Questions & Answers

NWWP4000-19-0074JM0C

Department of Commerce (DOC) National Oceanic and Atmospheric Administration (NOAA)

National Weather Service (NWS)

Southern Weather Region

ATTACHMENT 5

July 2019

Q&A NWWP4000-19-00074JM0C – NWS SR AC UNITS

Contents

A. ACQUISITION QUESTIONS

B. TECHNICAL QUESTIONS

A. ACQUISITION QUESTIONS

1. Is this requirement currently being performed by a contractor or have been performed in the past?

a. No, this is a new requirement and is for the replacement and one year warranty only. No follow on is projected at this time.

2. Will there be a site visit?

a. There is no intent for site visits at this time.

B. TECHNICAL QUESTIONS

1. Are there as built drawing in relation to this requirement?

a. Yes, available upon request via email to contracting specialist.

2. Will smoke detectors be attached to the alarm system?

a. No

3. Will a permit be required for this project?

a. No

4. Can we receive as built mechanical drawings to see the existing Building Automation System to enable monitoring of the CRAC units?

a. Yes, available upon request via email to contracting specialist.

5. Need line set lengths due to required replacement of refrigerant lines?

a. Reference mechanical drawings

6. Number of new and existing penetrations to be sleeved for line sets?

a. Reference mechanical drawings

7. Current breakers & wire sizes for existing units w/ distance from unit to electrical distribution panels?

a. Reference electrical drawings

8. Existing Building Automated System type & model?

a. Connected to a Niagara System, building is controlled by Seimens.

9. Are the (2) existing systems currently in fair working condition. Location of outdoor condensing units roof/ground?

a. Yes, refer to drawings for location of condensing units.

10. Do the current units have a domestic water source for humidifiers? Are the new units required to have moisture detection below the raised floor?

a. Water supply yes and water detection yes

11. Can NOAA supply load calculations?

a. Load calculations provided as Attachment - 6