McBain Weight Room Construction Documents 11-20-23 BIDDING AND CONSTRUCT....pdf
PDF 3 MB Posted
- Attached to
- Weight Room Expansion
- Solicitation number
- RFP - MCBA - 240000000462
- Issued by
- Lake County, Marcellus Village, Michigan
About this file
This document contains construction documents for a proposed Weight Room Renovation for the McBain Rural Agricultural School in McBain, Michigan. The project involves expanding the existing Weightlifting Room by 540 square feet, accomplished by removing an existing Locker Room and Hallway space. The renovated Weightlifting Room will total 1,865 square feet. This project will be considered a Level 2 Alteration due to the reconfiguration of space. The construction documents detail the architectural, plumbing, mechanical, and electrical work required, as well as code requirements, fire separation, means of egress, and other building specifications.
The documents indicate that the project is being bid for construction, with the issued date of November 20, 2023. No specific details on pricing, funding sources, set asides, or incumbents are provided. The documents focus on the technical specifications and construction requirements for the proposed Weight Room Renovation project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| McBain Weight Room Project Manual 11-20-23 BIDDING AND CONSTRUCTION.PDF | ||
| ShortAD (3).DOC | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
ARCHITECTURE
CONSTRUCTION MANAGEMENT
DEVELOPMENT
1104 S. MITCHELL ST.
CADILLAC, MICHIGAN 49601
(231) 779-4002
(231) 779-4022 FAX
ARCHITECT OF RECORD:
DRAWN BY:
PROJECT NUMBER:
SHEET NUMBER:
DATE ISSUED:
S. Kleinsorge
K. Taylor
Nov. 20, 2023 Bidding & Construction
23125-A
M c B a i n
R u r a l
A g r i c u l t u r a l
S c h o o l
E a s t
M a p l e
S t r e e t
M c B a i n
M
I
P r o p o s e d
W e i g h t
R o o m
R e n o v a t i o n f o r
McBain Rural Agricultural School
107 E. Maple St., McBain, Michigan 49657
Proposed Weight Room Renovation for:
AutoCAD SHX Text
INDEX OF DRAWINGS
AutoCAD SHX Text
PAGE
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text T
AutoCAD SHX Text
LOCATION MAP, SHEET INDEX
AutoCAD SHX Text
LS1.0
AutoCAD SHX Text
COMPOSITE LIFE SAFETY PLAN, CODE STUDY
AutoCAD SHX Text A1.0
AutoCAD SHX Text
ARCHITECTURAL PARTIAL PLANS, SCHEDULES, INTERIOR ELEVATION
AutoCAD SHX Text P1.0
AutoCAD SHX Text A2.0
AutoCAD SHX Text A2.1
AutoCAD SHX Text A2.2
AutoCAD SHX Text A2.3
AutoCAD SHX Text A2.4
AutoCAD SHX Text
ARCHITECTURAL SPECIFICATIONS
AutoCAD SHX Text
ARCHITECTURAL SPECIFICATIONS
AutoCAD SHX Text
ARCHITECTURAL SPECIFICATIONS
AutoCAD SHX Text
ARCHITECTURAL SPECIFICATIONS
AutoCAD SHX Text
ARCHITECTURAL SPECIFICATIONS
AutoCAD SHX Text
PLUMBING PARTIAL PLANS, SCHEDULES, SPECIFICATIONS
AutoCAD SHX Text M1.0
AutoCAD SHX Text
MECHANICAL PARTIAL PLANS, SPECIFICATIONS
AutoCAD SHX Text E1.0
AutoCAD SHX Text
ELECTRICAL PARTIAL PLANS, SPECIFICATIONS, DETAILS
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
LOCATION MAP
AutoCAD SHX Text
NOT TO SCALE
Code Study
Jurisdiction: State of Michigan Bureau of Fire Services.
State of Michigan Bureau of Construction Codes.
Code Enforced: 2015 Michigan Building Code (MBC), 2009 ICC & ANSI C A117.1.
2012 NFPA 101 - Life Safety Code w/ 1-28-2016 Amendments.
2015 Michigan Plumbing Code (MPC).
2015 Michigan Mechanical Code (MMC).
2017 National Electric Code (NEC) w/ Michigan Amendments.
2015 Michigan Energy Code (MEC).
Project Description:
Expand existing Weightlifting Room by 540 s.f. (+/- 20'x27'). This will be accomplished by the removal of an existing Locker Room and Hallway space. The renovated expanded area of the new Weightlifting Room will be 1,865 s.f. from 1,325 s.f.
This work will be considered a Level 2 Alteration due to the reconfiguration of space.
Building Use Group:
Use Group: Educational Group E (MBC 305.1), unchanged.
Building Parameters:
Construction type: IIB (MBC 602.2), II-000 (NFPA 220).
Building Area:
Total Existing Building: +/- 177,426 s.f.
Area to be Renovated:+/- 1,856 s.f. H.S. Weightlifting Room alteration.
Building Occupancy Load:
Total Occupancy: 1,070 occupants, Actual Student Enrollment (2023-2024).
Weightlifting Room Occupancy:1,865/ 50 gross= 38 occupants.
Building Code Requirements:
Fire separations:Existing to Remain.
A manual fire alarm system required throughout renovation area. F.A. contractor shall be certified in the State of Michigan per Michigan Act 144 and submit shop drawings to LARA - BFS for approval (MBC 907.2.3 & NFPA 101 9.6 & 14.3.4). Tie into existing system.
Means of egress illumination required with a minimum of 90 minutes emergency power
(MBC 1008 & NFPA 101 7.8 & 14.2.8.).
Emergency lighting must have an initial illumination of at least an average of 1 footcandle and a minimum of 0.1 footcandle measured along the path of egress at floor level (MBC 1008.3.5, NFPA 101 7.8.1.3 & 14.2.8.).
Allowable exit access travel distance: 200' (MBC, Table 1017.2, NFPA 101 14.2.6.2.)
Actual exit access travel distance: < +/-74' max.
Provide and install fire extinguishers as required by NFPA 10 and as directed by Fire Marshal.
All Areas: Maximum travel distance to any extinguisher shall be 75' (NFPA 10, Table 6.2.1.1). Area meets Light Hazard Occupancy (NFPA 10, 5.4.1.1, Table 6.2.1.1). Extinguisher shall be 2-A minimum.
(1) Total provided.
ARCHITECTURE
CONSTRUCTION MANAGEMENT
DEVELOPMENT
1104 S. MITCHELL ST.
CADILLAC, MICHIGAN 49601
(231) 779-4002
(231) 779-4022 FAX
ARCHITECT OF RECORD:
DRAWN BY:
PROJECT NUMBER:
SHEET NUMBER:
DATE ISSUED:
S. Kleinsorge
K. Taylor
Nov. 20, 2023 Bidding & Construction
23125-A
M c B a r a l
A g r i c u l t u r a l
S c h o o l
E a s t
M a p l e
S t r e e t
M c B a i n
M
I
P r o p o s e d
W i g h t
R o o m
R e n o v a t i o n f o r
LS1.0
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
2001 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1994 ADDITION
AutoCAD SHX Text
1994 ADDITION
AutoCAD SHX Text
1994 ADDITION
AutoCAD SHX Text
1994 ADDITION
AutoCAD SHX Text
1994 ADDITION
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
LIFE SAFETY FLOOR PLAN
AutoCAD SHX Text
SCALE 1" = 20'-0"
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1998 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
1988 ADDITION
AutoCAD SHX Text
2016 AUDITORIUM ADDITION
AutoCAD SHX Text
2016 AUDITORIUM ADDITION
AutoCAD SHX Text
2016 AUDITORIUM ADDITION
AutoCAD SHX Text
2016 AUDITORIUM ADDITION
AutoCAD SHX Text
2016 AUDITORIUM ADDITION
AutoCAD SHX Text
2 HOUR FIRE SEPARATION
AutoCAD SHX Text
1 HOUR FIRE SEPARATION
AutoCAD SHX Text
NOTE: REMAINDER OF THE BUILDING UNKNOWN
AutoCAD SHX Text McBAIN RURAL AGRICULTURAL SCHOOL
AutoCAD SHX Text
AutoCAD SHX Text A1.0
AutoCAD SHX Text McBAIN HIGH SCHOOL
AutoCAD SHX Text McBAIN MIDDLE SCHOOL
AutoCAD SHX Text McBAIN ELEMENTARY SCHOOL
AutoCAD SHX Text
AUDITORIUM
AutoCAD SHX Text
GYMNASIUM
AutoCAD SHX Text
LIBRARY
AutoCAD SHX Text
MULTI-PURPOSE
AutoCAD SHX Text
GYMNASIUM
AutoCAD SHX Text
EXISTING HIGH SCHOOL OFFICE WITH FIRE ALARM PANEL
AutoCAD SHX Text
EXISTING FIRE ALARM PULL
AutoCAD SHX Text
EXISTING FIRE ALARM PULL
AutoCAD SHX Text
EXISTING FIRE ALARM PULL
EXISTING ELECTRICAL ROOM
General notes:
1. Contractor shall verify all existing field conditions and notify architect immediately if that which exists differs from that which is shown on drawings.
2. All work to comply with current Federal, State and Local codes, laws and ordinances.The requirements of ICC/ANSI A117.1 and the Americans with disabilities act (ADA) are to be fully satisfied. All work shall meet the most stringent requirements of both including, but not limited to clearances, limitations, accessories, etc.
3. These drawings are prepared in accordance with the limited services for which the architect was contracted. The architect makes no representation that the interpretation of these documents will result in complete compliance with the
ADA.
4. All doors required to be labeled shall be set in labeled frames and identified with UL label and be provided with approved self-closing devices and positive latching hardware.
5. All designated exit doors shall be equipped with the required egress hardware.
6. Furnish hardware as scheduled without substitution, alternates may be approved by owner.
7. Furnish a keyed cylinder and two cut keys for each locking device specified;
keyed to the Owners' Master Key System. Include key conference and key system schedule.
8. Furnish and provide all necessary reinforcements, brackets, fasteners, spacers and fillers to provide a complete functioning opening.
9. Provide complete shop drawings, submittals and cut sheets complying with DHI prescribed methods and vertical format double spaced hardware schedule.
10. All access control modules, fobs and readers, to be furnished by Security
Vender under a separate section. Line voltage, circuits, cable and installation of power supplies for controllers and access control peripherals to be furnished and installed by electrical contractor.
Hardware Set 1 - Rim Panics x Mullion w/ Classroom Trim (Lock / Unlock) + Closers
6 ea. Butt Hinge 4B81 4 ½” x 4 ½” NRP 26D PBB
2 ea. Rim Panic 6300R CD (08) 32D PDQ
2 ea. Classroom Trim 6W 08 MIA 26D PDQ
1 ea. Keyed Removable Mullion 9300 689 PDQ
4 ea. LSDA Mortise Cylinder (08) (CD) 26D LSDA
1 ea. LSDA Rim Cylinder (KM) 26D LSDA
2 ea. Closer 7101 BC EDA (push side mount) 689 PDQ
2 ea. Kickplate 90 10 x 2” LDW B4E 32D Don Jo
2 ea. Wall Stop 1490 26D Don Jo
Hardware Set 2 - Fire Exit Hardware w/ Classroom Trim (Lock / Unlock) + Closer
3 ea. Butt Hinge 4B81 4 ½” x 4 ½” NRP 26D PBB
1 ea. Fire Exit Hardware 6300RF (08) 32D PDQ
1 ea. Classroom Trim 6W 08 MIA 26D PDQ
2 ea. LSDA Mortise Cylinder (08) (CD) 26D LSDA
1 ea. Closer 7101 BC EDA (push side mount) 689 PDQ
1 ea. Kickplate 90 10 x 2” LDW B4E 32D Don Jo
1 ea. Wall Stop 1490 26D Don Jo
1 set Smoke Seal 797B Black Reese
A1.0
ARCHITECTURE
CONSTRUCTION MANAGEMENT
DEVELOPMENT
1104 S. MITCHELL ST.
CADILLAC, MICHIGAN 49601
(231) 779-4002
(231) 779-4022 FAX
ARCHITECT OF RECORD:
DRAWN BY:
PROJECT NUMBER:
SHEET NUMBER:
DATE ISSUED:
S. Kleinsorge
K. Taylor
Nov. 20, 2023 Bidding & Construction
23125-A
M c B a r a l
A g r i c u l t u r a l
S c h o o l
E a s t
M a p l e
S t r e e t
M c B a i n
M
I
P r o p o s i g h t
R o o m
R e n o v a t i o n f o r
AutoCAD SHX Text
REMOVE EXISTING PLUMBING FIXTURES, COMPLETE. SEE PLUMBING FOR MORE INFO.
AutoCAD SHX Text REMOVE EXISTING LOCKERS AND WOOD BENCH, COMPLETE. PROTECT EXISTING LOCKERS FOR REUSE BY OWNER.
AutoCAD SHX Text REMOVE EXISTING MASONRY WALLS & DOORS, COMPLETE. PATCH / REPAIR EXISTING WALLS & SLAB AS REQ'D.
AutoCAD SHX Text
LIMITS OF CONSTRUCTION
AutoCAD SHX Text GENERAL DEMOLITION NOTES: 1. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS PRIOR TO THE START CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS PRIOR TO THE START OF DEMOLITION ACTIVITIES. 2. PROVIDE ALL SHORING AND BRACING AS REQ'D DURING DEMOLITION. PROVIDE ALL SHORING AND BRACING AS REQ'D DURING DEMOLITION. 3. PROVIDE PROTECTION FOR EXISTING CONSTRUCTION TO REMAIN. PATCH PROVIDE PROTECTION FOR EXISTING CONSTRUCTION TO REMAIN. PATCH AND REPAIR ALL AREAS DAMAGED DURING DEMOLITION / CONSTRUCTION. MATCH EXISTING CONSTRUCTION, MATERIALS AND FINISHES. TYPICAL AT ALL LOCATIONS. 4. OWNER SHALL REMOVE EXISTING WEIGHT EQUIPMENT BEFORE START OF OWNER SHALL REMOVE EXISTING WEIGHT EQUIPMENT BEFORE START OF CONSTRUCTION. 5. REMOVE ALL EXISTING FLOOR COVERING AT SAWCUT AREA, COMPLETE TO REMOVE ALL EXISTING FLOOR COVERING AT SAWCUT AREA, COMPLETE TO EXISTING SUB-FLOOR, UNLESS NOTED OTHERWISE. REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL INFORMATION. REMAINDER OF EXISTING RUBBER FLOORING TO REMAIN / BE REUSED. 6. REMOVE ALL EXISTING LAY-IN CEILING TILES & GRID AT LIMITS OF REMOVE ALL EXISTING LAY-IN CEILING TILES & GRID AT LIMITS OF CONSTRUCTION, UNLESS NOTED OTHERWISE. REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL INFORMATION. 7. EXISTING LIGHTING SHALL BE REMOVED & REPLACED AT LIMITS OF EXISTING LIGHTING SHALL BE REMOVED & REPLACED AT LIMITS OF CONSTRUCTION, UNLESS NOTED OTHERWISE. REFER TO ELECTRICAL PLANS. 8. AT WALLS TO BE REMOVED, REMOVE ELECTRICAL CIRCUIT OR BRANCH AT WALLS TO BE REMOVED, REMOVE ELECTRICAL CIRCUIT OR BRANCH WIRING BACK TO PANEL SERVING AREA. FIELD VERIFY. REFER TO ELECTRICAL PLANS. 9. ITEMS MARKED "TO BE REUSED / SALVAGED" ARE TO BE CAREFULLY ITEMS MARKED "TO BE REUSED / SALVAGED" ARE TO BE CAREFULLY REMOVED, CLEANED, PROTECTED AND STORED UNTIL REINSTALLED. 10. EACH CONTRACTOR INVOLVED IN DEMOLITION SHALL REMOVE AND EACH CONTRACTOR INVOLVED IN DEMOLITION SHALL REMOVE AND PROPERLY DISPOSE OF ALL REFUSE AND MATERIALS FROM DEMOLITION OPERATION. 11. DEMOLITION FOR INSTALLATION OF MECHANICAL, ELECTRICAL, AND DEMOLITION FOR INSTALLATION OF MECHANICAL, ELECTRICAL, AND PLUMBING ITEMS SHALL BE PROVIDED BY THE TRADE INSTALLING THOSE ITEMS OR AS DIRECTED BY THE GENERAL CONTRACTOR. SEE MECHANICAL, ELECTRICAL, AND PLUMBING FOR ADDITIONAL DEMOLITION INFORMATION. TRADE PROVIDING DEMOLITION SHALL PATCH EXISTING TO REMAIN AS REQ'D.
AutoCAD SHX Text
REMOVE EXISTING DOOR & FRAME, COMPLETE
AutoCAD SHX Text
ALL EXISTING MIRRORS TO REMAIN, PROTECT DURING CONSTRUCTION
AutoCAD SHX Text
PROTECT PICTURES ALONG THIS WALL DURING CONSTRUCTION
AutoCAD SHX Text SAWCUT & REMOVE EXISTING CONC. SLAB AS REQ'D AT EXISTING BATH / SHOWER / LOCKER ROOM TO EXTEND EXISTING SANITARY SEWER TO NEW PLUMBING FIXTURES. ;425 S.F. SEE NEW WORK / PLUMBING FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
PARTIAL PLAN
AutoCAD SHX Text
SCALE 1/8" = 1'-0"
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text
EXIST. GYM
AutoCAD SHX Text
NAME
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
ROOM FINISH SCHEDULE
AutoCAD SHX Text
WALL
AutoCAD SHX Text
NO.
AutoCAD SHX Text
ROOMS
AutoCAD SHX Text
FIN.
AutoCAD SHX Text
BASE
AutoCAD SHX Text
MAT'L
AutoCAD SHX Text
FIN.
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
HT.
AutoCAD SHX Text
MAT'L
AutoCAD SHX Text
FIN.
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text NOTES: 1. VERIFY & COORDINATE ALL FINISHES W/ OWNER PRIOR VERIFY & COORDINATE ALL FINISHES W/ OWNER PRIOR TO THE START OF CONSTRUCTION. 2. SEE INTERIOR ELEVATIONS & REFLECTED CEILING PLANS SEE INTERIOR ELEVATIONS & REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION. 3. SEE SPECIFICATIONS FOR MATERIAL DETAILS & FINISHES.SEE SPECIFICATIONS FOR MATERIAL DETAILS & FINISHES.
AutoCAD SHX Text LEGEND: ACT ACOUSTICAL CEILING TILE ACOUSTICAL CEILING TILE ETR EXISTING TO REMAIN EXISTING TO REMAIN EX. CMU EXISTING CMU EXISTING CMU FF FACTORY FINISH FACTORY FINISH MATCH EX. MATCHED EXISTING REMOVED RUBBER RUBBER MAT RUBBER MAT
AutoCAD SHX Text
WEIGHT ROOM
AutoCAD SHX Text
AutoCAD SHX Text
ACT
AutoCAD SHX Text
FF
AutoCAD SHX Text
ETR / RUBBER
AutoCAD SHX Text
PAINT
AutoCAD SHX Text
HARDWARE SETS
AutoCAD SHX Text
DOOR LOCATION
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
GLAZING
AutoCAD SHX Text
FRAME
AutoCAD SHX Text
HDWR.
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
DOOR SCHEDULE
AutoCAD SHX Text
RATING
AutoCAD SHX Text W
AutoCAD SHX Text H
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DOOR FRAME TYPES
AutoCAD SHX Text A
AutoCAD SHX Text
HM WELDED
AutoCAD SHX Text B
AutoCAD SHX Text
WEIGHT ROOM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ETR
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
PR. 3'-0"
AutoCAD SHX Text
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 100C
AutoCAD SHX Text 100B
AutoCAD SHX Text 100A
AutoCAD SHX Text
HM WELDED W/ REMOVABLE MULLION
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
DOOR TYPES
AutoCAD SHX Text
HM FLUSH
AutoCAD SHX Text
AutoCAD SHX Text
SEE DETAIL 1/A1.0 FOR TYPICAL WALL PAINT
AutoCAD SHX Text
AutoCAD SHX Text
EX. / NEW CMU
AutoCAD SHX Text
NOTE: VERIFY ALL ROUGH OPENINGS PRIOR TO ORDERING DOORS & FRAMES.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ETR
AutoCAD SHX Text
DETL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WEIGHT ROOM
AutoCAD SHX Text
WEIGHT ROOM
AutoCAD SHX Text 7'-0"
AutoCAD SHX Text
20 MIN.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MATCH EX.
AutoCAD SHX Text
LIMITS OF CONSTRUCTION
AutoCAD SHX Text
EXIST. GYM
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
%%UROOM
AutoCAD SHX Text
AutoCAD SHX Text VERIFY LOCATION OF EXISTING CEILING HUNG UNIT VENTILATORS. COORDINATE LIGHTING & NEW ACOUSTICAL CEILING AS REQ'D
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
PARTIAL PLAN
AutoCAD SHX Text
SCALE 1/8" = 1'-0"
AutoCAD SHX Text
REFLECTED CEILING
AutoCAD SHX Text
MATCH
AutoCAD SHX Text
EX. REMOVED
AutoCAD SHX Text
LIMITS OF CONSTRUCTION
AutoCAD SHX Text
EXIST. GYM
AutoCAD SHX Text 100A
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
%%UROOM
AutoCAD SHX Text
AutoCAD SHX Text 100B
AutoCAD SHX Text 100C
AutoCAD SHX Text
AutoCAD SHX Text A1.0
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text
CJ
AutoCAD SHX Text EXISTING MIRRORS TO REMAIN. INSTALL OWNER SUPPLIED MIRRORS TO REPLACE DAMAGED UNITS, VERIFY w/ OWNER.
AutoCAD SHX Text POUR NEW 4" CONC. SLAB w/ 6x6 W1.4x1.4 WWF. OVER 10 MIL VAPOR BARRIER @ REMOVED SLAB. ;425 S.F. @ EDGES PROVIDE #4 DOWEL @ 12" O.C., 12" LG. DRILLED & EPOXIED INTO ADJACENT EX. CONC. SLAB OR WALL
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
PARTIAL PLAN
AutoCAD SHX Text
SCALE 1/8" = 1'-0"
AutoCAD SHX Text
NEW WORK
AutoCAD SHX Text
4" CMU WALL
AutoCAD SHX Text F.E.C.
AutoCAD SHX Text GENERAL NEW WORK NOTE: 1. NEW WALLS TO EXTEND TO STRUCTURE ABOVE. NEW WALLS TO EXTEND TO STRUCTURE ABOVE. 2. NEW ELECTRICAL WORK SHALL BE CONCEALED WITH-IN EXISTING WALLS NEW ELECTRICAL WORK SHALL BE CONCEALED WITH-IN EXISTING WALLS (CMU) OR NEW WALLS (CMU.). PATCH / REPAIR EX. WALLS AS REQ'D.
AutoCAD SHX Text
(2) COLOR PAINT BAND, TYPICAL AROUND ENTIRE WEIGHT ROOM. 'McBAIN' YELLOW - TOP STRIPE 'McBAIN' GREEN - BOTTOM STRIPE
AutoCAD SHX Text 101A
AutoCAD SHX Text
36" MAX.
AutoCAD SHX Text
36" MAX.
AutoCAD SHX Text
38" MIN. - 43" MAX.
AutoCAD SHX Text
38" MIN. - 43" MAX.
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
30" MIN.
AutoCAD SHX Text
AutoCAD SHX Text A1.0
AutoCAD SHX Text
%%UNEW DRINKING FOUNTAIN
AutoCAD SHX Text \" = 1'-0"
AutoCAD SHX Text
SOLID COLOR PAINT AS SELECTED BY OWNER, TYPICAL AROUND ENTIRE WEIGHT ROOM.
SOLID COLOR PAINT AS SELECTED BY OWNER, TYPICAL AROUND ENTIRE WEIGHT ROOM.
CONCRETE TEMPERATURE:
TEST HOURLY WHEN AIR TEMPERATURE IS 40 DEGREES F. AND BELOW, AND WHEN 80 DEGREES
AND ABOVE, AND EACH TIME A SET OF COMPRESSION TEST SPECIMENS IS MADE.
COMPRESSION TEST SPECIMEN:
ASTM C 31 - ONE SET OF THREE (3) STANDARD CYLINDERS FOR EACH COMPRESSIVE
STRENGTH TEST, UNLESS OTHERWISE DIRECTED. MOLD AND STORE CYLINDERS FOR
LABORATORY CURED TEST SPECIMENS, EXCEPT WHEN FIELD-CURED TEST SPECIMENS ARE
REQUIRED.
COMPRESSIVE STRENGTH TEST:
ASTM C 39 - ONE SET FOR EACH 100 CU. YDS. OR FRACTION THEREOF OF EACH CONCRETE
CLASS PLACED IN ANY ONE DAY OR FOR EACH 5,000 SQ. FT. OF SURFACE AREA PLACED, ONE
SPECIMEN TESTED AT 7 DAYS, ONE SPECIMEN TESTED AT 28 DAYS, AND ONE SPECIMEN
RETAINED IN RESERVE FOR LATER TESTING, IF REQUIRED. WHEN THE STRENGTH OF FIELD-CURED
CYLINDERS IS LESS THAN 85% OF COMPANION LABORATORY-CURED CYLINDERS, EVALUATE
CURRENT OPERATIONS AND PROVIDE CORRECTIVE PROCEDURES FOR PROTECTING AND CURING
THE IN-PLACE CONCRETE.
TEST RESULTS WILL BE REPORTED IN WRITING TO THE ARCHITECT AND THE CONTRACTOR ON
THE SAME DAY THAT TESTS ARE MADE. REPORTS OF COMPRESSIVE STRENGTH TESTS SHALL
CONTAIN THE PROJECT IDENTIFICATION NAME AND NUMBER, DATE OF CONCRETE PLACEMENT,
NAME OF CONCRETE TESTING SERVICE, CONCRETE TYPE AND CLASS, LOCATION OF CONCRETE
BATCH IN THE STRUCTURE DESIGN, COMPRESSIVE STRENGTH AT 28 DAYS, CONCRETE MIX
PROPORTIONS AND MATERIALS, COMPRESSIVE BREAKING STRENGTH, AND TYPE OF BREAK FOR
BOTH 7-DAY TESTS AND 28-DAY TESTS AND LOCATION OF TEST.
04 00 00 MASONRY
GENERAL NOTES:
ALL PERTINENT REQUIREMENTS OF THE INSTRUCTION FOR BIDDERS, THE GENERAL CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND FINISH SCHEDULE SHALL FORM PART OF THESE
SPECIFICATIONS.
SCOPE:
PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS LISTED, MENTIONED OR
SCHEDULED ON DRAWINGS AND/OR HEREIN SPECIFIED, INCLUDING ALL LABOR, MATERIALS,
EQUIPMENT AND INCIDENTALS, NECESSARY AND REQUIRED FOR THEIR COMPLETION.
STANDARDS:
PROVISIONS OF THE FOLLOWING CODES, SPECIFICATIONS AND STANDARDS SHALL BE
MINIMUM GUIDELINES, MORE STRINGENT BUILDING CODE REQUIREMENTS SHALL GOVERN.
ACI530-02/ASCE5-02/TMS 602-02
- BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
BIA - TECHNICAL NOTES
NCMA - CONCRETE MASONRY SPECIFICATIONS
04 40 50 MORTAR & GROUT MATERIALS:
ALL MORTAR SHALL BE PREPARED MASONRY MORTAR MANUFACTURED IN ACCORDANCE WITH
THE RECOMMENDATIONS OF THE PORTLAND CEMENT ASSOCIATION AND MEETING ASTM C270
FOR TYPE S MORTAR.
ONLY ONE (1) BRAND OF MORTAR SHALL BE USED ON EXPOSED PORTIONS OF MASONRY.
COLOR(S) SHALL MATCH EXISTING. APPROVED MORTAR COLORING PRODUCTS ARE AS
FOLLOWS:
EUCLID CHEMICAL COMPANY
"EUCO SUPER CONCENTRATED MORTAR COLORS"
GEO. B. SMITH COLOR COMPANY
"SMITH COLORS"
SOLOMON GRIND-CHEM SERVICE
"CONCENTRATED MORTAR COLORS"
PORTLAND CEMENT:
ASTM C 150/ C 150M TYPE I OR II, EXCEPT WHERE TYPE III MAY BE USED FOR COLD WEATHER
CONSTRUCTION. PROVIDE NATURAL COLOR OR WHITE CEMENT AS REQUIRED TO PRODUCE
MORTAR COLOR INDICATED/ SELECTED.
AGGREGATE (CRUSHED STONE) and/or NATURAL SAND SHALL CONFORM TO ASTM C144.
HYDRATED LIME: ASTM C 207, TYPE S.
PORTLAND CEMENT-LIME MIX:
PACKAGED BLEND OF PORTLAND CEMENT AND HYDRATED LIME CONTAINING NO OTHER
INGREDIENTS.
MASONRY CEMENT:
ASTM C 91/ C 91M, AS MANUFACTURED BY LAFARGE NORTH AMERICA INC.
MASONRY PIGMENTS:
NATURAL AND SYNTHETIC IRON OXIDES AND CHROMIUM OXIDES, COMPOUNDED FOR USE IN
MORTAR MIXES AND COMPLYING WITH ASTM C979/ C 979M. USE ONLY PIGMENTS WITH A
RECORD OF SATISFACTORY PERFORMANCE IN MASONRY MORTAR AS MANUFACTURED BY
SOLOMON COLORS, INC. ONLY ONE (1) BRAND OF MORTAR SHALL BE USED ON EXPOSED
PORTIONS OF MASONRY. COLOR(S) SHALL BE AS SELECTED BY ARCHITECT/ OWNER.
COLORED CEMENT:
PACKAGED BLEND MADE FROM PORTLAND CEMENT AND HYDRATED LIME OR MASONRY CEMENT
AND MORTAR PIGMENTS COMPLYING WITH THE SPECIFIED REQUIREMENTS, COLORED PORTLAND
CEMENT-LIME MIX OR COLORED MASONRY CEMENT AS MANUFACTURED BY LAFARGE NORTH
AMERICA, INC.
MORTAR AGGREGATE:
ASTM C 144, FOR JOINTS LESS THAN |" USE AGGREGATE GRADED WITH 100% PASSING THE
NO. 16 SIEVE. WHITE MORTAR AGGREGATES, NATURAL WHITE SAND OR CRUSHED WHITE
STONE. COLORED AGGREGATES, NATURAL SAND OR CRUSHED STONE OF COLOR NECESSARY
TO PRODUCE REQUIRED MORTAR COLOR.
GROUT AGGREGATE: ASTM C 404.
COLD WEATHER ADMIXTURE:
NONCHLORIDE, NONCORROSIVE, ACCELERATING ADMIXTURE COMPLYING WITH ASTM C 494/ C
494M, TYPE C AND AS RECOMMENDED BY MANUFACTURER AS MANUFACTURED BY EUCLID
CHEMICAL COMPANY.
WATER REPELLENT ADMIXTURE:
LIQUID WATER REPELLENT MORTAR ADMIXTURE INTENDED FOR USE WITH CMU's CONTAINING
INTEGRAL WATER REPELLENT FROM SAME MANUFACTURER. EQUAL TO EUCLID CHEMICAL
COMPANY.
WATER: POTABLE.
MIXING SHALL BE POWERED MIXERS WITH STANDARDIZED BATCHING PROCEDURES, AND IN
QUANTITIES REQUIRED FOR IMMEDIATE USE. MIX SHALL BE ONE (1) PART MASONRY CEMENT TO
2 ¼ TO 3 PARTS SAND MEASURED BY VOLUME, ADJUSTED TO GIVE PROPER WORKABILITY.
ADJUST CONSISTENCY OF MORTAR FOR WORKABILITY, BUT ADD ONLY A MINIMUM AMOUNT OF
WATER. USE MORTAR WITHIN 2 1/2 HOURS OF INITIAL MIXING AND IN NO CASE AFTER IT HAS
BEGUN TO SET.
MASONRY ACCESSORIES:
WHERE SO SPECIFIED HEREIN, OR IN OTHER DIVISIONS OF THE SPECIFICATION, THE
CONTRACTOR SHALL SET OTHER MATERIALS. HE SHALL READ THE SPECIFICATIONS FOR THE
VARIOUS TRADES AND ACQUAINT HIMSELF WITH AND BE RESPONSIBLE FOR WORK WHICH HE IS
TO SET OR BUILD IN.
BUILT-IN MATERIALS AND EQUIPMENT OCCURRING IN MASONRY, WHICH ARE FURNISHED BY
OTHER CONTRACTORS SHALL BE COORDINATED WITH THE OTHER CONTRACTORS TO ALLOW
AMPLE OPPORTUNITY FOR PLACEMENT OF THEIR MATERIALS.
ALL EXTERIOR WALLS SHALL BE FLASHED AS SHOWN ON DRAWINGS AND AS IN KEEPING WITH
GOOD PRACTICE FOR A WATERTIGHT ASSEMBLY.
04 20 00 GENERAL UNIT MASONRY:
GENERAL:
COMPLY WITH TMS 602/ ACI 530-01/ ASCE 6. REFERENCED MASONRY UNIT STANDARDS MAY
ALLOW A CERTAIN PERCENTAGE OF UNITS TO CONTAIN CHIPS, CRACKS, OR OTHER DEFECTS
EXCEEDING LIMITS STATED. DO NOT USE UNITS WHERE SUCH DEFECTS ARE EXPOSED IN THE
COMPLETED WORK. FIRE RESISTANCE RATINGS SHALL COMPLY WITH REQUIREMENTS FOR FIRE
RESISTANCE RATED ASSEMBLY DESIGNS INDICATED.
CONCRETE MASONRY UNITS:
GENERAL:
PROVIDE SPECIAL SHAPES FOR LINTELS, CORNERS, JAMBS, SASHES, MOVEMENT JOINTS,
HEADERS, BONDING, AND OTHER SPECIAL CONDITIONS.
UNITS SHALL BE PROVIDED WITH INTEGRAL WATER REPELLENT FOR EXPOSED UNITS AS
MANUFACTURED BY ACM CHEMISTRIES OR EQUAL.
CONCRETE MASONRY UNITS (CMU) SHALL MEET ASTM C 90, NORMAL WEIGHT WITH A
COMPRESSIVE STRENGTH OF 2150 PSI. PATTERN AND TEXTURE SHALL BE AS INDICATED WITH-
IN CONSTRUCTION DOCUMENTS (THAT IS. STANDARD PATTERN, STANDARD PATTERN - GROUND
FACE FINISH, SCORED VERTICALLY - GROUND FACE FINISH, STANDARD PATTERN - SPLIT FACE
FINISH, ETC.).
LIGHTWEIGHT AGGREGATE BLOCK SHALL BE "WAYLITE" OR "HAYLITE" MANUFACTURED IN
ACCORDANCE WITH ASTM C90 AND IN ACCORDANCE WITH "Q" BLOCK SPECIFICATION
REQUIREMENTS. UNITS MAY BE OF TWO OR THREE CORE STYLE. LIGHT WEIGHT BLOCK SHALL
BE USED ONLY FOR ABOVE GRADE APPLICATION, NORMAL WEIGHT BELOW GRADE
APPLICATIONS.
ALL UNITS SHALL HAVE UNIFORM FACES AND SURFACE TEXTURE AND SHALL BE FREE FROM
DEFECTS FROM STAINS, CRACKS, CHIPS AND OTHER DEFECTS THAT WOULD IMPAIR THE
STRENGTH OR APPEARANCE. PROVIDE SPECIAL UNITS FOR CORNERS, LINTELS, BOND BEAMS,
PILASTERS, JAMBS, ETC., AS REQUIRED AND/OR SHOWN ON DRAWINGS.
UNITS SHALL BE CURED NOT LESS THAN THIRTY (30) DAYS BEFORE PLACING.
WHERE JOINTING IS EXPOSED TO VIEW AT INTERIOR, JOINTS SHALL BE FINISHED WITH A JOINT
TOOL TO PRODUCE A NEAT CONCAVE JOINT.
AT JOIST BEARING POINTS, LINTELS AND CONCENTRATED LOADS, GROUT CORES FULL 24"
MINIMUM BELOW POINT OF BEARING. ALL CORES CONTAINING VERTICAL REINFORCING SHALL
BE GROUTED FULL THEIR ENTIRE HEIGHT AND DOWELLED TO FOUNDATION. VERTICAL
REINFORCING SHALL EXTEND THROUGH BOND BEAMS.
WHERE INDICATED, PROVIDE VERTICAL CONTROL JOINTS. BREAK HORIZONTAL REINFORCING.
GROOVE OR WRAP BOND BEAMS. PROVIDE PAPER BREAK ONE SIDE OF CORE CONTINUOUS TO
FORM MICHIGAN JOINT. RAKE INTERIOR AND EXTERIOR JOINT BACK 1¼". INSTALL ½" DIAMETER
BACK ROD AND CAULK.
BLOCK SHALL BE NEATLY CUT USING A POWER MASONRY SAW.
CONCRETE LINTELS:
LINTELS SHALL COMPLY WITH ASTM C 1623, MATCH CMU COLOR, TEXTURE AND DENSITY
CLASSIFICATION, WITH REINFORCING BARS AS INDICATED.
STEEL LINTELS:
INSTALL STEEL LINTELS WHERE INDICATED. PROVIDE 8 INCHES AT EACH JAMB UNLESS
OTHERWISE INDICATED.
05 00 00 METALS
GENERAL:
PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS LISTED, MENTIONED OR
SCHEDULED HEREIN DRAWINGS INCLUDING ALL LABOR, MATERIALS, EQUIPMENT AND
INCIDENTIALS, NECESSARY AND REQUIRED TO COMPLETE WORK.
PROVISIONS OF THE FOLLOWING CODES, SPECIFICATIONS AND STANDARDS SHALL BE
MINIMUM GUIDELINES, MORE STRINGENT BUILDING CODE REQUIREMENTS SHALL GOVERN.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND PAYING ALL FEES FOR STEEL
TESTING.
AISC - THE DESIGN FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR
BUILDINGS.
AWS - AMERICAN WELDING SOCIETY - STANDARD QUALIFICATION PROCEDURE.
AISC - CODE OF STANDARD PRACTICE FOR DESIGN, FABRICATION AND ERECTION.
RCSC - SPECIFICATIONS FOR STRUCTURAL JOINTS.
SJI - STEEL JOIST INSTITUTE SPECIFICATIONS.
FABRICATOR SHALL BE QUALIFIED THAT PARTICIPATES IN AISC QUALITY CERTIFICATION
PROGRAM AND IS AN AISC CERTIFIED PLANT, CATEGORY STD OR CAN PROVIDE A WRITTEN
QUALITY CONTROL PROGRAM CERTIFIED BY AN INDEPENDENT TESTING AGENCY.
SPECIFICATIONS
01 00 00 GENERAL REQUIREMENTS
GENERAL:
THIS PLAN IS THE SOLE PROPERTY OF THE DK DESIGN GROUP LLC. REPRODUCTION IN WHOLE
OR IN PART IS PROHIBITED. USE IS CONFERRED ON OWNER/BUILDER FOR SINGLE TIME
CONSTRUCTION FROM THESE CONSTRUCTION DOCUMENTS.
COPYRIGHT BY THE DK DESIGN GROUP LLC, ALL RIGHTS RESERVED. NO PART OF THIS
PUBLICATION MAY BE REPRODUCED, STORED IN A RETRIEVAL SYSTEM OR TRANSMITTED IN ANY
FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL PHOTOCOPYING, RECORDING OR
OTHERWISE WITHOUT THE PRIOR WRITTEN PERMISSION OF THE PUBLISHER.
ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF THE
DRAWINGS, SPECIFICATIONS AND THE CURRENT BUILDING CODE.
CONTACT THE ARCHITECT IMMEDIATELY IF ANY DISCREPENCIES ARE DISCOVERED BETWEEN THE
DRAWINGS AND OR SPECIFICATIONS.
TEMPORARY CONSTRUCTION SHORING:
THE DK DESIGN GROUP ASSUMES NO RESPONSIBILTY FOR THE DESIGN OR PROPER
INSTALLATION OF TEMPORARY BUILDING BRACING AND SHORING OR THE MEANS AND METHODS
OF CONSTRUCTION NECESSARY TO COMPLETE THIS PROJECT.
THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND PROPER INSTALLATION OF BOTH
TEMPORARY BRACING AND SHORING REQUIRED FOR A SAFE AND STRUCTURALLY SOUND
PROJECT. THE STRUCTURAL COMPONENTS ARE NOT SELF-BRACING AND SHALL BE CONSIDERED
UNSTABLE UNTIL THE COMPLETED STRUCTURE IS IN PLACE AS INDICATED BY THESE DRAWINGS
AND SPECIFICATIONS. THE CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGES AND LIABILITY
INCURRED DUE TO IMPROPER BRACING AND SHORING DURING CONSTRUCTION.
DIMENSIONS:
DO NOT SCALE DRAWINGS. (USE DIMENSIONS). FIELD VERIFY ALL EXISTING DIMENSIONS AND EXISTING CONDITIONS BEFORE CONSTRUCTION. ALL INTERIOR AND EXTERIOR DIMENSIONS ARE SHOWN TO THE ROUGH FRAMING. ADDITIONAL FINISHES AND SHEATHING ARE NOT INCLUDED IN
THE DIMENSIONS.
03 00 00 CONCRETE WORK
GENERAL NOTES:
ALL PERTINENT REQUIREMENTS OF THE INSTRUCTION FOR BIDDERS, THE GENERAL CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND FINISH SCHEDULE SHALL FORM PART OF THESE
SPECIFICATIONS.
PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS LISTED, MENTIONED OR
SCHEDULED ON DRAWINGS AND/OR HEREIN SPECIFIED, INCLUDING ALL LABOR, MATERIALS,
EQUIPMENT AND INCIDENTALS, NECESSARY AND REQUIRED FOR THEIR COMPLETION.
STANDARDS: PROVISIONS OF THE FOLLOWING CODES, SPECIFICATIONS AND STANDARDS
SHALL BE MINIMUM GUIDELINES; MORE STRINGENT BUILDING CODE REQUIREMENTS SHALL
GOVERN.
ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS"
ACI 304 "RECOMMENDED PRACTICE FOR MEASURING, MIXING, TRANSPORTING
AND PLACING CONCRETE"
ACI 305 HOT WEATHER CONCRETING.
ACI 306 COLD WEATHER CONCRETING.
ACI 311 "RECOMMENDED PRACTICE FOR CONCRETE INSPECTION"
ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE"
ACI 347 "GUIDE TO FORMWORK FOR CONCRETE"
03 00 10 CONCRETE WALKS:
PROVIDE CONCRETE WALKS AS SHOWN AND DETAILED WITHIN THE DRAWINGS. WALKS SHALL BE
SLOPED 1/8" PER FOOT AWAY FROM BUILDINGS. EDGES SHALL BE TOOLED ROUND AT ALL
JOINTS. SCORE WALKS WITH 1" DEEP JOINTS. CONTROL JOINTS SHALL BE AT 5'-0" O.C. AND EXPANSION/ ISOLATION JOINTS AT 25'-0" AND AT ALL BUILDINGS, WALLS, CURBS AND FIXED
STRUCTURES.
03 10 00 CONCRETE FORMWORK:
DESIGN, ERECT, SHORE, BRACE AND MAINTAIN FORMWORK ACCORDING TO ACI 301.
FORMWORK SHALL BE ABLE TO SUPPORT VERTICAL, LATERAL, STATIC, DYNAMIC AND
COMBINATION LOADS THAT MIGHT BE APPLIED, UNTIL STRUCTURE CAN SUPPORT SUCH LOADS.
FORMS FOR CONCRETE SHALL BE INSTALLED AND BRACED PLUMB, LEVEL AND IN LINE WITH
BUILDING DIMENSIONS. CONSTRUCT FORMWORK SO CONCRETE MEMBERS AND STRUCTURES
ARE OF SIZE, SHAPE, ALIGNMENT, ELEVATION, AND POSITION INDICATED, WITH-IN TOLERANCE
LIMITS OF ACI 117. PROVIDE CHAMFER STRIPS ON ALL EXTERNAL CORNERS.
FORMWORK SHALL INCLUDE ALL SLOTS, CHASES, RECESSES, SLEEVES, NAILING BLOCKS,
HANGERS AND OTHER BUILT-IN DEVICES REQUIRED. DEVICES USED BY OTHER TRADES SHALL
BE FURNISHED TO THE CONCRETE CONTRACTOR FOR INSTALLATION.
PLACING OF CONDUIT:
ALL CONDUIT, PIPES, DUCTS AND DEVICES SHALL BE PLACED SO AS NOT TO WEAKEN THE
CONSTRUCTION, CONFORMING TO ACI 503. CONCRETE COVERAGE OF ALL CONDUIT, ETC.
SHALL BE NOT LESS THAN 2".
EXPANSION AND CONTRACTION JOINTS:
USE 3/8" ASPHALT IMPREGNATED VEGETABLE FIBER OR CLOSED CELL THERMO-SETTING PLASTIC
NON-EXTRUDING. WIDTH TO BE 1/2" LESS THAN SLAB THICKNESS. LOCATE JOINTS PER ACI
STANDARDS AT EXTERIOR SLABS.
CONTROL JOINTS:
DIVIDE CONCRETE SLABS AS SHOWN OR INTO NEARLY SQUARE AREAS WITH 1/8" WIDE BY 1"
DEEP JOINTS BY TROWELING OR SAWING WITHIN 24 HOURS AFTER POURING.
03 20 00 CONCRETE REINFORCEMENT:
REINFORCING BARS SHALL CONFORM TO ASTM 615 OR ASTM 616, 60,000 PSI YIELD.
WELDED WIRE FABRIC SHALL CONFORM TO ASTM 82 OR ASTM 185.
GLASS FIBER REINFORCING SHALL BE 1/2 " COLLATED POLYPROPYLENE FIBERS AS
MANUFACTURED BY W.R. GRACE & CO. DOSAGE RATES SHALL BE AS SPECIFIED BY THE
MANUFACTURER. GLASS FIBER REINFORCING SHALL BE USED IN ACCORDANCE WITH THE
MANUFACTURERS RECOMMENDATIONS, FOLLOW ASTM C-94 FOR MIXING AND ACI 302
INSTALLATION PROCEDURES
03 30 00 CAST IN PLACE CONCRETE:
CONCRETE SHALL BE READY MIX TYPE IN ACCORDANCE WITH ASTM C175 SPECIFICATIONS.
CONCRETE SHALL BE HANDLED AND INSPECTED IN ACCORDANCE WITH ALL APPROPRIATE CODES
AND STANDARDS INCLUDING ACI 301, 304, 305, 306, 311, 318 & 347.
MATERIALS SHALL BE AS FOLLOWS:
CEMENT:
PORTLAND CEMENT TYPE 1 OR 1A OR HIGH EARLY STRENGTH PORTLAND CEMENT TYPE 111
MEETING ASTM C150.
WATER: SHALL BE CLEAN, FREE OF ACIDS, ALKALIES AND POTABLE.
AGGREGATE – NORMAL THICKNESS SLABS:
SHALL CONFORM TO ALL REQUIREMENTS FOR HARDNESS, DURABILITY, PURITY, GRADATIONS,
ETC., AS SET FORTH IN ASTM C33. SAND SHALL BE NATURAL SHARP, COARSE, WASHED, FREE
FROM CLAY OR ORGANIC SUBSTANCES. GRAVEL AND STONE SHALL CONFORM TO ASTM C33-
55-T. AGGREGATE FOR ALL EXPOSED EXTERIOR SHALL BE 6AA LIMESTONE.
CONCRETE WALK/ CURB JOINTS:
WHERE SHOWN AND AS REQUIRED BY ACI PROVIDE AND INSTALL ALL NECESSARY CONTROL AND
EXPANSION JOINTS IN CONCRETE CURBS AND WALKS. UTILIZE PRE-MOLDED FILLER OF CLOSED
CELL POLYETHYLENE RESILIENT FOAM COMPATIBLE WITH SEALANT AND FREE OF OIL
IMPREGNATION, EQUAL TO SONOFLEX F BY SONNEBORN BUILDING PRODUCTS, DIVISION OF
CHEMREX, INC. SEALANT SHALL BE ONE (1) COMPONENT, NON-PRIMING, SELF LEVELING
POLYURETHANE EQUAL TO SONOLASTIC SL-1 BY SONNEBORN BUILDING PRODUCTS, DIVISION
OF CHEMREX, INC.
CONCRETE NOTES:
1. ACI BUILDING CODE (308) +/- MANUAL OF STANDARD PRACTICE FOR DETAILING (315)
FOR THE MIXING FABRICATION AND PLACEMENT OF CONCRETE, REINFORCING STEEL.
2. CONCRETE STRENGTH:
FOOTINGS, WALLS F'C = 3,000-3,500 PSI (MIN.)
FLOORS F'C = 3,000-3,500 PSI (MIN.)
EXTERIOR F’C= 4,000 PSI (MIN.)
3. REINFORCING BARS: ASTM A-615 GRADE 60 DEFORMED. SUPPORTS SHALL BE
BOLSTERS, CHAIRS, SPACERS OR OTHER DEVICES FOR SPACING AND SUPPORT AND
FASTENTING OF REINFORCING BARS AND WELDED WIRE FABRIC. PRODUCTS SHALL
CONFORM TO CRSI's "MANUAL OF STANDARD PRACTICE".
4. WELDED WIRE FABRIC: ASTM A 1064/ A 1064M
(FLAT SHEETS)
DEFORMED STEEL: ASTM A 1064/ A 1064M (FLAT
SHEETS).
GALVANIZED STEEL: ASTM A 1064/ A 1064M (FLAT
SHEETS).
5. SLAB ON GRADE REINFORCING: 4” SLABS - 6"x6" W1.4xW1.4 WWF, 5” SLABS - 6"x6" W2.1xW2.1 WWF, 6" SLABS - 6"x6" W2.9xW2.9 WWF UNLESS NOTED OTHERWISE.
LOCATE IN UPPER 1/3 OF SLAB.
6. FOOTINGS: SEE STRUCTURAL SHEETS AND SOIL REPORT FOR ADDITIONAL INFORMATION
(IF AVAILABLE).
7. REMOVE ALL UNSUITABLE EARTH COMPLETE. PLACE STRUCTURAL FILL IN 4" LOOSE
LAYER THICKNESS. COMPACT TO AT LEAST 95% MAXIMUM DENSITY PER ASTM D1557.
COMPACTING BY FLOODING IS NOT ALLOWED.
8. CENTER THICKENED SLABS UNDER WALLS, UNLESS
NOTED OTHERWISE.
9. SEE STRUCTURAL NOTES FOR SLUMP
REQUIREMENTS.
10. THE CONTRACTOR WILL EMPLOY A TESTING
LABORATORY TO PERFORM THE FOLLOWING TESTS
AND TO SUBMIT TEST REPORTS.
11. SAMPLING AND TESTING FOR QUALITY CONTROL DURING THE PLACEMENT OF CONCRETE
WILL INCLUDE THE FOLLOWING, AS DIRECTED BY THE ARCHITECT.
SITE MIXED CONCRETE SHALL CONFORM TO ACI-613-34. READY MIXED CONCRETE SHALL
CONFORM TO ASTM C94. SLABS SHALL DEVELOP A STRENGTH OF 3500 PSI WITH A SEVEN (7)
DAY STRENGTH 65% OF ULTIMATE STRENGTH.
CHEMICAL ADMIXTURES:
SHALL BE CERTIFIED TO BE COMPATABLE WITH OTHER ADMIXTURES AND THAT DO NOT
CONTRIBUTE WATER SOLUBLE CHLORIDE IONS EXCEEDING THOSE PERMITTED IN HARDENED
CONCRETE. DO NUT USE CALCIUM CHLORIDE OR ADMIXTURES CONTAINING CALCIUM CHLORIDE.
WATER REDUCING ADMIXTURE: ASTM C 494/ C 494M, TYPE A.RETARDING ADMIXTURE: ASTM C
494/ C 494M, TYPE B. WATER REDUCING & RETARDING ADMIXTURE: ASTM C 494/ C 494M,
TYPE D. HIGH RANGE WATER REDUCING ADMIXTURE: ASTM C 494/ C 494M, TYPE F. HIGH
RANGE WATER REDUCING & RETARDING ADMIXTURE: ASTM C 494/ C 494M, TYPE G.
PLASTICIZING & RETARDING ADMIXTURE: ASTM C 1017/ C 1017M, TYPE II.
SHEET VAPOR RETARDER:
POLYETHYLENE SHEET, ASTM D 4397, NOT LESS THAN 10 MIL THICKNESS.
EVAPORATION RETARDER:
WATERBORNE, MONOMOLECULAR FILM FORMING, MANUFACTURED FOR APPLICATION TO FRESH
CONCRETE. ABSORPTIVE COVER SHALL COMPLY WITH AASHTO M 182, CLASS 2, BURLAP
CLOTH MADE FROM JUTE OR KENAF; 9 OZ./ SYD. MOISTURE RETARDING COVER SHALL COMPLY
WITH ASTM C 171, POLYETHYLENE FILM OR WHITE BURLAP-POLYETHYLENE SHEET. WATER SHALL
BE POTABLE.
CONCRETE SAMPLING & TESTING:
SAMPLING FRESH CONCRETE: ASTM C 172, EXCEPT MODIFIED SLUMP ASTM
C 143, ONE TEST FOR EACH CONCRETE LOAD AT POINT OF DISCHARGE, AND ONE TEST FOR
EACH SET OF COMPRESSIVE STRENGTH TEST SPECIMENS. ON LARGER PROJECTS, PROVIDE ONE
TEST FOR EVERY THIRD LOAD OR USE RANDOM NUMBERS FOR DETERMINING THE NUMBER OF
TESTS.
AIR CONTENT:
ASTM C 231 PRESSURE FOR NORMAL WEIGHT CONCRETE: ONE FOR EACH TIME A SET OF
COMPRESSIVE STRENGTH TEST SPECIMENS.
A2.0
ARCHITECTURE
CONSTRUCTION MANAGEMENT
DEVELOPMENT
1104 S. MITCHELL ST.
CADILLAC, MICHIGAN 49601
(231) 779-4002
(231) 779-4022 FAX
ARCHITECT OF RECORD:
DRAWN BY:
PROJECT NUMBER:
SHEET NUMBER:
DATE ISSUED:
S. Kleinsorge
K. Taylor
Nov. 20, 2023 Bidding & Construction
23125-A
M c B a r a l
A g r i c u l t u r a l
S c h o o l
E a s t
M a p l e
S t r e e t
M c B a i n
M
I
P r o p o s i g h t
R o o m
R e n o v a t i o n f o r
QUALITY ASSURANCE:
CONTRACTOR SHALL PROVIDE EFFECTIVE, FULL TIME QUALITY CONTROL OVER ALL FABRICATION
AND ERECTION COMPLYING WITH THE PERTINENT CODES AND REGULATIONS OF GOVERNMENT
AGENCIES HAVING JURISDICTION.
TESTING AGENCY QUALIFICATIONS: QUALIFIED ACCORDING TO ASTM E 329 FOR TESTING
INDICATED.
WELDING QUALIFICATIONS: QUALIFY PROCEDURES AND PERSONNEL ACCORDING TO
AWS D1.3/D1.3M, "STRUCTURAL WELDING CODE - SHEET STEEL."
FM GLOBAL LISTING: PROVIDE STEEL ROOF DECK EVALUATED BY FM GLOBAL AND
LISTED IN ITS "APPROVAL GUIDE, BUILDING MATERIALS" FOR CLASS 1 FIRE RATING
AND CLASS 1-90 WINDSTORM RATINGS.
ROOF DECK
ROOF DECK: FABRICATE PANELS, WITHOUT TOP-FLANGE STIFFENING GROOVES, TO COMPLY
WITH "SDI SPECIFICATIONS AND COMMENTARY FOR STEEL ROOF DECK," IN SDI PUBLICATION
NO. 31, AND WITH THE FOLLOWING:
PRIME-PAINTED STEEL SHEET: ASTM A 1008/A 1008M, STRUCTURAL STEEL (SS),
GRADE 33 (230) MINIMUM, SHOP PRIMED WITH MANUFACTURER'S STANDARD
BAKED-ON, RUST-INHIBITIVE PRIMER. PRIME BOTH SIDES OF DECK.
DECK PROFILE: TYPE WR, WIDE RIB.
DECK PROFILE: DOVETAIL (EPICORE OR VERSA-DEK)
PROFILE DEPTH: AS INDICATED.
DESIGN UNCOATED-STEEL THICKNESS: AS INDICATED.
SPAN CONDITION: TRIPLE SPAN OR MORE.
SIDE LAPS: OVERLAPPED OR INTERLOCKING SEAMS.
ACCESSORIES:
GENERAL: PROVIDE MANUFACTURER'S STANDARD ACCESSORY MATERIALS FOR DECK THAT
COMPLY WITH REQUIREMENTS INDICATED.
MECHANICAL FASTENERS: CORROSION-RESISTANT, LOW-VELOCITY, POWER-ACTUATED OR
PNEUMATICALLY DRIVEN CARBON-STEEL FASTENERS; OR SELF-DRILLING, SELF-
THREADING SCREWS.
SIDE-LAP FASTENERS: CORROSION-RESISTANT, HEXAGONAL WASHER HEAD; SELF-DRILLING,
CARBON-STEEL SCREWS, NO. 10 MINIMUM DIAMETER.
FLEXIBLE CLOSURE STRIPS: VULCANIZED, CLOSED-CELL, SYNTHETIC RUBBER.
MISCELLANEOUS SHEET METAL DECK ACCESSORIES: STEEL SHEET, MINIMUM YIELD STRENGTH OF
33,000 PSI, NOT LESS THAN 0.0359-INCH DESIGN UNCOATED THICKNESS, OF SAME
MATERIAL AND FINISH AS DECK; OF PROFILE INDICATED OR REQUIRED FOR APPLICATION.
WELD WASHERS: UNCOATED STEEL SHEET, SHAPED TO FIT DECK RIB, 0.0747 INCH (1.90 MM)
THICK, WITH FACTORY- PUNCHED HOLE OF 3/8-INCH (9.5-MM) MINIMUM DIAMETER.
FLAT SUMP PLATES: SINGLE-PIECE STEEL SHEET, 0.0747 INCH THICK, OF SAME MATERIAL AND
FINISH AS DECK. FOR DRAINS, CUT HOLES IN THE FIELD.
GALVANIZING REPAIR PAINT: [ASTM A 780/A 780M] [SSPC-PAINT 20 OR MIL-P-21035B, WITH
DRY FILM CONTAINING A MINIMUM OF 94 PERCENT ZINC DUST BY WEIGHT].
REPAIR PAINT: MANUFACTURER'S STANDARD RUST-INHIBITIVE PRIMER OF SAME COLOR AS
PRIMER.
EXECUTION:
INSTALL DECK PANELS AND ACCESSORIES ACCORDING TO APPLICABLE SPECIFICATIONS AND
COMMENTARY IN SDI PUBLICATION NO. 31, MANUFACTURER'S WRITTEN INSTRUCTIONS, AND
REQUIREMENTS IN THIS SECTION. PLACE DECK PANELS FLAT AND SQUARE AND FASTEN TO
SUPPORTING FRAME WITHOUT WARP OR DEFLECTION. CUT AND NEATLY FIT DECK PANELS AND
ACCESSORIES AROUND OPENINGS AND OTHER WORK PROJECTING THROUGH OR ADJACENT TO
DECK. PROVIDE ADDITIONAL REINFORCEMENT AND CLOSURE PIECES AT OPENINGS AS REQUIRED
FOR STRENGTH, CONTINUITY OF DECK, AND SUPPORT OF OTHER WORK. COMPLY WITH AWS
REQUIREMENTS AND PROCEDURES FOR MANUAL SHIELDED METAL ARC WELDING, APPEARANCE
AND QUALITY OF WELDS, AND METHODS USED FOR CORRECTING WELDING WORK. MECHANICAL
FASTENERS MAY BE USED IN LIEU OF WELDING TO FASTEN DECK. LOCATE MECHANICAL
FASTENERS AND INSTALL ACCORDING TO DECK MANUFACTURER'S WRITTEN INSTRUCTIONS.
FIELD QUALITY CONTROL
TESTING AGENCY: OWNER WILL ENGAGE A QUALIFIED TESTING AGENCY TO PERFORM
TESTS AND INSPECTIONS.
FIELD WELDS WILL BE SUBJECT TO INSPECTION.
TESTING AGENCY WILL REPORT INSPECTION RESULTS PROMPTLY AND IN WRITING TO
CONTRACTOR AND ARCHITECT.
REMOVE AND REPLACE WORK THAT DOES NOT COMPLY WITH SPECIFIED
REQUIREMENTS.
ADDITIONAL INSPECTING, AT CONTRACTOR'S EXPENSE, WILL BE PERFORMED TO
DETERMINE COMPLIANCE OF CORRECTED WORK WITH SPECIFIED
REQUIREMENTS.
PROTECTION
REPAIR PAINTING: WIRE BRUSH AND CLEAN RUST SPOTS, WELDS, AND ABRADED
AREAS ON BOTH SURFACES OF PRIME- PAINTED DECK IMMEDIATELY AFTER
INSTALLATION, AND APPLY REPAIR PAINT.
07 00 00 THERMAL & MOISTURE PROTECTION
GENERAL:
ALL PERTINENT REQUIREMENTS OF THE INSTRUCTIONS FOR BIDDERS, THE GENERAL
CONDITIONS, SUPPLEMENTARY GENERAL CONDITIONS, AND FINISH SCHEDULE SHALL FORM
PART OF THESE SPECIFICATIONS.
PROVIDE ALL ITEMS, ARTICLES, MATERIALS, OPERATIONS OR METHODS LISTED, MENTIONED OR
SCHEDULED ON DRAWINGS AND/OR HEREIN SPECIFIED, INCLUDING ALL LABOR, MATERIALS,
EQUIPMENT AND INCIDENTALS, NECESSARY AND REQUIRED FOR THEIR COMPLETION.
07 01 00 GRADE VAPOR BARRIER
GENERAL: WHERE SHOWN ON DRAWINGS PROVIDE/ FURNISH UNDERSLAB VAPOR RETARDER.
INSTALLATION SHALL INCLUDE ALL PARTS, PIECES, COMPONENTS, ETC. FOR A COMPLETE
INSTALLATION.
REFERENCE STANDARDS:
ASTM D1709 STANDARD TEST METHODS FOR IMPACT RESISTANCE OF PLASTIC FILM BY THE
FREE-FALLING DART METHOD.
ASTM E96 STANDARD TEST METHODS FOR WATER VAPOR TRANSMISSION OF MATERIALS.
ASTM E154 STANDARD TEST METHODS FOR WATER VAPOR RETARDERS USED IN CONTACT
WITH EARTH UNDER CONCRETE SLABS, ON WALLS OR AS GROUND COVER.
ASTM E1643 STANDARD PRACTICE FOR INSTALLATION OF WATER VAPOR RETARDERS USED IN
CONTACT WITH EARTH OR GRANULAR FILL UNDER CONCRETE SLABS.
ASTM E1745 STANDARD SPECIFICATION FOR WATER VAPOR RETARDERS USED IN CONTACT
WITH SOIL OR GRANULAR FILL UNDER CONCRETE SLABS.
PRODUCTS:
PROVIDE .010" (10 MIL) POLYETHYLENE FILM VAPOR BARRIER or RETARDER UNDER ALL INTERIOR CONCRETE SLABS. LAP ALL JOINTS 6" AND TURN UP AT WALLS. ALL TEARS AND PENETRATIONS SHALL BE REPAIRED OR REPLACED BEFORE APPLICATION OF TOPPING. MATERIAL WEIGHT SHALL
BE 49 LBS/ 3,000 S.F., CLASS A WITH THE FOLLOWING TESTS:
TENSILE STRENGTH: ASTM E154, 52 LBS PER INCH, NEW MATERIAL.
ASTEM E154, 53 LBS PER INCH, AFTER SOAKING.
PUNCTURE RESISTANCE: ASTM D1709, >1,500 GRAMS.
PERMEANCE: ASTM E96, E154, 0.090 U.S. PERMS, NEW MATERIAL.
ACCESSORIES: SEAMING TAPE: VAPORBOND TAPE, 4” TAPE APPROVED BY VAPOR RETARDER
MANUFACTURER. PIPE BOOT KITS: VAPORBOOT SYSTEM OR OTHER APPROVED
MANUFACTURER’S SUPPLIED PIPE BOOT SYSTEM. BUTYL SEALANT 2-SIDED TAPE. MULTI-PIPE
PENETRATION SEALANT.
MANUFACTURER’S INSTRUCTIONS: COMPLY WITH MANUFACTURER’S PRODUCT DATA,
INCLUDING PRODUCT TECHNICAL BULLETINS, PRODUCT CATALOG INSTALLATION INSTRUCTIONS
AND PRODUCT CARTON/LABEL INSTRUCTIONS FOR INSTALLATION. REFERENCE SPEC-DATA
SECTION 5, INSTALLATION. VERIFY THAT SUBSTRATE CONDITIONS ARE ACCEPTABLE FOR
PRODUCT INSTALLATION IN ACCORDANCE WITH MANUFACTURER’S INSTRUCTIONS. INSTALL IN
ACCORDANCE WITH ASTM E1643.
07 84 43 JOINT FIRESTOPPING:
PROVIDE JOINT FIRESTOPPING WHERE INDICATED ON THE DRAWINGS, OR AS SPECIFIED HEREIN
AS REQUIRED TO ELIMINATE THE PASSAGE OF SMOKE AND OTHER GASES AND TO MAINTAIN
FIRE-RESISTANCE RATING OF ASSEMBLIES, IN OR BETWEEN AREAS.
PRODUCT SCHEDULE: FOR EACH JOINT FIRESTOPPING SYSTEM. INCLUDE LOCATION,
ILLUSTRATION OF FIRESTOPPING SYSTEM, AND DESIGN DESIGNATION OF QUALIFIED TESTING
AGENCY. WHERE PROJECT CONDITIONS REQUIRE MODIFICATION TO A QUALIFIED TESTING
AGENCY'S ILLUSTRATION FOR A PARTICULAR JOINT FIRESTOPPING SYSTEM CONDITION, SUBMIT
ILLUSTRATION, WITH MODIFICATIONS MARKED, APPROVED BY JOINT FIRESTOPPING SYSTEM
MANUFACTURER'S FIRE-PROTECTION ENGINEER AS AN ENGINEERING JUDGMENT OR EQUIVALENT
FIRE-RESISTANCE-RATED ASSEMBLY.
PRODUCTS:
JOINT FIRESTOPPING SYSTEMS: SYSTEMS THAT RESIST SPREAD OF FIRE, PASSAGE OF SMOKE
AND OTHER GASES, AND MAINTAIN ORIGINAL FIRE-RESISTANCE RATING OF ASSEMBLIES IN OR BETWEEN WHICH JOINT FIRESTOPPING SYSTEMS ARE INSTALLED. JOINT FIRESTOPPING SYSTEMS SHALL ACCOMMODATE BUILDING MOVEMENTS WITHOUT IMPAIRING THEIR ABILITY TO RESIST THE
PASSAGE OF FIRE AND HOT GASES.
JOINTS IN OR BETWEEN FIRE-RESISTANCE-RATED CONSTRUCTION: PROVIDE JOINT
FIRESTOPPING SYSTEMS WITH RATINGS DETERMINED PER ASTM E 1966 OR UL 2079.
MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE
MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE
WORK INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
3M FIRE PROTECTION PRODUCTS.
NELSON FIRESTOP; A BRAND OF EMERSON INDUSTRIAL AUTOMATION.
THERMAFIBER, INC.; AN OWENS CORNING COMPANY.
TREMCO, INC.
FIRE-RESISTANCE RATING: EQUAL TO OR EXCEEDING THE FIRE-RESISTANCE RATING OF
THE WALL, FLOOR, OR ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
JOINTS AT EXTERIOR/ INTERIOR WALL/FLOOR INTERSECTIONS: PROVIDE JOINT FIRESTOPPING
SYSTEMS WITH RATING DETERMINED PER ASTM E 2307.
MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE
MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE WORK
INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
3M FIRE PROTECTION PRODUCTS.
NELSON FIRESTOP; A BRAND OF EMERSON INDUSTRIAL AUTOMATION.
THERMAFIBER, INC.; AN OWENS CORNING COMPANY.
TREMCO, INC.
F-RATING: EQUAL TO OR EXCEEDING THE FIRE-RESISTANCE RATING OF THE FLOOR
ASSEMBLY.
JOINTS IN SMOKE BARRIERS: PROVIDE FIRE-RESISTIVE JOINT SYSTEMS WITH RATINGS
DETERMINED PER UL 2079 BASED ON TESTING AT A POSITIVE PRESSURE DIFFERENTIAL OF
0.30-INCH WG.
MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, AVAILABLE
MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE WORK
INCLUDE, BUT ARE NOT LIMITED TO THE FOLLOWING:
3M FIRE PROTECTION PRODUCTS.
NELSON FIRESTOP; A BRAND OF EMERSON INDUSTRIAL AUTOMATION.
THERMAFIBER, INC.; AN OWENS CORNING COMPANY.
TREMCO, INC.
L-RATING: NOT EXCEEDING 5.0 CFM/FT. OF JOINT AT BOTH AMBIENT AND ELEVATED
TEMPERATURES.
EXPOSED JOINT FIRESTOPPING SYSTEMS: FLAME-SPREAD AND SMOKE-DEVELOPED
INDEXES OF LESS THAN 25 AND 450, RESPECTIVELY, AS DETERMINED PER
ASTM E 84.
ACCESSORIES: PROVIDE COMPONENTS OF FIRE-RESISTIVE JOINT SYSTEMS, INCLUDING
PRIMERS AND FORMING MATERIALS THAT ARE NEEDED TO INSTALL ELASTOMERIC
FILL MATERIALS AND TO MAINTAIN RATINGS REQUIRED. USE ONLY COMPONENTS
SPECIFIED BY JOINT FIRESTOPPING SYSTEM MANUFACTURER AND APPROVED BY
THE QUALIFIED TESTING AGENCY FOR CONDITIONS INDICATED.
INSTALLATION: EXAMINE SUBSTRATES AND CONDITIONS, WITH INSTALLER PRESENT, FOR
COMPLIANCE WITH REQUIREMENTS FOR JOINT CONFIGURATIONS, SUBSTRATES, AND OTHER
CONDITIONS AFFECTING PERFORMANCE OF THE WORK. INSTALL FIRE-RESISTIVE JOINT SYSTEMS
TO COMPLY WITH MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS AND PUBLISHED
DRAWINGS FOR PRODUCTS AND APPLICATIONS INDICATED. INSTALL FORMING MATERIALS AND
OTHER ACCESSORIES OF TYPES REQUIRED TO SUPPORT ELASTOMERIC FILL MATERIALS DURING
THEIR APPLICATION AND IN POSITION NEEDED TO PRODUCE CROSS-SECTIONAL SHAPES AND
DEPTHS REQUIRED TO ACHIEVE FIRE RATINGS INDICATED.
AFTER INSTALLING ELASTOMERIC FILL MATERIALS AND ALLOWING THEM TO FULLY CURE,
REMOVE COMBUSTIBLE FORMING MATERIALS AND OTHER ACCESSORIES NOT INDICATED
AS PERMANENT COMPONENTS OF FIRE-RESISTIVE JOINT SYSTEM.
INSTALL ELASTOMERIC FILL MATERIALS FOR FIRE-RESISTIVE JOINT SYSTEMS BY PROVEN
TECHNIQUES TO PRODUCE THE FOLLOWING RESULTS:
ELASTOMERIC FILL VOIDS AND CAVITIES FORMED BY JOINTS AND FORMING MATERIALS
AS REQUIRED TO ACHIEVE FIRE-RESISTANCE RATINGS INDICATED.
APPLY ELASTOMERIC FILL MATERIALS SO THEY CONTACT AND ADHERE TO SUBSTRATES
FORMED BY JOINTS.
FOR ELASTOMERIC FILL MATERIALS THAT WILL REMAIN EXPOSED AFTER COMPLETING THE
WORK, FINISH TO PRODUCE SMOOTH, AND UNIFORM SURFACES THAT ARE FLUSH
WITH ADJOINING FINISHES.
INSTALLER SHALL BE QUALIFIED THAT PARTICIPATES IN AISC QUALITY CERTIFICATION PROGRAM
AND IS AN AISC CERTIFIED ERECTOR, CATEGORY CSE OR CAN PROVIDE A WRITTEN QUALITY
CONTROL PROGRAM CERTIFIED BY AN INDEPENDENT TESTING AGENCY.
05 10 00 STRUCTURAL AND MISCELLANEOUS STEEL:
FURNISH AND INSTALL ALL TUBE TRUSSES, BEAMS, COLUMNS, BEARING PLATES, FRAMES,
RAMP RAILINGS, ETC. FURNISH ANCHOR BOLTS, LOOSE LINTELS AND OTHER INCIDENTAL ITEMS
TO APPROPRIATE TRADE FOR INSTALLATION.
STRUCTURAL STEEL (W-SHAPES) MATERIALS SHALL CONFORM TO ASTM A 992/ A 992M GRADE
50 STEEL.
MISCELLANEOUS STEEL (CHANNELS, ANGLES, M & S SHAPES, PLATES, THREADED RODS, ETC.)
SHALL BE CONFORMING TO ASTM A-36 / A-36M STEEL.
MISCELLANEOUS STEEL (PIPES) SHALL BE CONFORMING TO ASTM A-53/ A-53M, TYPE E or TYPE
S, GRADE B STEEL. GALVANIZED, POWDER-COATED OR PAINTED FINISH.
WELDING ELECTRODES SHALL COMPLY WITH AWS REQUIREMENTS.
BOLTS CONNECTORS & ANCHORS:
HIGH STRENGTH BOLTS NUTS AND WASHERS SHALL COMPLY W/ ASTM A 325, TYPE 1 HEAVY
HEX STEEL STRUCTURAL BOLTS, ASTM A 563, CLASS 8S, GRADE C HEAVY HEX CARBON STEEL
NUTS AND ASTM F 436 TYPE 1 HARDEND CARBON STEEL WASHERS, ALL W/ PLAIN FINISH.
DIRECT TENSION INDICATORS ASTM F 959, TYPE 325.
ZINC COATED HIGH STRENGTH BOLTS NUTS AND WASHERS SHALL COMPLY W/ ASTM A 325,
TYPE 1 HEAVY HEX STEEL STRUCTURAL BOLTS, ASTM A 563 GRADE, CLASS 10S DH HEAVY HEX
CARBON STEEL NUTS AND ASTM F 436 TYPE 1 HARDEND CARBON STEEL WASHERS, ALL W/
PLAIN FINISH. DIRECT TENSION INDICATORS ASTM F 959, TYPE 490, HOT DIP GALVANIZED.
SHEAR CONNECTORS: ASTM A 108, GRADES 1015 THROUGH 1020, HEADED-STUD TYPE,
COLD-FINISHED CARBON STEEL; AWS D1.1/D1.1M, TYPE B.
HEADED AND UNHEADED ANCHOR RODS ASTM F 1554, GRADE 36 WELDABLE, STRAIGHT OR
BENT/ HOOKED W/ MECHANICALLY DEPOSITED ZINC COATING, ASTM B 695, CLASS 50 FINISH.
THREADED RODS SHALL COMPLY W/ ASTM A 36/ A 36M, W/ PLAIN FINISH.
PRIMER & GROUT:
ALL STEEL, EXCEPT FIELD WELDS SHALL HAVE ONE (1) COAT OF LEAD AND CHROMATE FREE,
NON-ASPHALTIC, RUST INHIBITING PRIMER. COMPLYING WITH MPI#18, MPI#19 OR SSPC-PAINT 20, APPLIED AT THE SHOP. ALL FIELD WELDS SHALL BE PAINTED WITH LIKE MATERIAL IN FIELD.
PRIMER EQUAL TO SSPC-PAINT 25 TYPE II ZINC OXIDE, ALKYD, LINSEED OIL PRIMER.
NON-METALLIC GROUT SHALL BE SHRINK RESISTANT COMPLYING W/ ASTM C 1107/ C 1107M,
FACTORY PACKAGED NONMETALLIC AGGREGATE GROUT. NON-METALLIC GROUT SHALL BE
SHRINK RESISTANT COMPLYING W/ ASTM C 1107/ C 1107M, FACTORY PACKAGED NON-
METALLIC AGGREGATE GROUT, NONCORROSIVE AND NONSTAINING, MIXED WITH WATER TO
CONCICTENCY SUITABLE FOR APPLICATION AND A 30 MINUTE WORKING TIME.
FABRICATION: FABRICATE AND ASSEMBLE STRUCTURAL STEEL IN SHOP TO GREATEST EXTENT
POSSIBLE. FABRICATE ACCORDING TO AISC'S "CODE OF STANDARD PRACTICE FOR STEEL
BUILDINGS AND BRIDGES" AND AISC 360.
CAMBER STRUCTURAL-STEEL MEMBERS WHERE INDICATED.
FABRICATE BEAMS WITH ROLLING CAMBER UP.
IDENTIFY HIGH-STRENGTH STRUCTURAL STEEL ACCORDING TO ASTM A 6/A
6M AND MAINTAIN MARKINGS UNTIL STRUCTURAL STEEL HAS BEEN
ERECTED.
MARK AND MATCH-MARK MATERIALS FOR FIELD ASSEMBLY.
COMPLETE STRUCTURAL-STEEL ASSEMBLIES, INCLUDING WELDING…