Montabella School Emergency Generator Upgrade - Drawings.pdf
PDF 3 MB Posted
- Attached to
- RFP for generator upgrade project
- Solicitation number
- RFP - MOCS - 240000000483
- Issued by
- Montcalm County, Michigan
About this file
This document is a set of drawings for a generator upgrade project for the Montabella school district in Michigan. The project scope includes upgrading the emergency generator systems at the elementary, middle, and high schools. Key elements of the project are:
At the elementary school, the scope involves adding additional lighting and receptacles to the emergency egress lighting panel, and connecting existing HVAC units RTU-07 and AHU-3 to the generator. At the high school and middle school, the existing 60 kW generator will be removed and replaced with a new 150 kW natural gas generator. A new 200A automatic transfer switch (ATS) will be installed to feed the general loads, and a new 70A lighting panel will be added to serve emergency egress lighting. The project is scheduled for bids on 11/17/2023.
The drawings also include details on the generator pad, gas piping, and electrical one-line diagrams for the existing and new systems at the elementary and high school/middle school. The project will be funded through local sources, but any applicable state or federal funding requirements must be met.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Montabella Schools Emergency Generator Upgrade - Project Manual 11-21-23.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DO
DO
OVERALL ELECTRICAL PLAN
1"=40'-0"
NORTH
U N
IT
'C
U
N
IT
'B
U N
IT
'D
U
N
IT
'C
U N
IT
'E
U
N
IT
'D 'U
N
IT
'G
U N
IT
'F
U N
IT
'F
U
N
IT
'E
UNIT 'G'
UNIT 'H'
U N
IT
'H
U
N
IT
'F
U N
IT
'B
U
N
IT
'A
UNIT 'I'
DUPLEX RECEPTACLE
COMBINATION MOTOR STARTER
3 PHASE MOTOR
JUNCTION BOX
FUSED SWITCH
NON-FUSED SWITCH
CIRCUIT BREAKER DISCONNECT
ELECTRICAL CONNECTION
PANEL BOARD
PUSH BUTTON
METER
TRANSFORMER
PULLBOX
CIRCUIT BREAKER
100% RATED CIRCUIT BREAKER
GROUND ROD
GROUNDING ROD
EQUIPMENT/ENCLOSURE GROUND CONNECTION POINT
REBAR GROUND CONNECTION
NEW UL924 DEVICE
EXISTING UL924 DEVICE
TEMP GENERATOR CONNECTION
UNDERGROUND CABLE
GENERATOR
UNINTERRUPTIBLE POWER SUPPLY
ROOM
PHASE
AUTOMATIC TRANSFER SWITCH
WIRE
WEATHER PROOF
EXISTING
EMERGENCY POWER OFF
FOUNDATION
MANUAL TRANSFER SWITCH
WP
JB
EX
EPO
MONTABELLA SCHOOLS GENERATOR
REPLACEMENT AND EMERGENCY
SYSTEMS STUDY
MONTABELLA, MICHIGAN
M
T
SYMBOLS AND ABBREVIATIONS
FND
P
W
ATS
Ø
RM
UPS
GEN
100%
TITLEDRAWING NO ISSUE DATE REVISION
TS1 TITLE SHEET 11/17/2023 BIDS
E101A FIRST FLOOR REVISED ELECTRICAL - UNIT A 11/17/2023 BIDS
E101B FIRST FLOOR REVISED ELECTRICAL - UNIT B 11/17/2023 BIDS
E101C FIRST FLOOR REVISED ELECTRICAL - UNIT C 11/17/2023 BIDS
E101D FIRST FLOOR REVISED ELECTRICAL - UNIT D 11/17/2023 BIDS
E101E FIRST FLOOR REVISED ELECTRICAL - UNIT E 11/17/2023 BIDS
E101F FIRST FLOOR REVISED ELECTRICAL - UNIT F 11/17/2023 BIDS
E101G FIRST FLOOR REVISED ELECTRICAL - UNIT G 11/17/2023 BIDS
E101H FIRST FLOOR REVISED ELECTRICAL - UNIT H 11/17/2023 BIDS
E101I FIRST FLOOR REVISED ELECTRICAL - UNIT I 11/17/2023 BIDS
E201 ELEMENTARY EXISTING ONE LINE DIAGRAM 11/17/2023 BIDS
E202 HIGH SCHOOL EXISTING ONE LINE DIAGRAM 11/17/2023 BIDS
E301 ELECTRICAL PANEL SCHEDULES 11/17/2023 BIDS
ISSUED FOR
UGE
EXECUTIVE SUMMARY FOR THE ELEMENTARY SCHOOL
THE PROJECT SCOPE FOR THE ELEMENTARY SCHOOL IS AS
FOLLOWS:
· ADD ADDITIONAL LIGHTING TO THE EXISTING
EMERGENCY EGRESS LIGHTING PANEL AS NOTED.
· ADD ADDITIONAL RECEPTACLES TO THE EMERGENCY
PANEL AS NOTED.
· ADD EXISTING UNITS "RTU-07" AND "AHU-3" TO THE
ELEMENTARY GENERATOR.
EXECUTIVE SUMMARY FOR THE HIGH SCHOOL AND MIDDLE SCHOOL
THE PROJECT SCOPE FOR THE HIGH SCHOOL AND MIDDLE SCHOOL
IS AS FOLLOWS:
· DE-ENERGIZE AND REMOVE THE EXISTING 60 KW GENERATOR
AND ASSOCIATED CONDUIT AND WIRE.
· FURNISH AND INSTALL A NEW 200A ATS TO FEED THE GENERAL
LOADS INCLUDING BUT NOT LIMITED TO RECEPTACLE(S) IN
CLASSROOMS, LOADS IN THE EXISTING KITCHEN AND
MECHANICAL EQUIPMENT.
· FURNISH AND INSTALL A NEW 150 KW NATURAL GAS
GENERATOR FOR THE LOADS IN THE HIGH SCHOOL AND MIDDLE
SCHOOL.
· RE-FEED PANEL EM FROM THE NEW FUSED DISCONNECT FED
FROM ATS-EMHS.
· FURNISH AND INSTALL A NEW 70A, 277/480V LIGHTING PANEL IN
THE HIGH SCHOOL TO FEED EMERGENCY EGRESS LOADS.
MODIFY AND EXTEND THE FEED FROM THE EXISTING 70A ATS
FOR THIS PANEL.
· FURNISH AND INSTALL UL924 DEVICES FOR EMERGENCY
EGRESS LIGHTING.
· FURNISH AND INSTALL (2) 120/208, 3 PHASE RECEPTACLE
PANELS IN HIGH SCHOOL
· FURNISH AND INSTALL A MANUAL TRANSFER SWITCH AND
ASSOCIATED GENERATOR RECEPTACLE FOR UNIT I WITH
ASSOCIATED CABLE.
(989) 894-4300 F (989) 894-9930 www.macmillanassociates.com
714 EAST MIDLAND STREET BAY CITY, MICHIGAN 48706
MacMILLAN ASSOCIATES
CONSULTING ENGINEERS
AR
MGBB
GBB
EX PNL P-1 EX TRX 11
EX TRX-ELEM
EX PNL GEN
EX GENERATOR
EX PORTABLE GEN.
CONNECTION
EX MDP-ELEM
EX ATS-EL
EX PNL EL1A
EX ATS-ES
EX PNL
ED1A
EX PNL ES1A
EX
PNL
RP7
ED1A- 19,21,23
EX VFD-P1
ED1A- 20,22,24
EX VFD-P2
EX TX-RP7
EX TX-ES1A
ER
1A
- 9
ER
1A
- 1
EX TRX-FP
EX PME-12
EX PME-5
EX SECTIONALIZING
CABINET
EX C/T CABINET
PAGING RACK
EXISTING ACP
ES1A- 15
EX WPEX GENERATOR
EM STOP
EX PNL K
EX EX
EX. MDP-1
EX EM
EX ATS
EX MCC-1
EX PNL L
EX. M
EX.
TRX-M
NEW GENERATOR
EX TRX-HS
EX EM
120V
NEW ATS
EX
P
N L
A
EX
P
N L
LP
S
NEW PANEL EL1B
EX PNL C
EBS
EX RTU-07
EX AHU-3
EX
PNL
ER1A
EX PNL RP4
EX PNL RP3
EX TX-32
EX TX-RP5
EX PNL RP5
EX PNL ER1B
EX
P
N L
BP
C
EX
P
N L
BP
C
EX
P
N L
D
PC
EX
P
N L
LP
C
EX PNL LPCS
ELEMENTARY SCHOOL
HIGH SCHOOL
EX PNL LPTEX PNL GG
NEW PNL EMRP-2
EX PNL 1C
EX PNL 2C
EX DATA RACK
RECOMMENDED
CONDUIT ROUTE
EX PNL B
EX PNL AA
NEW XFMR
EX DATA
RACKNEW PANEL
EMRP-1
RECOMMENDED
CONDUIT ROUTE
EX
P
N L
G
EX
P
N L
K
EX
P N
L K-
EX PNL GG
EX AHU-H2
EX AHU-H1
NEW PANEL EDP
EX TOWER PAD
4"
2' -0
5'-0"
6 3/4" 6 3/4"3'-10 1/2"
2" C
LR
3/4"x8"
EXPANSION
ANCHORS
(6) #5 L.W.
T&B @ 8" O.C.
NOTES:
1. CONCRETE - F'C=4000 PSI, 6% AIR ENTRAINED
2. REBAR - ASTM A615 GRADE 60
(6) 3/4"x8" HILTI KWIKBOLT
EXPANSION ANCHOR
COORDINATE LOCATION
WITH GENERATOR
MANUFACTURER
11'-0"
5' -0
1'-8 1/2"3'-3" 3'-3"
3/
4"
3/ 4"
3' -1
1/
2"
PLAN1
SECTION
1/2"=1'-0"
FIELD VERIFY DIMENSIONS WITH GENERATOR
MANUFACTURER PRIOR TO PAD CONSTRUCTION.
T&B
(12) #5 S.W.
3" C
LR
2"
TYP.
3. DIMENSIONS INDICATED ARE ONLY A GUIDELINE
AND SHOWN FOR COORDINATION PURPOSES.
ELD
MTS
EX D1L BUS FACILITY
EX R1L
EX TX-R1L
MTS
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
A U
N
IT
A R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
A U
N
IT
A R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT A
E101A
2023-01042RLM
BAV
JWF
U N
IT
'B
U
N
IT
'A
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT A
1/8"=1'-0"
NORTH
AR
MGBB
GBB
EX PNL P-1 EX TRX 11
R11
MUD
757B
TLT.
757A
LEVELED READING
Room
Room
TLT.
754A
TLT.
752A
Room
Room
MULTI-PURPOSE
STORAGE
726C
OFFICE
726B
STORAGE
726A
VESTIBULE
OFFICE / LIBRARY
730BPRACTICE
730ACORRIDOR
C701
UNISEX
UNISEX
MUSIC
TLT.
725A
MUD
725B
BUILDING STORAGE
743D
CORRIDOR
C704
CORRIDOR
C703
J.C.
Room
FREEZER
EX TRX-ELEM
FOOD STORAGE
ELECTRICAL
MECHANICAL
EX PNL GEN
EX GENERATOR
EX PORTABLE GEN.
CONNECTION
EX MDP-ELEM
EX ATS-EL
EX PNL EL1A
EX ATS-ES
EX PNL
ED1A
EX PNL ES1A
EX PNL ER1A
EX RP6
EX P-2
EX TX-RP6
EX
PNL
RP7
GIRLS
BOYS
ER1A- 7
ER1A- 6
ER1A- 7
ER1A- 7
ER1A- 6
ER1A- 8
ER1A- 8
ER1B- 9
ED1A- 19,21,23
EX VFD-P1
ED1A- 20,22,24
EX VFD-P2
EX TX-RP7
EX TX-ES1A
ER1A- 6 ER1A- 8
ER
1A
- 9
ER
1A
- 1
EX TRX-FP
EX PME-12
EX PME-5
EX SECTIONALIZING
CABINET
EX C/T CABINET
EX BACKBOARD CONTROL.
REFER TO DETAIL
PAGING RACK
EXISTING ACP
ER1A- 14
ES1A- 15
EX WP
ES1A- 15
EX WPEX GENERATOR
EM STOP
EX PNL K
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
ELD ELD
ELD
EL1A- 3
EL1A- 2
EL1A- 2 EL1A- 2
EL1A- 2
EL1A- 2
EL1A- 4
EL1A- 4
EL1A- 4
EL1A- 4
EL1A- 4
EL1A- 6EL1A- 6
EL1A- 8
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX PNL R11
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EM
EX
EM
EX EXEXEX
EX EX EX EX
SS
CONDUIT
TO CEILING
SS
EX
EX EX EX EX
EXEXEX
EX EX EX EX
EXEXEXEX
EX EX EX EX
EX
EX
EX
EX EX EX
EXEXEX
EX EXEX
EXEX
EX
EX EX
EXEX
EX EX EX
EX
KEYED NOTES
EXISTING FIXTURE IS ALREADY FED FROM
THE EMERGENCY LIGHTING PANEL AND IS
SHOWN FOR REFERENCE ONLY.
ELECTRICAL CONTRACTOR SHALL FEED
THE HALF SHADED FIXTURE WITH THE
EMERGENCY LIGHTING CIRCUIT AS SHOWN.
THE DESIGN INTENT IS FOR THE EXISTING
LIGHTING CONTROLS TO REMAIN IN USE
AND THE UL924 DEVICE TO OVERRIDE ANY
DIMMING OR OCCUPANCY FUNCTION IN THE
EVENT OF LOSS OF UTILITY POWER.
FIELD TRACE EXISTING FEED. RELOCATE
BREAKER TO EXISTING PANEL ED1A.
MODIFY AND EXTEND THE EXISTING
CONDUIT AND WIRES FROM THE SOURCE
TO PANEL ED1A.
THE DESIGN INTENT IS TO RE-FEED THE
EXISTING AHU FROM THE NEW CIRCUIT IN
ED1A. REFER TO THE RISER DIAGRAM FOR
MORE DETAIL.
EX
EX
EX
EL1A- 5
1 1
EBS
EBS
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. ALL NEW RECEPTACLES ON AN EMERGENCY
CIRCUIT SHALL BE RED WITH A RED COVER
PLATE. ALL EXISTING RECEPTACLES THAT HAVE
BEEN RE-FED FROM AN EMERGENCY CIRCUIT
SHALL HAVE A CONTRACTOR FURNISHED RED
COVER PLATE.
4. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
5. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
6. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
7. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
EX AHU-3ED1A-26,28,30
(MDP-ELEM-13) EX SERVICE GFI
RECEPTACLE
ER1A-11
EBS2
EL1A-4
EL1A-4
EL1A-4
EX
RTU-07
http://www.macmillanassociates.com
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
B U
N
IT
B R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
B U
N
IT
B R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT B
E101B
2023-01042RLM
BAV
JWF
U N
IT
'C
U
N
IT
'B ' U N
IT
'B
U
N
IT
'A
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT B
1/8"=1'-0"
NORTH
MEDIA CENTER
OFFICE
762C
DRAFTING
ISOLATION
T 767A
TOOL STORAGE
762D
SHOP
FINISH
762B
STORAGE
762A
VEST.
CORRIDOR
C703
1/2/3 CLASSROOM
757 MUD
757B
TLT.
757A
LEVELED READING
1/2/3 CLASSROOM
STORAGE
726C
OFFICE
726B
STORAGE
726A
1/2/3 CLASSROOM
GIRLS
TLT.
759A
TLT.
761A
BOYS
GROSS MOTOR
CI
CONF.
SW
KITCHENETTE
709A
WORK ROOM
COACH 1 & 2
PSYCH.
T.C.
705A
ASST. PRINCIPAL
REC. STORAGE
709B
TLT.
702A
SICK ROOM
702B
TLT.
709C
PRINCIPAL
RECEPTION
ISS
ISS
J.C.
SLP
TLT.
765A
STOR.
719A
RESOURCE
TITLE
TITLE
1/2/3 CLASSROOM
Pre-K / K
CLASSROOM
Pre-K / K
CLASSROOM
TLT.
723A
TLT.
721A
MUD
721B
MUD
723B
Pre-K / K
CLASSROOM
Pre-K / K
CLASSROOM
Pre-K / K
CLASSROOM
TLT.
715A
TLT.
717A
MUD
717B
MUD
715B
CORRIDOR
C702
CORRIDOR
C701
SEC. VEST.
CLOSET
709A
EX FACP
EX GAA
EX FAA
CORRIDOR
709D
CORRIDOR
709D
EX ER1A
EX TX-RP5
EX PNL RP5
EX PNL P-3
EX PNL RP4
EX TX-RP4
ON MEZZANINE ABOVE
EX TX-32
EX PNL
ER1B EX
ER1B- 16 ,48"
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EXEX
EXEX
EXEX
EXEX
EXEX
EX EX
EX
EX
EX
EXEX
EX
EX
EX
EX
EX
EX
ELD
ELD
ELD
ELD
ELD
ELD
ELD
ELD
ELD ELD ELD ELD ELD
ELD
ELD
ELD ELD ELD
ELD
ELD
ELD
ELD
ELD
ELD
ELD
EL1A- 7
EL1A- 6
EL1A- 1
EL1A- 1
EL1A- 1EL1A- 1
EL1A- 2
EL1A- 2 EL1A- 2 EL1A- 2
EL1A- 2
EL1A- 2
EL1A- 2
EL1A- 2
EL1A- 2 EL1A- 2
EL1A- 2
EL1A- 2
EL1A- 3
EL1A- 3
EL1A- 3
EL1A- 3 EL1A- 3 EL1A- 3
EL1A- 3
EL1A- 3
EL1A- 3 EL1A- 3 EL1A- 3
EL1A- 5
EL1A- 5
EL1A- 6
EL1A- 6
EL1A- 6
EL1A- 6
EL1A- 6
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX
EX
EX
EX
EX
EX
EX EX EX
EX
EX
EX
EX
EXEX
EX
EX
EXEX
EX
EX
EX
EX
EX
EX
EX
EXEXEX
EX
EX
EX
EX
EX
EX EX
EX EX
EX EX
KEYED NOTES
EXISTING FIXTURE IS ALREADY FED FROM
THE EMERGENCY LIGHTING PANEL AND IS
SHOWN FOR REFERENCE ONLY.
EXISTING RECEPTACLE UNDER THE
RECEPTION DESK IS FED FROM PANEL
RP5-15. INTERCEPT THE CIRCUIT AND
RE-FEED FROM ER1B. FURNISH AND
INSTALL A RED COVER PLATE FOR THE
RECEPTACLE.
EX
EX
EX
EXEX
EX
EX
EXEX
1 1
1 1
EXEX EXEX
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. UNLESS OTHERWISE NOTED RECEPTACLES AND
CIRCUITS SHOWN ARE EXISTING TO REMAIN.
4. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
5. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
6. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
7. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
ERB1-28
(RP5-15)
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
C U
N
IT
C R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
C U
N
IT
C R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT C
E101C
2023-01042RLM
BAV
JWF
U N
IT
'C
U
N
IT
'B
U N
IT
'D
U
N
IT
'C
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT C
1/8"=1'-0"
NORTH
EX
P
N L
BP
C
EX
P
N L
D
PC
EX
P
N L
BP
C
EX
P
N L
LP
C
EX PNL LPCS
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX EX
EXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
IDF
EX
KEYED NOTES
EXISTING LIGHTING IN CLASSROOM HAS BEEN
PRE-WIRED FOR AN EMERGENCY GENERATOR
FEED. THE DESIGN INTENT IS ONLY FOR THE
HALF SHADED FIXTURES TO BE ON THE
GENERATOR CIRCUIT.
EXISTING UL924 LIFE SAFETY DEVICE. EC SHALL
PROVIDE THE NEW EMERGENCY LIGHTING
CIRCUIT AS SHOWN TO THE EXISTING DEVICE.
HALF SHADED FIXTURES SHALL BE ON THE
EMERGENCY CIRCUIT.
EXISTING RECEPTACLES ARE FED FROM CIRCUIT
BCP2-78. INTERCEPT THE CIRCUIT AND FEED
FROM PANEL BCP1 AS SHOWN.
EXEXEXEXEXEXEXEXEXEX
EX
EX
EX
EX
EX
EXEX
EXEXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EXEX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX INVERTER
EX
B-2
EX
B-1
EBS
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
4. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
5. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
6. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
BPC1-43
BPC1-43
ELD EX
ELD
EX
ELD
EX
EX
ELD
EX
ELD
EX
ELD
EX
ELD
EX
EL1A-16
EL1A-16
EL1A-16
EL1A-16
EX
EX
EX
EX
EL1A-16
EL1A-16
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
D U
N
IT
D R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
D U
N
IT
D R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT D
E101D
2023-01042RLM
BAV
JWF
U N
IT
'D
U
N
IT
'C
U N
IT
'E
U
N
IT
'D
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT D
1/8"=1'-0"
NORTH
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX PNL G
EX PNL LPTEX PNL GG
EX EX
EX
EX
EX
EX
EX
EX EX EX EX EX EX EX EX EX EX EX EX
EX
EX
EX
EX
EX
EX EX EX EX
EXEXEXEX
EXEX
EX
EX
EXEXEXEX
EXEXEXEX
EX EX EX EX
EXEXEXEX
EX EX EX EX
EXEXEXEX
EX EX EX EX
EXEXEXEX
EBS
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
4. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
5. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
6. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
EL1B-2
4"
G
4" G
U N
IT
'E
U
N
IT
'D
U N
IT
'F
U
N
IT
'E
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT E
1/8"=1'-0"
NORTH
LPTEX PNL GG
EX. MDP-1
EX EM
EX ATS
EX MCC-1
EX PNL L
EX. M
EX.
TRX-M
NEW GENERATOR
EX TRX-HS
EX
P N L K
EX LPU
STOR.
A140.1
INSTRUMENTAL
MUSIC
A140
EX EM
120V
EX FACP
PANEL
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
S
EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EXEX
EX
EX
EX
EX EX
EX
EX
EX
EX EX
EX
EXEX
EXEX
EX
EX
EX
EX
EX
EXEXEX
EX EX
EX
EX
EX EX
EX EXEX
EX
EXEXEX
EXEX
EX
EX
EXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EBS
EBS
EBS
NEW ATS-EMHS
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
E U
N
IT
E R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
E U
N
IT
E R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT E
E101E
2023-01042RLM
BAV
JWF
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
4. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
5. MECHANICAL CONTRACTOR SHALL PRIME AND
PAINT ALL NEW GAS PIPING YELLOW, USING A
RUST-INHIBITOR PAINT WITH ZINC.
6. NEW GAS PIPING ABOVE GRADE SHALL BE
SCHEDULE 40 STEEL AND BE LOCATED A
MINIMUM OF 4" ABOVE GRADE. SUPPORT
PIPING WITH PRE-MANUFATURERED SUPPORTS,
SIMILAR TO MIRO 8-BASE-STRUT-5, WITH TOP
CLAMP OVER PIPE.
7. BURIED GAS PIPING SHALL BE BURIED A
MINIMUM OF 12" DEEP. BURIED GAS PIPING
SHALL HAVE ALL PIPING AND FITTINGS COATED
WITH A ZINC PROTECTIVE OUTER LAYER OR USE
A SYSTEM RATED FOR GAS PIPING, SUCH AS
PLASTIC PIPING WITH THE LABEL "ASTM D 2513"
ON THE PIPING AND HEAT FUSION FITTINGS.
8. ALL NEW GAS PIPING SHALL CONFORM TO THE
INTERNATIONAL FUEL GAS CODE AND SHALL BE
SUBMITTED ON FOR APPROVAL PRIOR TO
INSTALLATION.
9. COORDINATE WITH UTILITY PROVIDER THAT
EXISTING 10,000 CFH NATURAL GAS SERVICE AT
1 PSI WILL NEED TO BE REVISED TO 11,000 CFH
AT 1 PSI.
10. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
11. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
KEYED NOTES
EX UNIT AHU-H1 IS FED FROM THE EXISTING EM
PANEL. DISCONNECT AND RE-FEED FROM THE
SPARE 30A BUCKET IN THE EXISTING MCC.
THE DESIGN INTENT IS FOR THE EXISTING FREEZER
AND REFRIGERATOR TO BE FUNCTIONAL IN THE
RESULT OF A LOSS OF UTILITY POWER. INTERCEPT
THE EXISTING CIRCUIT AND RE-FEED FROM
EXISTING PANEL EM. CIRCUITS SHOWN. ARE BASED
OFF OF AS-BUILT DRAWINGS. ELECTRICAL
CONTRACTOR SHALL FIELD TRACE AND VERIFY.
MECHANICAL CONTRACTOR SHALL REMOVE
EXISTING GAS PIPING SERVING EXISTING
GENERATOR IN LOCATIONS SHOWN. REMOVE
EXISTING GAS REGULATOR AND RETURN TO
OWNER.
MECHANICAL CONTRACTOR SHALL CONNECT NEW
2" GAS PIPING TO EXISTING 2" GAS PIPING. FURNISH
AND INSTALL ISOLATION VALVE, THEN ROUTE PIPING
TO BELOW GRADE.
MECHANICAL CONTRACTOR SHALL ROUTE 2" GAS
PIPING UNDERGROUND TO NEW GENERATOR.
COORDINATE LOCATION WITH NEW AND EXISTING
UNDERGROUND SYSTEMS.
MECHANICAL CONTRACTOR SHALL ROUTE 2" GAS
PIPING UP FROM BELOW GROUND AND CONNECT TO
NEW GENERATOR. FURNISH AND INSTALL NEW
REGULATOR AND ISOLATION VALVE. REVISE PIPE
SIZE TO MATCH INLET SIZE ON GENERATOR AFTER
ISOLATION VALVE. INSTALL DIRT LEG AT
CONNECTION. REGULATOR SHALL REDUCE 1 PSI TO
12" W.C.
MOUNT NEW CAM LOCK CABINET TO A UNISTRUT
RACK IN THIS LOCATION. REFER TO
MANUFACTURERS INSTALLATION SHEET FOR FINAL
WIRING DIAGRAM.
VERIFY FINAL CONDUIT STUB LOCATION PRIOR TO
ROUGH IN WITH CONCRETE BASE.
DISCONNECT EXISTING GENERATOR FROM GAS
LINE, AND ATS FEED. REMOVE GENERATOR AND
PROPERLY DISPOSE OF. REMOVE EXISTING
GENERATOR FOUNDATION AND BACKFILL WITH TOP
SOIL. RE-SEED LOCATION.
EX
AHU-H2
EX
AHU-H1
MDP
(EM-1,3,5)
EX FENCE
1'-4"
2' -6
'-9
'-9
18'-6"
NEW
PANEL
EDP
EX TOWER PAD
BLOCK HEATER
BATTERY CHARGER
EM120-7
EM120-10
CONDUIT STUB LOCATION
EL1B-2
EL1B-4
EX
P N L K-
EX FREEZER
EX
REFRIGERATOR
EM120-16,18,20
(K-25,27,29)
EM120-12,14
(K-21,23)
EX. MDP-1
EX EM
EX ATS
EX MCC-1
EX PNL L
EX. M
EX. TRX-M
NEW GENERATOR
EX TRX-HS
EX EM 120V
NEW ATS-EMHS
EX FENCE
NEW
PANEL
EDP
EX TOWER PAD
BLOCK HEATER
BATTERY CHARGER
EM120-7
EM120-10
CONDUIT STUB LOCATION
ENLARGED PLAN
1/4"=1'-0"
G
G
G
EX 2" GAS PIPING (1 PSI)
6 2" GAS (12" W.C.)
2" GAS
UNDERGROUND
(1 PSI)
EX GENERATOR
EM120-22EM120-24
FREEZER LIGHTS,
ALARM FRIDGE LIGHTS,
ALARM
EM120-26,28
FREEZER
EVAPORATOR COIL
EX GENERATOR
CAM LOCK CABINET 7
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
F U
N
IT
F R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
F U
N
IT
F R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT F
E101F
2023-01042RLM
BAV
JWF
U N
IT
'F
U
N
IT
'E
U N
IT
'H
U
N
IT
'F
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT F
1/8"=1'-0"
NORTH
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX
P
N L
AOFFICE
203E
OFFICE
203D
EX
P
N L
LP
SEX
EX
EX
EX
LV
LV
OS
OS
OFFICE
203D
OFFICE
203E
A2
A2 A2
A2
SK
EX
PNL D
S S
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX EX
EX EX
EX EX EX EX
EX
EX
EX
EX
EX EX EX EX
EX
EX EX
EX EX
EX
EX
EX
EX
EX
EX
SSSS
EXEXEX
EX EX
EX EX
EX EX
EX EX
EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EBS
EBS
EX
EX
EBS
EBS
EBS
EBS
EBS
EBS
EBS
NEW PANEL EL1B
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. ALL NEW RECEPTACLES ON AN EMERGENCY
CIRCUIT SHALL BE RED WITH A RED COVER
PLATE. ALL EXISTING RECEPTACLES THAT HAVE
BEEN RE-FED FROM AN EMERGENCY CIRCUIT
SHALL HAVE A CONTRACTOR FURNISHED RED
COVER PLATE.
4. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
5. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
6. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
7. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
EX
(C28)
EX
(C28)
EX
(C28)
EX
(C28)
EX
(C28)
EX
EMRP1-9
EX EX
EX
EX
EX
EX EX
EX
EX
EMRP1-7
EX
EMRP1-7
EX
EX
EX
EX
(D10)
EX
(D10)
EX
(D10)
EX
(D9)
EX
(D9)
EX
(D9)
EX
(D9)
EX
(D11)
EX
(D11)
FBEX
(D7)
EX EX EX
(D8) (D8) (D8)
EX
(D10)
EX
(D10)
EX
EMRP1-5
EX
EMRP1-5
EMRP1-5
FBEX
(D8)
EX
EMRP1-3
EX
EX
EXEX EX
(D2)
EX
(D2)
EX
(D1)
FBEX
(D2)
FBEX
(D1)
EX
(D1)
EX
(D1)
EX
EMRP1-1
EX
EX
EX
EX
NEW
PANEL
ERP1
EMRP1-1
EMRP1-1
EMRP1-1
EMRP1-1
EL1B-1
EL1B-1
EMRP1-3
EMRP1-3
EMRP1-3
EMRP1-3 EMRP1-3
EL1B-1
EL1B-1
EMRP1-7
EMRP1-7
EMRP1-7
EMRP1-7
EL1B-1
EL1B-1
EL1B-1
EL1B-1
EL1B-1
EMRP1-9 EMRP1-9
EMRP1-9
EMRP1-9
EMRP1-9
NEW PANEL
EMRP-1
NEW
XFMR
EX
DATA
RACK
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
G U
N
IT
G R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
G U
N
IT
G R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT G
E101G
2023-01042RLM
BAV
JWF
U N
IT
'G
U
N
IT
'F
UNIT 'G'
UNIT 'H'
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT G
1/8"=1'-0"
NORTH
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX PNL B
EX PNL AA
(AA- 41)
(AA- 39)
(AA- 39)
(AA-40)
(AA- 42)
(AA- 40)
(AA- 42)
(AA- 40)(AA- 39)
(AA- 41)
CLASSROOM
CLASSROOM
EX EX
EX
EX
EX EX
EX
EX
EX
EXEX
EX
LV
LV
OS OS
CLASSROOM
CLASSROOM
X1 X1
EX
EX EX
EXEX
EX
SKSK
EX
SS
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX EX
EX EX
EX EX
EX EX
EX EX
EX EX
EX EX EX EX
EX
EX
EX
EX
EX EX EX EX
SSEX
EX
EX EX EX EX EX EX
SS
EX
EXEXEX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EBS
EBS
EBS
EBS
EBS
EBS
EBS
EBS
EX
EX EX
EX EX
EXEXEX
EX
EX
EX
EXEXEX
EX
EX
EX
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
4. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
5. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
6. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
(AA-7)(AA-7)
EX
(AA-7)
EX
(AA-2)
EX
(AA-2)
EX
(AA-2)
EX
(AA-2)
EX
(AA-4)
EX
(AA-4)
EX
(AA-4)
FB
(AA- 4)
EX
EX EX
(AA-5)(AA-5)
EX
(AA-3)
(AA-1)
EX
(AA-1)
EX
(AA-1)
EX
(AA-1) EX
(AA-1)
EX
(AA-1)
EX
(B-16)
EXEX
EMRP2-13
EX
(B-8)
EX
(B-8)
EX
(B-8)
EX
(B-8)
EX
(B-6)
EX
(B-6)
EX
(B-16)
EX
(B-7)
EX
(B-7)
EX
EMRP2-15
EX
EMRP2-15
FB
(B-7)
EX
EX
EMRP2-15
EX
EMRP2-15
EX
EMRP2-15
EX
(B-7)
EX
(B-7)
FB (B-6)
EX
EX
(B-6)
EX
(B-6)
EX
(B-14)
EX
(B-14)
EX
(B-14)
EX
(B-14)
EX
(B-2)
EX
(B-2)
EX
(B-4)
EX
EMRP2-17
EX
EX
EX EX EX
(B-2)
EX
(B-2)
EX
(B-1)
EX
(B-1)
EX
(B-1)
FB
(B-1)
EX
EX
EX
EX
EX
EX
(B-1)
EX
(B-1)
EX
EMRP2-19EX
EMRP2-19
EL1B-3
EL1B-3
EL1B-3
EL1B-3
EMRP2-13
EMRP2-13 EMRP2-13EMRP2-13
EL1B-3
EL1B-3
EL1B-3
EL1B-3
EMRP2-17
EMRP2-17
EMRP2-17 EMRP2-17
EMRP2-19
EMRP2-19
EMRP2-19
EMRP2-19
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
H U
N
IT
H R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
H U
N
IT
H R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT H
E101H
2023-01042RLM
BAV
JWF
UNIT 'G'
UNIT 'H'
U N
IT
'H
U
N
IT
'F
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT H
1/8"=1'-0"
NORTH
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
EX PNL 1C & 2C
SS SS
S
S S
EX
EX
EXEX
EX
EX
EX
EX
EX
EX EX EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX EX EX EX EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX
EX
EXEX
EX
EX
EX
EX EX
EX
EX
EX
EX
S S
EX
EX
EX EX EX EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
EX EX
EX
EX EX
EBS
EBS
EX
EX
EX
EBS
EBS
EBS
EBS
EBS
EBS
EBS
EBS
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. ALL NEW RECEPTACLES ON AN EMERGENCY
CIRCUIT SHALL BE RED WITH A RED COVER
PLATE. ALL EXISTING RECEPTACLES THAT HAVE
BEEN RE-FED FROM AN EMERGENCY CIRCUIT
SHALL HAVE A CONTRACTOR FURNISHED RED
COVER PLATE.
4. ELECTRICAL CONTRACTOR SHALL FIELD TEST
ALL RECEIPTS SHOWN TO VERIFY THEY ARE
FED FROM AN EMERGENCY CIRCUIT.
5. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
6. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
7. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
8. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
(C-3)
EX
(C-3)
EX(C-3)
EX
(C-2)
EX
(C-2)
EX
EMRP2-7
EX
EMRP2-7
EX
EMRP2-7
EMRP2-7
EMRP2-7
EMRP2-7
EX
(C-2)
EX
(C-2)
EX
(C-2)
EX
(C-3)
EX
(C-3)
EX
EMRP2-5
EX
EMRP2-5
EXEXEXEXEX
EMRP2-9
EX
(C-8)
EX
(C-8)
EX
(C-5)
(C-5)
(C-5)
EX
(C-8)
EX
(C-8)
(C-8)
EX
(C-8)
EX
(C-8)
EX
(C-8)
EX
(C-8)
EX
EMRP2-11
EX
(C-13)
EX
EX
EX
EMRP2-3
EX
EMRP2-3
EX
EMRP2-3
EX
(C-38)
EX
(C-38)
EX
(C-40)
EX
(C-40)
EX
(C-40)
EX
(C-38)
EX
(C-38)
EX EX
EX
EX
EX
EX
EMRP2-1
EX
EMRP2-1
NEW
PANEL
ERP2
EL1B-7
EL1B-7
EMRP2-5
EMRP2-5
EMRP2-5
EMRP2-5
EL1B-7
EMRP2-9 EMRP2-9 EMRP2-9 EMRP2-9 EMRP2-9
EL1B-5
EL1B-5
EL1B-7
EMRP2-11 EMRP2-11EMRP2-11
EL1B-7
EL1B-7
EMRP2-3
EMRP2-3
EMRP2-3
EL1B-5
EL1B-5
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
I U N
IT
I
R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E1
I U N
IT
I
R
EV
IS
ED
E
LE
C
TR
IC
AL
P
LA
N
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
FIRST FLOOR REVISED ELECTRICAL
PLAN - UNIT I
E101I
2023-01042RLM
BAV
JWF
FIRST FLOOR REVISED ELECTRICAL PLAN - UNIT I
1/8"=1'-0"
NORTH
MONTABELLA COMMUNITY SCHOOLS
A
KEY PLAN
SCALE: NO SCALE
C D
E F
G
H
I
B
GENERAL NOTES
1. THE DESIGN INTENT IS FOR ALL HALF SHADED
FIXTURES TO BE FED FROM A NEW CIRCUIT. THE
CIRCUIT SHALL BE FROM THE NEC 700
EMERGENCY LIGHTING PANEL AND ATS AND
SHALL BE USED AS EMERGENCY EGRESS
LIGHTING. ALL UL924 DEVICES SHALL
INTERCEPT THE CONTROL WIRING AND THE HOT
LEG FROM THE LOCAL LIGHTING CIRCUIT.
AHEAD OF ANY SWITCHING AND SHALL BRING
THE FIXTURE(S) IT FEEDS TO FULL OUTPUT IN
THE EVENT OF LOSS OF NORMAL POWER TO
THAT LOCATION. REFER TO THE UL924 DEVICE
WIRING DIAGRAM FOR WIRING DETAIL.
2. WHERE ACCESSIBLE MOUNT THE EBS DEVICE IN
THE CEILING SPACE ABOVE THE LIGHTING
CONTROL SWITCHES. UPDATE AS-BUILTS WITH
FINAL MOUNTING LOCATION.
3. ALL NEW RECEPTACLES ON AN EMERGENCY
CIRCUIT SHALL BE RED WITH A RED COVER
PLATE. ALL EXISTING RECEPTACLES THAT HAVE
BEEN RE-FED FROM AN EMERGENCY CIRCUIT
SHALL HAVE A CONTRACTOR FURNISHED RED
COVER PLATE.
4. ELECTRICAL CONTRACTOR SHALL FIELD TEST
ALL RECEIPTS SHOWN TO VERIFY THEY ARE
FED FROM AN EMERGENCY CIRCUIT.
5. EXISTING CIRCUIT DESIGNATION SHOWN IN
PARENTHESES. WHERE THE CIRCUIT IS BEING
ALTERED REMOVE BACK TO NEAREST LIGHT
FIXTURE OR SOURCE.
6. ALTERATIONS ARE SHOWN WITH CLOUDING. ALL
OTHER DEVICES, CIRCUITS AND EQUIPMENT
ARE SHOWN AS REFERENCE ONLY.
7. LABEL ALL RECEPTACLES BEING ALTERED IN
THIS PROJECT WITH AN ADHESIVE LABEL.
BLACK LETTERING ON CLEAR TAPE WITH THE
NEW CIRCUIT DESIGNATION.
8. EXISTING RECEPTACLES SHOWN WITH
CIRCUITING ARE BASED OFF OF AS-BUILT
DRAWINGS. THE DESIGN INTENT IS TO
INTERCEPT THE CIRCUIT FEEDING THE
CLOUDED RECEPTACLES AND FEED WITH THE
NEW CIRCUIT NOTED FROM THE NEW
GENERATOR FED PANELS. FURNISH AND
INSTALL A RED COVER PLATE FOR ALL
RECEPTACLES ON THE GENERATOR CIRCUIT.
EX PNL C
EX D1L BUS FACILITY
EX R1L
EX TX-R1L
MTS
KEYED NOTES
FURNISH AND INSTALL A NEMA 3R RECEPTACLE AND
ENCLOSURE FOR THE GENERATOR CONNECTION.
FUNISH A 10' LOCKING GENERATOR CABLE WITH
LOCKING ENDS.
COODINATE WITH THE OWNER FOR DESIRED CIRCUITS
TO RELOCATE TO THE MTS. EC SHALL FURNISH ALL
BREAKERS IN THE MTS AS WELL AS THE 60A BREAKER
IN THE EXISTING PANEL R-1I.
MTS SCHEDULE
60A RATED MTS. NEMA 3R
ENCLOSURE, 120/250 SINGLE PHASE
60 HZ WITH A 60A MAIN BREAKER
AND (4) BLANK CIRCUITS.
GENERAC #6333 OR EQUAL
EX PANEL
D-1I
60/2
EX XFMR
EX
PANEL
R-1I
EXEX
(3)#6
(3)#10 GND
1"C
NEW
MTS
TO GENERATOR
RECEPT
(3)#6
(3)#10 GND
1"C
UNIT I PARTIAL RISER
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E2
E
LE
M
EN
TA
R
Y
EX
IS
TI
N G
O N
E
LI
N E
D
IA
G R
AM
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E2
E
LE
M
EN
TA
R
Y
EX
IS
TI
N G
O N
E
LI
N E
D
IA
G R
AM
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
ELEMENTARY UPDATED
ONE LINE DIAGRAM
E201
2023-01042RLM
BAV
JWF
M
2000A/3P
ET
GFI
ULSE
A/
3P
EX MDP-ELEM
480/277V 3Ø, 4W, 2000A
SPD
12470V
480/277V
TRX-ELEM
1500kVA
BUILDING
GROUND BAR
WELL CASING
#3/0 Cu GND (TYP)
EXISTING P-1
480/277V 3Ø, 4W, 400A
A/
3P
A/
3P
0A /3
P
EXISTING
K
PANEL IRRIGATION
WELL
TO HIGH
SCHOOL
N E
EXISTING ATS-EL
150A/3P
4 POLE
OPEN
TRANSITION
EX GENERATOR TO SERVE EMERGENCY POWER
AT ELEMENTARY
150A/3P
ET
A/
3P
EXISTING EL1A
480/277V 3Ø, 4W
SPD
AFM
10'-0"
GROUND ROD
0A
/3 P
0A
/3 P
0A
/3 P
5A
/3 P
A/
3P
A/
3P
A/
3P
0A
/3 P
0A
/3 P
ET
0A /3
P
0A
/3 P
0A
/3
PGROUND BUS
ET ET
0A
/3 P
0A
/3 P
250KW
NATURAL GAS GENERATOR
N E
(3) #1/0, #6 GND, 2" C
ET
0A /3
P
PORTABLE
GEN.
CONNECTION
PERMANENT
GEN.K
K
1000A
ARC FLASH HAZARD
REDUCTION MAINTENANCE
SWITCH, LOCATED PER
FLOOR PLANS.
LSIG
400A/3P
A/
3P
EXISTING P-3
480/277V 3Ø, 4W, 400A
SPD
A/
3P
CONTACTOR
PLUG IN DUCT
EQUIPMENT IN EXISTING
WOOD SHOP
0A
/3 P
SPARE
400A/3P
A/
3P
EXISTING P-2
480/277V 3Ø, 4W, 400A
SPD
5A
/3 P
SPD
A/
3P
EXISTING
PANEL
RP4
SPD
A/
3P
0A
/3 P
SPARE
5A
/3 P
SPD
A/
3P
SPD
EXISTING UTILITY
CONSUMERS FEED
AHU-E1 AHU-E2 AHU-E3 ACCU-E1 ACCU-E2 ACCU-E3
0A
/3 P
D1I
EX PANEL
SPD
125A/3P
EXISTING
PANEL
R1I
SPD
BUS FACILITY
FIRE PUMP
COMBINATION
CONTROLLER / ATS,
WYE DELTA
40HP FIRE
PUMP
2 HOUR RATED CABLE
SPD
CONTROL
SECTION
A/
3P
2HP FIRE
JOCKEY
PUMP
JOCKEY
PUMP
CONTROL
A/
3P
SPARE
N E
350A/3P
A/
3P
EXISTING ED1A
480/277V 3Ø, 4W
SPD
EXISTING ATS-ES
350A/3P
4 POLE
OPEN
TRANSITION
0A
/3 P
200A/3P
400A/3P
ET
A/
3P
EXISTING ES1A
208/120V 3Ø, 4W
SPD
A/
3P
EXISTING
LPCS
PANEL
SPD
0A
/3 P
ER1B
PANEL
SPD
0A
/3 P
EXISTING
BPC1
PANEL
SPD
0A
/3 P
ER1A
PANEL
SPD
(3) #2 Cu, 15kV, MV-105, 133%, EPR, IN 4"C.
PROVIDE #350 Cu GND BETWEEN EQUIPMENT.
EXISTING C/T
EQUIPMENT
E
EXISTING SWITCH PMH-5
EX SECTIONALIZING
CABINET
SC-N-1
12470V
480/277V
EX TRX-FP
112.5kVA
E
EXISTING
SWITCH S2-A
PME-12
(1000KVA, 70A)
TO FIELD
BUILDING
(3) #2 Cu, 15kV, MV-105, 133%, EPR, IN 4"C.
#350 Cu GND BETWEEN EQUIPMENT.
(3) #2 Cu, 15kV, MV-105, 133%, EPR, IN 4"C.
PROVIDE #350 Cu GND BETWEEN EQUIPMENT.
(3) 1/0 Cu, 15kV, MV-105, 133%, EPR, IN 4"C.
#350 Cu GND BETWEEN EQUIPMENT.
A/
2P
GEN
PANEL
SPD
ELEMENTARY UPDATED ONE LINE DIAGRAM
EXISTING
480V
TRX-32
45 KVA
208/120V
EXISTING
480V
TRX-RP5
75 KVA
208/120V
EXISTING
480V
TRX-RP4
45 KVA
208/120V
EXISTING
480V
TX-R1I
75 KVA
208/120V
EXISTING
480V
TX-K
75 KVA
208/120V
EXISTING
480V
TRX-12
45 KVA
208/120V
EXISTING
480V
TRX-11
45 KVA
208/120V
EXISTING
PANEL
R-11
EXISTING
PANEL
R-12
EXISTING
480V
TRX-RP6
45 KVA
208/120V
EXISTING
480V
TRX-RP7
45 KVA
208/120V
EXISTING
PANEL
R-6
EXISTING
PANEL
R-7
480V
EXISTING
TX-ES1A
112.5 KVA
208/120V
EXISTINGEXISTINGEXISTING
BCP2
120/208V
PANEL
EXISTING
TO PANEL M
LPC
277/480V
PANEL
EXISTING
TO HIGH
SCHOOL MDP
DP2
277/480V
PANEL
EXISTING
TO HIGH
SCHOOL MDP
EXISTING
PANEL
RP5
UL294 DEVICE WIRING DIAGRAM
UL924 DEVICE
EMERGENCY
LIGHTING
PANEL
RELAY NC
CONTACT
EMERGENCY
LIGHT(S)
RELAY
CONTROL
OPEN
RELAY
CONTROL
CLOSE
NORMAL
LIGHTING
ATS
NORMAL
POWER
PANEL
EMERGENCY
POWER
NORMAL
POWER
LOCAL
LIGHTING
CONTROL
GENERATOR CAPACITY: 312.5 KVA
PANEL EL1A 8.44 KVA
PANEL ED1A 125.82 KVA
TOTAL: 135.26 KVA @ 480V 3PH = 161.68A
KEYED NOTES
ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL (1) NEW 35A, 3 POLE BREAKER SUITABLE
FOR A SQUARE D NF PANEL. UTILIZE CIRCUITS
26,28,30 FOR THE NEW BREAKER. RETURN THE
SPARE BREAKERS CURRENTLY IN THE PANEL TO
THE OWNER.
INTERCEPT THE EXISTING FEED TO AHU #3
LEAVING THE MDP. MODIFY AND EXTEND THE
CIRCUIT TO BE FED FROM EXISTING PANEL ED1A.
A/
3P
EX AHU-E3
JB
(3)#8
(1)#10 GND
3/4"C
EX
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E2
M S
EX
IS
TI
N
G O
N E
LI
N
E D
IA
G
R
AM
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E2
M S
EX
IS
TI
N
G O
N E
LI
N
E D
IA
G
R
AM
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
HIGH SCHOOL
EXISTING ONE LINE DIAGRAM
E202
2023-01042RLM
BAV
JWF
HIGH SCHOOL UPDATED ONE LINE DIAGRAM
EXISTING
NATURAL GAS
GENERATOR
60 KW
NE
EXISTING
70A
ATS-ELHS
EXISTING
PANEL
BPC2
SPD
CONNECTOR
SPD
CONNECTOR
SPDSPDSPD
EXISTING
PANEL
BPC1
EXISTING
PANEL D
EXISTING
PANEL B
EXISTING
PANEL
1C &2C
(TUB2)
EXISTING
PANEL
GG
EXISTING
PANEL
1K &2K
(TUB2)
EXISTING
PANEL L
EXISTING
PANEL G
EXISTING
PANEL A
EXISTING
PANEL
AA
SPDSPD
200A/3P200A/3P200A/3P200A/3P300A/3P125A/3P300A/3P125A/3P125A/3P125A/3P125A/3P
GROUND BUS
WELL
CASING
#3/0 CU GND (TYP)
1200A/3P
EX M
208/120V 3Ø, 4W, 1200A
DEMAND: 225A
ET
FED FROM: EX TRX-M
1200A MB
EX
P-2
EX
P-5
1.5 1
EX
P-3
EX
EQ-1
EX
P-13
EX
P-2
1.5
EX
AHU-1
EX
EQ-1
EX
P-4
EX
P-6
EX
P-1
1.5110
30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P30A/3P
EX MCC-1
480/277V 3Ø, 4W, 225A
EXISTING
PANEL
PORTABLE
CLASSROOM
SPD SPD
EX PANEL
INVERTER
EXISTING
PANEL
LPCS
20A/3P
EX TRX-M
500 KVA
208/120V 480V
200A/3P
200A/3P 200A/3P
SPD
CONNECTOR
SPD
CONNECTOR
EXISTING
PANEL
LPC
60A/3P
EXISTING
PANEL
DPC
EXISTING
PANEL
LPT
40A/3P
100A/3P125A/3P60A/3P100A/3P100A/3P600A/3P60A/3P
SPD
10' SPACING (TYP)
10'-0"
GROUND ROD
#3/0 CU GND (TYP)
WATER MAIN
GROUND BUS
BUILDING GROUND BAR
/3
EX MDP-1 480/277V, 3Ø, 4W, 1200A
FED FROM: TRX-HS 1200A
MDP SWGR METER PEAK DEMAND ESTIMATED 275A
EX
TRX-HS
1000 KVA
EX SWITCH
PMH-7
EXISTING UTILITY FEED FROM
ELEMENTARY (CONSUMERS)
EXISTING
PANEL
LPU
EXISTING
PANEL
LPS
EX
TRX
CLS
75 KVA
208/120V 480V
EN
L
NEW
200A
ATS-EMHS
NEW
PANEL
EL1B
70A/3P200A/3P200A
NEW CAM
LOCK/LOAD
BANK CABINET
200A, 480V, 3PH
BLOCK
HEATER
BATTERY
CHARGER
NATURAL GAS GENERATOR
150 KW/187.5 KVA
277/480V, 3PH, 4W
GND
NEW GENERATOR TO SERVE EMERGENCY
POWER AT HIGH SCHOOL AND MIDDLE SCHOOL
LOAD SUMMARY
LIGHTING 11.37 KVA
RECEPTACLES 40.86 KVA [10 KVA + 15.43 KVA = 25.43 KVA]
HVAC 45.51 KVA
KITCHEN 11.88 KVA
TOTAL 94.19 KVA @ 480V 3Ø = 113.42 AMP
200A/3P
LS
EXISTING
PANEL
EM
20A/3P
EX
TRX-EM
15 KVA
208/120V 480V
EXISTING
PANEL
EM 120V
EXISTING
PANEL
EM
20A/3P
EX
TRX-EM
15 KVA
208/120V 480V
EXISTING
PANEL
EM 120V
NEW EMRP-1
120/208V 3Ø, 4W
(4)#4
(1)#8 GND
1 1/4"C
2HR FIRE RATED
(4)#4 (1)#8 1 1/4"C
2HR FIRE RATED
KEYED NOTES
2 HOUR FIRE RATED CABLE SHALL BE
DURALIFE RHH/R90 OR EQUAL. CABLE SHALL
MEET UL 2196 STANDARD FOR TWO HOUR
FIRE RESISTIVE CABLE.
FURNISH AND INSTALL A NEW 70A 3 POLE
BREAKER IN THE EXISTING MDP TO FEED THE
EMERGENCY LIGHTING ATS.
EXISTING PANELS SHALL BE RE-FED FROM
THE NEW ATS "ATS-EMHS". MODIFY AND
EXTEND THE EXISTING CONDUCTORS AS
NEEDED.
FURNISH AND INSTALL A NEW 100A 3 POLE
BREAKER IN THE EXISTING MDP TO FEED THE
EXISTING AHU.
FURNISH AND INSTALL A NEW 200A BREAKER
IN THE EXISTING MDP TO FEED THE NEW ATS.
200A/3P
NEW
PANEL
EMRP-2
60A/3P
(4)#6
(1)#10 GND
1"C
100A/3P100A/3P
NEW WIREWAY
NEW TRX-ER
75 KVA
480:120/208V
(4)#3/0
(1)#6 GND
2"C
70A/3P 100A/3P2 4
(4)#4
(1)#8 GND
1 1/4"C
2HR FIRE RATED
EX
AHU-1
(3)#3
(1)#8 GND
1 1/4"C
150KW GENERATOR SCHEDULE
CUMMINS NATURAL GAS GENERATOR OR APPROVED EQUAL. 60HZ,
150KW STAND BY POWER RATED. UL 2200, WEATHER PROOF
ENCLOSURE, 277/480 VOLT 3PH 4 WIRE, 125/105C ALTERNATOR,
EXTERNALLY MOUNTED STOP SWITCH, (2) 200A 100% RATED LSI
ELECTRONIC TRIP CIRCUIT BREAKERS, 12 AMP BATTERY CHARGER,
COLLANT HEATER, REMOTE ANNUNCIATOR, (2) HOUR ON SITE LOAD
BANK TEST.
(3)#3
(1)#8 GND
1 1/4"C
EX
EX
RELOCATED
(4)#3/0,(1)#4 GND-2"C
(3)#3,(1)#8 GND-1 1/4"C
(4)#3/0
(1)#6 GND
2"C
200A/3P
(4)#3/0
(1)#6 GND
2"C
(4)#3/0
(1)#6 GND
2"C
CAM LOCK CABINET SCHEDULE
ASCO#30C-N-C-N-0-3-200-N-O-O-F OR EQUAL 200A RATED, 480V, NEMA
3R, WALL MOUNTED INPUT STYLE WITH FEMALE CAMLOCKS.
EM120-7
EM120-10
ATS SCHEDULE
200A, 480V AUTOMATIC TRANSFER SWITCH. CONVENTIONAL 2 POSITION
TRANSITION. 3 PHASE, SOLID NEUTRAL 3 POLE, NEMA 1 ENCLOSURE.
ASCO #J-07ATS-A-3-0200-N-50-C
EMRP-1 SCHEDULE
120/208V 3 PHASE 4 WIRE PANELBOAD. SURFACE MOUNTED WITH A
HINGED COVER, 225A MAIN RATED, 200A MAIN CIRCUIT BREAKER, 42
POLE, COPPER BUS BAR, 10 KAIC
SQUARE D #NQ OR EQUAL
EMRP-2 SCHEDULE
120/208V 3 PHASE 4 WIRE PANELBOAD. SURFACE MOUNTED WITH A
HINGED COVER, 100A MAIN RATED, MAIN LUG, 30 POLE, COPPER BUS
BAR, 10 KAIC
SQUARE D #NQ OR EQUAL
TRANSFORMER TRX-ER SCHEDULE
75 KVA, 3 PHASE ENERGY EFFICIENT TRANSFORMER, 480V DELTA
PRIMARY TO 120/208V WYE SECONDARY, FLOOR OR TRAPEZE
MOUNTED, COPPER WINDING, 5.56 IZ%, 1.76 X/R RATIO.
SQUARE D #EXN75T3HCU OR EQUAL
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E3
E
XI
ST
IN
G P
AN
EL
S
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
Since 1963
(989) 894-4300
714 East Midland Street Bay City, Michigan 48706 www.macmillanassociates.com
CONSULTING ENGINEERS
MacMILLAN ASSOCIATES
REV. DESCRIPTION BY DATE
0.5"0.0" 1.0" 2.0"1.5"2/ 3/
1:
A
M R
AI
N
EY
M
C C
AR
TH
Y (R
M C
C
AR
TH
Y@
M
AC
M
IL
LA
N
AS
SO
C
IA
TE
S.
C O
M
F:
\0
1- M
IS
C
\2
3-
M O
N
TA
BE
LL
A
SC
H O
O L
EM
ER
G
EN
C Y
G
EN
ER
AT
O R
U
PG
R
AD
ES
\2
3-
2- E-
E3
E
XI
ST
IN
G P
AN
EL
S
PROJECT DESCRIPTION
SHEET DESCRIPTION
AL
L
RI
GH
TS
R
ES
ER
VE
D.
C
OP
YR
IG
HT
M ac M
IL
LA
N
AS
SO
CI
AT
ES
, I
NC
SHEET No.
JOB No.DRAWN BY
DESIGNED BY
APPROVED BY
ISSUED FOR BIDS MAI 11/17/23
MONTABELLA SCHOOLS
ELECTRICAL
PANEL SCHEDULES
E…