STATEMENT OF WORK FOR MHX HVAC

The Contractor shall provide a full coverage Preventive Maintenance for the entire HVAC Mechanical System, Equipment and Control System installed at the National Weather Station Office, 533 Roberts Road, Newport, NC, 28570 and co-located NEXRAD RADAR site. This is a 24/7-day a week operation. The period of performance shall be one base year with four one-year options.

I. All HVAC mechanical equipment will be included in this service. All HVAC computer hardware, firmware, and software reloads will be included in this service.

II. Contractor is to provide job labor, travel labor, living expenses, and equipment and material required to do Preventive Maintenance (PM) and Emergency Maintenance on all systems, fans, air handlers, package units, stats, and thermostats, etc. The Electronic/Computer Control system will also be part of the service.

III. This Service will be provided on a quarterly basis four (4) times a year. The Contractor is responsible to visit the site, and assure that all equipment is in factory spec operation prior to the issuance of this contract.

A written statement will be required on any deficiency and will be handled, if necessary, as a separate repair order.

IV. Under this contract all work will be done quarterly and checklists (enclosed) turned in for continued payment of contract. All work outlined in this contract must meet or exceed manufacturers tolerances and will be inspected by local official. The Contractor will perform all PM Service as detailed in the attached specifications and service sheets.

V. As part of this PM all materials such as filters, pressure control switches, all gases, and belts must be new, factory approved and provided by the contractor.

VI. Contractor will maintain all equipment to manufacturer’s specifications after the initial inspection.

1. Any major repairs (Compressors, motors, etc…) or software reloads and reconfigurations due to system failure are covered under this contract with the following exceptions:

a) This agreement applies only to the maintainable portions of the system(s). Repair or replacement of non-maintainable parts such as duct work, boiler shell and tubes, cabinets, boiler refractory material, heat exchangers, main power service and electrical wiring, piping, tube bundles, valve bodies, structural supports tanks and other similar items are excluded.

b) This agreement does not include responsibility for the design of the system, obsolescence, safety test, removal and reinstallation of valve bodies and dampers, repair or replacement necessitated by freezing weather, electrical power failure, low voltage, burned-out main or branch fuses, low water pressure, vandalism, misuse or abuse of the system(s), negligence of others (including customer), failure of customer to properly operate the system(s), requirements of governmental regulatory or insurance agencies, or other causes beyond control of the Contractor.

Contractor will make emergency service call (call backs) as required, and respond within 6 hours of notification to be on site for troubleshooting. Any repair that is not covered under this contract will be handled on a per event basis, and presentation of a written estimate.

VII. Contractor will be required to follow all local rules and safety compliance, along with National Weather Service 50-1115 Safety Manual (AVAILABLE ON SITE & WEB) while performing this work. The contractor also will be required to dispose of any Hazardous wasted caused or created by this work and contract agreement (i.e. gases, fluids, etc.).

VIII. A local POC (point of contact) will be assigned so contractor can have all work reviewed as per schedule.

Copies of the enclosed checklist will be made by the local office for contractor. The contract option years will not automatically be exercised. Performance and satisfaction of the POC and Local Station Manager (MIC) will be the elements used to judge contractor’s work.

IX. Contractor shall include one (1) annual comprehensive maintenance action, and three (3) operational maintenance actions for the Forecast Office (three Air Handler Units, two Bard wall mounts units) and the NEXRAD RADAR Site (three external mount systems on two buildings) that will include coil cleaning, Page - 2 filters replacement, belt changes, motor megger, lubrication, gas pressure checks and/or replacement, and all visual inspections. Also, all filters will be changed at least four (4) times a year. Contractor shall also provide one (1) annual comprehensive inspection of the Control System, and three (3) operational inspections. All items are covered in the specs and checklist attachments. These visits shall include control loop tuning, temperature calibrations, voltage verifications and software archival.

NOTE: NO EXTRA charge will be levied for temperature adjustments, if needed, during visits for work or at request of local official.

EQUIPMENT TO BE COVERED UNDER CONTRACT (TO INCLUDE CONTROL SYSTEMS)

QTY SYSTEM

COMPONENTS

MANUFAC MODEL RATING LOCATION

WALL MOUNTS

AUTO CHANGER

CONDENSER

CONDENSER

*AIR HANDLERS

*AIR HANDLER

TCP-1 CONTROL

PANEL, WITH

TRANE BAS

SUITE, Version:

1.1.75

**EXTERNAL

UNITS

**EXTERNAL

UNIT

IN LINE

CENTRIFUGAL

BARD or Mini Split

UNIT & HEAT

PUMP &

CONDENSER

BARD

BARD

TRANE

TRANE

TRANE

TRANE

TRANE

BARD

BARD

Blower Motor

FUTURE

Installation

TRANE

WA721-B

MC-4001-BC

TTA180B400BA

TTA090A400BA

MCCA010…

MCCA006…

N/A

WA721-B

W36A2-

B09WXXJ

Direct Drive

N/A

TAM7B0C60H5

1SCB &

4TWR7060A100

0AA

6 TON

N/A

15 TON

5 TON

5HP

2HP

N/A

6 TON

3 TON

½ HP

N/A

COMPUTER

ROOM (Outside)

COMPUTER

ROOM

OUTSIDE

OUTSIDE

INSIDE

INSIDE

AHU ROOM

OUTSIDE

OUTSIDE

ELECTRICAL

ROOM

OUTSIDE

STORAGE

BLDG.

ANNEX

* Systems are controlled by Trane BAS Operator Suite, Version 1.1.75 Systems software on windows compatible computers and communicating with Trane Controllers.

** Systems located at NEXRAD RADAR Site.

Page - 3

INSPECTION CHECKLIST

LOCATION ID: ________________ EQUIP DESCRIPTION (AHU1, BARD’s, ETC…): _________________

FILTER CHANGE IS INCLUDED IN THIS VISIT __________

INSPECTION TYPE: ________COMPREHENSIVE _______OPERATIONAL

INDICATE THE FANS INCLUDED WITH THIS AIR HANDLER

_____ SUPPLY _____ RETURN _____EXHAUST

CHECK

IF TASK

DONE TYPE TASK DESCRIPTION

VISUAL INSPECTION AND CLEANING

_____ I Unusual noises, vibration, odor, etc.

_____ I Structural elements for corrosion and damage _____ I Cleanliness, integrity of cabinet insulation (acoustic & thermal) _____ I Mounting points for secureness, tighten if necessary _____ I Secureness of guards, doors and panels _____ I System leaks in piping, flange connections, etc.

_____ I Air filter condition – verify no bypass _____ IR Air filters, (See note above) _____ C Remove debris from louvers and dampers _____ I Flexible connections and ductwork for damage and leaks

UNIT CONTROL PANEL

_____ C Cabinet for cleanliness, moisture, oil, etc.

_____ IR Wires for security and damage _____ IR Connections for tightness and corrosion _____ V Indication and alarm devices _____ I Check for obvious errors on installed pressure and temperature gauges _____ V Start, stop and anti-recycle timers _____ V Dampers-supply, return and exhaust _____ L Dampers linkage-supply, return and exhaust _____ V Economizer cycle-assure min. damper position and flow

SUPPLY FAN STARTER

_____ I Enclosure and components for cleanliness, moisture, oil, etc.

_____ IR Connections for tightness and corrosion _____ IR Wires for security and damage _____ M Voltage L1 & L2 _____ L3 & L3_____ L1 & L3_____ _____ M Megger all motors greater than 5 HP. record on Page 5 _____ M Amperage for loads greater that ½ HP. record on Page 5

SUPPLY FAN AND MOTOR

_____ L Motor, fan and shaft bearings, grease as required.

_____ IR Belt tension and condition _____ I Pulleys for wear and alignment _____ I Secureness of blades (propeller type fan) _____ I Freedom of rotation, cracks and alignment _____ I Fan blades or wheel for cleanliness _____ I Vibration and/or noise _____ I Fan and motor mountings for security _____ C Motors and motor cooling openings _____ I Cooling coil condition _____ I Condensate drains and drain pan

Page - 4

RETURN FAN STARTER

_____ I Enclosure and components for cleanliness, moisture, oil, etc.

_____ IR Connections for tightness and corrosion _____ IR Wires for security and damage _____ I Contacts for signs of wear, arcing, overheating, etc.

_____ M Voltage L1 & L2 _____ L3 & L3 _____ L1 & L3 _____ _____ M Megger all motors greater than 5HP, record on Page 5 _____ M Load amperage for loads greater than ½ HP. record on Page 5

RETURN FAN AND MOTOR

_____ L Motor, fan and shaft bearings _____ IR Belt tension and condition _____ I Pulleys for wear and alignment _____ I Secureness of blades (propeller type fan) _____ I Freedom of rotation, cracks and alignment _____ I Fan blades or wheel for cleanliness _____ I Vibration and/or noise _____ I Fan and motor mountings for security _____ C Motor cooling openings

EXHAUST FAN STARTER

_____ I Enclosure and components for cleanliness, moisture, oil, etc.

_____ IR Connections for tightness and corrosion _____ IR Wires for security and damage _____ I Contacts for signs of wear, arcing, overheating, etc.

_____ M Voltage L1 & L2 _____ L3 & L3 _____ L1 & L3 _____ _____ M Megger all motors greater than 5 HP. Record on Page 5 _____ M Load amperage for loads greater that ½ HP. Record on Page 5

EXHAUST FAN AND MOTOR (All AHU’s & Electrical Room)

_____ L Motor, fan and shaft bearings, grease as required.

_____ IR Belt tension and condition _____ I Pulleys for wear and alignment _____ I Secureness of blades (propeller type fan) _____ I Freedom of rotation, cracks and alignment _____ I Fan blades or wheel for cleanliness _____ I Vibration and/or noise _____ I Fan and motor mountings for security _____ C Motor cooling openings

ELECTRIC HEAT

_____ M Amp draw on all stages.

_____ V Air flow switch, high temp, limit and switch _____ I Contacts for signs of wear, arcing, overheating, etc.

_____ I Inspect heating terminals – inspect isolators & fuses _____ V Operating controls. Heats when commanded, and shuts down when commanded.

CONTROL SYSTEM

_____ C Ensure needed computers for normal operation are up and functioning.

_____ IR Wires for security and damage _____ IR Connections for tightness and corrosion _____ V Indication and alarm devices _____ I Check for obvious errors on installed pressure and temperature gauges _____ V Start, stop and anti-recycle timers _____ V Ensure control software for system functions as designed.

_____ V Ensure all devices controlled by software/hardware are functional and can be controlled.

_____ V Ensure Dampers linkage-supply, return and exhaust can be commanded by software.

Page - 5

_____ V Economizer cycle-assure min. damper position and flow

DX COOLING

_____ I Coil surfaces _____ I Drain pans _____ I Control valves/stage controls _____ L Motor, fan and shaft bearings _____ IR Belt tension and condition _____ I Pulleys for wear and alignment _____ I Secureness of blades (propeller type fan) _____ I Freedom of rotation, cracks and alignment _____ I Fan blades or wheel for cleanliness _____ I Vibration and/or noise _____ I Fan and motor mountings for security _____ C Motor cooling openings

MOTOR LOG SHEET

MOTOR SIZE AMP READINGS MEGGER READINGS

NAME HP L1 L2 L3 NP* L1 L2 L3

SUPPLY FAN _____ _____ _____ _____ _____ _____ _____ _____

RETURN FAN _____ _____ _____ _____ _____ _____ _____ _____

EXHAUST FAN _____ _____ _____ _____ _____ _____ _____ ____

IN LINE CENT. _____ _____ _____ _____ _____ _____ _____ _____

*NP—NAME PLATE AMPS

_____ M LOG SHEET, IF required for troubleshooting

_____ Outside air _____ Supply air temp _____ Return air temp _____ Mixed air temp

TASK CODES: C - Clean, I – Inspect, IR – Inspect Regularly, L – Lube, M- Measure, V- Verify

COMMENTS/NOTES/REQUIREING ANY MORE ACTIONS: NOTE BELOW

Page - 6

COMPREHENSIVE AND OPERATIONAL MAINTENANCE

Bard Wall Mount Units / Air Handling Units /Annex

Comprehensive Maintenance

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls: Inspect control center, clean and tighten connections. Test low-pressure output and high-pressure safety systems. Verify/document operation of all associated safeties and indicators and record conditions.

Starter/Contactor(s) (Condenser): Inspect/tighten/replace as necessary all wiring, terminals and contacts to insure proper operation and record conditions. Measure operating voltages and record.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises. Clean motor and cooling openings. Lube motor and fan shaft bearings.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls (Compressor): Verify operation of oil temp, low ambient start-up and start-stop anti recycle control systems. Verify operation of all associated safety and indication devices (moisture, high pressure, etc.). Confirm control reaction.

Starter/Contactor (Compressor): Inspect/tighten/replace as necessary all wiring, terminals and contacts to insure proper operation and record conditions. Measure operating voltages and record.

Compressor(s): Inspect for working order.

System Level (Condenser): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

Condenser Section (Air Cooled): Inspect motor mountings, check for vibration and or unusual noises. Clean motor and cooling openings.

System Controls (Condenser): Verify operation of all associated safety and indication devices (moisture, high pressure, etc.). Confirm control reaction calibration.

Starter/Contactor(s) (Condenser): Inspect/tighten/replace as necessary all wiring, terminals and contacts to insure proper operation and record conditions. Measure operating voltages and record.

Clean Condenser Coils: Remove all debris, brush and wash coils.

Replace filters as designated.

Operational Maintenance

System Level: Inspect structural elements for corrosion, buildup, damage and leaks and record conditions.

System Controls: Inspect control center, clean and tighten connections. Verify/document operation of all associated safeties and indicators and record conditions.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks and record conditions.

System Controls (Compressor): Verify operation of all associated safety and indication devices (moisture, high pressure, etc.) and record conditions.

Compressor(s): Verify operation.

Page - 7

System Level (Condenser): Inspect structural elements for corrosion, buildup, damage and leaks and record conditions..

Condenser Section (Air Cooled): Inspect motor mountings, check for vibration and or unusual noises. Inspect condition on drive and fan belts, change as needed and record conditions.

Office Trane Units 1, 2, 3 Comprehensive Maintenance

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls: Inspect control center, clean and tighten connections. Test low-pressure cutout and high-pressure safety systems. Verify/document operation of all associated safeties and indicators and record conditions..

Starter/Contactor(s) (Condenser): Inspect/tighten/replace as necessary all wiring, terminals and contacts to ensure proper operation and record conditions. Measure operating voltages and record.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises. Clean motor and cooling openings. Lube motor and fan shaft bearings. Inspect belt tension and condition (replace as required) and record conditions..

Heat Pump (on applicable units): Check operation of reversing valve. Verify heating/cooling switch over controls and record conditions.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls (Compressor): Verify operation of all associated safety and indication devices (moisture, high pressure, etc.). Confirm control reaction.

Starter/Contactor (Compressor): Inspect/tighten/replace as necessary all wiring, terminals and contacts to ensure proper operation and record conditions. Measure operating voltages and record.

Compressor(s): Inspect and lubricate coupling (open compressors). Change oil and filter elements as required. Verify setting of oil cooler regulator. Measure and record all operating parameters, complete compressor log sheet and record conditions.

Electric heat: Inspect coil/isolators for damage. Brush coil, remove dust and debris and torque heating elements. Verify staging and operating control operation and record conditions.

Coil Cleaning: Remove debris, wash coil.

Replace filters as designated.

Operational Maintenance

System Level: Inspect structural elements for corrosion, buildup, damage and leaks and record conditions.

System Controls: Inspect control center, clean and tighten connections. Verify/document operation of all associated safeties and indicators and record conditions.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises. Inspect belt tension and condition (replace as required) and record conditions.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks and record conditions.

System Controls (Compressor): Verify operation of all associated safety and indication devices (moisture, high pressure, etc.) and record conditions.

Compressor(s): Verify operation.

Electric heat: Verify staging and operating control operation and record conditions.

Page - 8

NEXRAD RADAR Bard Units 1 & 2 and TPMS Shelter Bard UNIT

Comprehensive Maintenance

System Level (Compressor): Inspect structural elements for corrosion buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls: Inspect control center, clean and tighten connections. Test low-pressure cutout and high-pressure safety systems. Verify/document operation of all associated safeties and indicators and record conditions..

Starter/Contactor(s) (Condenser): Inspect/tighten/replace as necessary all wiring, terminals and contacts to ensure proper operation and record conditions. Measure operating voltages and record.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises. Clean motor and cooling openings.

Heat Pump (on applicable units): Check operation of reversing valve. Verify heating/cooling switch over controls and record conditions.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks. Check/tighten all mounting points and record conditions.

System Controls (Compressor): Verify operation of oil temp, low ambient start-up and start-stop anti-recycle control systems. Verify operation of all associated safety and indication devices (moisture, high pressure, etc.). Confirm control reaction.

Starter/Contactor (Compressor): Inspect/tighten/replace as necessary all wiring, terminals and contacts to ensure proper operation and record conditions. Measure operating voltages and record.

Compressor(s): Inspect and lubricate coupling (open compressors). Change oil and filter element as required. Verify setting of oil cooler regulator. Measure and record all operating parameters, complete compressor log sheet and record conditions.

Electric heat: Inspect coil/isolators for damage. Brush coil remove dust and debris and torque heating elements. Verify staging and operating control operation and record conditions.

Coil Cleaning: Remove debris, wash coil.

Replace filters as designated.

Operational Maintenance

System Level: Inspect structural elements for corrosion, buildup, damage and leaks and record conditions..

System Controls: Inspect control center; clean and tighten connections. Verify/document operation of all safeties and indicators and record conditions.

Fan(s) and Motor(s): Inspect motor mountings, check for vibration and or unusual noises. Inspect Fan Assembly and record conditions.

System Level (Compressor): Inspect structural elements for corrosion, buildup, damage and leaks and record conditions.

System Controls (Compressor): Verify operation of all associated safety and indication devices (moisture, high pressure, etc.) and record conditions.

Compressor(s): Measure and record all operating parameters, complete compressor log sheet and record conditions..

Electric heat: Verify staging and operating control operation and record conditions..

All Control Systems

Page - 9

Comprehensive Maintenance

System Level: Inspect structural elements for corrosion, buildup, damage and leaks and record conditions..

System Controls: Inspect control center, clean and tighten connections. Ensure all computers and data processing equipment/hardware is powered up and functional.

System Software: Ensure system software works according to specification without crashing or causing excessive delays. Notify office point of contact if a virus is detected. Ensure system is following automated instructions and schedules

Peripheral Equipment: Check and if needed calibrate all sensors (e.g. temp, pressure, switches, synchor/servos and valves) that interact with and/or can be viewed by the software.

Operational Maintenance

System Software: Ensure system software works according to specification without crashing or causing excessive delays. Notify office point of contact if a virus is detected.

Peripheral Equipment: Check and if needed calibrate all sensors (e.g. temp, pressure, switches, synchor/servos and valves) that interact with and/or can be viewed by the software.