TITAN OR EQUAL SALIENT CHARACTERISTICS FOR AIR HANDLING UNITS
The Air Handling Units (AHUs) must meet or exceed the following minimum specifications:
AHU: Titan Model Number: TAH-2.5-107 BI ST OA HRV or Equal
Quantity of 1
· Air Flow: 200 CFM
· Estimated Static Pressure (ESP): 1” wc
· Temperature Rise/Maximum Discharge Temperature: 210 ºF (EAT of 0 ºF) provided through 8” duct to 56”H x 89”W x 66”D Oven utilizing 100% Outside Air Intake
· Heating: 45,407 BTU/Hr Max
· Heat Medium: Preheat Steam Coil - 30 PSI Steam; Reheat (Main) Steam Coil - 30 PSI Steam
· Cool Medium - None
· Function: Air Make-Up Unit (Indoor Mounted)
· Motor Voltage: 230 3ph, 3 wire, 60Hz
· Motor HP: 0.5
· Motor National Electric Code (NEC) Full Load Amps (FLA) : 2.2
· Motor Unit FLA: 3.2
· Motor Speed: 1750 rpm ODP Premium Efficiency
· Motor and Bearing Location: Out of Airstream
· Outside Air Filter Section in Unit Casing Motor Type: 2 in. Pleated, MERV 8
· Intake Damper & Actuator (Al. Airfoil Low Leak) - Insulated Intake Damper
· BI CSW (AMCA CLASS A) Spark Free Blower
· Insulated Interior Wall
· 2” Construction/Mineral Wood Insulation
· Belimo LF120-S Motorized Damper Actuator or Equivalent
· Interior Unit Liner
· Insulated Unit (Conditioned Airstream)
· G-90 Galvanized Casing & Accessories
· AHU cabinet can be no more than 68” Long x 38” Wide; must be able to connect to bottom of existing oven supply air duct which is 69” from the floor. Air must be discharged vertically.
· Blower, Filter, and Damper Access doors and coil pipes must be on LEFT hand side.
· Vendor must provide drawings.
AHU: Titan Model Number: TAH-2.5-107 BI ST OA HLV or Equal
Quantity of 1
· Air Flow: 200 CFM
· Estimated Static Pressure (ESP): 1” wc
· Temperature Rise/Maximum Discharge Temperature: 210 ºF (EAT of 0 ºF) provided through 8” duct to 56”H x 89”W x 66”D Oven utilizing 100% Outside Air Intake
· Heating: 45,407 BTU/Hr Max
· Heat Medium: Preheat Steam Coil - 30 PSI Steam; Reheat (Main) Steam Coil - 30 PSI Steam
· Cool Medium - None
· Function: Air Make-Up Unit (Indoor Mounted)
· Motor Voltage: 230 3ph, 3 wire, 60Hz
· Motor HP: 0.5
· Motor National Electric Code (NEC) Full Load Amps (FLA) : 2.2
· Motor Unit FLA: 3.2
· Motor Speed: 1750 rpm ODP Premium Efficiency
· Motor and Bearing Location: Out of Airstream
· Outside Air Filter Section in Unit Casing Motor Type: 2 in. Pleated, MERV 8
· Intake Damper & Actuator (Al. Airfoil Low Leak) - Insulated Intake Damper
· BI CSW (AMCA CLASS A) Spark Free Blower
· Insulated Interior Wall
· 2” Construction/Mineral Wood Insulation
· Belimo LF120-S Motorized Damper Actuator or Equivalent
· Interior Unit Liner
· Insulated Unit (Conditioned Airstream)
· G-90 Galvanized Casing & Accessories
· AHU cabinet can be no more than 68” Long x 38” Wide; must be able to connect to bottom of existing oven supply air duct which is 69” from the floor. Air must be discharged vertically.
· Blower, Filter, and Damper Access doors and coil pipes must be on RIGHT hand side.
· Vendor must provide drawings.