This is a Notice of Intent to Include Sole Source Specifications in a Future Contract issued by the U.S. Army Corps of Engineers Nashville District for the supply and delivery of a Generator Vacuum Circuit Breaker. The solicitation number is W912P526Q1CED, and the contract will be a Single Award Firm Fixed-Price supply contract. The procurement is for a replacement vacuum circuit breaker (VCB) designed to work with EATON VacClad-W Metal-Clad Switchgear at the Center Hill Power Plant. The replacement part number is 3759A72H12, and the circuit breaker being replaced is an EATON 150VCP-WG50. The VCB must be compatible with the existing Center Hill Power plant Eaton switchgear unit and cabinet configuration or will be rejected.
The specifications require the VCB to meet multiple technical requirements including: maximum voltage of 15 KV RMS with a voltage range factor of 1; insulation and withstand test voltage requirements including 36KV RMS power frequency, 42KV peak impulse withstand, and 95KV peak lightning withstand; and current requirements including 3000 amperes continuous current at 60 Hz, 50 KA RMS short circuit current, and 50 milliseconds breaking time. Additional specifications include minimum opening time of 32 milliseconds, interrupting time of 3 cycles, permissible tripping time of 2 seconds, making current of 137KA peak, short-circuit withstand of 3 seconds, breaking current of 25KA, mechanical endurance of 10,000 cycles, and load switching endurance of 1,000 cycles. The VCB must include standard features such as motor cutoff switch, latch check switch, two position switches, auxiliary switch, ground contact assembly, casters, and other standard receiving components and parts. Responses must be received by Monday, August 24, 2026 at 11:00 a.m. Central Time. Interested parties should submit product information to Contract Specialist Jamie Lynn Barnes at Jamie.L.Barnes@usace.army.mil. The government will not be responsible for costs incurred in preparing responses.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTICE OF INTENT TO INCLUDE SOLE SOURCE SPECIFICATIONS IN A FUTURE
CONTRACT FOR CENTER HILL – 3000A GENERATOR VACUUM CIRCUIT BREAKER
Description(s):
U.S. ARMY CORPS OF ENGINEERS-NASHVILLE DISTRICT'S NOTICE OF INTENT TO
INCLUDE SOLE SOURCE SPECIFICATIONS IN A FUTURE CONTRACT FOR THE
SUPPLY AND DELIVERY OF CENTER HILL – 3000A GENERATOR VACUUM CIRCUIT
BREAKER – SOLICITATION W912P526Q1CED
The U.S. Army Corps of Engineers Nashville District will be soliciting a sole source quote for a
Single Award Firm Fixed-Price supply contract for the supply and delivery of a Generator
Vacuum Circuit Breaker.
For the purposes described herein, the USACE Nashville District intends to issue a sole source solicitation that will include the items listed below:
Specifications:
The Generator Vacuum Circuit Breaker (VCB) shall be designed to work with EATON
VacClad-W Metal-Clad Switchgear. VCB part number to replace is 3759A72H12. The new
VCB must work with the Center Hill Power plant Eaton switchgear unit and cabinet configuration, if not it will be rejected for non-compatibility.
Circuit breaker type to be replaced is an EATON 150VCP-WG50
The ANSI standards listed below must be met for technical acceptance.
A Voltage Requirement
A1. Maximum Voltage: 15 KV RMS
A2. Voltage Range Factor: 1
B Insultation Level & Withstand Test Voltage Requirements
B1. Power Frequency (1 minute): 36KV RMS
B2. Impulse Withstand: 42KV peak
B3. Lighting Withstand: 95KV peak
C Current Requirements
C1. Continuous Current: 60 Hz of 3000 amperes
C2. Short Circuit Current (at rated maximum KV): 50 KA RMS
C3. Breaking Time: 50 ms
C4. Minimum Opening Time: 32 ms
D. Interrupting time: 3 cycles
E. Permissible tripping time: 2 seconds
F. Maximum voltage divided by K: 15 KV RMS
G. Peak voltage E2: 27KV
H. Time to peak T2: 8.8 us
I. Making Current (peak): 137Ka
J. Breaking Current Time: 50KA
K. Short-Circuit Withstand: 3S
L. Breaking Current: 25KA
M. Timed peak I2: 3.5 Microseconds
N. Closed and latch capability momentary: 137 KA Peak
O. Charging motor: 125 VDC
P. Spring release coil: 125 VDC
Q. Anti pump Relay: 125 VDC
R. Shunt Trip Coil: 125 VDC
S. Mechanical Endurance: 10000
T. Load Switching Endurance: 1000
VCB Shall include standard features such as but not limited to motor cutoff switch, latch check switch, two (2) position switches, auxiliary switch, ground contract assembly, casters, and other standard receiving components and parts.
This Notice of Intent is not a request for competitive quotes. All responsible sources may identify their interest and submit clearly articulated product information. Product information provided will be considered solely at the discretion of the Government. Reponses must be received by Monday, August 24, 2026 at 11:00 am, Central Time to be considered.
The Government will not be responsible for any cost incurred in preparation of your response.
Submit a response and questions to this notice to, Contract Specialist Jamie Lynn Barnes:
Jamie.L.Barnes@usace.army.mil.
The posting of this Notice satisfies the provisions set forth in RFO Subpart 5.1 Presolicitation.
mailto:Jamie.L.Barnes@usace.army.mil
File details come from the government source that posted it. Updated .