUNDATION NOTES
SPECIAL INSPECTION NOTES
AutoCAD SHX Text 09/27/2022 4:16 pm
AutoCAD SHX Text M:\EO PROJECTS\2022 PROJECTS\13003-22-01 TOWER FOUNDATION RETROFIT DESIGN\4-DWG\STRUCTURAL\S-X NOAA.DWG
AutoCAD SHX Text
SHEET NO. OF 2
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
QC'D BY:
AutoCAD SHX Text 13003-22-01
AutoCAD SHX Text 455 E. Lanikaula St. Hilo Hawai`i 96720 Main (808) 933-7900 www.epinc.pro Hawai`i Las Vegas
AutoCAD SHX Text
SEPT 2022
AutoCAD SHX Text Y
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
WILL BE UNDER MY OBSERVATION.
AutoCAD SHX Text
CONSTRUCTION OF THIS PROJECT
AutoCAD SHX Text
ME OR UNDER MY SUPERVISION,
AutoCAD SHX Text
THIS WORK WAS PREPARED BY
AutoCAD SHX Text Exp. 04/30/24
AutoCAD SHX Text No. 9361-S
AutoCAD SHX Text
LICENSED PROFESSIONAL ENGINEER
AutoCAD SHX Text
AutoCAD SHX Text
MAF
AutoCAD SHX Text
KKC
AutoCAD SHX Text
YWF
AutoCAD SHX Text
KKC
AutoCAD SHX Text
1. ALL CONCRETE UNLESS OTHERWISE NOTED SHALL BE REGULAR WEIGHT HARD ROCK ALL CONCRETE UNLESS OTHERWISE NOTED SHALL BE REGULAR WEIGHT HARD ROCK TYPE (150#/CU.FT.). 2. ALL PHASES OF WORK PERTAINING TO THE CONCRETE CONSTRUCTION SHALL CONFORM ALL PHASES OF WORK PERTAINING TO THE CONCRETE CONSTRUCTION SHALL CONFORM TO THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-14) WITH MODIFICATIONS AS NOTED IN THE DRAWINGS OR SPECIFICATIONS. 3. SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES: SCHEDULE OF STRUCTURAL CONCRETE 28-DAY STRENGTH AND TYPES: LOCATION OF STRUCTURE STRENGTH STRENGTH FOOTINGS 3000 PSI 3000 PSI 4. PORTLAND CEMENT SHALL CONFORM TO ASTM C-150 TYPE II. PORTLAND CEMENT SHALL CONFORM TO ASTM C-150 TYPE II. 5. AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND AGGREGATE FOR HARDROCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS OF ASTM C-33 AND PROJECT SPECIFICATIONS. 6. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR HIS REVIEW 2 WEEKS PRIOR TO POUR. 7. CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C-94. CONCRETE MIXING OPERATION, ETC. SHALL CONFORM TO ASTM C-94. 8. PLACEMENT OF CONCRETE SHALL CONFORM TO ACI STANDARD 301 AND PROJECT PLACEMENT OF CONCRETE SHALL CONFORM TO ACI STANDARD 301 AND PROJECT SPECIFICATIONS. 9. UNLESS OTHERWISE NOTED ON THE PLANS, MINIMUM CLEAR COVERAGE OF NEW UNLESS OTHERWISE NOTED ON THE PLANS, MINIMUM CLEAR COVERAGE OF NEW CONCRETE OVER OUTER REINFORCING BARS SHALL BE AS FOLLOWS: A. CONCRETE POURED DIRECTLY CONCRETE POURED DIRECTLY AGAINST EARTH.........................................3" CLEAR TO REINFORCING B. WALL FACES: WALL FACES: EXPOSED TO EARTH WITH FORMED SURFACES OR EXPOSED TO WEATHER.............................1-1/2" CLEAR FOR #5 BAR & SMALLER 2" CLEAR FOR #6 BARS & LARGER 10. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE. 11. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, EQUIPMENT PADS, ETC., SHALL PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, EQUIPMENT PADS, ETC., SHALL BE FORMED WITH 3/4" CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS. 12. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN CONCRETE IS NOT PERMITTED EXCEPT AS SHOWN. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS. 13. CONDUIT OR PIPE SIZE (O.D.) THAT IS BURIED IN ANY CONCRETE SLABS SHALL NOT CONDUIT OR PIPE SIZE (O.D.) THAT IS BURIED IN ANY CONCRETE SLABS SHALL NOT EXCEED 25 PERCENT OF SLAB THICKNESS AND SHALL BE PLACED BETWEEN THE TOP AND BOTTOM REINFORCING UNLESS SPECIFICALLY DETAILED OTHERWISE. CONCENTRATIONS OF CONDUITS OR PIPES SHALL BE AVOIDED EXCEPT WHERE DETAILED OPENINGS ARE PROVIDED. 14. DO NOT USE CONCRETE ADMIXTURES CONTAINING CHLORIDE OR CHLORIDE SALTS. DO NOT USE CONCRETE ADMIXTURES CONTAINING CHLORIDE OR CHLORIDE SALTS. 15. ALL ROUGHENED SURFACES IN CONCRETE SHALL BE MADE WITH A MINIMUM ALL ROUGHENED SURFACES IN CONCRETE SHALL BE MADE WITH A MINIMUM AMPLITUDE OF 1/4" 16. NO ADDITIONAL WATER IS ALLOWED IN THE CONCRETE MIX AT THE SITE. NO ADDITIONAL WATER IS ALLOWED IN THE CONCRETE MIX AT THE SITE. 17. READY-MIX CONCRETE SUPPLIER SHALL INCLUDE WATER REDUCER, RETARDER, READY-MIX CONCRETE SUPPLIER SHALL INCLUDE WATER REDUCER, RETARDER, SUPERPLASTICIZER AND/OR OTHER CONCRETE ADMIXTURES TO ACHIEVE THE SPECIFICATION AND WORKABILITY AT THE JOB SITE. 18. CONTRACTOR AND READY-MIX CONCRETE SUPPLIER SHALL FOLLOW THE CONTRACTOR AND READY-MIX CONCRETE SUPPLIER SHALL FOLLOW THE ADMIXTURE MANUFACTURERS' RECOMMENDATIONS FOR MIXING, DOSAGE, HANDLING, PROCESSING OF THE ADMIXTURES AND FRESH CONCRETE.
AutoCAD SHX Text
1. REINFORCING STEEL DRILLED AND EXPOXIED INTO EXISTING CONCRETE AS DETAILED ON REINFORCING STEEL DRILLED AND EXPOXIED INTO EXISTING CONCRETE AS DETAILED ON THE DRAWINGS SHALL BE ONE OF THE FOLLOWING OR APPROVED EQUIVALENT: A. SIMPSON 'SET-XP' ICC REPORT ESR-2508 SIMPSON 'SET-XP' ICC REPORT ESR-2508 ICC REPORT ESR-2508 B. HILTI 'RE-500 V3' ICC REPORT ESR-2322 HILTI 'RE-500 V3' ICC REPORT ESR-2322 ICC REPORT ESR-2322 C. DEWALT 'PURE 110+' ICC REPORT ESR-3298 DEWALT 'PURE 110+' ICC REPORT ESR-3298 ICC REPORT ESR-3298 2. INSTALLATION OF EPOXIED DOWELS SHALL FOLLOW THE STRICT RECOMMENDATIONS OF INSTALLATION OF EPOXIED DOWELS SHALL FOLLOW THE STRICT RECOMMENDATIONS OF THE MANUFACTURER AND THE APPLICABLE ICC REPORT AND HAVE A MINIMUM OF 9 DIAMETERS EMBEDMENT. 3. INSTALLATION SHALL FOLLOW THE STRICT RECOMMENDATIONS OF THE MANUFACTURER INSTALLATION SHALL FOLLOW THE STRICT RECOMMENDATIONS OF THE MANUFACTURER AND THE APPLICABLE ICC ER REPORT. CONTRACTOR SHALL HAVE APPROPRIATE ICC ER REPORT ON-SITE DURING ALL INSTALLATIONS. 4. ANY ENGINEERING DESIGN PROVIDED BY CONTRACTOR OR OTHERS SHALL BE ANY ENGINEERING DESIGN PROVIDED BY CONTRACTOR OR OTHERS SHALL BE SUBMITTED FOR REVIEW BY THE INSURED AND REGISTERED STRUCTURAL ENGINEER WITH CONTINUOUS FIVE YEARS OF EXPERIENCE IN THE TYPE OF DESIGN SUBMITTED.
AutoCAD SHX Text
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-14), THE CRSI "MANUAL OF STANDARD PRACTICE," AND THE "ACI DETAILING MANUAL (SP-66) AS MODIFIED BY THE PROJECT DRAWINGS AND SPECIFICATIONS. 2. REINFORCING BARS SHALL CONFORM TO ASTM A-615 GRADE 60 REQUIREMENTS. #4 REINFORCING BARS SHALL CONFORM TO ASTM A-615 GRADE 60 REQUIREMENTS. #4 AND SMALLER BARS MAY BE GRADE 40. 3. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS ARE TO BE SECURELY TIED IN ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS ARE TO BE SECURELY TIED IN PLACE BEFORE CONCRETE IS POURED. 4. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. 5. REINFORCING SPLICES SHALL BE MADE ONLY WHERE INDICATED ON THE DRAWINGS. REINFORCING SPLICES SHALL BE MADE ONLY WHERE INDICATED ON THE DRAWINGS. 6. DOWELS BETWEEN FOOTING AND WALL OR COLUMNS SHALL BE THE SAME GRADE, SIZE, DOWELS BETWEEN FOOTING AND WALL OR COLUMNS SHALL BE THE SAME GRADE, SIZE, SPACING, AND NUMBER AS THE VERTICAL REINFORCING RESPECTIVELY, U.O.N. 7. WELDING OF REINFORCING STEEL IS NOT PERMITTED UNLESS OTHERWISE SHOWN ON WELDING OF REINFORCING STEEL IS NOT PERMITTED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. 8. CONTRACTOR SHALL SUBMIT REINFORCING BAR LAYOUTS AND DETAILS FOR ARCHITECT'S CONTRACTOR SHALL SUBMIT REINFORCING BAR LAYOUTS AND DETAILS FOR ARCHITECT'S REVIEW PRIOR TO FABRICATION. FABRICATE FROM REVIEWED DRAWINGS ONLY. FABRICATE FROM REVIEWED DRAWINGS ONLY. . 9. REINFORCING BARS SHALL BE AS LONG AS PRACTICABLE AND AS DETAILED AND SHALL REINFORCING BARS SHALL BE AS LONG AS PRACTICABLE AND AS DETAILED AND SHALL BE LAPPED AT SPLICES AND CORNERS NOT LESS THAN 32 BAR DIAMETER (24" MINIMUM), UNLESS OTHERWISE SHOWN. STAGGER HORIZONTAL WALL BAR SPLICES. IN GENERAL, BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN BEAMS AND SLABS, SPLICE TOP BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS, UNLESS OTHERWISE SHOWN. 10. EMBEDDED METAL COMPONENTS MADE UP OF ALLOYS THAT ARE DIS-SIMILAR TO THAT EMBEDDED METAL COMPONENTS MADE UP OF ALLOYS THAT ARE DIS-SIMILAR TO THAT OF THE REINFORCING STEEL SHALL NOT BE ATTACHED DIRECTLY TO REINFORCING. MEASURES SHALL BE TAKEN TO ELECTRICALLY ISOLATE SAID COMPONENTS FROM ANY REINFORCING TO PREVENT CATHODIC EFFECTS. 11. REINFORCING STEEL PLACED BELOW THE WATER TABLE SHALL BE EPOXY COATED PER REINFORCING STEEL PLACED BELOW THE WATER TABLE SHALL BE EPOXY COATED PER ASTM A775. ANY DAMAGES OR DEFFECTS OF EPOXY COATING SHALL BE REPAIRED WITH PATCHING MATERIAL PER MANUFACTURER'S INSTRUCTIONS. BARS WITH MORE THAN 1% DAMAGED AREA PER FOOT SHALL BE DISCARDED.
AutoCAD SHX Text
1. THE FOUNDATION DESIGN WAS BASED ON THE ASSUMPTIONS PRESENTED BELOW IN THE THE FOUNDATION DESIGN WAS BASED ON THE ASSUMPTIONS PRESENTED BELOW IN THE ABSENCE OF A SOILS REPORT: ALLOWABLE SOIL BEARING PRESSURE = 2000 PSF = 2000 PSF ALLOWABLE PASSIVE EARTH RESISTANCE = 150 PCF = 150 PCF FRICTIONAL RESISTANCE = 0.4 X DEAD LOAD = 0.4 X DEAD LOAD 2. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING AREA SHALL BE FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING AREA SHALL BE MECHANICALLY COMPACTED IN LAYERS. FLOODING IS PROHIBITED. 3. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM EITHER CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM EITHER SURFACE WATER, GROUND WATER, OR SEEPAGE. 4. IF THE CONTRACTOR DISCOVERS UNCOMPACTED FILL OR UNSUITABLE MATERIAL IN THE IF THE CONTRACTOR DISCOVERS UNCOMPACTED FILL OR UNSUITABLE MATERIAL IN THE EXCAVATION, ALL UNCOMPACTED FILL AND/OR UNSUITABLE MATERIAL WITHIN THE FOOTING SHALL BE REMOVED AND BACKFILLED WITH SUITABLE STRUCTURAL FILL. 5. UNSUITABLE MATERIALS ARE ORGANIC MATTERS I.E. GREEN WASTE, BAGASSE, ROOTS, STUMPS, UNSUITABLE MATERIALS ARE ORGANIC MATTERS I.E. GREEN WASTE, BAGASSE, ROOTS, STUMPS, CONSTRUCTION LUMBER, RUBBISH I.E. PLASTIC, METAL, DOMESTIC AND CONSTRUCTION WASTE, UNPROCESSED CONCRETE PARTICLES LARGER THAN 3 INCH DIAMETER, NATIVE VOLCANIC ASH SOIL AND CINDERS, MUCK, MUD AND ANY HAZARDOUS MATERIAL I.E. ASBESTOS, CONTAMINATED SOIL. 6. ALL BUILDING FOUNDATION AND SLAB SHALL BEAR ON FIRM SUBGRADE I.E. SOLID BASALT ROCK, ALL BUILDING FOUNDATION AND SLAB SHALL BEAR ON FIRM SUBGRADE I.E. SOLID BASALT ROCK, SCARIFIED AND RE-COMPACTED NATIVE FRACTURED ROCK / GRANULAR MATERIAL, OR COMPACTED STRUCTURAL BACKFILL OVER COMPACTED SUBGRADE. ALL COMPACTION EFFORT FOR BUILDING PAD SHALL BE MINIMUM 95% COMPACTION. 7. WHERE ROCK-SOIL (VOLCANIC ASH) MIX IS FOUND TO HAVE SOIL CONTENT MORE WHERE ROCK-SOIL (VOLCANIC ASH) MIX IS FOUND TO HAVE SOIL CONTENT MORE THAN 30% BY VOLUME, THE FOOTING SHALL BE OVER-EXCAVATED 2 FEET BELOW THE FOOTING, LAY DOWN MIRAFI HP 370 GEOTEXTILE AND BACKFILL WITH 3” MINUS COMPACTED MINUS COMPACTED STRUCTURAL FILL.
AutoCAD SHX Text
1. ALL WORK SHALL CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE AS AMENDED ALL WORK SHALL CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE AS AMENDED BY THE COUNTY OF HAWAII. 2. STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE, AND DO NOT SPECIFY STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE, AND DO NOT SPECIFY THE MEANS AND METHODS OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEANS NECESSARY TO PROTECT THE STRUCTURE, AND ANY ADJACENT NEW OR EXISTING STRUCTURES DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING AND SHORING FOR LOADS ACTING ON THE STRUCTURE DURING CONSTRUCTION. OBSERVATION BY THE STRUCTURAL ENGINEER DURING CONSTRUCTION WILL NOT INCLUDE INSPECTION OF AFOREMENTIONED BRACING AND SHORING. 3. EXISTING CONDITIONS ARE SHOWN TO THE BEST OF OUR KNOWLEDGE. DISCREPANCIES EXISTING CONDITIONS ARE SHOWN TO THE BEST OF OUR KNOWLEDGE. DISCREPANCIES SHALL PROMPTLY BE REPORTED TO THE ENGINEER AND BE RESOLVED BEFORE PROCEEDING WITH THE WORK. 4. PRIOR TO COMMENCEMENT OF CONSTRUCTION, THE CONTRACTOR SHALL VERIFY THE PRIOR TO COMMENCEMENT OF CONSTRUCTION, THE CONTRACTOR SHALL VERIFY THE LOCATIONS OF ALL UTILITIES, WHICH MAY BE AFFECTED BY ITS WORK. INTERFERENCES WITH THE STRUCTURE SHALL PROMPTLY BE REPORTED TO THE ENGINEER AND BE RESOLVED BEFORE PROCEEDING WITH THE WORK. 5. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR COORDINATING THE WORK OF THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND VERIFYING ALL DIMENSIONS. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ALL STRUCTURAL DISCREPANCIES, AND THESE DISCREPANCIES SHALL BE RESOLVED PRIOR TO PROCEEDING WITH THE WORK. 6. SHOULD A DISCREPANCY OCCUR ON THE DRAWINGS BETWEEN ANY PROJECT SPECIAL SHOULD A DISCREPANCY OCCUR ON THE DRAWINGS BETWEEN ANY PROJECT SPECIAL NOTES/SPECIAL DETAILS, AND THE TYPICAL SPECS/TYPICAL DETAILS, SAID SPECIAL NOTES/SPECIAL DETAILS SHALL TAKE PRECEDENCE. DETAILS NOTED AS TYPICAL SHALL APPLY IN ALL CONDITIONS UNLESS SPECIFICALLY SHOWN OR NOTED. 7. PENETRATIONS AND OPENINGS WITH ANY DIMENSION GREATER THAN 2" THAT ARE NOT PENETRATIONS AND OPENINGS WITH ANY DIMENSION GREATER THAN 2" THAT ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS ARE PROHIBITED UNLESS APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. NO PENETRATION SHALL BE ALLOWED THROUGH ANY STRUCTURAL MEMBER WITHOUT THE APPROVAL OF THE ENGINEER. 8. DESIGN CRITERIA - DESIGN CRITERIA - A. DESIGN DEAD LOADS DESIGN DEAD LOADS 1. SELF WEIGHT WITH ATTACHMENTS = 300 LB = 300 LB B. WIND WIND BASIC WIND SPEED 144 MPH 144 MPH Veff - ASD 112 MPH 112 MPH RISK CATEGORY III III EXPOSURE CATEGORY D D C. SEISMIC SEISMIC OCCUPANCY CATEGORY III III SITE CLASS D D Cs 1.0 1.0 9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF THE ADJACENT THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF THE ADJACENT PROPERTIES, STRUCTURES, STREETS AND UTILITIES DURING THE CONSTRUCTION PERIOD. 10. THE GENERAL CONTRACTOR AND ITS SUBCONTRACTORS MUST SUBMIT IN WRITING ANY THE GENERAL CONTRACTOR AND ITS SUBCONTRACTORS MUST SUBMIT IN WRITING ANY REQUESTS FOR MODIFICATIONS TO THE PLANS AND SPECIFICATIONS.
AutoCAD SHX Text
1. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT SPECIAL INSPECTION OF CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT SPECIAL INSPECTION OF PORTIONS OF THE WORK , AS REQUIRED BY THE BUILDING CODE OF THE COUNTY OF HAWAII, BE MADE AT THE APPROPRIATE TIME. THE CONTRACTOR SHALL GIVE TIMELY NOTICE OF WHEN AND WHERE INSPECTIONS ARE TO BE MADE AND PROVIDE ACCESS FOR THE INSPECTOR. THE CONTRACTOR SHALL CORRECT DEFECTIVE WORK AT NO ADDITIONAL COST TO THE OWNER AND THE CONTRACTOR SHALL PAY FOR RE-INSPECTION. 2. THE FOLLOWING IS A SUMMARY OF THE SPECIAL INSPECTION REQUIREMENTS: THE FOLLOWING IS A SUMMARY OF THE SPECIAL INSPECTION REQUIREMENTS: CONCRETE REINFORCING STEEL & FORMWORK YES, PER IBC TABLE 1705.3 YES, PER IBC TABLE 1705.3 ANCHOR BOLTS (RODS) IN CONCRETE YES, PER IBC TABLE 1705.3 YES, PER IBC TABLE 1705.3 CONCRETE POUR YES, PER IBC TABLE 1705.3 YES, PER IBC TABLE 1705.3 CONCRETE CYLINDER TEST YES, PER IBC TABLE 1705.3 YES, PER IBC TABLE 1705.3 PERIODIC SPECIAL CASES YES, EPOXY ANCHORS & DOWELSYES, EPOXY ANCHORS & DOWELS
1 TYP. FOOTING REINF. DETAIL
AT CORNER AT INTERSECTION AT ENDS
2 TYP. REINF. BENDING DETAIL
STANDARD HOOKS
TYPICAL
COLUMN
BAR OFFSET
90° HOOK180° HOOK
1-PIECE CLOSED HOOP ALTERNATE 2-PIECE HOOP
#3 or #4
VERT.
DOWEL
TIES &
STIRRUPS
5 BOLT RETROFIT FOUNDATION REPAIR 4 EPOXY ANCHOR FOUNDATION REPAIR 3 NEW 30' TILT TOWER FOUNDATION S02
FO
U
N D
A
TI
O N
P
LA
N S
A N
D D
ET
A
IL
S
P A R T N E R S
ENGINEERING
FO
U
N D
A
TI
O N
R
ET
R O
FI
T
D
ES
IG
N
F O
R
V A
R
IO
U S
LO
C
A
TI
O N
S, H
A W
A I'I
TM
K
: V A
R
IO
U S
N O
A A
N W
S
F
O O
T H
IN
G
ED
S
EN
SO
R P
O
LE
M
ET
EO
R
O
LO
G
IC
A L
TO
W
ER
S
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
STANDARD HOOK
AutoCAD SHX Text
STANDARD HOOK
AutoCAD SHX Text
#4 LAP 2'-0" #5 LAP 2'-6" #6 LAP 3'-0"
AutoCAD SHX Text
#4 LAP 2'-0" #5 LAP 2'-6" #6 LAP 3'-0"
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
BAR SIZE
AutoCAD SHX Text 'D'
AutoCAD SHX Text
#3 THRU #8
AutoCAD SHX Text
#9 THRU #11
AutoCAD SHX Text
#14 THRU #18
AutoCAD SHX Text 6d b
AutoCAD SHX Text 8d b
AutoCAD SHX Text 10d b
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
135° HOOK
AutoCAD SHX Text BEND DIA. "D" = 4d b
AutoCAD SHX Text
ALTERNATE HOOK
AutoCAD SHX Text
135° HOOK
AutoCAD SHX Text
90° HOOK
AutoCAD SHX Text
BEND DIA. "D" FOR STD. HOOKS
AutoCAD SHX Text
BAR SIZE
AutoCAD SHX Text 'D'
AutoCAD SHX Text #3
AutoCAD SHX Text #4
AutoCAD SHX Text #5
AutoCAD SHX Text 1-1/2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2-1/2"
AutoCAD SHX Text D=6d d b
AutoCAD SHX Text BEND DIA. "D" = 4d b
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 3/4" = 1'-0"
AutoCAD SHX Text 1'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3'
AutoCAD SHX Text
(E) FOUNDATION
AutoCAD SHX Text
(N) CONCRETE FOUNDATION
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
(6)-#7 BARS EVENLY SPACED EACH WAY TOP AND BOTTOM
AutoCAD SHX Text
(N) OR (E) TILT TOWER BASE PLATE
AutoCAD SHX Text
(N) TILT TOWER BASE PLATE
AutoCAD SHX Text
STD. 90°HOOK
AutoCAD SHX Text
6" THK. AGGREGATE BASECOURSE
AutoCAD SHX Text
6" THK. AGGREGATE BASECOURSE
AutoCAD SHX Text
6" THK. AGGREGATE BASECOURSE
AutoCAD SHX Text
3/4" CHAMFER AT EXPOSED EDGE
AutoCAD SHX Text
(N) CONCRETE FOUNDATION
AutoCAD SHX Text
(E) CONCRETE FOUNDATION
AutoCAD SHX Text (4)-1" X 32" LONG BNC GALVANIZED STEEL ANCHOR RODS, ASTM F1554 GR 55, TOP GALVANIZED PER ASTM 153. PROVIDE DOUBLE NUTS, LOCK WASHER AND FLAT WASHER AT EACH BOLT.
AutoCAD SHX Text
(N) ANCHOR RODS
AutoCAD SHX Text
1/2" SLOPE TO DRAIN TYPICAL
AutoCAD SHX Text
(N) OR (E) TILT TOWER BASE PLATE
AutoCAD SHX Text
(E) CONCRETE FOUNDATION
AutoCAD SHX Text (4)-1" BNC GALVANIZED STEEL ANCHOR RODS, ASTM F1554 GR 55, TOP GALVANIZED PER ASTM 153. PROVIDE DOUBLE NUTS, LOCK WASHER AND FLAT WASHER AT EACH BOLT.
AutoCAD SHX Text
(N) ANCHOR RODS ON SIMPSON HSCNW1 ZINC PLATED HIGH STRENGTH NUT COUPLER. THREAD EXISTING ROD IN PLACE AS REQUIRED TO INSTALL NUT COUPLER BELOW BASE PLATE.
AutoCAD SHX Text CHIP OUT AND REMOVE EXISTING CONCRETE TO EXPOSE NON-CORRODED PORTION OF EXISTING ANCHOR ROD. REMOVE DAMAGED PORTION OF ROD AND PATCH WITH PLANITOP X REPAIR MORTAR OR EQUAL.
AutoCAD SHX Text
90 DEGREE CUT BY 1" DEEP MINIMUM TYPICAL
AutoCAD SHX Text
(E) FOUNDATION
AutoCAD SHX Text
(N) HILTI HAS-E ROD WITH HIT-RE 500 VE EPOXY INTO EXISTING FOUNDATION, TYPICAL.
AutoCAD SHX Text (4)-1" X 18" HILTI HAS-E RODS. PROVIDE DOUBLE NUTS, LOCK WASHER AND FLAT WASHER AT EACH BOLT.
AutoCAD SHX Text
AutoCAD SHX Text
MAF
AutoCAD SHX Text
MAF
AutoCAD SHX Text
YWF
AutoCAD SHX Text
KKC
AutoCAD SHX Text 09/27/2022 4:16 pm
AutoCAD SHX Text M:\EO PROJECTS\2022 PROJECTS\13003-22-01 TOWER FOUNDATION RETROFIT DESIGN\4-DWG\STRUCTURAL\S-X NOAA.DWG
AutoCAD SHX Text
SHEET NO. OF 2
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
REV.
AutoCAD SHX Text
JOB NO.
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
QC'D BY:
AutoCAD SHX Text 13003-22-01
AutoCAD SHX Text 455 E. Lanikaula St. Hilo Hawai`i 96720 Main (808) 933-7900 www.epinc.pro Hawai`i Las Vegas
AutoCAD SHX Text
SEPT 2022
AutoCAD SHX Text Y
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text
AutoCAD SHX Text I
AutoCAD SHX Text U
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
WILL BE UNDER MY OBSERVATION.
AutoCAD SHX Text
CONSTRUCTION OF THIS PROJECT
AutoCAD SHX Text
ME OR UNDER MY SUPERVISION,
AutoCAD SHX Text
THIS WORK WAS PREPARED BY
AutoCAD SHX Text Exp. 04/30/24
AutoCAD SHX Text No. 9361-S
AutoCAD SHX Text
LICENSED PROFESSIONAL ENGINEER
SOW Attachment 4
Typical structural calculations for 30-ft tilt-down tower
EPI JOB #:
CALCS BY:
DATE:
Table of Contents
Design Code Search
1 Gravity Loads
Dead & Live Loads
2 Wind Load Analysis
Wind Load Data - 125 Knots 3-second gust = 144 mph IBC Basic Wind Speed
3 Foundation and Anchor Calculations
Foundation Calculation - Existing Fdns N.G. - 5' sq x 4' thick Req'd
Cast-in-Place Anchor Calculation - J bolt OK by inspection - Use Nut Coupler
Epoxy Anchor Calculation - 1" Hilti HAS steel rod & HIT-RE 500 V3 - 8" embed
4 Submittals
Nut Coupler Submittal -Simpson HSCNW1
Epoxy Anchor Submittal - 1 Hilti HAS Carbon steel rod & HIT-RE 500 V3
21-29
Description
Permit Submittal9/21/2022
DateRevision
Page
Various
Engineering PartnersNOAA Tower Fdn Retrofit 13003-22-01
MAF
9/21/2022
Structural Calculations For
NOAA Tower Fdn Retrofit
455 E. Lanikaula St.
Hilo, Hawaii 96720
(808) 933-7900
TMK:
Y
E
N
W
E N
F
A
N
G
S
I ,I
U
A
W
H
A
A
SIGNATURE
WILL BE UNDER MY OBSERVATION.
CONSTRUCTION OF THIS PROJECT
ME OR UNDER MY SUPERVISION,
THIS WORK WAS PREPARED BY
Exp. 04/30/24
No. 9361-S
LICENSED
PROFESSIONAL
ENGINEER
DATE:
DESIGN CODE SEARCH
Building Code: IBC
Project Address: Various
TMK: Various
Intended Use of Structure: Commercial
Fire Resistance Requirements: Non-Combustible
GRAVITY LOADS
Live Loads:
Dead Loads:
Sensor 20 lb Weight of 8" Al Pipe 10 lb/ft
Lights 15 lb Length of Straight Pipe ft
Cable 8 lb Weight of 4" Al Pipe 4 lb/ft
Length of Taper Pipe ft
Weight
Attach 43 lb Weight of Pole lb
Total Weight of Pole kip
7.5
22.5
0.3
None
9/21/2022 (808) 933-7900
NOAA Tower Fdn Retrofit Engineering Partners
13003-22-01 455 E. Lanikaula St.
MAF Hilo, Hawaii 96720
DATE:
Input Value
WIND LOAD ANALYSIS CODE: ASCE 7-16 Computed Ultimate Values
Computed ASD Values
V= mph Basic Wind Speed (Per Maps)
Veff-asd= mph Effective Allowable Stress Design Wind Speed [V * sqrt (.625)]
Risk Cat=
Exposure= From Hawaii Wind Maps
Gcpi = ± [ See ASCE 7-16 Table 26.13-1 ]
Height, h= ft
Kd=
Kzt=
Kz=
Ke=
G= qh=qi=q= PSF = [ 0.00256*V^2*Kzt*Kd*Kz*Ke ] q-asd= PSF
F=qGCfAf ASCE 7-16 29.4-1
Cf=
Area of Attachments
Aa= sq in
Aa= sq ft
Wind Load At Top of Pole
Fw= kip
Dist Wind Load on Pole dws= kip/ft dwt= kip/ft Wind Load Governs. Distributed Wind Load is >2x the self-weight.
Total Wind Reactions at Base
Vw= kip
Mw= ft-kip in-kip217.9
1.2
2.0
0.12
0.04
1.0
18.16
0.02
1.16
61.58
36.95
9/21/2022 (808) 933-7900
0.85
NOAA Tower Fdn Retrofit Engineering Partners
13003-22-01 455 E. Lanikaula St.
MAF Hilo, Hawaii 96720
III
D
0.18
Enclosed
General Footing LIC# : KW-06015905, Build:20.22.8.17 ENGINEERING PARTNERS LLC (c) ENERCALC INC 1983-2022
DESCRIPTION: Tilt-Tower Fdn
Project File: 13003-22-01.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
Code References Calculations per ACI 318-14, IBC 2018, CBC 2019, ASCE 7-16 Load Combinations Used : ASCE 7-16
General Information Material Properties Soil Design Values
2.0
Analysis Settings
250.0 ksi No ksfAllowable Soil Bearing =
3.0 60.0
3,122.02 145.0
= 0.30Flexure = 0.90 Shear =
Values
0.00090
Soil Passive Resistance (for Sliding)
1.0
Increases based on footing plan dimension
Add Pedestal Wt for Soil Pressure No:
Use Pedestal wt for stability, mom & shear No:
Allowable pressure increase per foot of depth = ksf when max. length or width is greater than = ft
Add Ftg Wt for Soil Pressure Yes Yes:Use ftg wt for stability, moments & shears when footing base is below ft pcf Increase Bearing By Footing Weight
= pcf
Min. Overturning Safety Factor
: 1
Increases based on footing Depth0.750
Soil/Concrete Friction Coeff.
Ec : Concrete Elastic Modulus
Footing base depth below soil surface ft
=Allow press. increase per foot of depth ksf
: 11.0Min. Sliding Safety Factor =
Concrete Density
Min Allow % Temp Reinf.
ksif'c : Concrete 28 day strength fy : Rebar Yield ksi
Min Steel % Bending Reinf.
Soil Density = 110.0 pcf
Dimensions Width parallel to X-X Axis 5.0 ft Length parallel to Z-Z Axis
5.0 ft
Pedestal dimensions...
px : parallel to X-X Axis in pz : parallel to Z-Z Axis in Height = in
Footing Thickness
48.0 in=
Rebar Centerline to Edge of Concrete...
= inat Bottom of footing 3.0
Reinforcing
Bars parallel to X-X Axis
Reinforcing Bar Size
Number of Bars
5.0
Bars parallel to Z-Z Axis
Reinforcing Bar Size = 7 Number of Bars = 5.0
Bandwidth Distribution Check (ACI 15.4.4.2) Direction Requiring Closer Separation n/a # Bars required within zone n/a # Bars required on each side of zone n/a
Applied Loads
0.30 D Lr
ksf
L S P : Column Load OB : Overburden = k W E
M-zz V-x
= 1.0 k
V-z k
M-xx =
18.20 k-ft= k-ft
H
DESCRIPTION: Tilt-Tower Fdn
Project File: 13003-22-01.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
PASS 4.440 Sliding - X-X 1.0 k 4.440 k D Only PASS n/a Sliding - Z-Z 0.0 k 0.0 k No Sliding
DESIGN SUMMARY Design OK Governing Load CombinationMin. Ratio Item Applied Capacity
PASS 0.9785 Soil Bearing 1.957 ksf 2.0 ksf D Only about Z-Z axis PASS n/a Overturning - X-X 0.0 k-ft 0.0 k-ft No Overturning PASS 1.667 Overturning - Z-Z 22.20 k-ft 37.0 k-ft D Only
PASS n/a Uplift 0.0 k 0.0 k No Uplift PASS 0.03083 Z Flexure (+X) 3.697 k-ft/ft 119.912 k-ft/ft +1.40D PASS 0.0210 Z Flexure (-X) 2.518 k-ft/ft 119.912 k-ft/ft +1.40D PASS 0.000438 X Flexure (+Z) 0.05250 k-ft/ft 119.912 k-ft/ft +1.40D PASS 0.000438 X Flexure (-Z) 0.05250 k-ft/ft 119.912 k-ft/ft +1.40D PASS n/a 1-way Shear (+X) 0.0 psi 82.158 psi n/a PASS 0.0 1-way Shear (-X) 0.0 psi 0.0 psi n/a PASS n/a 1-way Shear (+Z) 0.0 psi 82.158 psi n/a PASS n/a 1-way Shear (-Z) 0.0 psi 82.158 psi n/a PASS n/a 2-way Punching 0.2627 psi 82.158 psi +1.40D
Detailed Results
Rotation Axis & ZeccXecc Actual Soil Bearing Stress @ Location Actual / Allow Soil Bearing
(in)Gross Allowable Bottom, -Z Top, +Z Left, -X Right, +X RatioLoad Combination...
X-X, D Only 2.0 n/a0.5920 0.5920 n/a 0.2960.0n/a X-X, +0.60D 2.0 n/a0.3552 0.3552 n/a 0.1780.0n/a Z-Z, D Only 2.0 0.0n/a n/a 1.957 0.979n/a18.0 Z-Z, +0.60D 2.0 0.0n/a n/a 1.174 0.587n/a18.0
Rotation Axis & Overturning Stability
Load Combination... StatusOverturning Moment Resisting Moment Stability Ratio X-X, D Only None 0.0 k-ft Infinity OK X-X, +0.60D None 0.0 k-ft Infinity OK Z-Z, D Only 22.20 k-ft 37.0 k-ft 1.667 OK Z-Z, +0.60D 13.320 k-ft 22.20 k-ft 1.667 OK
Force Application Axis
Sliding Stability All units k
Load Combination... StatusSliding Force Resisting Force Stability Ratio X-X, D Only 1.0 k 4.440 k 4.440 OK X-X, +0.60D 0.60 k 2.664 k 4.440 OK Z-Z, D Only 0.0 k 4.440 k No Sliding OK Z-Z, +0.60D 0.0 k 2.664 k No Sliding OK
Flexure Axis & Load Combination in^2 in^2 in^2 k-ft As Req'd
Footing Flexure Tension k-ft Actual As StatusMu Side
Surface Gvrn. As Phi*Mn
X-X, +1.40D 0.05250 +Z Bottom 0.5184 AsMin 0.60 119.912 OK X-X, +1.40D 0.05250 -Z Bottom 0.5184 AsMin 0.60 119.912 OK X-X, +1.20D 0.0450 +Z Bottom 0.5184 AsMin 0.60 119.912 OK X-X, +1.20D 0.0450 -Z Bottom 0.5184 AsMin 0.60 119.912 OK X-X, +0.90D 0.03375 +Z Bottom 0.5184 AsMin 0.60 119.912 OK X-X, +0.90D 0.03375 -Z Bottom 0.5184 AsMin 0.60 119.912 OK Z-Z, +1.40D 2.518 -X Top 0.5184 AsMin 0.60 119.912 OK Z-Z, +1.40D 3.697 +X Bottom 0.5184 AsMin 0.60 119.912 OK Z-Z, +1.20D 2.158 -X Top 0.5184 AsMin 0.60 119.912 OK Z-Z, +1.20D 3.169 +X Bottom 0.5184 AsMin 0.60 119.912 OK Z-Z, +0.90D 1.619 -X Top 0.5184 AsMin 0.60 119.912 OK Z-Z, +0.90D 2.377 +X Bottom 0.5184 AsMin 0.60 119.912 OK
DESCRIPTION: Tilt-Tower Fdn
Project File: 13003-22-01.ec6
Project Title:
Engineer:
Project ID:
Project Descr:
One Way Shear Vu @ +XLoad Combination... Vu @ -X Vu @ -Z Vu @ +Z Vu:Max Vu / Phi*VnPhi Vn Status
+1.40D 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK +1.20D 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK +0.90D 0.00 0.00 0.00 0.00 0.00 82.16 0.00psipsipsipsipsipsi OK
Vu / Phi*Vn Two-Way "Punching" Shear All units k
StatusVu Phi*VnLoad Combination...
+1.40D 0.26 164.32 0.001599 OKpsipsi +1.20D 0.23 164.32 0.00137 OKpsipsi +0.90D 0.17 164.32 0.001028 OKpsipsi www.hilti.com Profis Anchor 2.9.4
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
Sub-Project I Pos. No.:
Date:
9/21/2022
Specifier's comments:
1 Input data Anchor type and diameter: Hex Head ASTM F 1554 GR. 55 1
Effective embedment depth: hef = 25.000 in.
Material: ASTM F 1554
Proof: Design method ACI 318-08 / CIP
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in.
Anchor plate: lx x ly x t = 24.000 in. x 24.000 in. x 0.500 in.; (Recommended plate thickness: not calculated
Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x 4.000 in. x 0.250 in.
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 48.000 in.
Reinforcement: tension: condition B, shear: condition B;
edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) no
R - The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.] & Loading [lb, in.lb]
Existing J bolts embedded 36" www.hilti.com
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
2 Load case/Resulting anchor forces Load case: Design loads
Anchor reactions [lb] Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 5,281 250 250 0
2 0 250 250 0 3 5,281 250 250 0 4 0 250 250 0 max. concrete compressive strain: 0.06 [‰] max. concrete compressive stress: 257 [psi] resulting tension force in (x/y)=(-9.500/0.000): 10,562 [lb] resulting compression force in (x/y)=(10.824/0.000): 10,862 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Tension Compression
1 2
3 4 x y
3 Tension load Load Nua [lb] Capacity f f f f Nn [lb] Utilization bbbbN = Nua/f f f f Nn Status
Steel Strength* 5,281 34,087 16 OK
Pullout Strength* 5,281 19,538 28 OK
Concrete Breakout Strength** 10,562 35,819 30 OK
Concrete Side-Face Blowout, direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
Nsa = Ase,N futa ACI 318-08 Eq. (D-3) f Nsa ³ Nua ACI 318-08 Eq. (D-1)
Variables
Ase,N [in.2] futa [psi]
0.61 75,000
Calculations
Nsa [lb] 45,450
Results
Nsa [lb] f steel f Nsa [lb] Nua [lb] 45,450 0.750 34,087 5,281
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
3.2 Pullout Strength
NpN = y c,p Np ACI 318-08 Eq. (D-14) Np = 8 Abrg f'c ACI 318-08 Eq. (D-15) f NpN ³ Nua ACI 318-08 Eq. (D-1)
Variables y c,p Abrg [in.2] f'c [psi]
1.000 1.16 3,000
Calculations
Np [lb] 27,912
Results
Npn [lb] f concrete f Npn [lb] Nua [lb] 27,912 0.700 19,538 5,281
3.3 Concrete Breakout Strength
Ncbg = (ANc ANc0
) y ec,N y ed,N y c,N y cp,N Nb ACI 318-08 Eq. (D-5) f Ncbg ³ Nua ACI 318-08 Eq. (D-1) ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b) ANc0 = 9 h2 ef ACI 318-08 Eq. (D-6) y ec,N = ( 1
1 + 2 e' N
3 hef ) £ 1.0 ACI 318-08 Eq. (D-9) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-08 Eq. (D-11) y cp,N = MAX(ca,min cac
, 1.5hef cac
) £ 1.0 ACI 318-08 Eq. (D-13)
Nb = 16 l √f'c h5/3 ef ACI 318-08 Eq. (D-8)
Variables hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
20.333 0.000 0.000 11.500 1.000 cac [in.] kc l f'c [psi]
0.000 16 1 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 1,764.00 3,721.00 1.000 1.000 0.813 1.000 132,748
Results
Ncbg [lb] f concrete f Ncbg [lb] Nua [lb] 51,170 0.700 35,819 10,562
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
4 Shear load Load Vua [lb] Capacity f f f f Vn [lb] Utilization bbbbV = Vua/f f f f Vn Status
Steel Strength* 250 17,725 2 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 1,000 130,272 1 OK
Concrete edge failure in direction x+** 1,000 17,382 6 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
Vsa = 0.6 Ase,V futa ACI 318-08 Eq. (D-20) f Vsteel ³ Vua ACI 318-08 Eq. (D-2)
Variables
Ase,V [in.2] futa [psi]
0.61 75,000
Calculations
Vsa [lb] 27,270
Results
Vsa [lb] f steel f Vsa [lb] Vua [lb] 27,270 0.650 17,725 250
4.2 Pryout Strength
Vcpg = kcp [(ANc ANc0
) y ec,N y ed,N y c,N y cp,N Nb] ACI 318-08 Eq. (D-31) f Vcpg ³ Vua ACI 318-08 Eq. (D-2) ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b) ANc0 = 9 h2 ef ACI 318-08 Eq. (D-6) y ec,N = ( 1
1 + 2 e' N
3 hef ) £ 1.0 ACI 318-08 Eq. (D-9) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-08 Eq. (D-11) y cp,N = MAX(ca,min cac
, 1.5hef cac
) £ 1.0 ACI 318-08 Eq. (D-13)
Nb = kc l √f'c h1.5 ef ACI 318-08 Eq. (D-7)
Variables kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] 2 7.667 0.000 0.000 11.500 y c,N cac [in.] kc l f'c [psi]
1.000 - 24 1 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 1,764.00 529.00 1.000 1.000 1.000 1.000 27,905
Results
Vcpg [lb] f concrete f Vcpg [lb] Vua [lb] 186,103 0.700 130,272 1,000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
4.3 Concrete edge failure in direction x+
Vcbg = (AVc AVc0
) y ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-08 Eq. (D-22) f Vcbg ³ Vua ACI 318-08 Eq. (D-2) AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b) AVc0 = 4.5 c2 a1 ACI 318-08 Eq. (D-23) y ec,V = ( 1
1 + 2e' v
3ca1 ) £ 1.0 ACI 318-08 Eq. (D-26) y ed,V = 0.7 + 0.3( ca2 1.5ca1
) £ 1.0 ACI 318-08 Eq. (D-28) y h,V = √1.5ca1 ha
³ 1.0 ACI 318-08 Eq. (D-29)
Vb = (7 ( le da )0.2
√da) l √f'c c1.5 a1 ACI 318-08 Eq. (D-24)
Variables ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]
11.500 11.500 0.000 1.000 48.000 le [in.] l da [in.] f'c [psi] y parallel,V
8.000 1.000 1.000 3,000 1.000
Calculations
AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [lb]
724.50 595.13 1.000 0.900 1.000 22,663
Results
Vcbg [lb] f concrete f Vcbg [lb] Vua [lb] 24,831 0.700 17,382 1,000
5 Combined tension and shear loads bN bV z Utilization bN,V [%] Status
0.295 0.058 5/3 14 OK
bNV = bz N + bz
V <= 1
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to your local standard.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
Fastening meets the design criteria!
J bolt OK by inspection
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
Coordinates Anchor in.
Anchor x y c-x c+x c-y c+y
1 -9.500 -9.500 11.500 30.500 11.500 30.500
2 9.500 -9.500 30.500 11.500 11.500 30.500 3 -9.500 9.500 11.500 30.500 30.500 11.500 4 9.500 9.500 30.500 11.500 30.500 11.500
7 Installation data Anchor plate, steel: -
Anchor type and diameter: Hex Head ASTM F 1554 GR. 55 1
Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x
4.000 in. x 0.250 in.
Maximum installation torque: -
Hole diameter in the fixture: df = 1.063 in. Hole diameter in the base material: - in.
Plate thickness (input): 0.500 in. Hole depth in the base material: 25.000 in.
Recommended plate thickness: not calculated
Minimum thickness of the base material: 26.172 in.
2.500 19.000 2.500
2.
.0
2.
x y
12.000 12.000
.0
.0
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
Specifier's comments:
1 Input data Anchor type and diameter: HIT-RE 500 V3 + HAS-E 1
Effective embedment depth: hef,act = 8.000 in. (hef,limit = - in.)
Material: 5.8
Evaluation Service Report: ESR-3814
Issued I Valid: 3/1/2021 | 1/1/2023
Proof: Design method ACI 318-08 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.500 in.
Anchor plate: lx x ly x t = 24.000 in. x 24.000 in. x 0.500 in.; (Recommended plate thickness: not calculated
Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x 4.000 in. x 0.250 in.
Base material: cracked concrete, 3000, fc' = 3,000 psi; h = 48.000 in., Temp. short/long: 32/32 °F
Installation: hammer drilled hole, Installation condition: Dry Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present edge reinforcement: none or < No. 4 bar Seismic loads (cat. C, D, E, or F) no
R - The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.] & Loading [lb, in.lb]
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
2 Load case/Resulting anchor forces Load case: Design loads
Anchor reactions [lb] Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 1 5,281 250 250 0
2 0 250 250 0 3 5,281 250 250 0 4 0 250 250 0 max. concrete compressive strain: 0.06 [‰] max. concrete compressive stress: 257 [psi] resulting tension force in (x/y)=(-9.500/0.000): 10,561 [lb] resulting compression force in (x/y)=(10.824/0.000): 10,861 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Tension Compression x y
3 Tension load Load Nua [lb] Capacity f f f f Nn [lb] Utilization bbbbN = Nua/f f f f Nn Status
Steel Strength* 5,281 28,541 19 OK
Bond Strength** 10,561 28,310 38 OK
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 10,561 23,461 46 OK
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
Nsa = ESR value refer to ICC-ES ESR-3814 f Nsa ³ Nua ACI 318-08 Eq. (D-1)
Variables
Ase,N [in.2] futa [psi]
0.61 72,500
Calculations
Nsa [lb] 43,910
Results
Nsa [lb] f steel f Nsa [lb] Nua [lb] 43,910 0.650 28,541 5,281
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
3.2 Bond Strength
Nag = (ANa ANa0
) y ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-11 Eq. (D-19) f Nag ³ Nua ACI 318-11 Table D.4.1.1 ANa = see ACI 318-11, Part D.5.5.1, Fig. RD.5.5.1(b) ANa0 = (2 cNa)2 ACI 318-11 Eq. (D-20) cNa = 10 da √t uncr 1100 ACI 318-11 Eq. (D-21) y ec,Na = ( 1
1 + e' N cNa ) £ 1.0 ACI 318-11 Eq. (D-23) y ed,Na = 0.7 + 0.3 (ca,min cNa
) £ 1.0 ACI 318-11 Eq. (D-25) y cp,Na = MAX(ca,min cac
, cNa cac
) £ 1.0 ACI 318-11 Eq. (D-27)
Nba = l a · t k,c · p · da · hef ACI 318-11 Eq. (D-22)
Variables t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] aoverhead t k,c [psi] 2,051 1.000 8.000 11.500 1.000 1,274 ec1,N [in.] ec2,N [in.] cac [in.] l a
0.000 0.000 11.290 1.000
Calculations cNa [in.] ANa [in.2] ANa0 [in.2] y ed,Na
13.595 1,053.97 739.25 0.954 y ec1,Na y ec2,Na y cp,Na Nba [lb]
1.000 1.000 1.000 32,029
Results
Nag [lb] f bond f Nag [lb] Nua [lb] 43,554 0.650 28,310 10,561
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
3.3 Concrete Breakout Strength
Ncbg = (ANc ANc0
) y ec,N y ed,N y c,N y cp,N Nb ACI 318-08 Eq. (D-5) f Ncbg ³ Nua ACI 318-08 Eq. (D-1) ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b) ANc0 = 9 h2 ef ACI 318-08 Eq. (D-6) y ec,N = ( 1
1 + 2 e' N
3 hef ) £ 1.0 ACI 318-08 Eq. (D-9) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-08 Eq. (D-11) y cp,N = MAX(ca,min cac
, 1.5hef cac
) £ 1.0 ACI 318-08 Eq. (D-13)
Nb = kc l √f'c h1.5 ef ACI 318-08 Eq. (D-7)
Variables hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
7.667 0.000 0.000 11.500 1.000 cac [in.] kc l f'c [psi]
11.290 17 1 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb]
966.00 529.00 1.000 1.000 1.000 1.000 19,766
Results
Ncbg [lb] f concrete f Ncbg [lb] Nua [lb] 36,094 0.650 23,461 10,561
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
4 Shear load Load Vua [lb] Capacity f f f f Vn [lb] Utilization bbbbV = Vua/f f f f Vn Status
Steel Strength* 250 15,807 2 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Concrete Breakout Strength controls)**
1,000 92,276 2 OK
Concrete edge failure in direction x+** 1,000 17,382 6 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
Vsa = ESR value refer to ICC-ES ESR-3814 f Vsteel ³ Vua ACI 318-08 Eq. (D-2)
Variables
Ase,V [in.2] futa [psi] aV,seis
0.61 72,500 1.000
Calculations
Vsa [lb] 26,345
Results
Vsa [lb] f steel f Vsa [lb] Vua [lb] 26,345 0.600 15,807 250
4.2 Pryout Strength (Concrete Breakout Strength controls)
Vcpg = kcp [(ANc ANc0
) y ec,N y ed,N y c,N y cp,N Nb] ACI 318-08 Eq. (D-31) f Vcpg ³ Vua ACI 318-08 Eq. (D-2) ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b) ANc0 = 9 h2 ef ACI 318-08 Eq. (D-6) y ec,N = ( 1
1 + 2 e' N
3 hef ) £ 1.0 ACI 318-08 Eq. (D-9) y ed,N = 0.7 + 0.3 ( ca,min 1.5hef
) £ 1.0 ACI 318-08 Eq. (D-11) y cp,N = MAX(ca,min cac
, 1.5hef cac
) £ 1.0 ACI 318-08 Eq. (D-13)
Nb = kc l √f'c h1.5 ef ACI 318-08 Eq. (D-7)
Variables kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] 2 7.667 0.000 0.000 11.500 y c,N cac [in.] kc l f'c [psi]
1.000 11.290 17 1 3,000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [lb] 1,764.00 529.00 1.000 1.000 1.000 1.000 19,766
Results
Vcpg [lb] f concrete f Vcpg [lb] Vua [lb] 131,823 0.700 92,276 1,000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
4.3 Concrete edge failure in direction x+
Vcbg = (AVc AVc0
) y ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-08 Eq. (D-22) f Vcbg ³ Vua ACI 318-08 Eq. (D-2) AVc see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b) AVc0 = 4.5 c2 a1 ACI 318-08 Eq. (D-23) y ec,V = ( 1
1 + 2e' v
3ca1 ) £ 1.0 ACI 318-08 Eq. (D-26) y ed,V = 0.7 + 0.3( ca2 1.5ca1
) £ 1.0 ACI 318-08 Eq. (D-28) y h,V = √1.5ca1 ha
³ 1.0 ACI 318-08 Eq. (D-29)
Vb = (7 ( le da )0.2
√da) l √f'c c1.5 a1 ACI 318-08 Eq. (D-24)
Variables ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]
11.500 11.500 0.000 1.000 48.000 le [in.] l da [in.] f'c [psi] y parallel,V
8.000 1.000 1.000 3,000 1.000
Calculations
AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [lb]
724.50 595.13 1.000 0.900 1.000 22,663
Results
Vcbg [lb] f concrete f Vcbg [lb] Vua [lb] 24,831 0.700 17,382 1,000
5 Combined tension and shear loads bN bV z Utilization bN,V [%] Status
0.450 0.058 5/3 28 OK
bNV = bz N + bz
V <= 1
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to your local standard.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the Evaluation Service Report for cleaning and installation instructions
• The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead applications.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
Fastening meets the design criteria!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Engineering Partners Matthew Fisk 455 E Lanikaula St. Hilo, Hawii 96720 808-930-7824 | matthew.fisk@epinc.pro
Page:
Project:
Coordinates Anchor in.
Anchor x y c-x c+x c-y c+y
1 -9.500 -9.500 11.500 30.500 11.500 30.500
2 9.500 -9.500 30.500 11.500 11.500 30.500 3 -9.500 9.500 11.500 30.500 30.500 11.500 4 9.500 9.500 30.500 11.500 30.500 11.500
7 Installation data Anchor plate, steel: -
Anchor type and diameter: HIT-RE 500 V3 + HAS-E 1
Profile: Square HSS (AISC), HSS4X4X.25; (L x W x T) = 4.000 in. x
4.000 in. x 0.250 in.
Maximum installation torque: 1,800.000 in.lb
Hole diameter in the fixture: df = 1.125 in. Hole diameter in the base material: 1.125 in.
Plate thickness (input): 0.500 in. Hole depth in the base material: 8.000 in.
Recommended plate thickness: not calculated
Minimum thickness of the base material: 10.250 in.
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
7.1 Recommended accessories
Drilling Cleaning Setting
• Suitable Rotary Hammer
• Properly sized drill bit
• Compressed air with required accessories to blow from the bottom of the hole
• Proper diameter wire brush
• Dispenser…