STATEMENT OF WORK

I. Title: Delivery and setup of a 64 x 24 temporary trailer for Code 300. Trailer to be located inside the Controlled Industrial Area (CIA) at the Portsmouth Naval Shipyard. The final location is to be determined by the TPOC prior to delivery.

II. Technical Point of Contact (TPOC): Mark Callahan, Code 981, is the Portsmouth Naval Shipyard TPOC. The TPOC will provide contractor directions to placement of the Code 300 trailer. TPOC will ensure all services, i.e., electrical, communications, water and sewer, are ready to be connected prior to execution of this contract. Contractor shall notify the Navy’s TPOC prior to commencing and upon completion of services.

III. Period of Performance: (POP): 7/15/15-7/14/16 with two (2) option years IV. Background: A temporary trailer is needed to allow sufficient space for Code 300 pre-planning team.

V. Scope of Work: Contractor shall provide all labor, material, and tools required to deliver, and setup temporary trailer. The trailer location to be determined. Contractor shall ensure the trailer’s interior seam at the connection is linear, neat, and secure. Contractor shall be responsible for properly leveling the trailer. Contractor shall remove all excess material and waste generated by the move, and shall leave the site in a neat and orderly fashion.

VI. SECURITY: No person not known to be an American citizen of good standing and repute shall be allowed access to Portsmouth Naval Shipyard. Proof of citizenship may be required.

VII. Trailer specs:

Standard Minimum Requirements that shall be met or exceeded for standard trailer rental Size

1) 64’ long (including hitch)

2) 60’ box size

3) 24’ wide nominal

4) 8’ ceiling height nominal

Interior Finish

1) Open floor plan

2) Panel walls

3) Vinyl floors

4) Gypsum ceiling

Electric

1) Work/Unit shall meet current:

a. NFPA 70 - National Electrical Code

b. NFPA 101 - Life Safety Code

2) Disconnect: Exterior 200 amp fused or breaker controlled 110/208V Single phase / 4 Wire disconnect. Whip provided by customer.

3) Panel: 100 amp interior panel with GFCI breakers for all 120v receptacles

4) Lights: grid mounted fluorescent lights w/T-8 lamps and protective covers

5) Exterior Lights: Fluorescent or LED lights w/Battery back-up emergency feature @ exterior doors (Photocell controlled)

6) Emergency: Dual head exit/emergency light w/ 90 Minute battery backup

7) AC / Heating shall be 220 volts.

8) Wall outlets on all four interior sides (minimum of 12 20amp duplex receptacles on a minimum of 4 dedicated 20 amp circuits. All receptacles shall have face plates ( all must be GFCI protected)

9) (2) 20amp circuit and minimum of (4) 15amp duplex outlets shall be located overhead in ceiling structure within each unit center line of each split structure that comprising one Unit.

10) Exterior entry for data and telephone lines

Windows/Doors

1) Horizontal/Vertical Slider windows

2) Mini blinds shall be installed at each vision panel

3) Vision Panel doors with Standard locks

4) Door kick plates shall be incorporated

5) All standard door shall be 36” wide unless noted in the attachments

Exterior Finish/Frame

1) Wood or vinyl siding

2) I-Beam outrigger frame

3) Standard drip rail gutters

4) Rain diverters above door openings

5) Skirting from base of unit to ground level

6) Power gable end roof ventilation system

7) Removable Tongue

8) Shall provide a sufficient amount of tie downs straps that meet or exceed industrial standards

Heating and Cooling

1) Central air conditioning and heating units

2) Thermostatic temperature controls

Statement of Work Installation of Code 300 trailer