NCTAMSLANT Facilities Department

Statement of Work

Circuit Breaker Replacement for Emergency Generator Switchgear at Building 352

2011-07-R-NW

NAVSATCOMMFAC Northwest, Chesapeake VA

PREPARED BY:

Christopher Conway 05 January 2011

1. SCOPE:

This statement of work provides the requirements for replacement of five (5) existing draw-out type motor operated circuit breakers located at NAVSATCOMMFAC Northwest, Chesapeake Virginia. The present switchboard has been in service for 20 years. The contractor will perform a survey to identify best methods to follow for replacement or retrofit of circuit breakers. The Contractor shall inspect, test, and calibrate new circuit breakers and their associated trip units to coordinate with a recent short circuit study.

The scope shall include all required design, drawings, and specifications; labor, equipment, tools and material for installation; testing; on-site training; operation and maintenance manuals; as-built drawings.

2. APPLICABLE DOCUMENTS:

NETA Maintenance Testing Specs. For Elect Dist. Eqt. and Systems

MIL-HDBK-1012/1

MIL-HDBK-1004/2A

Uniform Mechanical Code

NFPA 70, National Electric Code NFPA 70E, Standard for Electrical Safety in the Work Space NFPA 72, Fire Protection Code

IEEE C2, National Electric Safety Code, 1997

3. WORK PROCEDURES AND OUTAGES:

The new work will be accomplished in and around areas that will remain in operation. The power system, stand-by generator and UPS critical circuits must be maintained and fully operational throughout the project. Adequate dust control procedures shall be employed as required. Accordingly, measures shall be taken to avoid interference with the operational work routines. The site is a critical operational facility; therefore, the contractor shall ensure that electric power is not interrupted during the generator switchgear maintenance. The contractor shall diligently pursue the installation once started, to minimize the impact on facility operations.

The contractor shall request permission for power outages at least 21 days prior to the desired date of the outage. Operational circumstances may require the approval of the outage to be withdrawn at the last minute; however, the government will make all efforts to maintain the agreed schedule or will reschedule the outage in the shortest possible time. The design and installation of the work shall be planned and performed in a manner that will keep necessary outages (downtime) to the minimum possible; this includes the provision of temporary power or components, if required. The contractor shall coordinate all actions, which impact the facility power, or require a power outage, with the designated COR, or Navy Technical Representative, and the on-site Navy representative.

Work shall be sequenced to ensure that power is available to the critical bus at all times. Station personnel will accomplish all bypass, maintenance bypass and operations. Location of existing UPS, electric panels, and switchboards are shown on facility drawings.

4. PROJECT REQUIREMENTS:

a.) The Contractor shall replace/retro-fit five (5) G.E. Power Break draw-out type circuit breakers and their solid state trip devices. These breakers are electrically operated for the automatic operation of the Utility/generator switchboard. Verify each secondary contact function on existing circuit breakers and ensure new circuit breakers have the same operating characteristics.

OPTION 1:

Replace the existing five (5) G.E. Power Break type circuit breakers with a newer G.E. design, if available. The new design shall have an improved operating mechanism and shall be a direct replacement into the G.E. switchgear cubical cells. New trip units shall be outfitted with correct over-current protection for each circuit breaker for proper fault current trip coordination.

OPTION 2:

Replace the existing five (5) G.E. Power Break type circuit breakers with a different manufacturer’s design. Retro-fit the new circuit breaker and its racking mechanism to fit into the existing cubical cell. The new circuit breakers shall be of the draw-out design for maintenance purposes. New trip units shall be outfitted with correct over-current protection for each circuit breaker for proper fault current trip coordination.

b.) The Contractor shall inspect, clean, and test, the switchgear bus after any modifications. A complete operational test shall be performed on the automatic operation of the switchgear when the project is complete. Testing and maintenance performed shall be in accordance with the manufacturer’s instructions for each component.

c.) The Contractor shall provide written reports for calibration and submit to the on-site Navy representative, including the test results and overall condition of equipment included in this contact.

NOTE: Switchboard bus bar modifications will be addressed during site survey.

NAVSATCOMMFAC Northwest Generator and Tie Breakers List:

Generator breakers (Typ. Of 3) Tie Breakers (Typ. Of 2) Circuit Breaker (5 ea):

GE Power Break (draw-out breaker)

Low Voltage AC release trip breakers With bell alarms and over current lockouts ID: Tech Tie Breaker ID: Non-Tech Tie Breaker

C/N: TC2020SSE1C

C/N: TC2020SSE1C

S/N: V95322

S/N: V95323

2000A/ 480VAC

2000A/ 480VAC

Versa Trip Mod

Versa Trip Mod

ID: Gen-1

ID: Gen-2

ID: Gen-3

C/N: TC1616SSE1C

C/N: TC1616SSE1C

C/N: TC1616SSE1C

S/N: V95295

S/N: V95294

S/N: V95293

1600A/ 480VAC

1600A/ 480VAC

1600A/ 480VAC

Versa Trip Mod

Versa Trip Mod

Versa Trip Mod Contractor shall prepare written documentation of all testing results, visual inspections, calibrations, adjustments and maintenance recommendations. Service, calibration, and testing shall be as specified herein and in accordance with Maintenance Testing Specifications identified in International Electrical Testing Association (NETA).

5. SPECIAL REQUIREMENTS:

A. The access to the work site and the equipment room is restricted. The on-site Navy representative will provide any required escorts. The contractor shall schedule work with the on-site Navy representative to ensure access.

B. The Contractor is responsible for the safety of his employees. The Contractor shall determine if any confined space is a “permit required” confined space. The Contractor shall ensure his employees are adequately trained and qualified to work in confined spaces. The Contractor shall provide a copy of his Confined Space Entry Program to the on-site Navy representative prior to starting work.

C. The Contractor shall follow all OSHA and NCTAMS LANT safety regulations pertaining to the control of hazardous energy, (lockout-tag out). The Contractor shall provide a copy of his Energy Control Program to the on-site Navy representative before work commences. The plan shall contain information sufficient to ensure government employees safety and identify lockout-tag out procedures for hazardous energy sources.

D. The Contractor shall submit, via the Contract Control Authority/ on-site Navy representative, a list with the names and Social Security numbers of all personnel who will be working on the contract job site. The Contract Control Authority/ on-site Navy representative will forward this list to NAVSATCOMMFAC Northwest Technical Director with a cover letter confirming the contract and Contractor and identifying the time period involved.

E. The Contractor must demonstrate to the on-site Navy representative that he is certified and licensed to perform the required electrical work. All work shall be completed as per the latest edition of the National Electrical Code and the National Safety Code.

F. All Contractors and their employees must report to NSA Northwest Security Department to obtain permission to park each day prior to beginning any operations at the site. At this time the Contractor and employees will be required to identify and register any private or company vehicles that will be on site in association with the contract.

G. Proper operator licensing for vehicle operators is mandatory. All vehicles must have base decals or temporary passes. Immediately report instances of lost or stolen badges, decals or passes to the on-site Navy representative.

6. WARRANTY OF SERVICES:

The Contractor shall warrant all work against defects in material and workmanship for one year from the date of Government acceptance. The Contractor shall correct any defects in material or workmanship or any recurring maintenance problems caused by defects in material or workmanship within the warranty period by repair or replacement at no additional cost to the Government. If the defect results in any damage to Government or private property, the damage shall be corrected by repair or replacement at the option of the owner, at no additional cost to the Government. The Contractor shall respond and correct all warranty repairs within ten working days from the date of notification by the Government. Should the contractor not make the required repairs in a timely manner, the Government reserves the right to have the services performed by others and bill the contractor for actual costs incurred.

7. PERIOD OF PERFORMANCE:

The contractor shall complete the work within six months after notification to proceed. Completion shall include final clean up of job site and completion of all work.

8. POINTS OF CONTACTS:

Site Support

NAVSATCOMMFAC Northwest Technical Director

Mr. Doug Graves

(tel) 757-421-8611 email- douglas.graves@navy.mil Electrical and Technical matters

NCTAMS LANT, Norfolk, VA

Mr. Chris Conway (tel.) 757-443-9174 (fax) 757-443-9196 email- christopher.conway1@navy.mil NCTAMS LANT, Norfolk, VA

Mr. Steve Steeley

(tel) 757-443-9173/ DSN: 312-646-9173

(fax) 757-443-9196 email- steve.steeley@navy.mil N4 Facilities Manager

NCTAMS LANT, Norfolk, VA

Mr. Dave Bowery

(tel) 757-443-9191/ DSN: 312-646-9191

(fax) 757-443-9196 email- david.bowery@navy.mil

File details come from the government source that posted it. Updated .