This is a construction design document (CD drawings) prepared by the State of Michigan Department of Technology, Management and Budget for the MDOT Bay Region Office HVAC System Repairs project located at 5859 Sherman Road, Saginaw, Michigan 48604. The project involves the repair and replacement of the HVAC system, including the removal of existing furnaces, ductwork, dampers, inline fans, and duct heaters, along with the installation of new wall-mounted heat pumps, fan coil evaporators, direct expansion (DX) piping, condensate drainage systems, and associated ductwork and controls. The drawings are issued as the Construction Document (CD) set, dated November 6, 2026, with file number 591/26369.CTS and Matrix project number 260761.00. The scope encompasses both upper and lower level floor plans with detailed mechanical symbols, notes, abbreviations, demolition details, and new work specifications. Electrical work includes connections to new mechanical equipment, provision of conduit, wire, and breakers as noted on the electrical demolition and new work plans.
The design documents establish comprehensive technical requirements for HVAC contractors, including compliance with the Michigan Mechanical Code, manufacturer installation instructions, and standards set by ASHRAE, NFPA, OSHA, and other regulatory bodies. All work must be performed by licensed contractors and subcontractors as required by state law, with coordination among all trades to avoid conflicts. Specific provisions address ductwork specifications (galvanized sheet metal minimum 26 gauge with acoustic lining within 10 feet of fans), flexible duct limitations (maximum 6 feet length with one 90-degree turn), condensate drain requirements (minimum 1 percent slope terminating via air gap), vibration isolation, thermostat mounting at 48 inches above finish floor, and field verification of existing conditions. The contractor must maintain equipment integrity during construction, perform test and air balance (TAB) procedures on existing diffusers following demolition, and restore all damaged surfaces to match existing conditions. All exterior wall penetrations require waterproofing and sealing, and exposed refrigerant piping must be jacketed with 0.020-inch thick aluminum stucco-embossed material.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL DRAWING INDEX
5859 SHERMAN RD, SAGINAW, MI 48604
FILE NUMBER: 591/26369.CTS
MATRIX PROJECT NUMBER: 260761.00MECHANICAL/ELECTRICAL ENGINEER
STATE OF MICHIGAN
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
FOR DEPARTMENT OF TRANSPORTATION
MDOT BAY REGION OFFICE - HVAC SYSTEM REPAIRS
N SITE MAP
MECHANICAL DRAWING INDEX
MDOT BAY REGION OFFICE
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-000
TAT
CAT
TITLE SHEET
GENERAL HVAC NOTES
1. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. ALL EXISTING SYSTEMS (INCLUDING FURNACES; FANS) THAT
SERVES AREAS BEING RENOVATED SHALL BE REBALANCED AS
REQUIRED.
4. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
5. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY
CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS
NEEDED.
6. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
7. PROVIDE BALANCE DAMPERS FOR EACH DIFFUSER/GRILLE
AND BRANCH DUCT.
8. MAXIMUM LENGTH OF FLEXIBLE DUCT TO AIR TERMINAL
DEVICES SHALL NOT EXCEED 6'-0" IN LENGTH WITH A MAXIMUM
OF ONE 90° TURN AND SHALL BE INSULATED. ELBOWS SHALL
BE MIN. 1.5 RADIUS. CONNECTIONS TO TERMINAL DEVICES
SHALL BE BANDED AND TAPED.
9. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
10. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.
11. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
13. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
14. CONTRACTOR SHALL USE LOW PRESSURE LOSS DUCT
FITTINGS IN ACCORDANCE WITH SMACNA. (WYES, RADIUSED
OR VANED TEES, ETC.) DUCTWORK SHALL BE GALVANIZED
SHEET METAL, MIN. 26 GA.
15. ALL DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSION.
INCREASE DUCT SIZE FOR LINING.
16. ALL EXTERNALLY ISOLATED HVAC EQUIPMENT SHALL HAVE
FLEXIBLE DUCT CONNECTORS.
17. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.
18. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA
AIR GAP.
19. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
20. ANY INFORMATION FOUND ON THE DRAWINGS AND NOT IN THE
SPECIFICATIONS, OR FOUND IN SPECIFICATIONS AND NOT IN
THE DRAWINGS, SHALL BE CONSTRUED AS TO BE INCLUDED IN
BOTH THE SPECIFICATIONS AND THE DRAWINGS. ANY
CONFLICT BETWEEN THE PLANS AND THE SPECIFICATIONS
WILL BE INTERPRETED BY THE ARCHITECT. IN THE EVENT OF
CONFLICT, FOR THE PURPOSE OF BIDDING, THE CONTRACTOR
SHALL PRESUME THE MOST EXPENSIVE COMBINATION OF
QUALITY AND QUANTITY OF WORK SHALL PREVAIL.
21. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF
FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
22. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY
OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,
ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION
BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE
FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING
AND SPECIFICATIONS.
23. DUCTWORK SHALL BE ACOUSTICALLY LINED WITHIN 10 FT OF
THE INTAKE AND/OR DISCHARGE OF A FAN.
24. DUCT/PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH
BUILDING STRUCTURE, EQUIPMENT FURNISHED,
ARCHITECTURAL DRAWINGS, AND ALL OTHER TRADES PRIOR
TO INSTALLATION. ANY CONTRACTOR INSTALLING WORK
WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS WORK
AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF ANY
AND ALL TRADES WORK.
25. UNLESS OTHERWISE NOTED, ALL DUCT/PIPING SHALL BE
CONCEALED WHEREVER POSSIBLE. PROVIDE CHROME
ESCUTCHEON OR ALUMINUM DUCT COLLAR AT EACH
PENETRATION OF A FINISHED SURFACE.
26. DUCT/PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN
THE SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL
CODE.
27. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES OR THE SPECIFICATIONS. POWER SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
28. PROVIDE TRAP FOR CONDENSATION DRAIN LINES.
29. PROVIDE VIBRATION ISOLATION AT EACH CONNECTION TO A
MOTORIZED PIECE OF EQUIPMENT BY THE HVAC
CONTRACTOR.
30. MOUNT THERMOSTAT/SENSORS AT 48" AFF UNLESS NOTED
OTHERWISE.
31. FIRE PROTECTION CONTRACTOR SHALL BE CERTIFIED BY THE
STATE OF MICHIGAN, TO PERFORM THIS WORK.
32. ALL PIPE, FITTINGS, AND HANGERS SHALL BE AS PERMITTED
BY NFPA 13, CURRENT EDITION AND ATTACHED TO
STRUCTURAL MEMBERS.
33. ALL EQUIPMENT AND MATERIAL BEING UTILIZED SHALL BE
UNDERWRITERS LABORATORIES LISTED-(UL) APPROVED AND
LISTED IN THE CURRENT EDITION OF APPROVAL GUIDES.
34. AUTOMATIC SPRINKLERS SHALL BE DESIGNED PER THE
APPROPRIATE SEISMIC PER NFPA 13, CURRENT EDITION.
35. PROVIDE AND INSTALL ADDITIONAL AUTOMATIC SPRINKLERS
UNDER ALL OBSTRUCTIONS IN EXPOSED AREAS PER NFPA 13.
THIS SHOULD INCLUDE ADDITIONAL SPRINKLERS BELOW
DUCTS AND MEZZANINES WHICH ARE 48 INCHES WIDE OR
WIDER. ALL SPRINKLERS UNDER OBSTRUCTIONS SHALL BE
EQUIPPED WITH CAGE GUARDS.
36. FIRE SUPPRESSION PLANS ARE BASED ON A PERFORMANCE
SPECIFICATION AND IDENTIFY AREAS FOR FIRE SUPPRESSION.
DETAILED PLANS FOR THE FIRE SUPPRESSION LAYOUT AND
FLOW CALCULATIONS TO BE SUBMITTED SEPARATELY BY THE
CONTRACTOR TO PLAN REVIEW FOR APPROVAL WITH THEIR
HYDRAULIC CALCULATIONS.
37. FIRE SUPPRESSION DESIGN & PIPING SHALL BE COMPLETED
BY CERTIFIED FIRE SUPPRESSION CONTRACTOR.
38. FIRE PROTECTION SYSTEM SHALL BE DESIGNED IN COMPLIANCE
WITH THE LATEST EDITION OF NFPA 13 AND LOCAL FIRE CODE
REQUIREMENTS.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
F/S F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.
6. PATCH AND REPAIR ALL FLOOR AND WALL SURFACES LEFT DAMAGED OR
INCOMPLETE FROM REMOVAL OF EXISTING PARTITIONS, MILLWORK,
CASEWORK, OR OTHER FIXED ACCESSORIES AND EQUIPMENT WITH
MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE ARCHITECT.
7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL
ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE
DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE
REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR
RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE
NEW WORK AS SHOWN.
8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE
REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO
FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF
THIS WORK.
9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO
COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND
APPROVAL OF THE LOCAL CODE JURISDICTIONS.
10. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN
APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
11. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED
IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE
CONTRACTOR.
12. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE
DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.
GENERAL DEMOLITION NOTES
HANGER STRAPS HANGER RODS
STRAP HANGER TRAPEZE HANGER
NO POP RIVETS ALLOWED, USE
SELF-TAPPING SHEETMETAL SCREWS
ONLY (TYP)
3 DUCT HANGER DETAIL
SCALE: NTS
2 SUPPLY AIR DIFFUSER DETAIL
SCALE: NTS
CONICAL TAKE-OFF
WITH VOLUME DAMPER
(TYP)
SUPPLY AIR BRANCH
DUCT
FLEXIBLE DUCT
LAY-IN CLG TILE (TYP)
CEILING SUPPORT TEE
(TYP)
X-SUPPLY DIFFUSER
COLLAR
HARD ELBOW (AS
REQ'D)
NOTE:
90° ELBOW SHOWN
SIMILAR RADIUS
CONSTRUCTION FOR
ALL ANGLES
R
R
OFFSET
ELBOW
FULL RADIUS
(R=W)
FLOW
AIR
TRANSITION - CONTRACTION FLOW
TRANSITION - DIVERGING FLOW
FLOW
AIR
W
W
R=1/ W
W
RECTANGULAR TRANSITIONS, OFFSETS, AND
ELBOWS
SCALE: NTS
5 DUCT TRANSITION DETAIL
SCALE: NTS
VD
NOTES:
1. "ALTERNATE" FITTINGS SHALL BE
ACCEPTABLE ONLY WHEN DUCT HEIGHT
DOES NOT PERMIT THE USE OF
"PERMITTED" FULL SIZE BELLMOUTH
CONNECTION
2. THIS DETAIL APPLIES TO SINGLE TAKEOFFS
TO DIFFUSER AS WELL AS BRANCH
TAKEOFFS. IT ALSO APPLIES TO TAKEOFFS
IN THE HORIZONTAL AS WELL AS THE
VERTICAL DIRECTION.
DUCT SIZE:
(SEE PLANS)
PREFERRED
TAKE-OFF DETAIL
ALTERNATE 1
TAKE-OFF DETAIL
ALTERNATE 2
TAKE-OFF DETAIL
(WHEN OTHERS DO NOT FIT)
STANDARD
45° RECTANGULAR
DUCT CONNECTION
(SUPPLY SHOWN,
RETURN/EXHAUST SIMILAR)
RECTANGULAR TO ROUND
BOOT CONNECTIONMINI-BELLMOUTH CONNECTIONBELLMOUTH
CONNECTION
MANUAL VOLUME
DAMPER TYPICAL AT
ALL DUCT
TAKE-OFFS
VDVD
MAIN DUCT
AIR FLOW
6" min.
RADIUS ELBOW
FRAME
VANED ELBOW
LOCKING LUG
2-1/4"R
4-1/2"R
TURNING VANE
NOTES:
1. LOCKING LUGS INTEGRAL WITH VANE
2. MAXIMUM UNSUPPORTED VANE LENGTH 48"
3. FRAMES - BOLTED OR RIVETED TO ELBOW
4. VANES AND FRAMES - SAME GAUGE AS ELBOW
2 1/4"
3 1/2"
TURNING VANES FOR SQUARE ELBOW
DETAIL
SCALE: NTS
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-100
TAT
CAT
MECHANICAL SYMBOLS,
NOTES, ABBREVIATIONS,
DETAILS, & SCHEDULES
X-SD 200
24x24 ---
X-SD 200
24x24 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 125
24x6 TYP.6
X-SD 125
24x6 ---
X-SD 125
24x6 ---
X-SD 350
24x24 ---
X-SD 350
24x24 ---
X-SD 130
24x6 TYP.2
X-SD 100
24x6 ---
X-SD 75
24x6 ---
X-8" SA
X-8" SA X-SD 130
24x6 ---
X-SD 115
24x6 TYP.4
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-SD 135
24x6 ---X-20x8 SA
X-16x8 SA
X-10x8 SA
X-14x14 SA X-16x14 SA
X-8x8 SA
X-8x6 SA
X-SD 100
24x6 TYP.3
X-6"Ø SA
X-16x14 SA
X-26x8 SA
X-10x8 SA
X-6" SA
X-8x8 SA
X-6x8 SA
X-8x8 SA
X-14x8 SA
X-20x8 SA
X-10" SA
X-10" SA
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 100
24x6 TYP.2
X-SD 90
24x6 ---
X-8x8 SA
X-10x8 SA
X-12x8 SA
X-14x7 SA
X-16x8 SA
X-20x8
SA
X-20x8 SA
X-6x8 SA X-10x8 SA X-8x8 SA X-6"Ø SA
X-25x7 SA X-25x7 SA
X-8x8 SA
X-12x8 SA
X-12x8 SA
X-16x8 SA
X-18x8 SA
X-6"Ø SA
X-SD 135
24x6 ---
X-RG ---
20x20 ---
X-25x7 RA
X-EG 75
24x6 ---
X-6"Ø EA
X-6"Ø EA
X-16x14 SA
X-14x12 RA
X-14x12 RA
X-25x16 SA
X-RG ---
14x12 ---
X-RG ---
28x14 ---
X-28x14 RA
X-RG ---
30x14 ---
X-14x16 SA
X-16x8 SA
X-18x8 SA
X-F-8
X-F-1 X-F-7
X-F-2
X-EG ---
12x12 ---
X-EG ---
12x12 ---
X-EG ---
12x12 ---
X-RG ---
28x14 ---
X-32x10 SA UP
X-RG ---
20x7 ---
X-20x7 RA
X-F-4 X-F-6 X-F-3
X-RG ---
28x14 ---
X-44x10 SA UP
X-24x18 OA UP X-20x18 EA UP
X-24x18 OA UP X-35x10 SA UP X-24x18 OA UP
X-28x16 RA
X-16x16 SA
X-16x16 SA
X-30x12 RA UPX-32x14 RA UP
X-13x10 SA UP
X-20x10 SA UP X-25x7 RA UP
X-25x7 SA UP
T
T
S
X-F-8
X-F-8
S
X-F-8
X-16x7 RA X-F-2
T S
T
X-F-7
S X-F-7
T
X-DUCT HEATER /
INLINE FAN
X-SD 90
24x6 ---
X-SD 90
24x6 ---
S X-F-5
X-SD 125
24x6 ---
S X-F-7
X-DUCT HEATER
S
X-F-2
S
X-F-7
X-DUCT HEATER
S X-F-7
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-16x8 SA
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-16x16 SA
X-14x8 RA
X-14x8 RA
X-24x7 RA
X-15x7 RA
M
X-6"Ø SAX-6"Ø SAX-6"Ø SAX-6"Ø SA
X-6x8 SA
X-INLINE FAN
X-14x7 SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-20x8 SA
1 1
5 5
5 5
5 5
DEMOLITION NOTES
EXISTING FURNACE, SUPPLY AIR DUCTWORK, RETURN AIR DUCTWORK,
OUTDOOR AIR DUCTWORK, CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES TO REMAIN UNLESS OTHERWISE NOTED.
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY AIR DUCTWORK,
RETURN AIR DUCTWORK, HANGERS, SUPPORTS, AND ALL ASSOCIATED
ACCESSORIES TO THE EXTENTS SHOWN. CONTRACTOR TO MODIFY EXISTING
DUCTWORK AS REQUIRED TO MAKE NEW CONNECTION AS SHOWN ON NEW
DRAWINGS. CONTRACTOR TO PATCH AND SEAL AIR TIGHT THE EXISTING
FURNACE SUPPLY AIR DUCTWORK AND RETURN AIR DUCTWORK AS
REQUIRED TO ENSURE EXISTING FURNACE ONLY SERVES THE UPPER LEVEL.
CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALL IN THE
LOCATIONS OF DEMOLISHED THERMOSTATS/SENSORS AS REQUIRED TO
MATCH EXISTING WALL.
DISCONNECT, REMOVE, AND DEMO EXISTING DUCT HEATER, SUPPLY AIR
DUCTWORK, HANGERS, SUPPORTS, CONTROLS, CONTROL WIRING,
THERMOSTAT, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
CONTRACTOR TO MODIFY EXISTING DUCTWORK AS REQUIRED TO COMPLETE
THEIR WORK. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALL IN
THE LOCATIONS OF DEMOLISHED THERMOSTATS/SENSORS AS REQUIRED TO
MATCH EXISTING WALL.
DISCONNECT, REMOVE, AND DEMO EXISTING MOTORIZED DAMPER,
CONTROLS, CONTROL WIRING, SENSOR, AND ALL ASSOCIATED ACCESSORIES
IN THEIR ENTIRETY. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING
WALL IN THE LOCATIONS OF DEMOLISHED THERMOSTATS/SENSORS AS
REQUIRED TO MATCH EXISTING WALL. CONTRACTOR TO MODIFY EXISTING
DUCTWORK AS REQUIRED TO COMPLETE THEIR WORK. CONTRACTOR TO
MODIFY EXISTING ZONE DAMPER CONTROL PANEL AS REQUIRED TO ENSURE
PROPER OPERATION OF X-F-2 WITH THE REMOVAL OF EXISTING MOTORIZED
DAMPER AND ALL ASSOCIATED CONTROLS.
DISCONNECT, REMOVE, AND DEMO EXISTING INLINE FAN, SUPPLY AIR
DUCTWORK, HANGERS, SUPPORTS, CONTROLS, CONTROL WIRING,
THERMOSTAT, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY.
CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALL IN THE
LOCATIONS OF DEMOLISHED THERMOSTATS/SENSORS AS REQUIRED TO
MATCH EXISTING WALL.
DISCONNECT, REMOVE, AND DEMO EXISTING SUPPLY AIR DUCTWORK,
RETURN AIR DUCTWORK, HANGERS, SUPPORTS, RETURN GRILLES, FIRE
DAMPERS, AND ALL ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN.
CONTRACTOR TO MODIFY EXISTING DUCTWORK AS REQUIRED TO MAKE NEW
CONNECTION AS SHOWN ON NEW DRAWINGS. CONTRACTOR TO PATCH
PRIME, AND PAINT EXISTING WALLS IN THE LOCATION OF DEMOLISHED
RETURN GRILLES.
DISCONNECT, REMOVE, AND SALVAGE EXISTING X-F-2 THERMOSTAT/SENSOR,
CONTROLS, AND ALL ASSOCIATED ACCESSORIES IN THEIR ENTIRETY TO BE
RE-INSTALLED IN THE LOCATION SHOWN ON THE NEW UPPER LEVEL
DRAWING. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALL IN THE
LOCATIONS OF DEMOLISHED THERMOSTATS/SENSORS AS REQUIRED TO
MATCH EXISTING WALL.
GENERAL DEMOLITION NOTES
1. CONTRACTOR TO REMOVE AND REINSTALL EXISTING CEILING GRID/CEILING
TILES AS REQUIRED TO COMPLETE THEIR WORK. CONTRACTOR IS
RESPONSIBLE FOR REPLACEMENT OF DAMAGED/BROKEN CEILING TILES.
2. CONTRACTOR TO MODIFY EXISTING WALLS/CEILINGS AS REQUIRED TO
COMPLETE THEIR WORK. CONTRACTOR TO PATCH, PRIMES, AND PAINT
WALLS AND CEILINGS AS REQUIRED TO MATCH EXISTING AND MAINTAIN
EXISTING RATINGS ONCE DEMOLITION/NEW WORK IS COMPLETE.
3. ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, DIFFUSERS, GRILLES,
CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED ACCESSORIES TO
REMAIN UNLESS OTHERWISE NOTED.
4. CONTRACTOR TO MODIFY EXISTING FIRE SUPPRESSION PIPING AS
REQUIRED TO COMPLETE DEMOLITION/NEW WORK. CONTRACTOR TO
ENSURE ANY MODIFICATION TO FIRE SUPPRESSION SYSTEM MEET NFPA 13
REQUIREMENTS.
5. CONTRACTOR TO PATCH EXISTING FIRE WALLS IN THE LOCATION OF
DEMOLISHED DUCTWORK AS REQUIRED TO MATCH EXISTING AND MAINTAIN
EXISTING WALL RATING.
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-300
TAT
CAT
LOWER LEVEL FLOOR PLAN -
MECHANICAL DEMOLITION
N LOWER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
X-SD 120
24x6 TYP.6
X-SD 120
24x6 TYP.6
X-8x8 SA X-14x8 SA X-22x8 SA
X-26x8 SA
X-30x8 SA
X-30x8 SA
X-44x8 SAX-14x8 SA
X-14x8 SA X-10x8 SA
X-8x8 SA
X-6x8 SA
X-6x8 SA
X-6" SA
X-8x6 SA
X-8x6 SA
X-14x8 SA
X-12x8 SA
X-16x8 SA
X-10x16 SA
X-14x8 SA
X-8x8 SA
X-24x12 SA
X-10x16 SA
X-20x8 SA
X-14x8 SA
X-8x8 SA
X-10x8 SA
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-10x8 SA
X-18x8 SA
X-20x8 SA
X-10x8 SA
X-44x8 SA
X-12x9 SA DN X-32x10 SA DN
X-20x10 SA DN
X-13x10 SA DN X-6x8 EA TO SOFIT
X-10x8 SA
X-10x8 SA
X-14x8 SA
X-35x8 SA
X-16x8 SAX-8x8 SA X-8x8 SA
X-14x8 SA
X-14x8 SA
X-20x8 SA
X-14x8 SA
X-8x8 SA
X-20x8 SA
X-35x8 SA
X-35x8 SA
X-20x8 SA
X-20x8 SA
X-6x8 SA
X-14x8 SA
X-12x8 SA
X-10x8 SA
X-8x8 SA
X-18x8 SA
X-16x8 SA
X-14x8 SA
X-10x8 SA
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-SD 100
24x6 TYP.7
X-SD 120
24x6 TYP. 6
X-8x8 SA
X-SD 120
24x6 ---
X-SD 120
24x6 ---
X-SD 110
24x6 ---
X-SD 95
24x6 ---
X-SD 95
24x6 ---
X-SD 125
24x6 ---
X-SD 125
24x6 ---
X-SD 125
24x6 ---
X-SD 115
24x6 ---
X-SD 115
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 100
24x6 ---
X-SD 100
24x6 TYP. 4
X-SD 135
24x6 ---
X-SD 100
24x6 TYP. 4
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 125
24x6 TYP.8
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 180
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 125
24x6 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-SD 100
24x6 ---
X-44x10 SA DN
X-24x18 OA UP X-20x18 EA UP TO X-EF-1
X-24x18 OA UP X-35x10 SA DN X-24x18 OA UP
X-30x12 RA DNX-32x14 RA DN
X-25x14 SA
X-32x14 SA
X-14x12 SA UP/DN
X-F-5
X-16x12 RA UP/DN X-TG --- 16x12 ---
T
T
T
X-12x6 EA
X-EG ---
12x12 --- X-EG ---
12x12 ---
T
T
T
TT
T
T
X-F-1
S
X-F-4
X-F-5
X-F-4
S
X-F-4
S X-F-4
S
X-F-4
X-RG ---
20x20 ---
X-SD 100
24x6 ---
X-SD 100
24x6 ---
X-SD 100
24x6 ---
X-F-3
S
X-AC-1
T
X-F-6
X-F-3S
X-F-6
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-24x7 RA X-20x7 RA X-34x7 RA
X-11x7 RA
X-14x12 RA
X-11x7 RA
X-14x7 RA
X-14x7 RA
X-34x7 RA
X-RG ---
20x20 ---
M M
M
M
M
X-4x7 RAX-7x7 RA
X-4x7 RA
X-7x7 RA
M
X-12x7 RAX-18x7 RA
S
GENERAL DEMOLITION NOTES
1. NO DEMOLITION WORK ON THIS SHEET. REFER TO NEW DRAWINGS FOR NEW
WORK.
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-301
TAT
CAT
UPPER LEVEL FLOOR PLAN -
MECHANICAL DEMOLITION
N UPPER LEVEL FLOOR PLAN - MECHANICAL DEMOLITION
X-SD 200
24x24 ---
X-SD 200
24x24 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-SD 125
24x6 TYP.6
X-SD 125
24x6 ---
X-SD 125
24x6 ---
X-SD 350
24x24 ---
X-SD 350
24x24 ---
X-SD 130
24x6 TYP.2
X-SD 100
24x6 ---
X-SD 75
24x6 ---
X-8" SA
X-8" SA
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-SD 135
24x6 ---X-20x8 SA
X-16x8 SA
X-10x8 SA
X-14x14 SA X-16x14 SA
X-8x8 SA
X-8x6 SA
X-SD 100
24x6 TYP.3
X-6"Ø SA
X-16x14 SA
X-26x8 SA
X-10x8 SA
X-6" SA
X-8x8 SA
X-6x8 SA
X-8x8 SA
X-14x8 SA
X-20x8 SA
X-10" SA
X-10" SA
X-SD 135
24x6 ---
X-SD 135
24x6 ---
X-8x8 SA
X-10x8 SA
X-12x8 SA
X-16x8 SA
X-20x8 SA
X-6x8 SA
X-25x7 SA X-25x7 SA
X-8x8 SA
X-12x8 SA
X-12x8 SA
X-16x8 SA
X-18x8 SA
X-6"Ø SA
X-SD 135
24x6 ---
X-RG ---
20x20 ---
X-25x7 RA
X-EG 75
24x6 ---
X-6"Ø EA
X-6"Ø EA
X-16x14 SA
X-25x16 SA
X-RG ---
28x14 ---
X-28x14 RA
X-RG ---
30x14 ---
X-14x16 SA
X-16x8 SA
X-18x8 SA
X-F-8
X-F-1 X-F-7
X-F-2
X-EG ---
12x12 ---
X-EG ---
12x12 ---
X-EG ---
12x12 ---
X-RG ---
28x14 ---
X-32x10 SA UP
X-F-4 X-F-6 X-F-3
X-RG ---
28x14 ---
X-44x10 SA UP
X-24x18 OA UP X-20x18 EA UP
X-24x18 OA UP X-35x10 SA UP X-24x18 OA UP
X-28x16 RA
X-16x16 SA
X-16x16 SA
X-30x12 RA UPX-32x14 RA UP
X-13x10 SA UP
X-20x10 SA UP X-25x7 RA UP
X-25x7 SA UP
T
S
X-F-8
X-F-8
S
X-F-8
X-16x7 RA
T
X-F-7
S X-F-7
S X-F-5
X-SD 125
24x6 ---
S X-F-7
S
X-F-7
S X-F-7
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-16x8 SA
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-16x16 SA
X-14x8 RA
X-14x8 RA
X-24x7 RA
X-15x7 RA
X-6"Ø SAX-6"Ø SAX-6"Ø SAX-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
X-6"Ø SA
HP-1
FC-1
HP-2
DX
DX
DX DX
CO3/4" CD
3/4" CD
3/4" CD
DX
FC-2
12x12 SA & 18x8 RA DN
TO FC-2
10x10 SA
T
T
14x12 SA & 20x8 RA DN
TO FC-1
SHEET METAL WALL
CAP WITH BIRDSCREEN
FC-1
BACKDRAFT
DAMPER
20x8 RA
6"Ø OA
6"Ø OA
20x8 SA
FC-2
3/4" CD
SHEET METAL WALL
CAP WITH BIRDSCREEN
18x8 OPEN TO
ABOVE CEILING
PLENUM
20x8 RA OPEN TO ABOVE CEILING PLENUM
3/4" CD
3/4" CD
BACKDRAFT
DAMPER
18x8 RA
6"Ø OA
8x8 SA
CO CO
X-SD 135
24x6 TYP.2
X-SD 160
24x6 TYP. 3
X-SD 155
24x6 TYP.4
X-SD 250
24x6 ---
12x10 SA10x8 SA
3CD PUMP
CD PUMP3
4 4
8x8 SA
4 4 4
7 7
MECHANICAL KEY NOTES
INSTALL NEW FAN COIL EVAPORATOR, WALL MOUNTED HEAT PUMP,
DUCTWORK, DX PIPING, CONDENSATE PIPING, VALVES, FITTINGS, HANGERS,
SUPPORTS, THERMOSTAT, CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS. INSTALL NEW WALL
MOUNTED HEAT PUMP ON PROVIDED WALL MOUNTING BRACKET TO HAVE
THE BOTTOM OF THE UNIT FLUSH WITH THE TOP OF EXISTING WINDOW(S).
CONTRACTOR TO PROVIDE/FABRICATE UNISTRUT STAND AS REQUIRED FOR
BOTTOM RETURN AIR DUCTWORK INSTALLATION OF NEW FAN COIL.
INSTALL NEW DX PIPING, HANGERS, SUPPORTS, FITTINGS, AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS. ROUTE NEW DX PIPING
THROUGH EXISTING BRICK WALL. PATCH EXTERIOR BRICK WALL
PENETRATIONS TO MATCH EXISTING AND SEAL WATER TIGHT. INSTALL
0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL
EXPOSED DX PIPING.
INSTALL NEW CONDENSATE PIPING, CONDENSATE PUMP, HANGERS,
SUPPORTS, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN THE
LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. ROUTE NEW CONDENSATE PIPING TO NEAREST FLOOR
DRAIN IN MECHANICAL ROOM. CONTRACTOR TO ENSURE CONDENSATE
PIPING AND ALL ASSOCIATED ACCESSORIES ARE NOT INSTALLED ABOVE
ELECTRICAL GEAR.
INSTALL NEW SUPPLY AIR DUCTWORK, RETURN AIR DUCTWORK, OUTDOOR
AIR DUCTWORK, DAMPERS, TAKEOFFS, HANGERS, SUPPORTS, WALL CAP,
AND ALL ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN. MODIFY
EXISTING DUCTWORK AS REQUIRED TO MAKE NEW CONNECTION.
CONTRACTOR TO ROUTE NEW DUCTWORK THROUGH NEW ABOVE CEILING
WALL PENETRATIONS. PATCH, PRIME, AND PAINT NEW AROUND ABOVE
CEILING WALL PENETRATIONS AS REQUIRED TO MATCH EXISTING.
CONTRACTOR TO MODIFY EXISTING EXTERIOR BRICK WALL AS REQUIRED
TO INSTALL NEW WALL CAP, OUTDOOR AIR DUCTWORK AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN.
BALANCE EXISTING SUPPLY DIFFUSER TO CFM SHOWN.
CAP EXISTING DUCTWORK IN LOCATION SHOWN. MODIFY EXISTING
DUCTWORK AS REQUIRED TO INSTALL NEW CAP.
CONTRACTOR TO INSTALL NEW FAN COIL EVAPORATOR, DUCTWORK, DX
PIPING, CONDENSATE PIPING, CONDENSATE PUMP, VALVES, FITTINGS,
HANGERS, SUPPORTS, CONTROLS, CONTROL WIRING, AND ALL ASSOCIATED
ACCESSORIES IN THE CLOSET LOCATION SHOWN AS TIGHT AS POSSIBLE TO
THE SOUTH WALL FOR THE OWNER TO INSTALL A FUTURE CONCEALING
DOOR.
CONTRACTOR TO RE-COMMISSION X-F-2 AND X-F-3 TO ENSURE PROPER
HEATING/COOLING/FAN OPERATION AFTER DUCTWORK/CONTROL
MODIFICATIONS ARE COMPLETED.
GENERAL MECHANICAL NOTES
1. CONTRACTOR TO REMOVE AND REINSTALL EXISTING CEILING GRID/CEILING
TILES AS REQUIRED TO COMPLETE THEIR WORK. CONTRACTOR IS
RESPONSIBLE FOR REPLACEMENT OF DAMAGED/BROKEN CEILING TILES.
2. CONTRACTOR TO MODIFY EXISTING WALLS/CEILINGS AS REQUIRED TO
COMPLETE THEIR WORK. CONTRACTOR TO PATCH, PRIMES, AND PAINT
WALLS. CEILINGS AS REQUIRED TO MATCH EXISTING ONCE DEMOLITION/NEW
WORK IS COMPLETE.
3. CONTRACTOR TO PATCH ALL EXTERIOR WALL PENETRATIONS TO MATCH
EXISTING AND SEAL WATER-TIGHT.
4. CONTRACTOR TO MODIFY EXISTING FIRE SUPPRESSION PIPING AS
REQUIRED TO COMPLETE DEMOLITION/NEW WORK. CONTRACTOR TO
ENSURE ANY MODIFICATION TO FIRE SUPPRESSION SYSTEM MEET NFPA 13
REQUIREMENTS.
5. CONTRACTOR TO PATCH FIRE RATED WALL OPENINGS AS REQUIRED TO
MATCH EXISTING AND MAINTAIN EXISTING WALL RATING.
6. INSTALL 0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL
EXPOSED REFRIGERANT PIPING.
7. ALL NEW CONTROL WIRING, RACEWAYS, AND ALL ASSOCIATED
ACCESSORIES TO BE CONCEALED IN WALLS OR ABOVE CEILING SPACE.
CONTRACTOR TO CUT, PATCH, PRIME, AND PAINT WALLS AS NEEDED TO
INSTALL CONCEALED WIRING TO MATCH EXISTING.
8. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. ENSURE ALL MANUFACTURER REQUIRED CLEARANCES ARE
MAINTAINED.
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-400
TAT
CAT
LOWER LEVEL FLOOR PLAN -
MECHANICAL NEW
N LOWER LEVEL FLOOR PLAN - MECHANICAL NEW
X-SD 120
24x6 TYP.6
X-SD 120
24x6 TYP.6
X-8x8 SA X-14x8 SA X-22x8 SA
X-26x8 SA
X-30x8 SA
X-30x8 SA
X-44x8 SAX-14x8 SA
X-14x8 SA X-10x8 SA
X-8x8 SA
X-6x8 SA
X-6x8 SA
X-6" SA
X-8x6 SA
X-8x6 SA
X-14x8 SA
X-12x8 SA
X-16x8 SA
X-10x16 SA
X-14x8 SA
X-8x8 SA
X-24x12 SA
X-10x16 SA
X-20x8 SA
X-14x8 SA
X-8x8 SA
X-10x8 SA
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-10x8 SA
X-18x8 SA
X-20x8 SA
X-10x8 SA
X-44x8 SA
X-12x9 SA DN X-32x10 SA DN
X-20x10 SA DN
X-13x10 SA DN X-6x8 EA TO SOFIT
X-10x8 SA
X-10x8 SA
X-14x8 SA
X-35x8 SA
X-16x8 SAX-8x8 SA X-8x8 SA
X-14x8 SA
X-14x8 SA
X-20x8 SA
X-14x8 SA
X-8x8 SA
X-20x8 SA
X-35x8 SA
X-35x8 SA
X-20x8 SA
X-20x8 SA
X-6x8 SA
X-14x8 SA
X-12x8 SA
X-10x8 SA
X-8x8 SA
X-18x8 SA
X-16x8 SA
X-14x8 SA
X-10x8 SA
X-8x8 SA
X-8x8 SA
X-8x8 SA
X-SD 100
24x6 TYP.7
X-8x8 SA
X-SD 100
24x6 TYP. 4
X-SD 135
24x6 ---
X-SD 100
24x6 TYP. 4
X-SD 125
24x6 TYP.8
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 180
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 110
24x6 ---
X-SD 125
24x6 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-SD 100
24x6 ---
X-44x10 SA DN
X-24x18 OA UP X-20x18 EA UP TO X-EF-1
X-24x18 OA UP X-35x10 SA DN X-24x18 OA UP
X-30x12 RA DNX-32x14 RA DN
X-25x14 SA
X-32x14 SA
X-14x12 SA UP/DN
X-F-5
X-16x12 RA UP/DN X-TG --- 16x12 ---
T
T
T
X-12x6 EA
X-EG ---
12x12 --- X-EG ---
12x12 ---
T
T
T
TT
T
T
X-F-1
S
X-F-4
X-F-5
X-F-4
S
X-F-4
S X-F-4
S
X-F-4
X-RG ---
20x20 ---
X-SD 100
24x6 ---
X-SD 100
24x6 ---
X-SD 100
24x6 ---
X-F-3
S
X-AC-1
T
X-F-6
X-F-3S
X-F-6
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-RG ---
20x20 ---
X-24x7 RA X-20x7 RA X-34x7 RA
X-11x7 RA
X-14x12 RA
X-11x7 RA
X-14x7 RA
X-14x7 RA
X-34x7 RA
X-RG ---
20x20 ---
M M
M
M
M
X-4x7 RAX-7x7 RA
X-4x7 RA
X-7x7 RA
M
X-12x7 RAX-18x7 RA
S
X-SD ---
24x6 TYP. 6
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
1 1 1 1
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-SD ---
24x6 ---
X-F-2
ST
X-F-22 2
MECHANICAL KEY NOTES
AFTER DEMOLITION OF EXISTING DUCTWORK OF X-F-2 AND X-F-3 AND THE
PATCHING OF THE EXISTING SUPPLY AIR DUCTWORK AND RETURN AIR
DUCTWORK OF X-F-2 AND X-F-3 AS SHOWN ON M-300. CONTRACTOR TO
OPEN ALL DAMPERS FULLY IN THE LOCATION SHOWN AND PERFORM A TEST
AND AIR BALANCE (TAB) OF THE EXISTING SUPPLY DIFFUSERS.
CONTRACTOR TO SEND TAB REPORT TO ENGINEER FOR REVIEW TO
ESTABLISH FINAL CFM VALUES FOR THE DIFFUSERS IN THE LOCATION
SHOWN. AFTER DESIRED CFM RATES ARE ENGINEERED, CONTRACTOR TO
BALANCE EXISTING DIFFUSERS TO ENGINEER PROVIDED CFM RATES.
CONTRACTOR TO INSTALL SALVAGED THERMOSTAT, SENSOR, AND ALL
ASSOCIATED ACCESSORIES IN THE LOCATION SHOWN PER THE
MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONTRACTOR TO
PROVIDE AND INSTALL ALL NEW CONTROLS, CONTROL WIRING AND ALL
ASSOCIATED ACCESSORIES REQUIRED TO ENSURE THE PROPER
OPERATION OF X-F-2.
GENERAL MECHANICAL NOTES
1. CONTRACTOR TO REMOVE AND REINSTALL EXISTING CEILING GRID/CEILING
TILES AS REQUIRED TO COMPLETE THEIR WORK. CONTRACTOR IS
RESPONSIBLE FOR REPLACEMENT OF DAMAGED/BROKEN CEILING TILES.
2 260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
M-401
TAT
CAT
UPPER LEVEL FLOOR PLAN -
MECHANICAL NEW
N UPPER LEVEL FLOOR PLAN - MECHANICAL NEW
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
FUSED DISCONNECT SWITCH
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
IC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
SWITCH STYLE OCCUPANCY SENSOROC
DIGITAL TIME SWITCH
POWER PACK
DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT
DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
OCCUPANCY SENSOR / PHOTOCELL
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
CEILING MOUNTED WIFI
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERRUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST./EX.
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERRUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
1. ALL WALL AND FLOOR PENETRATIONS ARE TO BE SEALED TO MAINTAIN ORIGINAL
RATING.
2. ALL CONDUITS TO BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
3. THE DIVISION 26 CONTRACTORS SHALL VISIT THE PROJECT AND DETERMINE THE
EXACT EXTENT OF THE DEMOLITION WORK REQUIRED BEFORE BIDDING THE PROJECT.
4. REMOVE ALL EXISTING OBSOLETE EXPOSED CONDUIT, WIRE AND UNUSED EQUIPMENT
WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
5. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED TO MATCH ADJACENT.
6. EXISTING WORK WHICH IS PRESENTLY CONCEALED AND WHICH WILL REMAIN
CONCEALED AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED
NOT BE REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH
SURFACE AND THEN PATCHED TO MATCH, OR AS NOTED.
7. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
8. IF ASBESTOS IS PRESENT, IT WILL BE REMOVED OR RENDERED HARMLESS UNDER
SEPARATE CONTRACT BY THE OWNER.
9. THE DIVISION 26 CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING
WALLS TO MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED
EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT VOLTAGES AND LOADS PRIOR TO
INSTALLING SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENT AND CASUAL FIELD
OBSERVATION. REPORT ANY DISCREPANCIES TO ENGINEER FOR CLARIFICATION.
GENERAL ELECTRICAL NOTES
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
E-100
AWB
JFS
ELECTRICAL SYMBOLS,
NOTES, AND ABBREVIATIONS
EXISTING EQUIPMENT TO REMAIN.
DISCONNECT EXISTING EQUIPMENT FOR REMOVAL BY OTHERS. REMOVE
ASSOCIATED CONDUIT AND WIRE BACK TO SOURCE.
DEMOLITION NOTES
X-F-8
X-F-1 X-F-7
X-F-2
X-F-4 X-F-6 X-F-3
X-DUCT HEATER
X-DUCT HEATER
X-INLINE FAN
1 1
1 1 1
EX. PNL
"LP-A"
EX. PNL
"LP-B"
EX. PNL
"LPC"
EX. PNL
"DATA RM"
EX. PNL
"LPC-2"1
1 1
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
E-300
LOWER LEVEL FLOOR PLAN -
ELECTRICAL DEMOLITION
N LOWER LEVEL FLOOR PLAN - ELECTRICAL DEMOLITION
ELECTRICAL KEY NOTES
CONTRACTOR TO PROVIDE CONNECTION TO NEW MECHANICAL EQUIPMENT.
PROVIDE NEW CONDUIT, WIRE, AND BREAKER.
X-F-8
X-F-1 X-F-7
X-F-2
X-F-4 X-F-6 X-F-3
HP-1
208V-1Ø, 29MCA
FC-1
208V-1Ø, 4A
HP-2
208V-1Ø, 29MCA
FC-2
208V-1Ø, 4A
CP-1
120V-1Ø
CP-2
120V-1Ø
NEMA 3R
30/30/2
NEMA 3R
30/30/2
30/30/2
30/30/2
EX. PNL
"LP-A"
EX. PNL
"LP-B"
EX. PNL
"LPC"
EX. PNL
"DATA RM"
EX. PNL
"LPC-2"
LPC-2-1,3
LPC-2-1,3
LPC-2-9
LPC-2-9
LPC-2-2,4
LPC-2-2,4 1
260761.00
591/26369.CTS
file no.
checked by drawn by consultant issue date contract order no.
consultant job no.
M a t r ix funding code sheet description
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
11/6/2026 CD SET
E-500
LOWER LEVEL FLOOR PLAN -
ELECTRICAL NEW
N LOWER LEVEL FLOOR PLAN - ELECTRICAL NEW
| MDOT Bay Region Office - HVAC System Repairs - Mech CDs |
| M000-26075500-M-000 |
| M100-26075500-M-100 |
| M300-26075500-30x42 |
| M301-26075500-30x42 |
| M400-26075500-30x42 |
| M401-26075500-30x42 |
| MDOT Bay Region Office - HVAC System Repairs - Elec CDs |
| E100-26075500-30x42 |
| E300-26075500-30x42 |
| E500-26075500-30x42 |