Attach 4 Drawings.pdf
PDF 18 MB Posted
- Attached to
- Repairs to Substation 7 Federal contract opportunity
- Solicitation number
- N4008520B2556
About this file
This document provides details on a federal contract opportunity and related file. The solicitation number is N4008520B2556 for repairs to Substation 7 at Portsmouth Naval Shipyard in Kittery, Maine. The Naval Facilities Engineering Command within the Department of the Navy is seeking to update several electrical components in Substation 7 and conduct minor repairs to Building 165. The project description indicates the work includes electrical component updates and minor building repairs. An attachment lists the related drawings.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Opening Results.pdf | ||
| Attachment E _ ES101_RFC_REVB_MH Stamped (002).pdf | ||
| Attachment F _ Substation 7_Specifications_TOC_REVB.pdf | ||
| Attachment I _ PPI Responses (2).pdf | ||
| Attachment H _ Cover Sheet_RFC_REVB.pdf | ||
| Attachment G _ Substation 7_Specifications_33 71 02_REVB.pdf | ||
| Amendment 0002.pdf | ||
| Attachment D - Revised Bid Form.pdf | ||
| Attachment A - PPI Responses.pdf | ||
| Attachment B - 7-20-2020 Site Visit Sheet.pdf | ||
| Amendment 001 N4008520B2556.pdf | ||
| Attachment C - Credere Associates Hazardous Materials Survey 10-23-19.pdf | ||
| DBIDS Access Request From 5500.docx | DOCX document | |
| Scope of Work.pdf | ||
| Solicitation N4008520B2556.pdf | ||
| Base Access Pass Registration 5512.pdf | ||
| Attach 6_ISRL.pdf | ||
| Attach 5 eOMSI.pdf | ||
| Attach 3 Submittal Reg.pdf | ||
| Attach 2 Specifications.pdf | ||
| Attach 1 Bid Form.pdf | ||
| Attach 7_B165 Mitigation Requirements.pdf |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
G-001ES-20-1637
13 WATER STREET
NEWMARKET, NH
PORTSMOUTH NAVAL SHIPYARD
KITTERY, ME
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
G-002ES-20-1638
13 WATER STREET
NEWMARKET, NH
GENERAL NOTES UTILITY NOTES CONSTRUCTION NOTES
EROSION CONTROL NOTES
TRAFFIC NOTES
WINTER CONSTRUCTION
CONSTRUCTION PHASING NOTES
GENERAL SHEET NOTES
GRAPHIC SCALE
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
GC101ES-20-1639
CONSTRUCTION PHASE 1
13 WATER STREET
NEWMARKET, NH
LEGEND
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
GC102ES-20-1640
CONSTRUCTION PHASE 2
13 WATER STREET
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
GC103ES-20-1641
CONSTRUCTION PHASE 3
13 WATER STREET
A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
F-101ES-20-1642
B165 LIFE SAFETY PLAN
13 WATER STREET
NEWMARKET, NH
LIFE SAFETY AND BUILDING CODE DATA
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
CD101ES-20-1643
EXISTING CONDITIONS PLAN OVERVIEW
13 WATER STREET
O
O O O O O O O O O O O O O O
O O
OOOOOOOOOOOOOO
O O
GRAPHIC SCALE
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
CD102ES-20-1644
DEMOLITION PLAN
13 WATER STREET
NEWMARKET, NH
DEMOLITION KEYNOTES
O O O
OOO
O
GENERAL SHEET NOTES
GRAPHIC SCALE
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
C-101ES-20-1645
SITE PLAN OVERVIEW
13 WATER STREET
O
O O O O O O O O O O O O O O
O O
OOOOOOOOOOOOOO
O O
GRAPHIC SCALE
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
C-102ES-20-1646
SITE PLAN
13 WATER STREET
NEWMARKET, NH
NEW WORK KEYNOTES
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
C-501ES-20-1647
13 WATER STREET
NEWMARKET, NH
2PAVEMENT DETAIL, TYP.
1SUBSTATION YARD SOIL PROFILE
3ELECTRICAL TRENCH DETAIL 4CONCRETE PAD @ BUILDING ENTRANCE
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
C-502ES-20-1648
13 WATER STREET
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
C-503ES-20-1649
13 WATER STREET
NEWMARKET, NH
GENERAL CONSTRUCTION NOTES
1TYPE 1 CONSTRUCTION BARRIER
2TYPE 3 CONSTRUCTION BARRIER
3TYPE 2 CONSTRUCTION BARRIER
4TYPE 3 CONSTRUCTION BARRIER
5CONSTRUCTION BARRIER SIGN
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
S-101ES-20-1650
STRUCTURAL LOCUS PLAN
13 WATER STREET
NEWMARKET, NH
1TYP EQUIPMENT SLAB DETAIL
2CONTAINMENT WALL DETAIL
4B165 EX WALL INFILL DETAIL
5LIGHT POLE FOUNDATION, TYP.
GENERAL SHEET NOTES
GOVERNING CODE
CONCRETE AND REINFORCING NOTES
GRAPHIC SCALE
3SWITCH GEAR VAULT DETAIL
02/21/2020
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
S-501ES-20-1651
13 WATER STREET
NEWMARKET, NH
GRAPHIC SCALE
NUMBER
1CHAIN LINK FENCE DETAIL, TYP.
4GATE GROUNDING DETAIL, TYP. 5DROP BAR ASSEMBLY DETAIL
2EAST SIDE GATE, USED AS EGRESS
TYP FENCE POST DETAIL 6
3WEST GATE DETAIL
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
S-502ES-20-1652
13 WATER STREET
NEWMARKET, NH
GRAPHIC SCALE
NUMBER
1SINGLE GATE DETAIL 3LIGHT POLE DETAIL, TYP.2FENCE POST AT EXISTING BUILDING
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AD101ES-20-1653
B165 ARCHITECTURAL DEMOLITION PLAN
13 WATER STREET
NEWMARKET, NH
DEMOLITION KEYNOTES
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE101ES-20-1654
13 WATER STREET
NEWMARKET, NH
LEGEND
NEW WORK KEYNOTES
GENERAL SHEET NOTES
GRAPHIC SCALE
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
B165 ARCHITECTURAL PLAN
13 WATER STREET
NEWMARKET, NH
NEW WORK KEYNOTES
A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE201ES-20-1655
13 WATER STREET
NEWMARKET, NH
GENERAL SHEET NOTES
EXISTING EAST ELEVATION EXISTING SOUTH ELEVATION 6EXISTING WEST ELEVATION
PROPOSED EAST ELEVATION PROPOSED SOUTH ELEVATION PROPOSED WEST ELEVATION
KEY PLAN
7 8 9
NEW WORK KEYNOTES
EAST ELEVATION PHOTO 1 SOUTH ELEVATION PHOTO 2 WEST ELEVATION PHOTO 3
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE202ES-20-1656
13 WATER STREET
NEWMARKET, NH
GRAPHIC SCALE
GENERAL SHEET NOTES
WINDOW LOCATIONS
1WINDOW EXTERIOR 2WINDOW INTERIOR
3WINDOW EXTERIOR 4WINDOW INTERIOR 5WINDOW EXTERIOR 6WINDOW INTERIOR
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE203ES-20-1657
13 WATER STREET
NEWMARKET, NH
5EAST DOOR DEMOLITION (EXTERIOR)
GRAPHIC SCALE
GENERAL SHEET NOTES
6EAST DOOR DEMOLITION (INTERIOR) 7PROP. EAST DOOR (EXTERIOR) 8PROP. EAST DOOR (INTERIOR)
KEY PLAN
1WEST WINDOW DEMOLITION (EXTERIOR) 2WEST WINDOW DEMOLITION (INTERIOR) 3PROP. WEST DOOR (EXTERIOR) 4PROP. WEST DOOR (INTERIOR)
DEMOLITION KEYNOTES
NEW WORK KEYNOTESNEW WORK KEYNOTES
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE501ES-20-1658
13 WATER STREET
NEWMARKET, NH
1TYPICAL WINDOW INTERIOR
GRAPHIC SCALE
GENERAL SHEET NOTES
2TYPICAL WINDOW EXTERIOR
3WINDOW HEAD DETAIL
5WINDOW MEETING RAIL DETAIL
4TYPICAL MUNTIN PROFILE
7WINDOW SILL DETAIL
6WINDOW JAMB DETAIL
WINDOW REMOVAL NOTES
WINDOW RESTORATION NOTES
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
M
ID
-A
TL
A N
TI
C
AE502ES-20-1659
13 WATER STREET
NEWMARKET, NH
AWOOD DOOR TYPE
GRAPHIC SCALE
GENERAL SHEET NOTES
F1PROPOSED FRAME
F2PROPOSED FRAME
1TRANSOM WINDOW HEAD
3TRANSOM WINDOW TO DOOR TRANSITION 4ROOF MOUNTED RAIN DIVERTER
2DOOR SILL DETAIL
D c s B I w w
"' 0 c v
I A
" w i:i z Q.
,J tl • ·e u
> o.;
w " "" z w
G:
ELECTRICAL PHASING
PNSY HAS STRINGENT REQUIREMENTS FOR MAINTAINING ELECTRICAL
SERVICES TO THE LOADS FED FROM B165, SUBSTATION 7 AND THE
FEEDERS AND EQUIPMENT RELATED TO THE PROJECT EXECUTION.
CONTRACTOR SHALL PROVIDE ALL NECESSARY EQUIPMENT, INSTALLATION,
PROJECT MANAGEMENT AND DESIGN SERVICES TO MEET THE CONTRACTING
OFFICER'S CIRCUIT RELIABILITY REQUIREMENTS. PROVISION SHALL
INCLUDE AT LEAST (BUT IS NOT LIMITED TO) THE FOLLOWING:
1. TEMPORARY ELECTRICAL EQUIPMENT INCLUDING GENERATORS,
TEMPORARY PANELBOARDS, SAFETY EQUIPMENT, TEST EQUIPMENT
AND TEMPORARY CABLING
2. OFF HOURS INSTALLATION, TESTING, SUPERVISORY AND OTHER LABOR
3. PROJECT MANAGEMENT SUPPORT OF MEETINGS
4. DESIGN SUPPORT FOR CREATING TEMPORARY SCHEMES, TEMPORARY
SETTINGS, SWITCHING PLANS, EQUIPMENT PLACEMENT, AND OTHER
NECESSARY DESIGN WORK
5. PLANS, PROCEDURES, SCHEDULES, SAFETY REVIEWS, CODE REVIEWS
AND OTHER PLANNING OR WORK DOCUMENTATION
6. COORDINATION WITH PNSY GROUPS AND DEPARTMENTS OR OTHER
PROJECT TEAMS FOR ACCESS TO ANY NEEDED LABOR, LAYDOWN
AREAS, EQUIPMENT, REVIEW OR APPROVAL
ALL ELECTRICAL AND FIRE SUPPRESSION OUTAGES TO BE COORDINATED
WITH NAVFAC INCLUDING, BUT NOT LIMITED TO, NOTIFICATION SIGNAGE,
DOCUMENTATION, ETC.
CONDUCTORS
1. COPPER ONLY
2. INSULATION SHALL BE THHN/THWN. TYPE TW IS ACCEPTABLE
FOR GROUNDS.
3. MINIMUM #12 AWG, EXCEPT CONTROL WIRING IS MINIMUM #14
AWG
4. #12 AWG & LARGER - STRANDED
5. #14 AND SMALLER - SOLID
i. EXCEPTION: STRANDED WIRE AS ALLOWED IN UFGS 26 20
6. TWIST ON CONNECTORS {WIRE NUTS) SHALL BE SUITABLE FOR
BOTH STRANDED AND SOLID WIRE TERMINATIONS. COORDINATE
WITH MANUFACTURER'S TABLES AND RECOMMENDATIONS.
7. TYPE "NM" CABLES ARE PROHIBITED FOR NEW WORK.
i. EXISTING TYPE "NM" EMBEDDED IN WALLS & FEEDING
EXISTING WIRING DEVICES AND UTILIZATION EQUIPMENT
SHALL BE ALLOWED. {EXISTING UTILIZATION EQUIPMENT
RELOCATED TO NEW BRANCH CIRCUITS SHALL BE
CONSIDERED AS NEW EQUIPMENT.)
8. STANDARDS & SPECIFICATIONS:
j. UFC 3-520-01
ii. UFGS 26 20 00
9. COLOR CODE
i. > 240 V: A BROWN B ORANGE C YELLOW
ii. 240 V & BELOW: A BLACK B RED C BLUE
iii. NEUTRAL: WHITE
iv. GROUND: GREEN OR BARE COPPER
10. #14 AWG SOLID FOR FIRE ALARM CIRCUITS
11. COLOR CODE FOR FIRE ALARM CIRCUITS
1. ANNUNCIATION: { +) RED {-) BLACK
ii. INITIATION: { +) ORANGE {-) YELLOW
WIRING DEVICES
1. WIRING DEVICES SHALL BE "SPEC" OR "COMMERCIAL" GRADE AS
A MINIMUM.
2. GENERAL PURPOSE TOGGLE SWITCHES SHALL BE 120/277 VOLT
RATED.
3. PLASTIC WALL PLATES SHALL BE SHAnER PROOF.
4. GROUND FAULT RECEPTACLES SHALL BE SIDE WIRED OR SCREW
CLAMP BACK WIRED TYPE. PROVIDE RECEPTACLES WITH
THROUGH WIRE PROTECTION VIA THE GROUND FAULT CIRCUIT.
5. CAGE CLAMP TERMINATIONS ON WIRING DEVICES ARE PROHIBITED.
6. WIRING DEVICES SHALL BE SCREW CLAMP BACK WIRE TYPE
WHEN TERMINATING WITH STRANDED WIRE. SIDE WIRE
TERMINATION OF STRANDED WIRE IS PROHIBITED.
1. EXCEPTION: SIDE WIRING OF STRANDED WIRE IS ACCEPTABLE
IF TERMINATED WITH CRIMP-ON CONNECTORS.
7. STANDARDS & SPECIFICATIONS:
i. UFC 3-520-01
ii. UFGS 26 20 00
CONDUIT & RACEWAY
1. MINIMUM 3/4" TRADE SIZE
2. RMC - SHALL BE USED
i. IN ALL EXTERIOR LOCATIONS
ii. WHERE BURIED
iii. WHERE CAST INTO CONCRETE
iv. WHERE EXPOSED TO IMPACT/DAMAGE FROM TRAFFIC, STORED
MATERIALS, OR WORK PROCESSES, I.E. GENERALLY ALL
SURFACE MOUNTED INTERIOR SPACES IN INDUSTRIAL AREAS
BELOW 12 FEET AFF AND ALL AREAS THAT ARE SUBJECT TO
CRANE LOAD TRAFFIC.
3. EMT - MAY BE USED
i. IN INTERIOR DRY, CONCEALED LOCATIONS {NOT CAST INTO
CONCRETE)
ii. IN INTERIOR EXPOSED/SURFACE MOUNTED APPLICATIONS, E.G.
IN CEILINGS, AND WALLS.
iii. EMT CONNECTIONS AND COUPLINGS SHALL BE MADE UP
USING STEEL COMPRESSION FITIINGS.
4. DIE-CAST COMPRESSION FITIINGS ARE PROHIBITED.
5. SET SCREW FITIINGS ARE PROHIBITED.
iv. OUTLET BOXES SHALL BE SOLIDLY GROUNDED.
6. DO NOT RELY ON WIRING DEVICE YOKES TO PROVIDE EQUIPMENT
GROUND.
v. STANDARDS & SPECIFICATIONS:
7. UFC 3-520-01
8. UFGS 26 20 00
GENERAL
1. COMPLY WITH CURRENT EDITION OF NFPA 70, NEG
2. CONDITION OF UCE OF EMT VS. RMC, AS INDICATED, AND ONLY
IN ACCORDANCE WITH NFPA70.
3. COMPLY WITH CURRENT EDITION OF NFPA 70E, STANDARD FOR
ELECTRICAL SAFETY REQUIREMENTS FOR EMPLOYEE WORKPLACES
4. COMPLY WITH NECA 1-2006, STANDARD FOR GOOD
WORKMANSHIP IN ELECTRICAL CONSTRUCTION
5. PROVIDE SUBMITTALS FOR ALL ELECTRICAL MATERIALS
6. PROVIDE AS-BUILT DRAWINGS SHOWING ANY CHANGES FROM
DESIGN/CONTRACT DRAWINGS.
7. MATERIALS AND FASTENERS
1. UL LISTING FOR THE INTENDED PURPOSE IS REQUIRED FOR
ANY MATERIAL CATEGORIES WHERE UL LISTINGS ARE
AVAILABLE.
11. ZINC DIE-CAST, ZAMAC, AND SIMILAR "POT METAL"
MATERIALS AND COMPONENTS ARE NOT ALLOWED.
iii. FASTENERS SHALL BE REMOVABLE - NAILS AND OTHER
SIMILAR "DRIVE IN" TYPE FASTENERS THAT CANNOT BE
UNSCREWED ARE NOT ALLOWED.
UNCLASSIFIED
LIGHTING
I
1. INTERIOR LIGHTING
i. STANDARDS & SPECIFICATIONS:
1. UFC 3-530-01
2. UFGS 26 51 00
2. EXTERIOR LIGHTING
i. STANDARDS & SPECIFICATIONS:
1. UFC 3-530-01
2. UFGS 26 56 00
3. INTERIOR DRY LOCATIONS GENERALLY MAY BE NEMA 1, EXCEPT
WHERE SPECIAL EXPOSURES APPLY OR THE NEG REQUIRES, E.G.
INTERIOR SPACES WITH SIGNIFICANT DUST AND CONTAMINANTS
WOULD REQUIRE NEMA 12.
IDENTIFICATION AND MARKINGS
1. WHEN ADDING TO AN EXISTING PANEL THE ENTIRE CIRCUIT DIRECTORY SHALL
BE REPRINTED AND REINSTALLED UNDER A PROTECTIVE CLEAR PLASTIC SHEET.
2. INTERIOR JUNCTION BOXES
i. MARK CIRCUIT AND VOLTAGE ON COVER IN 1" HIGH BLOCK LETTERING
WITH INDELIBLE MARKER.
ii. IDENTIFIER/NAME, VOLTAGE, SOURCE AND DESTINATION WHERE APPLICABLE
iii. E.G. JB 1, 240 V, CKT 17 FROM PP-6 TO EF-3
3. TOGGLE SWITCHES & CONVENIENCE RECEPTACLES.
i. PRINTED TAPE, BLACK LETTERING ON CLEAR OR BACKGROUND COLOR TO
MATCH PLATE.
ii. INCLUDE SOURCE AND CIRCUIT
iii. E.G. PP-6, CKT 13
SAFETY
1. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A WORK SITE
COMPLIANT WITH EM 385-1-1 SAFETY AND HEALTH REQUIREMENTS MANUAL
(MOST CURRENT EDITION) AND ALL OTHER OSHA REGULATIONS ASSOCIATED
WITH THE COMPLETION OF THE WORK.
2. CONTRACTOR SHALL ENSURE ALL WORK COMPLETED MEETS THE
REQUIREMENTS SPECIFIED IN EM 385-1-1 (MOST CURRENT EDITION).
3. THE CONTRACTOR SHALL PREPARE A PROJECT SPECIFIC ACCIDENT
PREVENTION PLAN {APP) AND ACTIVITY HAZARD ANALYSIS {AHA) FOR THIS
WORK.
CIRCUIT BREAKERS
1. WHEN ADDING TO AN EXISTING PANEL, MATCH THE SAME BRAND WITHIN THE
PANEL.
2. PROVIDE CIRCUIT BREAKER KAIC EQUAL TO OR IN EXCESS OF THE RATING OF
THE PANEL AND/OR THE EXISTING BREAKERS.
PANEL BOARDS
1. PANEL BOARDS SHALL BE COMMERCIAL GRADE WITH BOLT -ON CIRCUIT
BREAKERS. SNAP-IN CIRCUIT BREAKERS ARE PROHIBITED.
2. ADDING NEW CIRCUITS TO EXISTING PANEL BOARDS THAT HAVE BEEN IN SERVICE
IN EXCESS OF 30 YEARS SHALL BE COORDINATED WITH THE PWD ME
ELECTRICAL ENGINEERING BRANCH.
3. SERIES RATED CIRCUIT BREAKERS ARE PROHIBITED.
i. IN HIGH FAULT CURRENT INSTALLATIONS IT MAY BE IMPRACTICAL TO
SELECT CIRCUIT BREAKERS WITH EQUIVALENT OR GREATER WITHSTAND
RATINGS. IN SUCH CASES, INSTALLATION OF A PROPERLY SIZED CURRENT
LIMITING FUSE AHEAD OF THE DOWNSTREAM BREAKER MAY BE CONSIDERED.
COORDINATE WITH PWD ME ELECTRICAL ENGINEERING BRANCH.
4. STANDARDS & SPECIFICATIONS:
i. UFC 3-520-01
ii. UFGS 26 20 00
5. THE DESIGNER OF RECORD SHALL BE RESPONSIBLE FOR PROVIDING BREAKER
SETTINGS VIA ELECTRONIC ANALYSIS OF THE SYSTEM.
6. LOW VOLTAGE SWITCHBOARDS USED FOR DISTRIBUTION OF INDUSTRIAL
ELECTRICAL SERVICES TO SHIPYARD FACILITIES (DRY DOCKS, BERTHS) SHALL BE
UNITIZED, ENCLOSED SWITCHGEAR.
1. THIS CLASS OF SWITCHGEAR SHALL MEET THE CRITERIA PREVIOUSLY STATED
FOR GENERAL PURPOSE, SERVICE DISTRIBUTION AS PREVIOUSLY INDICATED .
SEE ADDITIONAL CRITERIA BELOW.
n. THE FAULT BRACING SHALL BE SIZED TO CONSIDER 50% MOTOR
CONTRIBUTION.
UNCLASSIFIED
I
+ I -w I q_
6W
45'
--([]]r---
--3E:---m
I
C><J
__l_ -o o-
-H- --tf--
OR
75550
I
SYMBOLS
FEET
INCHES
NUMBER
AND
PLUS OR MINUS
WITH
CENTER LINE
SIX WAY
DEGREES
DELTA
WYE
PHASE, DIAMETER
GROUND ROD
AUTOMATIC LOAD BREAK SWITCH
DISCONNECT SWITCH
FUSE CUT -OUT
POWER FUSE
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
STATION CLASS LIGHTNING ARRESTER
GROUND
TRANSFORMER
CIRCUIT SWITCHER
DRAWOUT CIRCUIT BREAKER
W/ CURRENT LIMITING FUSE
TEST SWITCH
CONNECTION POINT
SPLICE
TERMINATION
VALVE
NEUTRAL GROUND RESISTOR
YARD LIGHT
ELBOW INSERT
PUSH BUTTON
CONTACT (OPEN)
CONTACT {CLOSED)
BRANCH CIRCUIT OR FEEDER WIRING IN
CONDUIT. TO TICK MARKS INDICATE 2
#12 CONDUCTORS AND 1 #12 GND IN
)2" UON. TICK MARKS, WHEN SHOWN
INDICATE NUMBER OF # 12 CONDUCTORS
IF OTHER THAN THREE; {7) INDICATES
GROUND, CONDUIT LARGER THAN )2" &
WIRE LARGER THAN #12 SHALL BE AS
INDICATED
HOMERUNS TO PANEL. PANEL &
CIRCUIT DESIGNATIONS AS
INDICATED
I
@]1 @]1 @]1
I PBMI 1
GY
®1 ®3 ®1 ®1 @1
@1 @1 cs c cs T
G s
0 occ
ODL
D(D D
K
AMPMETER SWITCH
VOLTMETER TRANSFER SWITCH
CONTROL SWITCH
PARALLEL BALANCING MODULE
VOLTMETER
WATTMETER
POWER FACTOR METER
AMMETER
VAR
TIME OVER CURRENT RELAY
OVER VOLTAGE RELAY
PRESSURE RELAY
TIME OVER CURRENT RELAY {GROUND)
DIRECTIONAL OVER CURRENT RELAY (GROUND)
KILOWATI HOUR / DEMAND METER
SUDDEN PRESSURE RELAY
MICRO PROCESSOR RELAY
THERMOSTAT
DIFFERENTIAL RELAY
LOCK OUT RELAY
RELAY
CONTROL SWITCH CLOSE
CONTROL SWITCH TRIP
PURE SINE WAVE INVERTER
GROUNDING ROD
CIRCUIT BREAKER
LOW VOLTAGE BREAKER
480V LOAD
208 /120V ELECTRICAL PANEL
WALL SWITCH
OCCUPANCY SENSOR
DAYLIGHT SENSOR
LUMINAIRE
FIXTURE SYMBOL
KEYPAD
OC?Cn archilects !engineers
1---c w
13 WATER STREET LL
NEWMARKET, NH
~~----------~--UJ IAPPRDVED U)
FOR COII~AN>jDER NAI·'FAC
ACT IV Ill'
SATISFACTORY TO DATE
DESIGNER WME
DR>WN " NMD
CHECKED BY M H
DESIGN MANAGER A. BE!At-iG~K-
PROJECT "'NAGER A. NEGRON
FEAD/PM&E JEFF HOYT
FIRE PRCT[CTION sr-." R"'lun-;.crr.IN""sK"I ---1
0:::
o_ ~ w b 0::: r-- :z
EPROJECT NO' 1632436
NAVFAC DRAWING NO
12811545
SHEET 24 OF 47
E-001 ES-20-1660
DAAWRlRIII RD1SION: 10 OCTOBER 2014
_j z
B c
RZ
D
E
1 2
UNCLASSIFIED
3 4
01-------- ~ r0 (1YP.) ;-0 (1YP.)
- ---1:~~~ -+--- I ----- - - --- - / - --- - -----1"~ V ./r
~~~.I
1 VR A VR C
c------.,---------, QS) " I ,----".d"-------, SHIP TO SHORE
AC
- INDUSTRIAL POWER
TO SHORE AC #2 TEST WELL
B I
.------c.d~_ --lof-- - --, _1_"_<1_ - "--~~
- P TO SHORE
- ----1 -fl---- ----1
L_j
Ll
·- ~II
DC
I I
~~<1 1--- ~/
- Ll-- ---1
8238 MG SHIP
TO SHORE DC
<1
E~.,~ \i\ ~ jjll I J
: :\ /d 0<1 <1"1
IMAIN TIE \ ~
I 8 I <1
BAY 3 < BAY 2 "
. ·.·•·•· J
- ' <I
I
BAY 1
<I
<1 I
II l : : ~ .j /{914 11 . :l <1 I "l r " _lV~ ~ I .._ I v<J - .lil '"l"'t-+-- --- _Q __ .J...,,r- -----.,.-- --+-, +- -r==U"'=--=-c==;--t-- ---- -+--1-1 •
. . ·· .. ·· I ~ MAIN TIE - A I _""'\J . . " <1
. · .. • .· .···. . w ~~ '- - .4' . \I C'I~I(;R 1 <1 4 <1· i <1 I SWG-R 2- - --'-;~ "C"'H~~===f='=='=~:::;===-~::;::::===i ' ~ --6. 72-4A ·
"' <1 "I"' II " u. . <1 ~ <1 '! ... ~~- - --t-1 . Ll .j ...
I
4 " .j < Ll .,.
<1 Ll . <1 " " .j - -A <I . .f- -A .j c ,______._ --- -. -.
<1 .J. Cjl--- - <1 t--:-- - <1 " "' 4'-:----,----_ _j_ -QI . I <I . J I r----1-----, ~ 1 iffiANSFoRMER B .4t. . '3 1 ... i*ANSFORMER A~ Q '-----,-----,--_J <J " _j A
<I 1 r 1 I 1 "<J .j <1 <1
. <1 " ... ~ C~:.--- - -<1- - -;:::===~=f_ ---::-:.j - . - A ~ Ll . 1- SECTIONALIZING
SWGR 3
72-1A
• • ~ <1 <!"'"' . ~ r CXJ CABINET I --.&.L_ ()() ~ _
I
~~~~-~~~~~c~--~~~-~~.~~·~=c•~~~~~~~ · 1 ~~~~~~~- --- -,~v---- ------<-c•--- -------'----~~---'---------- ~: "' o--- - --- - ---... , ___ - ------1
SUBSTATION 7 GROUNDING PLAN
SCALE: 1" - 5'
1 2
PLAN
NORTH
ffi
UNCLASSIFIED
GENERAL SHEET NOTES
1. SEE GENERAL NOTES SHEET E -001 FOR GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS.
2. GROUND GRID SYSTEM (GGS) HAS BEEN DESIGNED WITH
CONSIDERATION TO SIGNIFICANT UNDERGROUND CONFLICT AND
OBSTRUCTION. GRID DEPTH IS USUALLY 36", HOWEVER
SIGNIFICANT CONCRETE ENCASED SYSTEMS WERE DISCOVERED
DURING TEST PITS. AS SUCH, GGS IS DESIGN FOR A MINIMUM
DEPTH OF 18".
3. SITE PREPARATION REQUIRES 6" OF CRUSHED ROCK WITH A
RESISITIVITY OF GREATER THAN 4200 M-OHMS. BELOW THE
CRUSHED ROCK, 75% GYPSUM, 20% BENTONITE (WELL DRILLER'S
MUD) AND 5% SODIUM SULFATE FOR MITIGATING SOIL (OR
EQUIVALENT) IS RECOMMENDED WITH A RESISITVITIY EQUAL TO OR
LESS THAN 1 0 M-OHMS TO A DEPTH OF 4'-2". BELOW 4'-2",
IT IS ASSUMED FROM TEST PITS AND DISCUSSIONS OF LOCAL
RESOURCES, SALTY-SANDY MOIST LOAM WITH GRAVEL LIES
BENEATH.
4. ABOVE GRADE GROUNDING CONDUCTOR SHALL BE ROUTED ALONG
SIDE AND UP CONCRETE PADS WHERE NECESSARY. GROUNDING
CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY
USE OF SCHEDULE 80 CONDUIT FROM 12" BELOW GRADE TO
12" ABOVE OR BEYOND EDGE OF CONCRETE PADS •
5. MAXIMUM RESISTANCE OF GGS TO GROUND SHALL BE 25 OHMS
OR LESS. SYSTEM CONTINUI1Y MUST BE 1 OHM OR LESS.
NEW WORK KEYNOTES
1. SITE CONTRACTOR SHALL DETERMINE SITE RESISTIVITY AFTER
REPLACEMENT OF EXISTING SOIL AS A MINIMUM, A 4 POINT
WENNER METHOD SHALL BE EMPLOYED TO MAKE THIS
DETERMINATION. MINIMUM 5 TESTS SHALL BE PERFORMED THROUGH
OUT SITE. ONE AT EACH CORNER AND A FINAL TEST AT SCOPE OF
WORK CENTER. REPORT TEST RESULTS AND FINDINGS TO COR .
2. EXTEND GGS 3' BEYOND FENCE LINE.
3. INSTALLING CONTRACTOR SHALL PROVIDE PROPOSED TEST WELL
DETAIL
4. 3/4" X 10' CU CLAD GROUND ROD (TYP.) BURY TO DEPTH
EQUIVALENT TO GROUNDING GRID SYSTEM (GGS). EXOTHERMIC OR
NON-REVERSIBLE COMPRESSION BOND TO GGS (1YP.).
5. 250 MCM STRANDED BARE SOFT DRAWN CU (TYP.). BURY TO 18"
DEPTH OR GREATER.
6. EQUIPMENT GROUND - 4/0 STRANDED BARE SOFT DRAWN CU
{TYP.).
7. EQUIPMENT BOND (1YP.).
8. FLEXIBLE BRAIDED CU 4/0 MCM EQUIVALENT (1YP.). AT ALL
SERVICE GATES. BOND TO SERVICE GATE.
9. INSTALL EQUIPMENT GROUND BAR.
LEGEND
[] TEST WELL • BOND CONNECTION
A. EQUIPMENT BOND 0 3/4" X 10' CU GROUND ROD
--- UNDERGROUND GROUND GRID SYSTEM 250 MCM CU
- - - ABOVE GROUND EQUIPMENT BONDING JUMPER
'----- BRAIDED FENCING BONDING JUMPER
GRAPHIC SCALE
5 2.5 0 5 10 15
1, - 5' scale feet
CHECK GRAPHIC SCALE BEFORE USING
OGCn architects I enginee~
D c w
13 WATER STREET LL
NEWMARKET, NH
1-::==:--------L- c.n c.n
1-z :5 ' Cl f-
(J) 0:::
w 0:::, 1632436 a..
DRAWF'ORI.I REVISION: 10 ooroeER 2014
:z:
B
~ B w s
I .
I .
QUANTITY MANUFACTURER PART NUMBER
3 THOMPSON* 573BT
3 THOMPSON* 81
3 THOMPSON* 688
12 THOMPSON* 663BT
11 THOMPSON* 82-2
11 THOMPSON* 690
1 THOMPSON* 690
AS REQUIRED THOMPSON* 188M
AS REQUIRED THOMPSON* 32 STANDARD
AS REQUIRED THOMPSON* 14 cu
AS REQUIRED THOMPSON* -
UNCLASSIFIED
3 4
,)f------- 20' -------¥------- 20' -------7(-,------ 20' --------it'
LIGHTNING PROTECTION BILL OF MATERIALS
DESCRIPTION
3/8" X 24" SOLID COPPER AIR TERMINAL WITH NICKEL PLATED TIP, BLUNT TIP, WITH ADAPTER.
18" LONG BRACE FOR USE WITH 24" AIR TERMINALS. PLATED STEEL TRIPOD BRACES HAVE 1/4" DIAMETER LEGS AND ARE FOR USE WITH 3/8" THROUGH 5/8" DIAMETER AIR TERMINALS.
PREMIUM DIE CAST BRONZE POINT BASE FOR ADHESIVE MOUNTING ON FLAT ROOFS, ETC. THE BOLT PRESSURE CABLE CLAMP IS FOR CABLES THROUGH NO. 506. THIS BASE HAS AN EXTERNAL STUD FOR USE WITH ADAPTER TYPE AIR TERMINALS. THE STUD HAS 5/8 - 14 MALE THREADS. ORDER ADHESIVE SEPARATELY TO SUIT ROOFING SYSTEM IN USE.
3/8" X 36" SOLID COPPER AIR TERMINAL WITH NICKEL PLATED TIP, BLUNT TIP, WITH ADAPTER.
24" LONG BRACE FOR USE WITH 36" AIR TERMINALS. PLATED STEEL TWO LEG BRACES HAVE 1/4" DIAMETER LEGS AND ARE FOR USE WITH 3/8" THROUGH 5/8" DIAMETER AIR TERMINALS.
MOUNTING FEET ARE FIELD FORMED AND CAN BE SECURED WITH BOLTS, SCREWS OR NAILS AS REQUIRED.
VERTICAL POINT BASE FOR CONNECTION BETWEEN ADAPTER TYPE POINTS AND CABLE THROUGH NO. 506. STUD HAS 5/8 - 14 MALE THREADS.
VERTICAL POINT BASE FOR CONNECTION BETWEEN ADAPTER TYPE POINTS AND CABLE THROUGH NO. 506. STUD HAS 5/8 - 14 MALE THREADS.
COPPER WRAP-AROUND STRAP AND CLIP CABLE SUPPORT FOR SECURING CABLES THROUGH NO. 506 TO PIPES UP TO 2" O.D.
MAIN CONDUCTOR. 32 STRANDS OF 17 GAUGE COPPER WIRE, 7 /16" DIAMETER, BRAIDED SMOOTH TWIST 65,500 CIRCULAR MILS, NET WEIGHT 215 LBS. PER 1000 FT.
SECONDARY CONDUCTOR. 14 STRANDS OF 17 GAUGE COPPER WIRE, 1/4" DIAMETER, 28,500 CIRCULAR MILS, NET WEIGHT 92 LBS. PER 1000 FT.
CABLE HOLDERS AND FASTENERS.
BILL OF MATERIAL COMMENTS:
QUANTITIES AND DESIGN ARE FOR REFERENCE. MASTER CERTIFIED LIGHTNING PROTECTION CONTRACTOR TO VERIFY QUANTITIES AND INSTALLATION REQUIREMENTS PRIOR TO COMMENCING WORK.
*THOMPSON LIGHTNING PROTECTION PRODUCTS ARE LISTED AS REFERENCE. EQUIVALENT EQUALS ARE ACCEPTED.
NECESSARY APPURTENANCES SHALL BE PROVIDED BY PROTECTION CONTRACTOR.
SUBSTATION 7 LIGHTNING PROTECTION PLAN
SCALE: 1" = 5'
PLAN
NORTH
e?
UNCLASSIFIED
16'
16'
16'
GENERAL SHEET NOTES
1. SEE GENERAL NOTES SHEET E-001 FOR GENERAL NOTES,
SYMBOLS, AND ABBREVIATIONS.
2. GROUND GRID SYSTEM (GGS) HAS BEEN DESIGNED WITH
CONSIDERATION TO SIGNIFICANT UNDERGROUND CONFLICT AND
OBSTRUCTION. GRID DEPTH IS USUALLY 36", HOWEVER
SIGNIFICANT CONCRETE ENCASED SYSTEMS WERE DISCOVERED
DURING TEST PITS. AS SUCH, GGS IS DESIGN FOR A MINIMUM
DEPTH OF 18".
3. SITE PREPARATION REQUIRES 4" OF CRUSHED ROCK WITH A
RESISITIVITY OF GREATER THAN 4200 M-OHMS. BELOW THE
CRUSHED ROCK, 75% GYPSUM, 20% BENTONITE (WELL DRILLER'S
MUD) AND 5% SODIUM SULFATE FOR MITIGATING SOIL (OR
EQUIVALENT) IS RECOMMENDED WITH A RESISITVITIY EQUAL TO OR
LESS THAN 1 0 M-OHMS TO A DEPTH OF 4'. BELOW 4', IT IS
ASSUMED FROM TEST PITS AND DISCUSSIONS OF LOCAL
RESOURCES, SALTY-SANDY MOIST LOAM WITH GRAVEL LIES
BENEATH.
4. ABOVE GRADE GROUNDING CONDUCTOR SHALL BE ROUTED ALONG
SIDE AND UP CONCRETE PADS WHERE NECESSARY. GROUNDING
CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BY
USE OF SCHEDULE 80 CONDUIT FROM 12" BELOW GRADE TO
12" ABOVE OR BEYOND EDGE OF CONCRETE PADS.
5. MAXIMUM RESISTANCE OF GGS TO GROUND SHALL BE 25 OHMS
OR LESS. SYSTEM CONTINUITY MUST BE 1 OHM OR LESS .
6. LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED BY A
MASTER CERTIFIED INSTALLER.
0 NEW WORK KEYNOTES
1. 36" AIR TERMINAL EXOTHERMICALLY OR NON-REVERSIBLE CRIMP
BONDED TO (GGS) WITH SECONDARY CONDUCTOR.
2. ALONG ROOF LINE, 24" AIR TERMINAL EXOTHERMICALLY OR
NON-REVERSIBLE CRIMP BONDED TO GROUND GRID SYSTEM.
MINIMUM #2/0 SOFT DRAWN STRANDED COPPER.
3. ALONG ROOF LINE, 24" MOUNT AIR TERMINAL ON TOP OF LIGHT
STANDARD. ROUTE GROUNDING CONDUCTOR DOWN LIGHT
STANDARD WITH INSULATED STANDOFFS SUPPORTING CONDUCTOR
EVERY 3'. BOND CONDUCTOR TO ROOF TOP GROUNDING
CONDUCTOR.
4. MAIN LIGHTNING CONDUCTOR: ROOF TOP GROUNDING CONDUCTOR.
5. SECONDARY LIGHTNING CONDUCTOR: BONDED TO GGS. ALL
LOCATIONS (TYP.).
6. MAIN LIGHTNING CONDUCTOR: TO RUN ALONG TOP OF FENCING
AND BONDED AT AIR TERMINALS (TYP.).
7. WHEN EXOTHERMIC WELDS ARE USED, PROPER INTEGRITY
ASSURANCES WILL BE REQUIRED. AT A MINIMUM, HAMMER STRIKE
TESTS ARE RECOMMENDED. CONTRACTOR IS RESPONSIBLE FOR GGS
INTEGRITY AND PROPER INSTALLATION. MECHANICAL ATIACHMENTS
TO EQUIPMENT WITH APPROPRIATELY SIZED LUGGING IS
ACCEPTABLE. TYPICAL AT ALL LOCATIONS.
1" - 5'
LEGEND
SYSTEM BOND
LP SYSTEM AIR TERMINAL
LPS MAIN CONDUCTOR
LPS SECONDARY CONDUCTOR
GRAPHIC SCALE
5 2.5 0 5 1 0 15 seale feet
CHECK G~APHIC SCALE BEFORE USING
OC?G
architects I engineers
D c w
13 WATER STREET LL
NEWMARKET, NH
~~--------~-Ul APPROVED Ul
FOR COMMANDER NIIVFAC
ACTIVITY
SAnSFACTORY TO DATE
DESIGNER WME
NAVFAC DRAWING NO.
12811547
SHEET 26 OF 47
EG102 ES-20-1662
ORAWFORM REVISION: 10 OCTOBER 2014
::J z:
D B c;
w
1 2
UNCLASSIFIED
DC-- DC-- DC--
I
De
DC,--
DC-- DC-- DC-- DC--
u
EXISTING PANEL TO REMAIN
I
De/
Dc-
De oc- "'' "VlfXj~
EXISTING PANEL 208V 0 ---.....~ I
~~RVICE PANEL i"i LIGHTS AND CONDUIT "" I
: ~ I (TYP.) """
:-------> eX
EXISTING VAULT I • I IN; M ~· ~-""'
lo\ M NEL • --; OPENING IN SLAB ~~ '"' • _ , • REMOVE CONDUIT AND WIRING ~ ?I
\::._/ RE ovE PA __ ~ ____ / ~ IH+Itlm l [r\ : •• "' • • 'IF;. ,~;~~}o c~sLE "'TAP _- • ..!¢>.. ~ EXISTING SERVICE -~ · e L ~ ~ .J ~ ~ . . , · c5 ~~ . . . . '" . · . . ·· ; .
1-· · • PANELS TO REMAIN ~ =:-1 ff I I 1. • 7 _ ••• ~~~~--·~..:....r--:...-....:....1 . ·• lo\ EXISTING 2Q8V -........___ ·· .· , ~ ~ I I ..... , • , · ;-;;\ ITp,NJSf vtiMU< • o • :'.
\::._/ SERVICE PANEL . -· __ · .---·----.__ .-· I I ~ • " • \!:.._/ lo· _ T 42 .'. • • • _ ff
;-;;\ EXISTING. 120V --,. "" la"in~ -~ I I J;V ·_ •• o •0-· . . ·. ··~ : .
\!:.._/sERvicE PANEL.-·· " 1 1. (\ 1tl • 1 m~~-~ lf:\1 - 1: ~ , · _ ••• _ --~ ~
. .. . ~ "-.)" 5 101 . . . .0 • :\ ~ (j). STATION SERVICE ,_ ~~ F- MAIN! TIE I A o • . "' ", . •• •
. SWITCHBOARD AND ~ ~I- I- 2 1 1 •• _ ~ . o • - · tvN'rl"Jr •• • o • ·
. · .· TRANSFORMER --..........._ t= 1 I • • :si , ~ • ~ • • • •
;-;;\ EXISTING 480V ~ t;;, ,., ~ -~ I I ' -~ ·,.·~· --"-·-·_·"",·k'. ~. ~ •• • • \!:.._/ SERVICE PANEL - '\~~ MAIN TIE B l L J ~· r;: . • • . .:
EXISTING i\ l:.
I I
PAD 1
. · . -_· "o ..
~ <l .,_ d <I <l. ... .. " d
<l·- ..
4 :. . <:1 " ... .. .... <l
PORTABLE
RECTIFIER
EXISTING
PAD 2 -, ~ \o·
•• p. • :. • • -'-• • 0 RANSFDRME ~· "" ·.: :·., ·.:· : •• i \. ~ ~ ~S;:~~~ :~ o ..... "·. ... •o... ~·· .... ~.. . ~
" - !. --." .· -·.. . . . • o • • I • ", • • , •", •• -.-.. __ ·.. r\:: .. .. <l-., .,.. : <l ~ "., ~ f2\ a
• · - • • . . ., • - 1• . • .. • • o ru ~ ;s, .~ \!:.._/ r
1-." - . ; . DDI2 lEST (T 4E) • • •• ••• • • • :. • • • • ~ • . • • • • ~ I
Ac --------
AC --------
AC --------
AC --------
Ac --------
Ac --------
Ac --------
Ac --------
AC --------
AC --------
AC-99 J
AC --------
AC --------
AC
ELECTRICAL EQUIPMENT DEMOLITION PLAN
SCALE: 1" - 5'
1 2
PLAN
NORTH
EB
AC-- AC --
U NCLASSI FlED
AC --
SHIP TO
SHORE AC #1
" <l .. - "' .
......... ~-....J
AC-- AC--
AC-- AC-- AC--
GENERAL SHEET NOTES
1. SEE SHEET E -001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
2. DEMOLITION WASTE TO BE MANAGED PER SPECIFICATION 01 74
19.00 22.
3. REMOVE LCI-25 CABLE BACK TO AC-99. MAINTAIN OTHER
SERVICE POINTS. RE-USE CONDUIT.
4. DD2 WATER BOOSTER PUMP - REMOVE T-42 AND SWITCH.
DISCONNECT CABLE AT B242.
5. 72-1A: DISCONNECT AND PULL FEEDER CABLE TO AC-99 FOR
FEED RE-USE.
6. CONTRACTOR SHALL PROVIDE AN APPROVED OUTAGE AND
ENERGIZATION PLAN IDENTIFYING CIRCUIT OUTAGES PRIOR TO
DE-ENERGIZING CIRCUITS.
7. CONTRACTOR SHALL PROVIDE ALL NEEDED TEMPORARY
ELECTRICAL EQUIPMENT AND INSTALLATION TO MEET PNSY
ELECTRICAL CIRCUIT ELECTRICAL SERVICE CONTINUITY
REQUIREMENTS.
Q DEMOLITION KEYNOTES
1. REMOVE EXISTING SHIP TO SHORE BOX. MAINTAIN UNDERGROUND
AC ~--1
CONDUIT ACCESS FOR RE-USE WITH NEW EQUIPMENT.
2. EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED.
3. REMOVE EXISTING 480V BUS WORK AND B165 WALL PENETRATION.
4. REMOVE EXISTING RACEWAY AND B165 WALL PENETRATION.
5. REMOVE EXISTING CABLE TRAY.
6. REMOVE/RELOCATED BY GOVERNMENT DURING CONSTRUCTION.
7. EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED. PREPARE
JUNCTION BOX AT LOCATION FOR SPLICING TO EXISTING CIRCUITS.
8. EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED. NEW PANEL TO
BE PLACED AT THIS LOCATION FOR TIE IN TO EXISTING LOAD
CIRCUITS.
9. EXISTING ELECTRICAL EQUIPMENT TO BE REMOVED AND RETURNED
TO THE GOVERNMENT.
GRAPHIC SCALE
5 2.5 0 5 10 15
1" - 5' scale feet
CHECK GRAPHIC SCALF BEFORE USiNG
OGGn architects I engineers c w
13 WATER STREET LL
NEWMARKET, NH
~~----~--~-UJ
APPROVED UJ
FOR COf.O.!ANDER NAVFAC
ACTMTY
S47!SFACTORY TO DATE
DESIGNER WME
EPROJECT NQ., 1632436
NAVFAC DRAWING NO.
12811548
SHEET 27 OF 47
ED1 01 ES-20-1663
DAA'NFORM REVISIOH: 10 OCTOBER 2014
s z
'13
·g_ w
D c
E A i'n z
"' 0
0-g w
DC-- DC--
DC--
Oc
DC,-- DC--
DC-- DC-- DC--
oc
E 1---1-+-- ELECTRICAL
0 PANEL 480-1_ •...
EXISTING LIGHTING
. CONTACTOR .·
EXISTING LOAD HOUSE
PANEL
MANHOLE
. Ll". <1
. Ll .. .,:
<1 G.a . 0 ..
EMERGENCY HIGH "0
PRESS AIR
COMPRESSOR
EXISTING CRANE HOTEL CIRCUITS
IT] LV-1
0 LOW VOLTAGE
. SWITCHGEAR
W3
Ac -------
MAIN TIE- A 0
<t
.d ... ., ... <t f
L..-,-,_;;t.<t_..:...· ----, TRANSFORMER A TRANSFORMER B
0 0
Ac -------
Ac -------
Ac -------
Ac -------
Ac -------u u
De
I I
J----- DC 312 VAULT
l>
TO DD2 ~~ i';
WATER PUMP \f "-I De
VR A VR B VR C
UNCLASSIFIED
PROPOSED VOLTAGE
c REGULATOR CONTROL
SHIP TO SHORE
AC #1
DC -- ~EL , ..... _..,.. ~-.,..-----'
~ B238 SHIJ'lcTO Dc -- Dc ~
U
PANEL 208-1 011· ," ---...;""'+'!':-! ,-------., ;-· .;:..<~-"'"'"'--, r---'-"1
CONTROL CONDUIT
<t
NEW JUNCTION I
BOX
I
· INDUSTRIAL
l>
J
POWER TO ''"
·. SHORE AC #2). "'&r------'""---, "<t
. L'l <1.
SUMP PUMP
INDICATOR ·. u<t·
. . . ·. 4
<t
SW R 1
BAY 3
<t
<I
<t
.• . .d
<1 4
<t
'-------,.----' q
Ac -------
Ac -------
Ac -------
Ac ------- Ac
·<t
<t o0 SHORE DC #~
SHIP TO SHORE ·
DC #2
<1 r---------, :-o
BAY 2
<1
<t· .
Ll
6:1 0 1\ 0 ·"
PLAN
NORTH
SWGR 2
<t
0~
<t
ELECTRICAL EQUIPMENT AND CONDUIT PLAN ffi SCALE: 1 II = 51
2 3
UNCLASSIFIED
·.o~ <I
.1 -<t
0 <I
BAY 1
<t
L
<t
<I
SWGR 3
0~
Ac~- Ac~-
AC AC AC -
GENERAL SHEET NOTES
1. SEE SHEET E-001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
2. UNDERGROUND CONDUIT IS 5" FOR 15kV CLASS WIRING, 2" FOR
600V CONTROL WIRING.
3. PROVIDE AND INSTALL BREAKER LIFT SYSTEM FOR GOVERNMENT
SUPPLIED TRANSPORTABLE SUBSTATIONS PER TRANSPORTABLE
SUBSTATION BREAKER LIFT SPECIFICATION DATED 02/12/2020.
0 NEW WORK KEYNOTES
1. INSTALL ALUMINUM POLE MOUNTED 5000K, 289 WATT LED FLOOR
LIGHT. POLE HEIGHT TO BE 15' -0".
2. INSTALL ALUMINUM POLE MOUNTED 5000K, 163 WATT LED FLOOD
LIGHT. POLE HEIGHT TO BE 15' -0".
3. INSTALL ALUMINUM POLE MOUNTED 5DOOK, 289 WATT LED FLOOR
LIGHT. POLE HEIGHT TO BE 15' -0".
4. REPLACE AND RE-WIRE EXISTING POLE MOUNTED FLOOD LAMP ON
B165 WITH A 5000K, 289 WATT LED FLOOD LIGHT. RE-USE
CONDUIT IF CONDITION AND LOCATION IS VERIFIED ON FIELD TO BE
SUITABLE.
5. INSTALL YARD OUTLET EACH FROM SEPARATE 50-AMP BREAKER
DESIGNATED, TERMINATE AT 50 AMP 3R STAINLESS STEEL FUSED
SAFETY DISCONNECT SWITCH (208/120 THREE PHASE, FOUR WIRE).
6. INSTALL NEW ELECTRICAL EQUIPMENT.
7. INSTALL NEW SHIP TO SHORE BOX. COORDINATE LOCATION AND
EXISTING CONDUIT LINES WITH EXISTING CONDITIONS.
8. TRANSFORMERS A & B SHALL BE DESIGNED WITH NO MAINTENANCE 1-------t
ACCESS REQUIREMENT ON THE FENCE SIDE OF THE EQUIPMENT.
OGGn orcllilects I engineers
D w
9. KTR SHALL MEASURE, SUPPLY, AND INSTALL 600V IP66 BUSWAY
MEETING UL 857 AND NEMA BU-1 WITH RATING OF 3200A
MINIMUM. ALL SUPPORTS, FITTINGS, AND ANCILLARY EQUIPMENT
SHALL BE INCLUDED. ALL TRANSFORMER AND SWITCHGEAR
CONNECTIONS SHALL BE COORDINATED BY KTR TO MEET
REQUIREMENT OF THE INSTALLATION CONDITIONS AND
ARRANGEMENTS.
13 WATER STREET LL
NEWMARKET, NH
~~--...;..--t_ if)
APPROVED U)
10. PROVIDE 2" CONDUIT BETWEEN B165 INTERIOR AND VOLTAGE
REGULATOR AREA. EACH END SHALL HAVE WEATHERPROOF PIANO
HINGED JUNCTION BOX. 14" X 14" X 8" WITHIN B165 NEAR PANEL
FOR CO~MANOER NAVFAC
ACTIVITY
208-1. 12" X 12" X 4" MOUNTED NEAR VOLTAGE REGULATOR ON I-SA-nsc-ACTO_RY_To -DATE ___ _
STANCHION. UTILIZED BY PNSY TO ROUTE CAT6 CABLE. DESIGNERWME
DRAWN BY CGN
11. SHALLOW VAULT BELOW EACH SWITCH ASSEMBLY PROVIDED TO CHECKED BYMH
ALLOW CABLE STORAGE AND EASE OF LANDING. SWITCH DESIGN M>W.GER A. BELANGER
ASSEMBLIES SECURED ATOP A THROAT THAT EXTENDS ABOVE PROJECT MANAGER A. NEGRON FEAO/PN&E JEFF HOYT FINISH GRADE TO ALLOW RUNNING TEMPORARY CABLES. "" PROTECTION s. R
0 :0:: w
12. CONTRACTOR SHALL PROVIDE AND INSTALL LADDER CABLE TRAY ~ o ":. ~ MEETING THE REQUIREMENTS OF NEMA VE1. PROVIDE FIELD ~ t- ~ , oz~~
MEASUREMENT OF INSTALLATION LOCATION, FITTINGS, HANGERS AND " ~ ~ ~
ALL RELATED INSTALLATION BASED ON THE FINAL ELECTRICAL :!!: ..J ~ "'
EQUIPMENT SIZES, CABLE ENTRY POINTS AND MOUNTING. ~ 1: ~ 0
~----------------------------------------~~0~ ~ LEGEND ;~~ (/)
0::::
0..
~----------------------------------------~5 I ~ -oil!
~z
B,C,D
---o
@TO@
(DTO@
@To@
YARD OUTLETS
YARD LIGHTING
B= 5000K, 289 WATT MEDIUM FLOOD
LED LIGHT, FULL VISOR
C= 5000K, 163 WATT MEDIUM FLOOD
LED LIGHT, FULL VISOR
D= 5000K, 289 WATT WIDE FLOOD LED
LIGHT, FULL VISOR
CONDUIT DOWN
CONDUIT/CABLE RUNS SHOWN ON E-602
CONDUIT/CABLE RUNS SHOWN ON E-601
DD2 WATER BOOSTER PUMP CONDUIT
B165 WALL DESIGNATION
o__ 0 w :z 0:::: r---- 0
CJ
z a:
w w z CJ z w w I-.., ~ :Jz 0 W l;; {) i ~ ::::)
'<<{'a_
~U.ffi Bj~ :z:...Jj!!-' ... <{!ll """"""" .... > "' "' ...,::::: o<(~z
!ZZJQ~
"' i =o
~----------------------------------------~~ ~ 6 ~0~-n;~o_~~~--~
EPROJECT NO.o 1632436 GRAPHIC SCALE
NAVFAC DRAWING NO.
5 2.5 0 5 10 15 12811549
1" - 5' SHEET 28 OF 47
scale feet
CHECK GRAPHIC SCA.LE BEFORE USING ES 1 01 ES-20-1664
5 ORAWFORN REVISION: 10 OCTOBER 2014
::s :z
·a
D c
QA
Jl in z
~ ·e i N w "J G:
-DC--
De
DC-- DC--
DC·--
DC-- DC--
DC-- DC--
De
DC----
u
DC
u
,, -~- ,, ,, --:i:/~ " ~oc~ ~ ~
0 '"" Xor;--X X--------«
I l>
I l>
UNCLASSIFIED
Oe I IX-------;----- X-c I 6l ~ l> x x~x___:______,__x x~ x x· x · x~x . x~x X:-4----X --~ . x· •c ----------- "De -------- M . 4
, A DC ---_ ,--~-.r----, ~
I. , .,.. . ------"'x ~-----6l( \ ,-~-----:--c-+..--0.,..5"' -:-~---;-0.,.,.5' ___ o".5 __ ,.,3.u e ~ De ---_ De --l.r-...o:-"'~....-v-'-----, · .
· ·<~ :or- "..,->l'.f-r---~-...;-?i'-f-<1 .-1 -?!'.f- . r -,I' "" SHIP TO SHORE . 4', <I .
<I 4_; I ~ (j4 " . . ()
I I 0
<I ·.
"- • "- VR B VR C ·. r/IJ : ~~ De "" AC #1 " . f1lt. , D~---_ DC~ 4
De ~ · 'lf.l.l _j "" 8238 SHif'eTO oc DC -
<I
VR A
. ~~·/r~~ o ,=======t~~==~~~
I ~ <1 ·. 4 o0 o0 SHORE DC #~
~ ""' 4 5.o· I / 0 II II I ~ _L _ .J L _ .J L _ .J 0e SHIP TO SHORE "'
-t 3.o· t r [ * .. ·· l '-J.D; p --- t<,\111 ;t•L J .___ <I c. 4
_, ~ DC #2 2.1J•
/C)
<~ I---7L~~~---------..-------------4b,~·~l·~~----~ ' ./ • ' • • <I <I 3.0
. l::::-'-- J H r- L .. ~ ] r I I
F-1111 I 1-' ~ I MAIN tiE -/ .• .·
Uu - 1-B 1-14 'f I 1'--
1 3.0' I I '
- I I II { I I I
- I I 3~~ \I I I I I \. I : :
r-- _L _j -l---t-f--+--------+- ---l..rl--rT-i-1
~ p"' <I & ,.--~---'"'"-----, <I r-'---· . __ __,j~·
'" L <1.
0 0<1. ·.
"' <I_ <I_ <I
.-~.~··-. ~1·.~ .. ] . . . 4 .11 . ·I 5.fl' _.
BAY 3
<1_4
<I <I
• <I •
<I
.. 4.' <I
BAY 2
q r~--~ 4 5.o'l I
L~---------i . <I '
. <I .
. . .. I :J -.h.o' J< ""' WJN TIE - A - 3.0' J< IIJ SW< R I •
<I • 1 ~
SWGR 2
,f- 4.0' ......;
" <I ., <I <1
6.0'
" <I
BAY 1
<I
() <I
<I
<I
<I
-<I r-=:. "' j<:- 4 o· -.
'---~--' ,, _· ______c·· ___ _j -1 I I~ . <I . u· <1,. . . <I 4 . ~ .IL.---1- -.,--"'..., .. A' <I .• < 0 r: 3.2· ~ 4 . • 4 ... £ <I .·.<I' r.: .. "' . «~'
I. -- . - <I_ . - • <I .. .. " . <I " 4 I ... <I . - r ... ,J
. . r «~· .. <I " \ A I ..__ 5.0' -.r J". 4 . «~ l 3.0' f .. <I '" . . '>!' 3.C • 41<- '0 : . ~ 1· ~- "f -r""' -=-.· ·~:~ 5.0'1 I ¥ .. ..3.1L' ~--+"-..,____ - - 1 <I • ~- a:._,\-'r-----..... -'----: .. L......-,,-r"-"--'-------j---v-v . "1-f---t--"--~~'---j I I ~ I I t . 1 <I TRANsFoRMER A __ ·21 TRANSFORMERs ~L.<~.'-;-+·0_·-_·-: .. =====·<l~~-~5-+---o;::r~_+1~-:~~---f3: .. ~~:-. ==<1-----4====:----'-------'--<1 LL _ -1-r
, _<I_. <I -I 4 ~-5.o'----'--; - - - ,__.~ ~ -t----14
A'l ,.() 00 4. . <I . 4 I I . . . . L ·-· .+-------..,...-...,........._...:..... - .. __._ ___ __,..,......1...4--- f--'
. ~- . X <!<I X· X . X . X<r .4 X X ·Ji---+-:X x· X. . X X--:-'f--r--. --...-.. 1- " ., =--I -;,..:-X -------c-X.A.J X~X-c-1---X x· X X X / I
A C ......________
Ac ......________ A C ......________
A C ......________
A C ......________
A C ......________
A C ......________
AC ......________
A C ......________
A C ......________
A C ......________ Ac
ELECTRICAL LAYOUT AND CLEARANCE PLAN
SCALE: 1 II - 51
1 2
PLAN
NORTH
ffi
AC -- AC--
UNCLASSIFIED
AC--
SWGR 3
X~
I"" t
AC-- AC --- AC --
AC-- AC-- AC --1
GENERAL SHEET NOTES
1. SEE SHEET E -001 FOR GENERAL NOTES, SYMBOLS, AND
ABBREVIATIONS.
LEGEND
EQUIPMENT CLEARANCE
PROPOSED EQUIPMENT
GRAPHIC SCALE
5 2.5 0 5 10
1" - 5' scale feet
NIJ!I;ll\1':
OGG,
architects I engineers
D c w
13 WATER STREET LL
l':;p;cN£oN~EW_M_AR_K_E_T,;..N_H_f- U) U)
1-
1632436
NAVFAC DRAWING NO.
12811550
ES-20-1665
ORAWFORM REVISION: 10 OCTOBER 2014
:5 u :z o B d c iii
-f "6
" i A m z "-, g ·e Q_
N w w
G:
1 2
1 2
. <J <J .
Ll <1 . <J
UNCLASSIFIED
PLAN
NORTH
~1~~17!~~~~~~ AND EQUIPMENT DEMOLITION PLAN ffi
PANEL 208-2
PANEL 208-1
-/I
I // I L'_ - ~',],_____, I I I I
-----t;-1 ~ I
I I I
I I I I
I I I I I I I I '1---1- L _ _j
PLAN
NORTH
' 4
8165 LIGHTING AND EQUIPMENT PLAN ffi SCALE: 1 I 4" = 1' -0"
UNCLASSIFIED
GENERAL SHEET NOTES
1. DEMOLITION WASTE TO BE MANAGED PER SPECIFICATION 01 74
19.00 22
2. THERE ARE FOUR (4) EXISTING STRUT MOUNTED PENDANT 4 FOOT
LONG, SINGLE BULB FLORESCENT STRIP LIGHT FIXTURES. POWER
SUPPLIED FROM THE LIGHT SWITCH BY THE SWITCHGEAR NEXT TO
THE DOOR ENTRANCE.
3. THERE ARE TWO (2) COMBINATION EMERGENCY EXIT/BATIERY
FLOOD LIGHTS.
0 DEMOLITION KEYNOTES
1. REMOVE CEILING MOUNTED PENDANT FLUORESCENT LIGHT FIXTURES
AND DOME PENDANT LAMPS FROM LIGHTING PANEL AND ALIL
SUPPORTS, WIRING CONDUIT AND HANGERS. (12 TOTAL).
2. REMOVE ALL B165 INTERIOR 120/208 RECEPTACLES, LIGHT
SWITCHES, THERMOSTATS, ELECTRICAL HEATERS, AND ASSOCIATED
WIRING.
D NEW WORK KEYNOTES
1. INSTALL A THREE-WAY LIGHTING SWITCH AS SHOWN. WIRE SWITCHES
TO PANEL 208-1 •
2. INSTALL LED LOW BAY LIGHT ( 1 0,000 LM) 1 0' ABOVE FINISH FLOOR.
3. INSTALL LED LOW BAY LIGHT (4,000 LM) 10' ABOVE FINISH FLOOR.
4. INSTALIL GFI PROTECTED 20 AMPERE RECEPTACLES ALONGSIDE BUS
A. WIRE TO PANEL 208-2.
5. INSTALL GFI PROTECTED 20 AMPERE RECEPTACLES ALONGSIDE BUS
B. WIRE TO PANEL 208-1.
6. INSTALL EXIT SIGN OVER DOOR. INCLUDE EMERGENCY LIGHTING.
LIGHTING TO BE LITHONIA LIGHTING LLXC (2) 6V, 5.3W LIED LAMPS
(1 PER HEAD).
7. INSTALL NEW HEATERS WITH ELECTRONIC THERMOSTAT.
8. INSTALL LED LOW BAY LIGHT (10,000 LM) WITH BATIERY BACKUP
BALLAST, 1 0' ABOVE FINISH FLOOR.
EXISTING LIGHTS
ELECTRICAL WIRING
SINGLE BULB LED STRIP LIGHTING
THERMOSTAT
THREE-WAY LIGHTING SWITCH
GFI RECEPTACLE
ILLUMINATED EXIT SIGN
'-------'' E,F
PROPOSED LIGHTING
E= LED LOW BAY LIGHT, 46" LONG,
10,000 LM
1/4" = 1'
F= LED LOW BAY LIGHT, 46" LONG,
4,000 LM
GRAPHIC SCALE
4 2 0 4 8 12 scale feet
CHECK GRAPHIC SCALE BEFORE USING
OC?Cn architects I engineers c w
13 WATER STREET Li._
NEWMARKET, NH
1-:,P=PRO~V£D ___ .;...,_i-~
FOR COMMANDER NAVFAC
ACTIVIT\'
SATISFACTORY TO DATE
DESIGNER WME
DRAWN BY CGN
CHECKED BY MH
DESIGN MANAGER A. BELANGER
PROJECT M~AGERA. NEGRON
NAVFAC DRAWING NO.
12811551
SHEET 3Q OF J, 7
EL 1 01 ES-20-1666
ORAWFORW REVISION: 10 OCTOBER 2014
u :z c
3--Ll t!LL
~ 3tn-o',_J u i?Z p .Q u w s
8 B w
1 I
1 I
2 I
UNCLASSIFIED
AUX POWER RECEPTACLE L 14-50R ,
SUMP PUMP INDICATOR 125/250 VAC SINGLE PHASE, F~UR
(SEE GENERAL NOTE 6) .~ WIRE THREE p LE
LIGHT SWITCH WITH INDICATOR LIGHT
(SEE GENERAL NOTE 3)
B165 SOUTH WALL
3' -7" AC#2
SURFACE LEVEL ~
ib::~~::.;;L~:....:::: ~~Jf,..;,:~~~?~c~~L?__;V;.,;_A:..::....U::..:L T_;;;E.....;.L:..::....EC;;,_;T...;;_;R,;....;;.IC.;....;.AL::..:E=L=E...;,.;.VA...;,.;.T...;.,.;IO;..;...N;..__ ______ _,CD
UP TO LIGHT SWITCH
ON EXTERIOR OF
BUILDING 165
l
I .. ... ..... • •• .• • • • • • • . . . ....... •"'f ·-. • • • . 4 : • ....... 'f .... ,. ·-.· • ...t··· .. ··· •..• ·....... ·.• .• ·..• • ••• · . ·-.··. · ....... li ~·;;--
#1 PVC COATED RMC 6
#12 2 #12 GND TO
PANELBOARD 208-1
120/208V IN BUILDING
• •'•• o o'T • f 'o' • oo o o hoo oo • •• o o o o o o o .. ·'" •• •• •'\' "'4. • •••• • •••••• 0 ••• • • • • ••• 0 •• ••• ., ·"'. Jj • •• • • • • . . . , . .. . . . . . .. . . . . . . . . . . .. ':. . . . .... : v .. :· . . . " ~ I ... . . .•.
V VAPOR TIGHT 24 WATT,
WET LOCATION,
GASKETED 4' LED
STRIPLIGHT (TYP. 3)
3/4" PVC COATED RMC _j
6" X 6" X 4" J-BOX -
WITH HUBS ~
SUMP PUMP AND
HIGH LEVEL SWITCH
• •• <;• 12" X 12" X 4" ; v (4X STAINLESS STEEL) •:.O •• SS J-BOX ;- : . v
:~:1 ----- 3/4" PVC COATED RMC
I ----ko~ WITH 4 #12 1 #12 v--- .· · GND
~ (2) DEDICATED 20A
GFCI RECEPTACLES
~SU~B~ST~A~TI~ON~7~V~A~UL~T_E_LE~CT_R~IC_AL_P_~_N~--------------~/-2 ~)
SCALE: NOT TO SCALE \. ~
2 I
UNCLASSIFIED
I
GENERAL SHEET NOTES
1. DEMOLISH EXISTING LUMINARIES, SUMP PUMP, AND LIGHT
SWITCH.
2. ALL CONDUCTORS FOR LIGHTING AND RECEPTACLES SHALL BE
#12 THHN UNLESS INDICATED OTHERWISE.
3. RECEPTACLE/SWITCH BOXES SHALL BE CAST PVC COATED WITH
THREADED HUBS. RECEPTACLES SHALL HAVE IN-USE COVERS.
4. ALL CONDUIT IN VAULT AND EXPOSED EXTERIOR CONDUIT SHALL
BE PVC COATED RMC, TO INCLUDE FITTINGS, CONDUIT BODIES,
CLIPS, BACKERS, HUBS, SCREWS AND WASHERS SHALL BE
STAINLESS STEEL.
5. FEED TRANSPORTABLE AUX POWER RECEPTACLE FROM
PANELBOARD 208-1 WITH 30A 2-POLE BREAKER, EXTEND 3/4"
RMC WITH 3 #8 1 #10 GROUND.
6. SUMP PUMP INDICATOR INCLUDES THREE 1" BRIGHT LED LAMPS.
WHITE LIGHT INDICATES THAT POWER IS AVAILABLE AT THE PUMP.
g 0 " "' " "'
~ i'i li: ~ I
~ fl
GREEN LIGHT INDICATES THAT THE PUMP IS RUNNING. RED LIGHT I-
INDICATES A HIGH LEVEL CONDITIONS.
7. ALL ELECTRICAL EQUIPMENT AND WIRING SHOWN ON THIS
DRAWING TO BE PROVIDED AS NEW EXISTING CONDUIT BOXES TO NI!JfnrL
BE REUSED IF DETERMINED SUITABLE.
LEGEND
~...I _____ ___,, 4' LED STRIPLIGHT
ELECTRICAL WIRING
SINGLE BULB LED STRIP LIGHTING
GFI RECEPTACLE
OGCn orchileds I engineers w
13 WATER STREET u_
NEWMARKET, NH
t::=-----1---U) M'PROVED (/)
FOR COf.IM~ND[R ~'AVFAC
ACIIVIH
SATISFACTORY TO DAT£
DESIGNER WME
DRAWN BY CGN
CHECKED BY MH
DESIGN MANAGER A. BELANGER
PROJECT MM<AGER A. NEGRON
FEAD/PM&E JEFF HOYT
"RE PROTECTION s. RUCINSKI
:z :5 a..
....I C) 0::
t;
I..I.J ....I I..I.J
:z t;)
CD
U')
EPROJECT NO.. 1632436
NAVFAC DRAWING NO.
12811552
SHEET 31 OF 47
EL 1 02 ES-20-1667
DRAWFORW REVISION: lQ OCTOBER 2014
:5 z
B f-
N
: B c v
Q
~ ·g_ c-
! A if> in z
I <.0
-l'i v ·e
> N w " ~ z
2' -1 /2"
REMOTE TRIP RECEPTACLE, TYP. (3)
CABLE PIGTAIL. FULLY MOLDED
ASSEMBLY TO RECEPTACLE
PROVIDE A MEANS OF LIFT
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
REAR OF UNIT
PROVIDE OPENING ON BOTIOM
OF UNIT FOR CABLE AND
CONDUIT ENTRY FROM
EXISTING PAD
SHIP TO SHORE DC#1 - BOTTOM
SCALE: NOT TO SCALE
COMMUNICATION BOX. MOUNTED AND -----+--!!..__ ____ -_ -_ -J-t----1--_J
TERMINATED BY GOVERNMENT
FOLLOWING COMPLETION OF
CONSTRUCTION
SHIP TO SHORE DC#1 - SECTION
SCALE: NOT TO SCALE
1 2
UNCLASSIFIED
PROVIDE A MEANS OF LIFT
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
,j' v
.)'------ 2' -1/2" ------i(
UNCLASSIFIED
ANCHOR FOR MOUNTING UNIT
TO CONCRETE PAD
2' -7"
GENERAL SHEET NOTES
1. MAINTAIN REMOTE TRIP CIRCUITS. DISCONNECT, RE-ROUTE, AND
RECONNECT PRIOR TO REQUIRED WORK.
2. INSULATED CONDUCTORS MUST BE RATED 600 VOLTS UNLESS
OTHERWISE NOTED AND CONFORM TO THE REQUIREMENTS OF
NFPA 70.
3. PROVIDE EACH FEMALE RECEPTACLE WITH A FULLY MOLDED
ASSEMBLY AND CABLE.
4. PROVIDE EQUIPMENT WEIGHT AND DOCUMENTATION SUPPORTING
LIFTING EYE CARRYING CAPABILITY.
0 NEW WORK KEYNOTES
1. PROVIDE NEW 20A, 125/250V 3 POLE 4-WIRE NEMA
CONFIGURATION L14-20 TRIP RECEPTACLES SUITABLE FOR
MARINE USE.
2. PROVIDE FEMALE RECEPTACLE BLOCK HOUSING, 12 GAUGE
STAINLESS STEEL, WITH FEMALE HOLDING BARS MOUNTING
HARDWARE AND GASKETS.
3. GOVERNMENT SHALL REMOVE CONTROL CIRCUIT WIRING, JUNCTION
BOX, AND TERMINATION. COIL AND PROTECT WIRING PRIOR TO
CONSTRUCTION.
4. PROVIDE 1/4" X 2" NEOPRENE GASKET CEMENTED AT ALL
REMOVABLE PANELS.
5. PROVIDE REMOVABLE PANEL.
6. COORDINATE CABLE AND CONDUIT ENTRY WITH EXISTING PAD.
VERIFY OPENING DIMENSIONS IN FIELD.
z z
I M ~ 0
SEAL
OC?Gn architects I engineers
D c w
13 WATER STREET LL
NEWMARKET, NH
~-=~--~---L-Ul
APPROVED (/)
FOR COMMAND~R NAVFAC
ACTI~'iTY
SATISFACTORY 10 DATE
DESIGNER WME
DRAWN BY NMD
CHECKED BY MH
DESIGN MANAGER A. BELANGER
PROJECT MANAGER A. NEGR=ON...,__--1
FEAD/PM&E JEFF HOYf FIRE PROTECTION s. RU I
EPROJECT NO.· 1632436
NAVFAC DRAWING NO
12811554
SHEET 33 OF 47
E-1 02 ES-20-1669
ORAWFORM REVISION: 10 OCTOBER 2.014
_j u z c
E A iii D m 0> m z Q_
I u w 0::
u
N
J 2 I
/ REAR OF UNIT
\_ PROVIDE OPENING ON BOTTOM
OF UNIT FOR CABLE AND
CONDUIT ENTRY FROM
EXISTING PAD
UNCLASSIFIED
ANCHOR FOR MOUNTING UNIT
TO CONCRETE PAD
__ SH~I P_T~O~S __ H....;...OR_E_D_.;;.C...;._#2_-...;._B....;...OTT~O-M_--c( -1 "')
SCALE: NOT TO SCALE '- ~
REMOTE TRIP
RECEPTACLE, TYP. (3)
PROVIDE A MEANS OF LIFT
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
'0 ~
CABLE PIGTAIL. FULLY MOLDED ~ • • I s:114 ASSEMBLY TO RECEPTACLE ~ v L:..J
~ ·V~ (~ ~r----~~/ v / .__I-----· COMMUNICATION BOX. ~ & • t---~
MOUNTED AND TERMINATED I L..::.J
BY GOVERNMENT FOLLOWING
COMPLETION OF
CONSTRUCTION
I
Q Q
2 I
PROVIDE A MEANS OF LIFT ~
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
'0 0
UNCLASSIFIED
I 4
I 4
GENERAL SHEET NOTES
1. MAINTAIN REMOTE TRIP CIRCUITS. DISCONNECT, RE-ROUTE, AND
RECONNECT PRIOR TO REQUIRED WORK.
2. INSULATED CONDUCTORS MUST BE RATED 600 VOLTS UNLESS
OTHERWISE NOTED AND CONFORM TO THE REQUIREMENTS OF
NFPA 70.
3. PROVIDE EACH FEMALE RECEPTACLE WITH A FULLY MOLDED
ASSEMBLY AND CABLE.
4. PROVIDE EQUIPMENT WEIGHT AND DOCUMENTATION SUPPORTING
LIFTING EYE CARRYING CAPABILITY.
D NEW WORK KEYNOTES
1. PROVIDE NEW 20A, 125/250V 3 POLE 4-WIRE NEMA
CONFIGURATION L14-20 TRIP RECEPTACLES SUITABLE FOR
MARINE USE.
2. PROVIDE FEMALE RECEPTACLE BLOCK HOUSING, 12 GAUGE
STAINLESS STEEL, WITH FEMALE HOLDING BARS MOUNTING
HARDWARE AND GASKETS.
3. GOVERNMENT SHALL REMOVE CONTROL CIRCUIT WIRING, JUNCTION
BOX, AND TERMINATION. COIL AND PROTECT WIRING PRIOR TO
CONSTRUCTION.
4. PROVIDE 1/4" X 2" NEOPRENE GASKET CEMENTED AT ALL
REMOVABLE PANELS.
5. PROVIDE REMOVABLE PANEL.
6. COORDINATE CABLE AND CONDUIT ENTRY WITH EXISTING PAD.
VERIFY OPENING DIMENSIONS IN FIELD.
z "' I
OGGn architects I engineers z
1---c w
13 WATER STREET L.t_
NEWMARKET, NH
~A=PPRC~Vill~--------~-~
FOR COW/ANDER NAVFAC
ACTIVITY
SMISFACTORY TO DATE
OCSIGNER WM E
DRAWN BY NMD
CHECKED ovMH
DESIGN MANNOER A. BELANGER
PROJECT MANAGER A. NEGRON
FEAD/PM&E JEFF HOYT
FIRE PROTECTION s. RUCINSKI 0 2 w z z < 0 - <(
~-!5 "' ol-o >-' uz"' "' "'::5!;1 w z 0 1-
- Q. "' ~~I 0 z • Q
~0~ 1- :::E w~:;:
(/) § VI "'
I'! ! ~ 0:::
~0~ CD
<( .::z Q_ 0 <( :z
~~ w <C ~~ 0::: r----- LU
0 Cl 0 ~z: (/)
(!) NO I z Nl-cr: ...---- <( N w II- "'*~:::
w z c..oCJ1 (..)
..--OJ Cl z 2:::J LU w o:::CJ1 a::
C/) ::c w (/)
1-.., 2 _JZ oW 0
$0~ ~:::J I-
<<(I il: 0...
ZLJ..!z: E :E "' "' V)2 (/) :I:....l~ t-<( ::;!2 "->fh :;::
o<("" z
~z~ I
"' "' 5 ,. 1il 0 li: u "' < - 22 a. ~ "' "' "' 0
0 ~ CL
[PROJECT NO 1632436
NAVFAC DRAWING NO.
12811556
SHEET 35 OF 47
E-104 ES-20-1671
ORAWFORM REI/lSIOO: 10 OCTOBER 2Q14 u z
B
1---c
;p J_U w....__
"L_ E--
:iUJ
"UJ
~ I p cZ r::)
v w f= s
:c w
I w v
B c v v c ·e;, c w
§A w w z wl m u w
I 2
/ REAR OF UNIT
I
~ PRO~DE OPENING ON 80TIOM
OF UNIT FOR CABLE AND
CONDUIT ENTRY FROM
EXISTING PAD
UNCLASSIFIED
3 I
ANCHOR FOR MOUNTING UNIT
TO CONCRETE PAD
SHIP TO SHORE AC#1 - BOTTOM r-" .:;SC~A~LE;...: ~NO~T~T~O~S::-:C..:;;AL-::-E..;.;;:;;;...;...;:.;:::...;.;_..;._....::....::::......:......:......:::::....:..:...:. __ -{'- 1 ..1
REMOTE TRIP RECEPTACLE, TYP. (3),\ROVIDE A MEANS OF LIFT -
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
D ~ LJ•\o a •D
1 r---t--L. -[) 0 Q •
CABLE PIGTAIL. FULLY (r/ Y
MOLDED ASSEMBLY TO ~
RECEPTACLE
. VG
/ 7.-'-----, COMMUNICATION BOX. ~ •
MOUNTED AND TERMINATED / r
BY GOVERNMENT (/
FOLLOWING COMPLETION /
OF CONSTRUCTION •
SHIP TO SHORE AC#1 - SECTION
SCALE: NOT TO SCALE
I 2 I
PROVIDE A MEANS OF LIFT ~
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
0 0
!.. 1'-7" ,, -r2) ' ..1 -
UNCLASSIFIED
I.
'I
I
GENERAL SHEET NOTES
1. MAINTAIN REMOTE TRIP CIRCUITS. DISCONNECT, RE-ROUTE, AND
RECONNECT PRIOR TO REQUIRED WORK.
2. INSULATED CONDUCTORS MUST BE RATED 600 VOLTS UNLESS
OTHERWISE NOTED AND CONFORM TO THE REQUIREMENTS OF
NFPA 70.
3. PROVIDE EACH FEMALE RECEPTACLE WITH A FULLY MOLDED
ASSEMBLY AND CABLE.
4. PROVIDE EQUIPMENT WEIGHT AND DOCUMENTATION SUPPORTING
LIFTING EYE CARRYING CAPABILITY.
D NEW WORK KEYNOTES
1. PROVIDE NEW 20A, 125/250V 2 POLE 4-WIRE NEMA
CONFIGURATION L14-20 TRIP RECEPTACLES SUITABLE FOR
MARINE USE.
2. PROVIDE FEMALE RECEPTACLE BLOCK HOUSING, 12 GAUGE
STAINLESS STEEL, WITH FEMALE HOLDING BARS MOUNTING
HARDWARE AND GASKETS.
3. GOVERNMENT SHALL REMOVE CONTROL CIRCUIT WIRING, JUNCTION
BOX, AND TERMINATION. COIL AND PROTECT WIRING PRIOR TO
CONSTRUCTION.
4. PROVIDE 1/4" X 2" NEOPRENE GASKET CEMENTED AT ALL
REMOVABLE PANELS.
5. PROVIDE REMOVABLE PANEL.
6. COORDINATE CABLE AND CONDUIT ENTRY WITH EXISTING PAD.
VERIFY OPENING DIMENSIONS IN FIELID.
0::
I e
OC?Gn architects I engineers z li:
c w
13 WATER STREET Lt_
NEWMARKET, NH
APPRGVi:D UJ
!'OR COMMANfJER NAVFAC
AWill'l'
SATiSFACTORY TO DATE
DESIGNER WMr!lE..--___ , DRAWN BY NMD
CHECKED BYMH
DESIGN MANAGER A. BELANGER
PROJECT MANAGER A. NEGRON
FEAD/PM&E JEFF HOYT
FIRE PROTECTION s. RUCINSKI
EPROJECT NOc 1632436
NAVFAC DRAWING NO
12811558
SHEET 37 OF 47
Q::
:c
E-1 06 ES-20-1673
DRAWFORI.t REVISION: 10 OCTOBt:R 2014
__j
:z :::::::J
• 2 c
'iii
'6 ~ • "" c--c
§A D
" "' in z
~I u • ·e l:l N w
1 I 2 I
)f-------- 2'-10 518" ---------7(
3' -7" •
•--_,__-+_j_j 6 CD
INDUSTRIAL POWER TO SHORE AC#2- TOP r-"'
~SC~A~LE~:~NO~T~T~O-S-CA-LE~~~~~~~~~~~~--~ 1 )
lf-k -------- 2' -10 518" -------~~ l CD! (TYP.) r0 (TYP.) rf3l (TYP.) l J /L_j
3 ~f8" h-. --+. --. -+-. --. ----f/'-.-rl 1-T.--. --. --. --. --.-rl ~ (TYP.)
~~r~~ @ & @ @ ~®~~@==~@==~"'==~@~
5 114" • 0 1 ; 0 • • ., s F=lr====t-==1=-=l
-'1.--t++-. 0 @ (~) @ •7J •
4 318"
0 •
• ~ () Q 0~ ~(TYP.)
5 1 I 4" 2 6 "
~(JOO~ ~ 0 0 0 ~
4 318"
3' -1 0"
5 114" • 3 • • 7 •
----'!.---+++-. ~ 0 () () "' . • ~C)CJC)~.
4 318"
• • • 0 {!;] q; G) 0
5 1 I 4" ® 8 1."
• " 0 0 0 ~ ~(TYP.)
8 31 4"
INDUSTRIAL POWER TO SHORE AC#2 - FRONT
SCALE: NOT TO SCALE
1 I 2 I
UNCLASSIFIED
3 I 4 jf! -------- 2'-10 518" ---------71'1' l
I'- REAR OF UNIT
V v- PROVIDE OPENING ON BOTIOM
OF UNIT FOR CABLE AND
CONDUIT ENTRY FROM PAD
3'-7" / .
I v- GROUNDING BAR r ANCHOR FOR
I MOUNTING UNIT TO
CONCRETE PAD
INDUSTRIAL POWER TO SHORE AC#2 - BOTIOM -
/ "' 2 ) SCALE: NOT TO SCALE
D•
CABLE PIGTAIL. -r-..._ •
FULLY MOLDED ' ~~
ASSEMBLY TO V ,£" .
RECEPTACLE (V
~ vr
~ .,CV.
(TYP.)~ ~
•D
• YG(TYP.)
• /~(TYP.)
\,._.1
PROVIDE A MEANS OF LIFT \
STRUCTURE WITH 4-POINT
LIFT (TYP. 4 PLCS.)
0 0
INDUSTRIAL POWER TO SHORE AC#2- SIDES r-, ~SC~AL~E~:~NO~T~T~O~S~CA~LE~~~~~~~~~~~~~------;\ 4)
UNCLASSIFIED
I
GENERAL SHEET NOTES
1. PROVIDE EACH FEMALE RECEPTACLE WITH A FULLY MOLDED
ASSEMBLY AND 100' 535 DLO FINE CABLE WHIP.
2. INSULATED CONDUCTORS MUST BE RATED 600 VOLTS UNLESS
OTHERWISE NOTED AND CONFORM TO THE REQUIREMENTS OF
NFPA 70 .
3. SHORE POWER PHASE IDENTIFICATION
BLACK= A PHASE
BLUE= B PHASE
RED= C PHASE
4. EXOTHERMICALLY WELD 410 GROUND TO BOX, EXTEND GROUND
TO AN EXTERNALLY MOUNTED GROUND BAR .
5. ALL ENCLOSURE ARE NEW EQUIPMENT.
6. SPECIFICATION 26 05 33 PROVIDES THE ENCLOSURE MATERIAL,
PAINT, FABRICATION, AND MOUNTING DETAILS.
7. PROVIDE EQUIPMENT WEIGHT AND DOCUMENTATION SUPPORTING
LIFTING EYE CARRYING CAPABILITY .
~\\\\\IUIII411tlll:
»''' !'lEW H..}'~
#~r§ -~~\ l-==---------------------1 ~~ MICAH \~'t, 0 NEW WORK KEYNOTES (~':' ~~~1~20 k) \.. ~caas~ g:l
1. PROVIDE FEMALE RECEPTACLES FOR CIRCUITS 1 THROUGH 8. ·-., '8 ~ C
DURALINE FEMALE E1 023 LATCHING J STYLE PER PHASE FOR ?r"''tl'IO \. ~-$1 I';{, BLACK CONNECTOR WITH BLACK CAPS. If', y b V---::;,_
2. PROVIDE FEMALE RECEPTACLES FOR CIRCUITS 1 THROUGH 8.
DURALINE FEMALE E1023 LATCHING J STYLE PER PHASE FOR
BLUE CONNECTOR WITH BLUE CAPS.
3. PROVIDE FEMALE RECEPTACLES FOR CIRCUITS 1 THROUGH 8.
DURALINE FEMALE E1 023 LATCHING J STYLE PER PHASE FOR
RED CONNECTOR WITH RED CAPS.
4. PROVIDE 30 DEGREE ANGLE THREE GANG FEMALE RECEPTACLE
BLOCK HOUSING, 12 GAUGE STAINLESS STEEL, WITH FEMALE
HOLDING BARS MOUNTING HARDWARE AND GASKETS.
5. PROVIDED ENGRAVED LABELS WITH CIRCUIT ID FOR EACH BLOCK,
NAMING CONVENTION FOR EACH LABEL WILL BE COORDINATED
AND APPROVED IN THE FIELD WITH CONTRACTING OFFICIAL.
6. PROVIDE 1 I 4" X 2"NEOPRENE GASKET…