This document contains details for a federal contract opportunity to provide repair services for a chiller in Londonderry, New Hampshire. The Army Contracting Command - NJ intends to award a firm fixed price contract to replace two existing chillers. Services will include all labor, equipment, materials, supervision, and transportation required. Interested offerors should monitor the beta.sam.gov website for posting of the solicitation number W15QKN-24-R-5031, which will include the statement of work, maps, drawings, and details on a scheduled site visit and response date. The contract is anticipated to be awarded based on lowest pricing technically acceptable. Offerors should check the notice page for any amendments to requirements or timelines.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| NH014-Londonderry-A3-CSS 93937-SOW-Repair Chiller.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
YLAA0058 - YLAA0230
AIR-COOLED SCROLL CHILLERS
WITH BRAZED PLATE HEAT EXCHANGER
STYLE B (60 HZ) 4-10 FAN
55 - 230 TON
195 - 700 KW
R-410A
Issue Date:
December 29, 2017
AIR-COOLED SCROLL CHILLER
INSTALLATION, OPERATION, MAINTENANCE Supersedes: 150.72-ICOM6 (817) Form 150.72-ICOM6 (1217)
Products are produced at a f ac i l i t y whose qua l i t y -management systems are ISO9001 certified.
035-23572-100
JOHNSON CONTROLS2
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
This equipment is a relatively complicated apparatus.
During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain com-ponents or conditions including, but not limited to:
heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage.
Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, instal-lation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
which it is situated, as well as severe personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in-dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.
Indicates a potentially hazardous situa-tion which will result in possible injuries or damage to equipment if proper care is not taken.
Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollu-tion if proper care is not taken or instruc-tions and are not followed.
Highlights additional information useful to the technician in completing the work being performed properly.
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accor-dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn-ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
JOHNSON CONTROLS 3
ISSUE DATE: 12/29/2017
ASSOCIATED LITERATURE
Manual Description Form Number
Start-Up Checklist - Style A and B, 60 Hz 150.72-CL1
Renewal Parts - YLAA0070-YLAA230 Style B 60 Hz 150.72-RP3
Limited Warranty Engineered Systems Equipment 50.05-NM2
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls’ policy for con-tinuous product improvement, the information con-tained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the John-son Controls QuickLIT website at http://cgproducts.
johnsoncontrols.com.
It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rig-ging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller.
CHANGE BARS
Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical in-formation and any other changes in spelling, grammar or formatting are not included.
JOHNSON CONTROLS4
ISSUE DATE: 12/29/2017
NOMENCLATURE
YL A A 0125 H 46 X C B
YL = YORK CHILLER
A = AIR COOLED
S = STANDARD EFFICIENCY
H = HIGH EFFICIENCY
REFRIGERANT = R-410A
DESIGN SERIES
A = DESIGN SERIES
FOUR DIGIT UNIT
NUMBER
VOLTAGE CODE:
17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60
DEVELOPMENT
LEVEL = B (BPHX)
JOHNSON CONTROLS 5
ISSUE DATE: 12/29/2017
TABLE OF CONTENTS
SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY
Introduction Warranty Handling Safety and Quality About this Manual Misuse of Equipment
SECTION 2 – PRODUCT DESCRIPTION
Introduction General System Description Communications Building Automation System Interface Power Panel Accessories and Options
SECTION 3 – HANDLING AND STORAGE
Delivery and Storage Inspection Moving the Chiller Lifting Using Lugs Lifting Using Shackles Lifting Weights
SECTION 4 – INSTALLATION
Installation Checklist Startup/Commissioning Location and Clearances Spring Isolators (Optional) Compressor Mounting Remote Cooler Option Chilled Liquid Piping Pipework Arrangement Wiring Relief Valves High Pressure Cutout Single-Point Supply Connection – Terminal Block, Non-Fused Disconnect Switch or Circuit Breaker
SECTION 5 – TECHNICAL DATA
Physical Data YLAA0058 – YLAA0230 60Hz Electrical Data Compressor Heaters Electrical Notes Weight Distribution and Isolator Mounting Positions Clearances Isolator Locations Isolator Information
JOHNSON CONTROLS6
ISSUE DATE: 12/29/2017
TABLE OF CONTENTS (CONT’D)
SECTION 6 – COMMISSIONING
Preparation – Power Off Preparation – Power On How to Commission the Pump VFD
SECTION 7 – UNIT CONTROLS
Introduction IPU II and I/O Boards Transformer Display Keypad Unit Switch Battery Back-Up Programming # oOf Compressors Status Key Display/Print Keys Entry Keys Setpoints Keys Schedule/Advance Day Key Program Key Unit Keys Bacnet, Modbus, N2 and Yorktalk 2 Communications
SECTION 8 – UNIT OPERATION
Capacity Control Suction Pressure Limit Controls Discharge Pressure Limit Controls Leaving Chilled Liquid Control Leaving Chilled Liquid Control Override to Reduce Cycling Leaving Chilled Liquid System Lead/Lag and Compressor Sequencing Return Chilled Liquid Control Return Chilled Liquid System Lead/Lag and Compressor Sequencing Anti-Recycle Timer Anti-Coincidence Timer Evaporator Pump Control and York Hydro Kit Pump Control Evaporator Heater Control Pumpdown Control Standard Condenser Fan Control Load Limiting Compressor Run Status Alarm Status Remote BAS/EMS Temperature Reset Using a Voltage or Current Signal
JOHNSON CONTROLS 7
ISSUE DATE: 12/29/2017
TABLE OF CONTENTS (CONT’D)
SECTION 9 – SERVICE AND TROUBLESHOOTING
Clearing History Buffers Service Mode Service Mode – Outputs Service Mode – Chiller Configuration Service Mode – Analog and Digital Inputs Control Inputs/Outputs Checking Inputs and Outputs Optional Printer Installation Troubleshooting
SECTION 10 – MAINTENANCE
Compressors Condenser Fan Motors Condenser MCHX Cleaning Operating Parameters On-Board Battery Back-Up Brazed Plate Heat Exchanger (Evaporator) Heater Overall Unit Inspection Temperature
JOHNSON CONTROLS8
ISSUE DATE: 12/29/2017
LIST OF FIGURES
FIGURE 1 - Unit Components (Front) FIGURE 2 - Unit Components (Side) FIGURE 3 - Power Panel Components FIGURE 4 - Power Panel / Control Components FIGURE 5 - Process and Instrumentation Diagram FIGURE 6 - Unit Rigging/Lifting FIGURE 7 - Warning FIGURE 8 - Chilled Liquid System FIGURE 9 - Single-Point Supply Connection – Terminal Block, Non-Fused Disconnect Switch or
Circuit Breaker FIGURE 10 - Control Wiring Inputs FIGURE 11 - Thermal Dispersion Flow Switch FIGURE 12 - Thermal Dispersion Flow Switch (Combine Together) FIGURE 13 - Control Wiring Outputs FIGURE 14 - Elementary Wiring Diagram FIGURE 15 - Elementary Wiring Diagram FIGURE 16 - Fan Wiring, Standard Air Flow FIGURE 17 - Fan Wiring, High Air Flow FIGURE 18 - Single and Dual Point Wiring Options FIGURE 19 - Pump Wiring FIGURE 20 - Compressor Wiring FIGURE 21 - Power Options Connection Diagram FIGURE 22 - Power Panel FIGURE 23 - Micro Panel Connections FIGURE 24 - Four Fan Units Dimensions – YLAA0058HE, YLAA0065HE, YLAA0081HE FIGURE 25 - Four Fan Units Dimensions – YLAA0070SE, YLAA0080SE, YLAA0089SE FIGURE 26 - Five Fan Units Dimensions – YLAA0100SE FIGURE 27 - Six Fan Units Dimensions – YLAA0120SE, YLAA0092HE, YLAA0101HE FIGURE 28 - Eight Fan Units Dimensions – YLAA0136SE, YLAA0155SE, YLAA0142HE FIGURE 29 - Ten Fan Units Dimensions – YLAA0170SE, YLAA0156HE, YLAA0175HE FIGURE 30 - Twelve Fan Units Dimensions FIGURE 31 - Sample Printout Supplied in the Isolator Package and in the Chiller Panel Literature Packet FIGURE 32 - Unit Clearances – All Models FIGURE 33 - Status Key Messages Quick Reference List FIGURE 34 - Operation Data FIGURE 35 - Setpoints Quick Reference List FIGURE 36 - Unit Keys Options Programming Quick Reference List FIGURE 37 - Micro Panel Connections FIGURE 38 - Leaving Water Temperature Control Example FIGURE 39 - Setpoint Adjust FIGURE 40 - Condenser Fan Locations FIGURE 41 - Microboard Layout FIGURE 42 - I/O Board Relay Contact Architecture FIGURE 43 - Printer to Microboard Electrical Connections
JOHNSON CONTROLS 9
ISSUE DATE: 12/29/2017
LIST OF TABLES
TABLE 1 - Canadian Registration Numbers TABLE 2 - Complete Pin Number Description TABLE 3 - Temperatures and Flows TABLE 4 - Ethylene and Propylene Glycol Correction Factors TABLE 5 - Physical Data (English) 60 Hz TABLE 6 - Micropanel Power Supply TABLE 7 - Voltage Range TABLE 8 - Pump Electrical Data (60 hz) TABLE 9 - Transformer Load TABLE 10 - Electrical Data Without Pumps TABLE 11 - Wiring Lugs TABLE 12 - Cooling Setpoint, Programmable Limits and Defaults TABLE 13 - Program Key Limits and Default TABLE 14 - Minimum, Maximum and Default Values TABLE 15 - Values Required for BAS Communication TABLE 16 - Real Time Error Numbers TABLE 17 - Native Bacnet, Modbus and N2 Communications Data Map TABLE 18 - Yorktalk 2 Communications Data Map TABLE 19 - Sample Compressor Staging for Return Water Control TABLE 20 - Return Chilled Liquid Control for 4 Compressors (6 Steps) TABLE 21 - Lead/Lag Return Chilled Liquid Control for 4 Compressors (6 Steps) TABLE 22 - YLAA Standard Condenser Fan Control Using Discharge Pressure Only
(2, 3, or 4 Fans Per System) TABLE 23 - YLAA Standard Condenser Fan Control Using Discharge Pressure Only
(5 or 6 Fans Per System) TABLE 24 - Compressor Operation Load Limiting TABLE 25 - I/O Digital Inputs TABLE 26 - I/O Digital Outputs TABLE 27 - I/O Analog Inputs TABLE 28 - I/O Analog Outputs TABLE 29 - Outdoor Air Sensor Temperature/Voltage/Correlation TABLE 30 - Entering/Leaving Chilled Liquid Temp. Sensor, Temperature/Voltage Correlation TABLE 31 - Pressure Transducers TABLE 32 - Troubleshooting TABLE 33 - SI Metric Conversion
JOHNSON CONTROLS10
ISSUE DATE: 12/29/2017
THIS PAGE INTENTIONALLY LEFT BLANK
JOHNSON CONTROLS 11
ISSUE DATE: 12/29/2017
1SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY
INTRODUCTION
YORK YLAA chillers are manufactured to the highest design and construction standards to ensure high per-formance, reliability and adaptability to all types of air conditioning installations.
Rigging and lifting should only be done by a profes-sional rigger in accordance with a written rigging and lifting plan. The most appropriate rigging and lifting method will depend on job specific factors, such as the rigging equipment available and site needs. Therefore a professional rigger must determine the rigging and lifting method to be used, and it is beyond the scope of the manual to specify rigging and lifting details.
This manual contains all the information required for correct installation and commissioning of the unit, to-gether with operating and maintenance instructions.
The manuals should be read thoroughly before at-tempting to operate or service the unit.
All procedures detailed in the manuals, including in-stallation, commissioning and maintenance tasks must only be performed by suitably trained and qualified personnel.
The manufacturer will not be liable for any injury or damage caused by incorrect installation, commission-ing, operation or maintenance resulting from a failure to follow the procedures and instructions detailed in the manuals.
WARRANTY
Johnson Controls warrants all equipment and materi-als against defects in workmanship and materials for a period of eighteen months from date of shipment, or 12 months from date of start-up, whichever occurs first, unless labor or extended warranty has been purchased as part of the contract.
The warranty is limited to parts only replacement and shipping of any faulty part, or sub-assembly, which has failed due to poor quality or manufacturing errors. All claims must be supported by evidence that the failure has occurred within the warranty period, and that the unit has been operated within the designed parameters specified.
All warranty claims must specify the unit model, serial number, order number and run hours/starts. Model and serial number information is printed on the unit identi-fication plate.
The unit warranty will be void if any modification to the unit is carried out without prior written approval from Johnson Controls.
For warranty purposes, the following conditions must be satisfied:
• The initial start of the unit must be carried out by trained personnel from an Authorized Johnson Controls Service Center (see SECTION 6 – COM-
MISSIONING).
• Only genuine YORK approved spare parts, oils, coolants, and refrigerants must be used.
• All the scheduled maintenance operations detailed in this manual must be performed at the specified times by suitably trained and qualified personnel (see SECTION 10 – MAINTENANCE).
• Failure to satisfy any of these conditions will auto-matically void the warranty (see Warranty on this page).
HANDLING
These units are shipped as completely assembled units containing full operating charge, and care should be taken to avoid damage due to rough handling.
SAFETY AND QUALITY
Standards for Safety and Quality YLAA chillers are designed and built within an ISO 9002 accredited design and manufacturing organiza-tion. The chillers comply with the applicable sections of the following Standards and Codes:
• ANSI/ASHRAE Standard 15 - Safety Code for Mechanical Refrigeration.
• ANSI/NFPA Standard 70 - National Electrical Code (N.E.C.).
• ASME Boiler and Pressure Vessel Code - Section VIII Division 1.
• ARI Standard 550/590 - Positive Displacement Compressors and Air Cooled Rotary Screw Water Chilling Packages.
JOHNSON CONTROLS12
ISSUE DATE: 12/29/2017SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY
• ASHRAE 90.1 - Energy Efficiency compliance.
• Conform to Intertek Testing Services, formerly ETL, for construction of chillers and provide ETL/cETL listing label.
• Manufactured in facility registered to ISO 9002.
• OSHA – Occupational Safety and Health Act.
In addition, the chillers conform to Underwriters Labo-ratories (U.L.) for construction of chillers and provide U.L./cU.L. Listing Label.
Responsibility for Safety Every care has been taken in the design and manufac-ture of the unit to ensure compliance with the safety requirements listed above. However, the individual rigging, lifting, maintaining, operating or working on any machinery is primarily responsible for:
• Personal safety, safety of other personnel, and the machinery.
• Correct utilization of the machinery in accordance with the procedures detailed in the manuals.
ABOUT THIS MANUAL
The contents of this manual include suggested best working practices and procedures. These are issued for guidance only, and they do not take precedence over the above stated individual responsibility and/or local safety regulations.
This manual and any other document supplied with the unit are the property of Johnson Controls which re-serves all rights. They may not be reproduced, in whole or in part, without prior written authorization from an authorized Johnson Controls representative.
MISUSE OF EQUIPMENT
Suitability for Application The unit is intended for cooling water or glycol solu-tions and is not suitable for purposes other than those specified in these instructions. Any use of the equipment other than its intended use, or operation of the equip-ment contrary to the relevant procedures may result in injury to the operator, or damage to the equipment.
The unit must not be operated outside the design pa-rameters specified in this manual.
Structural Support Structural support of the unit must be provided as in-dicated in these instructions. Failure to provide proper support may result in injury to the operator, or damage to the equipment and/or building.
Mechanical Strength The unit is not designed to withstand loads or stresses from adjacent equipment, pipework or structures. Ad-ditional components must not be mounted on the unit.
Any such extraneous loads may cause structural failure and may result in injury to the operator, or damage to the equipment.
General Access There are a number of areas and features, which may be a hazard and potentially cause injury when working on the unit unless suitable safety precautions are taken.
It is important to ensure access to the unit is restricted to suitably qualified persons who are familiar with the potential hazards and precautions necessary for safe operation and maintenance of equipment containing high temperatures, pressures and voltages.
Pressure Systems The unit contains refrigerant vapor and liquid under pressure, release of which can be a danger and cause injury. The user should ensure that care is taken during installation, operation and maintenance to avoid dam-age to the pressure system. No attempt should be made to gain access to the component parts of the pressure system other than by suitably trained and qualified per-sonnel.
Electrical The unit must be grounded. No installation or main-tenance work should be attempted on the electrical equipment without first switching power OFF, isolat-ing and locking-off the power supply. Servicing and maintenance on live equipment must only be per-formed by suitably trained and qualified personnel. No attempt should be made to gain access to the control panel or electrical enclosures during normal operation of the unit.
JOHNSON CONTROLS 13
SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETYFORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
1Rotating Parts Fan guards must be fitted at all times and not removed unless the power supply has been isolated. If ductwork is to be fitted, requiring the wire fan guards to be re-moved, alternative safety measures must be taken to protect against the risk of injury from rotating fans.
Sharp Edges The fins on the air-cooled condenser coils have sharp metal edges. Reasonable care should be taken when working in contact with the coils to avoid the risk of minor abrasions and lacerations. The use of gloves is recommended.
Frame rails, brakes, and other components may also have sharp edges. Reasonable care should be taken when working in contact with any components to avoid risk of minor abrasions and lacerations.
Refrigerants and Oils Refrigerants and oils used in the unit are generally non-toxic, non-flammable and non-corrosive, and pose no special safety hazards. Use of gloves and safety glasses is, however, recommended when working on the unit.
The build up of refrigerant vapor, from a leak for ex-ample, does pose a risk of asphyxiation in confined or enclosed spaces and attention should be given to good ventilation.
High Temperature and Pressure Cleaning High temperature and pressure cleaning methods (e.g. steam cleaning) should not be used on any part of the pressure system as this may cause operation of the pressure relief device(s). Detergents and solvents, which may cause corrosion, should also be avoided.
Emergency Shutdown In case of emergency, the control panel is fitted with a Unit Switch to stop the unit in an emergency. When operated, it removes the low voltage 120VAC electri-cal supply from the unit controller, thus shutting down the unit.
JOHNSON CONTROLS14
JOHNSON CONTROLS 15
ISSUE DATE: 12/29/2017
SECTION 2 – PRODUCT DESCRIPTION
INTRODUCTION
YORK YLAA Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications us-ing central station air handling or terminal units. They are completely self-contained and are designed for out-door (roof or ground level) installation. Each complete packaged unit includes hermetic scroll compressors, a liquid cooler, air cooled condenser, a charge of Zero Ozone Depletion Potential Refrigerant R-410A and a weather resistant microprocessor control center, all mounted on a rugged steel base.
The units are completely assembled with all intercon-necting refrigerant piping and internal wiring, ready for field installation.
Prior to delivery, the packaged unit is pressure-tested, evacuated, and fully charged with Refrigerant R-410A and oil. After assembly, a complete operational test is performed with water flowing through the cooler to as-sure that the refrigeration circuit operates correctly.
The unit structure is heavy-gauge, galvanized steel.
This galvanized steel is coated with baked-on powder paint, which, when subjected to ASTM B117 1000 hour, salt spray testing, yields a minimum ASTM 1654 rating of “6”. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety code for mechanical refrigeration, ASME, and rated in accordance with ARI Standard 550/590.
GENERAL SYSTEM DESCRIPTION
Compressors The chiller has suction-gas cooled, hermetic, scroll compressors. The YLAA compressors incorporate a compliant scroll design in both the axial and radial direction. All rotating parts are statically and dynami-cally balanced. A large internal volume and oil res-ervoir provides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration.
Brazed Plate Evaporator The compact, high efficiency Brazed Plate Heat Ex-changer (BPHE) is constructed with 316L stainless steel corrugated channel plates with a filler material between each plate. It offers excellent heat transfer performance with a compact size and low weight, re-ducing structural steel requirements on the job site.
The heat exchanger is manufactured in a precisely con-trolled vacuum-brazing process that allows the filler material to form a brazed joint at every contact point between the plates, creating complex channels. The ar-rangement is similar to older plate and frame technol-ogy, but without gaskets and frame parts.
Water inlet and outlet connections are grooved for compatibility with field supplied ANSI/AWWA C-606 couplings.
JOHNSON CONTROLS16
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
The evaporator is equipped with a thermostat-con-trolled heater. The heater provides freeze protection for the evaporator down to -20°F (-29°C) ambient. The evaporator is covered with 3/4” flexible, closed-cell, foam insulation (K=0.25).
A 1/16” (1.6mm) mesh wye-strainer is provided as standard for installation upstream of the heat exchang-er to prevent clogging from water system debris.
Canadian Registration Number (CRN) Application & Proof of Conformance Since all YLAA brazed plate evaporators are catego-rized as pressure “H” fittings per CSA-B51, a CRN label or marking is not provided on the evaporator. Ac-cording to the Canadian Standards Association’s Boil-er, Pressure Vessel, and Pressure Piping Code B-51 (2009 version), a product registered as a category “H” fitting does not require a label or marking displaying the CRN.
TABLE 1 - CANADIAN REGISTRATION NUMBERS
CANADIAN PROVINCE CRN #
BC OH13953.51
AB OH13953.52
ON OH13953.5
PQ/MB/SK OH13953.56
NB OH13953.57
NS OH13953.58
PEI OH13953.59
NF OH13953.50
NU OH13953.5N
NWT OH13953.5T
YU OH13953.5Y
Condenser
Microchannel Condenser (MCHX) MCHX Condensers are made of a single material to avoid galvanic corrosion due to dissimilar metals.
MCHX and headers are brazed as one piece. Integral sub cooling is included. The design working pressure of the MCHX is 650 PSIG (45 bar). MCHX Condenser is easily washable with clear water.
Fans The condenser fans are composed of corrosion resis-tant aluminum hub and glass-fiber reinforced poly-propylene composite blades molded into a low noise airfoil section. They are designed for maximum effi-ciency and are statically and dynamically balanced for vibration free operation. They are directly driven by independent motors, and positioned for vertical air dis-charge. The fan guards are constructed of heavy gauge, rust resistant, coated steel. All blades are statically and dynamically balanced for vibration free operation.
Motors The fan motors are Totally Enclosed Air-Over, and are current protected. They feature ball bearings that are double sealed and permanently lubricated.
Control Center All controls are contained in a NEMA 3R/12 cabinet with hinged outer door and includes a Liquid Crystal Display with Light Emitting Diode backlighting for outdoor viewing:
• Two display lines
• Twenty characters per line
Display/Print Keys
• Color coded 12-button non-tactile keypad with sec-tions for display and print of typical information:
• Chilled liquid temperatures
• Ambient temperature
• System pressures (each circuit)
• Operating hours and starts (each compressor)
• Print calls up to the liquid crystal display
• Operating data for the systems
• History of fault shutdown data for up to the last six fault shutdown conditions.
• An RS-232 port, in conjunction with this press-to-print button, is provided to permit the capability of hard copy print-outs via a separate printer (by others).
Entry Keys This section is used to enter setpoints or modify system values.
Setpoints Keys Updating can be performed to:
• Chilled liquid temperature setpoint and range
• Remote reset temperature range
• Set daily schedule/holiday for start/stop
• Manual override for servicing
• Low and high ambient cutouts
JOHNSON CONTROLS 17
SECTION 2 – PRODUCT DESCRIPTIONFORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
• Number of compressors
• Low liquid temperature cutout
• Low suction pressure cutout
• High discharge pressure cutout
• Anti-recycle timer (compressor start cycle time)
• Anti-coincident timer (delay compressor starts)
Unit Keys This section is used to:
• Set time
• Set unit options
Oper Data Key The microprocessor control center is capable of dis-playing the following:
• Return and leaving liquid temperature
• Low leaving liquid temperature cutout setting
• Low ambient temperature cutout setting
• Outdoor air temperature
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• Discharge pressure (optional)
• Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by others) via a 4 to 20 milliamp or 0 to 10VDC input
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
• No cooling load condition
• Day, date and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control
• Lead system definition
• Compressor starts and operating hours
• (each compressor)
• Status of hot gas valves, evaporator heater and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load and unload timer status
• Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and two steps of demand load limiting from an external building automation system. Unit alarm contacts are standard.
The operating program is stored in non-volatile memo-ry battery backed RAM to eliminate chiller failure due to AC powered failure/battery discharge. Programmed setpoints are retained in lithium battery-backed RTC memory for 5 years minimum.
COMMUNICATIONS
• Native communication capability for BACnet
(MS/TP) and Modbus.
• Optional communication available for N2 and
LON via eLink Gateway option.
BUILDING AUTOMATION SYSTEM
INTERFACE
The Microprocessor Board can accept a 4 to 20 milli-amp, or 0 to 10VDC input to reset the leaving chiller liquid temperature from a Building Automation Sys-tem.
• The standard unit capabilities include remote start-stop, remote water temperature reset via a PWM 4 to 20 milliamp or 0 to 10VDC input sig-nal or up to two stages of demand (load) limiting depending on model.
• The standard control panel can be directly con-nected to a Johnson Controls Building Automated System.
POWER PANEL
Each panel contains:
• Compressor power terminals
• Compressor motor starting contactors per I.E.C.**
• Control power terminals to accept incoming for
115-1-60 control power
• Fan contactors and overload current protection
The power wiring is routed through liquid-tight con-duit to the compressors and fans.
JOHNSON CONTROLS18
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
ACCESSORIES AND OPTIONS
Power Options
Compressor Power Connections Single-point terminal block connection(s) are provid-ed as standard. The following power connections are available as options. (See electrical data for specific voltage and options availability.) (Factory-mounted)
Single-Point Supply Terminal Block Includes enclosure, terminal-block and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming compres-sor-power wiring. (Do not include this option if either the Single-Point Non-Fused Disconnect Switch or Sin-gle-Point Circuit Breaker options have been included.)
Single-Point Non-Fused Disconnect Switch Unit-mounted disconnect switch with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to isolate the unit power voltage for ser-vicing. Separate external fusing must be supplied, by others in the power wiring, which must comply with the National Electrical Code and/or local codes.
Single-Point Circuit Breaker A unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing.
(This option includes the Single-Point Power connection.)
Control Transformer Converts unit power voltage to 115-1-60 (2.0 or 3.0 KVA capacity). Factory mounting includes primary and secondary wiring between the transformer and the control panel. (Factory-mounted)
Control Options Ambient Kit (Low) Units will operate to 30°F (-1.1°C). This accessory in-cludes all necessary components to permit chiller opera-tion to 0°F (-18°C). (This option includes the Discharge Pressure Transducer / Readout Capability option.) For proper head pressure control in applications below 30°F (-1°C) where wind gusts may exceed 5 mph, it is recom-mended that Optional Condenser Louvered Enclosure Panels also be included. (Factory-mounted)
High Ambient Kit With Sunshield Allows units to operate when the ambient temperature is above 115°F (46°C). Includes sun shield panels and discharge pressure transducers.
Language LCD and Keypad Display Spanish, French, German, and Italian unit LCD con-trols and keypad display available. Standard language is English.
Compressor, Piping, Evaporator Options Low Temperature Glycol Replaces standard Thermostatic Expansion Valves with Electronic Expansion Valves to achieve leaving glycol temperatures as low as 10°F (-12°C). Required for any leaving liquid temperature below 30°F (-1°C).
Electronic Expansion Valves permit operation at both low temperatures and comfort cooling applications without a capacity loss or derate at either condition.
(Factory installed)
Chicago Code Relief Valves Unit will be provided with relief valves to meet Chi-cago code requirements. (Factory-Mounted)
Service Suction Isolation Valve Service suction (ball-type) isolation valves are added to unit per system (discharge service ball-type isolation valve is standard on each circuit). (Factory-Mounted)
Hot Gas By-Pass Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operat-ing conditions) by introducing an artificial load on the cooler. Hot gas by-pass is installed on only refrigerant system #1 on two-circuited units. (Factory-Mounted)
Flanges (ANSI/AWWA C-606 couplings Type) Consists of (2) Flange adapter for grooved end pipe (stan-dard 150 psi [10.5 bar] cooler). (Not available on optional DX cooler 300 PSIG DWP waterside.) (Field-mounted)
Flow Switch A thermal dispersion type flow switch provides ac-curate, low maintenance flow proving and is included standard. It is factory wired and installed in the exten-sion pipe between evaporator outlet and edge of chill-
er. The extension pipe is secured to the chiller frame for shipping to avoid risk of damage to evaporator
JOHNSON CONTROLS 19
ISSUE DATE: 12/29/2017
and is easily attached to the evaporator at startup us-ing the supplied ANSI/AWWA C-606 connector. The flow switch can be deleted if alternate or existing flow switch is field supplied.
Heat Recovery Condenser A partially condensing refrigerant to liquid condenser recovers heat off both refrigerant circuits and rejects into a single liquid circuit. Factory installed between the compressor discharge and the condenser (air) coils to capture the maximum amount of heat. Capable of recovering up to 85% total heat of rejection (cooling load plus work input); temperatures as high as 140°F (60°C) are possible.
Hydro-Kit Factory installed Hydro-Kit suitable for water and gly-col systems with up to 35% glycol at leaving tempera-tures down to 20°F. The hydro-kit option is available in a single or dual configuration (dual as standby duty only), with totally enclosed permanently lubricated pump motors.
The hydro-kit option comes standard with a balancing valve, discharge check valve, discharge shutoff valve, thermal dispersion flow switch, pressure ports, inlet wye-strainer, bleed and drain valves and frost protection.
Service shut off valves, additional pressure ports and ex-pansion tanks are optional within the hydro-kit option.
Condenser and Cabinet Options MCHX Condenser protection against corrosive envi-ronments is available by choosing any of the following options. For additional application recommendations, See FORM 150.12-ES1. (Factory-Mounted)
Post-Coated Dipped MCHX Condenser The unit MCHX is constructed with post dipped-epoxy MCHX condenser. This is recommended for seashore and other corrosive applications (with the exception of strong alkalies, oxidizers and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm).
Enclosure Panels (Unit) Tamper proof Enclosure Panels prevent unauthorized access to units. Enclosure Panels can provide an aes-thetically pleasing alternative to expensive fencing.
Additionally, for proper head pressure control, Johnson Controls recommends the use of Condenser Louvered Panels for winter applications where wind gusts may exceed five miles per hour. The following types of en-closure panels are available:
• Wire Panels (Full Unit) - Consists of welded wire-mesh guards mounted on the exterior of the unit. Prevents unauthorized access, yet provides free air flow. (Factory-Mounted)
• Wire/Louvered Panels - Consists of welded wire-mesh panels on the bottom part of unit and louvered panels on the condenser section of the unit. (Factory-Mounted)
• Louvered Panels (MCHX Condenser Only)
- Louvered Panels are mounted on the sides and ends of the MCHX condenser for protection.
(Factory-Mounted)
• Louvered Panels (Full Unit) - Louvered panels surround the front, back, and sides of the unit.
They prevent unauthorized access and visually screen unit components. Unrestricted air flow is permitted through generously sized louvered openings. This option is applicable for any out-door design ambient temperature up to 115°F (46°). (Factory-Mounted)
MCHX End Hail Guard Louvered panel attached to exposed MCHX end. (Fac-tory-Mounted)
Sound Attenuation One or both of the following sound attenuation options are recommended for residential or other similar sound sensitive locations:
• Compressor Acoustic Sound Blanket - Each compressor is individually enclosed by an acous-tic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fi-ber of 5/8” (15mm) thickness; one layer of anti-vibrating heavy material thickness of 1/8” (3mm).
Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance.
(Factory-Mounted)
• Ultra Quiet Fans - Lower RPM, 8-pole fan mo-tors are used with steeper-pitch fans. (Factory- Mounted)
Vibration Isolators Level adjusting, spring type 1” (25.4mm) or seismic deflection or neoprene pad isolators for mounting un-der unit base rails. (Field-mounted)
JOHNSON CONTROLS20
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
ITEM DESCRIPTION
1 Fan Assemblies 2 MCHX Condenser 3 Control Panel 4 Compressors
Receiver Included with Optional Heat Recovery Condenser
6 Filter Driers
FIGURE 1 - UNIT COMPONENTS (FRONT)
4 6
POWER
PANEL
POWER
PANEL
JOHNSON CONTROLS 21
ISSUE DATE: 12/29/2017
FIGURE 2 - UNIT COMPONENTS (SIDE)
ITEM DESCRIPTION
1 Fan Deck 2 MCHX Condenser 3 Coil Headers 4 Control and Power Panels 5 Compressors 6 Brazed Plate Evaporator 7 Formed Steel Base Rails 8 Hydro-Kit Pumps And Motors (Optional)
JOHNSON CONTROLS22
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
FIGURE 3 - POWER PANEL COMPONENTS
ITEM DESCRIPTION
1 Fan Contactor 2 Fan Fuses 3 Fan Contactor 4 Disconnect Switch (Optional)
5 XTBF1
6 Compressor Contactors 7 Compressor Overloads
LD13248
1 32
JOHNSON CONTROLS 23
ISSUE DATE: 12/29/2017
FIGURE 4 - POWER PANEL / CONTROL COMPONENTS
ITEM DESCRIPTION
1 Fan Contactor 2 Fan Fuses 3 Control Relay 4 Microcomputer Control Center 5 Display 6 Keypad
7 XTBC1
8 Microboard
9 XTCB2
10 XTBF2
11 Compressor Contactors 12 Compressor Overloads
LD13248
3 4
JOHNSON CONTROLS24
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
PRODUCT IDENTIFICATION NUMBER (PIN)
TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION
FEATURE FEATURE
DESCRIPTION OPTION OPTION DESCRIPTION
MODEL Model (PIN 1-4) YLAA
CAPACITY
Capacity
(PIN 5-8)
0058 0058 0065 0065 0070 0070 0080 0080 0081 0081 0089 0089 0092 0092 0100 0100 0101 0101 0115 0115 0120 0120 0125 0125 0136 0136 0142 0142 0150 0150 0155 0155 0156 0156 0170 0170 0175 0175 0200 0200
UNIT
Unit Designator
(PIN 9)
S Standard Efficiency H High Efficiency
REF. Refrigerant (PIN 10) E R-410A
VOLTS
Voltage
(PIN 11 & 12)
17 200/3/60 28 230/3/60 40 380/3/60 46 460/3/60 50 380-415/3/50 58 575/3/60
STARTER
Starter
(PIN 13)
X Across the Line starter T Soft Start
DESIGN
Design Series
(PIN 14)
A Design Series A (MicroChannel) Copeland Compressor
C Design Series C (MicroChannel CE/ETL Panel) Copeland Com-pressor
D Design Series D (MicroChannel) Bitzer Compressor F Design Series F (MicroChannel CE/ETL Panel) Bitzer Compressor
DEV
Development Level
(PIN 15)
B Development Level B
POWER
Power Field
(PIN 16 &17)
SX SP Supply TB SD SP NF Disconnect Switch BC SP Circuit Breaker w/ Lockable Handle, 65kA SCWR BX SP Circuit Breaker w/ Lockable Handle MB MP Supply w/Ind Sys CB&L Ext Handles
TRANS
Cntrl Transformer
(PIN 18)
X No Control Transformer Required T Control Transformer Required Q Special Control Transformer Required
JOHNSON CONTROLS 25
ISSUE DATE: 12/29/2017
TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D)
FEATURE FEATURE
DESCRIPTION OPTION OPTION DESCRIPTION
PFC
Power Factor Capacitor
(PIN 19)
X No Power Capacitor required C Power Capacitor required Q Special Power Capacitor required
AMB
Ambient Kits
(PIN 20)
H High Ambient Kit Standard (factory) A Both Low/High Ambient Kit required (factory) B Both Low/High Ambient Kit w/Sunshield (factory) S High Ambient Kit w/Sunshield (factory) Q Special Ambient Kit required
BAS
Bas Reset/Offset
(PIN 21)
X No Selection L LON E-Link S SC-Equip Board Q Special Quote
LCD
Language
(PIN 22)
X English S Spanish C Chinese (Simplified) (Not Applicable to eLogia)
E English with Chinese Displayed Board (Not Applicable to eLogia)
F French G German I Italian
RDOUT
Readout Kits
(PIN 23)
B Both Discharge & Suction Pressure Transducer Readout required Q Special Pressure Readout required
SAFETY
Safety Codes
(PIN 24)
C European Saftey Code ( CE ) G China Safety Code (GB) (Not Applicable to eLogia) L N American Safety Code (cUL/cETL)
SENSOR PIN 25
X X Q Special Quote
PUMP
Motor Current Module
(PIN 26)
C Motor Current Module Q Special Quote
REMOTE
Remote Panel
(PIN 27)
X No Remote Panel required Q Special Remote Panel required
SEQ
Sequence Kit
(PIN 28)
X No Sequence Kit required Q Special Sequence Kit required
TEMP
Leaving Water Temp
(PIN 29,30)
NUM Leaving Water Temp = Temp/Num Deg.
CHICAGO
Chicago Code Kit
(PIN 31)
X No Chicago Code Kit required B Both Chicago Code & Serv Isolation C Chicago Code Kit required G Both Suction Service Valve and Dual Relief Valve (Europe only) R Dual Relief Valves no Suction Service Valve (Europe only) S Service Isolation Valves Q Special Chicago Code Kit required
VALVES
Valves
(PIN 32)
X Standard Valves Req’d E Electronic Expansion Valve Q Special Optional Valves Req’d
HGBP
Hot Gas Bypass
(PIN 33)
X No Hot Gas Bypass required 1 Hot Gas Bypass required - 1 circuit Q Special Hot Gas Bypass required
GAUGE PIN 34
X X Q Special Quote
JOHNSON CONTROLS26
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
FEATURE FEATURE
DESCRIPTION OPTION OPTION DESCRIPTION
OVERLOAD PIN 35
X X Q Special Quote
PIN36 PIN 36
K Quick Start Q Special Quote
HTR
Crankcase Heater
(Pin 37) H Crankcase Heater Standard Q Special Crankcase Heater required
DWP
DWP
(PIN 38)
X 150psig DWP Waterside 3 300psig DWP Waterside
INS
Insulation
(PIN 39)
X Standard Insulation D Double Thick Insulation Q Special Insulation required
FLANGES
Flanges
(PIN 40)
X No Flanges required V Victaulic Flanges required Q Special Flanges required
FLOW
Flow Switch
(PIN 41)
X No Flow Switch required S One Flow Switch Required Y Flow Switch With Extension Kit
VESSEL
Vessel Codes
(PIN 42)
A ASME Pressure Vessel Codes E PED Pressure Vessel Codes G GB Pressure Vessel Codes Q Special Quote
CLR
Cooler
(PIN 43)
X Standard Cooler Required R Remote Cooler Required
PIN44 PIN 44
G Flow Switch >= 10% Glycol W Flow Switch < 10% Glycol
COILS
Coils
(PIN 45)
X Aluminum Coils P Post Coated Dipped Coil T Post Coated Microchannel Coils
HEAT
Heat Recovery
(PIN 46)
X No Option required H Heat Recovery Q Special Quote
FANMOTORS
Fan Motors
(PIN 47)
X TEAO Fan Motors Q Special Fan Motors required
ENCL
Enclosure Panels
(PIN 48)
X No Enclosure required 1 Wire (Full Unit) Encl Panels (factory) 2 Wire (Full Unit) Encl Panels (field) 3 Wire/Louvered Encl Panels (factory) 4 Wire/Louvered Encl Panels (field) 5 Louvered (Cond only) Encl Panels (factory) 6 Louvered (Cond only) Encl Panels (field) 7 Louvered (Full Unit) Encl Panels (factory) 8 Louvered (Full Unit) Encl Panels (field) 9 End Louver (End Hail Guard) Encl Panels (factory) A End Louver (End Hail Guard) Encl Panels (field) B Aesthetic Panel Kit only (factory) C Aesthetic Panel Kit only (field) D Aesthetic Panel Kit plus Hail Guards (factory) E Aesthetic Panel Kit plus Hail Guards (field) Q Special Enclosure Panels
TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D)
JOHNSON CONTROLS 27
ISSUE DATE: 12/29/2017
FEATURE FEATURE
DESCRIPTION OPTION OPTION DESCRIPTION
ACOUSTIC
Acoustic Blanket
(PIN 49)
X No Acoustic Blanket required B Acoustic Blanket Required E Acoustic Enclosure Q Special Acoustic Blanket required
SRDOCS
SR Documents
(PIN 50)
X No Documents Required A Base, Material & Witness Documents B Base Document M Base & Material Documents W Base & Witness Documents Q Special Quote
PIN 51 PIN 51
X X Q Special Quote
FANS
Sound Fans
(PIN 52)
X Standard Low Sound Fan Required L Ultra Quiet Fans Required G High Air Flow Fan Requied V Standard Low Sound Fan with VSD Required M Ultra Quiet Fans with VSD Required A High Air Flow Fan Requied (Vendor Specific) E Low Sound Fan Required (Vendor Specific) S High Static Fan Required (Vendor Specific) U Ultra Quiet Fans Required (Vendor Specific) 2 2-Speed Fans Required (Vendor Specific)
PAINT PIN 53
X X Q Special Quote
ISOL
Vibration Isolators
(PIN 54)
X No Isolators required 1 1” Deflection Isolators required N Neoprene Isolators required S 2” Deflection Isolators required Q Special Isolators required
PIN 55 PIN 55 Marketing Purposes Only!
PIN 56 PIN 56 Marketing Purposes Only!
SHIP
Ship Instructions
(PIN 57)
X No Containerization required with Shipping Bag A Buy American Act Compliance with Shipping Bag
B Both Buy American Act Compliance and Container Shipped with-out Shipping Bag (Factory Prep)
C Container Shipped without Shipping Bag (Factory Load) D Container Shipped with Shipping Bag (Factory Load US Port) E Container Shipped with Shipping Bag (Factory Load Mexico Port) F Container Shipped with Shipping Bag (Factory Prep)
G Both Buy America Act Compliance and Container Shipped with Shipping Bag (Factory Prep)
M Container Shipped without Shipping Bag (Factory Load Mexico Port)
N No Containerization required without Shipping Bag P Container Shipped without Shipping Bag (Factory Prep) U Buy American Act Compliance without Shipping Bag Q Special quote
JOHNSON CONTROLS28
ISSUE DATE: 12/29/2017SECTION 2 – PRODUCT DESCRIPTION
FEATURE FEATURE
DESCRIPTION OPTION OPTION DESCRIPTION
PIN 58 PIN 58 Marketing Purposes Only!
PKG
Pump Package
(PIN 59)
X No Pump A Pump Kit A B Pump Kit B C Pump Kit C D Pump Kit D E Pump Kit E F Pump Kit F G Pump Kit G H Pump Kit H I Pump Kit I J Pump Kit J K Pump Kit K L Pump Kit L M Pump Kit M N Pump Kit N O Pump Kit O P Pump Kit P R Pump Kit R S Pump Kit S T Pump Kit T U Pump Kit U V Pump Kit V W Pump Kit W Y Pump Kit Y Z Pump Kit Z
PKGOPT
Pump Package Options
(PIN 60)
X No Option 1 Single Pump, Standard 2 Single Pump, Full Feature 3 Dual Pump, Standard 4 Dual Pump, Full Feature 5 VSD Single Pump, Full Feature 6 VSD Dual Pump, Full Feature
PIN 61 PIN 61 Marketing Purposes Only!
LOC Mfg Location GZ Guangzhou, China
MTY Monterrey, Mexico SAT San Antonio, Texas
JOHNSON CONTROLS 29
ISSUE DATE: 12/29/2017
FIGURE 5 - PROCESS AND INSTRUMENTATION DIAGRAM
PS
ZCPR-1ZCPR-2ZCPR-3
DV
HPL
HPC
P
DV
LPC P
Condenser
Fans Fans
-YLLSV
S
Chilled Liquid
T
DV
CHT
LTC
Evaporator
Chilled Liquid
See P.R.V.
Options
Compressors
Control Functions:
DV - Display Value CHT - Chilled Liquid Temperature HPC - High Pressure Cutout LPC - Low Pressure Cutout HPL - High Pressure Load Limiting LTC - Low Temperature Cutout
Components:
Pressure Relief Valve
Service (Ball) Valve
Expansion Valve
Solenoid Valve
Sight Glass
Sensor Pressure or Temperature
Service (Stop) Access Valve
Pressure Switch
Filter Drier (Removable Core)
S
PS
T
Ambient Air Sensor
DV
HTC
LTC
585 PSIG
650 PSIG
450 PSIG
LD13139
Low pressure liquid refrigerant enters the cooler and is evaporated and superheated by the heat energy ab-sorbed from the chilled liquid passing through the cooler shell. Low pressure vapor enters at the compres-sor where pressure and superheat are increased. The high pressure vapor is fed to the air cooled condenser coil and fans where the heat is removed. The fully con-densed and subcooled liquid passes through the expan-sion valve where pressure is reduced and further cool-ing takes place before entering to the cooler.
JOHNSON CONTROLS30
JOHNSON CONTROLS 31
ISSUE DATE: 12/29/2017
SECTION 3 – HANDLING AND STORAGE
DELIVERY AND STORAGE
To ensure consistent quality and maximum reliability, all units are tested and inspected before leaving the fac-tory. Units are shipped completely assembled and con-taining refrigerant under pressure. Units are shipped without export crating unless crating has been speci-fied on the Sales Order.
If the unit is to be put into storage, prior to installation, the following precautions should be observed:
• The chiller must be “blocked” so that the base is not permitted to sag or bow.
• Ensure that all openings, such as water connec-tions, are securely capped.
• Do not store where exposed to ambient air tem-peratures exceeding 112 °F (44.5 °C).
• The condensers should be covered to protect the fins from potential damage and corrosion, particu-larly where building work is in progress.
• The unit should be stored in a location where there is minimal activity in order to limit the risk of ac-cidental physical damage.
• To prevent inadvertent operation of the pressure relief devices the unit must not be steam cleaned.
• It is recommended that the unit is periodically in-spected during storage.
INSPECTION
Remove any transit packing and inspect the unit to en-sure that all components have been delivered and that no damage has occurred during transit. If any damage is evident, it should be noted on the carrier’s freight bill and a claim entered in accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local Johnson Controls representative.
MOVING THE CHILLER
Prior to moving the unit, ensure that the installation site is suitable for installing the unit and is easily ca-pable of supporting the weight of the unit and all as-sociated services.
The unit must only be lifted by the base frame at the points provided. Never move the unit on rollers, or lift the unit using a forklift truck.
Care should be taken to avoid damaging the condenser cooling fins when moving the unit.
JOHNSON CONTROLS32
ISSUE DATE: 12/29/2017SECTION 3 – HANDLING AND STORAGE
FIGURE 6 - UNIT RIGGING/LIFTING
LD18120
A B
C D
Y
X
C on tro l P an el
LD18121
A B C
D E F
Y
X
C on tro l P an el
4 Fan Units
5 - 12 Fan Units
JOHNSON CONTROLS 33
SECTION 3 – HANDLING AND STORAGEFORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
LIFTING USING LUGS
Units are provided with lifting holes in the base frame which accept the accessory lifting lug set as shown in the figure below.