Lighthouse Academy Hastings- BID PERMIT SET (25-0331).pdf
PDF 3 MB Posted
- Attached to
- Hastings Lighthouse Academy Construction
- Solicitation number
- RFP-LHA-250000001998-1
- Issued by
- Baraga County, Lansing City, Michigan
About this file
This document is a comprehensive set of architectural and engineering design drawings for a tenant improvement project for Lighthouse Academy, located at 400 W. State Street in Hastings, Michigan. The project involves renovating approximately 1,988 square feet of existing space on the second level, with work focused on creating educational spaces including classrooms, a corridor, entry hall, work room, and electrical room. The design is prepared by Create 3 Architecture and follows the Michigan Building Code 2021, Michigan Rehabilitation Code 2015, and other applicable state and local building standards. The project is classified as a Level 3 Alteration for an E (Education) occupancy group, specifically for a K-12 educational setting.
The drawings provide detailed specifications for architectural, mechanical, electrical, and plumbing systems, including floor plans, reflected ceiling plans, interior elevations, and technical schedules. The renovation includes new wall partitions, ceiling grids, lighting fixtures, HVAC diffusers, electrical receptacles, and fire safety elements. The project does not require automatic sprinkler systems, as the space is under 12,000 square feet. Existing building infrastructure such as electrical panels, elevators, and some plumbing fixtures will remain. The design emphasizes accessibility, with ADA-compliant mounting heights for switches, fixtures, and signage, and incorporates fire-rated construction elements to meet local building code requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Leasehold Buildout Request - Barry.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHT SWITCHTYPICAL HVAC CONTROLSTYPICAL FIRE EXT CABINETTYPICALRECEPTACLESTYPICAL
COUNTERTOP
FIRE ALARMA/V STROBE
ACCESIBLE TOILET ROOMSIGNAGE, MIN 6" x 6"
BOTTOM PORTION OF DOOR
TO BE FLUSH / SMOOTH
SIGNAGE BASIS OF DESIGN:ROCKWOOD MFG. BF SERIES ADA,METAL SIGNS (US32D) WITH
PICTOGRAM, RAISED LETTERS ANDBRAILLE TRANSLATION.
WHERE TACTILE EXIT SIGNS ARE
IDENTIFIED, LOCATE WITHIN THEAREA INDICATED. WHEREADJACENT SURFACE IS GLASS,
PROVIDE VERTICAL SIGN MOUNTEDON DOOR FRAME.
RATED JOINTPROTECTION SYSTEM TOMATCH WALL RATING
METALLIC / NONMETALLICMEMBRANE PENETRATION
FIRE RATED CONSTRUCTION-SEE PLAN FOR LOCATIONSTHROUGH PENETRATION
5/8" GYP BOARD EACH SIDE2x4" WOOD METAL STUDS
@ 16" O.C.
CEILING- SEE PLAN FOR TYPEAND HEIGHT
WALL BASE AS SCHEDULEDCONT. LT GA METAL TRACK-SECURE TO FLOOR
GYP BD TIGHT TO FLOORINTERIOR PARITITION
SIMILAR EXCEPT 2x6 WOOD STUDS
5/8" TYPE "X" GYP BOARDEACH SIDE2x4" WOOD METAL STUDS@ 16" O.C.
CEILING- SEE PLAN FOR TYPEAND HEIGHT
FIRE RATED JOINT SEALANT- 1HR
WALL BASE AS SCHEDULED
CONT. LT GA METAL TRACK-
SECURE TO FLOOR
3" FIBERGLASS SOUND ATTEN.INSULATION
GYP BD TIGHT TO FLOOR
INTERIOR RATED PARITITION1 HR PER UL U309SIMILAR EXCEPT 2x6 WOOD STUDS
EXIST PRE-ENGINEERED WOOD TRUSSES-
EXIST WOOD FLOORSHEATHING, MIN 23/32"
(2) LAYERS 5/8" TYPE "X" GYP BD
FLOOR / CEILING ASSEMBLY
3/4" CONCRETE FLOOR TOPPING,1800 PSI MIN- ADDED WITHUPPER LEVEL TENANT BUILDOUT
GLASS FIBER OR MINERAL WOOLINSULATION (OPTIONAL)
1 HR GA #FC 5408
OPTIONAL
EXIST STEEL COLUMN(2) LAYERS 5/8" TYPE "X" GYP BDAT 1-HOUR ENCLOSURE
1-5/8" LT GA METAL FRAMING- CUT1/2" SHORT OF TOP OF ENCLOSUREMETAL CORNER BEAD PERASSEMBLY DESCRIPTION
STEEL COLUMN PROTECTION1 HR UL X528
ENCLOSURE SIZE SHALL BE SUCHTHAT THE ENTIRE BASE PLATE IS
WITHIN THE INSIDE OF THE GYP BD
CEILING RADIATIONDAMPER- BY LANDLORD
DIFFUSER IN SUSPENDEDCEILING GRID
DUCT WITHIN JOIST CAVITYSEE FLOOR / CEILING ASSEMBLYDETAIL FOR CONSTRUCTION
DAMPER SUPPORT BRACKSET
SECURED TO TRUSSES
FLEX DUCT
FLOOR / CEILING RADIATION DAMPERBASED ON RUSKIN CFD(2) SERIES OR EQ. 1 HOUR ASSEMBLY
EXISTING
EXISTING
458 SF
458 SF
392 SF
Lighthouse Academy Tenant Improvement 400 W. State Street - Hastings, Michigan
PROJECT TEAM:
OWNER:
LIGHTHOUSE ACADEMY
3300 36th Street SE Grand Rapids, MI 49512
G1.1 COVER SHEET & GENERAL INFORMATION
G1.2 ACCESSIBLE MOUNTING HEIGHTS, RATED ASSEMBLIES
A1.1 FLOOR PLAN, DOOR SCHEDULE & DETAILS
A3.1 REFLECTED CEILING PLAN
A4.1 INTERIOR ELEVATIONS, FINISH PLAN, AND DETAILS
M1.1 MECHANICAL HVAC & PLUMBING PLANS AND SCHEDULES
E1.1 ELECTRICAL POWER & LIGHTING LAYOUTS
E1.2 EMERGENCY LIGHTING PHOTOMETRIC
SHEET INDEX:
CODE SUMMARY
EXISTING BUILDING - LEVEL 2 ALTERATION FOR TENANT IMPROVEMENT
CHAPTER 3 - USE & OCCUPANCY:
OCCUPANCY: E - EDUCATION (K-12), ALSO SUBJECT TO STATE RULES
CHAPTER 6 - TYPES OF CONSTRUCTION (MBC TABLE 602)
CONSTRUCTION TYPE : TYPE 5B / NFPA 220 TYPE V-000
PRIMARY STRUCTURAL FRAME : 0 HRS
BEARING WALLS
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
NONBEARING INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 0 HRS
ROOF CONSTRUCTION: 0 HRS
CHAPTER 9 - FIRE PROTECTION SYSTEMS
AUTOMATIC SPRINKLER SYSTEMS - THIS STRUCTURE IS NOT PROTECTED BY AN
AUTOMATIC SPRINKLER SYSTEM.
· FPSS IS NOT REQUIRED BY THE MBC, <12,000 SF
· FPSS IS ONLY REQUIRED IN EDUCATION SPACES >12,000 SF PER NFPA
FIRE ALARM AND DETECTION SYSTEMS IS REQUIRED IN THE AREA OF WORK AND
WILLL BE PROVIDED.
APPLICABLE BUILDING CODES:
MICHIGAN REHABILITATION CODE 2015 (MRHC), LEVEL 3 ALTERATION
NEW TENANT IMPROVEMENT
MICHIGAN BUILDING CODE 2021 (MBC)
MICHIGAN PLUMBING CODE 2021 (MPC)
MICHIGAN MECHANICAL CODE 2021 (MMC)
MICHIGAN ELECTRICAL CODE (MEC)
(BASED ON THE 2023 NATIONAL ELECTRICAL CODE)
MICHIGAN ENERGY CODE (IECC)
(BASED ON ASHRAE 90.1 - 2019 W/MODIFICATIONS)
MICHIGAN BARRIER FREE / 2010 ADA STANDARDS
SCHOOL FIRE AND LIFE SAFETY RULES 2016 INCLUDING
LFE SAFETY CODE, NFPA-101 2012 (SCHOOLS)
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
G1.1
BIDS & PERMIT 03/31/25
Cover Sheet, Code Data, General Notes
EXIT PATH
TRAVEL DIST TO COMMON PATH OF TRAVEL
EXIT
EGRESS LEGEND
OCCUPANT AREA FOR CALCULATION
EXIT DISCHARGE
B
USE GROUP
OCCUPANT LOAD
EXISTING SUITE
NO WORK PROPOSED IN THIS AREA
CHAPTER 10 - MEANS OF EGRESS
OCCUPANT LOAD
EXISTING SUITE NOT IN SCOPE OF WORK
EDUCATION 1,988 / 20 SF = 66 OCC*
*REFER TO EGRESS PLAN FOR OCC LOAD OF INDIVIDUAL SPACES
EXITS: (2) EXITS SHALL BE PROVIDED FROM SPACES WITH MORE THAN 49 OCCS
(1) EXIT SHALL BE PROVIDED FROM SPACES WITH LESS THAN 50
OCCUPANTS THAT ALSO MEET THE EGRESS TRAVEL DISTANCES IN SECTION
DEAD END CORRIDOR- 20 FT MAX, < 20' PROVIDED
COMMON PATH OF TRAVEL- 75 FT MAX, <75 FT PROVIDED
PANIC EXIT HARDWARE IS PROVIDED ON ALL DOORS SERVING SPACES WITH AN
OCCUPANT LOAD OF 50 OR MORE.
CORRIDORS ARE 1 HOUR RATED, FIRE BARRIERS.
CLASSROOM DOOR OPENINGS 3/4 HR - D-H-45
OTHER CORRIDOR OPENINGS 3/4 HR - D-H-45
PLUMBING FIXTURE CALCULATIONS
MINIMUM REQUIRED PLUMBING FIXTURES
SUITE A EXISTING TO REMAIN- NOT IN WORK SCOPE
EDUCATIONAL - 66 OCCS
M- (1) WC REQ'D @ 1/50
W- (1) WC REQ'D @ 1/50
(2) UNISEX TOILET ROOMS (1WC + 1LAV EA) PROVIDED
(1) SERVICE SINK REQ'D / (1) PROVIDED- EXISTING
(1) DRINKING FOUNTAIN REQ'D / (1) PROVIDED- EXISTING
BUILDING CODE SUMMARY
GENERAL CONDITIONS
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH
ALL FEDERAL, STATE AND LOCAL CODES AND
ORDINANCES IN EFFECT IN THE PROJECT AREA AS WELL
AS OTHER REQUIREMENTS OF THE LOCAL AUTHORITY
HAVING JURISDICTION.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE
COORDINATION OF ALL PARTS OF THE WORK SO THAT NO
WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE
CONDITION.
3. ALL WORK SHALL CONFORM TO INDUSTRY AND
MANUFACTURER'S PUBLISHED STANDARDS AND THE
BUILDING OWNER'S REQUIREMENTS FOR QUALITY OF
MATERIALS AND WORKMANSHIP AS WELL AS ALL
REQUIREMENTS IN THESE DRAWINGS.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING
THE BUILDING PERMIT FOR THE WORK SHOWN ON THESE
DRAWINGS. INDIVIDUAL SUBCONTRACTORS SHALL
SECURE PERMITS FOR THEIR PORTION OF THE WORK
UNLESS DIRECTED OTHERWISE BY THE CONTRACTOR.
5. DO NOT SCALE DRAWINGS. USE PROVIDED DIMENSIONS.
6. ALL DIMENSIONS ASSOCIATED TO EXISTING STRUCTURE
ARE TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO
ANY FABRICATION OR SHOP DRAWINGS.
7. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
SHALL VERIFY ALL NEW AND EXISTING CONDITIONS
SHOWN ON THE DRAWINGS. IF DISCREPANCIES EXIST IN
THE CONSTRUCTION DRAWINGS, CONTACT THE
ARCHITECT FOR CLARIFICATION BEFORE PROCEEDING.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR
AND HAVE CONTROL OVER THE SCHEDULING,
SEQUENCING, CONSTRUCTION MEANS AND METHODS
EMPLOYED IN THE EXECUTION OF THE WORK AND FOR
SAFETY ON THE PROJECT SITE.
9. COORDINATE PROPER STORAGE OF BUILDING MATERIALS
ON SITE WITH THE OWNER'S REPRESENTATIVE TO AVOID
DISRUPTION OF THE OWNER'S ACTIVITIES WITHIN THE
BUILDING AND TO MAINTAIN PROPER ACCESS TO ALL
REQUIRED MEANS OF EGRESS.
10. PROVIDE TEMPORARY, PORTABLE FIRE EXTINGUISHERS
AS REQUIRED BY THE BUILDING CODE, INTERNATIONAL
FIRE CODE OR LOCAL AUTHORITY HAVING JURISDICTION
OVER THE PROJECT.
11. PROTECT ALL AREAS AND NEW AND EXISTING MATERIALS
AND FINISHES FROM DAMAGE THAT MAY OCCUR FROM
CONSTRUCTION, DIRT, DUST, WATER, ETC. ANY DAMAGE
RESULTING FROM CONSTRUCTION OPERATIONS OR
IMPROPER PROTECTION SHALL BE REPAIRED OR
REPLACED AT THE CONTRACTOR'S EXPENSE.
12. THE CONTRACTOR SHALL PROVIDE APPROPRIATE MEANS
AND BARRIERS TO PROTECT THE PROJECT SITE AND THE
PUBLIC AS REQUIRED BY APPLICABLE LOCAL, STATE AND
NATIONAL CODES AND REGULATIONS.
13. PROTECT FIRE ALARM AND FIRE PROTECTION SPRINKLER
SYSTEMS FROM DAMAGE DURING CONSTRUCTION.
MAINTAIN SYSTEMS OPERATIONAL UNLESS REQUIRED
OTHERWISE BY NEW WORK. NOTIFY THE OWNER OF
TIMES WHEN FIRE PROTECTION SYSTEMS WILL NOT BE
ACTIVE.
14. THE CONTRACTOR SHALL COORDINATE ALL CUTTING AND
PATCHING IN EXISTING WALLS, FLOORS, CEILING, ROOFS,
ETC. WHERE REQUIRED BY NEW WORK. SECURE
APPROVAL OF THE OWNER PRIOR TO COMMENCE WORK.
EMPLOY THE OWNER'S CONTRACTORS WHERE NECESSARY
TO MAINTAIN THE INTEGRITY OF EXISTING WORK AND
TO MAINTAIN THE OWNER'S EXISTING WARRANTY
COVERAGE.
15. ALL WORK IN THIS PROJECT SHALL BE WARRANTED
AGAINST ANY DEFECT IN MATERIALS OR WORKMANSHIP
FOR A PERIOD OF ONE YEAR COMMENCING AT THE DATE
OF SUBSTANTIAL COMPLETION, UNLESS A LONGER
PERIOD IS SPECIFIED IN THE CONSTRUCTION
DOCUMENTS. ANY DEFECTIVE MATERIAL OR
WORKMANSHIP SHALL BE REPAIRED OR REPLACED AT NO
COST TO THE OWNER.
16. REMOVE ALL RUBBISH AND WASTE MATERIALS ON A
DAILY BASIS TO PREVENT THE ACCUMULATION OF DIRT
OR DEBRIS. PROVIDE FINAL CLEANING AT THE END OF
THE PROJECT.
17. THE CONSTRUCTION DOCUMENTS, DRAWINGS AND
SPECIFICATIONS ARE INSTRUMENTS OF SERVICE OF THE
ARCHITECT AND REMAIN THE PROPERTY OF THE
ARCHITECT AND SHALL NOT BE USED WITHOUT HIS
EXPRESSED CONSENT.
NORTH
Scale:
EGRESS PLAN
3/32" = 1'-0"
NORTH
Scale:
LOCATION PLAN
NONE
PROJECT LOCATION
BUILDING ENVELOPE
1. ALTERED ELEMENTS OF THE BUILDING ENVELOPE SHALL
COMPLY WITH THE REQUIREMENTS OF THE CURRENT
MICHIGAN ENERGY CODE, ASHRAE 90.1-2013,
NON-RESIDENTIAL, PRESCRIPTIVE METHOD. MINIMUM
R-VALUE / MAXIMUM U-VALUES FOR INDIVIDUAL
COMPONENTS ARE INDICATED BELOW.
2. BUILDING INSULATION SHALL BE:
ROOF ABOVE DECK (POLYISO, 2 LAYERS) R30
STUD WALLS (BATT WITH VAPOR BARRIER) R19
CMU, CELLS FILLED R12
SLAB EDGE (POLYISO, 2"x24") R10
3. FENESTRATION VALUES SHALL BE (MINIMUM):
STOREFRONT U-VALUE 0.29
STOREFRONT SHGC 0.39
STOREFRONT VLT 70%
OPAQUE DOOR U-VALUE 0.34
4. ALL FACTORY BUILT FENESTRATION SHALL BE LABELED OR
CERTIFIED AS MEETING AIR LEAKAGE, U-FACTOR, SHGC
AND VT REQUIREMENTS.
GLAZED DOORS 1.0 CFM/SF
STOREFRONT / CURTAINWALL 0.06 CFM/SF
SWINGING OPAQUE DOORS 0.2 CFM/SF
NON-SWINGING OPAQUE DOORS 0.4 CFM/SF
5. PROVIDE CONTINUOUS AIR BARRIER ON ALL EXTERIOR
WALLS AND BE WRAPPED, SEALED, CAULKED AND / OR
TAPED PER THE MANUFACTURER'S INSTRUCTIONS.
6. INSULATION IN CONTACT WITH THE GROUND SHALL BE
POLYISO, 40PSF, MAX 0.3% WATER ABSORPTION AND BE
INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
7. VAPOR BARRIER SHALL BE INSTALLED UNDER CONCRETE
SLAB ON GRADE, 10 MIL (MINIMUM) POLYETHYLENE
SHEETING. TAPE OR SEAL ALL JOINTS AND PENETRATIONS.
E
458 SF
EXIST ADA
TOILET RM
EXIST ADA
TOILET RM
EXIST
ELEV.
WATER METER ROOM
ELECT ROOM
E
458 SF
E
392 SF
EGRESS PLAN KEY NOTES
1. EXISTING OPERABLE WINDOW- 36" W x 54" H, SILL @ 38"
SFF, DOUBLE-HUNG, MEETS MIN 20"W x 24"H, 5.7 SF CLEAR
OPENING.
2. 1-HOUR FIRE BARRIER AT EXIT ACCESS CORRIDOR,
TERMINATING AT THE UNDERSIDE OF RATED
FLOOR/CEILING ASSEMBLY ABOVE.
3. EXIT ACCESS CORRIDOR OPENINGS TO HAVE MINIMUM 45
MINUTE (3/4 HOUR) RATING.SEE DOOR SCHEDULE FOR
ADDITIONAL REQUIREMENTS.
4. 1-HOUR FIRE BARRIER AT AREA SEPARATION.
5. AREA SEPARATION OPENINGS TO HAVE MINIMUM 45
MINUTE (1 HOUR) RATING. SEE DOOR SCHEDULE FOR
ADDITIONAL REQUIREMENTS.
6. EXISTING BUILDING EXIT DOOR EQUIPPED WITH PANIC
EXIT HARDWARE.
PROPOSED TENANT SPACE
1,988 SF
ARCHITECT:
CREATE 3 ARCHITECTURE
100 Cesar E. Chavez Ave Suite 200 Grand Rapids, MI 49503
DESIGN BUILD SYSTEMS
1. THE DESIGN OF MECHANICAL, PLUMBING AND ELECTRICAL
SYSTEMS NOT SHOWN IN THE CONSTRUCTION
DOCUMENTS SHALL BE PROVIDED BY THE TRADE
CONTRACTOR AS A DESIGN-BUILD.
2. THE SYSTEMS SHALL BE DESIGNED BY A REGISTERED
ENGINEER AS LICENSED IN THE STATE OF MICHIGAN.
SEALED DOCUMENTS, CALCULATIONS, SUBMITTALS, ETC.
SHALL BE PROVIDED TO THE ARCHITECT FOR REVIEW
PRIOR TO SUBMITTING TO THE AUTHORITIES HAVING
JURISDICTION. ANY AND ALL PLAN REVIEW COMMENTS
SHALL BE ADDRESSED AND RESUBMITTED AS REQUIRED.
3. THE SYSTEMS SHALL BE DESIGNED IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CURRENT BUILDING CODE AS
WELL AS ANY OTHER SPECIFIC TRADE CODE (MECHANICAL,
PLUMBING, ELECTRICAL, ETC.) IN EFFECT AT THE TIME OF
SUBMITTAL.
4. THE ARCHITECT IS NOT RESPONSIBLE FOR THE DESIGN,
ENGINEERING, TIMELINESS, COORDINATION,
COMPLETENESS OF DESIGN-BUILD SYSTEMS ENGINEERED
BY OTHERS.
LIGHT SWITCH
TYPICAL
MI
N
UN
OB
ST
RU
CT
ED
RE
AC
H
RA
NG
E
MA
X
8"
OP
ER
AB
LE
P
AR
TS
HVAC CONTROLS
TYPICAL
FIRE EXT CABINET
TYPICAL
RECEPTACLES
TYPICAL
3' -4
"M
AX
AB
OV
E
CO
UN
TE
R
1' -6
TY
PI
CA
L
COUNTERTOP
6' -8
FIRE ALARM
A/V STROBE
4' -0
ACCESIBLE TOILET ROOM
SIGNAGE, MIN 6" x 6"
18"
MAX
" L
OW
ES
T
LE
TT
ER
" M
AX
H
IG
HE
ST
LE
TT
ER
8"
HA
RD
W
AR
E
BOTTOM PORTION OF DOOR
TO BE FLUSH / SMOOTH
SIGNAGE BASIS OF DESIGN:
ROCKWOOD MFG. BF SERIES ADA,
METAL SIGNS (US32D) WITH
PICTOGRAM, RAISED LETTERS AND
BRAILLE TRANSLATION.
WHERE TACTILE EXIT SIGNS ARE
IDENTIFIED, LOCATE WITHIN THE
AREA INDICATED. WHERE
ADJACENT SURFACE IS GLASS,
PROVIDE VERTICAL SIGN MOUNTED
ON DOOR FRAME.
RATED JOINT
PROTECTION SYSTEM TO
MATCH WALL RATING
METALLIC / NONMETALLIC
PIPE THROUGH PENETRATION
FLOOR / CEILING ASSEMBLY-
SEE TYPES
2x TOP & BOTTOM PLATES
RATED JOINT
PROTECTION SYSTEM TO
MATCH WALL RATING
METALLIC / NONMETALLIC
MEMBRANE PENETRATION
FIRE RATED CONSTRUCTION-
SEE PLAN FOR LOCATIONS
THROUGH PENETRATION
5/8" GYP BOARD EACH SIDE
2x4" WOOD METAL STUDS @ 16" O.C.
CEILING- SEE PLAN FOR TYPE
AND HEIGHT
WALL BASE AS SCHEDULED
CONT. LT GA METAL TRACK-
SECURE TO FLOOR
GYP BD TIGHT TO FLOOR
INTERIOR PARITITION
W6 SIMILAR EXCEPT 2x6 WOOD STUDS
W4
5/8" TYPE "X" GYP BOARD
EACH SIDE
2x4" WOOD METAL STUDS @ 16" O.C.
CEILING- SEE PLAN FOR TYPE
AND HEIGHT
FIRE RATED JOINT SEALANT- 1HR
WALL BASE AS SCHEDULED
CONT. LT GA METAL TRACK-
SECURE TO FLOOR
3" FIBERGLASS SOUND ATTEN.
INSULATION
GYP BD TIGHT TO FLOOR
INTERIOR RATED PARITITION
1 HR PER UL U309
R6 SIMILAR EXCEPT 2x6 WOOD STUDS
R4
EXIST PRE-ENGINEERED WOOD TRUSSES-
EXIST WOOD FLOOR
SHEATHING, MIN 23/32"
(2) LAYERS 5/8" TYPE "X" GYP BD
FLOOR / CEILING ASSEMBLYFC1
3/4" CONCRETE FLOOR TOPPING,
1800 PSI MIN- ADDED WITH
UPPER LEVEL TENANT BUILDOUT
GLASS FIBER OR MINERAL WOOL
INSULATION (OPTIONAL)
1 HR GA #FC 5408
OPTIONAL
EXISTING
EXIST STEEL COLUMN
(2) LAYERS 5/8" TYPE "X" GYP BD
AT 1-HOUR ENCLOSURE
1-5/8" LT GA METAL FRAMING- CUT
1/2" SHORT OF TOP OF ENCLOSURE
METAL CORNER BEAD PER
ASSEMBLY DESCRIPTION
STEEL COLUMN PROTECTION
1 HR UL X528
ENCLOSURE SIZE SHALL BE SUCH
THAT THE ENTIRE BASE PLATE IS
WITHIN THE INSIDE OF THE GYP BD
EXISTING
CEILING RADIATION
DAMPER- BY LANDLORD
DIFFUSER IN SUSPENDED
CEILING GRID
DUCT WITHIN JOIST CAVITY
SEE FLOOR / CEILING ASSEMBLY
DETAIL FOR CONSTRUCTION
DAMPER SUPPORT BRACKSET
SECURED TO TRUSSES
FLEX DUCT
FLOOR / CEILING RADIATION DAMPER
BASED ON RUSKIN CFD(2) SERIES OR EQ. 1 HOUR ASSEMBLY
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L T
A N
T I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
G1.2
BIDS & PERMIT 03/31/25
Accessibility Details, Rated Assemblies
MOUNTING HEIGHTS- DEVICES & CONTROLS
NO SCALE
DOORS & SIGNAGE
NO SCALE
HORIZONTAL ASSEMBLY FIRE RATED JOINT PROTECTION
NO SCALE
PARTITION FIRE RATED JOINT PROTECTION
NO SCALE
PAINTED
HOLLOW METAL
SE
E
SC
HE
D
SEE
SCHED
2"
2"2"
HM1
SE
E
SC
HE
D
SEE
SCHED
FLUSH
SE
E
SC
HE
D
SEE
SCHED
F
SE
E
SC
HE
D
SEE
SCHED
HALF GLASS
G
NARROW LITE
N
SEE PLAN & PARTITION TYPES
FOR WALL ASSEMBLY
DOUBLE-RABBET, HOLLOW METAL
DOOR FRAME
WALL THICKNESS + 1/2"
SOLID CORE WOOD OR HOLLOW
METAL DOOR AS SCHEDULED
DOUBLE JAMB STUDS, FULL HEIGHT
6"
DIMENSION AT INSIDE CORNER U.N.O.
SEE PLAN & PARTITION TYPES
FOR WALL ASSEMBLY
DOUBLE-RABBET, HOLLOW METAL
DOOR FRAME
WALL THICKNESS + 1/2"
SOLID CORE WOOD OR HOLLOW
METAL DOOR AS SCHEDULED*
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
NORTH
Scale:
FLOOR PLAN
1/4" = 1'-0"
A1.1
BID & PERMIT 03/31/25
LA
ST
P
RI
NT
ED
B Y:
JI
M
O N
3/ 4/
:3
PM
CR
EA
TE
3-
FI
LE
SV
R\
PR
OJ
EC
TS
\2
5-
LI
GH
TH
OU
SE
A
CA
DE
M Y-
H
AS
TI
NG
S\
_W
OR
KI
NG
D
RA
W
IN
GS
\S
HE
ET
S
- T
I\ A1
.X .D
W G
Floor Plan Door Schedule & Details
18'-6 3/8" 24'-3 1/2" 6'-4 3/8"±
15'-2 3/8" 9'-4"
20'-6 7/8" 4'-1"
'-3
/8
'-8
/8
3'-4" 6'-0"
5' -5
'-5
4' -7
/8
'-8
6' -0
CL
EA
R
1' -8
ENTRY HALL
TOILET ROOM
EXIST
TOILET ROOM
EXIST
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
ETR ETR
110A
114 115
R4
R4
7'-9 3/8"±
'-8
5'
-0
ELEVATOR
EXIST
DOOR SCHEDULE
MARK LOCATION SIZE MATL TYPE MATL TYPE
DOOR FRAME HARDWARE
HI
NG
ES
FU
NC
TI
ON
CL
OS
ER
ST
OP
RA
TI
NG
(M
IN
REMARKS
110A MAIN ENTRY 3'-0" x 7'-0" WD G HM HM1 A-P E C W 45
PARTITION NOTES
GENERAL
1. ALL DIMENSIONS ARE TO THE FINISHED FACE OF GYPSUM
BOARD AND / OR COLUMN LINES UNLESS NOTED
OTHERWISE.
2. WALL TYPES DO NOT INCLUDE FINISHES. REFER TO
ROOM FINISH SCHEDULE AND ELEVATIONS FOR FINISH
INFORMATION.
3. ALL FIRE AND SOUND RATED WALLS SHALL BE
CONSTRUCTED IN ACCORDANCE WITH THE TESTING
AGENCY DESIGN REPORT WHICH MAY INCLUDE
ADDITIONAL REQUIREMENTS NOT IDENTIFIED IN THE
DETAILS.
4. MEMBRANE AND THROUGH PENETRATIONS IN RATED
CONSTRUCTION SHALL BE PROTECTED BY AN APPROVED
PENETRATION FIRE STOP SYSTEM TESTED IN
ACCORDANCE WITH ASTM E814 OR UL 1479.
5. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, OR ANY
OTHER WALLS REQUIRED TO HAVE PROTECTED OPENINGS
OR PENETRATIONS SHALL BE PERMANENTLY IDENTIFIED
ABOVE ACCESSIBLE CEILINGS WITH SIGNS OR STENCILING
A MINIMUM OF 1/2" LETTERING LOCATED WITHIN THE
CONCEALED SPACE AT INTERVALS NOT EXCEEDING 30'.
6. EDGE OF DOOR FRAMES SHALL BE 4" OFF ADJACENT
SURFACE / CORNER UNLESS NOTED OTHERWISE.
GYPSUM BOARD SYSTEMS
GYPSUM BOARD
1. ALL GYPSUM BOARD USED ON ALL RATED AND NON-RATED
SYSTEMS SHALL COMPLY WITH ASTM C1396 AND BE A
MINIMUM OF 5/8" TYPE "X", UNLESS THE RATED ASSEMBLY
REQUIRES A DIFFERENT TYPE.
2. ABUSE AND IMPACT RESISTANT GYPSUM BOARD SHALL BE
PROVIDED WHERE INDICATED AND COMPLY WITH ASTM
C1629.
3. WATER RESISTANT GYP BOARD SHALL BE PROVIDED AT
ALL TOILET ROOMS, JANITOR'S CLOSETS, KITCHENS,
MECHANICAL ROOMS AND SIMILAR SPACES THAT MAY BE
SUBJECT TO WATER, STEAM OR EXCESSIVE MOISTURE AND
SHALL COMPLY WITH ASTM C1178.
4. CEMENTITIOUS BACKER PANELS SHALL BE PROVIDED
BEHIND ALL WALL TILE INSTALLATIONS AT SHOWERS AND
SIMILAR AREAS SUBJECT TO WETTING AND COMPLY WITH
ASTM C1325.
5. FINISHING TRIMS INCLUDING CORNER BEAD, J-TRIM, AND
EXPANSION JOINTS (V-SHAPED) SHALL COMPLY WITH
ASTM C1047.
6. EXPANSION JOINTS SHALL BE LOCATED AS SHOWN ON THE
DRAWINGS. WHERE NO JOINTS ARE INDICATED,
PRE-FORMED EXPANSION JOINTS SHALL BE INSTALLED ON
CONTINUOUS WALLS AT INTERVALS NOT TO EXCEED 30'
AND SHALL NOT TERMINATE INTO OPENINGS, DOOR
FRAMES OR SIMILAR ITEMS.
7. ACOUSTIC SEALANT SHALL BE PROVIDED AT THE
PERIMETER OF ALL SOUND RATED ASSEMBLIES AND
PENETRATIONS AND COMPLY WITH ASTM C843 OR AS
RECOMMENDED BY GYP BOARD MANUFACTURER.
8. ALL JOINTS SHALL BE FINISHED, SMOOTH, IN
ACCORDANCE WITH ASTM C840 / GA 214. ALL EXPOSED
SURFACES SHALL BE A MINIMUM OF LEVEL 4 UNLESS
NOTED OTHERWISE. ALL RATED ASSEMBLIES AND
CONCEALED AREAS MAY BE LEVEL 2.
9. AREAS TO RECEIVE TILE WALL BASE SHALL BE FINISHED
SO AS TO PROVIDE A FLAT SURFACE WITH NO MORE THAN
1/8" IN DEVIATION IN 4 FEET TO PREVENT GAPS BEHIND
TILE.
WOOD FRAMING
1. ALL FRAMING MEMBERS SHALL BE THE SIZE AND SPACING
INDICATED. FRAMING SHALL COMPLY WITH AF & PA'S
WCD-1, DETAILS FOR CONVENTIONAL WOOD FRAME
CONSTRUCTION.
2. WOOD FRAMING FOR STUDS SHALL BE KILN-DRIED,
GRADED PER DOC PS 20 WITH 19% MOISTURE CONTENT
MAXIMUM. HEM-FIR OR S-P-F STUD GRADE OR BETTER.
3. WOOD FRAMING AND PLATES IN CONTACT WITH
CONCRETE SHALL BE PRESSURE PRESERVATIVE TREATED
(PT) IN ACCORDANCE WITH AWPA U1. CCA TREATED
LUMBER IS NOT ALLOWED.
4. FIRE RETARDANT TREATED (FRT) LUMBER AND
SHEATHING SHALL BE PROVIDED WHERE INDICATED AND
COMPLY WITH ASTM D3201.
PARTITION LEGEND
NOTES:
1. ALL PARTITIONS NOT DESIGNATED SHALL BE TYPE W4
2. REFER TO PARTITION TYPES ON SHEET G1.2 FOR
ADDITIONAL INFORMATION.
3. ALL PARTITIONS SHALL BE FULL HEIGHT EXCEPT WHERE
NOTED ADJACENT TO TAG (#'-##" )
EXISTING PARTITION TO REMAIN
EXISTING PARTITION TO BE REMOVED
NEW PARTITION- SEE TYPES
A3
PARTITION TYPE DESIGATION
CORE SIZE / THICKNESS
MODIFIER / FINISH
METAL FRAMING
1 1" FURRING
2 2-1/2" STUD
3 3-5/8" STUD
6 6" STUD
8 8" STUD
WOOD FRAMING
1 1x FURRING 2 2x FURRING 4 2x4 STUD 6 2x6 STUD
PARTITION TYPES
W WOOD FRAMING
R FIRE BARRIER
DOOR TYPES
NO SCALE
FRAME TYPES
NO SCALE
DOOR HARDWARE NOTES
1. THE FINISH FOR ALL DOOR HARDWARE SHALL BE BHMA
626 SATIN CHROME, U.N.O. COORDINATE AND PROVIDE
CLOSEST MATCHING FINISH WITH MFGR WHERE THIS
OPTION IS NOT AVAILABLE.
2. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION
OF FINAL HARDWARE SELECTIONS, MODEL NUMBERS, ETC.
TO MEET THE DESIGN INTENT SPECIFIED HERE AND
ENSURE COMPATIBILITY OF ALL COMPONENTS.
3. ALL HARDWARE SHALL BE INSTALLED AND ADJUSTED TO
MEET ADA / ACCESSIBILITY REQUIREMENTS AND SHALL BE
OPERABLE WITHOUT TIGHT PINCHING, GRASPING OR
TWISTING.
FUNCTION- MORTISE LEVER LOCKSET, GRADE 1, SINGLE
CYLINDER WITH DEADBOLT, SARGENT 7900 SERIES
OR EQUAL, "BL" LEVER, "O" ROSE. PROVIDE STRIKE
PLATE SUITABLE FOR THE FRAME DEPTH.
A 71 FUNCTION FAIL SECURE, ELECTROMECHANICAL
B ANSI F13 EXIT FUNCTION W/ INTERIOR THUMBTURN
"-P" SUFFIX DENOTES PANIC EXIT DEVICE ON EGRESS
SIDE
HINGES- # DENOTES QTY PER LEAF
H 4-1/2" x 4-1/2" STEEL BB, 5 KNUCKLE, NRP, FULL
MORTISE
E SAME AS "A" EXCEPT ELECTRIFIED
CLOSERS- SET TO MAX 5 LB OPENING FORCE
C SURFACE MTD, OVERHEAD
STOP
W WALL, CONCAVE, ROCKWOOD #409 OR EQ
SPECIAL
S SMOKE SEALS
ACCESS
C CARD READER
111 CLASSROOM 111 3'-0" x 7'-0" WD N HM R1B H C W
112 CLASSROOM 112 3'-0" x 7'-0" WD N HM R1B H C W
113 CLASSROOM 113 3'-0" x 7'-0" WD N HM R1B H C W
114 WORK ROOM 114 3'-0" x 7'-0" WD N HM R1B H C W
115 ELECTRICAL 115 3'-0" x 7'-0" WD F HM R1B H C W 45
SP
EC
IA
L
DOORS & FRAMES
WOOD DOORS
1. WOOD DOORS SHALL BE 1-3/4" THICK, 5-PLY, SOLID
PARTICLEBOARD CORE, FREE OF UREA FORMALDEHYDE IN
ACCORDANCE WITH ANSI/WDMA I.S. 1A OR 6A.
2. RATED DOORS SHALL MEET THE REQUIREMENTS OF NFPA
80 AND UL 10C.
3. DOOR LITE GLAZING SHALL BE WIRED SAFETY GLASS,
COMPLYING WITH ASTM E119 AND NFPA 80.
4. PROVIDE FACE VENEER FOR TRANSPARENT FINISH, MAPLE,
GRADE 'A', BOOK AND RUNNING MATCH.
5. PREFINISHED DOORS SHALL BE UV CURED, STANDARD
COLOR AS SELECTED BY THE ARCHITECT.
AC
CE
SS
S
REMARKS
R1 CLASSROOM / ROOM SIGNAGE PROVIDED BY
OWNER
RATING
## NUMBER OF MINUTES, DOOR & FRAME
METAL DOORS
1. ALL METAL DOORS SHALL BE 1-3/4" THICK, CONFORMING
WITH STEEL DOOR INSTITUTE (SDI) GUIDE
SPECIFICATIONS.
2. INTERIOR METAL DOORS SHALL BE 18 GA FACE SHEET / 16
GA FRAME WITH POLYSTYRENE CORE.
3. EXTERIOR METAL DOORS SHALL BE 16 GA FACE SHEET /
14 GA FRAME WITH G60 COATING AND INSULATED CORE.
MIN R=6 OR AS REQUIRED BY THE ENERGY CODE.
4. METAL DOORS SHALL BE FULL FLUSH STYLE WITH
INTERLOCKED, HEMMED EDGES AND HAIRLINE SEAMS.
5. RATED DOORS SHALL MEET THE REQUIREMENTS OF UL
10B, TEMPERATURE RISE RATED, POSITIVE PRESSURE
WITH STEEL STIFENERS & MINERAL WOOL INSULATION.
VISION LITES SHALL INCORPORATE FIRE RATED GLAZING
TO MEET THE RATINGS INDICATED.
6. PROVIDE INTERNAL REINFORCEMENT FOR APPLIED
HARDWARE SUCH AS HINGES, CLOSERS, EXIT DEVICES,
ETC.
7. LITES AND LOUVERS SHALL BE FABRICATED WITH THE
DOORS. POST-INSTALLED LITE KITS ARE NOT PERMITTED.
8. ALL GLAZING SHALL BE TEMPERED, SAFETY GLASS, CLEAR.
EXTERIOR GLAZING SHALL BE INSULATED, CLEAR.
9. DOORS SHALL BE FACTORY PRIMED, READY FOR FIELD
PAINTING.
METAL FRAMES
1. HOLLOW METAL DOOR FRAMES SHALL BE STEEL, UNEQUAL
RABBET CONFORMING TO THE STEEL DOOR INSTITUTE
(SDI) GUIDE SPECIFICATIONS.
2. FIRE RATED FRAMES SHALL MEET THE REQUIREMENTS OF
NFPA 252 / ANSI UL10B AND NFPA 80.
3. FRAME DEPTH SHALL BE AS REQUIRED TO ACCOMMODATE
THE WALLS IN WHICH THEY ARE INSTALLED.
CONTRACTOR TO COORDINATE ALL SIZES AND OPENINGS.
4. INTERIOR FRAMES SHALL BE 16 GA, KNOCK DOWN (KD)
OR SLIP ON CONSTRUCTION AT INTERIOR STUD
PARTITIONS.
5. EXTERIOR FRAMES, FIRE RATED FRAMES AND FRAMES IN
MASONRY OPENINGS SHALL BE 14 GA, G90, WELDED
CONSTRUCTION.
6. PROVIDE FRAME ANCHORS AS RECOMMENDED BY THE
MANUFACTURER, SUITABLE FOR THE CONDITIONS OF
EACH OPENING.
7. FRAMES SHALL BE PREPARED BY THE MANUFACTURER FOR
ALL HINGES, STRIKES, CLOSERS, ETC.
8. FRAMES SHALL BE FACTORY PRIMED, READY FOR FIELD
PAINTING.
ETR
ETR
J1 A1.1
DOOR JAMB DETAIL
SCALE: 1-1/2"= 1'-0"
H1 A1.1
DOOR HEAD DETAIL
SCALE: 1-1/2"= 1'-0"
J1 A1.1
H1 A1.1
A4.1
101B
COMMON AREA
EGRESS
WINDOW
(EXIST)
EG
RE
SS
W
IN
DO
W (E
XI
ST
EG
RE
SS
W
IN
DO
W (E
XI
ST
EWC W/
BOTTLE FILLER
SAWCUT & REMOVE EXIST CONC
SLAB TO EXTEND U/G PLUMBING
TO NEW LOCATION
'-0
/8
REF
(BY OWNER)
IT EQPT BY
OWNER
36"x24" SS TABLE
BY OWNER
PATCH SLAB TO MATCH EXST
1'-4"3'-0 1/2"
VERIFY
ALIGN
6'-0"
CLEAR
W4
R4
W4 R4
EXIST 1-HR RATED
PARTITION & DOOR
EXIST EWC
EXIST PROTECTED COLUMNS
EXIST 1-HR
FIRE BARRIER
ELECT PANEL
BY LANDLORD
ETR
ETR
EXIST SOLID, FLUSH
HM DOOR & FRAME
W/ PANIC EXIT HDWR
EXIST GLASS & ALUM
ENTRANCE DOOR EQUIPPED
WITH PANIC EXIT HDWR
HM1
HM1
HM1
HM1
HM1
C
45S
45S
45S
45S
S
R4
R4
R4
A4.1
A4.1
A4.1
A4.1
A4.1
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
NORTH
Scale:
REFLECTED CEILING PLAN
1/4" = 1'-0"
A3.1
BID & PERMIT 03/31/25
LA
ST
P
RI
NT
ED
B Y:
JI
M
O N
3/ 4/
:3
PM
CR
EA
TE
3-
FI
LE
SV
R\
PR
OJ
EC
TS
\2
5-
LI
GH
TH
OU
SE
A
CA
DE
M Y-
H
AS
TI
NG
S\
_W
OR
KI
NG
D
RA
W
IN
GS
\S
HE
ET
S
- T
I\ A1
.X .D
W G
Reflected Ceiling Plan
ENTRY HALL
TOILET ROOM
EXIST
TOILET ROOM
EXIST
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
ELEVATOR
EXIST
EXISTING CEILING GRID TO REMAIN
CEILING LEGEND
EXISTING CEILING GRID TO BE REMOVED
NEW CEILING GRID
EXISTING CEILING DIFFUSER TO BE REMOVED /
RELOCATED
NEW / RELOCATED CEILING DIFFUSER
EXISTING LIGHT FIXTURE TO REMAIN
EXISTING LIGHT FIXTURE TO BE REMOVED /
RELOCATED
NEW / RELOCATED LIGHT FIXTURE
CEILING NOTES
1. SUSPENDED ACOUSTICAL CEILINGS SHALL BE INSTALLED
IN ACCORDANCE WITH ASTM C635 AND C636.
2. CEILING PRODUCTS SHALL COMPLY WITH THE CEILING
FINISH REQUIREMENTS LISTED IN THE BUILDING CODE
DATA FOR SMOKE DEVELOPED AND FLAMESPREAD.
3. SUSPENDED TILE CEILINGS SHALL BE LAID OUT SO THAT
THE GRID OR TILES ARE CENTERED IN THE ROOM U.N.O.
AVOID THE USE OF LESS THAN HALF-WIDTH TILES.
4. COORDINATE THE LOCATION OF MECHANICAL AND
ELECTRIAL ITEMS TO BE INTEGRATED INTO THE CEILING
GRID. LIGHT FIXTURE PLACEMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER COMPONENTS.
5. RECESSED LIGHTS, SPRINKLER HEADS AND SIMILAR
ACCESSORIES SHALL BE CENTERED IN THE TILE IN WHICH
THEY ARE LOCATED.
6. HANGER WIRES SHALL BE SECURELY ATTACHED TO
STRUCTURAL MEMBERS (NOT FLOOR OR ROOF DECK)
WITH A MINIMUM No. 12 GAGE, GALVANIZED, SOFT
ANNEALED, MILD STEEL WIRE AND BE BRACED TO
PREVENT SWAY. WIRES SHALL BE INSTALLED PLUMB AS
REQ'D.
7. SUSPENDED GRID SYSTEMS AND HANGER WIRES SHALL
NOT BE USED TO SUPPORT CONDUIT, PIPING, DUCTWORK
OR LOOSE CABLING. ALL SUCH ELEMENTS SHALL BE
INDEPENDENTLY SUPPORTED.
8. PERIMETER WALL TRIMS SHALL BE SECURED THROUGH
GYP BOARD INTO WALL FRAMING MEMBERS.
8'-0"
ACT
8'-0"
ACT
8'-0"
ACT
8'-0"
ACT
8'-0"
ACT
EXP
8'-0"
ACT
8'-0"
ACT
X'-XX" INDICATES HEIGHT OF CEILING ABOVE
FINISHED FLOOR LEVEL
COMMON AREA
AutoCAD SHX Text M
PRE-FINISHED MAPLE MELAMINE
INTERIOR, U.NO.
LAMINATE OR WOOD VENEER ON
3/4" PART. BD. PANELS- SEE ELEVS
PRE-FINISHED 3/4" PLYWD SHELF
TO MATCH CABINET INTERIOR ON
SHELF PINS @ 3" O.C. VERT.
COORD BLK'G IN WALL
ADA COMPLIANT WIRE PULLS, U.N.O.
120° EUROPEAN STYLE HINGES
SE
E
EL
EV
S.
2"
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
A4.1
BID & PERMIT 03/31/25
LA
ST
P
RI
NT
ED
B Y:
JI
M
O N
3/ 4/
:3
PM
CR
EA
TE
3-
FI
LE
SV
R\
PR
OJ
EC
TS
\2
5-
LI
GH
TH
OU
SE
A
CA
DE
M Y-
H
AS
TI
NG
S\
_W
OR
KI
NG
D
RA
W
IN
GS
\S
HE
ET
S
- T
I\ A1
.X .D
W G
Interior Elevations, Finish Plan & Details
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A1.1
INTERIOR ELEVATION
SCALE: 1/4"= 1'-0"
A4.1
CABINET SECTION
SCALE: 1"= 1'-0"
COLUMN (NEAR SIDE)
EXIST GLASS &
ALUM STOREFRONT
EXIST TEMPERED
GLASS
MILLWORK NOTES
1. MILLWORK, CABINETRY, COUNTER TOPS, ETC. SHOWN ARE
TO ILLUSTRATE DESIGN INTENT ONLY. SUPPLIER SHALL
BE RESPONSIBLE FOR FINAL DETAILING TO THE
DIMENSIONS PROVIDED.
2. CABINET DIMENSIONS, HARDWARE, ETC. SHALL COMPLY
WITH THE REQUIREMENTS OF ANSI A117.1 (ADA).
3. ALL CABINETS FACES SHALL BE PLASTIC LAMINATE CLAD,
U.N.O. INTERIORS SHALL BE MAPLE MELAMINE, U.N.O.
4. PROVIDE FACE MATCHING LAMINATE AT ALL EXPOSED
LOCATIONS VISIBLE BEHIND DOORS OR BETWEEN GAPS.
5. LAMINATE SHALL BE AS SPECIFIED OR AS SELECTED BY
ARCHITECT.
6. PROVIDE FINISHED PANELS AT ALL EXPOSED CABINET
ENDS AND OPENINGS FOR EQUIPMENT AND APPLIANCES.
7. COORDINATE OPENINGS AND SPACES FOR APPLIANCES
WITH PRODUCT SPECIFICATIONS.
8. ALLOW FOR A A CONTINUOUS RUN OF UNDER CABINET
LIGHTING AT ALL WALL CABINETS.
9. COUNTER TOPS SHALL BE MANUFACTURED STONE OR
QUARTZ, 3 cm. COLOR AS SPECIFIED OR SELECTED BY
ARCHITECT, U.N.O. PROVIDE PENCIL EDGE PROFILE, 1/8"
RADIUS.
10. PROVIDE 3/4" SUB TOPS. USE WATER RESISTANT
MATERIALS AT ALL WET LOCATIONS.
11. PROVIDE BACK AND SIDE SPLASHES, 4" HIGH, TO MATCH
COUNTER TOP, U.N.O.
12. COORDINATE LOCATION OF WALL BLOCKING FOR
CABINETS, COUNTER TOPS, ETC. W/ OTHER TRADES.
13. PROVIDE COUNTER TOP SUPPORT BRACES AT OPEN WORK
SURFACES NOT TO EXCEED 42" O.C.
14. COORDINATE LOCATION OF COUNTER TOP GROMMETS IN
WORK SURFACE TOPS WITH OWNER. PROVIDE 2"
DIAMETER, BLACK.
15. PAINT OR SEAL ALL VISIBLE / EXPOSED WOOD, PLYWOOD,
BLOCKING, CLEATS, SUPPORTS, BRACES, ETC.
16. SEAL COUNTER TOP TO BACK AND SIDE SPLASHS AT ALL
WET AREAS WITH CLEAR SILICONE SEALANT.
17. CABINET DOORS AND DRAWERS SHALL BE FURNISHED
WITH WIRE PULLS, ADA COMPLIANT, SATIN CHROME
FINISH, U.N.O.
18. HINGES SHALL BE 120 DEGREE OPEN, EUROPEAN STYLE,
U.N.O. DOORS OVER 32" HIGH SHALL HAVE THREE HINGES
PER SIDE.
19. CABINET DRAWERS SHALL BE FURNISHED WITH
FULL-DEPTH, SIDE MOUNT, SOFT-CLOSE, BALL BEARING
DRAWER SLIDES.
ENTRY HALL
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
W:
B:
F:
PT
VB
VCT
W:
B:
F:
PT
VB
VCT
W:
B:
F:
PT
VB
CPT
W:
B:
F:
PT
VB
CPT
W:
B:
F:
PT
VB
CPT
W:
B:
F:
PT
VB
VCT
W:
B:
F:
PT
VB
VCT
FIN
AC ACOUSTIC CEILING
CPT CARPET, MODULAR
CT CERAMIC TILE
EPT EPOXY PAINT
EXP EXPOSED STRUCT.
FRP FIBER REINF. PANEL
GYP GYPSUM BOARD
LVP LUXURY VINYL PLANK
LVT LUCURY VINYL TILE
PL PLASTIC LAMINATE
PT PAINT
QT QUARRY TILE
SC SEALED CONCRETE
SS SOLID SURFACE OR
MFG. QUARTZ
SSV SEAMLESS SHEET VINYL
STC STAINED CONCRETE
STS STAINLESS STEEL
VB VINYL BASE
VCT VINYL COMP. TILE
WC WALL COVERING
WD WOOD
MATERIAL ABBREVIATIONS
N.I.C.
(BY LANDLORD)
NORTH
Scale:
FINISH PLAN
1/8" = 1'-0"
VB
PNT
VB
PNT
VB
PNT
VB
PNT
INTERIOR FINISH MATERIALS
MARK
CLEAR, EPOXY SEALER WITH NON-SLIP FINISH. ENSURE COMPATIBILITY WITH NEW
CONCRETE AT SAWCUT AND PATCHED AREAS OF FLOOR.
VINYL BASE: 4" HIGH WITH COVE. COLOR AS SELECTED BY OWNER.
LATEX PAINT: GENERAL WALLS, COLOR AND SHEEN AS SELECTED BY OWNER.
PLASTIC LAMINATE (CABINETS): AS SELECTED BY OWNER.
STAINLESS STEEL COUNTER TOP, 18 GA, BRUSHED FINISH.
ACOUSTICAL CEILING TILE: 2'x2' TILE, ARMSTRONG "ULTIMA" #1993 W/ BEVELED TEGULAR
EDGE IN 15/16" PRELUDE SUSPENDED METAL GRID SYSTEM, WHITE. OR EQUAL.
EXPOSED CONSTRUCTION. PAINT CEILING WHITE, U.N.O.
CARPET: MODULAR CARPET TILES, 12" x 48", SOLUTION DYED, MIN 25 OZ/YD. QUICK SHIP.
COLOR & PATTERN AS SELECTED BY OWNER. INSTALL PER MFGR RECOMMENATIONS.
SC
CPT
VB
ACT
EXP
PNT
PL
STS
WALK-OFF CARPET: 24" x 24" MODULAR, COLOR: BLACK OR CHARCOAL. INSTALL PER MFGR
RECOMMENDATIONS.CPT2
DESCRIPTION
VINYL COMPOSITION TILE: 12"x12" SQUARE, 0.125" THICK. PROVIDE OPTION FOR UP TO 3
COLORS (NEUTRAL + 2 ACCENT), AS SELECTED BY OWNER. INSTALL PER MFGR RECOMM.VCT
FINISH NOTES
1. ALL FINISHES SHALL COMPLY WITH THE FLAME SPREAD
AND SMOKE DEVELOPED CLASSIFICATIONS LISTED IN THE
BUILDING CODE DATA.
2. WORKMANSHIP SHALL BE IN CONFORMANCE WITH
CURRENT TRADE ASSOCIATION STANDARDS FOR EACH
PRODUCT OR SYSTEM INSTALLED.
3. CONTRACTOR(S) SHALL BE RESPONSIBLE FOR EXAMINING
AND CONFIRMING ALL SUBSTRATE CONDITIONS WHERE
NEW MATERIALS ARE APPLIED. SUBSTRATE SHALL BE
SMOOTH, FREE OF DEFECTS AND SHALL CONFORM TO
THE REQUIREMENTS OF THE FINISHED MATERIAL
MANUFACTURERS WRITTEN RECOMMENDATIONS.
4. FINISH SUBSTITUTIONS SHALL ONLY BE APPROVED PRIOR
TO THE AWARD OF CONTRACT BY ARCHITECT. PROVIDE
PRODUCTS AS SPECIFIED UNLESS DESIGNATED "OR
EQUAL".
5. REFER TO REFLECTED CEILING PLAN(S) FOR CEILING
DETAILS, ACCENTS, ETC.
6. ALL FLOORING TRANSITIONS SHALL OCCUR BENEATH THE
CENTER OF THE DOOR U.N.O.
7. ALL PAINTS AND ADHESIVES SHALL BE LOW VOC / ODOR.
8. COUNTERTOP SUPPORT BRACKETS SHALL BE FINISHED TO
MATCH THE COUNTER TOP. VENEER OR LAMINATE
SUPPORT PANELS SHALL MATCH THE ADJACENT CABINET
FINISH, U.N.O.
9. PROVIDE SCALED MILLWORK DRAWINGS OF ALL
SHOP-BUILT CABINETS, COUNTER TOPS, ETC.
10. PROVIDE PHYSICAL FINISH SAMPLES FOR APPROVAL OF
ALL FINISH MATERIALS SPECIFIED. PAINT AND STAIN
FINISHES SHALL BE PROVIDED IN THE SPECIFIED SHEEN.
TRANSPARENT FINISHES SHALL BE ON THE WOOD
SPECIES INDICATED.
11. FIELD FINISH VENTS, GRILLES, ACCESS PANELS,
RACEWAYS, ELECTRICAL PANEL BOARDS (IN FINISHED
SPACES) TO MATCH SURFACE ON WHICH THEY OCCUR
UNLESS NOTED OTHERWISE.
EXCEPTION: ITEMS WITH FACTORY WHITE FINISH,
OCCURRING ON WHITE ACT OR WHITE GYPSUM BOARD
CEILING SHALL NOT BE PAINTED. STAINLESS STEEL
ITEMS SHALL NOT BE PAINTED
12. REPAIR / REPLACE EXISTING SUSPENDED CEILING GRID &
TILE AFFECTED BY NEW WORK.
13. REPAINT EXISTING WALLS, FULL LENGTH, WHERE
AFFECTED BY NEW WORK. SPOT PAINTING TO MATCH IS
NOT ACCEPTABLE.
14. PROVIDE NEW WALL BASE AT EXISTING WALL AFFECTED
BY NEW WORK. NEW AND EXISTING SHALL NOT BE MIXED
ON THE SAME WALL.
CPT2
2' -1
0"
SS TABLE BY
OWNER
WASH / PREP SINK
HANDWASH SINK
EXIST WINDOW
VB
PNT
NOTE:
THE OWNER SHALL
FURNISH ALL WINDOW
OBSCURING COVERINGS
OR DEVICES AS REQ'D.
4' -4
2'
-6
2'-6"
FILLER AS REQ'D
A4.1
N.I.C.
(BY LANDLORD)
W:
B:
F:
PT
VB
VCT
M
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
NORTH
Scale:
MECHANICAL HVAC LAYOUT
1/4" = 1'-0"
M1.1
BID & PERMIT 03/31/25
LA
ST
P
RI
NT
ED
B Y:
JI
M
O N
3/ 4/
:3
PM
CR
EA
TE
3-
FI
LE
SV
R\
PR
OJ
EC
TS
\2
5-
LI
GH
TH
OU
SE
A
CA
DE
M Y-
H
AS
TI
NG
S\
_W
OR
KI
NG
D
RA
W
IN
GS
\S
HE
ET
S
- T
I\ M
EP
1.
X.
DW
G
Mechanical HVAC & Plumbing Plans and Schedules
NORTH
Scale:
PARTIAL PLUMBING PLAN
1/4" = 1'-0"
NOTES:
1. PROVIDE MIXING VALVE AT EACH LAVATORY CONFORMING TO ASSE 1070.
2. COVER EXPOSED PIPES AT ALL LAVATORIES AND WALL SINKS.
3. PROVIDE STOPS AT ALL FIXTURES.
4. ALL DVW PIPING TO BE PVC
5. WATER SUPPLY PIPING TO BE TYPE A PEX W/ COPPER STUB OUTS.
MODEL / DESCRIPTION
PLUMBING FIXTURE SCHEDULE
EXIST BY LANDLORDWATER CLOSET
FIXTUREMK
EXIST BY LANDLORDWALL LAVATORY
WALL MOUNT 17" x 15" STAINLESS WITH BACKSPLASH
AND LEVER FAUCETHAND SINK
FREE STANDING, 41" x 22-1/2", 2 COMP. STAINLESS
WITH BACKSPLASH AND LEVER FAUCETWASH SINK
SAN VENT COLD HOT REMARKS
WC
WL
S2
S1 2" 2" 1/2" 1/2"
2" 2" 1/2" 1/2"
EXIST BY LANDLORDWATER HEATERWH
SINGLE UNIT (LOW) WITH BOTTLE FILLERELECT WATER COOLEREWC
WH
WC WC
WL WL
4" S
AN3/
4"
H W
3/ 4"
C W
S2
1-1/2" 2" 1/2"
EWCS1
CONN TO
EXST
24"x24" SUPPLY AIR DIFFUSER WITH DAMPER-
CONNECT TO EXIST DUCT / RADIATION
DAMPER IN CEILING ABOVE- TYP
24"x24" RETURN AIR GRILLE WITH DAMPER-
CONNECT TO EXIST DUCT / RADIATION
DAMPER IN CEILING ABOVE- PLENUM RETURN
IS NOT ALLOWED- TYP
BASIS OF DESIGN: ELKAY LZS8WSLK
BASIS OF DESIGN: REGENCY #60021717G
BASIS OF DESIGN: REGENCY #600HS17
ENTRY HALL
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
NOTES:
1. ALL WORK SHALL BE IN CONFORMANCE WITH THE 2021 MICHIGAN MECHANICAL CODE.
2. CONTRACTOR TO VERIFY CAPACITY OF EXISTING EQUIPMENT AND SUPPLEMENT AS MAY BE REQUIRED.
3. FURNISH TEST AND BALANCE REPORT PRIOR TO OCCUPANCY.
4. COORDINATE WITH THE WORK OF OTHER TRADES AS REQUIRED.
VENTILATION SCHEDULE
CORRIDOR
NAMEROOM
CLASSROOM
REMARKS
458 35 10
392 35 10
WORK ROOM
OCC/
1000 SF
AREA
SF
CFM /
PERSON
CFM /
SF
CLASSROOM
CLASSROOM
MMC TABLE 403.3.1.1
0.12
0.12
0.06
4 5 0.06
35 10 0.12
OCC
CONFIRM IT EQPT
COOLING
REQUIREMENTS W/
OWNER & FURNISH
AS NEEDED
FUTURE
PANEL
100A
FUTURE
PANEL
100A
EXIST FURNACES IN
ATTIC W/ FUSED DISC.
HOUSE
PANEL
100A
120/240
(EXIST)
PANEL
LP-1C
100A
120/240
(EXIST)
PANEL
LP-1B
100A
120/240
(EXIST)
PANEL
LP-1A
100A
120/240
(EXIST)
CT
CAB
(EXIST)
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
NORTH
Scale:
LIGHTING PLAN
1/4" = 1'-0"
E1.1
BID & PERMIT 03/31/25
LA
ST
P
RI
NT
ED
B Y:
JI
M
O N
3/ 4/
:3
PM
CR
EA
TE
3-
FI
LE
SV
R\
PR
OJ
EC
TS
\2
5-
LI
GH
TH
OU
SE
A
CA
DE
M Y-
H
AS
TI
NG
S\
_W
OR
KI
NG
D
RA
W
IN
GS
\S
HE
ET
S
- T
I\ M
EP
1.
X.
DW
G
Electrical Power & Lighting Plans
ENTRY HALL
TOILET ROOM
EXIST
TOILET ROOM
EXIST
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
ELEVATOR
EXIST
NORTH
Scale:
POWER PLAN
1/4" = 1'-0"
EXIST
EXIT
EXIST
EXIT
EXIST
EXIT
EXIST
EM
EXIST
EM
EM
EM
EM
EM
EM EM
EMEM
REF
20A
EXST
EXST
EXST EXST EXST
EXST
EXST
EXST
DUPLEX RECEPTACLE, 120V
ELECTRICAL SYMBOLS
ELECTRICAL POWER / LIGHTING PANEL
JUNCTION BOX- CONFIRM REQUIREMENTS- PROVIDE
APPROPRIATE COVER PLATE
DUPLEX RECEPTACLE, GFCI 120V
ROUGH-IN FOR CARD READER (BY OTHERS). CONFIRM
LOCATIONS & STUB CONDUIT TO ACCESSIBLE CEILING.
ROUGH-IN FOR DOOR BELL (BY OTHERS). CONFIRM
LOCATIONS & STUB CONDUIT TO ACCESSIBLE CEILING.
JUNCTION BOX FOR CAMERA (BY OTHERS)- CONFIRM
LOCATIONS (WALL OR CEILING MOUNT) & STUB 3/4"
CONDUIT TO ELECT ROOM 115.
MICRO
20A
LIGHT FIXTURE LEGEND
LED TROFFER, 2x4
SURFACE MOUNTED FIXTURE
WALL SCONCE
WALL / CEILING MTD EXIT SIGN (LED)
WALL / CEILING MTD EMERGENCY LIGHT (LED)
LIGHTING
1. THE FIXTURES REPRESENTED ABOVE ARE FOR DESIGN
INTENT ONLY. ELECTRICAL CONTRACTOR SHALL VERIFY
LIGHTING PLANS FOR FINAL FIXTURE SPECS, LOCATIONS,
CONTROLS AND OTHER REQUIREMENTS.
2. ALL LIGHT FIXTURES SHALL HAVE LOCAL AND DAYLIGHT
CONTROLS / OCC SENSORS AS REQUIRED BY THE ENERGY
CODE.
3. LIGHTING LAYOUT AND ILLUMINATION LEVELS (TO MEET
IES STANDARDS) SHALL BE CONFIRMED BY ELECTRICAL
CONTRACTOR PROVIDED PHOTOMETRIC LAYOUT BASED ON
ACTUAL FIXTURES PROVIDED.
LED STRIP, SURFACE MOUNT
TV
+60" AFF
TV
+60" AFF
TV
+60" AFF
PATCH & REPAIR WALL AS
REQD TO INSTALL NEW
DEVICE AND CONDUIT
POWER
1. CONFIRM FINAL LOCATION, MOUNTING HEIGHTS AND
OTHER REQUIREMENTS FOR DEVICES INDICATED FOR TV'S.
2. DEVICES MARKED EXIST ARE INSTALLED AS PART OF THE
LANDLORD'S WHITE BOX SCOPE OF WORK AND WILL BE
CONNECTED TO THE (EXISTING) TENANT PANEL.
3. PROVIDE PROTECTION FOR BOXES AND DEVICES
INSTALLED IN RATED PARTITIONS.
4. ALL PENETRATIONS IN RATED WALLS SHALL BE FIRE
CAULKED.
5. THE LOCATION OF FIRE ALARM DEVICES SHALL BE AS
DETERMINED BY THE FIRE ALARM CONTRACTOR IN
ACCORDANCE WITH ALL APPLICABLE CODES. OTHER
DEVICES, FIXTURES AND EQUIPMENT SHALL BE PROVIDED
AS NECESSARY FOR A COMPLETE AND FUNCTIONAL
SYSTEM.
ENTRY HALL
CORRIDOR
CLASSROOM
CLASSROOM
CLASSROOM
WORK ROOM
ROOM
ELECT
ELECTRICAL ONE-LINE DIAGRAM
EXISTING
LP
-1
C
LP
-1
C
EXIST CT CABINET & METERS
LP
-H
OU
SE
LP
-H
OU
SE
COORD FINAL CAMERA
LOCATION(S) WITH
OWNER & LANDLORD
ELECTRICAL NOTES
FIRE ALARM HORN / STROBE
FIRE ALARM PULL STATION
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text
OS
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text J
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text
CR
AutoCAD SHX Text
DB
AutoCAD SHX Text J
AutoCAD SHX Text
CR
AutoCAD SHX Text
DB
AutoCAD SHX Text C
F
1.0
2.0
1.6
1.2
1.9
1.1
0.9
0.6
2.5
1.4
1.1
1.3
1.5
1.8
1.3
1.4
2.1
2.9
2.9
4.3
3.5
2.1
1.6
2.1
3.6
4.4
3.6
2.6
1.6
2.2
2.2
1.8
1.8
2.5
4.2
4.8
3.6
2.5
1.2
1.4
1.5
1.5
1.9
2.3
2.9
2.5
2.0
1.4
1.6
1.6
1.6
2.0
2.0
1.8
2.4
2.5
1.5
2.6
2.9
1.3
1.9
2.4
1.2
1.5
1.8
1.1
1.3
1.4
1.2
1.4
1.4
1.5
1.8
1.8
2.4
3.4
3.1
1.3
1.7
2.1
2.1
1.9
2.0
2.2
2.1
1.7
4.5
4.5
3.0
3.0
4.1
3.3
2.3
2.7
3.7
4.5
3.6
4.9
5.9
4.5
3.7
5.2
3.9
2.5
2.7
4.1
5.2
4.4
1.0
1.0
6.4
6.4
0.8
1.0
1.2
1.2
1.1
0.9
0.7
0.5
1.3
1.9
2.2
1.7
1.5
1.2
0.9
0.7
2.0
3.6
3.6
2.3
1.9
1.8
1.3
0.8
2.8
4.1
2.3
2.2
2.6
1.9
1.1
2.6
3.2
3.0
1.9
2.1
2.8
2.4
1.5
1.9
2.2
1.9
1.4
1.8
2.3
2.1
1.6
1.3
1.4
1.2
1.0
1.3
1.7
1.7
1.4
0.9
0.9
0.8
0.8
0.9
1.2
1.3
1.2
0.7
0.6
0.6
0.6
0.7
0.9
1.0
1.0
0.5
0.5
0.5
0.5
0.6
0.7
0.8
0.8
0.4
0.4
0.4
0.4
0.5
0.5
0.6
0.6
0.4
0.4
0.4
0.5
0.5
0.3
0.3
0.3
4.3
0.4
0.5
0.6
0.7
0.9
1.0
1.1
1.0
0.8
0.7
0.6
0.5
0.4
0.6
0.7
1.0
1.3
1.7
1.8
1.5
1.2
1.0
0.8
0.6
0.5
0.4
0.8
1.0
1.5
2.1
2.7
2.4
1.8
1.4
1.1
0.8
0.7
0.5
0.4
1.0
1.3
1.9
2.4
2.7
2.4
1.8
1.4
1.0
0.8
0.6
0.5
0.4
1.0
1.4
1.8
2.1
2.0
1.8
1.4
1.1
0.8
0.7
0.5
0.4
0.4
1.0
1.4
2.0
2.4
2.5
2.0
1.5
1.1
0.8
0.6
0.5
0.4
0.4
0.8
1.2
1.8
2.6
2.3
1.7
1.3
0.9
0.7
0.5
0.4
0.4
1.8
2.3
2.0
1.6
1.3
1.0
0.7
0.6
0.5
0.4
1.4
1.6
1.4
1.2
0.9
0.7
0.6
0.5
0.4
0.3
2.8
0.8
1.0
1.2
1.5
1.8
2.1
2.3
2.2
1.9
1.6
1.3
1.1
0.9
1.0
1.2
1.6
2.0
2.7
3.1
3.2
3.3
3.0
2.3
1.7
1.3
1.1
1.2
1.5
2.0
2.8
3.7
3.7
3.6
3.7
3.8
3.1
2.3
1.6
1.3
1.4
1.8
2.3
2.8
3.3
3.4
3.2
3.3
3.2
2.8
2.3
1.8
1.5
1.5
2.0
2.5
2.6
2.4
2.2
2.1
2.0
2.0
2.0
1.9
1.9
1.7
1.5
2.6
3.8
3.8
2.7
1.9
1.6
1.5
1.5
1.8
2.2
2.6
2.2
1.4
2.4
4.4
3.3
2.2
1.6
1.3
1.4
1.9
3.1
4.2
3.1
1.1
1.7
2.9
3.5
2.8
2.1
1.6
1.3
1.5
2.1
0.9
1.2
1.6
2.1
2.2
1.8
1.4
1.3
1.5
0.6
4.6
0.8
1.0
1.3
1.6
1.7
1.8
1.6
1.0
1.5
2.2
2.6
2.3
2.7
3.0
1.3
2.3
4.0
4.3
3.0
3.2
4.9
1.5
3.2
2.7
2.9
4.8
2.0
2.0
3.0
1.4
1.3
1.7
1.0
0.9
1.0
0.7
0.7
0.7
0.5
0.5
0.4
0.4
5.3
5.3
3.6
3.7
4.3
4.0
3.5 4.4
4.9
4.0
2.9
2.3
6.7
4.4
3.5
9.5
7.2
5.6
5.7
6.6
5.3
5.3
5.6
5.9
5.1
4.3
4.5
5.8
5.7
3.8
3.4
4.1
4.1
3.3
2.5
2.5
2.6
2.5
2.2
2.4
2.1
3.1
2.4
3.7
4.7
2.8
2.7
4.5
5.0
2.8
0.610.5
5.3
4.8
2.7
1.9
2.1
3.0
4.4
4.6
4.1
2.8
2.0
1.9
2.5
4.3
2.1
2.3
2.0
1.8
1.8
2.3
3.1
3.6
1.7
5.5
1.2
0.7
0.3
0.8
0.3
0.9
0.5
0.2
1.7
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM1 @ 7.5'
EM2 @ 7.5'
EM2 @ 7.5'
EM1 @ 7.5'
Statistics
Description Symbol Avg Max Min Max/Min Avg/Min
CLASSROOM 112 1.2 fc 2.8 fc 0.3 fc 9.3:1 4.0:1 CLASSROOM 113 1.3 fc 4.3 fc 0.3 fc 14.3:1 4.3:1 COMMON AREA 110B 4.3 fc 10.5 fc 0.6 fc 17.5:1 7.2:1 CORRIDOR 110 2.6 fc 6.4 fc 1.0 fc 6.4:1 2.6:1 CORRIDOR EXTERIOR 1.4 fc 2.5 fc 0.6 fc 4.2:1 2.3:1 ELECT ROOM 115 3.9 fc 4.4 fc 3.5 fc 1.3:1 1.1:1 ENTRY EXTERIOR 0.7 fc 1.7 fc 0.2 fc 8.5:1 3.5:1 ENTRY HALL 101 3.0 fc 5.5 fc 1.7 fc 3.2:1 1.8:1 WORK ROOM 114 2.1 fc 5.3 fc 0.4 fc 13.3:1 5.3:1 CLASSROOM 111 2.2 fc 4.6 fc 0.6 fc 7.7:1 3.7:1
Schedule
Symbol Label Image QTY Manufacturer Catalog Description Number Lamps
Lamp Output LLF Input
Power Polar Plot
EM1
12 Lithonia Lighting ELM4L ELM4L SP640L 1 345 1 2.5
EM2
2 Lithonia Lighting ELA Q L0304 ELM2 LED REMOTE LAMP HEAD 1 80 1 0
DATEDESCRIPTION
P R
O J E
C T
S H
E E
T N
U M
B E
R P
R O
C O
N S
U L
T A
N T
I N
F O
Lighthouse Academy
400 W. State Street Hastings, Michigan
05-0208
100 CESAR E. CHAVEZ AVE SW
SUITE 200
G R A N D RAPIDS, MI 49503
www.create3architecture.com
CR3ATE
A R C H I T E C T U R E
S E
A L
COPYRIGHT
CREATE 3,PLLC 2025
PERMITS 03-28-25
SCALE: 1/4" = 1'-0"
FLOOR PLAN
EMERGENCY
PHOTOMETRICS
P:
\2
5\
H as tin gs
L ig ht ho us e
Ac ad em y
- E le ct ric al \W or ki ng D ra w in gs
\2
E 1.
dw g, /2
8/
0:
:2
AM
, c ll
03.28.25
E1.2
File details come from the government source that posted it. Updated .