September 23, 2014
Boardwalk Construction
4025 Ventor Avenue
Atlantic City, NJ 08401
Re: Hope well Furnance Maintenance Building
Elverson, PA
This letter shall acknowledge Versico’s intent to warrant the proposed VersiFleece TPO Adhered
Roofing Systems on the above-mentioned project.
Roof Assembly:
Deck: 3-1/2” Tongue & Groove Wood Plank Deck.
Insulation: Tapered Versico MP-H Polyiso Insulation (Min. ½” to 7”) is adhered to the wood plank deck using Versico DASH DC Bead Adhesive at 6” o.c.
Cover Board: 1/4” thick Versico Dens Deck Prime Cover Board is adhered to the polyiso using Versico’s DASH DC Bead Adhesive at a rate of 6” o.c.
Membrane: .080” thick VersiFleece TPO membrane is set in 4” o.c. beads of Versico’s
DASH DC Bead Adhesive throughout.
Upon completion of an inspection by a Versico Field Service Representative to ascertain that the roof system has been installed in accordance to Versico Specifications, Versico will issue a 30-year Total System Warranty with 55 mph wind coverage on the referenced project. As with all
Total System Warranty projects, all materials used to complete the roofing system (insulation, fasteners, termination bars, etc.) must be manufactured or marketed by Versico.
If you have any questions or need any additional information, feel free to contact our office.
Sincerely, Robin Levens
Sr. Design Analyst
Project Review & Design Services
Cc: Rick Carns, Project File
Hopewell Furnance Table of Contents
1. VersiFleece TPO Membrane (tdb) 2
2. MP-H Tapered Polyisocyanurate Insulation (tdb) 4
3. Versico VersiTrim Fascia System (tdb) 6
4. DASH Bag in a Box Adhesive (tdb) 8
5. Total System Warranty 11
Overview
VersiFleece TPO membranes are manufactured using a hot-melt extrusion process for complete scrim encapsulation. Once the VersiWeld TPO is reinforced and enhanced with fl eece, the total sheet thicknesses available are 100, 115 and 135 mils creating a very tough, durable and versatile sheet that is ideal for re-roofi ng or new construction projects. VersiFleece TPO sheets are chlorine free and plasticizer free with excellent chemical resistance to acids, bases, restaurant oils and greases.
All VersiFleece TPO membranes utilize OctaGuard XT™ weathering package technology to withstand extreme durability testing intended to simulate exposure to severe climates. VersiFleece TPO’s advanced polymerization technology combines the fl exibility of ethylene-propylene (EP) rubber with the heat weldability of polypropylene.
VersiFleece TPO membranes are intended to be used with fully adhered or mechanically attached roofi ng systems.
VersiFleece TPO is ideally suited for garden roofs, solar panel applications and projects demanding superior wind uplift resistance due to its added toughness and durability. VersiFleece TPO is also a great solution for buildings requiring low noise and odors during roofi ng application.
Features and Benefi ts
• Choice of white, gray or tan membranes that are UL Class A rated
T E C H N I C A L D A T A B U L L E T I N
VERSIFLEECE® TPO MEMBRANES
• Superior wind uplift performance and ratings (up to an FM 1-945) due to a mechanical bond between fl eece and adhesive
• 75% fewer seams than Modifi ed Bitumen
• Wide window of weldability
• Fleece reinforcement adds toughness, durability and enhanced puncture resistance
– 115-mil membrane delivers 33% greater puncture resistance and 33% greater breaking strength than 60-mil TPO
– Greater puncture resistance than Modifi ed Bitumen
• Excellent hail damage resistance
– Passes FM’s severe hail test
– Passes UL-2218 Class 4 rating
– Passes National Bureau of Standards – 23 Ice Ball test up to 3"-diameter hail with the membrane cooled to 32°F
Installation
Insulation is mechanically fastened or adhered with DASH™ Adhesive to the roof deck. When adhering insulation with DASH Adhesive, the adhesive is applied to the substrate and allowed to rise and foam. Once DASH Adhesive develops string/body/gel (typically 1½–2 minutes) place insulation into the adhesive and walk it in.
Roll the insulation with a 30"-wide 150-pound weighted roller to ensure full embedment. Extrude DASH Adhesive to the substrate and allow foam to develop string/body/ gel (typically 2 minutes) prior to setting VersiFleece TPO into the DASH Adhesive. Roll VersiFleece TPO membrane with a 30"-wide 150-pound weighted roller to ensure full embedment. Splices are hot-air welded. End laps are butted and sealed with reinforced membrane or a head sheet may be utilized.
REVIEW CURRENT VERSICO SPECIFICATIONS AND DETAILS
FOR SPECIFIC INSTALLATION REQUIREMENTS.
Precautions
1. Use proper stacking procedures to ensure suffi cient stability.
2. Exercise caution when walking on wet membrane.
3. UV-resistant sunglasses are required for VersiFleece TPO membranes.
A S I N G L E S O U R C E F O R S I N G L E - P LY R O O F I N G
Vers ico, PO Box 1289, Car l i s le, PA 17013 Te l : 800.992 .7663 Fax : 717.96 0.4 036 Web : www.vers ico.com
T E C H N I C A L D A T A B U L L E T I N
4. White surfaces refl ect heat and may become slippery due to frost and ice accumulation.
5. Care must be exercised when working close to a roof edge when the surrounding area is snow covered.
6. VersiFleece TPO membrane rolls must be tarped and elevated to keep dry prior to installation. If the fl eece gets wet, use a wet vac system to help remove moisture from the fl eece. DO NOT INSTALL MEMBRANE
IF FLEECE IS WET.
7. VersiFleece TPO membrane exposed to the weather must be prepared with Weathered Membrane Cleaner prior to hot-air welding.
VERSICO EXTREME TESTING – HEAT AGING
ASTM Requirement VersiFleece TPO Results
ASTM Test 240°F 670 hours or 4 weeks 5,376 hours or 32 weeks*
Carlisle Extreme Test 275°F N/A 1,344 hours or 8 weeks
*Comparable to 1,024 weeks (20 years) at 185°F for 6 hrs/day.
Heat Aging accelerates the oxidation rate that roughly doubles for each 10°C (18°F) increase in roof membrane temperature. Oxidation (reaction with oxygen) is one of the primary chemical degradation mechanisms of roofi ng materials.
Environmental Cycling subjects the membrane to repeated cycles of heat aging, hot-water immersion or acid fog followed by xenon-arc exposure.
LEED® INFORMATION
Pre-consumer Recycled Content 10%
Post-consumer Recycled Content 0%
Manufacturing Location Tooele, UT, Senatobia, MS
Solar Refl ectance Index White: 99 Gray: 53 Tan: 86
VERSICO EXTREME TESTING – ENVIRONMENTAL CYCLING
– 10 days heat aging at 240°F (116°C) followed by 5 days water immersion at 158°F (70°C)
– Followed by 5,040 kJ/m² (2,000 hrs. at 0.70 W/m² irradiance) xenon-arc exposure
RADIATIVE PROPERTIES FOR ENERGY STAR®*,
COOL ROOF RATING COUNCIL (CRRC) AND LEED
Physical Property Test Method White Gray Tan
ENERGY STAR –
Initial solar refl ectance
Solar Spectrum Refl ectometer 0.79 N/A 0.71
ENERGY STAR –
Solar refl ectance after 3 years
Solar Spectrum Refl ectometer (after cleaning)
0.70 N/A 0.64
CRRC –
Initial solar refl ectance
ASTM C1549 0.79 0.46 0.71
CRRC –
Solar refl ectance after 3 years
ASTM C1549
(uncleaned)
0.70 0.43 0.64
CRRC –
Initial thermal emittance
ASTM C1371 0.90 0.89 0.86
CRRC –
Initial thermal emittance after 3 years
ASTM C1371
(uncleaned)
0.86 0.88 0.87
LEED –
Thermal emittance
ASTM C1371 0.90 0.89 0.86
Solar Refl ectance Index (SRI) ASTM E1980 99 53 86
VERSIFLEECE TPO MEMBRANES
Physical Property Test Method SPEC. (Pass) VersiFleece TPO
Tolerance on Nominal Thickness, %
ASTM D751 +/-10 +/-10
Thickness over Fleece, min 100-mil (2.54 mm) 115-mil (2.92 mm) 135-mil (3.43 mm)
.045 (1.14)
.060 (1.52)
.080 (2.03)
Weight, lbm/ft² 100-mil 115-mil 135-mil
0.27 0.33 0.46
Breaking Strength, min, lbf (kN) 100-mil 115-mil 135-mil
ASTM D751
Grab Method 220 (1) 350 (1.6)
450 (2) 500 (2.2)
Elongation at break of internal fabric, % ASTM D751 15 25
Tearing Strength, min, lbf (N) 100- & 115-mil, 135-mil
ASTM D751
B Tongue Tear 55 (245) 100 (445)
Puncture Resistance, Joules 100-mil 115-mil 135-mil
ASTM D5635
17.5 22.5 30.0
Puncture Resistance, lbf 100-mil 115-mil 135-mil
FTM 101C
Method 2031 350
Brittleness point, max, °F (°C) ASTM D2137 -40 (-40) -50 (-46)
Linear Dimensional Charge, % ASTM D1204 ± 1 max -0.2 typical
Field Seam Strength, lbf/in. (kN/m) ASTM D1876 tested in peel 100-mil 115-mil 135-mil
ASTM D1876
25 (4.4) 25 (4.4) 40 (7.0)
50 (8.8) 60 (10.5) 70 (12.3)
Water Vapor Permeance, Perms ASTM E96 Proc B
— 0.10 max
0.05 typical
Resistance to Microbial Surface Growth, Rating (1 is very poor, 10 is no growth)
ASTM D3274 — 9–10 typical
Properties after heat aging –ASTM D573, 670 hrs. at 240°F Breaking strength, % retained Elongation reinf. % retained Tearing Strength, % retained Weight Change, %
ASTM D573
90 min.
90 min.
60 min.
± 1.0 max
Ozone Resistance 100 pphm, 168 hours
ASTM D1149 No cracks No cracks
Resistance to Water Absorption After 7 days immersion @ 158°F (70°C) Change in mass, max, % (one side)
ASTM D471 ±3.0 0.90
Resistance to Outdoor (Ultraviolet) Weathering Xenon-Arc, total radiant exposure at 0.70 W/m² irradiance, 80°C black panel temp.
100-mil 115-mil 135-mil
ASTM G155 No cracks No loss of breaking or tearing strength
No cracks No loss of breaking or tearing strength
17,640 kJ/m² 20,160 kJ/m² 27,720 kJ/m²
Typical properties and characteristics are based on samples tested and are not guaranteed for all samples of this product. This data and information is intended as a guide and does not refl ect the specifi cation range for any particular property of this product.
© 2013 Versico. 10.07.13. Versico, VersiWeld, DASH, OctaGuard XT and the Versico logo are trademarks of Versico. LEED is a registered trademark of the United States Green Building Council.
ENERGY STAR is a registered trademark owned by the U.S. Government. *ENERGY STAR qualifi cation is only valid in the U.S.
ocean Typewritten Text 135-Mil on Hopewell Furnace Roof ocean Typewritten Text ocean Line
Product Description
Tapered MP-H is a sloped rigid roof insulation panel composed of a closed-cell polyisocyanurate foam core bonded during the manufacturing process to fi ber-reinforced facers. Tapered MP-H is designed to promote positive drainage and prevent ponding water. For best results, use Versico’s Tapered Shop Drawings.
Features and Benefi ts
• Tapered MP-H polyiso insulation provides the highest R-value per inch of commercially available insulation products
• Environmentally friendly construction with 0% ozone-depleting components and CFC free
• Approved for direct application to steel decks
T E C H N I C A L D A T A B U L L E T I N
VERSICO’S
TAPERED MP-H POLYISO
Panel Characteristics
• Available in 4' x 4' (1220 mm x 1220 mm) in thickness of ½" (12 mm) minimum to 4.0" (102 mm) maximum in a single layer
• Available slopes are 1/16" (2 mm), 1/8" (3mm), 3/16" (5mm), ¼" (6 mm), 3/8" (10 mm) and ½" (12mm) per foot
• Available in two grades of compressive strengths per ASTM C1289-06a, Type II, Class 1, Grade 2 (20 psi), Grade 3 (25 psi)
Applications
• Constructions requiring Class A ratings
• Single-Ply Roof Systems (Ballasted, Mechanically Attached, Fully Adhered)
A S I N G L E S O U R C E F O R S I N G L E - P LY R O O F I N G
© 2011 Versico. Updated: 10/11. Versico, DASH Adhesive and the Versico logo are trademarks of Versico. *ENERGY STAR qualifi cation is only available in the U.S.
Installation
BALLASTED SINGLE-PLY SYSTEMS
Each Tapered MP-H panel is loosely laid on the roof deck.
Butt edges and stagger joints of adjacent panels. Install the roof membrane according to the manufacturer’s specifi cations.
MECHANICALLY ATTACHED SINGLE-PLY SYSTEMS
Each Tapered MP-H panel must be secured to the roof deck with fasteners and plates (appropriate to the deck type). Butt edges and stagger joints of adjacent panels.
Install the roof membrane according to the manufacturer’s specifi cations.
FULLY ADHERED SINGLE-PLY SYSTEMS
Each Tapered MP-H panel must be secured to an approved roof deck with fasteners and plates (appropriate to deck type) or can be adhered using Versico’s DASH™ adhesive.
Butt edges and stagger joints of adjacent panels. Install the roof membrane according to manufacturer’s specifi cations.
Tapered MP-H Codes and Compliances
• ASTM C1289-06, Type II, Class 1, Grade 2 (20 psi), Grade 3 (25 psi)
• International Building Code (IBC) Section 2603 NOTE: Please be aware the Federal Specifi cation HH-I-1972/GEN has been replaced.
FLORIDA BUILDING CODE APPROVAL FL#1296
MIAMI-DADE COUNTY, FLORIDA NOA NO: 04-1018.01
Underwriters Laboratories, Inc.
• Component of Class A Roof Systems (UL 790)
• Hourly Rated P series roof assemblies (UL 263) P 225, 230, 59, 302, 303, 508, 510, 514, 519, 701, 710, 713, 717, 718, 719, 720, 722, 723, 727, 728, 729, 730, 732, 734, 735, 739, 741, 742, 743, 819, 824, 827, 828
• Insulated metal deck assemblies - (UL 1256) nos. 120, 123, 292
• Tapered MP-H classifi ed by ULC
Warnings and Limitations
Insulation must be protected from open fl ame and kept dry at all times. Install only as much insulation as can be covered the same day by completed roof-covering material. Versico will not be responsible for specifi c building and roof design by others, for defi ciencies in construction or workmanship, for dangerous conditions on the jobsite or for improper storage and handling. Technical specifi cations shown in this literature are intended to be used as general guidelines only and are subject to change without notice.
Call Versico for more specifi c details, or refer to PIMA Technical Bulletin No. 109: Storage & Handling Recommendations for Polyiso Roof Insulation.
Other Polyiso Products by Versico
• SECURSHIELD POLYISO BONDED TO COATED GLASS FACER
• MP-HCG POLYISO BONDED TO COATED GLASS FACER
• MP-HF POLYISO BONDED TO FOIL
• MP-HNB POLYISO BONDED TO ORIENTED STRAND BOARD
• MP-HWF POLYISO BONDED TO WOOD FIBERBOARD
• TAPERED MP-HCG POLYISO BONDED TO COATED GLASS FACER
• TAPERED MP-HWF TAPERED POLYISO BONDED TO WOOD
FIBERBOARD
• MP-H POLYISO
TYPICAL PROPERTIES AND CHARACTERISTICS**
POLYISO FOAM CORE ONLY
Property Test Method Value Compressive
Strength
ASTM D1621
ASTM 1289-06
20 psi* minimum
(138 kPa, Grade 2)
Dimensional Stability
ASTM D2126 2% linear change (7 days)
Moisture Vapor Transmission
ASTM E96
12.10
< 1 perm (57.5 ng/(Pa•s•m²))
Water Absorption ASTM C209 < 1% volume
Service Temperature -100°F to 250°F -73°C to 122°C
*Also available in 25 psi minimum, Grade 3
Foamed plastic as roof deck construction material with resistance to an internal fi re exposure only for use in construction no.(s) 120 and 123.
See UL Directory of Products Certifi ed for Canada and UL Roofi ng Materials and Systems Directory. 99DL.
** Typical properties and characteristics are based on samples tested and are not guaranteed for all samples of this product. This data and information is intended as a guide and does not refl ect the specifi cation range for any particular property of this product.
VERSICO VERSITRIM™ FASCIA SYSTEM
GENERAL:
VersiTrim is an advanced roof edge fascia specifically designed for use with Versico Roofing Systems. Its unique engineered design provides maximum protection against roof edge damage caused by high wind velocities. The fascia system consists of a heavy extruded aluminum retainer guard, corrosion resistant fasteners and a snap-on fascia cover. VersiTrim is available in two versions, one for Fully Adhered and Mechanically Attached Roofing Systems and one for Ballasted Roofing Systems. VersiTrim is an FM 1- 90 approved edging system.
TYPICAL PROPERTIES AND CHARACTERISTICS:
STANDARD BALLASTED
Style Face Coverage Style Face Coverage
VT-40 4” 2 3/8” VTB-45 4 ½” 2 ½”
VT-55 5 ½” 3 7/8” VTB-60 6” 4”
VT-70 7” 5 3/8” VTB-75 7 ½” 5 ½”
MATERIALS AND FINISHES:
Versico offers 27 standard colors of coit-coated Kynar paint on steel and aluminum in the following gauges:
24 gauge steel .040 aluminum 22 gauge steel .050 aluminum .063 aluminum*
*.063” Kynar aluminum is ONLY available in the following colors : Matte Black, Dark Bronze, Sandstone, Stone White, Bone White, and Medium Bronze.
Versico also furnishes products in these materials:
Mill Finish Aluminum: .040, .050, .063, .080, .125 Galvanized Steel (G-90 or Paint Grip): 24 gauge, 22 gauge 110 Copper: 16 ounce, 20 ounce 304 Stainless Steel (28 or Polished): 24 gauge, 22 gauge
Versico VersiTrim Fascia System TDB – Updated 1/2005 Page 1
Line
Accessories: - Factory Welded Retainer Guards, Inside & Outside Corners
- Overflow Scuppers (A or B)* ½" Extension
- Spillout Scuppers (A or B)* 4" Extension
- Downspout Scuppers (A or B)*
- * (A: Tapered) or (B: Regular/Flat)
- Fascia Extenders - 3" - 8" w/2-1/2" continuous cleat
Packaging: - Retainer Guard (per carton)
- 12' lengths
- Retainer Guard splice plates
- #12 x 1 5/8” (41.3 mm) Stainless Steel Hex Head Fasteners
- Fascia Cover
- 12' lengths
CAUTIONS AND WARNINGS:
1. Material must be kept clean and dry during storage. A protective poly film is laminated to the Kynar fascia and must be removed after installation.
2. VersiTrim should be installed above the potential ponded water level on the roof.
INSTALLATION:
See appropriate installation guide.
Versico and VersiTrim are trademarks of Versico Incorporated.
© 2005 Versico Incorporated.
Versico VersiTrim Fascia System TDB – Updated 1/2005 Page 2
Overview
DASH Bag in a Box Adhesive is a VOC-free two-component, construction-grade, insulating, polyurethane adhesive. The low-rise, expanding characteristics of DASH Bag in a Box Adhesive are designed to securely bond Versico’s VersiFleece® TPO membranes and insulations to a variety of substrates. DASH Adhesive is compatible with: fi berboard, polyiso, extruded polystyrene (XPS), expanded polystyrene (EPS), spray polyurethane foam (SPF), DensDeck®, SECUROCK® and OSB. Compatible deck types include concrete, cellular lightweight concrete, gypsum, cementitious wood fi ber, wood, and painted or galvanized steel. DASH is also compatible with the following roofi ng materials for recover applications:
weathered smooth- or gravel-surfaced BUR, mineral cap sheet, weathered smooth- or granule-surfaced Mod-Bit, weathered coal tar pitch, aged EPDM, aged TPO, aged Hypalon and Versico’s 725TR Air and Vapor Barrier. Previously unexposed asphalt vapor barriers or unexposed asphalt must be primed with CAV-GRIP™.
DASH Bag in a Box Adhesive is extruded to produce a strong, low-rise adhesive with superior wind uplift resistance and a nominal free-rise core density of 2.5 lbs.
per cu. ft.
DASH Application
Requires PaceCart 2™
1. The surface to which adhesive is to be applied shall be dry and free of fi ns, protrusions, sharp edges, loose and foreign materials, oil and grease. Depressions
T E C H N I C A L D A T A B U L L E T I N
DASH BAG IN A BOX ADHESIVE
greater than ¼" (6 mm) shall be fi lled with DASH Adhesive or other approved patching material.
All sharp projections shall be removed. Previously unexposed asphalt must be primed with CAV-GRIP for extrusion application.
2. Seal gaps between the wall/penetration and concrete deck with Versico’s 725TR or other suitable material to avoid condensation issues and positive pressure from air infi ltration.
3. For re-roofi ng sprayed-in-place (SPF) urethane roofs, all wet areas must be removed. The surface must then be scarfed or perforated, depending on the coating, before applying DASH Bag in a Box Adhesive.
4. Apply DASH Bag in a Box when substrate and ambient temperatures are 50ºF (10ºC) or above.
5. Apply DASH Bag in a Box Winter Grade when substrate and ambient temperatures are between 25°–50°F (-4°–10°C). DASH must be kept warm.
6. Remove static mixing nozzle when stopping for more than one minute. Failure to remove nozzle can cause damage to the PaceCart™.
7. High-slope applications may require adhesive to be applied to the bottom of the insulation board to avoid running.
VersiFleece® TPO Installation
Mod-Bit Method:
1. Unroll VersiFleece sheet and position. Fold sheet in half lengthwise.
2. Apply DASH Bag in a Box Adhesive to the substrate at 4", 6" or 12" on center with a minimum ½" wet bead achieving light-yellowcolored foam.
3. Once “string time” occurs, gradually feed VersiFleece sheet into DASH adhesive checking for “string body” every few feet. Stop feeding VersiFleece sheet into the adhesive when applicator reaches adhesive that has NOT developed “string body”. Immediately begin to roll membrane with a 150-lbs. weighted roller width-wise. Repeat process until VersiFleece sheet is fully installed.
A S I N G L E S O U R C E F O R S I N G L E - P LY R O O F I N G
Barn Door Method:
1. Unroll VersiFleece TPO sheet and position. Fold sheets in half width-wise and bond one sheet at a time.
2. Apply DASH Bag in a Box Adhesive to the substrate at 4", 6" or 12" on center with a minimum ½" wet bead achieving light-yellow-colored foam.
3. Allow adhesive to rise and develop string/body (approx. 1½-2 minutes), then place VersiFleece TPO membrane into DASH Adhesive. String time will vary based on environmental conditions like temperature and humidity.
4. As soon as membrane is set, roll membrane with a roller not to exceed 150 lbs. to ensure fl eece embedment. If adhesive contaminates the splice area, immediately remove with Weathered Membrane Cleaner.
REVIEW CURRENT VERSICO SPECIFICATIONS AND DETAILS
FOR SPECIFIC INSTALLATION REQUIREMENTS.
Insulation Attachment
1. Apply DASH Bag in a Box Adhesive to the substrate at 4", 6" or 12" on center with a minimum ½" wet bead achieving light-yellow-colored foam. For steel decks, extrusion of DASH must run parallel with and be on top of the steel deck fl utes.
Bead Spacing parameters for 5-, 10- or 15-year 55 mph warranties (Contact Versico Project Review for bead spacing on higher mph warranties or 20- and 30-year warranty projects.)
Building Height
Bead Spacing (Perimeter)
Bead Spacing (Field)
0' – 25' 6" o.c. (4' perimeter) 12" o.c.
25' – 50' 6" o.c. (8' perimeter) 12" o.c.
50' – 75' 6" o.c. (12' perimeter) 12" o.c.
75' – 100' 6" o.c. (16' perimeter) 12' o.c.
100' or greater: Contact Versico for bead spacing requirements
2. Factory Mutual bead spacing guidelines in the perimeter and corner may differ from the table above.
Beads at 12" o.c. are not acceptable at perimeters or corners.
3. Place insulation boards (maximum 4' x 4' insulation boards when DASH Adhesive is extruded at 12" o.c. or when boards exceed 4" thickness) into DASH Bag in a Box Adhesive after allowing it to rise between ½" to ¾" and develop string/body (approx. 1.5-2 min.). String time will vary based on environmental conditions like temperature and humidity. Do not allow the adhesive to over-cure prior to setting insulation boards.
4. Designate one person to walk boards into place and then roll the boards between 5-7 minutes from the initial adhesive application. Boards may be temporarily weighted or relief cut where necessary to keep the boards in constant contact with the adhesive until the adhesive cures.
5. At the beginning of the insulation attachment process and periodically throughout the day, check the adhesion of boards to ensure a tight bond is created and maximum contact is achieved. Allow a minimum of 30 minutes before checking boards.
Precautions
1. Review the application MSDS for complete safety information prior to use.
2. The foam produced is an organic material. It must be considered combustible and may constitute a fi re hazard. The foam adhesive must not be left exposed or unprotected. Shield from heat and sparks.
3. Do not smoke during application.
4. Use with adequate ventilation. Avoid breathing vapors. Wear a NIOSH- or MSHA-approved respirator for organic vapors with prefi lters and solvent-resistant cartridges if concentrations of MDI exceed the TLV or are unknown. Proper safety training is essential for all persons involved in the installation process. If vapor is inhaled, remove to fresh air and administer oxygen if breathing is diffi cult. Consult a physician immediately.
5. Avoid contact with eyes. Safety glasses or goggles are required. If splashed in eyes, immediately fl ush eyes with plenty of clean water for at least 15 minutes.
Contact a physician immediately.
6. Avoid contact with skin. Wear long-sleeved shirts and long pants. Wash hands thoroughly after handling.
In case of contact with skin, thoroughly wash affected area with soap and water or corn oil.
NOTE: Permeation-resistant gloves that meet ANSI/ISEA 105-2005 are required when handling the material or during application.
7. Jobsite storage temperatures in excess of 90ºF (32ºC) may affect product shelf life. Should the components be stored at temperatures lower than 55ºF (13ºC), restore to room temperature prior to use. Do not allow DASH Adhesive to freeze.
8. Previously unexposed asphalt must be primed with
CAV-GRIP.
9. KEEP OUT OF THE REACH OF CHILDREN.
ocean Typewritten Text 4" OC Beads of Versico Dash Adhesive ocean Typewritten Text
© 2014 Versico. 02.25.14 Versico, VersiFleece and the Versico logo are trademarks of Versico.
DensDeck is a trademark of Georgia Pacifi c. Securock is a trademark of USG Corporation.
Coverage Rates
VersiFleece TPO attachment to a smooth, fl at non-porous approved surface:
170 sq.ft. per gallon at 12" o.c.
95 sq.ft. per gallon at 6" o.c.
65 sq.ft. per gallon at 4" o.c.
(Sq.ft. per gallon may vary due to jobsite conditions… gravel BUR will consume twice as much adhesive.)
TYPICAL PROPERTIES AND CHARACTERISTICS
Base DASH Part A (1) Polymeric Isocyanate
DASH Part B (2) Polyols, Surfactants & Catalysts
Mixing Ratios by Volume 1:1 Part A to Part B .015"
Viscosity (CPS@25°C) 250 300-500
Avg. Net Weight 10.25 lbs/gal 8.75 lbs/gal
Packaging 5-gal box (19 L) 5-gal box (19 L)
Speeds Standard Standard (50°F and above) DASH Winter Grade (25°-50°F)
Shelf Life 1 year 1 year
VOC Content 0 g/L 0 g/L
Manufacturing Location Carlisle, PA Carlisle, PA
Typical properties and characteristics are based on samples tested and are not guaranteed for all samples of this product. This data and information is intended as a guide and does not refl ect the specifi cation range for any particular property of this product.
VSW-1
VERSICO TOTAL ROOFING Rev 8/13
SYSTEM WARRANTY
Versico, a division of Carlisle Construction Materials (h) The Versico Roofing System encounters leaks or is otherwise Incorporated (Versico), warrants to the Building Owner (Owner) of the damaged by condensation resulting from any condition within the building described below, that subject to the terms, conditions, and building that may generate moisture.
limitations stated in this warranty, Versico will repair any leak in the 4. This Warranty shall be null and void if Versico determines that Versico Total Roofing System (Versico Roofing System) installed by any of the following has occurred:
a Versico Authorized Roofing Contractor for a period of years (a) If, after installation of the Versico Roofing System by a Versico commencing with the date of Versico's acceptance of the Versico Authorized Roofing Contractor, there are any alterations, test cuts, or Roofing System installation. However, in no event shall Versico's repairs made on or through the roof, or objects such as, but not limited obligations extend beyond years subsequent to the date of to, structures, fixtures, solar panels, wind turbines, roof gardens or substantial completion of the Versico Roofing System. See below for utilities are placed upon or attached to the roof without first obtaining exact date of warranty expiration. written authorization from Versico, or The Versico Roofing System is defined as the following Versico (b) Failure by the Owner to use reasonable care in maintaining the Materials: Membrane, Flashings, Adhesives and Sealants, Fastener roof, including, but not limited to, periodic cleaning of drains and removal Assemblies, Metal Edging, Insulation, Cover Boards, Metal Work, of harmful debris from the roof, or Insulation Adhesives and any other Versico brand products utilized in (c) Owner fails to comply with every term and/or condition stated this installation. herein.
TERMS, CONDITIONS, LIMITATIONS 5. During the term of this Warranty, Versico shall have free access
1. Owner shall provide Versico with written notice via letter, fax or to the roof during regular business hours.
email to the address printed below within thirty (30) days of the 6. Versico shall have no obligation under this Warranty while any discovery of any leaks in the Roofing System. By so notifying Versico, bills for installation, supplies, services, and warranty charges have not the Owner authorizes Versico to investigate the cause of the leak. been paid in full to the Versico Authorized Roofing Contractor, Versico, Should the investigation reveal the cause of the leak to be outside the or material suppliers.
scope of this warranty, investigation and repair costs for this service 7. Versico's failure at any time to enforce any of the terms or shall be paid by the Owner. conditions stated herein shall not be construed to be a waiver of such
2. If, upon inspection, Versico determines that the leak is caused provision.
by defects in the Versico Roofing System's material or workmanship of 8. This warranty is not assignable by operation of law or otherwise.
the Versico Authorized Roofing Contractor in installing the same, Application may be made by a new building owner for reissuance of the Owner's remedies and Versico's liability shall be limited to Versico's warranty during the original warranty period. Certain procedures, repair of the leak. including an inspection of the Versico Roofing System by a Versico
3. This Warranty shall not be applicable if Versico determines that representative, and fees will apply to any reissuance. Versico reserves any of the following has occurred: the right, in its sole discretion, to refuse to reissue this warranty.
(a) The Versico Roofing System (Membrane, Insulation, or 9. Only Versico brand insulations are covered by this warranty.
Accessory) is damaged by natural disasters, including, but not limited Versico specifically disclaims liability, under any theory of law, for to, lightning, fire, insect infestations, earthquake, tornado, hail, damages sustained by or caused by non-Versico brand insulation hurricanes, or winds of (3 second) peak gust speeds of mph products.
or higher measured at 10 meters above ground, or 10. Versico shall not be responsible for the cleanliness or
(b) Loss of integrity of the building envelope and, or structure discoloration of the Versico Roofing System caused by environmental including, but not limited to partial or complete loss of roof decking, conditions including, but not limited to, dirt pollutants or biological agents.
wall siding, windows, doors or other envelope components or from roof 11. Versico shall have no liability under any theory of law for any damage by wind-blown objects, or: claims, repairs, restoration, or other damages including, but not limited
(c) The Versico Roofing System is damaged by any acts of to, consequential or incidental damages, relating, directly or indirectly, to negligence, accidents, or misuse, including but not limited to, the presence of any irritants, contaminants, vapors, fumes, molds, fungi, excessive traffic, recreational activities, storage of materials on the bacteria, spores, mycotoxins, or the like in the building or in the air, land, roof, vandalism, or civil disobedience; or or water serving the building.
(d) The Versico Roofing System is damaged by infiltration of VERSICO DOES NOT WARRANT PRODUCTS UTILIZED IN THIS moisture in, through, or around walls, skylights, vents, copings, HVAC INSTALLATION WHICH IT HAS NOT FURNISHED; AND SPECIFICALLY units, building structures, or underlying or surrounding areas; or DISCLAIMS LIABILITY, UNDER ANY THEORY OF LAW, ARISING OUT OF THE
(e) The Versico Roofing System is damaged by the building INSTALLATION AND PERFORMANCE OF, OR DAMAGES SUSTAINED BY OR
CAUSED BY, PRODUCTS NOT FURNISHED BY VERSICO OR THE PRIOR
structure failing to have adequate strength to support all live and dead EXISTING ROOFER MATERIAL OVER WHICH THE VERSICO ROOFING loads, including water and snow loads, or by any other structural SYSTEM HAS BEEN INSTALLED.
defects or failures; or THE REMEDIES STATED HEREIN ARE THE SOLE AND EXCLUSIVE
(f) The Versico Roofing System is damaged by settlement, REMEDIES FOR FAILURE OF THE ROOFING SYSTEM OR ITS COMPONENTS.
distortion, cracking, movement or failure of the roof substrate, coping, THERE ARE NO WARRANTIES EITHER EXPRESSED OR IMPLIED, INCLUDING walls, structural members or components adjacent to the roof or THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND foundation of said building; or MERCHANTABILITY, WHICH EXTEND BEYOND THE FACE HEREOF. VERSICO
SHALL NOT BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL OR OTHER
(g) The Versico Roofing System is damaged as a result of DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF PROFITS OR attack by roof top contaminants such as solvents, petroleum, oil DAMAGE TO THE BUILDING OR ITS CONTENTS UNDER ANY THEORY OF LAW.
products, acids or other harmful chemicals; or
OWNER:
BUILDING :
ROOFER:
DATE INSTALLATION COMPLETED :
DATE OF ACCEPTANCE BY VERSICO : WARRANTY NUMBER:
WARRANTY EXPIRATION DATE :
VERSICO, a division of Carlisle Construction Materials Incorporated
P.O. Box 1289 Carlisle, PA 17013
(800) 992-7663 (717) 960-4035 FAX
SAMPLE
Fax To: FRAN JACKSON Company: ABC SUPPLY CO, INC # 417 25 Spring Mill Drive Malvern, PA 19355 Phone #: 610-640-1852 Fax #: 610-640-1859Fax #: 610-640-1859 Copy To:
General Project Information:
Date Quoted: 9/23/2014 Job Name:
Location:
HOPEWELL FURNACE
Project Manager: Bill Rosado
530 JAMES STREET
LAKEWOOD, N.J. 08701
TEL: 888-827-3733 /FAX: 732-730-9450
Location:
Job #:
Tapered System Description:
Material: ISO 20 PSI Cricket Material: ISO 20 PSI Tapered Area (sq): 55.40 Cricket Area (sq): 0 Slope: 1/4" Cricket Slope: N/A Minimum Start: 0.5" Cricket Fill: N/A
RO-117-2588-X3
Project Manager: Bill Rosado
E-Mail: bill.rosado@abcsupply.com
530 JAMES STREET
LAKEWOOD, N.J. 08701
TEL: 888-827-3733 /FAX: 732-730-9450
Minimum Start: 0.5" Cricket Fill: N/A Maximum Thick: 6.8" Fill Insulation: 2" (4'x4') Total Sqs. Applied: 130.76
Total Sqs. Material: 146.08 Base Layer: NOT INCLUDED Overlay: N/A Total ISO Truckloads: 0.69
Total PERLITE Truckloads: 0.00
Avg. R-Value: 23.6 Price: *
R' Value based on new testing :R'= 5.7 per inch Valid if shipped by: 10/31/2014
* Price does not include tax or fuel surcharge (if applicable)
Notes: ANY FLAT STOCK NEEDED FOR SLOPING DECKS TO BE PRICED SEPARATELY.
IMAGE SHOWN ABOVE REFLECTS TAPERED SOLUTION'S DESIGN INTENT - ALL SUBMITTALS ARE SUBJECT TO ARCHITECT / CONTRACTOR APPROVALS.IMAGE SHOWN ABOVE REFLECTS TAPERED SOLUTION'S DESIGN INTENT - ALL SUBMITTALS ARE SUBJECT TO ARCHITECT / CONTRACTOR APPROVALS.
IMPORTANT - As a supplier of materials only, ABC Supply. does not assume responsibility for errors in design, engineering, quantities or dimensions. Architect and/or contractor shall verify all drain locations, perimeter dimensions, sizes, materials and R-values. Contractor is responsible for verifying this quote to insure that it meets job specifications. All shop drawings must be approved prior to material shipment.
| TPO Assembly-roofWarranty.pdf |
| TPO Roof Submittal |
| 1. VersiFleece TPO Membrane (tdb) |
| Hopewellroof-tapered-submittal |
| Hopewellroof-tapered.pdf |
| Hopewellroof-Taperedlayout |