QUESTIONS & ANSWERS
SOLICITATION #NIHOF2010210
As of: 04/08/2010
REPLY
BY
QUESTIONS RESPONSES TO QUESTIONS
1. Sheet A3.03 Note #3 requests that you reference the Project Specifications for skylights manufacturers, details, etc. No specification has been provided for information regarding skylights. Please advise.
1. Refer to new Specification SECTION 08630 METAL - FRAMED SKYLIGHT attached
2. Detail 4/A5.20 indicates the stair from the North Lobby down to the first floor level comprises of 9 equal treads. In reviewing detail 2/A5.21, there appears to be 10 equal treads. Please advise.
2. The top tread is at the entrance lobby elevation. As a result 9 equal tread is correct.
3. Ceramic Tile details on Sheet A5.50 provide details regarding the wall elevation tile pattern, but do not include any details associated with the floor tile pattern. Please provide a pattern for the floor tiling and base.
3. Refer to detail 1/A5.25
4. Please review and provide interior elevations, schedule of finishes for both elevator cabs, as none have been identified by the Contract Documents.
4. Refer to Specification Section 14210 - ELECTRIC TRACTION ELEVATOR, 2.6 CAR ENCLOSURES, D. Car Materials and Finishes: Add the following General: Provide wall hung panels as manufactured by SnapCab, model "Traditional" finished with choice of Standard Laminate finishes:
5. Detail 2/S3.04 indicates details the elevation for the elevator machine room. Please review and advise where this steel slab is being constructed, please provide a connection detail for the new masonry to the existing to remain roof structure. If the steel slab is being placed above the elevator shaft, does this elevation allow for sufficient overrun space?, and if so, what is the access to the elevator hoisting equipment and control panels.
5. Plan 2/S3.04 is partial plan of the existing machine room between lines F & G and lines 3 and 4. This area is not intended to be a machine room as part of the renovation work.
The elevation tag shown is to the existing slab that is located above the 5th floor level. No new slab is to be constructed at this location, above the 5th floor level.
6. If the contractor is to receive electronic CAD files prepared by the A/E and be required to create & maintain complete & full construction BIM Model…will the CAD files be provided in 2-D or 3-D? Or...will the provided files already be in a 3-D BIM Model format?
This will have a huge impact on the initial cost to set up the BIM Model for this project.
6. Requirement shall be removed (BIM)
7. Will electronic CAD files be provided by each of the design disciplines, i.e. Civil, Structural, Architectural, and MPE? Will the software be compatible / consistent to integrate to the BIM Model software or should we expect to utilize NAVIS for the integration?
7. Requirement shall be removed (BIM) Electronic record drawings will be required per section 01781
CO
8. In the RFP / Part IV Representations And Instructions
- Section K - Representations, Certifications and Other Statements of Offerors: there are parts that should be completed by the Contracting Officer.
When will this be completed, and will it be sent out as an addendum?
8. See Section L for the Business Size and NAICS Code.
Additionally, see Paragraph 1.(b)(2) which indicates that FAR Clause 52.204-7 applies. You must therefore go to Paragraph 1.(d) page 4 of the Section K document, which directs that you go to the hyperlink to the ORCA site and complete the Online Representation and Certification Application.
9. Other than the Pre Proposal Conference scheduled for March 24th I do not see any meetings scheduled for a walk through of the facility.
Due to the number of subcontractors involved I would hope to have at least two opportunities made available.
9. See response to RFI #8 above.
10. Spec Section 01270 -- Unit Price Item # 9 asks for pricing for "additional shoring and bracing" with a unit of measurement per LINEAR METER. Specification Section 02300 does not address this"unit price" or provide a height. Since this unit of measurement is normally provided as a per square unit measure instead of linear…do you have a unit height to correspond with the linear meter length so the
10. Linear meter is correct. The shoring requirement for the work is to be included in the base bid. Unit price item #9 is intended to address the possibility that the shoring (included as par to the base bid) may need to extend deeper that expected.
contractor can properly quantify the item? Or should this item be provided per square meter?
11. Spec Sections 03300 & 03720 -- Unit Price Item # 12 Concrete Repair refers to providing unit prices for additions and deductions for each of the repair quantities identified in the Concrete Repair notes on sheet S4.11 and per Division 03. The three REPAIR NOTES specific to concrete repairs are detailed on:
4/S4.11, 5/S4.11 & 7/S4.11. The additional concrete repair references in Divison 03300 Part 3 - Execution, Section 3.15 that refer to Concrete Surface Repairs for the following: A. Defective Concrete, B. Patching Mortar, C. Repairing Formed Surfaces, D. Repairing Unformed Surfaces, & E. structural repairs of concrete. Should the contractor assume the three details shown on sheet S4.11 are the only requested Unit Prices for this item?
11. The concrete repairs associated with Division 03300 are to address pouring and forming defects that may occur in newly poured concrete.
12. Spec Section 17723 - The Electrical drawings on sheet E0.02 refer to Specification Section 17723, regarding the Mass Evacuation System. Has this specification section been released yet? Where can I get a copy?
12. The specification section for the Mass Evacuation System is 16723.
13. The RFP - Section F - Deliveries of Performance, Article F.3 Time of Delivery, (a) states the delivery of the services described in Section C within 540 days.
The Solicitation, Offer, and Award Form 1442 issued on March 11, 2010 indicates a completion within 502 days. Please provide correct project period/duration for this solicitation / work.
13. The performance period is actually 365 working days which is 511 calendar days (365/(5/7)
14. Spec Section 01222 - I can find no reference to Cost Breakdown Item # CB27 on the plans. Please identify the work and location of the work in the contract document.
14. CB#27 refers to cleaning of existing trench drains at entrance to service area. Refer to drawing C1.03 and trench drain at SW corner of building and note "EX TRENCH DRAIN TO
REMAIN, CONTRACTOR IS TO CLEAN AND ENSURE IN
PROPER WORKING ORDER". Refer also to drawing A0.00 and to specification section 01700 "EXECUTION
REQUIREMENTS".
15. Spec Section 01222 - The Cost Breakdown Items stop at Item # CB33. On drawing sheets A2.01 & A3.01 a Cost Breakdown designation CB34 appears on each drawing with a different description at each location. How shall the contractor proceed with the two distinct CB items? Are they supposed to be included with the other breakdown items?
15. Refer to sheet Bid set (January 8, 2010) sheet A0.00 for list of cost breakdown items. Specification section 01222- COST
BREAKDOWN ITEMS, PART 3 - EXECUTION, 3.1 LIST OF
LINE ITEM BREAKDOWN PRICES, Add the following :
GG Line Item No. CB34 - Additional excavation of subsoil and sheeting and shoring if applicable.
Provide as indicated and specified
16. Divisions 8 & 13 -- Line Item No. CB28 within the proposed alternates for the Project identified within the formal RFP, as well as on sheet A8.05 of the Contract Documents, identifies that there should be a blast resistant laminated glass. Please review and advise the specifications and criteria that should be utilzied.
16. Refer to Bid set (January 8, 2010) sheet A0.00 for list of cost breakdown items. Section 01222- COST BREAKDOWN
ITEMS, PART 3 - EXECUTION, 3.1 LIST OF LINE ITEM
BREAKDOWN PRICES, BB line Item No. 28 delete "Blast Resistant Laminated Glass" and replace with the following the following: - Provide Exterior Windows with laminated glass.
1. Provide as indicated and specified
17. Article B. 3 Prices -- The statement at the bottom of Table B-1 -- Schedule Of Charges For The Basic Award Period instructs the contractor to provide back-up pricing information to support each CSI Division.
Are you asking for the individual Subcontractor bid quotations for each trade we submit? When is the "back-up" documentation due? Given the MEP trades "last minute" pricing due to supply houses not releasing material quotations, it is not expected we will know which subcontractor we will use, or have a completed subcontractor proposal in time to turn in our proposal. Can we have 48 to 72 hours to review subcontractor scopes and quotes prior to this disclosure?
17. We will accept back up calculations showing how you arrive at the B.3 pricing (unit pricing and quantities). Prior to award, the selected offeror must provide the subcontractor written quotes to support the calculations.
18. Article B.3 Prices -- Table B-1 -- Schedule Of Charges For The Basic Award Period is different from Attachment 6 - Pricing Schedule. Which Pricing Schedule do you wish the contractor to submit for this proposal?
18. Please disregard Attachment #6 – Provide your individual pricing calculations to support you B.3 pricing. See #17 above.
19. Article B.3 Pricing - Are we expected to include the
Owner Contingency at $2,000,000 in the Pricing Schedule we turn in?
19. You may; however, this amount may go up or down based on the selected offeror’s award price.
20. Spec Section 02620 -- Structural Drawing S3.01 indicates that the existing subdrainage lines shall be cleaned, serviced and utilized for the renovated building. Drawing Note #2 on sheet DP2.01 states that all plumbing utilities within the building shall be removed in their entirety and replaced with new piping. Please advise which note shall take precedence.
20. The existing sub-slab drainage system is to remain and is not part of the plumbing utilities of the building although, there is a note on the plumbing and structural drawings to tie the existing sub-slab drainage system into the storm water system as part of the work.
21. Please review and confirm that it shall be the General Contractors responsibility to design, furnish and install a permanent ground water system for the sub-basement level. Please advise if there is a current system in place, and if the Engineer of record has sized the new building systems to receive additional water from the dewatering system. Also, if there is a current system in place, will you provide all of the calculations and information downstream of the proposed work? If it is a CG responsibility to design are we precluded from using the Engineer of record as the designer? Since the Engineer of record already has the baseline studies and records it should be significantly less expensive and faster to produce the design.
21. According to the existing structural drawings, there is a sub-slab drainage system below the basement level slab and the layout of this system is shown on 1/S3.01. This layout is copied from the existing structural drawings. The existing structural drawings do not indicate a sub-slab drainage system in the sub-basement level. The new sub-slab drainage system shown in the new portion of the sub-basement is to be designed by the Contractor as noted on the drawings. Using the Engineer of record could be perceived as a conflict of interest.
22. The Contract Documents indicate that there is an Opaque Film to be applied to several of the window
22. Refer to new Specification SECTION 08871 PRIVACY FILM attached openings. Please review and advise what type of film, thickness and manufacturer should be utilized.
23. Article H.6. Wage Rates -- Can you confirm that the Wage Rate Decision to be implemented for this project is, in fact, the General Wage Decision (Montgomery County, MD) No. MD080056, Modification No. 22, dated 02/05/2010?
23. Note that there is a new Davis Bacon Wage Determination for Montgomery County, Maryland. The Wage Determination number is MD100056, dated 03/12/2010 and may be accessed at http://www.wdol.gov/wdol/scafiles/davisbacon/MD56.dvb
24. Our firm “An 8(a) firm” is Teaming with “Large Firm”, under written teaming agreement to submit proposal for NIH Bldg 3, and would like to use “Large Firms Resources, Past Performance & Relevant Experience” in our Technical Proposal, We have the following Questions:
1. WILL NIH ACCEPT LARGE FIRMS EXPERIENCE AS
“OFFERORS RELEVENT EPERIENCE?”
2. WILL NIH ACCEPT LARGE FIRMS PAST
PERFORMANCE AS “OFFERORS PAST
PERFORMACNE?”
3. IS HASCON CONSTRUCTION MANAGEMENT FOR
FEE EXPERIENCE ACCEPTABLE AS “OF
OFERORS RELEVENT EPERIENCE?”
4. Will NIH “Accept combined team of 8(a) Firm and Large Firm as Key Personnel” as “OFFERORS KEY
PERSONNEL”?
24. The solicitation doesn’t restrict a firm from teaming with another form (large or small); however, please see FAR Clause 52.219-14 (Limitations on Subcontracting). This clause was erroneously left out of Article I.3 of the Solicitation and will be added via an amendment. FAR Clause 52.219-14 requires that the prime contractor performs at least 15 percent of the work with his own staff.
25. We are submitting the following questions for the pre-proposal conference for the above-referenced solicitation:
1. Has the LEED charette been completed? If so, what will be required of the construction contractor?
25. 1. The LEED charette has been completed. The LEED Scorecard as of 2-23-2010, which indicates decisions made, will be distributed. For LEED requirements refer to specification sections 01352 "LEED REQUIREMENTS", 01440 "CONSTRUCTION INDOOR AIR QUALITY", 01524 "
CONSTRUCTION WASTE MANAGEMENT" and 01810
"GENERAL COMMISSIONING REQUIREMENTS".
Contractor is responsible for LEED requirements in all spec sections such as VOC limits, and items in LEED Scorecard http://www.wdol.gov/wdol/scafiles/davisbacon/MD56.dvb�
2. Past Performance: Please clarify the past performance requirements. The requirements as stated on pages 74 and 77 do not match.
Page 74, Item 10: “A list of the last 3 contracts completed during the past 7 years and or currently being performed…”
Page 77, Item a: “A list of the last contracts completed during the past Seven (7) years and THE LAST THREE CONTRACTS AWARDED currently being performed…” identified as "C".
2. Delete Paragraph 10, page 74. It is a duplicate of the Past Performance Information on page 77. In the 2nd sentence in Paragraph “a.” under Past Performance, change the first part of the sentence to read “A list of all contracts completed during the past Seven (7) years….
26. Drawing A4.03- Please confirm that projection screens will go in rooms 4E04 and 5E04. They are shown graphically, but they are not noted with section 5/A4.12.
26. Please provide projection screens in room 4E04, and 5E04 in accordance with detail indicated on construction documents.
27. Will there be a cap on the number of days for the liquidated damages stated in item 52.211-12, Item (a), on page 19 of the RFP?
27. There is no Cap. Liquidated damaged will be assessed beginning the day after the performance period ends. See #13 above for performance period and will depend on the contract performance period.
28. 01310-6 (1.9A) Is the Environmental Safety Officer / Industrial Hygienist required as a full time employee throughout the duration of the project or only when needed?
28. This in not required to be a full time position but on call when needed.
29. 01500-3 (D2) Is the Integrated Pest Management Quality Control Supervisor required as a fulltime employee throughout the duration of the project or only as needed?
29. This in not required to be a full time position but on call when needed.
30. Specification section 15900 - Building Automation and 30. Johnson Controls will be added as an acceptable controls
Temperature Controls calls for Siemens to be the only acceptable controls vendor. As one of two approved controls companies on the NIH Bethesda campus, and in the spirit of competition, Johnson Controls requests to be added as an acceptable controls vendor for this project.
vendor for this project. All controls submittals shall comply with the contract documents.
31. Solicitation- Page 69- Please confirm that RFIs can be sent in until noon on 4/9/10.
31. Solicitation questions can only be sent thru March 29, 2010 at 12 noon. Note that Section L, Paragraph 1.e. (page 68) has been changed to read:
……..”In addition you may sent written questions after the 3/22/2010 thru noon 03/29/2010. Answers to all question will be consolidated and posted as an amendment to this solicitation. The 03/29/2010 cut-off will allow time for any addendum to the drawings/specifications.” ……
32. Please confirm that the schedule to be submitted with the bid need not be on Primavera P6, but can be on any software.
32. The schedule for the bid can be any commercially available PC based software that is used for projects of this scope and size. The submission must be contain predecessors, successors and durations and be editable to view the logic to be considered responsive
33. Solicitation- Page 18- Article F.1- “The period of performance of this contract shall be from 4/27/10 through 10/19/11.” Please confirm that the dates shown supersede all other references to project duration.
33. The period of performance shall be 511 calendar days after Award/Notice to Proceed. The April 27th date is an estimated award date.
34. Please provide a list of the current bid documents including the dates.
34. See Amendment #000001 and #000003
35. Specification section 02111- All H Drawings- Please confirm whether or not the soffit and/or fascia at the roof overhang and dormers shown on drawings A8.03 and A8.04 have lead-based paint on them.
35. Yes, the soffit and fascia do contain lead-based paint.
Refer to notes on Drawing H1.00.
36. Solicitation- Page 6- The note at the bottom of the 36. Show your calculations (i.e., other works sheets to show table reads..”Provide back-up pricing information to support each CSI division.” Please provide a description of what is required.
how you arrived at proposed price for each division -- show unit prices, quantities; RS Means). You must provide supporting subcontractor quotes to support subcontractor pricing prior to contract award.
37. Solicitation – Page 30- Will AIS be required? If so, is there a specific software program we should use?
37.
38. Should we include any roof work in our bid? If so, please provide roof specs.
38. Refer to construction documents for extent of work.
39. C5.01- Section 5- Please provide spec for the stone, geo fabric and edging material. Please provide depth and width of stone strip.
39. Detail 5/C501 provides specification for stone as washed stone, type CR6. The depth of stone should be 100mm and the width should be 1.0M, as shown in the detail.
Contractor is to use any commercial grade seellandscape edging. For the geotextile fabric, Mirafi 140N or equivalent.
40. Please provide a specification for site restoration, i.e., Can disturbed areas of grass be re-seeded or will it be required to be sodded?
40. See sheet C4.02 for vegetative stabilization and seeding specifications.
41. We have submitted several RFIs and wanted to confirm that we have submitted them properly. Please let me know if we should re-submit them in a different format.
41. See the list of RFI. We are working on the responses and will update this list shortly.
42. I was hoping that you would be able to provide me with a list of interested bidders, planholders or Pre-Bid attendees so that we can submit our pricing for signage. Thanks so much in advance for your assistance.
42. A copy of t he Pre-proposal sign-in sheet is attached to Amendment #000001. You can also view the list of interested party list under this solicitation number at the FBO site.
43. Plan Sheet: A8.05 -- Specification Section: 08550
a. In the Pre-Conference yesterday it was mentioned that the windows will need to have a blast rating, but
43. a. Refer to construction documents and specifications
b. Provide substitution request of glazing for review.
c. Contractor to coordinate quantity of windows based on construction documents and field verification none are shown on the drawings or specs. If a blast rating is required will it fall under UFC-4-010-01. Can an all aluminum window be used in lieu of the aluminum clad?
b. On the window schedule notes some windows are scheduled to receive opaque film can acid etched or obscure glass be used in lieu of the opaque?
c. Can we rely on the window quantity noted on the schedule on sheet A8.05 or must we got individual floor plans?
d. Is the design intent to have a double hung window that is in operable or can a fixed window to simulate a double hung be used instead?
d. Refer to specification section 08550 Wood Windows
44. pre bid was not mandatory right, and three page of the standard form is all you need to be submitted right?
44. No, attendance to the pre-proposal conference is not a prerequisite to submitting a proposal. You must follow the solicitation instructions in submitting your proposal.
45. Please provide the contact information and procedure to gain access into Building # 3. Thanks!
45. The Project Officer contact information is as follows:
Mr. Dexroy Chism 301.402.7958 Dexroy.chism@nih.gov
46. Is there a limit to the area of the limit of disturbance
46. The limit of disturbance (LOD) shall be limited to 4500 sf and will be defined using orange blaze safety fence
47. Is stabilization required at the construction entrance?
47. Provide stabilized construction entrance(s) shall be constructed at every gate in the safety fence.
48. Is it the contractors responsibility to clean the roadway?
48. Any dirt tracked onto the roadway will be cleaned immediately – dry brushed. Use of water to wash the road is prohibited.
49. Does NIH require the fire standpipes to remain active during construction?
49. Yes, per NFPA 241. Standpipes will need to be in place prior to construction (before the storage of combustible mailto:Dexroy.chism@nih.gov� material). The standpipes in the stairwells need to be installed and connected to the FDC's while the permanent water supplied is being installed. Once the permanent supply is ready, the standpipes will need to be connected to it.
50. What LEED points will the project pursue 50. Please refer to the LEED score sheet
51. What Codes / Standards apply? 51. Please refer to www.orf.od.nov.gov
52. Section 07162- Crystalline waterproofing is in the specs, but not on the drawings. Please clarify.
52. Provide crystalline waterproofing per specifications at below grade conditions of Elevator pit #1, and #2, and Mechanical expansion
53. When will the contractors be allowed to walk thru Building #3?
53. Contractor can visit the work site (Building 3) Monday – Friday from 9:00am-4:30 pm. Contractors must first sign in at building 13 room 210 before visiting the site. Contractors must also follow lockout tag out procedures( two person) and wear the proper safety clothing.
54. A8.03- Elevation 2/A8.03 is missing some flag numbers. Please clarify.
54. Refer to attached SK-1 for revised detail 2/A8.03
55. Is there an NIH preferred Security Contractor? 55. No there is not an preferred security contractor.
56. C1.03- There are two gates at the jobsite entrance. Is this to stop all vehicles coming into the site for inspections? If so, should the GCs include a fulltime security guard at the gate?
56. The two gates are to be phased and are intended to limit delivery trucks from stacking outside the construction site.
Refer to note 4 on C100 and note 5 on A101. The North gate is intended to be installed first with the second gate to be installed during the second phase of the security work involving the sensing loops. Phasing of the security work as indicated on the Security drawings. For security requirements refer to Spec Section 01355 "Construction Security Requirements". The means and methods of the sequencing of all fence installations to accommodate the add alternates and cost breakdown items shall be indicated on the project schedule and included in the contractors bid.
57. My name is Khalid Saeed and I am the owner of Trichmir Marble and Granite Pvt. Ltd. I would
57.
http://www.orf.od.nov.gov/� like to obtain the following information regarding the project of 'Renovate Building 3, NIH, Bethesda, Maryland'.
My firm, Trichmir Marble and Granite Pvt. Ltd, is a well reputed firm in the field of marble and granite. This is the 15th year of our operation.
Over the last 15 years the firm has grown into three main firms. The other two are Indus Stone and Habib Marble and Granite. Also, we have quarries where we extract our raw material in block form, which is then transformed into bespoke products in our own processing units.
The project mentioned above include construction, which means that there will be required marble and granite and I want to be a vendor of marble and granite. Therefore, I will ask you for guidance on how to get my firm enlisted as a reputable vendor of marble and granite. I am not sure whether I can be a direct vendor or contractor or not. Can you please provide guidance on the said subject.
58. Drawing C1.00 indicates that 4 of the temporary trailers are NIC (Not in Contract). Please verify.
58. Temporary trailer shown are for possible locations only (except the government trailer which is required). The disturbance at the site cannot exceed 4500 sf unless the contractor will submit for MDE permit at no additional cost / time penalty to the government. The laydown work areas are to be inside the building.
59. C1.06- A note along the east side of the building indicates "Proposed Vegetation". Please provide specs for this item.
59. This is the proposed vegetation line. Contractor is to restore site vegetation (bushes, shrubs, ivy, etc.) to pre construction condition per note on sheet C1.06.
60. Please confirm that there is no silt fence required on this project. There is none shown on the plans.
60. Correct. No silt fence is proposed on-site.
61. A0.00/ A1.01- A1.01 shows 6 bike racks, however on A0.00 Item CB20 under Cost Breakdown Items Legend asks for a price for 19 additional bike racks. It is our understanding that the Cost Breakdown Items are those within the Base Price for the project. Item CB20, however appears to be an add alternate. Please clarify.
61. Bicycle racks shown are intended to accommodate 19 bicycles in accordance with LEED occupancy requirements.
Refer to response #126.
62. Please confirm Project Duration. It is indicated as 365, 502 and 540 days on different documents.
62. Please see #13
63. The Solicitation indicates 40 hours of Primavera P6 training for each of 10 people. Can this occur in one 40 hour class in which all 10 participants attend?
63. The training shall be in five (5) eight hour sessions on campus at time and date approved by the Government.
Contractor shall provide all materials, equipment, hardware and software for training and use on this project for the duration of the project.
64. A0.00- Cost Breakdown Item CB34 asks for pricing for
Additional Excavation. Please confirm that this is part of the Base Bid Price and not an Add Alternate.
64. Refer to response #126
65. There are somewhat different descriptions of what is required. Section L, Instructions, Conditions, and Notices to Offerors, item #2, Instructions to Offerors/a. General Instructions, item 10, Past Performance Information (page 74) requires “a list of the last 3 contracts completed during the past 7 years and/or currently being performed that are similar in nature to the administrated office facilities. Of these projects, at least one (1) project shall be a renovation project similar in scope and size to the Building 3 renovation.”
Section c. Technical Proposal Instructions / Past
65. Please see response to Question #25 (paragraph 2)
Performance Information (page 77) requires “a list of the last contracts completed during the past 7 years and THE LAST THREE CONTRACTS AWARDED currently being performed that are similar in nature to the solicitation work-scope.
Please clarify the Past Performance and Relevant Experience requirements.
66. Please advise for what projects the following information is required.
• Name of Contracting Organization
• Contract Number (for subcontracts, provide the prime contract number and the subcontract number)
• Contract Type
• Total Contract Value
• Description of Requirement
• Contracting Officer's Name and Telephone Number
• Program Manager's Name and Telephone Number
• North American Industry Classification System (NAICS) Code Information on problems encountered and offeror’s corrective actions
66. Assuming that you are referring to the Past Performance information, as indicated provide this information for all contracts completed with the 7 year period including three that are similar to the scope.
67. Offeror’s Relevant Experience (page 77) states:
“The offeror shall provide information to support demonstrate successfully completing at least one
(1) renovation project and not more than three (3) additional projects that are similar to the project type, size, scope, and magnitude.” Are these projects be the same as Past Performance projects?
67. If your relevant projects are the same as those provided in response to the Past Performance criteria then it’s your option as to which project(s) you want to use.
68. SECTION VII: Technical Summary Cost Form (Section J) QUESTION: This form is not listed in Section J.
Please provide or advise requirement.
68. Please see #18. This attachment has been removed;
however, we expect that you will provide calculations to support your summary prices in Section B. You should adjust the sections in your proposal accordingly.
69. Spec. section 01355-5, 1.8A notes “The contractor shall provide unarmed guards at the project site after construction hours.”, however note #4 on drawing C1.04 indicates that a guard shall be at the security gate at all times. Please clarify the hours and days in which a guard shall be on-site.
69. Suggest the guard be on site any time there is work being done at the site at the contractors option to secure the site.
The government takes no responsibility for the security of site.
70. The civil drawings show a concrete steam trench. Is it to be cast in place or pre cast? We need steel reinforcement requirements
70. Trench may be precast or cast-in-place and will require reinforcing bars. Provide 300 mm thick concrete with #13 bars at 200 mm o.c., each face. Provide a continuous dumbbell type water stop at cold joints between the bottom and side walls. Provide lifting inserts for concrete top and water seal between concrete top and the side walls.
71. Could you confirm if NIH will hire CxA directly, or GC should hire CxA? Spec section 01810 "General Commissioning Requirements" page 01810-2 reads "Owner will engage the CxA under a separate contract". But the original rfp at https://www.fbo.gov/index?s=opportunity&mode=for m&id=6b43b8cfd3c63a77671c9858bff04964&tab=core&_ cview=1 states "The Contractor will obtain and provide the services of a professional Commissioning Firm."
71. Should be independent and paid for by the owner
72. Does this project involve any safety or solar window film?
72. Yes. See New Section 08871 – Privacy Film.
73. On page 71, the RFP lists Section VII – Technical 73. See #68 above.
https://www.fbo.gov/index?s=opportunity&mode=form&id=6b43b8cfd3c63a77671c9858bff04964&tab=core&_cview=1� https://www.fbo.gov/index?s=opportunity&mode=form&id=6b43b8cfd3c63a77671c9858bff04964&tab=core&_cview=1� https://www.fbo.gov/index?s=opportunity&mode=form&id=6b43b8cfd3c63a77671c9858bff04964&tab=core&_cview=1�
Summary Cost Form (Section J); however, this form is not included in Section J, nor is it included in the technical proposal instructions that begin on page 77. Is it required?
74. The business proposal instructions starting on page 79 do not match the list of tabs for the business proposal as listed on page 71. Should the business proposal follow the outline presented on page 71, or should it follow the instructions that begin on page 79?
74. Page 71 provides recommended format to allow ease of evaluation; page 79 provides recommended on some of the information to include as part of your business proposal but doesn’t say specifically where to put the information.
75. What is supposed to be included in Section VIII:
Other Attachments and Supporting Information of the business proposal? Is it supposed to include the information that begins on page 79?
75. Section VIII should contain information that doesn’t logically fit in any other section. See #74 above.
76. Item 5, Qualifications of the Offeror, as stated on page 83 of the RFP repeats much of the information requested in the technical proposal.
Please confirm that the offeror should include this in the business proposal.
76. This item actually help to clarify/enhance the technical proposal instructions. See Section M beginning on page 84 on what we will evaluate.
77. Will temporary power and water be required? 77. Refer to Spec Section 01500 - "TEMPORARY FACILITIES AND CONTROLS" Part 1-B
78. The Division 16 specifications do not appear to contain a Panelboards section. Manufacturer's reps requested that section when we send them riser diagrams, panel schedules, specs, etc. Will a Panelboard specification section be provided?
78. Refer to new Specification SECTION 16442 "PANELBOARDS" attached.
79. The fixture type 9 inside the building I believe is marked incorrectly. These fixtures should be marked 9A which have a battery backup. Please
79. The fixtures indicated as fixture No.9 on the interior of the building are actually “Unit Equipment”. They should have been listed as Fixture Type “9B”. The following confirm. manufacturers with associated catalogue numbers are acceptable as Fixture Type “9B “for this project:
a) Lithonia – #ELM1254-H20120N0SD – 120/277V
b) Dual-Lite - #CVEC50N-12-I-V-120/277V
c) Lightolier – #EN-2-50N-H20F-W-SD2-120/277V
80. Both Schedule of Charges For The Basic Award and Attachment 6 - Pricing Schedule do not have columns for equipment costs…only labor and material, then the total. Since equipment costs can be significant for specific trades, in which column should we include the equipment costs, either labor or material?
80. Note that Attachment 6 has been removed; and that we recommend that you provide information to support your unit pricing including material, labor and sub-contractor pricing.
81. The Cost Breakdown Items Legend on drawing A0.00 includes item CB25, but this item does not appear on Table B-2 (page 8 of solicitation) the Price Breakdown Sheet.
Please clarify.
81. It seems CB25 was mistakenly left off the list. This item should be added in your proposal. Additionally, items that that are on A0.00 and not included in Section B should also be included in your pricing.
Provide CB #25 as indicated in Section 01222 "Cost Breakdown" 2Y. Refer to Security (SE) Drawings and Spec Section 13700 "Electronic Security Systems".
82. A8.03- Note 12 implies that the entire dormers are to be removed. Is this accurate or do we replace only the rotten wood as needed?
82. See SECTION 06450 - "EXTERIOR ARCHITECTURAL
WOODWORK AND RESTORATION", PART 1.2A
HISTORIC BUILDING LIMITATIONS"( section reference does not absolve contractor from reviewing all construction documents to define scope of work.
83. For the Technical Evaluation is it acceptable for a small 8a firm teaming with a large firm using a team agreement, to use large firms Past Performance information, relevant experience, key personnel while understanding that the small 8a firm has to perform at least 15% of the work?
83. We will evaluate your technical proposal based on the prime and sub’s relevant projects.
84. SF1442 states 502 calendar days from NTP;
Article F.3 Time of Delivery (page 18) states 540 days after date of contract award. Is this consistent?
84. See #13
85. Attachment 1 – Packing and Delivery of Proposals: States the number of copies to be submitted for the Technical and Business Proposals are: “original and 4 copies” whereas the SF1442 and Solicitation state requires to be an original and 5 copies of each. Which is correct?
85. Provide one original and 4 copies of your technical proposal and 1 original and 1 copy of your business proposal.
86. Attachment 2 – Proposal Intent Response Form:
There is no date specified for returning the form.
86. Provide at your earliest convenience. This gives us an idea of how may proposals to expect.
87. Attachment 4 – Summary of Related Activities: Is this to be completed and submitted with the Technical and Business Proposal and if so, where is it to be included?
87. Technical proposal -- See Section J for the appropriate section to include each attachment.
88. Attachment 5 – Proposal Summary and Data Record: Parts of this form do not seem relevant to this solicitation - i.e., name/title, social security number, estimated hours weekly, and telephone number of Principal Investigator and co-investigator plus question regards experiments with human subjects. Please advise.
88. Put information that is relevant to the project and disregard information that is not relevant (i.e., SSN)
89. Attachment 8 – Offeror’s Points of Contact: The names, titles, etc. of a Business Representative and Principal Investigator do not seem relevant to this contract. Please clarify.
89. Substitute Principal Investigator with Project Manager.
90. Attachment 9 – Certificate of Current Cost or Pricing Data: Is this to be completed and submitted with the Business Proposal and if so, is it to be included in SECTION VIII: Other
90. No, not at this time. We do not require certified cost or pricing date when there is adequate competition; however, future change to the contract causing the price to increase/decrease by more that $650K the selected
Attachments and Supporting information? contract will need to execute the Certificate of Current Cost or Pricing Data.
91. Attachment 11 – Disclosure of Lobbying Activities:
Is this to be completed and submitted with the Business Proposal and if so, is it to be included in SECTION VIII: Other Attachments and Supporting information?
91. Yes
92. Submission of Electronic Funds Transfer Information (page 82) WITH the offer seems premature. Please confirm this is indeed required to be submitted with our Business Proposal, and if so, in what section.
92. You do not need to provide this information IAW FAR 52.232-38 since we pull the selected contractor’s information via CCR into the resulting contract. You CCR account must be current (i.e., banking information) at the time you submit your proposal and must remain current throughout the contract performance period.
93. Qualifications of the Offeror (page 83) is similar to information requested in the Technical Proposal Factors 1 and 2 with the addition of questions regarding contract value and schedule performance. Please advise your intent is that we provide this information for the same projects identified in the Technical Proposal. In what section of the Business Proposal is this information to be placed?
93. See #74
94. Subcontractors (page 83): As a General Contractor, we plan to subcontract a large percentage of the work. Please advise guidelines as to the level of subcontractor commitment desired to be included in our proposal. Also, in what section of the Business Proposal are subcontractor commitment letters from to be placed?
94. Since this pertains to your management plan it is assumed that the commitments letter and team make-up should be included under this tab. It is recommended that you provide enough information to support you organization chart.
95. Travel Policy: (page 83): In what section of the
Business Proposal is the written corporate travel policy to be placed?
95. See #75
96. In the Solicitation Section L.1.e Pre-Proposal Conference, the 4th paragraph states that written questions may be sent thru noon 04/09/2010. At the Pre-Bid Meeting held March 24, 2010, the handout lists the cutoff date for questions as March 29, 2010. Please advise.
96. See Amendment #000001.
97. Are windows Historic ? and therefore, Brick Mold, Sill Profile, and Sash Rails and Muntins must match exactly?
97. No... Refer to window requirements indicated in Section 08550. ( referred section does not absolve contractor for reviewing construction documents to define scope of work.
98. Are screens required? Half or full? 98. It is assumed this comment refers to screens for the wood windows. If so screens are not required.
99. Is mfg. standard Hardware required? 99. See Section 08550, Paragraph 2.5 F.
100. Is mfg standard paint color acceptable? Must we match existing historic color?
100. See Section 08550, Paragraph 2.6 B.1.
101. Are cheapest grilles/muntins OK or SDL or GBG required (muntins both inside and outside an between the glass?) or just grilles on the outside of the windows?
101. See Section 08550, Paragraph 2.5F..
102. Must both sash operate? 102. See Section 08550, Paragraph 2.1 A.1.
103. Is blocking required at jambs? If so, what type (Treated or fire treated). Must the entire original window be demolished back to the brick or can we install a new cartridge window into the existing window frame and cover same with aluminum trim?
103. See Sections 06100 and 08550.
104. S-3.01 Indicates Sec.12/ S3.14. (Cut @ Fire
Pump Room). Sheet does not exist
104. Section cut 12/S3.14 on sheet S3.01 should read
12/S4.14. If it helps, detail 12/S4.14 is labeled “Fire Pump Room Wall Section”.
105. Locate Overhead Door on plans 105. Overhead doors are not in the project
106. What is the different between Mail boxes & mail slots
106. There is no difference between mail boxes and slots
107. Can breakouts be turned in at a later time?
Within 24 Hrs?
107. No … needed as part of the bid evaluation
108. Spec. or Model # for Knox Box 108. See New Spec SECTION - 10410 "EMERGENCY
BUILDING ACCESS CABINETS"
109. Spec. for shelf at Janitor closets. Wood, Wire, Manufactured
109. See Drawings for accessory schedule. Otherwise see Section 06410.
110. Provide spec for skylights 110. See New SECTION 08630 - METAL-FRAMED
SKYLIGHTS
111. Provide spec. for coat rack. 111. Coat rack is not required
112. A.703 General note #1 indicates see A.7.01 for detail.
No detail cut thru plan.
112. General note should be changed to indicate A3.03 instead of A7.01
113. A 7.03 & A5.43 - Are eave details for the same building?
113. Sheet A7.03 to be deleted
114. In spec. 06410-16 & 17 indicates under counter refrigerator and misc specialties. Are they required and what is the location?
114. Under counter refrigerators are not required.
115. 07540-7 2.06. Locate roof walkway pads if pads required.
115. Roof walkway pads are not required
116. Section 01810.2 1.5 132 Indicate Owner will engage CxA under a separate contract.
Page 14 of the Solicitation item 5.4 Commissioning Services obtained by Contractor.
Which is correct
116. Cost for commissioning shall be borne by the contractor that will be overseen/managed by the A/E. Provide separate cost breakout for this item. Refer to response 145.
117. Spec. 07620-6: references manufactured roof expansion, are they required and if so where there is no spec section.
117. Manufactured roof expansion joints are not required in project
118. Spec. 07820-1: reference roof specialties & roof accessories there is no spec. Are they required and where?
118. Roof specialties are not required
119. 07811-6 2.3,. Locate where intumescent coatings required
119. Intumescent coatings are not required. Refer to response #135
120. Spec 14210-4 1.2E. Does this paragraph apply to apply to Manufactures Listed. Kone, Otis, &
120. See Section 01600, Paragraph 2.1 E;
Schindler. Are they considered Substitutions?
121. Sheet M2.04 Drawing Note 22-HVAC
Ductwork. Detail 2/A4.12 referenced appears not to be a correct section.
121. Detail-2/A4.12 has been moved to A5.28. Dimensions should be as indicated in Note 22 on M2.04.
122. Sheet A5.25 Sidewall grilles shown as Stainless Steel. Window sill grilles shown as Stainless Steel Are there any other Stainless Steel Registers, grilles, & Diffusers. Sheet M6.01- Diffuser, Registers, & Grilles schedule indicates ALL to be Baked Enamel Finishes.
No references to Stainless Steel in this schedule. What is correct?
122. Note-6 on M6.01- Diffuser, Registers, & Grilles schedule should read "Anodic baked white finish unless otherwise noted". Architectural drawings shall supersede this schedule for finishes.
123. The windows as currently installed have 4" glazed block surrounding them. In order to secure the windows to the blast standard are we to assume thatb we should remove the glazed block and install treated lumber blocking lagg bolted to the existing brick.
123. Blast resistant windows are not required. Refer to construction documents and specifications
124. Drawing M-209 steam and condensate are shown to connecting to existing within the building – a site inspection revealed that the existing piping is in poor condition to connect to.
124. Refer to C1.04 and work related to Alternate #6 as indicated in the contract documents.
125. Please explain the meaning of plumbing breakdown item CB20 “.05% fulltime occupancy …..”
125. This refers to the formula, or requirement, required by USBGC for the pursuit of the sustainable site credit 4.2 - "alternative transportation." Full time equivalent occupants or "FTE" for the purposes of LEED is based on the ratio of occupants that work 8 hours a day. The FTE result for bldg 3 is 212 people and requires providing two showers to satisfy the credit. Refer to DWG A3.02 for work identified as CB-20 related to showers.
126. Are breakdown items to be included in the base bid?
126. Provide CB items on separated form by each item for separate evaluation by the government. The CB items are not to be included in the base price.
127. Ref: Sheet A3.07.
This drawing indicates an enlarged view of Womens Rm. #5W24 And Mens Rm #5W27 To be shown on 3/A5.30. This detail 3/A5.30 shows a railing that is unrelated to the two restrooms. Please clarify if the enlarged drawings exist and where they are located.
127. Detail reference is to be changed from 3/A5.30 to 3/A5.50
128. Ref: Sheet A5.50 Toilet Room Plans, Elevations, Details.
These elevations show the restrooms with ceramic wall tile at full-height throughout the rooms. However, the Finish Schedule lists the wall finishes for in these rooms with paint and ceramic tile in these areas. Please clarify the extent of the ceramic tile in these rooms.
128. Full height ceramic tile is to be provided at restroom walls as indicated. Paint is not to be provided.
129. Ref: Sheet A9.01/9.02 Finish Schedule.
Rooms #BW05A, #BW05B, #3E12 are shown in the Finish Schedule but not on the Floor Plans. Please clarify the existence and locations of these rooms in the project.
129. Rooms #BW05A, #BW05B, and #3E12 are not included in the project.
130. Ref: Spec. 09653 – Vinyl Corner Guards are listed in section 09653, but are not shown in the drawings. Please clarify the location and extent of Vinyl Corner Guards in this project.
130. Vinyl corner guards are not required in project
131. Ref: Spec. 09900 – Paint designations P-1
Through P-5 are shown on the finish schedule but are not listed in Specification 09900.
131. Color designations P-1 through P-5 as designated on the drawings are based on manufacturers listed in the Material Legend. These designations identify color only and do not determine which paint systems are used at each location, substrate, or application. See Paint Schedule in Section 09900 for paint systems to be used at substrates and applications. Provide paint systems using colors scheduled in Material Legend and Finish Schedule.
132. Ref: DETAIL 5/A8.09. Please provide the location of the existing wood framing and the location of the double layer of fire-rated drywall required for this project.
132. Double layer of fire rated gypsum board is not required in the project
133. I am inquiring about the NIH Building 3 Bid due on April 12th. Is furniture included as part of the bid package? If furniture is not included in this bid please advise how the furniture will be procured for this project.
133.
134. I am interested in submitting RFI questions for this project. Is there a specific form or just E-mail you the questions? They are related to the specification in which the architect has listed two products for bidding, problem neither of them are manufactured any longer.
134. The questions and answers session closed 3/29/2010.
You can send your question but we cannot guarantee responses.
135. In section 07811 item 2.3 Exposed Intumescent Mastic Fire-resistive Coatings. The listed Intumescent products are no longer manufactures, are sub-contractors able to bid other standard industry standard Intumescent products (since there are no ASTM requirements listed)?
135. Intumescent fireproofing has been deleted from the project. All firestopping must comply with and have certification under FMG-4491.
There is a fire resistive joint section on the ORS website http://orf.od.nih.gov/NR/rdonlyres/0C4FDC46-6B54- 463F-A203-http://orf.od.nih.gov/NR/rdonlyres/0C4FDC46-6B54-463F-A203-401D5F4740B0/14374/078413firestoppingDFMmetricizedversion1.pdf� http://orf.od.nih.gov/NR/rdonlyres/0C4FDC46-6B54-463F-A203-401D5F4740B0/14374/078413firestoppingDFMmetricizedversion1.pdf�
401D5F4740B0/14374/078413firestoppingDFMmetricize dversion1.pdf
136. In section 07811 item 2.1 subsection A, 1.
Indicates that Dry-mix fireproofing is not permitted, but this product meets/exceeds the intent of the specification. Are subcontractor's not able to bid a product that carries an International Code Council (IBC) approval, showing that it meets all code criteria?
Item 2.1 subsection C.3 indicates a required bond strength of 300 psf.
GSA and AIA industry requirements are listed at 150 psf. Will bidders be held to a random bond strength requirement chosen by the Architect?
136. Exclusion of dry mix fireproofing is per NIH Fire Marshal directives. Use of dry-mix fireproofing as defined is not permitted.
d) Unless…