Attachment A - N4215824Q0026.docx
DOCX document 26 KB Posted
- Solicitation number
- N4215824Q0026
About this file
This document is an Attachment A to a Request for Quote (RFQ) solicitation numbered N4215824Q0026 for the rental of Grade D Air Compressors and Regenerative Air Dryers to support operations at Naval Operating Base (NOB) Norfolk and Norfolk Naval Shipyard (NNSY).
The RFQ requires the vendor to provide three (3) 800 CFM Grade D oil-free air compressors and three (3) 930 CFM minimum heatless regenerative air dryers with specific technical capabilities. The air compressors and air dryers must meet detailed specifications outlined in the document. The Period of Performance is split into two parts - POP-A from 8/15/2024 to 1/13/2025, and POP-B from 1/13/2025 to 4/13/2026. Quotes are due by July 24, 2024 at 2:30 PM EST. The contracting agency is the Department of the Navy Naval Sea Systems Command (NAVSEA).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment To Solictitaion_N4215824-Q-0026_Air Compressors and Dryers.docx | DOCX document | |
| Copy of Attachment III Specifications Sheet Without Price.xlsx | XLSX spreadsheet | |
| Attachment_III_PastPerformanceQuestionnaire.docx | DOCX document | |
| Attachment_II_PastPerformanceQuestionnaire.docx | DOCX document | |
| Copy of Attachment II Specifications Sheet With Price.xlsx | XLSX spreadsheet | |
| Combined Synopsis Solicitation N4215824-Q-0026_Air Compressor and Dryer Rentals.docx | DOCX document | |
| Attachment_I_Past Performance_Information_Form.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT A – N4215824Q0026 6
TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBILITY CERTIFICATION STATEMENT
GRADE D AIR COMPRESSORS and REGENERATIVE AIR DRYERS
Vendor shall certify for equipment quoted that his product meets each capability listed below by initializing at the bottom. In order to be considered for award, this must be completed and submitted with your quote.
Technical Capabilities Statement
Item #0001 THREE (3) GRADE D AIR COMPRESSORS
| Shall be provided with the following capabilities, features, and specifications: |
| YES |
| NO |
· Air Compressor shall be oil free and utilize a rotary screw design.
· Air Compressor shall deliver Grade “D” air as per Commodities Specification of Air (CGA) G-7.1 or oil free air per ISO 8573-1 Class 0.
**An oil flooded rotary screw design with attached oil separator is NOT acceptable.
· Air Compressor shall be fixed speed design.
**A variable speed design is NOT acceptable.
· Air Compressor shall provide at least 800 Cubic Feet per Minute (CFM).
· Air Compressor Supply pressure shall be 125 Pounds per Square Inch (PSI).
· Gearbox casing shall be designed to maintain a vacuum on its oil contents in order to prevent a potential of contamination of the air supply in the event of a seal failure.
· Air Compressor shall have moisture separator (electric type) after coolers.
· Discharge shall be 2" NPT. (If unit is not equipped with 2” Male NPT Outlet connection, contractor to provide adapters as required to provide 2” Male NPT outlet connection on the unit.)
· Air Compressor shall be electrical powered 230/460V and capable of starting and running on a 400 amp circuit breaker.
· Air Compressor shall have a male 500 mcm Camlock fitting.
· Air Compressor shall be capable of running 24 hours/day, 7 days/week.
· Air Compressor shall be a complete system.
· Whip-check devices shall be supplied with compressor.
· Unit shall be free standing and must have forklift slots (capable of being moved with a forklift).
· Air Compressor is to be provided with a 27 Cubic Feet (cu.ft.) or larger air receiver tank. Tank must be an ASME coded vessel with a working pressure rating of 150 psig or more. Tank is to have an appropriately sized pressure relief valve(s) attached. Tank is to have a pressure regulating/reducing valve set at 120 Pounds per Square Inch (PSI) on the outlet of the receiver tank.
· The Air Compressors shall comply with Lifting and Rigging requirements as outlined in sections entitled “Requirement for Lifting of Equipment” and “Rigging Sketch Requirements” for contractor equipment at NNSY.
· The Air Compressors shall be free standing and must have forklift slots (capable of being moved with a forklift).
· The Air Compressors shall contain all identifying markings to include:
· Contractor’s name and point of contact information (name, tele#, etc)
· Government Contract Number; Contracting Officer’s information (name, tele#, etc)
· Vessel Name/Code
TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBLITY CERTIFICATION
Vendor hereby certifies that his/her service meets or exceeds all specifications in this solicitation, in their entirety, with no exceptions.___________________ (initials)
Technical Capabilities Statement
Item #0002 THREE (3) REGENERATIVE AIR DRYERS
| Shall be provided with the following capabilities, features, and specifications: |
| YES |
| NO |
· The REGENERATIVE AIR DRYER shall provide an extra low dew point to -100 degrees Fahrenheit.
· The REGENERATIVE AIR DRYER shall be capable of handling at least 930 cubic feet minute (CFM) at 125 PSIG
· The REGENERATIVE AIR DRYER shall be 110/120 VAC, 60 HZ, 1 Phase.
· The REGENERATIVE AIR DRYER shall have 2” NPT Inlet and outlet. **(If unit is not equipped with 2” Male NPT Inlet and Outlet connections, contractor to provide adapters as required to provide 2” Male NPT inlet and outlet connections on the unit.)
· The REGENERATIVE AIR DRYER shall be heatless design.
**Heated or refrigerated regenerative air dryers are NOT acceptable.
· The REGENERATIVE AIR DRYER shall comply with Lifting and Rigging requirements as outlined in sections entitled “Requirement for Lifting of Equipment” and “Rigging Sketch Requirements” for contractor equipment at NNSY.
· The REGENERATIVE AIR DRYER shall be free standing and must have forklift slots (capable of being moved with a forklift).
· The REGENERATIVE AIR DRYER shall contain all identifying markings to include:
· Contractor’s name and point of contact information (name, tele#, etc)
· Government Contract Number; Contracting Officer’s information (name, tele#, etc)
· Vessel Name/Code
TECHNICAL CAPABILITY/CONTRACTOR RESPONSIBLITY CERTIFICATION
Vendor hereby certifies that his/her service meets or exceeds all specifications in this solicitation, in their entirety, with no exceptions.___________________ (initials)