This is a mechanical design drawing and specification document for the replacement of reverse osmosis (RO) water systems at ICVA Health Care System. The document includes equipment schedules, pump specifications, and plumbing details for a water treatment system.
The RO system (AMERIWATER 00HCRO-3X402) is specified to produce 300 gallons per hour of purified water with circulation up to 70 gallons per minute, exceeding the existing equipment demand of 180 gallons per hour with maximum instantaneous usage of 32 gallons per minute. The system requires 208-3-60 electrical service at 15 amperes and operates with a feed temperature of 77°F and feed pressure between 20 and 50 PSI. The RO package includes two circulation pumps (P-1 and P-2, GRUNDFOS CRI 15-2 model) piped in parallel to provide redundancy, each rated at 70 gallons per minute and 5 horsepower with 277/480-3-60 volt service. Supporting equipment includes a deionizer, storage tank, alarm panel, UV filter, endotoxin filter, blending valve, carbon filter, and water softener, all specified with AMERIWATER or equivalent manufacturer models. The contractor is required to provide full structural support for pumps using steel supports anchored to the floor, with connections to Schedule 80 PVC distribution piping and a test port with stainless steel ball valve and chemically injected ozone introduction port at user level. These record documents dated February 1, 2024, represent 100 percent construction documents prepared by Fourfront Design, Inc., for the Office of Construction and Facilities Management.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Wage Determination.pdf | ||
| M-002 RO SYSTEMS ONE LINE FLOW DIAGRAMS.pdf | ||
| M-110 BASEMENT NEW RO PLAN AREA B.pdf | ||
| 36C26326Q0881.pdf | ||
| VA NOTICE OF LIMITATIONS ON SUBCONTRACTING.docx | DOCX document | |
| M-120 NEW RO DISTRIBUTION ISOMETRIC VIEW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
1. P-1 AND P-2 TO BE PIPED IN PARALLEL TO KEEP ONE PUMP IN RESERVE FOR REDUNDANCY.
2. P-1 AND P-2 TO BE INCLUDED IN RO-1 PACKAGE.
3. CONTRACTOR TO FULLY SUPPORT PUMPS WITH STEEL TO FLOOR SUPPORT AND PROPER
SUSPENSION. NO PUMP WEIGHT ALLOWED ON PLASTIC PIPING OR FITTINGS.
2" ROS2" ROS
CHECK
VALVE (TYP)
BALL VALVE
(TYP)
PIPE UNION ON
VALVES (TYP)
PRESSURE
GAUGE
P
P
R/O SYSTEM SCHEDULE
ITEM
NO.
NOTES:
LOCATION
ELECTRICAL
VOLT.-PH.-CY.
MANUFACTURER & MODELSERVICE NOTES
FUSE
RO
AMERIWATER 00HCRO-3X402120-1-60 - 1,4
1. PRODUCES 300 GPH OF RO WATER WITH CIRCULATION UP TO 70GPM. EXISTING EQUIPMENT DEMANDS 180GPH WITH MAX
INSTANTANEOUS USAGE OF 32GPM.
2. INCLUDES P-1, P-2 DISTRIBUTION PUMPS.
3. INCLUDES REMOTE INDICATOR TO BE LOCATED IN SPS SPACE, REFER TO ELECTRICAL.
4. REFER TO SPECIFICATION SECTION 22-67-19.16 FOR MATERIAL REQUIREMENTS.
77°F
FEED TEMP
20 PSI
MIN. FEED
PRESSURE
50 PSI
MAX. FEED
PRESSURE
EQUIPMENT
RO UNIT
(x1) DEDICATED
DEDICATED CIRCUIT
OR FUSED DISCONNECT
208-3-60 15A(x1) DISC.
ANTI-SCALANT TANK - - INCLUDED W/ RO UNIT
DEIONIZER 120-1-60 (x1) DEDICATED AMERIWATER 00HC-2003
STORAGE TANK AMERIWATER 00HC-0097
ALARM PANEL 120-1-60 (x1) DEDICATED AMERIWATER 00HC-0019- UV FILTER 120-1-60 (x1) DEDICATED AMERIWATER 001-014-0012-
ENDOTOXIN FILTER - - AMERIWATER 001-021-0006-
BLENDING VLAVE - - AMERIWATER 00HC-5001-
RO-1 R/O
FILTER
MECH
BW02
208-3-60 20A(x1) DISC. 2,4 3,4
CARBON FILTER 120-1-60 (x1) DEDICATED - - WATER SOFTENER 120-1-60 (x1) DEDICATED AMERIWATER FLECK 2850 SXT- -
AMERIWATER FLECK 2850 SXT
PUMP SCHEDULE
ITEM
NO.
NOTES:
LOCATION GPM SIZE MOTOR
HP VOLT.-PH.-CY.
MANUFACTURER & MODELSERVICE NOTES
FLA
P
P-1,2 RO CIRCULATION MECH BW02 GRUNDFOS CRI 15-270 277/480-3-60 6.8 1,2,352"
1. INCLUDED IN THE RO EQUIPMENT PACKAGE WITH STORAGE TANK CONTROL PANEL.
2. PROVIDE WITH CONNECTIONS FOR CONNECTION TO SCH80 PVC DISTRIBUTION PIPING.
3. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
FT HEAD
FLUID
RO H2O
SEE PLUMBING PLANS FOR RO
PIPING IN THE CEILING
CONNECTION TO RO
EQUIPMENT, MAKE AS
SHORT AS POSSIBLE
CONTRACTOR TO PROVIDE AND
INSTALL AMERIWATER OR EVOQUA
TEST PORT AT USER LEVEL.
STAINLESS STEEL SOV AND
CHEMWORLD CS2-316, OR EQUAL,
STAINLESS STEEL INJECTION
PORT FOR OZONE INTRODUCTION
TO STERILIZE RO DROP
PRESSURE GAUGE W/ SOV
Drawing Title
COR Project Engineer
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT 636A8-22-004
01 / 03 / 2023
Office of Construction and Facilities Management of
REPLACE RO SYSTEMS
RECORD DOCUMENTS
ICVA HEALTH CARE SYSTEM
FOURFRONT DESIGN, INC.
517 7TH STREET
RAPID CITY, SOUTH DAKOTA
57701
PH: (605) 342-9470
FAX: (605) 342-2377
WWW.FOURFRONTDESIGN.COMFOUR FRON T
D E S I G N I N C .
Phase
FULLY SPRINKLERED
15RD PM/JB
RECORD DOCUMENTS 02/01/2024
THESE RECORD DOCUMENTS CONFORMING TO THE
MARKED-UP PRINTS, DRAWINGS AND OTHER DATA
FURNISHED TO THE DESIGN PROFESSIONAL BY THE
CONTRACTOR. THIS SET OF RECORD DOCUMENTS WILL
SHOW THE REPORTED LOCATION OF THE WORK AND
SIGNIFICANT CHANGES MADE DURING THE
CONSTRUCTION PROCESS. THESE RECORD
DOCUMENTS ARE BASED ON THE INFORMATION
PROVIDED BY OTHER PARTIES WHICH WILL BE
ASSUMED RELIABLE. THE DESIGN PROFESSIONAL HAS
NOT VERIFIED THE ACCURACY AND/OR COMPLETENESS
OF THIS INFORMATION AND SHALL NOT BE
RESPONSIBLE FOR ANY ERRORS OR OMISSIONS WHICH
MAY BE INCORPORATED HEREIN AS A RESULT.
M-003
MECHANICAL SCHEDULES AND
DETAILS
MICHAEL WILCOX
100% CONSTRUCTION
DOCUMENTS
VERTICAL CIRCULATION PUMP SCHEMATIC
SCALE: NTS
M003
RO TEST PORT ISOMETRIC DETAIL
SCALE: NTS
M003
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text