Specifications for Fiberglass Shelter

CONSTRUCTION:

Dimensions: 10' x 20' x 8' (wall height) Insulation: ~R-10, 1.5" thick.

Wood, 3/4" plywood encapsulated within end walls surrounding large bulkheads

EXTERIOR:

Color exterior, Custom Color System: FAA Orange and White UV resistant gel coat with simulated brick appearance Qty 4, U-Bolt, 3/8" stainless steel for shipping tie-down. Can be used for off-loading if no metal base frame.

Qty 6, Sealant, 14.5 ft roll ConSeal-Bituman blend for weather-tight interface with concrete base. (ships loose)

INTERIOR:

Color interior, white gel coat.

Qty 1, Flange, internal, 1/4" thick FRP fiberglass, at least 2" wide, for attachment to floor (by others).

Qty 1, Hole, pre-drilled in mounting flange, 24" on center, 7/16" diameter.

DOORS, ACCESS, PENETRATIONS:

Qty 1, Door, single, 4'-0"W x 6'-8"H, rain drip edge, high-end industrial hydraulic closer. Raised step-over threshold.

Qty 1, 3-point door hardware; latches top, bottom, and middle. Pad-lockable, anti-entrapment.

Qty 2, Bulkhead, 6' x 6' FRP bulkhead without core & gelcoat. Wall bulkheads to be RF transparent windows with FRP structural support as needed.

ELECTRICAL DISTRIBUTION:

Qty 1, Load Center, single-phase, NEMA 1, 120/240V, 20 space, 40 circuit, up to 100 amp main breaker.

Qty 12, Leviton BR20-W White Duplex NEMA5-20R Qty 1, Conduit, Schedule 40 PVC. Wiring per latest NEC.

ILLUMINATION:

Qty 1, Switch, two-way, 20 amp, weatherproof.

Qty 4, Light, interior, 4 ft,, 3 T8 lamps (32 Watts each), vapor-proof, fluorescent, 120-277V.

Qty 1, Light, exterior 70 watt High Pressure Sodium wall pack, 120V, photocell operation, cULus Listed, E-conolight E-WW2H071ZP.

HVAC:

Qty 1, Air Conditioner, 208/230 volt, single-phase, 3-ton with heat, supply and return filter grills, and thermostat.

Qty 1, Vent, 12" gravity louver, aluminum blades, galvanized steel frame, insect screen.

Qty 1, Fan, 12" diameter, aluminum blades, galvanized steel frame, up to 800 CFM.

Qty 1, Thermostat, 30-110F, 120-240V, located within 5 ft of fan.

Qty 2, Rain Hood, 16" FRP weatherproof, matching shelter exterior color (may ship loose).

DESIGN SPECIFICATIONS:

25-Year limited warranty.

Roof Load: 20 psf.

Wind Load: 120 mph

OPTIONS & ALTERNATES (for additional cost when requested):

1) Bulkhead, rectangular, allows user to cut through wall (or roof), for any penetration larger than 2" diameter, and maintain 25 Year Warranty.

2) Wood, 19/32" Oriented Strand Board (OSB) encapsulated within interior surface of walls, roof and doors for International Building Code (IBC) 15 minute thermal (fire) barrier.