The Contractor must clean and inspect all control consoles, lighting panels, and switchboards in the Engineering Control Center (compartment 3-152-0-E) due to damage from an electrical fire and dispersal of Purple-K (Potassium Bicarbonate Powder). Equipment requiring cleaning includes the Main Propulsion Control and Monitoring System (MPCMS) console, Main Service Switchboard, 400 Hz Switchboard, 120V Lighting Panel, Tank Level Indicating Panel, Fire Fighting Control Panel, Fire and Smoke Detection Panel, Fire Handling Alarm Switchboard, 723 Control Modules, Pre-heater Controller, and UPS components. The MPCMS console requires extensive internal cleaning of all five cabinets, including removal and cleaning of wire runs, contacts, PLC components, power supplies, transformers, junction boxes, electrical instruments, indicators, and HMIs. Cleaning must employ HEPA vacuuming for initial removal, dry ice cleaning for non-conductive internal surfaces, and non-conductive solvent wipes for final removal. Work must be performed at CGC Northland, 4000 Coast Guard Boulevard, Portsmouth, VA 23703, during the period of June 8-22, 2026. The Contractor must conduct a mandatory site visit prior to bidding, coordinate with a NAVSEA representative on-site, witness initial and final operational tests, provide temporary ventilation, and submit Completion/Correction Forms (CFR) following visual inspections by the Coast Guard Inspector.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| FAR Matrix2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK (SOW)
CGC Northland (WMEC-904) Engineering Control Center Cleaning
1. BACKGROUND
1.1 Intent. CGC Northland must have all control consoles, lighting panels, and switchboards cleaned and inspected due to electrical fire and disbursement of Purple-K or Potassium Bicarbonate Powder (PKP) in the Main Propulsion Control and Monitoring System (MPCMS) console located within Engineering Control Center (3-152-0-E).
1.2 Government-Furnished Property.
None.
2. REFERENCES
Coast Guard Drawing 901 WMEC 202-001, Rev J. Engineering Control Center Arrangement Coast Guard Maintenance Card WMEC-270 E-A-13909, Ship Service Switchboard Inspect and Clean Coast Guard Maintenance Card WMEC-270 E-A-1200, 400 Hz Switchboard Inspect and Clean
Surface Forces Logistics Center Standard Specification 0000 (SFLC Std Spec 0000), 2022, General Requirements
3. REQUIREMENTS
3.1 Site Visit. The Contractor must make a site visit prior to any bidding or proposal submission to ensure full understanding of requirements and scope of work.
3.2. Protective measures. The Contractor must furnish and install all protective measures in accordance with SFLC Std Spec 0000, paragraph 3.3.3 (Vessel component, space, and equipment protection)
3.2.1 Tech Rep. None. However, a NAVSEA Rep will be available for guidance when they are onboard the vessel.
3.2.2 Interferences. The Contractor must handle all interferences in accordance with SFLC Std Spec 0000, (Interferences). Known interferences include, but are not limited to the following:
Wire runs Electrical junction boxes Electrical/Electronic components Console doors
3.3 Operational test, initial. Prior to commencement of work, the Contractor must witness Coast Guard personnel perform an initial operational test of all items or shipboard devices to be disturbed, used, repaired, or altered, to demonstrate existing operational condition excluding MPCMS console.
3.3 Preparation.
3.3.1 Temporary Ventilation. The Contractor must provide adequate temporary ventilation to each compartment that is affected by shipboard console/switchboard cleaning and by securing associated fans, in accordance with the requirements of paragraph 3.3.1.1 (Temporary ventilation) of SFLC Std Spec 0000.
3.4 Cleaning Requirements. The Contractor must clean and inspect the internals of the following equipment listed in Table 1 or as designated by the Coast Guard Inspector using Coast Guard Drawing 901WMEC 202-001 as guidance:
Table 1 Equipment
MPCMS Console Main SS Switchboard 400 Hz Switchboard 120V Lighting Panel
Tank Level Indicating Panel (ACMS) Fire Fighting CTRL Panel
Fire and Smoke Detection Panel and associated junction boxes
Fire and Fire Handling Alarm Switchboard (2)723 CTRL Module
Pre-heater Controller (3-153-1) UPS above console
3.4.1 Particulars. MPCMS Console internals of all five cabinets (front, back, and in the space below the console) will need to be removed for further cleaning and inspection including but not limited to:
Wire Runs/Ways (Separate Only) Contacts PLC Components Power Supplies Terminal Boards (Do not remove) Transformers Junction Boxes Electrical Instruments Indicators HMIs MPCMS Cable Way Access Panels (Located in the Engine Room)
3.4.2 Mechanical Cleaning – General. Employ suitable mechanical means to clean all interior surfaces of consoles/switchboards/panels including all removed equipment from the designated MPCMS console to a condition free from PKP, dirt, grease, lint, impurities and any other foreign matter. Required methods include:
HEPA Vacuuming for initial removal Dry Ice cleaning for non-conductive, non-abrasive internal cleaning.
Non-conductive solvent wipes for final removal
3.4.3 Inspections. After completion of all cleaning operations, the Contractor must visually inspect, in the presence of the Coast Guard Inspector and Tech Rep, for cleanliness. Be aware that inspection of areas that are difficult to access may be conducted by means of a borescope. Submit a CFR.
3.5 Operational test, post repairs. After completion of work, the Contractor must thoroughly test, in the presence of the Coast Guard Inspector and demonstrate all items or shipboard devices that have been disturbed, used, repaired, altered, or installed to be in satisfactory operating condition (exception to
MPCMS).
4.0 ADMINISTRATION.
4.1 CONTRACTOR PERSONNEL
4.1.1 Qualified Personnel.
4.1.2 Employee Conduct.
Contractor employees shall present a professional appearance, and their conduct shall not reflect discredit upon the U.S. Government, and any involved Departments or Agencies.
4.1.3 Conflict of Interest.
The Contractor shall not employ any person who is an employee of the U.S. Government if that employment would, or would appear to cause, a conflict of interest. The Contractor shall take appropriate precautions as delineated in the Federal Acquisition Regulation (FAR) to preclude actual or apparent conflicts of interest.
4.2 PERIOD OF PERFORMANCE.
08JUN-22JUN2026
4.3 PLACE OF PERFORMANCE.
The primary place of performance shall be at CGC NORTHLAND located at below address:
CGC NORTHLAND
4000 Coast Guard Blvd Portsmouth, VA 23703
(571) 613-1598