Monitoring_Certification_Test_Reports.pdf
PDF 11 MB Posted
- Attached to
- RE-ADVERTISED* IFB No. 131760 Underground Storage Tank Monitoring & Testing, Multiple Locations
- Solicitation number
- 0000040289
- Issued by
- Los Angeles County, Monterey County, San Bernardino County, San Joaquin County, San Luis Obispo County, San Joaquin City, East Los Angeles CDP, Lake Los Angeles CDP, Los Angeles City, Monterey Park City, Santa Monica City, Monterey City, San Bernardino City, San Luis Obispo City, Monterey Park Tract CDP, California
About this file
Monitoring and Certification Test Reports for Underground Storage Tank Systems at California Military Installations
This document is a consolidated PDF containing 12 monitoring, certification, and testing reports for underground storage tank (UST) systems at four California Army National Guard installations: Camp Roberts (MATES 2), Long Beach CSMS, Barstow FMS#2, and Stockton AASF. The reports document compliance inspections and certifications conducted between October 2023 and June 2026, covering overfill prevention equipment, secondary containment systems, release detection equipment, spill containment systems, monitoring system certifications, and emergency safety equipment. Testing services were performed by Baseline Enterprises DBA Central Coast Tank Testing and SunWest Engineering Constructors, Inc., utilizing standardized California regulatory forms and industry standards including PEI/RP1200 guidelines. The reports document inspections of multiple fuel storage tanks ranging from 2,200 to 15,000 gallons, including pressure and vacuum testing of secondary containment systems, verification of sensor and leak detector functionality, spill bucket testing, shear valve inspections, and emergency stop switch operations. Test results predominantly indicate passing conditions, with minimal exceptions noted including one drain valve failure requiring replacement at Camp Roberts and one emergency stop switch requiring replacement at MATES 2.
The reports identify licensed contractors holding appropriate certifications and ICC numbers conducting the work, with service technicians demonstrating current manufacturer training credentials and tank tester licenses in good standing through dates ranging from 2024 to 2027. Documentation confirms adherence to California Code of Regulations Title 23, Division 3, Chapter 16, and includes detailed sensor IDs, equipment models, test methodologies, and measurement data supporting compliance determinations. Equipment manufacturers documented include Veeder-Root, OPW, Red Jacket, Incon, and CNI systems, with all secondary containment, monitoring, and safety systems tested and certified operational. Test equipment calibration is documented per manufacturer specifications, and all post-testing reports and monitoring system setup documentation have been generated and attached where applicable.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IFB_131760_Packet__Re-advertisement_.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
There are 12 reports in total all consolidated in this PDF file.
Appendix IX Underground Storage Tank
Overfill Prevention Equipment Inspection Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council, OPE = Overfill Prevention Equipment
TYPE OF ACTION Installation Repair 36 Month
1. FACILITY INFORMATION
CERS ID Inspection Date
Facility Name
Facility Address City ZIP Code
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Inspection Phone
Mailing Address
Service Technician Performing Inspection
Contractor/Tank Tester License Number
ICC Number Expiration Date
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
4. INSPECTION PROCEDURES INFORMATION
Inspection Procedures Used Components Inspected
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING INSPECTION
I hereby certify that the OPE was inspected in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637.2; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
10471906 06/18/2024
CA Armyt National Guard MATES 2
Hwy 101, East Garrison, Bldg 25025 San Miguel 93451
Baseline Enterprises DBA Central Coast Tank Testing (805) 687-6640
P.O. Box 2155 Santa Barbara, Ca 93120
Andrew Proft
CSLB#873533 / TT#17-1765
5259477 8/19/24
Veeder Root #B33127 11/28/25
OPW 100205 07/29/25
PEI/RP1200 overfill equipment
06/18/2024 4
10471906
Overfill Prevention Equipment Inspection Report
Additional copies of this page may be attached.
Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s)
6. OVERFILL PREVENTION EQUIPMENT DETAILS
Tank ID (one OPE per column) Are both vent and tank riser piping secondarily contained?
Yes No
Yes No
Yes No
Yes No
OPE Model What is the OPE response when activated?
(Check all that apply.)
Shut off Flow Restricts
Flow Audible
Alarm Visual
Alarm
Shut off Flow Restricts Flow Audible
Alarm Visual
Alarm
Shut off Flow Restricts
Flow Audible
Alarm Visual
Alarm
Shut off Flow Restricts
Flow Audible
Alarm Visual
Alarm
Are flow restrictors installed on vent piping that may interfere with the OPE operation?
Yes* No
Yes* No
Yes* No
Yes* No
At what level in the tank is the OPE set to activate? (Inches from bottom of tank) What is the percent capacity of the tank at which the OPE activates?
Is the OPE in proper operating condition to respond when the stored substance reaches the designated regulatory level?
Yes No
Yes* No
Yes* No
Yes* No
7. SUMMARY OF TESTING RESULTS
OPE Inspection Results Pass Fail
Pass Fail
Pass Fail
Pass Fail
8. COMMENTS
Describe all answers marked “No” or “Fail” and proposed remedy.
List all monitoring equipment either replaced or repaired.
* Mark here if:
Flow restrictors interfere with overfill prevention and equipment repairs required.
T#2 (JP8) T#3 (JP8)
OPW OPW
86 86
95 95
INSPECTION PROCEDURE INFORMATION
OPW flapper: Manufacturer guidelines not available. Performed overfill equipment inspection according to Petroleum Equipment Institute (PEI) RP1200 Section 7. Petroleum Equipment Institute RP1200 is copyrighted material.
Tank #1 Removed
Doc Separator
Sheet Each doc is it's own separate report.
Appendix VII
Secondary Containment Testing Report Form
CERS = California Environmental Reporting System, ICC = International Code Council, ID = Identification, NA = Not Applicable, UDC = Under-Dispenser Containment, TYPE OF ACTION Installation Repair 6 Month 36 Month
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
Manufacturer and Test Equipment Training Certifications Expiration Date
Test Procedures Used Components Tested
I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
1. FACILITY INFORMATION
2. SERVICE TECHNICIAN INFORMATION
3. TRAINING AND CERTIFICATIONS
4. TEST PROCEDURE INFORMATION
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
10045075 10/02/2023
CA Army Nat’l Guard FMS 2
1601 Armory Rd. Barstow 92311
Baseline Enterprises DBA Central Coast Tank Testing (805) 687-6640
P.O. Box 2155, Santa Barbara, CA 93120
Jerry Brooks
CSLB#873533
8146908 08/31/2024
Incon Sump Test System #1016093709 11/24/24
PEI/RP1200 Tank Secondary, Line Secondary, Sumps, UDCs
10/02/2023 6
Secondary Containment Testing Report Form
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Tank ID Tank Manufacturer Tank Capacity Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
6. TANK SECONDARY CONTAINMENT TEST
7. PIPE SECONDARY CONTAINMENT TEST
Mc Daniels/3D Test Gauges NIST Tank 1 Tank 2 Owens Corning Owens Corning 6,000 gallons 2,200 gallons 1100 1200
10.0 “Hg 10.0 “Hg 1200 1300
10.0 “Hg 10.0 “Hg 0 0 No change No change
Mc Daniels/3D Test Gauges NIST Tank 1 Product Tank 2 Product Environ Environ 1030 1030
5.0 psi 5.0 psi 1130 1130
5.0 psi 5.0 psi 0 0 No change No change
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID
Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST
Incon TS-STS Sump Test System
Tank 1 Sump Tank 2 Sump UDC 1 UDC 2 ContainmentSolutions ContainmentSolutions Environ Environ 51 51 29 29 21 21 15 15
1224 1224 1224 1224
4.2918 6.0624 4.9463 3.5430
1240 1240 1240 1240
4.2904 6.0624 4.9463 3.5429 -0.001 0 0 -0.001 +/-0.002” +/-0.002” +/-0.002” +/-0.002”
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST (continued)
Measuring stick (accurate w/in 1/16" & of sufficient length) Incon TS-STS Sump Test System
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
9. COMMENTS
Secondary Containment Testing Report Form
CERS = California Environmental Reporting System, ICC = International Code Council, ID = Identification, NA = Not Applicable, UDC = Under-Dispenser Containment, TYPE OF ACTION Installation Repair 6 Month 36 Month
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
Manufacturer and Test Equipment Training Certifications Expiration Date
Test Procedures Used Components Tested
I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
1. FACILITY INFORMATION
2. SERVICE TECHNICIAN INFORMATION
3. TRAINING AND CERTIFICATIONS
4. TEST PROCEDURE INFORMATION
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
10152341 10/18/2023
CA ARNG Long Beach CSMS
3500 Stearns St. Long Beach 90822
Baseline Enterprises DBA Central Coast Tank Testing (805) 687-6640
P.O. Box 2155, Santa Barbara, CA 93120
Jerry Brooks
CSLB#873533
8146908 08/31/2024
Incon Sump Test System #1016093709 11/24/24
10/18/2023 6
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Tank ID Tank Manufacturer Tank Capacity Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
6. TANK SECONDARY CONTAINMENT TEST
7. PIPE SECONDARY CONTAINMENT TEST
Mc Daniels/3D Test Gauges NIST Tank 1 Tank 2 Owens Corning Owens Corning 6,000 gallons 10,000 gallons 1030 1242
10.0 “Hg 10.0 “Hg 1130 1332
10.0 “Hg 10.0 “Hg 0 0 No change No change
Mc Daniels/3D Test Gauges NIST Tank 1 Product Tank 1 Vent Tank 2 Product Tank 2 Vent Environ Environ Environ Environ 1200 1200 1330 1330
5.0 psi 5.0 psi 5.0 psi 5.0 psi 1300 1300 1430 1430
5.0 psi 5.0 psi 5.0 psi 5.0 psi 0 0 0 0 No change No change No change No change
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID
Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST
Incon TS-STS Sump Test System Tank 1 Piping Sump Tank 1 Fill Sump Tank 2 Piping Sump Tank 2 Fill Sump
Owens Corning Owens Corning Owens Corning Owens Corning 42 42 42 42 18 22 18 22
1204 1204 1204 1204
2.8475 5.4489 3.2572 1.7494
1220 1220 1220 1220
2.8474 5.4488 3.2556 1.7489
0.0001 0.0001 0.0016 0.0005
+/-0.002” +/-0.002” +/-0.002” +/-0.002”
UDC 1 UDC 2
Environ Environ 24 24
14 14
1230 1230
7.5594 6.8679
1245 1245
7.5597 6.8681
0.0003 0.0002
+/-0.002” +/-0.002”
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST (continued)
Measuring stick (accurate w/in 1/16" & of sufficient length) Incon TS-STS Sump Test System
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Secondary Containment Testing Report Form
CERS = California Environmental Reporting System, ICC = International Code Council, ID = Identification, NA = Not Applicable, UDC = Under-Dispenser Containment, TYPE OF ACTION Installation Repair 6 Month 36 Month
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
Manufacturer and Test Equipment Training Certifications Expiration Date
Test Procedures Used Components Tested
I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
1. FACILITY INFORMATION
2. SERVICE TECHNICIAN INFORMATION
3. TRAINING AND CERTIFICATIONS
4. TEST PROCEDURE INFORMATION
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
10181267 10/12/2023
Stockton AASF
2000 Stimson Rd Stockton 95206
Baseline Enterprises DBA Central Coast Tank Testing (805) 687-6640
P.O. Box 2155, Santa Barbara, CA 93120
Jerry Brooks
CSLB#873533
8146908 08/31/2024
Incon Sump Test System #1016093709 11/24/24
10/12/2023 6
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Tank ID Tank Manufacturer Tank Capacity Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
6. TANK SECONDARY CONTAINMENT TEST
7. PIPE SECONDARY CONTAINMENT TEST
Mc Daniels/3D Test Gauges NIST Tank 1 Owens Corning 15,000 gallons
10.0 “Hg
10.0 “Hg No change
Mc Daniels/3D Test Gauges NIST Tank 1 Product AST Product Smith Smith 0930 0930
5.0 psi 5.0 psi 1030 1030
5.0 psi 5.0 psi 0 0 No change No change
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID
Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST
Incon TS-STS Sump Test System
UST STP Reel UDC Transition Sump Containment Solutions Containment Solutions Western Fiberglass
32 36 48 18 16 32
1044 1044 1044
7.5098 5.7213 3.3910
1059 1059 1059
7.5096 5.7213 3.3905
0.0002 0 0.0005
+/-0.002” +/-0.002” +/-0.002”
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST (continued)
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Secondary Containment Testing Report Form
CERS = California Environmental Reporting System, ICC = International Code Council, ID = Identification, NA = Not Applicable, UDC = Under-Dispenser Containment, TYPE OF ACTION Installation Repair 6 Month 36 Month
CERS ID Test Date
Facility Name
Facility Address City ZIP Code
Company Performing the Test Phone
Mailing Address
Service Technician Performing Test
Contractor/Tank Tester License Number
ICC Number ICC Expiration Date
Manufacturer and Test Equipment Training Certifications Expiration Date
Test Procedures Used Components Tested
I hereby certify that the secondary containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2637; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date Total # of Pages
1. FACILITY INFORMATION
2. SERVICE TECHNICIAN INFORMATION
3. TRAINING AND CERTIFICATIONS
4. TEST PROCEDURE INFORMATION
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
10471906 10/11/2023
CA Army Nat’l Guard, Camp Roberts, Camp Roberts MATES 2
Hwy 101, East Garrison, Bldg 25025 San Miguel 93451
Baseline Enterprises DBA Central Coast Tank Testing (805) 687-6640
P.O. Box 2155, Santa Barbara, CA 93120
Jerry Brooks
CSLB#873533
8146908 08/31/2024
Incon Sump Test System #1016093709 11/24/24
10/11/2023 7
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Tank ID Tank Manufacturer Tank Capacity Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Pipe Run ID Pipe Manufacturer Test Start Time Initial Reading Test End Time Final Reading Change in Reading Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
6. TANK SECONDARY CONTAINMENT TEST
7. PIPE SECONDARY CONTAINMENT TEST
Mc Daniels/3D Test Gauges NIST Tank 2 Tank 3 Trusco Trusco 5,000 gallons 5,000 gallons 0900 1050
10.0 “Hg 10.0 “Hg 1000 1150
10.0 “Hg 10.0 “Hg 0 0 No change No change
Mc Daniels/3D Test Gauges NIST Tank 2 Product Tank 3 Product Tank 3 Vent AO Smith AO Smith AO Smith 1030 0900 0900
5.0 psi 5.0 psi 5.0 psi 1130 1000 1000
5.0 psi 5.0 psi 5.0 psi 0 0 0 No change No change No Change
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID
Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Additional copies of this page may be attached.
8. SUMP/UDC TEST
Incon TS-STS Sump Test System
DISP #1 Tank 3 DISP#2 Tank 2 DISP#3 Tank 2 DISP#4 Tank 2 Bravo Bravo Bravo Bravo
24.5 24.5 24.5 24.5 12 10 7 9.5
1012 1012 1012 1045
7.1284 3.1209 4.2295 3.6430 1027 1027 1027 1101
7.1283 3.1213 4.2295 3.6434 -0.0001 -0.0004 0 -0.0004 +/-0.002” +/-0.002” +/-0.002” +/-0.002”
Tank 2 STP Tank 3 STP Containment Solutions Containment Solutions
33.5 35
13 15
1045 1045
1.2578 6.1450 1101 1101
1.2579 6.1448 -0.0001 0.0002
+/-0.002” +/-0.002”
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Test Method Developed by Manufacturer Industry Standard Professional Engineer Test Type Pressure Vacuum Hydrostatic Test Equipment Used:
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
Sump/UDC ID Sump Manufacturer Sump Depth (inches) Sump Bottom to Top of Highest Pipe Penetration (inches) Test Start Time
Initial Reading
Test End Time
Final Reading
Change in Reading
Pass/Fail Criteria
Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail
8. SUMP/UDC TEST (continued)
All tests marked “Fail” and any repairs made before or during the tightness test must be described in the COMMENTS section.
Overfill Prevention Equipment Inspection Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council, OPE = Overfill Prevention Equipment
TYPE OF ACTION ☐ Installation ☐ Repair ☒ 36 Month
1. FACILITY INFORMATION
CERS ID
10045075
Inspection Date
2025-10-22 Facility Name
CA Army National Guard Barstow FMS#2
Facility Address
1601 Armory Rd
City
Barstow
ZIP Code
92311
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Inspection
SunWest Engineering Constructors, Inc
Phone
(888) 588-8737
Mailing Address
4780 Cheyenne Way, Chino, CA 91710 Service Technician Performing Inspection
Westley Troncoso Contractor/Tank Tester License Number
703190 ICC Number
9430867
Expiration Date
2026-01-03
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
VEEDER - ATG Technician 2026-02-11
4. INSPECTION PROCEDURES INFORMATION
Inspection Procedures Used Components Inspected
Manufacturer ATG
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING
INSPECTION
I hereby certify that the OPE was inspected in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.2; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
Service Technician Signature Date
2025-10-22
Total # of Pages
SA-63844
Overfill Prevention Equipment Inspection Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council, OPE = Overfill Prevention Equipment
6. OVERFILL PREVENTION EQUIPMENT DETAILS
Tank ID (one OPE per column) T1 Diesel T2 Diesel
Are both vent and tank riser piping secondarily contained?
☒ Yes ☐ No
☒ Yes ☐ No
☐ Yes ☐ No
☐ Yes ☐ No
OPE Model 846390-104 846390-104
What is the OPE response when activated?
(Check all that apply.)
☐ Shuts off Flow
☐ Restricts Flow
☒ Audible Alarm
☒ Visual Alarm
☒ Shuts off Flow
☒ Restricts Flow
☐ Audible Alarm
☐ Visual Alarm
☐ Shuts off Flow
☐ Restricts Flow
☐ Audible Alarm
☐ Visual Alarm
☐ Shuts off Flow
☐ Restricts Flow
☐ Audible Alarm
☐ Visual Alarm
Are flow restrictors installed on vent piping that may interfere with the OPE operation?
☐ Yes ☒ No
☐ Yes ☒ No
☐ Yes ☐ No
☐ Yes ☐ No
At what level in the tank is the OPE set to activate? (Inches from bottom of tank)
57.5 50
What is the percent capacity of the tank at which the OPE activates?
90 90
Is the OPE in proper operating condition to respond when the stored substance reaches the designated regulatory level?
☒ Yes
☐ No
☒ Yes
☐ No
☐ Yes
☐ No
☐ Yes
☐ No
7. SUMMARY OF TESTING RESULTS
OPE Inspection Results ☒ Pass
☐ Fail
☒ Pass
☐ Fail
☒ Pass
☐ Fail
☐ Pass
☐ Fail
8. COMMENTS
Are Flow Restrictors Installed?
☐ Yes
☒ No
☐ Yes
☒ No
☐ Yes
☐ No
☐ Yes
☐ No
Describe all results marked "Fail" and each proposed remedy.
* Mark here if:
☐ Flow restrictors interfere with overfill prevention and equipment repairs required.
Additional copies of this page may be attached.
Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s)
Appendix 5
Release Detection Equipment Testing Report Form
TYPE ACTION ☐ Installation ☐ Repair ☒ 12 Month
1. FACILITY INFORMATION
CERS ID
10152341
Test Date 2026-04-30
Facility Name CA Army National Guard Long Beach CSMS
Facility Address 3500 Stearns St
City Long Beach
ZIP Code 90822
2. SERVICE TECHNICIAN INFORMATION
Company Performing Testing SunWest Engineering Constructors, Inc.
Phone
(888) 588-8737
Mailing Address 4780 Cheyenne Way, Chino, CA 91710
Service Technician Performing Testing William Wright
Contractor License Number 703190
ICC Certification 10233162
ICC Expiration Date 2026-12-02
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Training Expiration Date
VEEDER - ATG Technician 2027-04-04
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that all equipment identified in this form has been tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2663; that required supporting documentation is attached; and all information contained herein is accurate.
Service Technician Signature Date 2026-04-30
Total # of Pages
CERS = California Environmental Reporting System, GPH = Gallons Per Hour, ID = Identification, ICC = International Code Council, LLD = Line Leak Detector, NA = Not Applicable, UDC = Under Dispenser Containment, UST = Underground Storage Tank, VPH = Vacuum/Pressure/Hydrostatic
SA-56474
Release Detection Equipment Testing Report Form
5. MONITORING SYSTEM AND PROGRAMMING
A separate Release Detection Equipment Testing Report Form must be prepared for each monitoring system.
Manufacturer of Monitoring
System Control Panel
Veeder-Root
Model of Monitoring System
Control Panel
TLS-350
Software Version Installed
122.00
Attach the post-testing reports if the monitoring system is capable of generating either: ☒ Monitoring System Set-up Report ☒ Alarm History Report Yes No NA
Is all release detection equipment that was tested operational per manufacturer's specifications?
Is the secondary containment free of damage, debris, or liquid? ☒ ☐
Are the release detection audible and visual alarms operational? ☒ ☐
Have all sensors been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational?
Are all sensors installed to detect a release at the earliest opportunity? ☒ ☐ ☐
Was the monitoring system set-up reviewed, and proper settings confirmed? ☒ ☐ ☐
Was the monitoring system's backup battery visually inspected, functionally tested, and confirmed operational?
Was it confirmed that the flow of hazardous substance stops at the dispenser if a release is detected in the under-dispenser containment?
Does the pressure supply pump automatically shut down if the piping secondary containment monitoring system fails to operate or is disconnected?
Does the pressure supply pump automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down? (Check all that apply) ☐ Containment Sump ☐ UDC
If release detection alarms are relayed to a remote monitoring center, is all communication equipment operational?
If there is any buried single-wall suction hazardous substance piping, was it confirmed using the inspection method approved by the Unified Program Agency, that the pipe contents drain back into the UST if the suction is released?
Describe all answers marked "No" or "Fail" and the proposed remedy in Section 8.
List all equipment either replaced or repaired (including cleaning or adjustment) in Section 8
6. SENSOR TEST RESULTS
☐ Check this box if Appendix 5.1 continuation page is attached.Check this box if Appendix 5.1 continuation page is attached.
List only sensors tested. List "Sensor ID" as labeled in system programming. For VPH monitoring, continuity must be confirmed between the most distant points in the interstitial space to the extent practical as approved by the Unified Program Agency and the sensor that monitors the zone.
Sensor
ID
Sensor Model
Component(s) Monitored Function Continuity
Pass Fail Pass Fail NA
C1 794390-344 Diesel Tank Interstitial ☒ ☐ ☐ ☐ ☒
C2 794390-344 Diesel Tank Interstitial ☒ ☐ ☐ ☐ ☒
L1 794380-208 Diesel Fill Sump ☒ ☐ ☐ ☐ ☒
L2 794380-208 Diesel Piping Sump ☒ ☐ ☐ ☐ ☒
L4 794380-208 Diesel UDC ☒ ☐ ☐ ☐ ☒
L5 794380-208 Diesel Fill Sump ☒ ☐ ☐ ☐ ☒
L6 794380-208 Diesel Piping Sump ☒ ☐ ☐ ☐ ☒
L8 794380-208 Diesel UDC ☒ ☐ ☐ ☐ ☒
Describe all answers marked "No" or "Fail" and the proposed remedy in Section 8.
List all equipment either replaced or repaired (including cleaning or adjustment) in Section 8.
7. LINE LEAK DETECTOR TEST RESULTS
☒ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
☐ Check this box if Appendix 5.2 continuation page is attached.
Simulated release rate verified: (Check all that apply.)
☐ 3 GPH ☐ 0.1 GPH (Required only if LLD performs line tightness testing) Yes No NA
Has the testing equipment been properly calibrated? ☐ ☐ ☐
For emergency tank systems, does the LLD create an audible and visual alarm when a release is detected?
For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected?
For electronic LLDs, does the pressure supply pump automatically shut off when a release is detected?
For electronic LLDs, does the pressure supply pump automatically shut off if the monitoring system or LLD is disabled or disconnected?
For electronic LLDs, does the pressure supply pump automatically shut off if the monitoring system or LLD malfunctions or fails a tightness test?
For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks?
Were all items on the equipment manufacturer's maintenance checklist completed?
Were all LLDs confirmed operational within regulatory requirements? ☐ ☐ ☐
List only line leak detectors tested.
LLD ID LLD Model Lines Monitored Pass Fail
8. COMMENTS
Describe all answers marked "No" or "Fail" and proposed remedy.
List all release detection equipment either replaced or repaired (including cleaning or adjustment).
9. MONITORING SITE PLAN
Attach a copy of the facility's UST Monitoring Site Plan that shows the general layout of tanks and dispensers, locations of the monitoring panel and all other release detection equipment, VPH monitoring zones (if applicable), and the date the site plan was prepared. Include a legend for all symbols depicted.
Date Site Plan Was Prepared: 2026-04-30
Describe all answers marked "No" or "Fail" and the proposed remedy in Section 8.
Appendix 6
Spill Containment Testing Report Form TESTING TYPE ☐Installation ☐Repair ☒ 12 Month
1. FACILITY INFORMATION
CERS ID
10152341
Test Date 2026-04-30
Facility Name CA Army National Guard Long Beach CSMS
Facility Address 3500 Stearns St
City Long Beach
ZIP Code 90822
2. SERVICE TECHNICIAN INFORMATION
Company Performing Testing SunWest Engineering Constructors, Inc
Phone
(888) 588-8737
Mailing Address 4780 Cheyenne Way, Chino, CA 91710
Service Technician Performing Testing William Wright
Contractor License Number 703190
ICC Certification 10233162
ICC Expiration Date 2026-12-02
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Training Expiration Date
CNI - EVR System Trained Installer EVR Phase 1 E.O 2026-06-21
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
All spill containment tested
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING TEST
I hereby certify that each spill containment was tested in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2664; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures must be made available upon request by the governing authority.
Service Technician Signature Date 2026-04-30
Total # of Pages
CERS = California Environmental Reporting System, ICC = International Code Council, ID = Identification
PEI/PR 1200
Spill Containment Testing Report Form
6. SPILL CONTAINMENT DETAILS
Test Method Developed by ☐ Manufacturer ☐ Industry Standard ☐ Professional Engineer
Test Type ☐ Pressure ☐ Vacuum ☒ Hydrostatic
☐ Check this box if Appendix 6.1 continuation page is attached.
Tank ID T1 T2
Spill Containment Manufacturer: CNI CNI
Method of Cathodic Protection ☒ Nonmetallic ☒ Nonmetallic ☐ Nonmetallic ☐ Nonmetallic
☐ Other ☐ Other ☐ Other ☐ Other
Is the spill containment minimum capacity five gallons excluding riser volume?
☒ Yes ☒ Yes ☐ Yes ☐ Yes
☐ No* ☐ No* ☐ No* ☐ No*
Method to keep spill containment empty
☒ Drain ☒ Drain ☐ Drain ☐ Drain
☐ Pump ☐ Pump ☐ Pump ☐ Pump
☐ Other ☐ Other ☐ Other ☐ Other
Spill Containment Test Results ☒ Pass ☒ Pass ☐ Pass ☐ Pass
☐ Fail ☐ Fail ☐ Fail ☐ Fail
Tank ID
Spill Containment Manufacturer:
Method of Cathodic Protection ☐ Nonmetallic ☐ Nonmetallic ☐ Nonmetallic ☐ Nonmetallic
☐ Other ☐ Other ☐ Other ☐ Other
Is the spill containment minimum capacity five gallons excluding riser volume?
☐ Yes ☐ Yes ☐ Yes ☐ Yes
☐ No* ☐ No* ☐ No* ☐ No*
Method to keep spill containment empty
☐ Drain ☐ Drain ☐ Drain ☐ Drain
☐ Pump ☐ Pump ☐ Pump ☐ Pump
☐ Other ☐ Other ☐ Other ☐ Other
Spill Containment Test Results ☐ Pass ☐ Pass ☐ Pass ☐ Pass
☐ Fail ☐ Fail ☐ Fail ☐ Fail
7. COMMENTS
Check this box if any spill containment has less than 5 gallons capacity and requires replacement Describe all answers marked "Other," "No," or "Fail" and each proposed remedy in Section 7.
Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities
APPENDIX C-11
EMERGENCY STOP SWITCH OPERATION INSPECTION
Facility Name: CA Army National Guard Long Beach CSMS Owner: Fred Delucchi
Address: 3500 Stearns St Address:
City, State, Zip Code: Long Beach, CA 90822 City, State, Zip Code: , Facility I.D. #: Phone #:
Testing Company: SunWest Engineering Constructors, Inc Phone #: (888) 855-8737 Date:
This procedure is to verify the operation of all emergency stop switches/buttons (E-stops). Each E-stop must disconnect power to dispensers, submersible turbine pumps (STPs) and all non-intrinsically safe electrical equipment in classified areas. Test each
E-stop separately. See PEI/RP1200 Section 11 for the inspection procedure.
E-stop Number or ID 1
Location Building C Wall
1. E-stops labeled and located where easily accessible?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
2. System fully powered and in normal operating condition?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3. After activating E-stop, power disconnected from:
3a. All dispensing devices on all islands?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3b. All STPs for all fuel grades? ☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3c. All power, control and signal circuits associat- ed with the dispensing devices and the
STPs?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
3d. All other non-intrin- sically safe electrical equipment in classified areas surrounding fuel dispensing devices?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
4. All intrinsically safe electri- cal equipment remains energized after E-stop acti- vation?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
5. After testing, E-stop has been reset and power rees-tablished to normal operat- ing condition?
☒Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No ☐Yes ☐No
A "No" to lines 3a-3d indicates a test failure.
Test Results ☒Pass ☐Fail ☐Pass
☐Fail
☐Pass
☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
☐Pass
☐Fail
Comments:
Tester's Name (print) William Wright Tester's Signature pei.org 63
P E
I/ R
P
-2
A
P E
N D
IX
C
-1
SHEAR VALVE OPERATION INSPECTION
Owner: Fred Delucchi
Address:
City, State, Zip Code: , Phone #:
Phone #: (888) 588-8737
This data sheet is for inspecting shear valves located inside dispensers. See PEI/RP1200 Section 10 for the inspection procedure.
☐Yes ☐No
☐Yes ☐No
☐Yes
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
A "No" to Lines 1-4 or a "Yes" for Line 5 indicates a test failure.
☐Pass
☐Fail
Comments:
2026-04-30 Test Date
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
Facility Name: CA Army National Guard Long Beach CSMS
Address: 3500 Stearns St
City, State, Zip Code: Long Beach, CA, 90822
Facility I.D.#: 10152341
Testing Company: SunWest Engineering Constructors, Inc.
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
☐Yes ☐No
☐Yes ☐No
☐Yes ☐No
☐NA
☐Yes ☐No
☐NA
☐Yes ☐No ☐Yes ☐No
☐NA
☐Pass
☐Fail
Tester's Signature
Diesel
Product
☒Yes ☐No
☒Yes ☐No
☒Yes ☐No
☐NA
☒Yes ☐No
☐NA
☐Yes ☒No ☐Yes ☒No
☐NA
☒Pass
☐Fail
Diesel
Product
☒Yes ☐No
☒Yes ☐No
☒Yes ☐No
☐NA
☒Yes ☐No
☐NA
☐Yes ☒No ☐Yes ☒No
☐NA
☒Pass
☐Fail
Product Grade
Dispenser ID#
Shear Valve Type
(Product/Vapor)
1. Is the shear valve rigidly anchored to the dispenser box frame or dispenser island?
2. Is the shear section posi-tioned between ½ inch above or below the top surface of the dispenser island?
3. Is the lever arm free to move?
4. Does the lever arm snap shut the poppet valve?
5. Can any product be dis-pensed when the product shear valve is closed?
Test Results
Tester's Name (print) p e i.o rg
Monitoring System Certification Form
TYPE OF ACTION ☐ Installation ☐ Repair ☒ 12 Month
1. FACILITY INFORMATION
CERS ID
10181267
Certification Date
2025-07-01
Facility Name
CA Army National Guard Stockton AASF
Facility Address
2000 Stimson Rd
City
Stockton
ZIP Code
95206
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification
SunWest Engineering Constructors, Inc.
Phone
(888) 588-8737
Mailing Address
4780 Cheyenne Way, Chino, CA 91710 Service Technician Performing Test
William Wright Contractor/Tank Tester License Number
703190
ICC Number
10233162
ICC Expiration Date
2026-12-02
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
VEEDER - ATG Technician 2027-04-04
VMI - VMI LDT-890 Leak Detector Tester 2025-09-06
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING
TEST
I hereby certify that the monitoring system is operational in accordance with California Code of Regulations, title 23, division 3, chapter 16, section 2638; that required supporting documentation is attached; and all information contained herein is accurate.
Service Technician Signature
Date
Total # of Pages
SA-56472
5. MONITORING SYSTEM AND PROGRAMMING
A separate Monitoring System Certification Form must be prepared for each control panel.
Make of Monitoring System
Control Panel
Veeder Root
Model of Monitoring System
Control Panel
TLS-350
Software Version Installed
129.02
Attach the post-certification reports if the monitoring system is capable of generating either; # ☒ Monitoring System Set-up ☒Alarm History Report Yes No NA
All monitoring equipment is operational per manufacturer's specifications? ☒ ☐
Secondary containment systems are free of damage, debris, or liquid? ☒ ☐
Are the audible and visual alarms operational? ☒ ☐
All sensors have been: 1) visually inspected for wiring kinks, breaks and residual buildup on floats; and 2) tested for functionality and confirmed operational?
Are all sensors installed to detect a release at the earliest opportunity in the secondary containment?
The monitoring system set-up was reviewed, and proper settings confirmed?
Was the monitoring control panel's backup battery visually inspected, functionally tested, and confirmed operational?
Does the flow of fuel stop at the dispenser if a release is detected in the under-dispenser containment?
Does the turbine automatically shut down if the piping secondary containment monitoring system fails to operate or is electrically disconnected?
Does the turbine automatically shut down if the piping secondary containment monitoring system detects a release? Which sensors initiate positive shut down?
(Check all that apply) ☒ Sump ☒ UDC
If monitoring system alarms are relayed to a remote monitoring center, is all communication equipment operational?
Describe all answers marked "No" or "Fail" and proposed remedy in Section 9.
List all monitoring equipment either replaced or repaired in Section 9
6. SENSOR TESTING RESULTS
List only sensors tested on date of this certification. List "Sensor ID" as labeled in system programming. Additional copies of this page may be attached to accommodate all sensors tested.
Sensor ID Sensor Model Component(s) Monitored Pass Fail
L1 794390-420 T1 Annular Space ☒ ☐
L2 794380-208 T1 STP Sump ☒ ☐
L3 794380-208 Transition Sump ☒ ☐
L4 794380-208 Bulk UDC ☒ ☐
L5 794390-420 T2 Annular Space ☒ ☐
7. LINE LEAK DETECTOR TESTING
☐ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.)
Simulated release rate verified: (Check all that apply.)
☐ 3 GPH ☐ 0.1 GPH ☐ 0.2 GPH
Yes No NA
Has the testing apparatus been properly calibrated? ☐ ☐ ☐
For emergency generator tank systems, does the LLD create an audible and visual alarm when a leak is detected?
For mechanical LLDs, does the LLD restrict the flow through the pipe when a release is detected?
For electronic LLDs, does the turbine automatically shut off when a release is detected?
For electronic LLDs, does the turbine automatically shut off if any portion of the monitoring system is disabled or disconnected?
monitoring system malfunctions or fails a tightness test?
For electronic LLDs, have all accessible wiring connections been visually inspected for kinks and breaks?
Were all items on the equipment manufacturer's maintenance checklist completed?
Were all LLDs confirmed operational within regulatory requirements? ☐
LLD ID LLD Model Lines Monitored Pass Fail
8. IN-TANK GAUGING TESTING
☒ Check this box if tank gauging is used only for inventory control.
☐ Check this box if NO tank gauging equipment is installed.
(Do not complete this section if either box is checked.)
Yes No NA
All wiring has been: 1) visually inspected for kinks, breaks and proper entry and termination; and 2) tested for ground faults?
Were all in-tank gauging probes visually inspected for damage and residue buildup to ensure that floats move freely, functionally tested, and confirmed operational?
Was accuracy of system's product level readings tested? ☐ ☐ ☐
Was accuracy of system's water level readings tested? ☐ ☐ ☐
Were all probes reinstalled properly? ☐ ☐ ☐
Were all items on the equipment manufacturer's maintenance checklist
Probe ID Probe Model Tanks Monitored Pass Fail
List all monitoring equipment either replaced or repaired.
Line Leak Detector was not able to be tested at this time.
10. MONITORING SITE PLAN
Date site plan was prepared: 2025-07-01
If a site plan has been prepared that shows all required information, you may include it, rather than this page, with your Monitoring System Certification Form. The site plan must show the general layout of tanks and identify locations of the monitoring panel, and all leak detection equipment and monitoring locations. Include a legend for all symbols depicted.
Mechanical Leak Detector Test Data Sheet
Site Name Date
Address
1 2 3 4 5
Product
Manufacturer
Model
Full Operating Pressure (PSI)
Line Bleed Back (mL)
Trip Time (sec)
Metering Pressure (PSI)
F/E Holding Pressure (PSI)
Test Leak Rate (ml/min)(gph)
This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment manufacturers procedures and limitations and the results as listed are to my knowledge true and correct. The mechanical leak detector test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI.
Inspected By: Contractor SunWest Engineering Constructors
Technician William Wright Lic#10233162
Signature
Test Information
CA Army National Guard Stockton AASF
2025-07-01
Stockton 95206
Emergency Stop Switch Test
Work Order # 00065772
Date 2025-07-01
Street Address 2000 Stimson Rd
City, State Stockton, 95206
Total Time Testing E-Stop 0.834792916
Shut Down Location of E-Stop Turbine (Y/N) Dispenser (Y/N) Comments/Repairs
Outside Wall Y N
Inside Wall N N
Other
Other
Other
Test Result (Pass/Fail) Pass
Appendix VIII
Spill Container Testing Report Form
CERS = California Environmental Reporting System, ID = Identification, ICC = International Code Council
10181267
Test Date
Facility Name
CA Army National Guard Stockton AASF
Stockton
95206
Company Performing the Test
SunWest Engineering Constructors, Inc
Phone
(888) 588-8737
Mailing Address
4780 Cheyenne Way, Chino, CA 91710 Service Technician Performing Test
William Wright Contractor/Tank Tester License Number
703190 ICC Number
10233162
2026-12-02
OPW - EVR UST /AST
2027-02-17
4. TEST PROCEDURE INFORMATION
Test Procedures Used Components Tested
PEI/RP 1200 T1 Diesel Spill Bucket
5. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING
TEST I hereby certify that each spill container was tested in accordance with California Code of
Regulations, title 23, division 3, chapter 16, section 2637.1; that required supporting documentation is attached; and all information contained herein is accurate. I understand that test procedures shall be made available upon request by the governing authority.
6. SPILL CONTAINER DETAILS
SA-56472
Spill Container Testing Report Form
Test Method Developed by ☐ Manufacturer ☒ Industry Standard ☐ Professional Engineer
Test Type ☐ Pressure ☐ Vacuum ☒ Hydrostatic
Tank ID T1 Diesel
Spill Container Manufacturer: OPW
Method of Cathodic Protection ☒ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
Is the spill container minimum capacity five gallons excluding riser volume?
☒ Yes ☐ No*
☐ Yes ☐ No*
☐ Yes ☐ No*
☐ Yes ☐ No*
Method to keep spill container empty
☒ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
Spill Container Test Results ☒ Pass ☐ Fail
☐ Pass ☐ Fail
☐ Pass ☐ Fail
☐ Pass ☐ Fail
Tank ID
Spill Container Manufacturer:
Method of Cathodic Protection ☐ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
☐ Nonmetallic ☐ Other
Is the spill container minimum capacity five gallons excluding riser volume?
☐ Yes ☐ No*
☐ Yes ☐ No*
☐ Yes ☐ No*
☐ Yes ☐ No*
Method to keep spill container empty
☐ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
☐ Drain ☐ Pump ☐ Other
Spill Container Test Results ☐ Pass ☐ Fail
☐ Pass ☐ Fail
☐ Pass ☐ Fail
☐ Pass ☐ Fail
8. COMMENTS
Describe all answers marked "Other," "No," or "Fail" and each proposed remedy.
Other Cathodic Protection Comments: || Other Method Comments: || Failure
Explanations: || Additional Comments:
☐ Spill containers do not have a minimum capacity of five gallons and require replacement.
Spill Container Testing Report Form
TYPE OF ACTION ☐ Installation ☐ Repair ☒ 12 Month
1. FACILITY INFORMATION
CERS ID
10045075
Certification Date
2025-10-22
Facility Name
CA Army National Guard Barstow FMS#2
Facility Address
1601 Armory Rd
City
Barstow
ZIP Code
92311
2. SERVICE TECHNICIAN INFORMATION
Company Performing the Certification
SunWest Engineering Constructors, Inc.
Phone
(888) 588-8737
Mailing Address
4780 Cheyenne Way, Chino, CA 91710 Service Technician Performing Test
Westley Troncoso Contractor/Tank Tester License Number
703190
ICC Number
9430867
ICC Expiration Date
2026-01-03
3. TRAINING AND CERTIFICATIONS
Manufacturer and Test Equipment Training Certifications Expiration Date
VEEDER - ATG Technician 2026-02-11
4. CERTIFICATION BY SERVICE TECHNICIAN CONDUCTING
TEST
I hereby certify that the monitoring system is operational in accordance with California Code of…