About this file
The document provided is a set of technical drawings and a description of a state and local contract opportunity for a new biomass boiler system at the Cypress Branch State Park in Millington, Maryland. The contract involves the installation of a 50,000 BTU/hr pellet boiler system, including a 119-gallon thermal storage tank, hydronic unit heaters, and associated piping and controls, to heat two specific zones (Zones 4 and 5) of the existing shop building. The project is being managed by the Maryland Department of Natural Resources and the Department of General Services, with an anticipated start date in early 2023.
The contract opportunity does not provide specific pricing terms, set-asides, or incumbent information. However, it does indicate that the project is funded by the State of Maryland and will require the selected contractor to provide all necessary labor, equipment, materials, and insurance to properly install the specified biomass boiler system at the Cypress Branch State Park location.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
State of Maryland
DEPARTMENT OF NATURAL RESOURCES
Engineering & Construction
CS
SITE
FOR THE
STATE OF MARYLAND
DEPARTMENT OF NATURAL RESOURCES
ENGINEERING AND CONSTRUCTION
TAWES STATE OFFICE BUILDING D-3
580 TAYLOR AVENUE
ANNAPOLIS, MARYLAND 21401-2351
NEW BIOMASS BOILER SYSTEM
10803 GALENA ROAD,
MILLINGTON, MD 216151
39°26'94.44"W 75°83'36.03"W
DEPARTMENT OF NATURAL RESOURCES
JEANNIE HADDAWAY-RICCIO, SECRETARY
DEPARTMENT OF GENERAL SERVICES
ELLINGTON E. CHURCHILL, JR., SECRETARY
STATE OF MARYLAND, BOARD OF PUBLIC WORKS
LARRY HOGAN, GOVERNOR
PETER FRANCHOT, COMPTROLLER
DERECK E. DAVIS, TREASURER
LIST OF DRAWINGS
SHEET DESCRIPTION
CS COVER SHEET
A.1 EXISTING SHOP LAYOUT
A.2 PROPOSED SYSTEM LAYOUT
A.3 PROPOSED HYDRONIC SCHEMATIC
CYPRESS BRANCH STATE PARK
SITE
AutoCAD SHX Text MD Dept. of Natural ResourcesMD Dept. of Natural Resources
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text
CYPRESS BRANCH NRMA 10803 GALENA ROAD, MILLINGTON, MD. 21651
AutoCAD SHX Text
PROPOSED PELLET BOILER SYSTEM
AutoCAD SHX Text 1/12/2022
AutoCAD SHX Text
EC23-09514-01
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text The ADC map image was provided by Kappa Map Group, 6198 Butler Pike, Blue Bell, PA 19422. All rights reserved. This publication may not be reproduced, in whole or in part, in any form or by any means, without written permission of the copyright owner.
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text
LOCATION MAP
AutoCAD SHX Text
SCALE: N.T.S.
AutoCAD SHX Text B.D.
AutoCAD SHX Text B.D.
AutoCAD SHX Text Date
AutoCAD SHX Text Date
AutoCAD SHX Text
PREPARED BY
AutoCAD SHX Text Using Agency
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Project Coor.
AutoCAD SHX Text Date
AutoCAD SHX Text Eng. & Con.
AutoCAD SHX Text
DEPARTMENT OF NATURAL RESOURCES
AutoCAD SHX Text
STATE OF MARYLAND
AutoCAD SHX Text
ENGINEERING & CONSTRUCTION
AutoCAD SHX Text Engineering & Construction Director
AutoCAD SHX Text
DEPARTMENT OF GENERAL SERVICES
AutoCAD SHX Text Chief, Engineering & Design
AutoCAD SHX Text Project Manager
AutoCAD SHX Text
APPROVAL
30,000
BTU LPG
FURNACE
ZONE 1
30,000
BTU LPG
FURNACE
ZONE 2
500 LPG FUEL TANK
20'-3"
20'
51'-2
17'-5"
33'-1
142'
ZONE 1
OFFICE
SPACE
ZONE 2
CONFERENCE
SPACE
ZONE 3
UNHEATED
EQUIP.
STORAGE
ZONE 4
SHOP WORK
SPACE
#1
ZONE 5
SHOP WORK
SPACE
#2
State of Maryland
DEPARTMENT OF NATURAL RESOURCES
Engineering & Construction
A.1
CYPRESS BRANCH SHOP
SCALE: N.T.S.
A
ZONE #1 AND ZONE #2 ARE CURRENTLY BEING HEATED USING PROPANE FURNACES THAT WERE INSTALLED IN SPRING OF 2022.
THE DESIRE IS TO HAVE ZONE #4 AND ZONE #5 HEATED USING A PELLET STOVE SYSTEM.
AutoCAD SHX Text MD Dept. of Natural ResourcesMD Dept. of Natural Resources
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text
CYPRESS BRANCH NRMA 10803 GALENA ROAD, MILLINGTON, MD. 21651
AutoCAD SHX Text
EXISTING SHOP LAYOUT
AutoCAD SHX Text 1/12/2022
EC23-09514-01
ZONE 4 ZONE 5
State of Maryland
DEPARTMENT OF NATURAL RESOURCES
Engineering & Construction
A.2
SHOP ZONE 4 & 5
SCALE: N.T.S.
A
AutoCAD SHX Text
HYDRONIC UNIT HEATER
AutoCAD SHX Text
HYDRONIC UNIT HEATER
AutoCAD SHX Text
5 TON OUTDOOR PELLET STORAGE SILO LOCATION
AutoCAD SHX Text
VENT STACK
AutoCAD SHX Text
119 GAL. THERMAL STORAGE TANK
AutoCAD SHX Text
HYDRONIC UNIT HEATER
AutoCAD SHX Text
VACUUM LINE FOR AUTOMATIC PELLET CONVEYANCE
AutoCAD SHX Text
50,000 BTU/HR PELLET BOILER
AutoCAD SHX Text MD Dept. of Natural ResourcesMD Dept. of Natural Resources
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text
CYPRESS BRANCH NRMA 10803 GALENA ROAD, MILLINGTON, MD. 21651
AutoCAD SHX Text 1/12/2022
AutoCAD SHX Text
EC23-09514-01
PROPOSED SYSTEM LAYOUT
State of Maryland
DEPARTMENT OF NATURAL RESOURCES
Engineering & Construction
A.3
PELLET BOILER HYDRONIC SCHEMATIC
SCALE: N.T.S.
A
AutoCAD SHX Text Notes: 1. System is shown as using a System is shown as using a non-ASME boiler with a vent tank. If an ASME boiler is selected, the schematic will be different because the vent tank and heat exchanger will not be needed. 2. This drawing is a conceptual This drawing is a conceptual layout for the purposes of showing biomass system options. 3. Final design and layout will change Final design and layout will change based on equipment selected, designer, and site conditions. 4. Not all hydronic components Not all hydronic components required for system are shown.
AutoCAD SHX Text
VFD
AutoCAD SHX Text T
AutoCAD SHX Text Variable Frequency Drive
AutoCAD SHX Text Temperature Transmitter
AutoCAD SHX Text Pump
AutoCAD SHX Text Three Way Mixing Valve
AutoCAD SHX Text Legend
AutoCAD SHX Text Boiler Protection Valve to ensure return water temperature > 140°F
AutoCAD SHX Text 119 Gallon Thermal Storage Tank
AutoCAD SHX Text T1
AutoCAD SHX Text V1
AutoCAD SHX Text T3
AutoCAD SHX Text P3
AutoCAD SHX Text
VFD
AutoCAD SHX Text Heat Exchanger separating open boiler system from pressurized distribution system
AutoCAD SHX Text 50,000 Btu/hr Pellet Boiler
AutoCAD SHX Text P1
AutoCAD SHX Text Vent Tank
AutoCAD SHX Text Elevation 4ft above highest point in open loop
AutoCAD SHX Text Vent
AutoCAD SHX Text To Drain
AutoCAD SHX Text P2
AutoCAD SHX Text
VFD
AutoCAD SHX Text Control Valve
AutoCAD SHX Text Zone 4
AutoCAD SHX Text Sequence of Operations: 1. The pellet boiler will supply hot water to the The pellet boiler will supply hot water to the thermal storage tank at 160°F. T1 controls V1 whichallows supply water from the boiler to bypass the thermal storage in order to maintain a return water temperature of at least 140°F to preventflue gas condensation. This is mainly a concern during boiler startup and at times of heavy load. 2. When the boiler is operating, P3 supplies hot water When the boiler is operating, P3 supplies hot water to Zones 4 & 5. P3 operates on a proportional differential pressure control scheme. 3. The temperature of water delivered to the Zones The temperature of water delivered to the Zones 4 & 5 is controlled by varying the speed of P2 in order to maintain the temperature setpoint at T3. It is recommended to design the radiator system to utilize water temperatures of 120°F or lower in order to optimze the performance of the thermal storage and ensure that the system can be easily adapted to other low carbon technologies in the future. 4. Zone valves at each heat emitter are controlled Zone valves at each heat emitter are controlled by thermostats. A minimum flow bypass should be provided at the end of the loop for the case where no thermostats are calling for heat.
AutoCAD SHX Text T2
AutoCAD SHX Text Hydronic Unit Heater
AutoCAD SHX Text Zone 5
AutoCAD SHX Text Hydronic Unit Heater
AutoCAD SHX Text Hydronic Unit Heater
AutoCAD SHX Text Bypass
AutoCAD SHX Text MD Dept. of Natural ResourcesMD Dept. of Natural Resources
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text No.
AutoCAD SHX Text Project Number:
AutoCAD SHX Text Drawing Number:
AutoCAD SHX Text
CYPRESS BRANCH NRMA 10803 GALENA ROAD, MILLINGTON, MD. 21651
AutoCAD SHX Text 1/12/2022
AutoCAD SHX Text
EC23-09514-01
PROPOSED HYDRONIC SCHEMATIC
| Sheets and Views |
| ShopOffice Layout-CS |
| ShopOffice Layout-Layout1 |
| ShopOffice Layout-Layout1 (2) |
| ShopOffice Layout-Layout1 (3) |
File details come from the government source that posted it. Updated .