# Question Answer
I wanted to reach out to you on the “emergency standby power” comment in the bid material. I assume you are requesting pricing for an emergency rental generator at no more than 70%
(1750KW) of the rated 2500KW power, correct?
No need for a rental generator since we have N+3 Redundancy.
Meaning we have 3 other generators that can be used if 1 goes down.
NIAID‐RFQ18‐1914944 ‐ Question and Answer