Minimum Requirements.pdf
PDF 942 KB Posted
- Solicitation number
- N6660424Q0295
About this file
This document appears to be the Minimum Requirements for a federal contract solicitation related to Fiber Optic Cabling and Accessories.
The solicitation, numbered N6660424Q0295, is for Fiber Optic Cabling and Accessories, Unshielded Twisted Pair Cable and Accessories, and Network Cabinets and Accessories. The document specifies the required fiber optic cable, connectors, and associated hardware, identified by manufacturer part numbers, with no substitutions allowed. The cable and components must meet detailed technical requirements such as fiber count, cable type, jacket color, and tensile strength. The document also lists the required quantities for each CLIN. This is likely an attachment to the full solicitation, which is not provided here.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| I.G. Minimum Requirements.pdf | ||
| Combined Synopsis.pdf | ||
| Combined Synopsis.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N66604-24-Q-0295 Minimum Requirements
A. Fiber Optic Cabling and accessories:
The following items are required on a Brand Name basis – No substitutions allowed, and will be represented by CLINs 1 – 24:
Material List A: (CLINs 1-24) BRAND NAME SPECIFIC – NO SUBSTITUTIONS
CLIN Manufacturer Part Number Description Qty.
1 Corning 024EWP-T4101D20 FREEDM® Loose Tube, Gel-Free Cable, Plenum 24 F, Single-mode (OS2)
2 Corning 024EWP-T4101D20 FREEDM® Loose Tube, Gel-Free Cable, Plenum 24 F, Single-mode (OS2)
3 3M 80-6111-2762-4 Hotmelt Sing Mode ST (8100-YS) 100 4 3M 80-6111-2765-7 Hotmelt Sing Mode SC (8300) 100 5 L-Com SFODLC-01 9/125, Single mode Fiber Cable, Dual LC /Dual LC, 1.0m
6 L-Com SFODLC-03 9/125, Single mode Fiber Cable, Dual LC /Dual LC, 3.0m
7 L-Com SFODLC-05 9/125, Single mode Fiber Cable, Dual LC /Dual LC, 5.0m
8 L-Com SFODLC-10 9/125, Single mode Fiber Cable, Dual LC /Dual LC, 10.0m
9 L-Com SFODSC-LC-01 "SC to LC, Duplex Singlemode Fiber Optic Cables, 9/125 with OFNR Jacket, 1 Meter"
10 L-Com SFODSC-LC-03 "SC to LC, Duplex Singlemode Fiber Optic Cables, 9/125 with OFNR Jacket, 3 Meter"
11 L-Com SFODSC-LC-05 "SC to LC, Duplex Singlemode Fiber Optic Cables, 9/125 with OFNR Jacket, 5 Meter"
12 L-Com SFODSC-LC-10 "SC to LC, Duplex Singlemode Fiber Optic Cables, 9/125 with OFNR Jacket, 10 Meter"
13 L-Com SFODSC-01 9/125, Single mode Fiber Cable, Dual SC /Dual SC, 1.0m
14 L-Com SFODSC-02 9/125, Single mode Fiber Cable, Dual SC /Dual SC, 2.0m
15 L-Com SFODSC-03 9/125, Single mode Fiber Cable, Dual SC /Dual SC, 3.0m
16 L-Com SFODSC-05 9/125, Single mode Fiber Cable, Dual SC /Dual SC, 5.0m
17 L-Com SFODSC-10 9/125, Single mode Fiber Cable, Dual SC /Dual SC, 10.0m
18 Leviton 5R1UM-S03 Opt-X 1000i 1U Distribution and Splice Enclosure With Sliding Tray
19 Leviton 5R2UM-S06 Opt-X 1000i 2RU Distribution and Splice Enclosure With Sliding Tray
20 Leviton 5WMED-04C Sdx Medium Wall-Mount Patch And Splice Enclosure, Leviton 5F100-2LC
Opt-X Precision Molded Plate (Blue), Single-mode OS1/2, Duplex SC, 12 Fibers, Zirconia Ceramic
Sleeve 150
Leviton T5PLS-24F Injection Molded High Density Splice Tray, Heat
Shrink Style 85 23 Leviton SPLMT-HKT Leviton Kit, Splice Tray Mounting Hardware 25
Fibertronics SP-12SCSM3
12 FIBER SC SINGLEMODE 9/125UM FIBER OPTIC
PIGTAILSFOR SPLICING, MULTI-COLOR 900 50
CLINs 1-2 shall meet the following minimum requirements:
o 2 strand Fiber Single Mode OS2 Fiber;
o Tight Buffered;
o ONFR Riser Zipcord ;
o Yellow color outer jacket;
o Maximum Short term tensile strength – 50 lbf;
o Maximum Long term Tensile Strength – 22.5 lbf;
CLINs 3-4 shall meet the following minimum requiremens:
o <0.2 dB Insertion Loss;
o Zirconia ceramic connector ferrule;
o -40dB Reflection;
CLINs 5-17 shall meet the following minimum requiremens:
o 9/125 SINGLEMODE DUPLEX FIBER ZIPCORD;
o Ceramic connector ferrule;
o OFNR (Riser rated) jacket;
o Available in 1-meter, 2-meter, 3-meter, 5-meter, 10-meter lengths o Available in the following connector configurations;
Dual LC/Dual LC Connectors Dual SC/Dual LC Connectors Dual SC/Dual SC Connectors
CLINs 18-23 shall meet the following minimum requirements:
o Fiber optic wall mount enclosures to be made from 16-Guage steel;
o Santoprene cable entry/exit grommets;
o Enclosures must have black powder coat;
o Enclosures must accept SDX adapter plates, splice modules and/or cassettes;
o Enclosures must be capable of following maximum single type fiber density;
Small Wall Mount enclosure;
48 LC connectors;
24 SC connectors;
Medium Wall Mount Enclosure;
96 LC Connectors;
48 SC Connectors;
Large Wall Mount Enclosures;
288 LC Connectors;
144 SC Connectors;
2RU Rack Mountable Enclosures;
144 LC Connectors;
72 SC connectors;
1RU Rack Mountable Enclosures;
72 LC Connectors;
36 SC Connectors;
o Adapter Plates must be compatible with SDX enclosures;
Plates must be blue;
Plates must be available in both 12 SC connector configurations;
Plates must have a Zirconia Ceramic Sleeve;
Plates must have visible sequential numbering;
o Splice Trays must accept 24 heat-shrink-style fusion spliced fibers;
Splice Sleeves to be included;
Accommodates standard heat-shrink sleeves in 40 or 60 mm lengths;
Center hole for mounting of tray;
Four ratchet action clamps with foam rubber padding to minimize crush of loose tube or tight buffer fiber;
Must be compatible with SDX enclosures;
o Mounting hardware must be compatible to mount Leviton splice trays;
CLIN 24 shall meet the following minimum requirements:
o 12 single mode fiber (OS2) 9/125 SC connector multicolor pigtails;
o Pigtails to be 3 meters in length
B. Unshielded Twisted Pair (UTP) Cable and accessories:
The following items are required on a Brand Name basis – No substitutions allowed, and will be represented by CLINs 25 – 30:
Material List B: (CLINs 26-30) BRAND NAME SPECIFIC – NO SUBSTITUTIONS
CLIN Manufacturer Part Number Description Qty.
25 Commscope Uniprise
UNJ600-YL UNIPRISE MODULAR RJ45 JACK CAT 6, UTP 8 POSITION,
YELLOW
26 Commscope Uniprise
UNJ600-RD UNIPRISE MODULAR RJ45 JACK CAT 6, UTP 8 POSITION, RED 400
27 Commscope Uniprise
M12L-262 L TYPE FLUSH MOUNTED FACEPLATE, TWO PORT WHITE 200
28 Panduit NK6PPG48Y NK PUNCHDOWN PATCH PANEL, CATEGORY 6, FLAT, 48 PORT, 2 RU
29 Panduit LD5WH6-A PANWAY LD5 WHITE – RIGID PVC, 6 FEET IN LENGTH 50
30 Panduit LD10WH6-A LD10 Low Voltage 1-piece Single Channel Raceway With Adhesive 6FT
CLINs 25-26 shall meet the following minimum requirements:
o Meets ANSI/TIA Category 6 requirements;
o Modular jacks must be available in Yellow and Red colors;
o Accepts Solid and Stranded Cat 6 cable;
o Displays T568A and T568B standards on the side of the jack;
o Jacks must be able to mount to M-series faceplates and panels;
o Compatible with 24-22 AWG solid conductor;
o Compatible with 26-24 AWG stranded conductor;
o Gold plated contacts;
CLIN 27 shall meet the following minimum requirements:
o Flush Mount faceplate needs to be compatible with two M Series Modular jacks;
o Flush mount faceplate to be white in color;
o Flush mount faceplate to have Two Available ports;
CLIN 28 shall meet the following minimum requirements:
o Punch down patch panel to be made from Steel;
o Patch panel to have 48 available ports;
o Patch panel to display T568A /T568B wiring schemes on back;
o Patch panel must be 2RU (Rack Units) in height;
o Patch panel must fit a standard 19” Server rack;
o Patch Panel must have adhesive type identification labels;
CLINs 29-30 shall meet the following minimum requirements:
o Raceway must be made from white rigid PVC;
o Raceway must be a one piece latching system;
o Raceway must have an adhesive backing;
o Raceway must come in 6 foot lengths;
o Raceway must be 0.77” W x 0.46” D;
o Raceway must be 1.51" W x 0.94" D;
The following items are required on a Brand Name or Equal basis, and will be represented by CLINs 31 – 46:
Material List C: (CLINs 31-46) BRAND NAME OR EQUAL CLIN Manufacturer Part Number Description Qty.
31 Panduit
TMEH-S25-Q0 EXTRA HEAVY CABLE MOUNT #1/4 (M6) - 25PK 20
32 LIEBERT 11171448 CABLE HOLDER - 2U RACK HEIGHT 100
New York Cable NYC-613
YELLOW CAT6 PLENUM ETHERNET CABLE, 100%
SOLID COPPER CONDUCTOR,
CMP, 23AWG, UTP 550MHZ 50
New York Cable NYC-617
RED CAT6 PLENUM ETHERNET CABLE, 100% SOLID
COPPER CONDUCTOR,
CMP, 23AWG, UTP 550MHZ 60
Leviton 62460-3G
EXTREME 6+ PATCH CORD, CAT6 COLOR GREEN, 3
FT LONG 500
Leviton 62460-7G
EXTREME 6+ PATCH CORD, CAT6 COLOR GREEN, 7
FT LONG 500
Leviton
62460-15G EXTREME 6+ PATCH CORD, CAT6 COLOR GREEN, 15
FT LONG 500
Leviton 62460-25G
EXTREME 6+ PATCH CORD, CAT6 COLOR GREEN, 25
FT LONG 500
Leviton 62460-3R
EXTREME 6+ PATCH CORD, CAT6 COLOR RED, 3 FT
LONG 100
Leviton 62460-7R
EXTREME 6+ PATCH CORD, CAT6 COLOR RED, 7 FT
LONG 100
Leviton 62460-15R
EXTREME 6+ PATCH CORD, CAT6 COLOR RED, 15 FT
LONG 100
Leviton 62460-25R
EXTREME 6+ PATCH CORD, CAT6 COLOR RED, 25 FT
LONG 100
43 MACLEAN
NETWORK
SOLUTIONS SI-4754
DISTRIBUTING RING 13B INSIDE DIAM. 3.11"W X
3.74"H 300
44 MACLEAN
NETWORK
SOLUTIONS SI-4755
DISTRIBUTING RING 13C INSIDE DIAM. 5.12"W X
3.74"H 300
45 Ortronics 110ABC6050 110 BLOCK,CAT6 50PR 30
Startech RK419WALLV 4U 19in Steel Vertical Wall Mount Equipment Rack
Bracket 30
CLINs 31-32 shall meet the following minimum requirements:
o Weather Resistant Nylon Cable mount o 2U Routing panel with integrated D-Rings
CLINs 33-34 shall meet the following minimum requirements:
o 23 AWG bare copper wire insulated with FEP and FRPP;
o Must comply with Plenum rating and have CMP marked on outer jacket;
o Bulk cable to have distance marking on the cable jacket;
o Minimum bend radius of 1 inch;
o Maximum Installation tension of 25 pounds;
o Be available in Yellow and Red color outer cable jackets;
o Packaged with a reel in box configuration;
o Each box to contain 1000 feet of continuous cable;
o Compliant with IEEE 802.3, IEEEE 802.3af, IEEEE 802.3at, and IEEE 802.3bt standards.
CLINs 35-42 shall meet the following minimum requirements:
o 24-gauge stranded conductor with an 8-position modular plug on each end;
o 24-gauge, UTP stranded conductor cable;
o Plug body is high-impact, fire-retardant plastic rated;
o Color-matched cords and boots;
o Available in 3 foot, 7 foot, 15 foot, and 25 foot lengths;
o Compliant with IEEE 802.3bt PoE Type 1, Type 2, Type 3, Type 4 ;
o Compliant with Cisco UPoE, and UPoE+.
CLINs 43-44 shall meet the following minimum requirements:
o Distribution Ring material will be Die Cast Aluminum
CLIN 45 shall meet the following minimum requirements:
o Standard 50-pair 110 footprint o Color-coded C6110C4 connecting blocks o Backward compatible to Category 5 and 5e;
CLIN 46 shall meet the following minimum requirements:
o Wall mount Bracket must have Mounting holes on 16” on center
C. Network Cabinets and accessories:
The following items are required on a Brand Name basis – No substitutions allowed, and will be represented by CLINs 47 – 51:
Material List B: (CLINs 47-51) BRAND NAME SPECIFIC – NO SUBSTITUTIONS
CLIN Manufacturer Part Number Description Qty.
47 Master Lock 720DPF Hasp and Hasp Lock 115
48 Tripp-Lite SR42UBCL 42U SmartRack Co-Location Standard-Depth Rack Enclosure Cabinet
49 APC PE625 APC Essential SurgeArrest 6 Outlet 25 Foot Cord 120V 35
50 Tripp-Lite SRWF2U
SmartRack 2U Low-Profile Vertical-Mount Switch-Depth Wall- Mount Rack Enclosure Cabinet
51 Tripp-Lite SRWF4U
SmartRack 4U Low-Profile Vertical-Mount Switch-Depth Wall- Mount Rack Enclosure Cabinet
CLIN 47 shall meet the following minimum requirements:
o 6-1/4in (16cm) Single-hinge hasp o Accepts shackle diameter up to 7/16in (11mm) o Zinc plated hardened steel o Hinge body conceals hinge pins and mounting hardware.
CLIN 48 shall meet the following minimum requirements:
o 42U of overall height o Two compartment co-location rack with doors and side panels o Secure cable channel for each individual compartment o Individually locking Front and Rear Doors o Ships fully assembled.
CLIN 49 shall meet the following minimum requirements:
o 6 outlets o 25 foot cord
CLINs 50-51 shall meet the following minimum requirements:
o 2U and 4U low profile cabinet o Keyed locking mechanism o Includes space for internal patch panel o Reversible front door.
o Wall-mounting holes spaced 16 in. apart