Description of Requirement: SERMC Gas and Hydrogen Sulfide Monitors
1 | P a g e
1. INTRODUCTION
USS IWO JIMA requires a combustible gas and hydrogen sulfide alarm system upgrade IAW SA 87640 D
LHD-1 CL Combustible gas and hydrogen sulfide monitors. This alteration will replace obsolete/unsupported Mine Safety Appliances INC (MSA) hazardous gas monitoring equipment. The obsolete monitors and local controllers will be replaced with MSA Ultima XE sensor assemblies and MSA
GasGard XL controllers utilizing exiting wiring and some existing mounting equipment.
2. REQUIREMENTS
Quantity of 6 GasGard XL Combustible gas (0-100% LEL) 8-channel controllers with Shock Tech P/N
70987-1 isolated enclosure using four Shock Tech P/N 71003-0 arch mounts
Quantity of 31 Combustible (0-100% LEL) Ultima XE monitor with Shock Tech P/N 70984-1 isolated mount using four Shock Tech P/N 70780-2 conical isolators
Quantity of 4 GasGard XL HS2 (0-100 PPM) 8 channel controller with Shock Tech P/N 70987-1 isolated enclosure using four Shock Tech P/N 71003-0 arch mounts
Quantity of 8 H2S (0-100 ppm) Ultima XE monitor with Shock Tech P/N 70984-1 isolated mount using four Shock Tech P/N 70780-2 conical isolators
3. DELIVERY
Southeast Regional Maintenance Center (SERMC) Address
A) SERMC
Building 1488 Massey Ave.
Mayport, FL 32228
All Deliveries must be made within 154 days after award of Contract.