| Line Item # | Description | Qty |
| 0001 | Cooling System | 1 |
| 0002 | Shipping to 22448 | 1 |
| Salient Charcteristics: | ||
| Mandatory Requirements: | Minimium 48.5 GPM at 50 psi | |
| Closed Loop Cooling System | ||
| Air-cooled heat exchanger | ||
| Heat Exchanger Capacity @ 92F Ambient Dry Bulb Air Temperature: 500k BTU/hr |
| Pump Station: | Process pump sized for 48.5 GPM at 50 psi |
| 240 gallon reservoir with sight glass, drain, fill port, process return connection, and tank blanket valve regulator | |
| 2" piping supplied with shut-off valves, pressure gauges, check valve and strainer | |
| 460V/3Ø/60Hz UL508A Listed, NEMA-4 Electrical Control Panel to include disconnect; control circuit transformer; motor starter for the pump; and ON/OFF selector switch. Factory mounted, wired and tested. | |
| Pumping station is to be fully assembled, skid-mounted, shop-wired, pressure tested, run tested, and painted. | |
| Complete mechanical and electrical drawings provided for approval prior to fabrication. | |
| Complete installation, operation and maintenance manuals provided with the unit in hardcopy and electronic form. |
| Backup ermergency pump: | Provide uniterrupted circulation of coolant by automatically turning ON emergancy pump during a loss of electrical power. |
| Sized for a minimum of 10 GPM at 25 psi |
| Heat Exchanger: | Seemless copper tubing |
| Dry nitrogen leak tested at >350 PSIG in water test tank | |
| Housing Constructed of corrosion resistant material | |
| Fan motors factory wired to control panel and cycled using a temperature controller or thermostats |
Electrical Supply: 220V or 440V / 3 phase / 60 Hz
| Additional Features Requested: | Startup and Training |
| Warranty: Standard 1 Year labor & 1 Year parts | |
| Spare parts kit |