RFI Q_A_ B1320 HVAC.pdf

PDF 359 KB Posted

Attached to
Construction - B1320 HVAC Retrofit Federal contract opportunity
Solicitation number
N6660421Q0292
Issued by
Department of the Navy Naval Sea Systems Command

View the file

Other files for this federal contract opportunity

Other files attached to Construction - B1320 HVAC Retrofit, newest first.
File Type Posted
N6660421Q0292 Amendment 0002.pdf PDF
N6660421Q0292 Amendment 0001.pdf PDF
N6660421Q0292.pdf PDF
Attachment_5_ 52.204_24 COMPLETE AND RETURN.pdf PDF
Attachment_4_USE OF MASKS AND OTHER PUBLIC HEALTH MEASURES OSD000860-21 RES FINAL.pdf PDF
Attachment_3_ Covid Questionare (1).pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q1-Pictures of each breaker panel (able to zoom on existing breakers to match part# and AIC ratings, location of existing disconnect for dehumidifier and new disconnect for heat pump, general picture of above ceiling tiles in electric room, wall above electric panels.

A1-The existing panel is a square D cat. No. NEHB30435-2CU, series E1.

Q2-Can flexible metal conduit be installed above drop ceiling? Change over to EMT conduit below drop ceiling(s) in mechanical room #170 and electrical room #146?

A2- Metal flexible conduit is not allowed, only a maximum of 6’-0” at the operating equipment.

Q3-drwaing E-1 notes to remove 45 amp breaker in space 13 (in panel HP12)… Space 13 has a 20 amp breaker in it and space 16 has a 45 amp breaker: which breaker/space will actually be used removed and replaced with 50 amp shunt breaker for HP-1?

A3-Remove 45 amp breaker in panel space 14,16,18 and replace with a 50 amp shunt breaker.

Q4- is there glycol in the water piping system? If so, is it propylene glycol?

A4-This is a condenser water loop there is no glycol.

Q5- are there isolation valves on the water piping serving the heat pump unit? No valves were visible during the walk-thru..

A5- There are no isolation valves present.

Q6-can ‘grooved’ copper fittings (ie: Victualic) be used for the new water piping to heat pump?

A6-Grooved copper fittings are no allowed.