MDVL192129 Plans.pdf

PDF 2 MB Posted

Attached to
MDVL192129 - Repair Fire Suppression System at Bldg. 104 at the 186th ARW
Solicitation number
W50S7J21R0003
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MS Air National Guard

186 Air Refueling Wing

6225 M Street

Meridian, MS 39307

AIR

NAT I

NALO

GUA

RD

R protecting Mississippi's vital flow...one call at a time

CALL BEFORE YOU DIG!

601.555.1212

Ù

PROJECT

LOCATION

WAGGONER

Inspire. Engage. Deliver.

Jackson, MSHernando, MSGulfport, MS

Ruston, LA New Orleans, LA www.waggonereng.com

1-800-661-3733

AutoCAD SHX Text

MAY 2021

AutoCAD SHX Text KEY FIELD AIR NATIONAL GUARD BASE REPAIR FIRE SUPPRESSION SYSTEM, B104 186TH AIR REFUELING WING PROJECT# MDVL192129

AutoCAD SHX Text

INDEX TO DRAWINGS

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

COVER SHEET

AutoCAD SHX Text

FA - 001

AutoCAD SHX Text

FIRST FLOOR PLAN - FIRE ALARM (EXISTING)

AutoCAD SHX Text

FA - 002

AutoCAD SHX Text

FIRST FLOOR PLAN - FIRE ALARM (NEW)

AutoCAD SHX Text

FA - 003

AutoCAD SHX Text

SECOND FLOOR PLAN - FIRE ALARM (EXISTING) AND FIRE ALARM (NEW)

AutoCAD SHX Text

FP - 001

AutoCAD SHX Text

FIRE PROTECTION - FIRST FLOOR PLAN

AutoCAD SHX Text

FP - 002

AutoCAD SHX Text

FIRE PROTECTION - SECOND FLOOR PLAN

AutoCAD SHX Text

FA - 004

AutoCAD SHX Text

ELECTRICAL SCHEDULES AND DETAILS

KEYED NOTES

Ops Floor

A6 Staff

ACOMF Maint. A4

DIRECTOR

Mechanical

103D A3/5/9

103F Elect. / Comm.

103E A3/5/9

103B Battle Cab

103G A3 Director

103J Stairwell

103N A1

103M A1

103L A1

103K

ACOS CC

103H JACCE Director

102D Break Room

111A A6 Director

102A A4

102D Break Room

102C Commander Conference

Room112 A6

CL

FIRE PROTECTION LEGEND

GENERAL FIRE PROTECTION NOTES

FIRE RISER DETAIL

GENERAL CONSTRUCTION NOTES

WAGGONER

Jackson, MS Hernando, MS Gulfport, MS Ruston, LA New Orleans, LA www.waggonereng.com 1-800-661-3733

Inspire. Engage. Deliver.

Scott C. Woods and Associates

Mechanical Engineers

SCWA

FIRE PROTECTION -

FP - OO1

FIRST FLOOR PLAN

FIRST FLOOR PLAN / FIRE PROTECTION

AutoCAD SHX Text

PHASE 1

AutoCAD SHX Text

PHASE 2

AutoCAD SHX Text

PHASE 3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text AUDITORIUM TABLES ARE NOT MOVEABLE. EXTENDED COVERAGE HEADS SHALL BE USED TO ALLOW FOR INSTALLATION WITHOUT REMOVAL OF TABLES.

AutoCAD SHX Text

AutoCAD SHX Text

UP

AutoCAD SHX Text

UP

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

EXISTING RISER. SEE DETAIL.

AutoCAD SHX Text

ROOM 103 IS LIGHT HAZARD OPEN TO ABOVE

AutoCAD SHX Text CONTRACTOR TO PROVIDE PROTECTION TO RAISED FLOOR FROM SCAFFOLDING, LADDERS, ETC. IF LIFTS ARE USED, DO NOT EXCEED WEIGHT RATING OF FLOOR.

AutoCAD SHX Text

AutoCAD SHX Text 3.

AutoCAD SHX Text 2.

AutoCAD SHX Text 1.

AutoCAD SHX Text

ALL SYSTEMS AND EQUIPMENT SHALL STRICTLY COMPLY WITH NFPA 13 AND ALL

AutoCAD SHX Text

LOCAL CODES.

AutoCAD SHX Text

CALCULATIONS AND SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER AND

AutoCAD SHX Text

ARCHITECT FOR APPROVAL BEFORE INSTALLING FIRE PROTECTION SYSTEM.

AutoCAD SHX Text

ALL FIRE PROTECTION WORK SHALL BE COORDINATED WITH OTHER TRADES TO

AutoCAD SHX Text

AVOID CONFLICTS.

AutoCAD SHX Text 4.

AutoCAD SHX Text

SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF CEILING TILES WHERE

AutoCAD SHX Text

POSSIBLE.

AutoCAD SHX Text

ORDINARY HAZARD GROUP II

AutoCAD SHX Text

LIGHT HAZARD

AutoCAD SHX Text 5.

AutoCAD SHX Text

SPRINKLER HEADS SHALL BE SEMI-RECESSED TYPE IN SPACES WITH CEILINGS.

AutoCAD SHX Text

SPACES WITHOUT CEILINGS SHALL HAVE UPRIGHT HEADS WITH HEAD GUARDS.

AutoCAD SHX Text 6.

AutoCAD SHX Text

CONTRACTOR SHALL VISIT SITE PRIOR TO BID DATE AND FIELD VERIFY EXACT

AutoCAD SHX Text

LOCATION OF THE EXISTING FIRE MAIN.

AutoCAD SHX Text 7.

AutoCAD SHX Text

CONTRACTOR SHALL PROVIDE OFFSETS OR MOVE ANY EXISTING SPRINKLER

AutoCAD SHX Text

PIPE (AT NO ADDITIONAL COST TO THE OWNER) WHICH CONFLICTS WITH

AutoCAD SHX Text

THE INSTALLATION OF THE NEW WORK THAT IS REQUIRED.

AutoCAD SHX Text 8.

AutoCAD SHX Text

FLOOR

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CONNECT TO EXISTING 4" VALVE

AutoCAD SHX Text

8" FLANGE

AutoCAD SHX Text 4"

AutoCAD SHX Text

ADD AUXILIARY SYSTEM DRAINS AS REQUIRED FOR POSITIVE DRAINAGE.

AutoCAD SHX Text 1.

AutoCAD SHX Text THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION AND EXTREME CAUTION MUST BE TAKEN TO PROTECT EXISTING EQUIPMENT.

AutoCAD SHX Text 2.

AutoCAD SHX Text ANY REQUIRED NEW WALL OPENINGS AND/OR PATCH WORK SHALL BE REPAIRED WITH LIKE MATERIALS AND REPAINTED TO MATCH EXISTING SURFACES.

AutoCAD SHX Text 3.

AutoCAD SHX Text CEILING TILES SHALL BE REMOVED AND REPLACED AS REQUIRED. THE CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES OR GRID.

AutoCAD SHX Text 4.

AutoCAD SHX Text DUE TO SECURITY OF THE FACILITY, EACH PHASE OF CONSTRUCTION, ENTRY POINTS OF BUILDING, ETC., SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE ANY WORK BEGINS.

AutoCAD SHX Text 5.

AutoCAD SHX Text CONTRACTOR SHALL GIVE 30 DAYS NOTICE IN ADVANCE BEFORE STARTING ANY WORK IN EACH PHASE.

AutoCAD SHX Text 6.

AutoCAD SHX Text

PLEASE NOTE THAT THE LARGEST CURRENT ENTRY TO THE FACILITY IS A 36" DOOR.

AutoCAD SHX Text 6.

AutoCAD SHX Text CONTRACTOR SHALL MAINTAIN A CLEAN WORKING ENVIRONMENT AT ALL TIMES. DAILY CLEAN UP SHALL OCCUR AT THE END OF EACH WORK SHIFT.

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

CO13-063.026

AutoCAD SHX Text

FEB 2021

AutoCAD SHX Text

PROJECT:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DRAWING TITLE:

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DRAWING REVISIONS

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REPAIR FIRE SUPPRESSION SYSYTEM, B104

AutoCAD SHX Text

NTS

AutoCAD SHX Text

GLH

AutoCAD SHX Text

SCW

AutoCAD SHX Text

GLH

AutoCAD SHX Text Ph. (601)859-9864/Fax (601)859-2564/Email www.scweng.com

AutoCAD SHX Text 112 Lone Wolf Dr./Madison, Ms 39110

AutoCAD SHX Text

SCWA# 19-104

AutoCAD SHX Text

PROJECT# MDVL 192129

AutoCAD SHX Text

MS AIR NATIONAL GUARD 186TH AIR REFUELING WING

AutoCAD SHX Text

SCALE: 1/8"=1'-0"

NORTH

Stairwell

VTC Conference

Room 1

Director of Operations

(ACOS/A3)

Ops Floor Mezzanine

VTC Conference

Room 2

WAGGONER

Jackson, MS Hernando, MS Gulfport, MS Ruston, LA New Orleans, LA www.waggonereng.com 1-800-661-3733

Inspire. Engage. Deliver.

Scott C. Woods and Associates

Mechanical Engineers

SCWA

FIRE PROTECTION -

FP - OO2

SECOND FLOOR PLAN

SECOND FLOOR PLAN / FIRE PROTECTION

AutoCAD SHX Text

PHASE 1

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

CO13-063.026

AutoCAD SHX Text

FEB 2021

AutoCAD SHX Text

PROJECT:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DRAWING TITLE:

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NO.

AutoCAD SHX Text

DRAWING REVISIONS

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REPAIR FIRE SUPPRESSION SYSYTEM, B104

AutoCAD SHX Text

NTS

AutoCAD SHX Text

GLH

AutoCAD SHX Text

SCW

AutoCAD SHX Text

GLH

AutoCAD SHX Text Ph. (601)859-9864/Fax (601)859-2564/Email www.scweng.com

AutoCAD SHX Text 112 Lone Wolf Dr./Madison, Ms 39110

AutoCAD SHX Text

SCWA# 19-104

AutoCAD SHX Text

PROJECT# MDVL 192129

AutoCAD SHX Text

MS AIR NATIONAL GUARD 186TH AIR REFUELING WING

AutoCAD SHX Text

SCALE: 1/8"=1'-0"

NORTH

Sheets and Views
Cover
21-0401 Fire Protection.pdf
Sheets and Views
Pbase 19104-FP-001
Pbase 19104-FP-002
21-0518 Electrical.pdf
FA-001
FA-002
FA-003
FA-004

File details come from the government source that posted it. Updated .