N6660424Q0174 Amend 0001.pdf
PDF 445 KB Posted
- Attached to
- Construction- Bldg 47 Emergency Generator Project Federal contract opportunity
- Solicitation number
- N6660424Q0174
About this file
This document contains an amendment to a federal solicitation for construction services. The Naval Undersea Warfare Center Division, Newport is seeking a contractor to prepare and install an emergency generator in Building 47. The amendment extends the proposal due date from March 7 to March 15, 2024 at 2:00 PM ET. It also replaces the wage determination attachment, adds a circuit sketch drawing, and provides answers to contractor questions to clarify technical requirements. The work includes installing a 200KW, 102/208V generator with a 48-hour sub-base fuel tank and standard open-transition automatic transfer switch. A 120V circuit is required at the generator for accessories. The estimated value is between $100,000 and $250,000. The opportunity is set aside exclusively for small businesses.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| N6660424Q0174 Amend 0002.pdf | ||
| II. H. Davis-Bacon Act WD # RI20240001 20240223.pdf | ||
| I. E. Davis-Bacon Act WD # RI20240001 20240112.pdf | ||
| N6660424Q0174.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1301130637
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
See section A.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 4
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 05-Mar-2024
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X N6660424Q0174
X 9B. DATED (SEE ITEM 11)
06-Feb-2024
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
05-Mar-2024
CODE
NAVAL UNDERSEA WARFARE CENTER
JAY PARKER, CODE 0221
CONTRACTS DEPARTMENT
1176 HOWELL STREET
NEWPORT RI 02841
N66604 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N6660424Q0174
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION A - SOLICITATION/CONTRACT FORM
The required response date/time has changed from 07-Mar-2024 02:00 PM to 15-Mar-2024 02:00 PM.
The required performance has changed from PROJECT TITLE AND DESCRIPTION: B47 Emergency Generator ProjectProposal Due: 7 Mar 2024 before 2:00 pm ET. Email to jay.a.parker2.civ@us.navy.mil and michael.n.ouellette.civ@us.navy.mil. Questions accepted up to one week prior to proposal due date (29APR24).
Offeror MUST be registered in the System for Award Management to be considered for award.This requirement is 100% Small Business Set-Aside: NAICS 236220; $45 MillionMagnitude per FAR 36.204: Between $100,000 and $250,000.Method of Payment: If no surcharge is applicable, the Government’s preferred method of payment is via credit card. Otherwise, Electronic Payment through Wide Area Workflow will be used. Please confirm Government Purchase Card is an acceptable form of payment within the proposal.Site Visit: 2:00 PM ET 21 Feb 2024. See Section A for complete details.IMPORTANT: PLEASE NOTE THAT TECHNICAL INFORMATION IS
REQUIRED, PLEASE SEE SECTIONS L AND M FOR SPECIFIC REQUIRMENTS. OFFERORS NOT
SUBMITTING THIS INFORMATION RISK BEING EXCLUDED FROM CONSIDERATION FOR AWARD. to PROJECT TITLE AND DESCRIPTION: B47 Emergency Generator ProjectProposal Due: 15 Mar 2024 before 2:00 pm ET. Email to jay.a.parker2.civ@us.navy.mil and michael.n.ouellette.civ@us.navy.mil. Questions accepted up to one week prior to proposal due date (8MAR24). Offeror MUST be registered in the System for Award Management to be considered for award.This requirement is 100% Small Business Set-Aside: NAICS 236220; $45 MillionMagnitude per FAR 36.204: Between $100,000 and $250,000.Method of Payment: If no surcharge is applicable, the Government’s preferred method of payment is via credit card. Otherwise, Electronic Payment through Wide Area Workflow will be used. Please confirm Government Purchase Card is an acceptable form of payment within the proposal.Site Visit: 2:00 PM ET 21 Feb 2024. See Section A for complete details.IMPORTANT: PLEASE NOTE THAT TECHNICAL INFORMATION IS REQUIRED, PLEASE SEE
SECTIONS L AND M FOR SPECIFIC REQUIRMENTS. OFFERORS NOT SUBMITTING THIS
INFORMATION RISK BEING EXCLUDED FROM CONSIDERATION FOR AWARD..
The following have been modified:
GENERAL INFORMATION
Distribution: To be provided at award NUWCDIVNPT PR number: To be provided at award
NUWCDIVNPT PID: N66604-24-SIMACQ-NPT-10-0149
NUWCDIVNPT Point of Contact: Jay Parker, jay.a.parker2.civ@us.navy.mil, (401) 832 2687
Amendment 0001: The purpose of this amendment it to:
1. Extend the proposal due date from 7 Mar 2024 @ 1400 EST to 15 Mar 2024 @1400 EST.
2. Remove Attachment 2, RI Wage Determination dated 01-Jan-2024 and replace with Davis-Bacon Act WD # RI20230001 dated 23-Apr-2024.
3. Add Attachment 3, 23-062A B47 NEW NMCI EMERGENCY GENERATOR 120V 20A 1P Circuit Sketch dated 01-Mar-2024
4. Provide answers to RFI 0001
1. Generator rating – spec states 400 kw, drawing states 200 kw.
Response: 200KW
2. System voltage – spec states 277/480 volt, drawing states 120/208 volt.
Response: 102/208V
3. Fuel Tank – spec states day tank with no capacity listed, drawing states 48 hour tank.
Response: 48 hour sub-base Fuel Tank
4. Spec states both engine mounted radiator and heat exchanger.
Response: Unit Mounted radiator
5. Spec calls out Bypass isolation ATS, drawing calls out standard open transition.
Response: Standard-type/open-transition ATS
6. What is the source of the existing emergency power; is it currently active? Do we need to wait to sequence a swapover once the generator arrives or can the circuit/breaker be disconnected in advance?
Response: There isn’t an existing emergency power source. Existing equipment is indicated correctly on the drawing set. Shutdown of panel board MDP-A required for this project will be coordinated with the project engineer at least two weeks in advance, and scheduled for a weekend.
7. Is there a time limit on your outages?
Response: A weekend shutdown is required for minimum impact to mission and personnel. The time of the shutdown is expected to be 8 hours or less. Multiple or longer duration shutdowns can be discussed and considered.
8. Per the specifications, conduits will be required for generator accessories such as battery charger, jacket coolant heater, E-stop, annunciator panel, etc. but these are not shown in the drawings. Are these just not shown for clarity?
Response: A 120V circuit is required at the generator for power to the block heater, battery charger, and a convenience receptacle.
9. What is the power source for these added items; low voltage accessories in particular?
Response: See the attached 23-062A B47 NEW NMCI EMERGENCY GENERATOR 120V 20A 1P Circuit Sketch for the 120V power source required at the generator.
10. The drawings do not show any 120v branch circuits for a battery charger or block heater or a start stop circuit from the ATS, will these circuits be required?
Response: See response to #9.
11. The drawings do not note to install a remote annunciator/alarm panel for the generator, but the specs do mention it, is one required and if so, where will it be located?
Response: A remote annunciator/alarm panel is not required, that requirement should be deleted from the specs.
12. Seeing the transfer switch is located within a secure data center, can work be completed in there at anytime with the exception of any shutdowns?
Response: Advance notice for contractor access to room 101 is required to ensure a government escort is available.
13. For shutdowns to switch power over to the ATS, will that be completed on a Saturday or Sunday? If so, please provide times when that work can be accomplished.
Response: Any planned interruption to electrical power will be scheduled and coordinated with the Project Engineer, for completion on a Saturday or Sunday (typically Saturday mornings are preferred).
14. Can the ATS be located in Room 101 instead of Room 103?
-If not, can the raised floor in 103 support the weight if the ATS structurally Response: The new ATS can be located in room 103 if the weight of the ATS on the existing raised floor is an issue.
All other terms and conditions remain unchanged.
SECTION J - LIST OF DOCUMENTS, EXHIBITS AND OTHER ATTACHMENTS
The Table of Contents has changed from:
Exhibit/Attachment Table of Contents
DOCUMENT TYPE DESCRIPTION PAGES DATE
Attachment 1 SPEC & DWGS B47
USW Data Center Resiliency Upgrades
177 07-DEC-2023
Attachment 2 Davis-Bacon Act WD #
RI20240001
15 12-JAN-2024
to:
Exhibit/Attachment Table of Contents
DOCUMENT TYPE DESCRIPTION PAGES DATE
Attachment 1 SPEC & DWGS B47
USW Data Center Resiliency Upgrades
177 07-DEC-2023
Attachment 2 Davis-Bacon Act WD #
RI20240001
15 23-FEB-2024
Attachment 3 23-062A B47
EMERGENCY
GEN120V 20A 1P Circuit Sketch
1 01-MAR-2024
(End of Summary of Changes)