N42158-19-Q-0017 ATTACHMENT 1
TECHNICAL CAPABILITY CERTIFICATIONS
Vendor shall self-certify that the equipment and services proposed either meets or does not meet the Government’s minimum requirements specified in the associated Statement of Work (SOW) reference by initialing in the “YES” or “NO” area of the chart below.
Any deviation to the Government specifications shall be identified as such – A detailed explanation shall be provided for each negative response.
Note: In order to be considered for award, the table must be completed in its entirety and submitted with your quotation in accordance with FAR 52.212-1 Instructions of Offerors ADDENDUM.
Technical Capabilities Statement
Item #1 Specifications for Four (4) 20 Ton Air Conditioning Units
| Shall be provided with the following capabilities, features, and specifications: |
| YES |
| NO |
Provide and deliver (4) 20 Ton Air Conditioning Units
Design shall be in accordance with all State and Federal Codes: ANSI, NEMA, NEC, and the ASME Pressure Vessel Code
Units are weather-resistant for continuous use outdoors
Units are saltwater-resistant
All components must be weather-resistant
Must meet or exceed NEMA Type 4 for outdoor use
Must be electric-powered
Must have rated airflow of 8000 CFM
Must lower temperature to 55°F
Maximum size is 106’’LG X 78’’W X 49’’H
Maximum weight is 3,500 lbs.
Full load amps cannot exceed 135 amps @ 460V
Must have electric panel in NEMA 4 metal enclosure with lockable disconnect with Camlok cords
Must come with two (2) 17 1/2”OD inlets, and two (2) 17 ½’’ OD outlets per unit
Must be capable of being used without any recirculation of air
Must have reheat capabilities at 70 kW
Must provide two (2) 18’’DIA X 25’LG insulated flex ducts
Must have stenciled gross weight on four (4) sides per unit
Must have forklift pockets and 4-point certified lift frame
Must be model # JTS-DX-20-MCS-E or equal
Vendor shall provide a rigging sketch that must be attached to unit. Lifting and Rigging must conform to NAVFAC-P-307 Standards
Vendor shall be responsible for all repairs / maintenance
Vendor shall be available within 6 hours of notification for all service related items, including holidays (24/7)
If applicable Vendor shall provide an electronic remote equipment monitoring and/or management tool for use by NNSY Personnel for best and quickest method for communication with vendor
Should a unit breakdown and become inoperable, vendor shall have a replacement box available within 24 hours
Unit shall comply with the applicable OSHA regulations
Unit shall be complete and operational after delivery and setup. Setup shall be complete within 24 hours of installation onboard the ship. The unit shall be highly reliable and shall function without repair or adjustment when set-up is complete. If units initially fail, cannot be repaired within 24 hours, another equal unit must be provided by vendor at no additional cost
Power cable end fittings will be lugged and color coded to indicate proper phasing
Unit shall be capable of being moved via fork lift and/or lifting pad eyes.
The equipment shall be outfitted with suitable attachments for overhead lifting
Each lifting attachment shall be capable of supporting one half the gross weight of the equipment with a design factor of five to one based on ultimate strength
Each lifting attachment shall be designed to accept a standard anchor shackle (Federal Specification RR-C-271D, type IVA) which is capable of supporting one half the gross weight of the equipment
Design of the lifting attachments shall be such that the shackles are not side loaded.
Each lifting attachment shall be conspicuously marked in a contrasting color “Lift Here”. Letters shall have a minimum height of 1”
The lifting sketch shall detail any specific requirements and / or configurations that must be meet prior to lifting (i.e. “engage swing lock”, “Tilt mast back fully”, “Rotate lifting basket over side”, “Utilize 10’ minimum length slings”, “Spreader beam required”, etc.)
The equipment shall be marked in a prominent location with vendor Point Of Contact information, including name and phone number
The equipment shall be marked in a prominent location with the gross weight. Marking shall be upper case letters of a contrasting color, with a minimum height of 1”. Marking shall include the units (i.e. “pounds”, “long tons”, etc.)
In order to be considered technically acceptable, this form must be completed in its entirety.
Vendor shall certify that his product meets or does not meet each specification listed above by initialing in the applicable YES or NO box beside each specification.
Vendor Name and Signature:
Vendor’s Certification is as of _____________________.
Date