TITAN OR EQUAL SALIENT CHARACTERISTICS FOR AIR HANDLING UNITS

The Air Handling Units (AHUs) must meet or exceed the following minimum specifications:

AHU: Titan Model Number: TAH-2.5-107 BI ST OA HRV or Equal

Quantity of 1

· Air Flow: 200 CFM

· Estimated Static Pressure (ESP): 1” wc

· Temperature Rise/Maximum Discharge Temperature: 210 ºF (EAT of 0 ºF) provided through 8” duct to 56”H x 89”W x 66”D Oven utilizing 100% Outside Air Intake

· Heating: 45,407 BTU/Hr Max

· Heat Medium: Preheat Steam Coil - 30 PSI Steam; Reheat (Main) Steam Coil - 30 PSI Steam

· Cool Medium - None

· Function: Air Make-Up Unit (Indoor Mounted)

· Motor Voltage: 230 3ph, 3 wire, 60Hz

· Motor HP: 0.5

· Motor National Electric Code (NEC) Full Load Amps (FLA) : 2.2

· Motor Unit FLA: 3.2

· Motor Speed: 1750 rpm ODP Premium Efficiency

· Motor and Bearing Location: Out of Airstream

· Outside Air Filter Section in Unit Casing Motor Type: 2 in. Pleated, MERV 8

· Intake Damper & Actuator (Al. Airfoil Low Leak) - Insulated Intake Damper

· BI CSW (AMCA CLASS A) Spark Free Blower

· Insulated Interior Wall

· 2” Construction/Mineral Wood Insulation

· Belimo LF120-S Motorized Damper Actuator or Equivalent

· Interior Unit Liner

· Insulated Unit (Conditioned Airstream)

· G-90 Galvanized Casing & Accessories

· AHU cabinet can be no more than 68” Long x 38” Wide; must be able to connect to bottom of existing oven supply air duct which is 69” from the floor. Air must be discharged vertically.

· Blower, Filter, and Damper Access doors and coil pipes must be on LEFT hand side.

· Vendor must provide drawings.

AHU: Titan Model Number: TAH-2.5-107 BI ST OA HLV or Equal

Quantity of 1

· Air Flow: 200 CFM

· Estimated Static Pressure (ESP): 1” wc

· Temperature Rise/Maximum Discharge Temperature: 210 ºF (EAT of 0 ºF) provided through 8” duct to 56”H x 89”W x 66”D Oven utilizing 100% Outside Air Intake

· Heating: 45,407 BTU/Hr Max

· Heat Medium: Preheat Steam Coil - 30 PSI Steam; Reheat (Main) Steam Coil - 30 PSI Steam

· Cool Medium - None

· Function: Air Make-Up Unit (Indoor Mounted)

· Motor Voltage: 230 3ph, 3 wire, 60Hz

· Motor HP: 0.5

· Motor National Electric Code (NEC) Full Load Amps (FLA) : 2.2

· Motor Unit FLA: 3.2

· Motor Speed: 1750 rpm ODP Premium Efficiency

· Motor and Bearing Location: Out of Airstream

· Outside Air Filter Section in Unit Casing Motor Type: 2 in. Pleated, MERV 8

· Intake Damper & Actuator (Al. Airfoil Low Leak) - Insulated Intake Damper

· BI CSW (AMCA CLASS A) Spark Free Blower

· Insulated Interior Wall

· 2” Construction/Mineral Wood Insulation

· Belimo LF120-S Motorized Damper Actuator or Equivalent

· Interior Unit Liner

· Insulated Unit (Conditioned Airstream)

· G-90 Galvanized Casing & Accessories

· AHU cabinet can be no more than 68” Long x 38” Wide; must be able to connect to bottom of existing oven supply air duct which is 69” from the floor. Air must be discharged vertically.

· Blower, Filter, and Damper Access doors and coil pipes must be on RIGHT hand side.

· Vendor must provide drawings.