RENOVATION OF BUILDING # 3 WR#HQC 90298
NIH, BETHESDA, MARYLAND WFT#09033.NIH.A
PANELBOARDS 16442-1
BID SET JANUARY 08, 2010
SECTION 16442 - PANELBOARDS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Distribution panelboards.
2. Lighting and appliance branch-circuit panelboards.
1.3 SUBMITTALS
A. Product Data: For each type of panelboard, switching and over-current protective device, transient voltage suppression device, accessory, and component indicated. Include dimensions and manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes. Coordinate final submittal with Specification Section 16055, Over-current Protection Device Coordination results and recommendations.
B. Shop Drawings: For each panelboard and related equipment.
1. Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings.
2. Detail enclosure types and details for types other than NEMA 250, Type 1.
3. Detail bus configuration, current, and voltage ratings.
4. Short-circuit current rating of panelboards and over-current protective devices.
5. Include evidence of NRTL listing for series rating of installed devices.
6. Detail features, characteristics, ratings, and factory settings of individual over-current protective devices and auxiliary components.
7. Include wiring diagrams for power, signal, and control wiring.
8. Include time-current coordination curves for each type and rating of over-current protective device included in panelboards. Submit on translucent log-log graft paper;
include selectable ranges for each type of over-current protective device.
C. Qualification Data: For qualified testing agency.
D. Field Quality-Control Reports:
PANELBOARDS 16442-2
1. Test procedures used.
2. Test results that comply with requirements.
3. Results of failed tests and corrective action taken to achieve test results that comply with requirements.
E. Panelboard Schedules: For installation in panelboards. Submit final type-written versions after load balancing.
F. Operation and Maintenance Data: For panelboards and components to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:
1. Manufacturer's written instructions for testing and adjusting over-current protective devices.
2. Time-current curves, including selectable ranges for each type of over-current protective device that allows adjustments.
1.4 QUALITY ASSURANCE
A. Testing Agency Qualifications: Member company of NETA or an NRTL.
1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.
B. Source Limitations: Obtain panelboards, over-current protective devices, components, and accessories from single source from single manufacturer.
C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for panelboards including clearances between panelboards and adjacent surfaces and other items.
Comply with indicated maximum dimensions.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
E. Comply with NEMA PB 1.
F. Comply with NFPA 70.
1.5 DELIVERY, STORAGE, AND HANDLING
A. Remove loose packing and flammable materials from inside panelboards; install temporary electric heating (250 W per panelboard) to prevent condensation.
B. Handle and prepare panelboards for installation according to NECA 407.
PANELBOARDS 16442-3
1.6 PROJECT CONDITIONS
A. Environmental Limitations:
1. Do not deliver or install panelboards until spaces are enclosed and weather-tight, wet work in spaces is complete and dry, work above panelboards is complete, and temporary HVAC system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.
2. Rate equipment for continuous operation under the following conditions unless otherwise indicated:
a. Ambient Temperature: Not exceeding minus 22 deg F to plus 104 deg F.
b. Altitude: Not exceeding 6600 feet.
B. Service Conditions: NEMA PB 1, usual service conditions, as follows:
1. Ambient temperatures within limits specified.
2. Altitude not exceeding 6600 feet.
C. Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities occupied by NIH unless permitted under the following conditions and only after arranging to provide temporary electric service according to requirements indicated:
1. Notify NIH Contracting Officer no fewer than 15 days in advance of proposed interruption of electric service .
2. Do not proceed with interruption of electric service without NIH Contracting Officer’s written permission.
3. Comply with NFPA 70E.
1.7 COORDINATION
A. Coordinate layout and installation of panelboards and components with other construction that penetrates walls or is supported by them, including electrical and other types of equipment, raceways, piping, encumbrances to workspace clearance requirements, and adjacent surfaces.
Maintain required workspace clearances and required clearances for equipment access doors and panels.
B. Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 3.
1.8 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace transient voltage suppression devices that fail in materials or workmanship within specified warranty period.
PANELBOARDS 16442-4
1. Warranty Period: Five years from date of Substantial Completion.
1.9 EXTRA MATERIALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Keys: Two spares for each type of panelboard cabinet lock.
2. Circuit Breakers Including GFCI and Ground Fault Equipment Protection (GFEP) Types:
Two spares for each panelboard.
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS FOR PANELBOARDS
A. Fabricate and test panelboards according to IEEE 344 to withstand seismic forces defined in Division 16 Section "Vibration and Seismic Controls for Electrical Systems."
B. Enclosures: Surface-mounted cabinets.
1. Rated for environmental conditions at installed location.
a. Indoor Dry and Clean Locations: NEMA 250, Type 1.
b. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive
Liquids: NEMA 250, Type 5.
2. Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match box dimensions; for flush-mounted fronts, overlap box.
3. Hinged Front Cover: Entire front trim hinged to box and with standard door within hinged trim cover.
4. Skirt for Surface-Mounted Panelboards: Same gage and finish as panelboard front with flanges for attachment to panelboard, wall, and ceiling or floor.
5. Gutter Extension and Barrier: Same gage and finish as panelboard enclosure; integral with enclosure body. Arrange to isolate individual panel sections.
6. Finishes:
a. Panels and Trim: Steel and galvanized steel, factory finished immediately after cleaning and pre-treating with manufacturer's standard two-coat, baked-on finish consisting of prime coat and thermosetting topcoat.
b. Back Boxes: Galvanized steel.
c. Fungus Proofing: Permanent fungicidal treatment for over-current protective devices and other components.
7. Directory Card: Inside panelboard door, mounted in metal frame with transparent protective cover.
PANELBOARDS 16442-5
C. Incoming Mains Location: Top and bottom.
D. Phase, Neutral, and Ground Buses:
1. Material: Hard-drawn copper, 98 percent conductivity.
2. Equipment Ground Bus: Adequate for feeder and branch-circuit equipment grounding conductors; bonded to box.
3. Isolated Ground Bus: Adequate for branch-circuit isolated ground conductors; insulated from box.
4. Extra-Capacity Neutral Bus: Neutral bus rated 200 percent of phase bus and UL listed as suitable for nonlinear loads.
5. Split Bus: Vertical buses divided into individual vertical sections.
E. Conductor Connectors: Suitable for use with conductor material and sizes.
1. Material: Hard-drawn copper, 98 percent conductivity.
2. Main and Neutral Lugs: Compression type.
3. Ground Lugs and Bus-Configured Terminators: Compression type.
4. Feed-Through Lugs: Compression type, suitable for use with conductor material. Locate at opposite end of bus from incoming lugs or main device.
5. Sub-feed (Double) Lugs: Compression type suitable for use with conductor material.
Locate at same end of bus as incoming lugs or main device.
6. Gutter-Tap Lugs: Compression type suitable for use with conductor material. Locate at same end of bus as incoming lugs or main device.
7. Extra-Capacity Neutral Lugs: Rated 200 percent of phase lugs mounted on extra-capacity neutral bus.
F. Service Equipment Label: NRTL labeled for use as service equipment for panelboards with one or more main service disconnecting and over-current protective devices.
G. Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices.
H. Panelboard Short-Circuit Current Rating: Fully rated to interrupt symmetrical short-circuit current available at terminals.
2.2 DISTRIBUTION PANELBOARDS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Eaton Electrical Inc.; Cutler-Hammer Business Unit.
2. General Electric Company; GE Consumer & Industrial - Electrical Distribution.
3. Siemens Energy & Automation, Inc.
B. Panelboards: NEMA PB 1, power and feeder distribution type.
PANELBOARDS 16442-6
C. Doors: Secured with vault-type latch with tumbler lock; keyed alike.
1. For doors more than 36 inches high, provide two latches, keyed alike.
D. Mains: Circuit breaker and Lugs only.
E. Branch Over-current Protective Devices for Circuit-Breaker Frame Sizes 125 A and Smaller:
Bolt-on circuit breakers.
F. Branch Over-current Protective Devices for Circuit-Breaker Frame Sizes Larger Than 125 A:
Bolt-on circuit breakers; plug-in circuit breakers where individual positive-locking device requires mechanical release for removal.
G. Branch Over-current Protective Devices: Fused switches.
H. Contactors in Main Bus: NEMA ICS 2, Class A, mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard.
1. Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection.
2. External Control-Power Source: 120-V branch circuit.
2.3 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Eaton Electrical Inc.; Cutler-Hammer Business Unit.
2. General Electric Company; GE Consumer & Industrial - Electrical Distribution.
3. Siemens Energy & Automation, Inc.
4. Square D; a brand of Schneider Electric.
B. Panelboards: NEMA PB 1, lighting and appliance branch-circuit type.
C. Mains: Circuit breaker or lugs only.
D. Branch Over-current Protective Devices: Bolt-on circuit breakers, replaceable without disturbing adjacent units.
E. Contactors in Main Bus: NEMA ICS 2, Class A, mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard.
1. Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection.
2. External Control-Power Source: 120-V branch circuit
F. Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.
PANELBOARDS 16442-7
G. Column-Type Panelboards: Narrow gutter extension, with cover, to overhead junction box equipped with ground and neutral terminal buses.
2.4 DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Eaton Electrical Inc.; Cutler-Hammer Business Unit.
2. General Electric Company; GE Consumer & Industrial - Electrical Distribution.
3. Siemens Energy & Automation, Inc.
4. Square D; a brand of Schneider Electric.
B. Molded-Case Circuit Breaker (MCCB): Comply with UL 489, with interrupting capacity to meet available fault currents.
1. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger.
2. Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with front-mounted, field-adjustable trip setting.
3. Electronic trip circuit breakers with rms sensing; field-replaceable rating plug or field-replicable electronic trip; and the following field-adjustable settings:
a. Instantaneous trip.
b. Long- and short-time pickup levels.
c. Long- and short-time time adjustments.
d. Ground-fault pickup level, time delay, and I2t response.
4. Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller; let-through ratings less than NEMA FU 1, RK-5.
5. GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault protection (6-mA trip).
6. Ground-Fault Equipment Protection (GFEP) Circuit Breakers: Class B ground-fault protection (30-mA trip).
7. Arc-Fault Circuit Interrupter (AFCI) Circuit Breakers: Comply with UL 1699; 120/240- V, single-pole configuration.
8. Molded-Case Circuit-Breaker (MCCB) Features and Accessories:
a. Standard frame sizes, trip ratings, and number of poles.
b. Lugs: Compression style, suitable for number, size, trip ratings, and conductor materials.
c. Application Listing: Appropriate for application; Type SWD for switching fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity discharge (HID) lighting circuits.
d. Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable pickup and time-delay settings, push-to-test feature, and ground-fault indicator.
PANELBOARDS 16442-8
e. Communication Capability: Circuit-breaker-mounted communication module with functions and features compatible with power monitoring and control system specified in Division 16 Section "Electrical Power Monitoring and Control."
f. Shunt Trip: 120-V trip coil energized from separate circuit, set to trip at 55 percent of rated voltage.
g. Under-voltage Trip: Set to operate at 35 to 75 percent of rated voltage with field-adjustable 0.1- to 0.6-second time delay.
h. Auxiliary Contacts: Two SPDT switches with "a" and "b" contacts; "a" contacts mimic circuit-breaker contacts and "b" contacts operate in reverse of circuit-breaker contacts.
i. Alarm Switch: Single-pole, normally open contact that actuates only when circuit breaker trips.
j. Key Interlock Kit: Externally mounted to prohibit circuit-breaker operation; key shall be removable only when circuit breaker is in off position.
k. Zone-Selective Interlocking: Integral with electronic trip unit; for interlocking ground-fault protection function with other upstream or downstream devices.
l. Multi-pole units enclosed in a single housing or factory assembled to operate as a single unit.
m. Handle Padlocking Device: Fixed attachment for locking circuit-breaker handle in on or off position.
n. Handle Clamp: Loose attachment for holding circuit-breaker handle in on position.
2.5 ACCESSORY COMPONENTS AND FEATURES
A. Accessory Set: Include tools and miscellaneous items required for over-current protective device test, inspection, maintenance, and operation.
B. Portable Test Set: For testing functions of solid-state trip devices without removing from panelboard. Include relay and meter test plugs suitable for testing panelboard meters and switchboard class relays.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Receive, inspect, handle, and store panelboards according to NECA 407.
B. Examine panelboards before installation. Reject panelboards that are damaged or rusted or have been subjected to water saturation.
C. Examine elements and surfaces to receive panelboards for compliance with installation tolerances and other conditions affecting performance of the Work.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
PANELBOARDS 16442-9
3.2 INSTALLATION
A. Install panelboards and accessories according to NECA 407.
B. Equipment Mounting: Install panelboards on concrete bases, 4-inch nominal thickness.
Comply with requirements for concrete base specified in Division 3.
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around full perimeter of base.
2. For panelboards, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to panelboards.
5. Attach panelboard to the vertical finished or structural surface behind the panelboard.
C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from panelboards.
D. Comply with mounting and anchoring requirements specified in Division 16 Section "Vibration and Seismic Controls for Electrical Systems."
E. Mount top of trim 90 inches above finished floor unless otherwise indicated.
F. Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with fronts uniformly flush with wall finish and mating with back box.
G. Install over-current protective devices and controllers not already factory installed.
1. Set field-adjustable, circuit-breaker trip ranges.
H. Install filler plates in unused spaces.
I. Stub four 1-inch empty conduits from panelboard into accessible ceiling space or space designated to be ceiling space in the future. Stub four 1-inch empty conduits into raised floor space or below slab not on grade.
J. Arrange conductors in gutters into groups and bundle and wrap with wire ties after completing load balancing.
K. Comply with NECA 1.
3.3 IDENTIFICATION
A. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs complying with Division 16 Section "Electrical Identification."
PANELBOARDS 16442-10
B. Create a directory to indicate installed circuit loads after balancing panelboard loads;
incorporate Owner's final room designations. Obtain approval before installing. Use a computer or typewriter to create directory; handwritten directories are not acceptable.
C. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 16 Section "Electrical Identification."
D. Device Nameplates: Label each branch circuit device in distribution panelboards with a nameplate complying with requirements for identification specified in Division 16 Section "Electrical Identification."
3.4 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
C. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
D. Acceptance Testing Preparation:
1. Test insulation resistance for each panelboard bus, component, connecting supply, feeder, and control circuit.
2. Test continuity of each circuit.
E. Tests and Inspections:
1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.
2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.
F. Panelboards will be considered defective if they do not pass tests and inspections.
G. Prepare test and inspection reports, including a certified report that identifies panelboards included and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.
PANELBOARDS 16442-11
3.5 ADJUSTING
A. Adjust moving parts and operable component to function smoothly, and lubricate as recommended by manufacturer.
B. Set field-adjustable circuit-breaker trip ranges as indicated.
C. Load Balancing: After Substantial Completion, but not more than 60 days after Final Acceptance, measure load balancing and make circuit changes.
1. Measure as directed during period of normal system loading.
2. Perform load-balancing circuit changes outside normal occupancy/working schedule of the facility and at time directed. Avoid disrupting critical 24-hour services such as fax machines and on-line data processing, computing, transmitting, and receiving equipment.
3. After circuit changes, recheck loads during normal load period. Record all load readings before and after changes and submit test records.
4. Tolerance: Difference exceeding 20 percent between phase loads, within a panelboard, is not acceptable. Rebalance and recheck as necessary to meet this minimum requirement.
3.6 PROTECTION
A. Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions.
END OF SECTION 16442
| GENERAL |
| RELATED DOCUMENTS |
| Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. |
| SUMMARY |
| Section Includes: |
| Distribution panelboards. |
| Lighting and appliance branch-circuit panelboards. |
| SUBMITTALS |
| Product Data: For each type of panelboard, switching and over-current protective device, transient voltage suppression device, accessory, and component indicated. Include dimensions and manufacturers' technical data on features, performance, electri... |
| Shop Drawings: For each panelboard and related equipment. |
| Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings. |
| Detail enclosure types and details for types other than NEMA 250, Type 1. |
| Detail bus configuration, current, and voltage ratings. |
| Short-circuit current rating of panelboards and over-current protective devices. |
| Include evidence of NRTL listing for series rating of installed devices. |
| Detail features, characteristics, ratings, and factory settings of individual over-current protective devices and auxiliary components. |
| Include wiring diagrams for power, signal, and control wiring. |
| Include time-current coordination curves for each type and rating of over-current protective device included in panelboards. Submit on translucent log-log graft paper; include selectable ranges for each type of over-current protective device. |
| Qualification Data: For qualified testing agency. |
| Field Quality-Control Reports: |
| Test procedures used. |
| Test results that comply with requirements. |
| Results of failed tests and corrective action taken to achieve test results that comply with requirements. |
| Panelboard Schedules: For installation in panelboards. Submit final type-written versions after load balancing. |
| Operation and Maintenance Data: For panelboards and components to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following: |
| Manufacturer's written instructions for testing and adjusting over-current protective devices. |
| Time-current curves, including selectable ranges for each type of over-current protective device that allows adjustments. |
| QUALITY ASSURANCE |
| Testing Agency Qualifications: Member company of NETA or an NRTL. |
| Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing. |
| Source Limitations: Obtain panelboards, over-current protective devices, components, and accessories from single source from single manufacturer. |
| Product Selection for Restricted Space: Drawings indicate maximum dimensions for panelboards including clearances between panelboards and adjacent surfaces and other items. Comply with indicated maximum dimensions. |
| Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. |
| Comply with NEMA PB 1. |
| Comply with NFPA 70. |
| DELIVERY, STORAGE, AND HANDLING |
| Remove loose packing and flammable materials from inside panelboards; install temporary electric heating (250 W per panelboard) to prevent condensation. |
| Handle and prepare panelboards for installation according to NECA 407. |
| PROJECT CONDITIONS |
| Environmental Limitations: |
| Do not deliver or install panelboards until spaces are enclosed and weather-tight, wet work in spaces is complete and dry, work above panelboards is complete, and temporary HVAC system is operating and maintaining ambient temperature and humidity cond... |
| Rate equipment for continuous operation under the following conditions unless otherwise indicated: |
| Ambient Temperature: Not exceeding minus 22 deg F to plus 104 deg F. |
| Altitude: Not exceeding 6600 feet. |
| Service Conditions: NEMA PB 1, usual service conditions, as follows: |
| Ambient temperatures within limits specified. |
| Altitude not exceeding 6600 feet. |
| Interruption of Existing Electrical Service: Do not interrupt electrical service to facilities occupied by NIH unless permitted under the following conditions and only after arranging to provide temporary electric service according to requirements ind... |
| Notify NIH Contracting Officer no fewer than 15 days in advance of proposed interruption of electric service . |
| Do not proceed with interruption of electric service without NIH Contracting Officer’s written permission. |
| Comply with NFPA 70E. |
| COORDINATION |
| Coordinate layout and installation of panelboards and components with other construction that penetrates walls or is supported by them, including electrical and other types of equipment, raceways, piping, encumbrances to workspace clearance requiremen... |
| Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 3. |
| WARRANTY |
| Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace transient voltage suppression devices that fail in materials or workmanship within specified warranty period. |
| Warranty Period: Five years from date of Substantial Completion. |
| EXTRA MATERIALS |
| Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| Keys: Two spares for each type of panelboard cabinet lock. |
| Circuit Breakers Including GFCI and Ground Fault Equipment Protection (GFEP) Types: Two spares for each panelboard. |
| PRODUCTS |
| GENERAL REQUIREMENTS FOR PANELBOARDS |
| Fabricate and test panelboards according to IEEE 344 to withstand seismic forces defined in Division 16 Section "Vibration and Seismic Controls for Electrical Systems." |
| Enclosures: Surface-mounted cabinets. |
| Rated for environmental conditions at installed location. |
| Indoor Dry and Clean Locations: NEMA 250, Type 1. |
| Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive Liquids: NEMA 250, Type 5. |
| Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match box dimensions; for flush-mounted fronts, overlap box. |
| Hinged Front Cover: Entire front trim hinged to box and with standard door within hinged trim cover. |
| Skirt for Surface-Mounted Panelboards: Same gage and finish as panelboard front with flanges for attachment to panelboard, wall, and ceiling or floor. |
| Gutter Extension and Barrier: Same gage and finish as panelboard enclosure; integral with enclosure body. Arrange to isolate individual panel sections. |
| Finishes: |
| Panels and Trim: Steel and galvanized steel, factory finished immediately after cleaning and pre-treating with manufacturer's standard two-coat, baked-on finish consisting of prime coat and thermosetting topcoat. |
| Back Boxes: Galvanized steel. |
| Fungus Proofing: Permanent fungicidal treatment for over-current protective devices and other components. |
Directory Card: Inside panelboard door, mounted in metal frame with transparent protective cover.
| Incoming Mains Location: Top and bottom. |
| Phase, Neutral, and Ground Buses: |
| Material: Hard-drawn copper, 98 percent conductivity. |
| Equipment Ground Bus: Adequate for feeder and branch-circuit equipment grounding conductors; bonded to box. |
| Isolated Ground Bus: Adequate for branch-circuit isolated ground conductors; insulated from box. |
| Extra-Capacity Neutral Bus: Neutral bus rated 200 percent of phase bus and UL listed as suitable for nonlinear loads. |
| Split Bus: Vertical buses divided into individual vertical sections. |
| Conductor Connectors: Suitable for use with conductor material and sizes. |
| Material: Hard-drawn copper, 98 percent conductivity. |
| Main and Neutral Lugs: Compression type. |
| Ground Lugs and Bus-Configured Terminators: Compression type. |
| Feed-Through Lugs: Compression type, suitable for use with conductor material. Locate at opposite end of bus from incoming lugs or main device. |
| Sub-feed (Double) Lugs: Compression type suitable for use with conductor material. Locate at same end of bus as incoming lugs or main device. |
| Gutter-Tap Lugs: Compression type suitable for use with conductor material. Locate at same end of bus as incoming lugs or main device. |
| Extra-Capacity Neutral Lugs: Rated 200 percent of phase lugs mounted on extra-capacity neutral bus. |
| Service Equipment Label: NRTL labeled for use as service equipment for panelboards with one or more main service disconnecting and over-current protective devices. |
| Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices. |
| Panelboard Short-Circuit Current Rating: Fully rated to interrupt symmetrical short-circuit current available at terminals. |
| DISTRIBUTION PANELBOARDS |
| Manufacturers: Subject to compliance with requirements, provide products by one of the following: |
| Eaton Electrical Inc.; Cutler-Hammer Business Unit. |
| General Electric Company; GE Consumer & Industrial - Electrical Distribution. |
| Siemens Energy & Automation, Inc. |
| Panelboards: NEMA PB 1, power and feeder distribution type. |
| Doors: Secured with vault-type latch with tumbler lock; keyed alike. |
| For doors more than 36 inches high, provide two latches, keyed alike. |
| Mains: Circuit breaker and Lugs only. |
| Branch Over-current Protective Devices for Circuit-Breaker Frame Sizes 125 A and Smaller: Bolt-on circuit breakers. |
| Branch Over-current Protective Devices for Circuit-Breaker Frame Sizes Larger Than 125 A: Bolt-on circuit breakers; plug-in circuit breakers where individual positive-locking device requires mechanical release for removal. |
| Branch Over-current Protective Devices: Fused switches. |
| Contactors in Main Bus: NEMA ICS 2, Class A, mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard. |
| Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection. |
| External Control-Power Source: 120-V branch circuit. |
| LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS |
| Manufacturers: Subject to compliance with requirements, provide products by one of the following: |
| Eaton Electrical Inc.; Cutler-Hammer Business Unit. |
| General Electric Company; GE Consumer & Industrial - Electrical Distribution. |
| Siemens Energy & Automation, Inc. |
| Square D; a brand of Schneider Electric. |
| Panelboards: NEMA PB 1, lighting and appliance branch-circuit type. |
| Mains: Circuit breaker or lugs only. |
| Branch Over-current Protective Devices: Bolt-on circuit breakers, replaceable without disturbing adjacent units. |
| Contactors in Main Bus: NEMA ICS 2, Class A, mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard. |
| Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection. |
| External Control-Power Source: 120-V branch circuit |
| Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike. |
| Column-Type Panelboards: Narrow gutter extension, with cover, to overhead junction box equipped with ground and neutral terminal buses. |
| DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES |
| Manufacturers: Subject to compliance with requirements, provide products by one of the following: |
| Eaton Electrical Inc.; Cutler-Hammer Business Unit. |
| General Electric Company; GE Consumer & Industrial - Electrical Distribution. |
| Siemens Energy & Automation, Inc. |
| Square D; a brand of Schneider Electric. |
| Molded-Case Circuit Breaker (MCCB): Comply with UL 489, with interrupting capacity to meet available fault currents. |
| Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger. |
| Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with front-mounted, field-adjustable trip setting. |
| Electronic trip circuit breakers with rms sensing; field-replaceable rating plug or field-replicable electronic trip; and the following field-adjustable settings: |
| Instantaneous trip. |
| Long- and short-time pickup levels. |
| Long- and short-time time adjustments. |
| Ground-fault pickup level, time delay, and I2t response. |
| Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller; let-through ratings less than NEMA FU 1, RK-5. |
| GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault protection (6-mA trip). |
| Ground-Fault Equipment Protection (GFEP) Circuit Breakers: Class B ground-fault protection (30-mA trip). |
| Arc-Fault Circuit Interrupter (AFCI) Circuit Breakers: Comply with UL 1699; 120/240-V, single-pole configuration. |
| Molded-Case Circuit-Breaker (MCCB) Features and Accessories: |
| Standard frame sizes, trip ratings, and number of poles. |
| Lugs: Compression style, suitable for number, size, trip ratings, and conductor materials. |
| Application Listing: Appropriate for application; Type SWD for switching fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity discharge (HID) lighting circuits. |
| Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable pickup and time-delay settings, push-to-test feature, and ground-fault indicator. |
| Communication Capability: Circuit-breaker-mounted communication module with functions and features compatible with power monitoring and control system specified in Division 16 Section "Electrical Power Monitoring and Control." |
| Shunt Trip: 120-V trip coil energized from separate circuit, set to trip at 55 percent of rated voltage. |
| Under-voltage Trip: Set to operate at 35 to 75 percent of rated voltage with field-adjustable 0.1- to 0.6-second time delay. |
| Auxiliary Contacts: Two SPDT switches with "a" and "b" contacts; "a" contacts mimic circuit-breaker contacts and "b" contacts operate in reverse of circuit-breaker contacts. |
| Alarm Switch: Single-pole, normally open contact that actuates only when circuit breaker trips. |
| Key Interlock Kit: Externally mounted to prohibit circuit-breaker operation; key shall be removable only when circuit breaker is in off position. |
| Zone-Selective Interlocking: Integral with electronic trip unit; for interlocking ground-fault protection function with other upstream or downstream devices. |
| Multi-pole units enclosed in a single housing or factory assembled to operate as a single unit. |
| Handle Padlocking Device: Fixed attachment for locking circuit-breaker handle in on or off position. |
| Handle Clamp: Loose attachment for holding circuit-breaker handle in on position. |
| ACCESSORY COMPONENTS AND FEATURES |
| Accessory Set: Include tools and miscellaneous items required for over-current protective device test, inspection, maintenance, and operation. |
| Portable Test Set: For testing functions of solid-state trip devices without removing from panelboard. Include relay and meter test plugs suitable for testing panelboard meters and switchboard class relays. |
| EXECUTION |
| EXAMINATION |
| Receive, inspect, handle, and store panelboards according to NECA 407. |
| Examine panelboards before installation. Reject panelboards that are damaged or rusted or have been subjected to water saturation. |
| Examine elements and surfaces to receive panelboards for compliance with installation tolerances and other conditions affecting performance of the Work. |
| Proceed with installation only after unsatisfactory conditions have been corrected. |
| INSTALLATION |
| Install panelboards and accessories according to NECA 407. |
| Equipment Mounting: Install panelboards on concrete bases, 4-inch nominal thickness. Comply with requirements for concrete base specified in Division 3. |
| Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around full perimeter of base. |
| For panelboards, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor. |
| Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. |
| Install anchor bolts to elevations required for proper attachment to panelboards. |
| Attach panelboard to the vertical finished or structural surface behind the panelboard. |
| Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from panelboards. |
| Comply with mounting and anchoring requirements specified in Division 16 Section "Vibration and Seismic Controls for Electrical Systems." |
| Mount top of trim 90 inches above finished floor unless otherwise indicated. |
| Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with fronts uniformly flush with wall finish and mating with back box. |
| Install over-current protective devices and controllers not already factory installed. |
| Set field-adjustable, circuit-breaker trip ranges. |
| Install filler plates in unused spaces. |
| Stub four 1-inch empty conduits from panelboard into accessible ceiling space or space designated to be ceiling space in the future. Stub four 1-inch empty conduits into raised floor space or below slab not on grade. |
| Arrange conductors in gutters into groups and bundle and wrap with wire ties after completing load balancing. |
| Comply with NECA 1. |
| IDENTIFICATION |
| Identify field-installed conductors, interconnecting wiring, and components; provide warning signs complying with Division 16 Section "Electrical Identification." |
| Create a directory to indicate installed circuit loads after balancing panelboard loads; incorporate Owner's final room designations. Obtain approval before installing. Use a computer or typewriter to create directory; handwritten directories are no... |
| Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 16 Section "Electrical Identification." |
| Device Nameplates: Label each branch circuit device in distribution panelboards with a nameplate complying with requirements for identification specified in Division 16 Section "Electrical Identification." |
| FIELD QUALITY CONTROL |
| Testing Agency: Engage a qualified testing agency to perform tests and inspections. |
| Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. |
| Perform tests and inspections. |
| Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. |
| Acceptance Testing Preparation: |
| Test insulation resistance for each panelboard bus, component, connecting supply, feeder, and control circuit. |
| Test continuity of each circuit. |
| Tests and Inspections: |
| Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters. |
| Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest. |
| Panelboards will be considered defective if they do not pass tests and inspections. |
| Prepare test and inspection reports, including a certified report that identifies panelboards included and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action. |
| ADJUSTING |
| Adjust moving parts and operable component to function smoothly, and lubricate as recommended by manufacturer. |
| Set field-adjustable circuit-breaker trip ranges as indicated. |
| Load Balancing: After Substantial Completion, but not more than 60 days after Final Acceptance, measure load balancing and make circuit changes. |
| Measure as directed during period of normal system loading. |
| Perform load-balancing circuit changes outside normal occupancy/working schedule of the facility and at time directed. Avoid disrupting critical 24-hour services such as fax machines and on-line data processing, computing, transmitting, and receiving... |
| After circuit changes, recheck loads during normal load period. Record all load readings before and after changes and submit test records. |
| Tolerance: Difference exceeding 20 percent between phase loads, within a panelboard, is not acceptable. Rebalance and recheck as necessary to meet this minimum requirement. |
| PROTECTION |
| Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions. |