NVCC-AN M25NV120 Project Drawings 2026-09-15.pdf
PDF 2 MB Posted
- Attached to
- Replace AHUs at CE Building at Northern Virginia Community College, Annandale Campus, PC#M25NV120
- Solicitation number
- DBB-129572
- Issued by
- Fairfax County, Virginia
About this file
These project drawings document the NVCC-AN M25NV120 Replace Air Handling Units project for Northern Virginia Community College's Annandale Campus located at 8333 Little River Turnpike, Annandale, Virginia 22003. The project involves the replacement of three air handling units (AHU-1, AHU-2, and AHU-3) and three return air fans (RAF-1, RAF-2, RAF-3) serving a mixed-use theater and multi-purpose building with a gross area of 55,294 square feet. The work is classified as in-kind equipment replacement for the Building CE facility. The project is divided into two phases: Phase 1, which includes AHU-1, AHU-2, RAF-1, and RAF-2, must be completed within sixty consecutive calendar days from commencement and is prioritized to restore theater operations; Phase 2, encompassing AHU-3 and RAF-3, must commence only after Phase 1 substantial completion and be completed within thirty consecutive calendar days. The entire project must achieve substantial completion within ninety consecutive calendar days of the Notice to Proceed, with final completion within thirty days thereafter. The owner's target construction window is August 2027 through November 2027. The drawings are dated September 15, 2026, and prepared by Virginia A&E, PLLC.
The project scope includes demolition plans, mechanical specifications, new equipment installation plans, equipment schedules detailing three Innovent brand air handling units with capacities ranging from 9,200 to 22,000 CFM, return air fans including Greenheck brand models, a heating water pump, Variable Frequency Drives (VFDs) with ratings from 5 HP to 30 HP, updated branch circuits, and complete controls system replacement to be coordinated through the owner's control vendor, Schneider Electric. All work must comply with the 2021 Virginia Uniform Statewide Building Code, Virginia Mechanical Code, National Electrical Code, and ADA accessibility standards. The contractor is responsible for providing material data submittals, assembling operation and maintenance manuals, maintaining as-built drawings, site safety and security, pre-demolition documentation, dust control, and coordination with the building's commissioning agent for functional testing. The project requires contractor site visits prior to bidding to verify existing conditions and clearances for equipment delivery and assembly.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| NVCC-AN M25NV120 Project Manual 2026-09-15.pdf | ||
| NVCC-AN M25NV120 Notice of Invitation for Bids.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST:
SITE LOCATION
SITE
NORTH NORTH
PROJECT LOCATION MAPVICINITY MAP
ASBESTOS DISCLOSURE STATEMENT:
LEAD PAINT DISCLOSURE STATEMENT:
DRAWING NO TITLE
T1 TITLE SHEET
D1 DEMOLITION PLAN - AHU-1
D2 DEMOLITION PLAN - AHU-2
D3 DEMOLITION PLAN - AHU-3
ME1 MECHANICAL LEGEND, SPECIFICATIONS, AND DETAILS
ME2 ELECTRICAL LEGEND, ABBREVIATIONS, GENERAL NOTES, AND SPECIFICATIONS
ME3 NEW WORK PLAN - AHU-1
ME4 NEW WORK PLAN - AHU-2
ME5 NEW WORK PLAN - AHU-3
ME6 EQUIPMENT SCHEDULES
ME7 CONTROLS - AHU-1 AND AHU-2
ME8 CONTROLS - AHU-3
AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORIGINALLY CONSTRUCTED AFTER JANURARY 1, 1985. IF SUSPECT MATERIALS ARE ENCOUNTERED OR WILL BE DISTURBED, WORK SHALL STOP AND THE MATERIALS SHALL BE EVALUATED BEFORE PROCEEDING.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURE TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS
SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
FOR BIDDING / CONSTRUCTION
SEPTEMBER 15, 2026
Drawing No.:
Project No.:
1"
Full Scale Verification
0"
T1
26007
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VA 24551
PHONE: (434) 316-6001
VAE PROJECT NO: 26007
DISCLAIMER STATEMENT:
VIRGINIA A&E ASSUMES NO RESPONSIBILITY FOR THE ADEQUACY OR ACCURACY OF THE ASBESTOS AND LEAD BASED PAINT INFORMATION PROVIDED ABOVE BY THE OWNER. THE CONTRACTOR SHALL ADDRESS ANY RELATED QUESTIONS TO THE OWNER'S PROJECT MANAGER.
I 495
RT 50
LITTLE RIVER
TURNPIKE
RT 620
LITTLE RIVER
TURNPIKE
WEST DR
EAST DR
CENTER DR
GENERAL INFORMATION:
PROJECT INFORMATION:
AGENCY: NORTHERN VIRGINIA COMMUNITY COLLEGE
PROJECT TITLE: NVCC - ANNANDALE CAMPUS CE REPLACE AHUs
PROJECT CODE: M25NV120
INSTITUTION: ANNANDALE CAMPUS
ADDRESS: 8333 LITTLE RIVER TURNPIKE, ANNANDALE, VIRGINIA 22003
BUILDING INFORMATION:
BUILDING NAME/NUMBER: BUILDING CE
WORK PERMITTED: IN-KIND EQUIPMENT REPLACEMENT
PURPOSE/OCCUPANCY: MIXED USE
USE GROUP CLASSIFICATION: THEATER, MULTI-PURPOSE, OTHER
TYPE OF CONSTRUCTION: IB & IIB
OCCUPANT LOAD OF BUILDING: EXISTING - UNCHANGED
OCCUPANCY LOAD OF RENOVATED AREA: EXISTING - UNCHANGED
BUILDING HEIGHT (FEET): 40'-0"± ABOVE GRADE
NUMBER OF STORIES: 2
GROSS AREA (GSF): 55,294 GROSS SQUARE FEET
BUILDING VOLUME: 1,220,801 CUBIC FEET
CODE MODIFICATIONS ISSUED: N/A
APPLICABLE CODES & STANDARDS:
BUILDING CODES: 2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE - VUSBC
(EFFECTIVE JANUARY 18, 2024)
VIRGINIA CONSTRUCTION CODE - VCC (2021)
VIRGINIA MECHANICAL CODE - VMC (2021)
VIRGINIA EXISTING BUILDING CODE - VEBC (2021)
VIRGINIA ENERGY CONSERVATION CODE - VECC (2021)
NATIONAL ELECTRICAL CODE - NFPA-70 (2020)
NATIONAL FIRE ALARM CODE - NFPA-72 (2019)
ACCESSIBILITY STANDARDS: ADA90-TITLE II: CHAPTER 2 OF 2010 ADA STANDARD FOR ACCESSIBLE DESIGN DATED
SEPTEMBER 15, 2010 AND CHAPTERS 1 AND 3 THROUGH 11 OF STANDARDS FOR
ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ICC A117.1-2017) APPROVED
MARCH 28, 2017.
OTHER STANDARDS: CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL - CPSM 2026 EDITION, REVISION 0
(JULY 31, 2026)
VIRGINIA COMMUNITY COLLEGE SYSTEM CONSTRUCTION AND PROFESSIONAL SERVICES
MANUAL - MARCH 5, 2026
NORTHERN VIRGINIA COMMUNITY COLLEGE DESIGN GUIDELINES - Q1 2023 EDITION
GENERAL NOTES:
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED FOR USE AS
FABRICATION DRAWINGS. THESE DRAWINGS INDICATE THE GENERAL AND APPROXIMATE
SIZE AND LOCATION OF MATERIAL. FIELD VERIFY ALL DIMENSIONS AND LOCATIONS
PRIOR TO BEGINNING WORK. ALL UTILITIES NOTED ON PLANS ARE APPROXIMATE AND
CONTRACTOR SHALL FIELD VERIFY LOCATION.
2. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES AND
REGULATIONS, INCLUDING, BUT NOT LIMITED TO, THE 2021 VIRGINIA UNIFORM
STATEWIDE BUILDING CODE (JANUARY 18, 2024) AND ASSOCIATED CODES OF
REFERENCE. REFER TO APPLICABLE CODES LIST THIS DRAWING.
3. ALL MATERIAL SHALL BE NEW UNLESS OTHERWISE NOTED. NO ASBESTOS CONTAINING
MATERIALS SHALL BE USED. MATERIALS ARE BASED ON THE INDICATED
MANUFACTURER'S/MODELS AND ARE INTENDED ONLY TO SHOW THE GENERAL SIZE,
CONFIGURATION, LOCATION, CONNECTIONS, AND SUPPORT FOR INDICATED MATERIAL
WITH RELATION TO OTHER BUILDING SYSTEMS. MATERIAL BY ANY MANUFACTURER THAT
MEETS THE SCHEDULED CRITERIA IS ACCEPTABLE. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING ACTUAL INSTALLED MATERIAL AND ASSOCIATED
CHANGES.
4. CONTRACTOR SHALL COORDINATE THE WORK WITH EXISTING CONDITIONS, INCLUDING
BEAMS, COLUMNS, SITE FEATURES, AND OTHER OBSTRUCTIONS, WHETHER OR NOT
SUCH IS SHOWN ON DRAWINGS.
5. CONTRACTOR SHALL COORDINATE THE WORK BETWEEN ALL TRADES. MATERIAL
LOCATIONS SHALL BE COORDINATED BETWEEN MECHANICAL, ELECTRICAL, AND
DEMOLITION PLANS TO AVOID CONFLICTS.
6. EXISTING MATERIAL TO BE REMOVED SHALL BE REMOVED CAREFULLY TO AVOID
DAMAGING MATERIAL TO REMAIN. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
DAMAGE THAT OCCURS TO EXISTING MATERIAL TO REMAIN OR TO BE RELOCATED
DURING DEMOLITION AND CONSTRUCTION.
7. CONTRACTOR SHALL ADVISE THE A/E IMMEDIATELY OF DISCREPANCIES FOUND ON THE
DRAWINGS, IN THE SPECIFICATIONS, OR BETWEEN THE TWO. WHERE CONFLICTS ARE
ENCOUNTERED, THE AFFECTED WORK SHALL NOT BE INSTALLED UNTIL THE CONFLICT
HAS BEEN RESOLVED. NEITHER THE A/E NOR THE OWNER SHALL BE RESPONSIBLE FOR
CONSEQUENCES OF PROCEEDING WITH WORK BASED ON CONTRACTOR
INTERPRETATION OR ON DIRECTION FROM OTHER PARTIES, INCLUDING THE OWNER
AND INSPECTORS.
8. ALL MATERIAL SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS, MAINTAINING ALL REQUIRED CLEARANCES AND WITH ALL
COMPONENTS ACCESSIBLE AND SERVICEABLE.
9. CONTRACTOR SHALL PROVIDE MATERIAL DATA SUBMITTALS FOR ALL NEW MATERIAL.
REFER TO INDIVIDUAL DRAWINGS FOR ADDITIONAL SUBMITTAL REQUIREMENTS. THE
CONTRACTOR SHALL PROVIDE A SUBMITTAL SCHEDULE WITHIN 30 DAYS OF AWARD OF
CONTRACT.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR ASSEMBLING OPERATION AND
MAINTENANCE MANUALS CONTAINING ALL MATERIAL SUBMITTALS, INSTALLATION AND
OPERATING INSTRUCTIONS, AND WARRANTY INFORMATION. ONE (1) ELECTRONIC PDF
COPY OF O&M MANUALS SHALL BE SUBMITTED TO THE A/E FOR REVIEW AT THE TIME OF
SUBSTANTIAL COMPLETION. PROVIDE THREE (3) HARD COPIES AND ONE (1) ELECTRONIC
PDF COPY OF THE FINAL O&M MANUALS TO THE OWNER.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A SET OF AS-BUILT DRAWINGS
ON SITE WHICH INDICATE IN RED ALL DEVIATIONS FROM ORIGINAL CONSTRUCTION
DOCUMENTS, INCLUDING APPROVED CONSTRUCTION CHANGE ORDERS. AS-BUILT
DRAWINGS SHALL BE SUBMITTED TO THE A/E AT THE TIME OF SUBSTANTIAL
COMPLETION. AS-BUILT DRAWINGS SHALL BE CLEARLY LEGIBLE AND COMPLETE.
12. CONTRACTOR SHALL KEEP PUBLIC AREAS FREE OF TRASH AND CONSTRUCTION DEBRIS
AND CLEAN ENTIRE WORK AREA ON A DAILY BASIS.
13. TEMPORARY POWER AND WATER SERVICE ARE AVAILABLE ON SITE FOR THE
CONTRACTOR'S USE. CONTRACTOR SHALL COORDINATE ACCESS WITH OWNER AND
SHALL PROVIDE ANY REQUIRED TEMPORARY CONNECTIONS AND EXTENSIONS.
14. CONTRACTOR'S PERSONNEL MAY USE THE TOILET FACILITIES IN THE BUILDING FOR THE
DURATION OF THE PROJECT. CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING
TOILET FACILITIES CLEAN.
15. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE SCOPE OF WORK
AND TO VERIFY EXISTING CONDITIONS PRIOR TO BIDDING THIS PROJECT. ANY
DISCREPANCIES OR AMBIGUOUS ITEMS MUST BE REPORTED TO THE A/E AND THE
OWNER FOR CLARIFICATION PRIOR TO BIDDING.
16. CONTRACTOR IS TYPICALLY PERMITTED TO WORK BETWEEN 7:00 AM AND 5:00 PM
MONDAY THRU FRIDAY. WORK OUTSIDE THESE HOURS SHALL BE COORDINATED WITH
OWNER'S PROJECT MANAGER DURING CONSTRUCTION. CONTRACTOR SHALL
COORDINATE CONSTRUCTION ACTIVITIES WITH OWNER AND BUILDING TENANTS FOR
SPECIAL EVENTS.
17. CONTRACTOR SHALL PROVIDE A DUST-PROOF BARRIER BETWEEN THE CONSTRUCTION
ZONE AND OCCUPIED PORTIONS OF THE BUILDING. CONTRACTOR SHALL FILTER
EXISTING HVAC GRILLES IN WORK AREA TO MITIGATE SPREAD OF DUST INTO OCCUPIED
AREAS OF THE BUILDING.
18. CONTRACTOR SHALL PROTECT THE BUILDING, ADJACENT FEATURES, ROADWAYS,
WALKWAYS, SITE IMPROVEMENTS, EXTERIOR PLANTINGS, LANDSCAPING, ETC AS
REQUIRED FROM DAMAGE AND CORRECT DAMAGE RESULTING FROM CONSTRUCTION
ACTIVITIES TO THE SATISFACTION OF THE OWNER.
19. CONTRACTOR SHALL COLLECT DEMOLISHED MATERIALS AND PLACE IN APPROPRIATE
DISPOSAL CONTAINERS. DEMOLISHED MATERIALS SHALL BE PROMPTLY REMOVED FROM
THE OWNER'S PROPERTY AND DISPOSED OF LEGALLY.
20. CONTRACTOR SHALL COORDINATE MATERIAL STORAGE AND DUMPSTER LOCATION WITH
OWNER DURING CONSTRUCTION.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR SITE SAFETY AND SECURITY FOR THE
DURATION OF THE PROJECT.
22. CONTRACTOR SHALL PROVIDE PRE-DEMOLITION PHOTOGRAPHIC OR VIDEOGRAPHIC
DOCUMENTATION TO SHOW EXISTING CONDITIONS OF FINISHED SURFACES IN WORK
AREA AND ADJOINING CONSTRUCTION INCLUDING SITE STORAGE AND ACCESS AREAS
PRIOR TO PRE-CONSTRUCTION MEETING AND A MINIMUM OF 10 WORKING DAYS PRIOR
TO COMMENCEMENT OF WORK.
23. CONTRACTOR SHALL NOTIFY OWNER OF ANY INTERRUPTION OF UTILITIES INCLUDING
BUT NOT LIMITED TO POWER, WATER, COMMUNICATIONS, ETC AND COORDINATE
OUTAGE WITH OWNER AND ALL BUILDING TENANTS.
24. ANY ROAD/PARKING LOT CLOSURE SHALL BE DONE IN ACCORDANCE WITH THE LATEST
VERSION OF THE VIRGINIA WORK AREA PROTECTION MANUAL.
25. DEFINITIONS:
FURNISH: SUPPLY AND DELIVER TO PROJECT SITE FOR INSTALLATION BY OTHERS.
INSTALL: INSTALL ITEMS FURNISHED BY OTHERS, INCLUDING UNLOADING, TEMPORARILY
STORING, UNPACKING, AND ASSEMBLY.
PROVIDE: FURNISH AND INSTALL, COMPLETE AND READY FOR THE INTENDED USE.
REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF
THEM OFF-SITE UNLESS INDICATED TO BE REMOVED AND SALVAGED OR REMOVED AND
REINSTALLED.
REMOVE AND REINSTALL: DETACH ITEMS FROM EXISTING CONSTRUCTION, PREPARE
FOR REUSE, AND REINSTALL WHERE INDICATED.
REMOVE AND SALVAGE: CAREFULLY DETACH FROM EXISTING CONSTRUCTION, IN A
MANNER TO PREVENT DAMAGE, AND DELIVER TO OWNER.
26. CONTRACTOR SHALL ENGAGE OWNER'S CONTROL VENDOR (SCHNEIDER ELECTRIC) FOR
ALL CONTROLS SCOPE. REFER TO DRAWINGS ME7 AND ME8.
27. CONTRACTOR SHALL COORDINATE WITH AND ASSIST OWNER'S COMMISSIONING AGENT
FOR FUNCTIONAL TESTING OF EQUIPMENT AND CONTROLS. REFER TO SPECIFICATION
SECTIONS 019100, 019110, 230800, AND 230810.
PHASING NOTES:
1. CONTRACTOR SHALL MEASURE AIR AND WATER FLOWS AT EACH AIR HANDLING
UNIT AND FAN AND REPORT RESULTS TO ENGINEER BEFORE PREPARING
EQUIPMENT SUBMITTALS.
2. DEMOLITION SHALL NOT TAKE PLACE UNTIL NEW EQUIPMENT IS ON SITE.
3. AIR HANDLING UNITS SHALL BE DELIVERED ASSEMBLED TO CONTRACTOR'S
OFFSITE STORAGE LOCATION FOR DISASSEMBLY.
4. PHASE 1 SHALL INCLUDE AHU-1, AHU-2, RAF-1, AND RAF-2. PHASE 1 SHALL BE
COMPLETED FIRST AND PRIOR TO THE START OF PHASE 2. THE WORK IN PHASE 1
IS CRITICAL TO RESTORING OPERATION OF THE THEATER AND SHALL BE
PRIORITIZED ACCORDINGLY. PHASE 1 SHALL BE SUBSTANTIALLY COMPLETE
WITHIN SIXTY (60) CONSECUTIVE CALENDAR DAYS FROM COMMENCEMENT OF
PHASE 1 WORK.
5. PHASE 2 SHALL INCLUDE AHU-3 AND RAF-3. PHASE 2 SHALL COMMENCE ONLY
AFTER SUBSTANTIAL COMPLETION OF PHASE 1. PHASE 2 SHALL BE
SUBSTANTIALLY COMPLETE WITHIN THIRTY (30) CONSECUTIVE CALENDAR DAYS
FROM COMMENCEMENT OF PHASE 2 WORK.
6. THE ENTIRE PROJECT SHALL ACHIEVE SUBSTANTIAL COMPLETION WITHIN NINETY
(90) CONSECUTIVE CALENDAR DAYS OF THE NOTICE TO PROCEED.
7. THE OWNER'S TARGET CONSTRUCTION WINDOW IS AUGUST 2027 THROUGH
NOVEMBER 2027. CONTRACTOR SHALL PLAN PROCUREMENT, SUBMITTALS,
DELIVERY, AND CONSTRUCTION ACTIVITIES TO SUPPORT THIS TARGET
COMPLETION WINDOW.
8. FINAL COMPLETION, INCLUDING PUNCH LIST ITEMS AND CLOSEOUT
DOCUMENTATION, SHALL BE ACHIEVED WITHIN THIRTY (30) CONSECUTIVE
CALENDAR DAYS FOLLOWING SUBSTANTIAL COMPLETION.
Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026 09/15/2026
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
SCALE:
NORTH
6"0 1' 2' 5' 1/2"=1'-0"
DEMOLITION PLAN - AHU-1
AHU-1
PAD
9'-3 1/2" x48 24
8' -2
/4
RAF-1
42x24
48x24
36x34
34x3430x26
A D1 D1
1 2
CONTROL
PANEL
FLEX
TYP OF 2
2"CWS/R
2"HWS/R
FD
SAT
FRZ
MAT
RAT
RET
REL
OA
SCALE:
6"0 1' 2' 5'
1/2"=1'-0"
AHU-1 ELEVATIONA
D1 D1
FINISHED
FLOOR
WALLWALL
PAD
FILTER
COILS
RETURN
PLENUM
3"
4' -2
/4
4' -0
2"
FLEXFLEX
SUPPLY FAN
AHU-1
48x24 34x34
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
GENERAL NOTES:
1. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR ADDITIONAL
DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING: ANY EXISTING CONSTRUCTION THAT IS TO BE
REMOVED SHALL BE REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY
EXISTING CONSTRUCTION THAT IS TO REMAIN.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. CONTRACTOR SHALL MEASURE AIR AND WATER FLOWS AT AHU-1 AND AIRFLOW
AT RAF-1 AND REPORT RESULTS TO ENGINEER PRIOR TO PREPARING
EQUIPMENT SUBMITTALS.
5. RETAIN EXISTING BRANCH CIRCUITS TO FURTHEST EXTENT FEASIBLE FOR
REMOVED EQUIPMENT FOR RECONNECTION.
6. REPLACE CONTROLS DEVICES ASSOCIATED WITH AHU-1 AND RAF-1 SEQUENCE
OF OPERATIONS. REFER TO DRAWING ME7. AIRFLOW MEASURING STATION
SHALL BE REMOVED AND NOT REPLACED.
DEMOLITION SYMBOLS LEGEND:
DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION PLAN - AHU-1
D1
X
DEMOLITION NOTES:XX
1. DISCONNECT HYDRONIC AND DRAIN PIPING. REMOVE SUPPLY AND RETURN DUCT
TO POINTS INDICATED. REMOVE AHU. PAD TO REMAIN.
2. DISCONNECT AND REMOVE CONTROLS DEVICES. RETAIN WIRING. REFER TO I/O
POINTS LIST ON DRAWING ME7.
3. REMOVE FAN, DUCT TRANSITIONS, AND FLEXIBLE CONNECTORS.
4. REMOVE DRAIN LINES.
5. REMOVE DISCONNECT. RETAIN BRANCH CIRCUIT FOR RECONNECTION.
MATERIAL TO BE DEMOLISHED
Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026 09/15/2026
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text M
AutoCAD SHX Text V
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
DEMOLITION PLAN - AHU-2
AHU-2
A D2 D2
8' -2
PAD
11'-3"
RAF-2
PLENUM
36x26 x2 x2 x3
1 2
FLEX
TYP OF 2
FD
FRZ
FD
RET
REL
OA
RAT
SCALE:
0 6" 2'1' 3' 4' 5'
3/8"=1'-0"
AHU-2 ELEVATIONA
D2 D2
FINISHED
FLOOR
WALLWALL
COILS
RETURN
PLENUM
FILTER
3/
4"
4' -2
/4
3' -1
1/
2"
SUPPLY FAN
AHU-2
PAD
3"CWS/R
2"HWS/R
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
DEMOLITION PLAN - AHU-2
D2
GENERAL NOTES:
1. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR ADDITIONAL
DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING: ANY EXISTING CONSTRUCTION THAT IS TO BE
REMOVED SHALL BE REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY
EXISTING CONSTRUCTION THAT IS TO REMAIN.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. CONTRACTOR SHALL MEASURE AIR AND WATER FLOWS AT AHU-2 AND AIRFLOW
AT RAF-2 AND REPORT RESULTS TO ENGINEER PRIOR TO PREPARING
EQUIPMENT SUBMITTALS.
5. RETAIN EXISTING BRANCH CIRCUITS TO FURTHEST EXTENT FEASIBLE FOR
REMOVED EQUIPMENT FOR RECONNECTION.
6. REPLACE CONTROLS DEVICES ASSOCIATED WITH AHU-2 AND RAF-2 SEQUENCE
OF OPERATIONS. REFER TO DRAWING ME7. AIRFLOW MEASURING STATIONS
SHALL BE REMOVED AND NOT REPLACED.
DEMOLITION SYMBOLS LEGEND:
DEMOLITION NOTE
LIMIT OF DEMOLITION
X
DEMOLITION NOTES:XX
1. DISCONNECT HYDRONIC AND DRAIN PIPING. REMOVE SUPPLY AND RETURN DUCT
TO POINTS INDICATED. REMOVE AHU. PAD TO REMAIN.
2. DISCONNECT AND REMOVE CONTROLS DEVICES. RETAIN WIRING. REFER TO I/O
POINTS LIST ON DRAWING ME7 .
3. RAF-2 HOUSING CANNOT BE REMOVED AND REPLACED DUE TO SURROUNDING
CONSTRUCTION. HOUSING TO REMAIN. REMOVE DUCT TRANSITION AND FLEXIBLE
CONNECTOR ON ONE END. REMOVE FAN MOTOR AND INTERNALS.
4. REMOVE FLEXIBLE DUCT CONNECTOR.
5. REMOVE DUCT ELBOW. SALVAGE AND CLEAN FOR REINSTALLATION.
6. REMOVE DRAIN LINES.
MATERIAL TO BE DEMOLISHED
Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026 09/15/2026
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
DEMOLITION PLAN - AHU-3
AHU-3
A D3 D3
10'-2"
PAD
'-1
/2
RAF-3
1 2
FLEX
TYP OF 2
FD
4"CWS/R
1 1/2"HWS/R
MCC2
MAT
FRZ
REL
SAT
OA
RET
RAT
SCALE:
0 6" 2'1' 3' 4' 5'
3/8"=1'-0"
AHU-3 ELEVATIONA
D3 D3
FINISHED
FLOOR
PAD
WALL
RETURN
PLENUM
FILTER
COILS
3/
4"
7' -0
SUPPLY
FAN
AHU-3
FLEX
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
DEMOLITION PLAN - AHU-3
D3
GENERAL NOTES:
1. REFER TO ELECTRICAL AND MECHANICAL DRAWINGS FOR ADDITIONAL
DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING: ANY EXISTING CONSTRUCTION THAT IS TO BE
REMOVED SHALL BE REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY
EXISTING CONSTRUCTION THAT IS TO REMAIN.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. CONTRACTOR SHALL MEASURE AIR AND WATER FLOWS AT AHU-3 AND AIRFLOW
AT RAF-3 AND REPORT RESULTS TO ENGINEER PRIOR TO PREPARING
EQUIPMENT SUBMITTALS.
5. RETAIN EXISTING BRANCH CIRCUITS TO FURTHEST EXTENT FEASIBLE FOR
REMOVED EQUIPMENT FOR RECONNECTION.
6. REPLACE CONTROLS DEVICES ASSOCIATED WITH AHU-3 AND RAF-3 SEQUENCE
OF OPERATIONS. REFER TO DRAWING ME8. AIRFLOW MEASURING STATIONS
SHALL BE REMOVED AND NOT REPLACED.
DEMOLITION SYMBOLS LEGEND:
DEMOLITION NOTE
LIMIT OF DEMOLITION
X
DEMOLITION NOTES:XX
1. DISCONNECT HYDRONIC AND DRAIN PIPING. REMOVE SUPPLY AND RETURN DUCT
TO POINTS INDICATED. REMOVE AHU. PAD TO REMAIN.
2. DISCONNECT AND REMOVE CONTROLS DEVICES. RETAIN WIRING. REFER TO I/O
POINTS LIST ON DRAWING ME8.
3. REMOVE FAN, DUCT TRANSITIONS, AND FLEXIBLE CONNECTORS.
4. REMOVE HEATING COIL CIRCULATING PUMP.
5. REMOVE DRAIN LINES.
6. REMOVE VARIABLE FREQUENCY DRIVE. RETAIN BRANCH CIRCUIT FOR
RECONNECTION.
MATERIAL TO BE DEMOLISHED
Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026 09/15/2026
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text P
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text C
AutoCAD SHX Text M
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text V
AutoCAD SHX Text
VFD
AutoCAD SHX Text
VFD
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
NOTES:
1. CONCRETE SHALL HAVE A MIN f'c = 4,000 PSI IN 28 DAYS.
2. REINFORCEMENT SHALL BE GRADE 60.
3. WATER AND CEMENT RATIO = .50.
4. AIR ENTRAINMENT SHALL BE 2% (±1%).
5. CONTRACTOR SHALL VERIFY MINIMUM REQUIRED HEIGHT OF EQUIPMENT
ABOVE PAD FOR INSTALLATION OF CONDENSATE DRAIN.
3/4" CHAMFER
4"
#4@12" EACH WAY
4"
1" C
LR
ROUGHEN CONTACT
SURFACE & APPLY
BONDING COMPOUND
WELDED WIRE FABRIC
WWF 6x6-W2.1xW2.1
(OR #3@8"OC)
#4 DOWEL, DRILL &
EPOXY INTO (E)FLOOR
SLAB @ 2'-0" AROUND
PERIMETER OF PAD
(4" MINIMUM EMBED)
6"
EDGE OF EQUIPMENT
EXISTING FLOOR
EXISTING PAD
POUR NEW CONC TO
MATCH EXISTING HEIGHT
T/PAD
T/(E)SLAB
SCALE: NONE
INTERIOR HOUSEKEEPING PAD EXTENSION DETAIL
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
MECHANICAL LEGEND, SPECIFICATIONS, AND DETAILS
ME1
CONSTRUCTION NOTE A AMPERE
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CA COMPRESSED AIR
CF CHEMICAL FEED, CUBIC FEET
CFM CUBIC FEET PER MINUTE
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
D DRAIN
DIA, Ø DIAMETER
DB DRY BULB
DBA DECIBELS, A WEIGHTED
DEG, ° DEGREE
DTR DUAL TEMPERATURE WATER RETURN
DTS DUAL TEMPERATURE WATER SUPPLY
DX DIRECT EXPANSION
DWG DRAWING
(E) EXISTING
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EL, ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FD FIRE DAMPER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FT FOOT, FEET
G GAS
GA GAGE
GAL GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT
HD HEAD
HP HORSEPOWER
HR HOUR(S)
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HZ FREQUENCY
ID INSIDE DIAMETER
IN INCHES
INWG INCHES WATER GAUGE
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB POUND(S)
LF LINEAR FEET
LPG LIQUEFIED PETROLEUM GAS (PROPANE)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NC NORMALLY CLOSED
NG NATURAL GAS
NO NORMALLY OPEN, NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
% PERCENT
PD PRESSURE DROP OR DIFFERENTIAL
PH PHASE
PRV PRESSURE REDUCING OR REGULATING
VALVE
PSIG POUNDS PER SQUARE INCH GAGE
PSV PRESSURE SAFETY VALVE
R12, R22 REFRIGERANT (12, 22, ETC.)
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SQUARE FOOT, FEET
SHR SENSIBLE HEAT RATIO
SP STATIC PRESSURE
SPEC SPECIFICATION
SQ SQUARE
TD TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TOD TOP OF DUCT
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T'STAT THERMOSTAT
TYP TYPICAL
V VOLTS
VAV VARIABLE AIR VOLUME
VTR VENT THRU ROOF
W WATT, WIDTH
WB WET BULB
MANUAL VOLUME DAMPER
FLEXIBLE DUCTWORK
TRANSITION IN DUCT SIZE
45° BRANCH CONNECTION
FIRE DAMPER IN WALL
FIRE DAMPER IN FLOOR,
CEILING OR ROOF
CONNECT TO EXISTING
INDICATES NUMBER OF
REVISIONS, CORRESPONDS
AIRFLOW
M
M
PIPE CAP
PUMP
THERMOMETER
PRESSURE GAUGE
UNION
PIPE TURNING DOWN
WYE STRAINER
PIPE TURNING UP
TEE DOWN
MOTOR OPERATED DAMPER
REVISION CLOUD
REVISION TRIANGLE
SYMBOLS
LEGEND
ABBREVIATIONS
TAG NO
CFM
DIFFUSER/GRILL TAG
HVAC SPECIFICATIONS
CONCENTRIC REDUCER
PIPE FLANGE
GLOBE VALVE
CHECK VALVE
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
ECCENTRIC REDUCER
MOTORIZED 2-WAY VALVE
PNEUMATIC 2-WAY VALVE
SOLENOID VALVE
MOTORIZED 3-WAY VALVE
PNEUMATIC 3-WAY VALVE
CALIBRATED BALANCING VALVE
BACKFLOW PREVENTER
AIR VENT (AUTO)
PLUG VALVE
SAFETY RELIEF VALVE
PRESSURE REDUCING VALVE
TEMPERATURE SENSOR
FLOW SWITCH
AIR VENT (MANUAL)
EQUIPMENT TAG
PIPE FLOW ARROW
WITH REVISION NOTE
ACCESS DOOR
M
M
S
F
T
A
M
SUPPLY/OA DUCT SECTION OR
DIFFUSER/GRILLE
RETURN/EXHAUST DUCT SECTION
OR DIFFUSER/GRILLE
TRANSITION FROM RECTANGULAR
TO ROUND
45° BRANCH TO ROUND
TAKEOFF CONNECTION
FLEXIBLE CONNECTOR
90° ELBOW UP
90° ELBOW DOWN
45° CONICAL TAP
90° CONICAL TAP
WALL MOUNTED HUMIDISTAT OR
DUCT SMOKE DETECTOR
CONICAL SPIN-IN WITH DAMPER
WALL MOUNTED THERMOSTAT
HUMIDITY SENSOR
OR TEMPERATURE SENSOR
H
T
90° ELBOW WITH TURNING VANES
(RECTANGULAR DUCT)
90° RADIUS ELBOW
(RECTANGULAR DUCT)
45° RADIUS ELBOW
(RECTANGULAR DUCT)
TEE WITH TURNING VANES
(RECTANGULAR DUCT)
RADIUS TEE
(RECTANGULAR DUCT)
Y FITTING
(ROUND DUCT)
AHU-1
X-1
WALL MOUNTED SWITCH
1. DRAWINGS DO NOT INDICATE PIPING SUPPORT LOCATIONS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY PIPE SUPPORTS. SELECTIONS OF PIPE SUPPORT TYPES, SIZES, AND LOCATIONS SHALL CONFORM TO MSS SP-58. SUPPORT SPACING SHALL COMPLY WITH MSS SP-58, INDIVIDUAL SPECIFICATION SECTIONS, OR
TABLE BELOW, WHICHEVER IS MORE STRINGENT.
PIPE SUPPORT (HORIZONTAL HANGER SPACING - VERTICAL SUPPORT SPACING)
PVC 4 FT 10 FT
STEEL 1" AND SMALLER 6 FT 10 FT
STEEL 1 1/4" - 2" 10 FT 10 FT
STEEL 2 1/2" AND LARGER 12 FT 15 FT
2. DUCTWORK SHALL BE G-90 GALVANIZED STEEL, FABRICATED, INSTALLED, AND SUPPORTED PER SMACNA STANDARDS FOR +/- 2.0 INWG. SUPPLY AND RETURN DUCTWORK SHALL BE LINED, THICKNESS TO MATCH EXISTING. SEAL DUCTWORK TO
ACHIEVE MINIMUM 95% TOTAL AIRFLOW.
3. PROVIDE AIR TURNING DEVICES IN DUCTWORK AT ANY CHANGE IN DIRECTION GREATER THAN 30 DEGREES. SQUARE THROAT ELBOWS WITHOUT TURNING VANES, MITERED ELBOWS, STRAIGHT RECTANGULAR AND ROUND DUCT TAPS, AND AIR
SCOOPS ARE NOT PERMITTED.
4. PROVIDE FLEXIBLE CONNECTIONS BETWEEN EQUIPMENT AND CONNECTING DUCTWORK. FLEXIBLE CONNECTORS SHALL BE 3 - 1/2" GLASS FABRIC DOUBLE COATED WITH NEOPRENE ATTACHED TO GALVANIZED STEEL STRIPS.
5. INTERIOR PIPING SHALL BE INSTALLED AS HIGH AS POSSIBLE AND ALL HYDRONIC PIPING SLOPED 1/8" PER FOOT BACK TOWARDS LOW POINT DRAINS. ALL PIPING SHALL BE CLEAN AND FREE OF DIRT AND SCALE AT TIME OF INSTALLATION.
6. PROVIDE AIR VENTS AT HIGH POINTS AND DRAINS AT LOW POINTS IN HYDRONIC PIPING SYSTEMS.
7. INSTALLATION OF FIELD MOUNTED CONTROL COMPONENTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
8. AN ASSOCIATED AIR BALANCE COUNCIL OR NATIONAL ENVIRONMENTAL BALANCING BUREAU CERTIFIED TESTING AND BALANCING CONTRACTOR SHALL BALANCE AIR AND WATER FLOWS AND SUBMIT REPORTS TO THE ENGINEER AND OWNER
FOR APPROVAL.
9. CONDENSATE DRAIN PIPING SHALL BE SCHEDULE 40 PVC, ASTM D 1785, SAME SIZE AS EQUIPMENT CONNECTION.
10. CHILLED WATER AND HEATING WATER PIPING SHALL BE CARBON STEEL, ASTM A53, SCHEDULE 40. 2" AND SMALLER PIPING SHALL BE THREADED WITH MALLEABLE IRON FITTINGS. 2-1/2" AND LARGER PIPING SHALL BE FLANGED OR WELDED WITH
CARBON STEEL FITTINGS.
11. CHILLED WATER PIPING INSULATION SHALL BE 1-INCH-THICK PRE-MOLDED CLOSED-CELL ELASTOMERIC FOAM. APPLY
ADHESIVE PER MANUFACTURER'S INSTRUCTIONS. SELF-SEALING STRIPS ARE NOT PERMITTED.
12. HEATING WATER PIPE INSULATION SHALL BE MINERAL FIBER, ASTM C 553, TYPE II WITH ASJ-SSL JACKET, 2-INCH-THICK FOR
2" AND LARGER PIPING AND 1-INCH-THICK FOR 1-1/2" AND SMALLER PIPING.
13. AFTER NEW EQUIPMENT HAS BEEN INSTALLED AND FILLED, CONTRACTOR SHALL RECHECK SYSTEM FILL PRESSURE, CHECK/SET EXISTING MAKEUP VALVE ACCORDINGLY, AND CHECK/SET EXISTING HEATING AND CHILLED WATER EXPANSION TANK CHARGES TO MATCH THE CALCULATED SYSTEM PRESSURE AFTER ALL AIR HAS BEEN PURGED FROM THE SYSTEM.
CO2 SENSOR
AIRFLOW RATE
CLEANOUT PLUG
DRAIN PIPE FULL SIZE
SAME AS PAN CONNECTION
SLOPE DOWN
1/8"/FT MIN
NOTE:
PROVIDE TRAP PER MANUFACTURER'S WRITTEN INSTRUCTIONS. WHEN INSTRUCTIONS ARE
NOT AVAILABLE, PROVIDE TRAP PER DETAIL. MINIMUM SIZE H1 AND H2 (IN INCHES) AS
FOLLOWS:
1. DRAW THRU UNITS
H1 = (FAN SUCTION PRESSURE) + 1"
H2 = 1/2 H1 + 1/2"
2. BLOW THRU UNIT
H1 = 1/2"
H2 = (FAN DISCHARGE PRESSURE) X 1.5
3. ALL UNITS H1 + H2 AT LEAST 4".
4. DO NOT REDUCE SIZE OF CONDENSATE DRAIN.
5. DISCHARGE CONDENSATE TO GRADE OR FLOOR DRAIN WITH AIR GAP EQUAL TO 2 TIMES
PIPE DIAMETER.
6. VERIFY ADEQUATE HEIGHT ABOVE FLOOR, CONCRETE PAD, ROOF OR CEILING FOR
INSTALLATION AND MAINTENANCE OF TRAP.
H
H
N O
TE
UNIT OR DRAIN
PAN BOTTOM
SCALE: NONE
CONDENSATE DRAIN DETAIL
Lic. No. 035249
STEVEN M. HOVIS
09/15/2026
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text V
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
ELECTRICAL LEGEND,
ABBREVIATIONS, GENERAL
NOTES, AND SPECIFICATIONS ME2
CONSTRUCTION NOTE
DEMOLITION NOTE
SYMBOLS ABBREVIATIONS
MDP-1
MDP-1
INDICATES MULTIPLE HOMERUN CIRCUITS FROM SINGLE
PANEL/CIRCUIT.
HOMERUN TO PANEL AND CIRCUIT NUMBER AS INDICATED.
CONDUCTOR AND RACEWAY SIZE AS INDICATED IN
PANELBOARD SCHEDULE, UON.
HOMERUN CIRCUIT TO OTHER CIRCUIT. CONDUCTORS AND
RACEWAY SIZE AS NOTED.
CONDUCTORS AND RACEWAYS
CONDUIT RUN EXPOSED OR ABOVE CEILING
EQUIPMENT CONNECTION
POWER
(3)#12
IN 3/4"C
CONDUIT RUN CONCEALED UNDER FLOOR
JUNCTION BOX
CONDUIT TURNING DOWN
CONDUIT TURNING UP
PANELBOARD PANELBOARD NUMBER
VOLTAGE
POLES, WIRES
AMP RATING
POINT OF CONNECTION
NEW-TO-EXISTING
LIMIT OF DEMOLITION
A AMPERE
AC ABOVE COUNTER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AT AMP TRIP
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
BCSD BARE COPPER SOFT DRAWN
C CONDUIT
CB CIRCUIT BREAKER
DWG DRAWING
(E) EXISTING
ECB ENCLOSED CIRCUIT BREAKER
EMT ELECTRICAL METALLIC TUBING
FD FUSED DISCONNECT
FMC FLEXIBLE METALLIC CONDUIT
FTL FEED THROUGH LUGS
FVNR FULL VOLTAGE NON REVERSING
G, GND GROUND
GFI GROUND FAULT INTERRUPTING
HOA HAND-OFF-AUTO
HP HORSEPOWER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
JB JUNCTION BOX
KVA KILOVOLTAMPS
LFMC LIQUID-TIGHT FLEXIBLE METALL CONDUIT
MAX MAXIMUM
MC METAL CLAD CABLE
MCA MIN CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MIN MINIMUM
MLO MAIN LUGS ONLY
MOPD MAX OVERCURRENT PROTECTION DEVICE
N NEUTRAL
NF NON FUSED
NIC NOT IN CONTRACT
OCPD OVERCURRENT PROTECTION DEVICE
P PHASES OR POLES
PB PUSHBUTTON
RNC RIGID NONMETALLIC CONDUIT
RSC RIGID STEEL CONDUIT
SE SERVICE ENTRANCE
SPD SURGE PROTECTION DEVICE
STP SHIELDED TWISTED PAIR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WIRES
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
LEGEND
LP3
120/208 3P/4W 225A
MCB
STANDARD MOUNTING HEIGHTS
DEVICE MOUNTING HEIGHT (AFF) TO:
MOTOR STARTER AND VFD 6'-6" MAX TOP
1. ALL MOUNTING HEIGHTS SHALL BE AS LISTED ABOVE UNLESS
OTHERWISE INDICATED ON DRAWINGS.
2. ALL MOUNTING HEIGHTS SHALL BE IN ACCORDANCE WITH THE
AMERICANS WITH DISABILITIES ACT.
GENERAL NOTES:
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE THE GENERAL AND
APPROXIMATE LOCATION OF EQUIPMENT AND EXISTING CONSTRUCTION.
FIELD-VERIFY ALL DIMENSIONS AND LOCATIONS.
2. THESE DRAWINGS MAY NOT INDICATE ALL FITTINGS, PARTS AND ACCESSORIES
THAT ARE REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM. NO EXCLUSION
FROM OR LIMITATION IN THE SYMBOLISM USED ON THE DRAWINGS FOR THE WORK,
OR THE LANGUAGE USED IN THE SPECIFICATIONS FOR THE WORK SHALL BE
INTERPRETED AS A REASON FOR OMITTING THE APPURTENANCES OR
ACCESSORIES NECESSARY TO COMPLETE AND REQUIRED WORK, SYSTEM, OR ITEM
OF EQUIPMENT.
3. ALL ELECTRICAL WORK ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE
WITH THE 2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE, NFPA 70-2020
(NATIONAL ELECTRICAL CODE), NFPA 72-2019 (NATIONAL FIRE ALARM CODE),
CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: 2026 CPSM EDITION,
REVISION 0 (JULY 31, 2026), CHAPTER 2 OF 2010 ADA STANDARDS FOR ACCESSIBLE
DESIGN DATED SEPTEMBER 15, 2010, AND CHAPTERS 1 AND 3 THROUGH 11 OF
STANDARDS FOR ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ICC
A117.1-2017) APPROVED MARCH 28, 2017.
4. MATERIALS, EQUIPMENT, AND SYSTEMS SHALL MEET ALL PERTINENT
REQUIREMENTS OF THE AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM), THE
UNDERWRITERS LABORATORY (UL), THE NATIONAL ELECTRIC MANUFACTURER'S
ASSOCIATION (NEMA), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), AND OTHER NATIONALLY
RECOGNIZED AGENCIES.
5. COORDINATE ARRANGEMENT, MOUNTING, AND SUPPORT OF ELECTRICAL
EQUIPMENT TO AVOID INTERFERENCES WITH ELECTRICAL AND OTHER TRADES.
COORDINATE WORK WITH EXISTING CONDITIONS INCLUDING BEAMS, COLUMNS,
SITE FEATURES, AND OTHER CONSTRUCTION WHETHER OR NOT SUCH IS SHOWN
ON THE DRAWINGS. SET SLEEVES IN CAST-IN-PLACE CONCRETE AND MASONRY
WALLS, AS THEY ARE CONSTRUCTED. COORDINATE LOCATION OF ACCESS PANELS
AND DOORS FOR ELECTRICAL EQUIPMENT THAT ARE BEHIND FINISHED SURFACES
OR ARE OTHERWISE CONCEALED. COORDINATE AMPACITY, VOLTAGE, PHASING,
OVERCURRENT PROTECTION, AND LOCAL DISCONNECT REQUIREMENTS WITH
ACTUAL EQUIPMENT PROVIDED.
6. MAINTAIN A SET OF AS-BUILT RED-LINE MARKUPS INDICATING ACTUAL
INSTALLATION. DELIVER TO OWNER AT CONCLUSION OF PROJECT.
7. PROVIDE PRODUCT DATA SUBMITTALS FOR THE VFD'S. MATERIALS INSTALLED
PRIOR TO OBTAINING AN APPROVED SUBMITTAL ARE AT CONTRACTOR'S RISK.
8. CUT EXISTING CONSTRUCTION AS NEEDED FOR DEMOLITION AND CONSTRUCTION.
USE CUTTING METHODS THAT MINIMIZE DAMAGE TO FINISHED AND ADJACENT
SURFACES. PATCH EXISTING AND NEW CONSTRUCTION AND REPAIR ALL DAMAGED
SURFACES TO MATCH EXISTING. PATCH UNUSED AND ABANDONED PENETRATIONS.
9. CONTRACTOR SHALL ADVISE A/E IMMEDIATELY OF DISCREPANCIES WITHIN
DRAWINGS. MINOR DEVIATIONS FROM THE PLANS MAY BE MADE TO AVOID MINOR
CONFLICTS. WHERE MAJOR CONFLICTS ARE ENCOUNTERED, THE AFFECTED WORK
SHALL NOT BE INSTALLED UNTIL THE CONFLICT HAS BEEN RESOLVED. THE A/E IS
NOT RESPONSIBLE FOR THE CONSEQUENCES OF PROCEEDING WITH WORK BASED
ON CONTRACTOR INTERPRETATION OR ON DIRECTION FROM OTHER PARTIES.
10.CONTACT INFORMATION
SITE REPRESENTATIVE: KAYLIN BREWER: 260.580.4909
PANELBOARD, HATCHED AREA IS
DESIGNATED WORKING SPACE,
PAINTED PER SPECIFICATIONS AND
CPSM MANUAL
NON-FUSIBLE DISCONNECT
VARIABLE FREQUENCY DRIVE WITH BYPASS AND
LOCKABLE IN "OFF" POSITION
ELECTRICAL SPECIFICATIONS
RACEWAYS AND BOXES
A. MATERIALS:
EMT - ANSI C80.3, COMPRESSION FITTING ONLY, MIN SIZE 3/4-INCH
LFMC - MIN SIZE 3/4-INCH
SET SCREW FITTINGS SHALL NOT BE USED
B. INDOOR RACEWAY APPLICATIONS:
EXPOSED OR CONCEALED: EMT, UON
BOXES AND ENCLOSURES: NEMA 250, TYPE 1, UON
C. USE UP TO 72 INCHES OF LFMC FOR CONNECTION TO VIBRATING EQUIPMENT INCLUDING TRANSFORMERS AND MOTOR-DRIVEN EQUIPMENT.
WIRING METHODS
A. SINGLE CONDUCTORS SHALL BE COPPER, #12 MINIMUM CONDUCTOR SIZE, SOLID FOR #10 AWG AND SMALLER, STRANDED FOR #8 AWG AND LARGER. FOR ABOVE-GROUND APPLICATIONS USE THHN-THWN, 600VAC INSULATION.
B. RACEWAY APPLICATIONS:
BRANCH CIRCUITS: SINGLE CONDUCTORS IN RACEWAY, UON
ELECTRICAL IDENTIFICATION
A. EQUIPMENT IDENTIFICATION: PROVIDE LABELS FOR VARIABLE FREQUENCY DRIVES, AND AS ADDITIONALLY INDICATED. LABELS SHALL BE LAMINATED ACRYLIC, WITH 1/2-INCH ENGRAVED BLACK LETTERING ON 1-1/2-INCH WHITE STOCK ATTACHED WITH SCREWS. LABEL SHALL INDICATE EQUIPMENT FED AND ASSOCIATED CIRCUIT SOURCE.
B. USE VINYL OR VINYL-CLOTH, SELF-ADHESIVE, WRAPAROUND TYPE TAPE MARKERS FOR WIRE. FOLLOW THESE WIRE COLOR CODING CONVENTIONS.
CONDUCTOR 480/277V
PHASE A BROWN
PHASE B ORANGE
PHASE C YELLOW
GROUND GREEN
SUPPORT AND ANCHORAGE
A. PROVIDE SUPPORT AND ANCHORAGE THAT ARE ADEQUATE IN TENSION, SHEAR, AND PULLOUT FORCE TO RESIST MAXIMUM LOADS CALCULATED OR IMPOSED WITH A MINIMUM STRUCTURAL SAFETY
FACTOR OF FIVE.
B. STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-3 FACTORY FABRICATED COMPONENTS FOR FIELD ASSEMBLY WITH FINISH SUITABLE FOR THE ENVIRONMENT.
C.FOR ATTACHMENT TO CONCRETE AND SOLID MASONRY, USE WEDGE-TYPE, ZINC-COATED STEEL EXPANSION ANCHOR FASTENERS. DRILL HOLES AT LOCATIONS AND DEPTHS THAT AVOID REINFORCING BARS. FOR CONNECTIONS TO HOLLOW MASONRY USE ALL-STEEL SPRINGHEAD TYPE TOGGLE BOLTS.
D. HANGER RODS TO BE THREADED STEEL.
E. FOR CONNECTIONS TO LIGHT STEEL USE SHEET METAL SCREWS.
F. SEPARATE DISSIMILAR METALS AND METAL PRODUCTS FROM CONTACT WITH WOOD OR CEMENTITIOUS MATERIALS BY PAINTING EACH METAL SURFACE IN AREA OF CONTACT WITH A BITUMINOUS
COATING OR BY OTHER PERMANENT SEPARATION.
G.RACEWAY SUPPORT INTERVALS
RACEWAY MAX DISTANCE MAX SUPPORT MAX LENGTH
TYPE TO FIRST SUPPORT INTERVAL OF RUN
LFMC 12 INCHES 54 INCHES 72 INCHES
EMT 36 INCHES 120 INCHES NONE
VARIABLE FREQUENCY MOTOR CONTROLLERS OR DRIVES (VFC OR VFD).
A. PROVIDE SUBMITTALS THAT INCLUDE DIMENSIONS, CAPACITY, OPERATING CHARACTERISTICS, AND ELECTRICAL CHARACTERISTICS. THE SUBMITTAL SHALL INCLUDE A WIRING DIAGRAM INDICATING ALL
POWER, SIGNAL AND CONTROL WIRING REQUIREMENTS.
B. PROVIDE VFD SUITABLE FOR THE APPLICATION AND COMPATIBLE WITH THE HVAC EQUIPMENT MOTOR LOAD. COORDINATE WITH OTHER TRADES INCLUDING CONTROL VENDOR AND EQUIPMENT
MANUFACTURER FOR THE INSTALLED EQUIPMENT.
C. PROVIDE DRIVE OR CONTROLLER THAT IS COMPLIANT WITH IEEE 519 GUIDE FOR HARMONIC CONTENT AND CONTROL.
D. PROVIDE VARIABLE-FREQUENCY MOTOR CONTROLLER, CONSISTING OF POWER CONVERTER THAT EMPLOYS PULSE-WIDTH-MODULATED INVERTER, FACTORY BUILT AND TESTED IN AN ENCLOSURE, WITH INTEGRAL DISCONNECTING MEANS AND OVERCURRENT AND OVERLOAD PROTECTION; LISTED AND LABELED BY AN NATIONALLY RECOGNIZED TESTING LABORATORY AS A COMPLETE UNIT; ARRANGED TO PROVIDE SELF-PROTECTION, AND VARIABLE-SPEED CONTROL OF ONE OR MORE THREE-PHASE INDUCTION MOTORS BY ADJUSTING OUTPUT VOLTAGE AND FREQUENCY.
E. PROVIDE WITH NEMA 250, TYPE 1 ENCLOSURE.
F. PROVIDE VFD THAT IS LISTED AND LABELED FOR INTEGRATED SHORT-CURRENT CURRENT (WITHSTAND) RATING SUITABLE FOR THE APPLICATION.
G.DESIGN AND RATING: TO MATCH THE HVAC LOAD SCHEDULED ON THE MECHANICAL DRAWINGS.
H. OUTPUT RATING: THREE PHASE; 10-60 HERTZ WITH VOLTAGE PROPORTIONAL TO FREQUENCY THROUGHOUT VOLTAGE RANGE; MAXIMUM VOLTAGE EQUALS INPUT VOLTAGE OF 460-480 VOLTS.
I. PROVIDE WITH PROVISIONS TO BE LOCKED "OFF".
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026
AutoCAD SHX Text E
AutoCAD SHX Text
JB
AutoCAD SHX Text
XXXA
AutoCAD SHX Text
VFD
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
6"0 1' 2' 5' 1/2"=1'-0"
MECHANICAL PLAN - AHU-1
RAF-1
AHU-1
(E)42x24
(E)48x24
(E)36x34
(E)34x34
A
ME3 ME3
(E)48x24
(E)CONTROL
PANEL
2 3 11
FLEX
TYP OF 2
FD
MCC1 (REFER TO
DRAWING ME4)
VFD 7
MCC1 (REFER TO
DRAWING ME4)
VFD 5
FRZMAT
SAT
RAT
RET
REL
OA
SCALE:
6"0 1' 2' 5'
1/2"=1'-0"
AHU-1 ELEVATIONA
ME3 ME3
(E)34x34
AHU-1
(E)FINISHED
FLOOR
(E)WALL(E)WALL
FLEX
FLEX
PAD
EXTENSION
PAD
EXTENSION
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
GENERAL NOTES:
1. NEW AIR HANDLING UNITS SHALL FIT WITHIN AVAILABLE SPACE AND SHALL BE
BROKEN DOWN INTO COMPONENT PARTS WHICH CAN BE DELIVERED TO THE
LOCATION THROUGH AVAILABLE BUILDING OPENINGS AND ACCESS AISLES AND
REASSEMBLED IN PLACE. CONTRACTOR SHALL BE RESPONSIBLE FOR
DETERMINING THE AVAILABLE CLEARANCES IN THE FIELD AND CONVEYING TO
THE MANUFACTURER PRIOR TO SUBMITTING PRODUCT DATA SUBMITTALS.
2. PROVIDE CONDENSATE DRAIN PIPING FULL SIZE TO FLOOR DRAIN.
3. REWORK BRANCH CIRCUITS AS REQUIRED TO PROVIDE VFD'S.
4. REFER TO BRANCH CIRCUIT SCHEDULE ON DRAWING ME6 FOR REWORKED
BRANCH CIRCUITS.
5. REQUIRED ELECTRICAL CLEARANCES ARE SHOWN AS HATCHED AREAS.
CONSTRUCTION NOTES:
1. PROVIDE PAD EXTENSION.
2. PROVIDE UNIT ON PAD. RECONFIGURE HYDRONIC PIPING AS REQUIRED TO
RECONNECT TO COILS. PROVIDE SUPPLY AND RETURN DUCT AND RECONNECT
TO EXISTING AT POINTS INDICATED. PROVIDE FLEX CONNECTORS IN SUPPLY AND
RETURN DUCTS.
3. PROVIDE CONTROLS DEVICES AND RECONNECT WIRING. REFER TO I/O POINTS
LIST ON DRAWINGS ME7.
4. PROVIDE FAN, DUCT TRANSITIONS, AND FLEXIBLE CONNECTORS.
5. REPLACE FLEXIBLE METAL CONDUIT FROM JUNCTION BOX ABOVE AHU-1 WITH
LIQUID FLEXIBLE METAL CONDUIT. STRAP LIQUID FLEXIBLE METAL CONDUIT
WITHIN 12" OF BOXES AND DO NOT EXCEED MORE THAN 3' WITHOUT SUPPORT.
6. PROVIDE 15 HP, UL LISTED VFD WITH BYPASS AND 6 POLES ON THE LOAD SIDE.
PROVIDE WITH 30" W x 36" L WORKING CLEARANCES IN FRONT OF VFD.
7. PROVIDE 5 HP, UL LISTED VFD WITH BYPASS. PROVIDE WITH 30" W x 36" L
WORKING CLEARANCES IN FRONT OF VFD.
XX
NEW WORK PLAN - AHU-1
ME3Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 0402061572
JOSEPH R. GOSSEN
09/15/2026 09/15/2026
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text
VFD
AutoCAD SHX Text
VFD
AutoCAD SHX Text E
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text W
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text T
0 6" 2'1' 3' 4' 5' 3/8"=1'-0"
MECHANICAL PLAN - AHU-2
RAF-2
AHU-2
(E)PLENUM
(E)36x26
(E )3
6x
(E )5
0x 22(E
)3 6x
A
ME4 ME4
FD
7 1098(E)MCC1
MCC1
MCC1
MAT FRZ
SAT
RAT
OA
RET
REL
AHU-2
SCALE:
0 6" 2'1' 3' 4' 5'
3/8"=1'-0"
AHU-2 ELEVATIONA
ME4 ME4
(E)FINISHED
FLOOR
PAD
EXTENSION
(E)WALL
(E)PAD
NVCC - ANNANDALE CAMPUS
CE REPLACE AHUs
PROJECT CODE: M25NV120
ANNANDALE, VIRGINIA
26007 2026-09-15
DATE:PROJECT NO:
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VIRGINIA 24551
PHONE: (434) 316-6001
Drawing No.:
1"
Full Scale Verification
0"
REVISIONS DATEBYNO.
NEW WORK PLAN - AHU-2
ME4
GENERAL NOTES:
1. NEW AIR HANDLING UNITS SHALL FIT WITHIN AVAILABLE SPACE AND SHALL BE
BROKEN DOWN INTO COMPONENT PARTS WHICH CAN BE DELIVERED TO THE
LOCATION THROUGH AVAILABLE BUILDING OPENINGS AND ACCESS AISLES AND
REASSEMBLED IN PLACE. CONTRACTOR SHALL BE RESPONSIBLE FOR
DETERMINING THE AVAILABLE CLEARANCES IN THE FIELD AND CONVEYING TO
THE MANUFACTURER PRIOR TO SUBMITTING PRODUCT DATA SUBMITTALS.
2. PROVIDE CONDENSATE DRAIN PIPING FULL SIZE TO FLOOR DRAIN.
3. PROVIDED OVER CURRENT PROTECTIVE DEVICES SHALL BE A MINIMUM OF 22
KAIC.
4. REWORK BRANCH CIRCUITS AS REQUIRED TO PROVIDE VFD'S.
5. REFER TO BRANCH CIRCUIT SCHEDULE ON DRAWING ME6 FOR REWORKED
BRANCH CIRCUITS.
6. REQUIRED ELECTRICAL CLEARANCES ARE SHOWN AS HATCHED AREAS.
CONSTRUCTION NOTES:
1. PROVIDE PAD EXTENSION.
2. PROVIDE UNIT ON PAD. RECONFIGURE HYDRONIC PIPING AS REQUIRED TO
RECONNECT TO COILS. PROVIDE SUPPLY AND RETURN DUCT AND RECONNECT
TO EXISTING AT POINTS INDICATED. PROVIDE FLEX CONNECTORS IN SUPPLY AND
RETURN DUCTS.
3. PROVIDE CONTROLS DEVICES AND RECONNECT WIRING. REFER TO I/O POINTS
LIST ON DRAWING ME7.
4. PROVIDE MOTOR. PROVIDE INTERNALS INSIDE EXISTING FAN HOUSING. PROVIDE
DUCT TRANSITION AND FLEXIBLE CONNECTOR.
5. PROVIDE FLEXIBLE CONNECTOR.
6. REINSTALL SALVAGED DUCT ELBOW.
7. PROVIDE 20A OVER CURRENT PROTECTION DEVICE TO REPLACE EXISTING OVER
CURRENT PROTECTION DEVICE ASSOCIATED WITH AHU-1.
8. PROVIDE 20A OVER CURRENT PROTECTION DEVICE TO REPLACE EXISTING OVER
CURRENT PROTECTION DEVICE ASSOCIATED WITH RAF-1.
9. PROVIDE 20A OVER CURRENT PROTECTION DEVICE TO REPLACE EXISTING OVER
CURRENT PROTECTION DEVICE ASSOCIATED WITH AHU-2.
10. PROVIDE 20A OVER CURRENT PROTECTION DEVICE TO REPLACE EXISTING OVER
CURRENT PROTECTION DEVICE ASSOCIATED WITH RAF-2.
11. PROVIDE 15 HP, UL LISTED VFD WITH BYPASS AND 6 POLES ON THE LOAD SIDE.
PROVIDE WITH 30" W x 36" L WORKING…
This is the start of the file's text. The full file is on GovTribe.