JCCA_24793-9_OSFM_Approved_Drawings_-_2025-12-05.pdf
PDF 26 MB Posted
- Attached to
- MSH Central Kitchen Air Conditioning
- Solicitation number
- 0000040196
About this file
This is a set of approved construction drawings and specifications for the Department of State Hospitals (DSH) Metropolitan facility in Norwalk, California, prepared by J.C. Chang & Associates, Inc. The project involves the installation of supplemental HVAC (heating, ventilation, and air conditioning) cooling systems for the central kitchen located at Building 517, 11401 Bloomfield Avenue. The scope of work includes two new outdoor air conditioning units with piping and supports, eight new indoor mini-split wall-mounted units, new refrigerant and condensate piping, and all associated electrical infrastructure to power and control the equipment. The project is designated as JCCA #24793-9 with OSFM (Office of the State Fire Marshal) Permit Number 25-1380. The drawings were submitted as a 100% construction document submittal dated November 27, 2024, and approved by the State Fire Marshal on December 4, 2025, for fire and panic safety only. Major project milestones include mobilization, obtaining permits to install HVAC equipment, equipment submittals, and installation completion.
The project utilizes Samsung Variable Refrigerant Flow (VRF) equipment as the basis of design, with the mechanical equipment consisting of one 12-ton outdoor condensing unit (OU1), one 4-ton outdoor unit (OU2), and eight indoor units (IU1-IU8) rated at 24 MBH cooling capacity each. The electrical work requires new circuit breakers and disconnect switches fed from existing panels KP3 and PP1, with conduit and conductor sizing specified per California Electrical Code requirements. All work must comply with 2022 California Building, Mechanical, Electrical, Plumbing, and Fire codes, as well as seismic bracing requirements using pre-approved systems from manufacturers such as B-Line/Tolco, Mason Industries, or ISAT. The contractor is responsible for coordinating with all trades, verifying field conditions, submitting shop drawings for approval, performing acceptance testing, and providing as-built documentation. Fire-rated penetration details using 3M firestop systems are required where piping penetrates fire-rated assemblies, and condensate drainage must include level sensors with automatic system shutdown capabilities in the event of overflow.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| MSH_IFB_26-20063_Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T0.1
TITLE SHEET
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :5
A
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 T
V3
SITE PLAN VICINITY MAP
SCOPE OF WORK (NOT LIMITED TO)
11401 BLOOMFIELD AVENUE, NORWALK, CALIFORNIA 90650
DEPARTMENT OF STATE HOSPITALS - METROPOLITAN
OSFM PERMIT NUMBER: 25-1380
DEPARTMENT OF STATE HOSPITALS
1. CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 33 - FIRE SAFETY
DURING CONSTRUCTION OF THE 2022 CALIFORNIA FIRE CODE.
FIRE SAFETY DURING CONSTRUCTION
PROJECT'S MAJOR MILESTONES:
A. PROJECT MOBILIZATION
B. OBTAIN PERMIT TO INSTALL HVAC EQUIPMENT
C. EQUIPMENT SUBMITTALS
D. INSTALLATION OF HVAC EQUIPMENT
PROJECT MILESTONES
REFERENCE: 2022 CALIFORNIA FIRE CODE
1. SEE OVERALL SITE PLAN FOR SITE ACCESS FOR BOTH PUBLIC RIGHT OF WAY AND DSH FIRE
DEPARTMENT.
2. TURNAROUND CAN BE ACCOMPLISHED BY USING EXISTING SITE ROADS. SEE T0.3.
FIRE APPARATUS ACCESS
SEE MECHANICAL SHEETS & T0.2 FOR SEISMIC NOTES.
SEISMIC NOTES
THE SCOPE OF WORK INCLUDES, BUT NOT LIMITED TO:
MECHANICAL SCOPE:
1. PROVIDE AND INSTALL SUPPLEMENTAL COOLING FOR THE CENTRAL KITCHEN.
1.1. TWO (2) NEW OUTDOOR AIR CONDITIONING UNITS WITH PIPING AND SUPPORTS
1.2. EIGHT (8) NEW INDOOR MINI-SPLIT UNITS WALL-MOUNTED OVERHEAD.
1.3. NEW REFRIGERANT AND CONDENSATE PIPING
ELECTRICAL SCOPE:
1. PROVIDE AND INSTALL ALL ELECTRICAL ITEMS REQUIRED TO POWER NEW MECHANICAL
EQUIPMENT.
2. PROVIDE CONDUIT AND CONDUCTORS AS REQUIRED BY MECHANICAL PLANS.
SUPPLEMENTAL HVAC
517 CENTRAL KITCHEN
PROJECT INFORMATION
DRAWING INDEX
1. NO DEFERRED APPROVAL ON THIS PROJECT
DEFERRED APPROVALS
APPLICABLE CODES AND STANDARDS
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.
7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,
TITLE 24 C.C.R.
9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
PARTIAL LIST OF APPLICABLE STANDARDS
1. NFPA 13 AUTOMATIC SPRINKLER SYSTEMS (CA AMENDED) 2022 EDITION
2. NFPA 14 STANDPIPE SYSTEM (CA AMENDED) 2022 EDITION
3. NFPA 17a WET CHEMICAL SYSTEMS 2022 EDITION
4. NFPA 20 STATIONARY PUMPS 2022 EDITION
5. NFPA 24 PRIVATE FIRE MAINS (CA AMENDED) 2022 EDITION
6. NFPA 72 NATIONAL FIRE ALARM CODE (CA AMENDED) 2022 EDITION
7. NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2022 EDITION
W/ CA AMENDMENTS
8. NFPA 101 LIFE SAFETY CODE 2022 EDITION
9. REFERENCE CODE SECTION FOR NFPA STANDARDS 2022 CBC (SFM) CHAPTER 35
REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN 2022 CBC CHAPTER 35 OR 2022 CFC
CHAPTER 80. SEE CHAPTER 35 FOR STATE OF CALIFORNIA AMENDMENTS TO NFPA STANDARDS
PREPARED FOR:
DEPARTMENT OF STATE HOSPITALS
METROPOLITAN (DSH-M)
11401 BLOOMFIELD AVENUE
NORWALK, CA 90650
DEPARTMENT OF STATE HOSPITALS (DSH)
1215 O STREET
SACRAMENTO, CA 95814
SUSANNA PETROVICH
CONSTRUCTION MANAGER
PHONE: (714) 920-0334
OFFICE: SUSANNA.PETROVICH@DSH.CA.GOV
PANG HER
CONSTRUCTION ADMINISTRATOR
CELL: (916) 508-8283
EMAIL: PANG.HER@DSH.CA.GOV
DOUGLAS AZORES
CHIEF OF PLANT OPERATION III
PHONE: (562) 651-4376
CELL: (562) 229-8326
EMAIL: PAUL.SMITH@DSH.CA.GOV
PREPARED BY:
J.C. CHANG & ASSOCIATES, INC.
ENGINEERS, ARCHITECTS AND PLANNERS
385 VAN NESS AVENUE, SUITE 208
TORRANCE, CALIFORNIA 90501
PHONE : (310) 212-7644
MECHANICAL ENGINEER OF RECORD
ROBERT NOLAN
LIC. NO. 31684
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
ELECTRICAL ENGINEER OF RECORD
HECTOR LACSA
LIC. NO. E18399
385 VAN NESS AVE. #208
TORRANCE, CALIFORNIA 90501
PROJECT AREA
T E L E G
R A P H
R D
TE
LE
G R A
PH
R D
F L O
R E N C
E A
V E
PIONEER BLVD.
NORWALK BLVD.
BLOOMFIELD AVE.
IM
P E R
IA
L H
W Y
SANTA ANA FW
Y
STUDEBAKER RD.
F
IR
E S T O N E B
LV
D
N O
R W
A L K
R O
S E C
R A N S A
V E
GREENSTONE AVE.
105 605
PROJECT LOCATION
NN
SHEET NO SHEET TITLE
GENERAL
T0.1 TITLE SHEET
T0.2 SEISMIC PROTECTION NOTES
T0.3 FIRE ACCESS SITE PLAN
T0.4 STATE FIRE MARSHAL TRIAGE LIST
T0.5 BUILDING INFORMATION, BLDG. 517 SITE PLAN
MECHANICAL
M0.1 MECHANICAL GENERAL NOTES
M0.2 MECHANICAL EQUIPMENT SCHEDULES
M2.1 MECHANICAL NEW WORK PLAN
M3.1 MECHANICAL DETAILS
M3.2 MECHANICAL DETAILS
M3.3 MECHANICAL REFERENCE PHOTOS
M5.1 TITLE 24 MANDATORY MEASURES
M5.2 TITLE 24
ELECTRICAL
E0.1 ELECTRICAL COVER SHEET
E0.2 ELECTRICAL PANEL SCHEDULES
E2.1 ELECTRICAL NEW WORK PLAN
E3.1 FIRE RATED PENETRATION DETAILS
1. THIS PROJECT IS UNDERTAKEN SOLELY FOR THE PURPOSE OF ADDING SUPPLEMENTAL AIR
CONDITIONING TO THE KITCHEN AREA. THIS PROJECT IS EXEMPT PER ACCESSIBILITY CODE
PROVISION AND DOES NOT REQUIRE DSA ACCESS COMPLIANCE REVIEW OR APPROVAL UNDER
DSA IR 11B-6. THIS PROVISION INCLUDES MECHANICAL ONLY PROJECTS THAT CONTAIN
INCIDENTAL STRUCTURAL UPGRADES REQUIRED SOLELY FOR THE PURPOSE OF PERFORMING
MECHANICAL ONLY WORK. HOWEVER, COMPLIANCE WITH THE CALIFORNIA BUILDING CODE IS
STILL REQUIRED AND PROVIDED.
DSA EXEMPTION NOTES
BUILDING PHOTO
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1380
T0.2
SEISMIC PROTECTION
NOTES
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E M a r :2
A
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 T
V3
SEISMIC PROTECTION NOTES
1. ONLY ONE PRE-APPROVED BRACING SYSTEM SHALL BE USED FOR A RUN OF PIPE, DUCT, OR
CONDUIT. COMPONENTS OF TWO OR MORE BRACING SYSTEMS SHALL NOT BE MIXED. A COPY
OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION GUIDE/MANUAL SHALL BE ON THE
JOBSITE PRIOR TO STARTING THE INSTALLATION OF HANGERS AND/OR BRACES. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO OBTAIN COPIES OF HCAI PEER REVIEW PRE-APPROVALS
AND FURNISH THE OWNER WITH A COPY OF EACH.
2. IF AN HCAI PEER REVIEW PRE-APPROVED BRACING SYSTEM IS UTILIZED, PROVIDE COPIES OF
PRE-APPROVED DETAILS ON JOB SITE PRIOR TO STARTING INSTALLATION OF THE COMPONENT
OR SYSTEM.
3. IN NEW WORK AREAS AND LIMITED NEW WORK AREAS ALL NEW PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC. SHALL BE SEISMICALLY BRACED (SEE NOTE 4 BELOW).
4. SEISMIC ANCHORAGE OF ALL NEW PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC.
SHALL BE BY ONE OF THE FOLLOWING MANUFACTURERS IN ACCORDANCE WITH THE 2022 CBC
AND THE LATEST ISSUE OF "ENGINEERED SEISMIC BRACING OF SUSPENDED UTILITIES" AS
PUBLISHED BY THE INTERNATIONAL SEISMIC APPLICATION TECHNOLOGY (ISAT). APPROVED
MANUFACTURERS INCLUDE: ISAT OPM-0403-13, MASON INDUSTRIES OPM-0043-13,
B-LINE/TOLCO OPM-0052-13, OR EQUAL.
5. DEFERRED APPROVAL - LAYOUT DRAWINGS, SHOWING THE BRACING/SUPPORT LOCATIONS
AND REFERENCES TO DETAILS FROM THE RELEVANT HCAI PEER REVIEW PRE-APPROVALS FOR
PIPING/DUCTS/CONDUITS EXCEPT FIRE SPRINKLERS, NEED TO BE SUBMITTED FOR USE BY THE
INSPECTOR IF RECORD (IOR) (IF APPLICABLE FOR THIS PROJECT) AND OWNER. THE LAYOUT
DRAWINGS, PREPARED PER ASCE 7 CHAPTER 13 AS MODIFIED BY CBC SECTIONS 1613A/1615A, NEED TO BE REVIEWED AND ACCEPTED BY THE OWNER PRIOR TO STARTING INSTALLATION OF
THE BRACING/SUPPORT. IOR (IF APPLICABLE FOR THIS PROJECT) SHALL ENSURE THE ABOVE
REQUIREMENTS ARE SATISFIED.
6. FOR ALL NEW SEISMIC BRACING OF PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC., A COPY OF EACH BRACING SYSTEM INSTALLATION GUIDE/MANUAL SHALL BE ON THE JOBSITE
PRIOR TO STARTING THE INSTALLATION.
7. CONTRACTOR SHALL PROVIDE CALCULATIONS AND DETAILS FOR THE SUPPORT AND BRACING
OF ALL PIPES, DUCTS, EQUIPMENT AND CONDUITS. SHOP DRAWINGS SHALL INCLUDE ALL
BRACING AND SUPPORT LOCATIONS AND REFERENCES TO DETAILS FROM RELEVANT HCAI
PEER REVIEW PRE-APPROVALS AND SHALL BE SUBMITTED TO THE IOR (IF APPLICABLE FOR
THIS PROJECT) AND OWNER.
8. THE IOR (IF APPLICABLE FOR THIS PROJECT) SHALL ASSURE THAT THE FIELD INSTALLATION
CONFORMS TO APPROVED SUBMITTED DETAILS.
9. ONCE EXACT LOCATIONS OF ALL CONDUIT HAVE BEEN ESTABLISHED, THE ENGINEER OF
RECORD (EOR) MUST CHECK THE ADEQUACY OF THE SUPPORTING STRUCTURE TO ENSURE
THAT THE ORIGINAL DESIGN IS STILL ADEQUATE. THE INSPECTOR OF RECORD SHALL ENSURE
THAT ALL WORK IS PROPERLY INSTALLED PER THE APPLICABLE HCAI PEER REVIEW
PRE-APPROVAL.
10. SPECIAL INSPECTION SHALL BE PERFORMED BY SPECIAL INSPECTOR IN ACCORDANCE WITH
CBC 1705A.12.4 FOR SPECIAL SEISMIC CERTIFICATION.
PRE-APPROVED COMPONENT AND SYSTEM LIMITATIONS:
A. SOME PRE-APPROVALS HAVE LIMITATIONS THAT REQUIRE EITHER A DEFERRED SUBMITTAL
COMMENT ON LAYOUT DRAWINGS AND COMPONENT DESIGN OR A PRE-ENGINEERED DESIGN
THAT IS A PART OF THE CONTRACT DOCUMENTS. ALL OF THE PRE-APPROVED SYSTEMS
REQUIRE THAT THE SEISMIC LATERAL FORCE, Fp, INCLUDING CONSIDERATION OF Ap AND Rp BE
DETERMINED AT EACH LEVEL OF THE BUILDING SO THAT BRACE SPACING AND ANCHORAGE
REQUIREMENTS CAN BE DETERMINED. PROVIDE ALL PARAMETERS REQUIRED TO COMPUTE Fp (e.g. Ap,Rp,Sps,Ip,h AND z AT EACH LEVEL) ON THE SHOP DRAWINGS.
PRE-APPROVED PIPE, DUCT, AND CONDUIT BRACING:
A. SHOP DRAWINGS OF THE SUPPORT AND BRACING SYSTEMS PER THE PRE-APPROVAL SHALL BE
SUBMITTED TO THE DISCIPLINE IN RESPONSIBLE CHARGE OF THE PROJECT FOR REVIEW TO
VERIFY THAT THE DETAILS ARE IN CONFORMANCE WITH ALL CODE REQUIREMENTS. THE SHOP
DRAWINGS SHALL BE IN ACCORDANCE WITH ASCE 7-16 SECTION 13.6.
a) A "SHOP DRAWING STAMP" MAY BE USED TO INDICATE COMPLIANCE WITH THIS
REQUIREMENT.
b) THE REGISTERED DESIGN PROFESSIONAL (OTHER THAN SEOR) MAY PROVIDE THE SHOP
DRAWING STAMP FOR SMALL INSTALLATIONS AT THE DISCRETION OF THE SEOR.
B. THE CONTRACTORS STRUCTURAL ENGINEER SHALL DESIGN ANY SUPPLEMENTARY FRAMING
THAT IS NEEDED TO RESIST THE LOADS, MAINTAIN STABILITY AND/OR IS REQUIRED FOR
INSTALLATION OF PRE-APPROVED SYSTEM. THE SUPPLEMENTARY FRAMING SHALL BE
SUBMITTED TO THE SEOR PRIOR TO CONSTRUCTION FOR REVIEW.
C. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON THE JOBSITE AND
CAN THEN BE USED FOR INSTALLATION OF THE SUPPORT AND BRACING.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
X
X X X X X X X X X X
X
X
X X X X X X X X X X X X X X
X XX X X X X X X X X X X XX
X X
X
X X
X X
X X X X X X X X X X X X X X X X X X X X X
X
X
X X X X X X X X X X
X X X X X X XX X X X
XX
X
X X
X X X
X X
X
X
X
X
X
X
X X X X
XX X X XX X
XX
X X X
X X X X X X
X X X XX X X X X X X X X
X
X
X
X
X
X X
X X X
X X
X
X
X
X X X XXX X X X XX X X X X X
X X X
X X X X X X X X X X X X
X
X X X X X X X X X X X X X X
X X X X X XXX XXX X XXX
X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X
X
X X X X X XX
X
X X X X X X X X X
X XX X X X X X X X X X X
X
X X
X
X
X
X
X
X X X X X
X
X X X X X
X
X X X X X X
X X
X X X
X
X X
X
X
X
X
X X
X
X
X X X X X
X
X X X X X X X X X X X X X X X
R-20
R-12
G-12
R-11
G-10
R-10
305/307
GB-5
515 309/311
306/308 516 /2
/2
/2
/2
/2
PW-1
PW-3
EB-1
GB-8
GB-3GB-4
GB-6
R-1
R-5R-6
R-8
R-15
R-13
R-16
R-17
G-16
G-13
G-14
G-15
536542
CEDAR ST
BLOOMFIELD AVE
/2
5T H S
T
T H
S T
NORWALK BLVD
528GB-14
S-1
S-7
S-8
S-6
S-5
564565
S-11 S-12
CS-1 - CS-2
CS-3
S-4
S-3
S-2
MB-1
CS-7 - CS-10
CS-11
S-13
S-9 S-10
S-14
GB-9
GB-11
GB-12
GB-13
MB-3
T H
S T
S O U T H C
IR
C L E D
R
ELM
ST
N O R T H C
IR
C
LE
D R
S-15
S-16
S-19
S-20
S-17
S-18
S-21
S-22
CS-16
CS-5 -
CS-6
CS-15
CS-4
S-24
S-23
MB-4
CTW
CTE SNF
DATE ST
T H
S T
H
S T
T H
S T
T H
S T
R-14
313/315
EB-2
NORTH CIRCLE
DR
R
D
S T
GB-10
BALSAM ST
T H
S T
T H
S
201/203
N
D S
T
CHP FUTURE
LOCATION
FUTURE
SUPPORT
BUILDINGS
HPD
FUTURE
LOCATION
GB-1
R-7
FIR ST
FIR ST
BALSAM ST
CS-13
CS-14
MB-2
DATE
ST
CS-19
S-25
PLOPS
WAREHOUSE
X X
X X
T H S
T
CS-17
CS-18
T H
S T
X
X X X
X X X
T0.3
FIRE ACCESS SITE PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E J u n
:5
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 T
V3
FIRE ACCESS SITE PLAN
SCALE: N0 24020 FEET120
1" = 120'
SITE ACCESS FROM PUBLIC RIGHT OF WAY AND
FROM FIRE APPARATUS ROUTE USING EXISTING
PAVED ROADS
LEGEND:
FIRE TRUCK ROUTE
(E) FIRE HYDRANT
(E) FIRE HYDRANT
GENERAL NOTE:
1. PROTECT 20FT FIRE LANES DURING CONSTRUCTION.
BUILDING 517
FOR REFERENCE ONLY
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
T0.4
STATE FIRE MARSHAL
TRIAGE LIST
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E J u n
:1
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 T
V3
NOT APPLICABLE
ALL FLOOR PLANS ARE 1/8" SCALE MINIMUM. ALL SITE PLANS ARE 1"=30'
ADOPTED CODE CYCLE LISTINGS ARE INCLUDED ON TITLE SHEET
SITE PLAN IS ORIENTED TO NORTH, INDIVIDUAL DRAWINGS HAVE KEYPLAN
NORTH ORIENTED SITE PLAN IS PROVIDED
SITE KEY PLAN IS PROVIDED
SCOPE OF WORK IS INCLUDED ON TITLE SHEET
ELECTRONIC SIGNATURE PROVIDED ON DOCUMENT
SHEET INDEX IS ON T0.1
NOT APPLICABLE
PROJECT IS NOT PHASED
OSFM NO IS NOTED ON THE TITLE SHEET
NOT APPLICABLE
BUILDING 517: EXISTING TENANT SPACE
BUILDING 517: TENANT IMPROVEMENT
3102 HIGHLAND AVE., PATTON, CA 92369
SHEET SIZE: 42"X30"
TWO (2) PLAN REVIEW APPLICATIONS PROVIDED WITH SUBMITTAL
NOT APPLICABLE
OWNER: DEPARTMENT OF STATE HOSPITALS
OCCUPANT: DEPARTMENT OF STATE HOSPITALS
PROVIDE APPROVED REFERENCE PLANS/DOCUMENTATION
PROVIDE A LEGIBLE SCALE. TYPICALLY 1/8"
PROVIDE ADOPTED CODE CYCLE LISTINGS AND STANDARDS
ORIENTATE ALL SHEETS TO NORTH
PROVIDE A NORTH ORIENTED SITE MAP
PROVIDE A KEY PLAN COORDINATED TO EACH SHEET
SCOPE OF WORK
WET STAMP AND SIGN SHEETS
SHEET INDEX
SLIP SHEETS SHALL BE BOUND TO SET
PROJECT IS A PHASED SUBMITTAL
ADD OSFM FILE NUMBER TO TITLE SHEET
IDENTIFY IF DEFERRED SUBMITTAL
IDENTIFY IF NEW OR EXISTING TENANT SPACE
IDENTIFY IF NEW CONSTRUCTION OR T.I
PROVIDE NAME OF OWNER AND OCCUPANT
PROVIDE SITE ADDRESS
SUBMIT PLANS SUFFICIENT SIZE
PROVIDE A COMPLETE PLAN REVIEW APPLICATION
SEE FOR SPECIFIC SECTION COMMENTS
ALL RELEVANT
SHEETS
T0.1
ALL RELEVANT
SHEETS
T0.3
ALL RELEVANT
SHEETS
T0.1
ALL SHEETS
T0.1
T0.1
T0.1
T0.1
ALL RELEVANT
SHEETS
SUBMITTAL RESPONSE SUBMITTAL REQUIREMENTS REFERENCEITEM
GENERAL
SUBMITTAL RESPONSESUBMITTAL REQUIREMENTS REFERENCEITEM
ACCESS AND WATER SUPPLY
PROVIDE LOCAL FIRE AUTHORITY APPROVAL LETTER
FIRE DEPARTMENT ACCESS
FIRE DEPARTMENT CONNECTION
FIRE HYDRANTS
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
KNOX BOX/KEY SWITCH
EMERGENCY RESPONDER RADIO COVERAGE
ELEVATOR GURNEY ACCOMODATION
PROVIDE A COMPLETE FIRE ACCESS PLAN
PROVIDE 6 MO. CURRENT SITE FIRE FLOW INFORMATION
PROVIDED ON FIRE ACCESS SITE PLAN
T0.3
NOT APPLICABLE
NOT APPLICABLE
LOCAL FIRE DEPARTMENT SHOWN ON SITE PLAN
NOT APPLICABLE
ALL BUILDINGS ARE FIRE TRUCK ACCESSIBLE USING EXISTING ROADS
NOT APPLICABLE
T0.3
T0.3
T0.3
PROVIDED ON FIRE ACCESS SITE PLAN
NOT AVAILABLE - USE FIRE HYDRANTS
NOT AVAILABLE
T0.4NOT APPLICABLE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
X XX X
30' TYP.
T0.5
BUILDING INFORMATION
BLDG. 517 SITE PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :0
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 T
V3
BUILDING 517 SITE PLAN
SCALE: N0 100 5 FEET50
1" = 50'
BLDG
LEGEND:
SETBACK
(E) FIRE
HYDRANT
(E) FIRE
HYDRANT
(E) FIRE
HYDRANT
BUILDING INFORMATION
BUILDING NAME
CONSTRUCTION
TYPE
NUMBER
OF STORIES
BUILDING
AREA
IN SQ. FT.
SEPARATED /
NONSEPARATED
SPRINKLER
COVERAGE
FIRE ALARM
OTHER
PROTECTION
SYSTEM
SMOKE
CONTROL
SYSTEM
OCCUPANT
LOAD
YEAR BUILDING
CONSTRUCTED
HIGH FIRE
HAZARD
SEVERITY ZONE
SEISMIC JOINT
EMERGENCY
RESPONDER RADIO
COVERAGE
OCCUPANCY
GROUP
BUILDING 517 1 38' 27,232 161 2007 NO NO YES
BUILDING
HEIGHT
NONSEPARATED YES YES NO NO
AREA OF
PROJECT
ALLOWABLE
STOREY
(CBC TABLE
504.4)
USE
KITCHEN
STORAGE
OFFICE
ALLOWABLE
AREA
(CBC TABLE
506.2)
27,000 B
S-2 V-B
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
M0.1
MECHANICAL GENERAL
NOTES
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :3
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 M
V3
1. ALL WORK SHALL COMPLY WITH THE 2022 EDITIONS OF THE CALIFORNIA BUILDING, MECHANICAL, PLUMBING, AND OTHER APPLICABLE FEDERAL, STATE AS ADOPTED AND ENFORCED BY THE AUTHORITY HAVING JURISDICTION (AHJ). IN CASE THE PLANS SHOW MORE STRINGENT REQUIREMENTS, THE PLANS SHALL GOVERN THE DESIGN, YET NOTHING ON THE DESIGN DOCUMENTS SHALL BE INTERPRETED AS
AUTHORITY TO VIOLATE CODE(S) OR REGULATION(S).
2. SUBMISSION OF BID IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER HAS EXAMINED THE JOB SITE UNDER WHICH THE CONTRACTOR WILL BE OBLIGATED TO OPERATE UNDER THIS CONTRACT. NO EXTRA CHARGE WILL BE ALLOWED FOR FAILURE OF ANY BIDDER TO EXAMINE THE SITE PRIOR TO BID.
3. WHERE USED, THE TERM "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".
4. CONTRACTOR AND SUBCONTRACTORS SHALL VERIFY ALL DIMENSIONS AT THE JOB SITE PRIOR TO
COMMENCEMENT OF ANY CONSTRUCTION. THE CONSULTANTS AND OWNER SHALL IMMEDIATELY BE
NOTIFIED OF ANY DISCREPANCIES.
5. THE CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE ALL WORK PERFORMED AND ALL EQUIPMENT AND MATERIALS FURNISHED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE
WORK BY THE OWNER'S REPRESENTATIVE.
6. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON THE DRAWINGS. TYPICAL DETAILS AND
GENERAL NOTES ARE MINIMUM REQUIREMENTS TO BE USED WHEN CONDITIONS ARE NOT SHOWN
OTHERWISE.
7. NOTES AND DETAILS ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR ON PROJECT.
8. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON DESIGN PLANS WITH
CODE REQUIREMENTS, THE MORE STRINGENT STANDARD SHALL PREVAIL.
9. CONTRACTOR SHALL FURNISH LABOR, MATERIALS, EQUIPMENT, AND TRANSPORTATION AS REQUIRED TO PROPERLY INSTALL ALL NEW HVAC SYSTEMS OR RELATED COMPONENTS AS INDICATED ON PLANS AND
SPECIFIED HEREIN.
10. ALL NEW EQUIPMENT AND MATERIAL TO BE INSTALLED AS PART OF THE RENOVATION SHALL BEAR AN UNDERWRITERS LABORATORIES LABEL (UL), AND INSTALLED IN THE APPROVED MANNER FOR WHICH THEY
ARE DESIGNED.
11. CONTRACTOR SHALL DOCUMENT AND RELAY ANY MAJOR DEVIATIONS FROM THE DESIGN DOCUMENTS, AND ATTAIN APPROVAL FROM THE E.O.R. BEFORE PROCEEDING. AS-BUILT COPIES SHALL BE PROVIDED INDICATING ALL CHANGES AND DEVIATIONS MADE DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE
COMPLETED AS-BUILT DRAWINGS TO E.O.R. FOR RECORD AND PUBLISHING.
12. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARE SHALL BE EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TO OTHER AREAS OF THE BUILDING WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS BY MEANS TO KEEP DUST AND DIRT WITHIN THE
CONSTRUCTION AREA.
13. NO PIPING, EQUIPMENT, ETC. SHALL BE REMOVED, DISCONNECTED OR SHUT DOWN WITHOUT PRIOR REVIEW WITH THE OWNER'S REPRESENTATIVE TO CONFIRM THAT AREAS TO REMAIN IN OPERATION WILL NOT BE AFFECTED. IF ANY AREAS NOT WITHIN THE SCOPE OF WORK SHALL BE AFFECTED BY ANY
SHUTDOWN, REMOVAL OR DISCONNECTION, THE OWNER NEEDS ADVANCE NOTICE PER APPROVAL
SCHEDULE.
14. THE ARRANGEMENT OF EQUIPMENT, DUCTWORK, AND PIPING SHOWN ON THE DRAWINGS IS BASED UPON INFORMATION AVAILABLE TO THE ENGINEER AT THE TIME OF DESIGN AND IS NOT INTENDED TO SHOW
EXACT DIMENSIONS PECULIAR TO A SPECIFIC MANUFACTURER. THE DRAWINGS ARE, IN PART,
DIAGRAMMATIC AND SOME FEATURES OF THE ILLUSTRATED EQUIPMENT INSTALLATION MAY REQUIRE REVISION TO MEET ACTUAL EQUIPMENT INSTALLATION REQUIREMENTS. STRUCTURAL SUPPORTS, FOUNDATIONS, CONNECTED PIPING, VALVES, PIPE SUPPORTS AND ELECTRICAL CONDUIT SPECIFIED MAY
HAVE TO BE ALTERED OR ADDITIONAL ITEMS REQUIRED TO ACCOMMODATE THE EQUIPMENT PROVIDED.
NO ADDITIONAL PAYMENT WILL BE MADE FOR SUCH REVISIONS, ALTERATIONS AND ADDITIONS.
15. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AT THE SITE MAKING FIELD MEASUREMENTS AND SHOP DRAWINGS NECESSARY FOR FABRICATION AND INSTALLATION OF HVAC SYSTEMS. MAKE ALLOWANCE FOR BEAMS, PIPES AND OTHER OBSTRUCTIONS IN BUILDING CONSTRUCTION. CHECK DRAWINGS SHOWING
WORK OF OTHER TRADES AND CONSULT WITH THE STATE'S REPRESENTATIVE IN THE EVENT OF
POTENTIAL INTERFERENCE. SHOP DRAWINGS SHALL BE MINIMUM 1/4"=1'-0" SCALE, INDICATING FITTINGS, SIZES, WELDS AND CONFIGURATIONS AND SUBMITTED TO ENGINEER FOR REVIEW.
16. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES PRIOR TO FABRICATION, PURCHASE AND/OR INSTALLATION OF HIS WORK.
17. BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, ELEVATIONS, AND CHARACTERISTICS OF ALL UTILITIES.
18. THE CONTRACTOR SHALL SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.
19. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED IN NEW SYSTEMS, EXCEPT WHERE
INDICATED AS BEING RELOCATED.
20. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS.
21. GALVANIZED SHEET METAL SHALL BE PROVIDED FOR ALL HVAC DUCT SYSTEMS, AND CONSTRUCTED, SUPPORTED AND INSTALLED IN ACCORDANCE WITH THE 2022 CALIFORNIA MECHANICAL CODE AND THE
LATEST SMACNA STANDARDS.
22. ALL PIPING SHALL BE INSTALLED IN A NEAT WORKMANSHIP-LIKE MANNER AND BE SUPPORTED AS REQUIRED BY CODES. PIPING SHALL BE SET UP AND DOWN AND OFFSET AS REQUIRED TO SUIT FIELD CONDITIONS. DIELECTRIC COUPLINGS SHALL BE USED WHERE DISSIMILAR METALS ARE JOINED.
23. CONTRACTOR SHALL PROVIDE ALL NECESSARY SUPPORTS FOR FIXTURES, DUCTWORK, PIPING, AND MECHANICAL EQUIPMENT, IN ORDER TO COMPLY WITH SEISMIC REQUIREMENTS AS OUTLINED BY THE LATEST EDITION(S) OF THE CALIFORNIA BUILDING CODE, SMACNA INSTALLATION STANDARDS.
24. ALL VALVES, UNIONS, ETC. TO BE LINE SIZE UNLESS OTHERWISE INDICATED ON DRAWINGS.
25. UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH THREADED TYPE VALVE AND PRIOR TO
EQUIPMENT CONNECTIONS.
26. ALL BRACING OF DUCTS AND PIPING SHALL BE
A. INSTALLED IN ACCORDANCE WITH SMACNA GUIDELINES, OR AS DETAILED AND SPECIFIED HEREIN.
SEE SEISMIC PROTECTION NOTE SHEET FOR MORE INFORMATION.
B. WHERE BRACING DETAILS ARE NOT SHOWN ON THE DRAWINGS OR IN THE GUIDELINES, THE FIELD
INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER
27. A COPY OF THE GUIDELINES PUBLISHED BY SMACNA SHALL BE PROVIDED BY THE CONTRACTOR AND KEPT
ON THE JOB AT ALL TIMES.
28. CONTRACTOR SHALL NOT BORE, NOTCH, CUT, OR PENETRATE INTO A STRUCTURAL MEMBER WITHOUT
WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD AND STATE'S REPRESENTATIVE.
29. ALL CONDUIT AND WIRE REQUIRED FOR THE DIRECT DIGITAL CONTROL SYSTEM SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. THE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL
ELECTRICAL ITEMS REQUIRED FOR AN OPERATIONAL CONTROLS SYSTEM.
30. ALL DUCTWORK AND PIPING INSULATION SHALL MEET FIRE AND SMOKE HAZARD RATING AS TESTED UNDER PROCEDURE ASTM E-84, NFPA 255 AND UL 723 AND SHALL NOT EXCEED FLAME SPREAD RATING OF
25 AND MAXIMUM SMOKE DEVELOPED RATING OF 50.
31. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ROUTING OF ALL DUCTWORK AND PIPING AND SUBMIT DETAILED, CLEARLY LEGIBLE, FULL SIZE (MINIMUM 30"x42") DUCT AND PIPING SHOP DRAWINGS IN
AUTOCAD FORMAT FOR APPROVAL FROM THE ENGINEER PRIOR TO FABRICATION, CONSTRUCTION AND
INSTALLATION OF DUCTWORK AND PIPING.
32. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF COMPONENTS AT LEAST TWO WEEKS PRIOR TO
INSTALLATION.
33. OWNER'S REPRESENTATIVE SHALL INSPECT AND APPROVE OF ALL WORK BEFORE COVERING WITH
INSULATION OR INSTALLATION WITHIN CEILING SPACE.
34. APPROVAL OR DISAPPROVAL BY THE INSPECTOR OF RECORD DOES MEAN APPROVAL OR FAILURE TO COMPLY WITH THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. ANY DESIGN WHICH IS NOT CLEAR OR IS AMBIGUOUS SHALL BE REFERRED TO THE EOR AND OWNER FOR INTERPRETATION OR
CLARIFICATION.
35. CONTRACTOR SHALL USE ALL NECESSARY APPROVED MEANS TO PROTECT HIS PORTION OF THE WORK BEFORE, DURING, AND AFTER INSTALLATION, UNTIL ACCEPTED, AND TO PROTECT THE INSTALLED WORK
AND MATERIALS OF OTHER TRADES IN A LIKE MANNER. IN THE EVENT OF ANY DAMAGE, CONTRACTOR SHALL MAKE ALL REQUIRED REPAIRS AND REPLACEMENTS TO THE SATISFACTION OF THE EOR AND
OWNER AND AT NO ADDITIONAL COST TO THE OWNER.
36. NEITHER THE E.O.R. OR OWNER SHALL BE RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, OR FOR THE SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. ALL SUCH MATTERS ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
37. A MINIMUM OF 36" CLEAR WORKING SPACE, NOT LESS THAN 30" WIDE, SHALL BE MAINTAINED IN FRONT OF
ALL SWITCHES, OVERCURRENT PROTECTION DEVICES, AND ELECTRICAL CONTROL COMPONENTS.
38. CONTRACTOR SHALL OBTAIN AND FOLLOW ALL REQUIREMENTS, GUIDELINES, RULES, AND PROCEDURES
FOR CONSTRUCTION.
39. DEMOLITION OF ANY EXISTING AC UNITS, DUCTWORK, AND PIPING SHALL BE COORDINATED WITH
FACILITIES AND OPERATIONS. CONTRACTOR SHALL SCHEDULE WORK TO MINIMIZE SHUT-DOWN OF
EXISTING UNITS.
40. EXISTING SURFACES AND AREAS NOT INCLUDED IN THE WORK AREA SHALL BE PROTECTED FROM DAMAGE
BY APPROVED MEANS. IF DAMAGE OCCURS, THE DAMAGE SHALL BE REPAIRED BY THE CONTRACTOR TO
SATISFACTION OF THE E.O.R. AND OWNER AND AT NO ADDITIONAL COST TO THE OWNER.
41. REMOVE ALL SURPLUS MATERIALS, EQUIPMENT AND DEBRIS INCIDENTAL TO THIS PROJECT AND LEAVE
THE PREMISES CLEAN AND ORDERLY UPON COMPLETION OF WORK.
42. UPON COMPLETION OF PIPING, BUT PRIOR TO APPLICATION OF INSULATION, THE CONTRACTOR SHALL TEST THE PIPING SYSTEMS FOR LEAKS. EQUIPMENT WHICH MAY BE DAMAGED BY THE SPECIFIED TEST
CONDITIONS SHALL BE ISOLATED.
43. ON INSULATED PIPING: ALL VALVES HANDLES, AIR VENTS AND PRESSURE/ TEMPERATURE READOUT
PORTS TO BE PROVIDED WITH 2" EXTENSION TO CLEAR PIPING INSULATION.
44. ALL EXISTING DUCTING TO REMAIN SHALL BE CLEANED
45. CONTRACTOR SHALL COORDINATE WITH OWNER TO SCHEDULE INSTALLATION OF INDOOR UNITS DURING
OFF-HOURS. NO HEAVY EQUIPMENT SHALL BE USED DURING INSTALLATION.
46. REFRIGERANT PIPING AND ALL JOINTS INSTALLED ON THE PREMISES SHALL BE LEFT EXPOSED TO VIEW FOR VISUAL INSPECTION AND SHALL NOT BE COVERED OR ENCLOSED UNTIL THE REQUIRED INSPECTION
HAS BEEN COMPLETED AND APPROVED BY THE AUTHORITY HAVING JURISDICTION, IN ACCORDANCE WITH
CMC SECTION 1109.8.
47. PIPING AND TUBING SHALL BE SECURELY FASTENED TO A PERMANENT SUPPORT WITHIN 6 FEET
FOLLOWING THE FIRST BEND IN SUCH TUBING FROM THE COMPRESSOR AND WITHIN 2 FEET OF EACH
SUBSEQUENT BEND OR ANGLE.
48. BASIS OF DESIGN CONTACT:
LENNOX COMMERCIAL
RAMIRO RODRIGUEZ
PH: 951-491-9195
EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM
GENERAL NOTES
AFF ABOVE FINISHED FLOOR
BDD BACKDRAFT DAMPER
BSC BIOSAFETY CABINET
CD CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
CFSD COMBINATION FIRE/SMOKE DAMPER
CV CONTROL VALVE
(A) EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMP.
°F FAHRENHEIT
FC FAN COIL UNIT
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FS FIRE SPRINKLER
FT FEET
GPM GALLONS PER MINUTE
HHWS HEATING HOT WATER SUPPLY
HHWR HEATING HOT WATER RETURN
HTS HIGH TEMP. WATER SUPPLY
HTR HIGH TEMP. WATER RETURN
HOA HAND/OFF/AUTO SWITCH
HP HORSEPOWER
HR HOUR
IN INCHES
IN. W.C. INCHES OF WATER COLUMN
KW KILOWATT
L LENGTH
(L) LINER
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LWT LEAVING WATER TEMP.
MAX MAXIMUM
MIN MINIMUM
MUA MAKEUP AIR
(N) NEW
OSA OUTSIDE AIR
dP DIFFERENTIAL PRESSURE
PH PHASE
QTY QUANTITY
RA RETURN AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
SA SUPPLY AIR
SD SMOKE DETECTOR
SF SUPPLY FAN
SR SUPPLY REGISTER
SQFT. SQUARE FEET
TI TEMPERATURE INDICATOR
TT TEMPERATURE TRANSDUCER
TYP TYPICAL
TSP TOTAL STATIC PRESSURE
V VOLTS
VAV VARIABLE AIR VOLUME
VEL VELOOWNER
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VP VELOOWNER PRESSURE
WG WATER GAUGE
WT WEIGHT
LIGHT, THIN LINES INDICATE EXISTING.
HEAVY, THICK LINES INDICATE NEW.
HEAVY, SHORT DASHED INDICATE
DEMOLITION OR REMOVAL.
THIS SYMBOLOGY TO BE USED BY MECHANICAL AND LAYOUT FOR ALL FLOOR PLANS,
EQUIPMENT, DEVICES, UTILITIES, ETC., SHOWN ON DRAWINGS.
ABBREVIATIONS MECHANICAL SYMBOL LIST
TYPICAL PLAN LEGEND
FLEXIBLE DUCT
AIR VOLUME IN CFM
RETURN CEILING GRILLE
EXHAUST CEILING GRILLE
DUCT SIZE IN INCHES
TYPE OF DIFFUSER OR GRILLE
10"ØA
SUPPLY CEILING DIFFUSER
ELBOW W/TURNING VANES
RECTANGULAR TO ROUND TRANSITION
MANUAL VOLUME DAMPER
EXISTING DUCT TO REMAIN
SPLITTER VANES OR MITTERED
SHORT RADIUS ROUND ELBOW W/
EXISTING DUCTWORK TO BE REMOVED
NEW DUCTWORK
"Ø
MOTORIZED DAMPER
VD
FSD FIRE/SMOKE DAMPER
VOLUME DAMPER, MANUAL
SIDE POINTED TO
DUCT SIZE - FIRST DIMENSION IS FOR
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST AIR DUCT SECTION
ROUND DUCT SECTION
24"x12"
"Ø
HVAC SYMBOLS
DESCRIPTIONDOUBLE LINE SINGLE LINE
SYMBOL
DESCRIPTIONSYMBOL
DESCRIPTION
POINT OF CONNECTION
POINT OF DISCONNECTION
NEW WORK KEYNOTE1
DEMOLITION KEYNOTE
CONTROL PANEL
HUMIDITY SENSOR
THERMOSTAT SENSOR
THERMOSTAT
DUCT SMOKE DECTOR
AIR TIGHT DAMPER
SYMBOL DESCRIPTION
REFRIGERANT: R-410A
ALLOWABLE QUANTITY PER CMC 1102.3: 26-LBS PER1,000 CF OF SPACE
SMALLEST AREA FOR POTENTIAL LEAK
ROOM: 107 - WOMEN'S RESTROOM
DIMENSIONS (LxWxH): 20' 8" X 9' 6" X 9'
VOLUME (CF): 1,767
ALLOWABLE REFRIGERANT QTY: 45.942-LBS
POUNDS (LBS) OF REFRIGERANT IN SYSTEM
LINEAR DENSITY LENGTH QTY
REFRIGERANT LOCATION (LBS/FT) (FT) (LBS)
EQUIPMENT CHARGE: 23.100
PIPE - 1/2" LIQUID 0.098 85 8.345
PIPE - 3/8" LIQUID 0.055 40 2.209
PIPE - 1-1/8" SUCTION 0.002 85 0.153
PIPE - 5/8" SUCTION 0.001 40 0.022
ACCESSORIES/BUFFER 2.000
TOTAL 35.829
SYSTEM OK
REFRIGERANT CONCENTRATION LIMIT
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
M0.2
MECHANICAL EQUIPMENT
SCHEDULES
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :3
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 M
V3
VARIABLE REFRIGERANT FLOW (VRF) INDOOR UNIT SCHEDULE
NOTES:
SELECTION BASED ON EQUIPMENT MANUFACTURED BY SAMSUNG.
SEE OUTDOOR CONDENSING UNIT SCHEDULE FOR DETAILS REGARDING CONNECTION CAPACITY, OUTDOOR CONDITIONS AND OTHER FACTORS ASSOCIATED WITH CORRECTED CAPACITIES.
INDOOR (AIR HANDLING) UNITS SHALL BE OF THE SAME MANUFACTURER AND SHALL BE CERTIFIED FOR USE WITH EACH OTHER. REMOTE CONDENSING UNITS SHALL BE SECURELY MOUNTED AS DETAILED IN THE MANUFACTURERS
INSTALLATION MANUAL.
SIZE REFRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER DESIGN SOFTWARE AFTER ESTIMATED LINE LENGTHS THAT ARE PROVIDED AND INCLUDED IN THE REPORT.
MECHANICAL CONTRACTOR SHALL SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS BASED ON ACTUAL ROUTING OF REFRIGERANT LINES.
CORRECTED CAPACITIES ARE BASED ON THE ENTERING AIR CONDITIONS AS NOTED IN THE ABOVE TABLE.
LOCAL ZONE CONTROLLERS ARE NOTED ABOVE IN THE "LOCAL CONTROLLER" COLUMN.
THE SYSTEM SHALL CONNECT TO SAMSUNG CENTRAL CONTROL SOLUTIONS.
NOTE INDOOR UNIT SERIAL NUMBERS ON PLANS DURING INSTALL FOR FUTURE REFERENCE DURING COMMISSIONING. FOR HEAT RECOVERY SYSTEMS, ALSO NOTE WHICH PORT(S) EACH INDOOR IS CONNECTED TO.
UNIT SHALL BE MOUNTED PER MANUFACTURE'S RECOMMENDATION.
PROVIDE WITH LIQUID LEVEL SENSOR / FLOAT SWITCH AND CONTR4OL MODULE FOR UNIT SHUTDOWN IN THE EVENT OF CONDENSATE OVERFLOW.
EQUIPMENT TAG
MANUFACTURER
MODEL NO.
SAMSUNG
AM024TNVDCH/AA
R410A
REFRIGERANT
IU
RATED PERFORMANCE
23,200
IU
MBH
COOLING
(BTU/H)
23,800
HEATING
(BTU/H)
FAN
LOW
(CFM)
MID
(CFM)
HIGH
(CFM)
AIRFLOW
466.20 529.70 593.30 208/230
VOLT
PHASE
HZ
ELECTRICAL
0.50
MCA
15.00
MOP
0.40
FAN
FLA
43.00
NOISE
(dB(A))
REFRIGERANT
3/8
LIQUID
PIPE
(IN.)
5/8
GAS
PIPE
(IN.)
REMARKS
1 2 3 4 5 6 7 8 9
26.46
PRODUCT
WEIGHT
VARIABLE REFRIGERANT FLOW (VRF) OUTDOOR UNIT SCHEDULE
NOTES:
SELECTION BASED ON EQUIPMENT MANUFACTURED BY SAMSUNG.
CORRECTED CAPACITIES ARE BASED ON THE ENTERING AIR CONDITIONS AS NOTED IN THE ABOVE TABLE ALONG WITH PIPE LENGTH AND VERTICAL SEPARATION.
SYSTEM MUST BE CAPABLE OF SIMULTANEOUS HEATING AND COOLING.
REFER TO THE MANUFACTURER'S ENGINEERING TECHNICAL DATA BOOK FOR SOUND RATING DETAILS.
SIZE REFRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER DESIGN SOFTWARE AFTER ESTIMATED LINE LENGTHS ARE PROVIDED AND INCLUDED IN THE REPORT.
AIR SOURCE CONDENSING UNITS SHALL HAVE RATED CAPACITY DATA FROM -13°F - 120°F (-25°C - 48.9°C).
PROVIDE DEDICATED 16/2 STRANDED, SHIELDED COMMUNICATION WIRE BETWEEN CONDENSING UNIT, INDOOR UNIT(S), AND HEAT RECOVERY MODE CONTROL UNIT(S) (MCU).
NOTE OUTDOOR UNIT SERIAL NUMBERS ON PLANS DURING INSTALL FOR FUTURE REFERENCE DURING COMMISSIONING.
THE SYSTEM SHALL CONNECT TO SAMSUNG CENTRAL CONTROL SOLUTIONS. PROVIDE WITH SAMSUNG THERMOSTAT MODEL MWR-WG00UN.
EQUIPMENT
TAG
MANUFACTURER
MODEL NO.
SAMSUNG
AM048TXMDCH/AA
R410A
REFRIGERANT
RATED PERFORMANCE
48,000
OU
TON
COOLING
(BTU/H)
54,000
HEATING
(BTU/H)
FAN
AIRFLOW
(CFM)
3884.76 208/230
VOLT
PHASE
HZ
ELECTRICAL
29.00
MCA
50.00
MOP
SCCR
51.00
NOISE
(dB(A))
REFRIGERANT
3/8
LIQUID
PIPE
(IN.)
3/4
GAS
PIPE
(IN.)
REMARKS
1 2 3 4 5 6 7 8 9
213.85
PRODUCT
WEIGHT
DVM S ECO,
HEAT PUMP
TYPE
SAMSUNG
AM144BXVGFH/AA
R410A 144,000
OU
12 162,000 10170.00 208/230 3 60 52.60 60.00 5 60.00 1/2 1 1/8 612.89
DVM S2, HEAT
PUMP
THRU
1 2 3 4 5 6 7 8 9
INDOOR
TEMP
OUTDOOR
TEMP
47°F DB
43°F WB
NOMINAL HEATING NOMINAL COOLING
INDOOR
TEMP
OUTDOOR
TEMP
70°F DB
60°F WB
95°F DB
75°F WB
80°F DB
67°F WB
BASIS OF DESIGN CONTACT:
LENNOX COMMERCIAL
RAMIRO RODRIGUEZ
PH: 951-491-9195
EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM
BASIS OF DESIGN CONTACT:
LENNOX COMMERCIAL
RAMIRO RODRIGUEZ
PH: 951-491-9195
EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject
B.4 B.7 C C.2 C.6 D
B.4
B.7 C C.6 D D.6
HALL
RESTROOM
MEN'S
130 131
DISH WASH
UTENSIL/TRAY/
DISPATCH COOLER
INVENTORY
COOLER
MEAT
MEN
CORRIDOR
BREAKROOM
ADMIN
SUPERVISOR II
FOOD SERVICE
DIRECTOR
ASSISTANT
COPY
STORAGE/
HALL
DIRECTOR
ASSISTANT
COOK II
SUPERVISING
OFFICE
OPEN
COOK I
SUPERVISING
DIRECTOR
DIRECTOR
ASSISTANT
ROOM
ELECTRICAL
TELECOM
ROOM
MECHANICAL
FREEZER
BULK
COOLER
BULK
ASSEMBLY
CART STORAGE/
INVENTORY COOLER
FOOD BANK/
INGREDIENT CONTROL
DRY STORAGE/
HOT PREP.
COOKING/
SUPERVISOR I
FOOD SERVICE
LOBBY 102
CONFERENCE
RESTROOM
WOMEN'S
LOCKERS
CORRIDOR
HALL
WOMEN
DIETITIAN
COLD PREP.
T T
12"
MIN.
M
IN
10' MIN
10' MIN
M2.1
MECHANICAL NEW WORK
PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :3
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 M
V3
0 FEET8
1/8" = 1'-0"
4 16SCALE:
MECHANICAL NEW WORK PLAN
NEW WORK KEYNOTES:
(N) 12 TON VRF OUTDOOR UNIT. SEE DETAIL 1/M3.1 FOR MOUNTING.
(N) 4 TON VRF OUTDOOR UNIT. SEE DETAIL 5/M3.1 FOR WALL MOUNT.
(N) VRF INDOOR UNIT 10' AFF.
(N) REFRIGERANT PIPING. SEE 1/M3.1.
CONNECT CONDENSATE DRAIN TO (E) SEWER. SEE 2/M3.1
(N) CONDENSATE DRAIN PIPING. ROUTE TO NEAREST DRAIN.
CONDENSATE PIPING SHALL NOT SLANT UPWARD. SEE 2/M3.1 AND
3/M3.1
(N) EQUIPMENT PAD. SEE DETAIL 1/M3.1.
(N) THERMOSTAT W/ LOCKING COVER. COVER SHALL BE APPROVED
BY OWNER PRIOR TO INSTALLATION. PROVIDE AND INSTALL ALL
CONDUIT, WIRING, AND CONNECTIONS FOR FULL OPERATION AND
CONTROL OF EQUIPMENT. THERMOSTAT FOR SET-POINT AND
ON/OFF OPERATION. LOCATION SHOWN FOR OFFICE REFERENCE.
CONTRACTOR SHALL COORDINATE EXACT LOCATION WITH OWNER
PRIOR TO INSTALL.
INDIRECT DRAIN TERMINATION AT FLOOR SINK
(N) LEVEL SENSOR IN CONDENSATE LINE AND CONTROL MODULE
INTERLOCKED WITH VRF INDOOR UNIT POWER. VRF SHALL POWER
OFF IN THE EVENT OF CONDENSATE OVERFLOW PER CMC 310.2
N
IU
OU
OU
IU
IU
IU
IU
IU
IU
IU
3 3
1/2" LIQUID
1-1/8" SUCTION
3/8" LIQUID
5/8" SUCTION
3/4" CONDENSATE
(TYP. 8 UNITS)
TYP
6TYP
M3.1
M3.1
M3.2
M3.2
M3.2
A.8 B.4 B.7 C C.2 C.6 D E E.6
7.4
6.7
5.2
4.4
3.6
2.8
A A.8 B B.4
B.7 C C.6 D D.6
6.5
4.4
0.1
2.1
5.6
E E.7
2.4
E.9 F
E.9
7.1
HALL
RESTROOM
MEN'S
130 131
DISH WASH
UTENSIL/TRAY/
JANITOR
WASH
CART
DISPATCH COOLER
INVENTORY
ROOM
BREAD
COOLER
DAIRY/PRODUCE
COOLER
MEAT
RR
UNISEX
DOCK
RECEIVING
MEN
CORRIDOR
BREAKROOM
ADMIN
SUPERVISOR II
FOOD SERVICE
DIRECTOR
ASSISTANT
COPY
STORAGE/
HALL
DIRECTOR
ASSISTANT
COOK II
SUPERVISING
OFFICE
OPEN
COOK I
SUPERVISING
DIRECTOR
DIRECTOR
ASSISTANT
ROOM
ELECTRICAL
TELECOM
ROOM
MECHANICAL
FREEZER
BULK
COOLER
BULK
CHARGING
FORKLIFT
ASSEMBLY
CART STORAGE/
INVENTORY COOLER
FOOD BANK/
INGREDIENT CONTROL
DRY STORAGE/ 137
STORAGE
BULK DRY
HOT PREP.
COOKING/
SUPERVISOR I
FOOD SERVICE
BREAK ROOM
LOBBY 102
CONFERENCE
RESTROOM
WOMEN'S
LOCKERS
CORRIDOR
DOCK
DISPATCH
HALL
WOMEN
DIETITIAN
COLD PREP.
HALL
RESTROOM
MEN'S
130 131
DISH WASH
UTENSIL/TRAY/
JANITOR
WASH
CART
DISPATCH COOLER
INVENTORY
ROOM
BREAD
COOLER
DAIRY/PRODUCE
COOLER
MEAT
RR
UNISEX
DOCK
RECEIVING
MEN
CORRIDOR
BREAKROOM
ADMIN
SUPERVISOR II
FOOD SERVICE
DIRECTOR
ASSISTANT
COPY
STORAGE/
HALL
DIRECTOR
ASSISTANT
COOK II
SUPERVISING
OFFICE
OPEN
COOK I
SUPERVISING
DIRECTOR
DIRECTOR
ASSISTANT
ROOM
ELECTRICAL
TELECOM
ROOM
MECHANICAL
FREEZER
BULK
COOLER
BULK
CHARGING
FORKLIFT
ASSEMBLY
CART STORAGE/
INVENTORY COOLER
FOOD BANK/
INGREDIENT CONTROL
DRY STORAGE/ 137
STORAGE
BULK DRY
HOT PREP.
COOKING/
SUPERVISOR I
FOOD SERVICE
BREAK ROOM
LOBBY
CONFERENCE
RESTROOM
WOMEN'S
LOCKERS
CORRIDOR
DOCK
DISPATCH
HALL
WOMEN
DIETITIAN
COLD PREP.
KEY PLAN
N
CONTROL WIRING
END OF LINE CLEANOUT (TYP)
1/2" LIQUID
1-1/8" SUCTION
1" CONDENSATE
1/2" LIQUID
1-1/8" SUCTION
1" CONDENSATE
1/2" LIQUID
1-1/8" SUCTION
1" CONDENSATE
3/4" CONDENSATE
3/8" LIQUID
5/8" SUCTION
3/8" LIQUID
5/8" SUCTION
1" CONDENSATE
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
12/04/25
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
25-1380
AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x
INSULATE SUCTION LINE &
LIQUID LINES WITH 2" THICK
ARMAFLEX
CONTRACTOR TO VAPOR SEAL
PENETRATIONS
DRAIN LINE TO EXIT 45° @ BACK OF COIL.
EXIT FROM FREEZER AT EARLIEST
POSSIBLE DISTANCE.
INSULATED CONDENSATE
DRAIN LINE WITH 1" THICK
ARMAFLEX INSULATION. ALL
INSULATED DRAIN LINES
REQUIRE A MINIMUM 1/4 "
FALL PER FT.
NOTE:
ROUTE EACH CONDENSATE DRAIN
SEPARATELY FROM EVAPORATOR COIL TO
FLOOR SINK
CEILING SPACE
OUTSIDE
AIR FLOW
A F F
INSTALL ELECTRIC HEATER SPIRALED
AND TAPED ON FREEZER INSULATED
CONDENSATE DRAIN LINE BY
CONTRACTOR
(E) LIGHTING
M3.1
MECHANICAL DETAILS
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 24793-9
00000000000XXXX
DEPARTMENT OF STATE
HOSPITALS, METROPOLITAN
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
SUPPLEMENTAL
HVAC - CENTRAL
KITCHEN
11/27/2024
100% SUBMITTAL
DSH
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
JCCA
D A T E T
IM
E O c t :5
P
M
F
IL
E L \2
-9
C e n tr a l K it c h e n A
C D
S H
-M \C
A D
\2 M
V3
OUTDOOR CONDENSING UNIT DETAIL
NO SCALE M3.1
CONDENSATE TO TAILPIECE
M3.1
NO SCALE
CONDENSING UNIT
(E) EXTERIOR WALL
UNISTRUT P1000
ANCHORED TO
EXTERIOR WALL, 48"
OC.
INSULATED REFRIGERANT
PIPING SECURED TO
P1000 UNISTRUT W/PIPE
CLAMP
SEAL PIPE WATER TIGHT AT
SOFFIT PIPE PENETRATION
(E) ROOF
REFRIGERANT PIPING IN CEILING
TO NEW INDOOR UNITS. SEE
PLANS.
PIPE BRACE
SECTION
WALL
TO MATCH PIPE SIZE
3/4" COPPER ELBOW
INSULATE
3/4" COPPER COUPLING
DRAINAGE SYSTEM
WASTE WATER
SINK
X 1" TEE
1 1/2" X 1 1/2"
1 1/2" TAILPIECE
1 1/2" TRAP ARM
1 1/2" 'P' TRAP
1/8"/FT SLOPE
3/4" INSULATED
CONDENSATE DRAIN
FROM FCU
NOTES:
1. GENERAL CONTRACTOR SHALL SUBMIT CUT SHEETS FOR APPROVAL.
2. PROVIDE PIPE SLEEVES WHERE PIPE PENETRATES THROUGH FIRE RATED FLOOR
OR WALLS.
3. PIPING AND TUBING SHALL BE SECURELY FASTENED TO A PERMANENT SUPPORT
WITHIN 6 FEET FOLLOWING THE FIRST BEND IN SUCH TUBING FROM THE
COMPRESSOR AND WITHIN 2 FEET OF EACH SUBSEQUENT BEND OR ANGLE.
TYPICAL CONDENSATE DRAIN LINE
M3.1
NO SCALE
PIPE HANGER DETAIL
M3.1
NO SCALE
ADJUSTABLE
HALF HINGE
PART NO.
B335V-½
B335V-½
B335V-½
B335V-½
B335V-½
B335V-½
B335V-½
B335V-½
RISER
CLAMP
IN.
COPPER
TUBING SIZE
1"
1¼"
1½"
2"
2½"
3"
LONGITUDINAL BRACE
B-LINE CHANNEL
HINGE
ADJUSTABLECLEVIS HANGER
PART NO.
8"B335-2-
N/A
N/A
8"
8"
8"B335-2-
B335-2-
B335-2- 3
B3104CT-½
B3104CT-
B3104CT-1
B3104CT-1¼
B3104CT-1½
B3104CT-2
PART NO.
B3104CTPS-1
B3104CTPS-1¼
B3104CTPS-1½
B3104CTPS-2
PART NO.*
N/A
N/A
PIPE
SLEEVE
ADJUSTABLE HALF HINGE
B355V-BOLT SIZE
4"
B3373CT
4" MAX.
(101 mm)
INSTALL HANGER AT 6' MAX INTERVALS. INSTALL BRACES AT 20' MAX INTERVALS
STRUCTURAL SUPPORT FOR PIPING SEISMIC BRACING SHALL BE IN ACCORDANCE WITH OSHPD
PRE-APPROVAL DETAILS OF B-LINE SEISMIC RESTRAINTS No. OPM-0052-13, OPM-0043-13 OR
APPROVED EQUAL.
RISER CLAMP SERIES
8"
8"
8" B335-2-
B335-2-
B335-2- 3
8B335-2- 3 "
B3104CT-2½
B3104CT-3
B3104CT-3½
B3104CT-4 B3104CTPS-4
B3104CTPS-2½
B3104CTPS-3
B3104CTPS-3½
3½" B3373CT-3½
B3373CT-4
PART NO.
B3373CT-2
B3373CT-2½
B3373CT-3
B3373CT-1
B3373CT-1¼
B3373CT-1½
1"
½"
1¼"
1½"
2"
1 (MIN.)
B-LINE CHANNEL
ROD STIFFENER
3/8", MIN. ALL THREADED ROD
2½"
3"
3½"
4"
B355-2-BOLT SIZE
B3104CTPS PIPE SLEEVE
B3104CT SERIES CLEVIS HANGER
ADJUSTABLE HINGE
TRANSVERSE BRACE
*NOT INCLUDED WHEN ORDERING STANDARD B1304CT SERIES
CLEVIS HANGER.
NOTES:
COPPER
TUBING SIZE
IN.
(E) CEILING
SMOOTH
TROWEL
FINISH
4" CHAMFER TYP.
ALL AROUND
#4 @ 12" O.C.
(N) OUTDOOR
CONDENSING UNIT
PROVIDE SEISMIC
RESTRAINTS FOR
AC. ANCHOR W/
HILTI EPOXY OR
WEDGE ANCHORS
12" MIN
4" MIN
6"
MIN
ALL
AROUND
SAWCUT EXISTING ASPHALT CONCRETE
PAVEMENT. FIELD VERIFY THICKNESS.
BOTTOM
ELEVATION
ANCHOR BOLT LOCATION
(TYP. 6)
1/2" ANCHOR, 3" EMBED
PROVIDE WITH NEOPRENE
ISOLATION PAD
MINIMUM SLEEVE LENGTH OF 2
INCHES AND A MINIMUM OF A 4
INCH ANCHOR IF 3 INCHES IS
EMBEDDED. SEE INSTALLATION
INSTRUCTIONS.
FIRE RATED PIPE PENETRATION
M3.1
NO SCALE
SYSTEM NO. F-A-5028
APRIL 12, 2017
F RATING - 3 HR
T RATING - 1/2, 3/4, 1-3/4, 2-3/4 and 3 Hr (SEE ITEM 4)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 5A)
L RATING AT 400° F - LESS THAN 1 CFM/SQ FT (SEE ITEM 5A)
W RATING - CLASS 1 (SEE ITEMS 4B AND 5A)
1. FLOOR ASSEMBLY -- MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT
OR NORMAL WEIGHT (100-150 PCF OR 1600 - 2400 KG/M3) CONCRETE.
2. FIRESTOP DEVICE* -- CAST IN PLACE FIRESTOP DEVICE PERMANENTLY
EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE
ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION
INSTRUCTIONS. THE DEVICE MAY BE TRIMMED FLUSH WITH TOP SURFACE OF
FLOOR OR MAY PROJECT UP TO MAX 3-1/2 IN. (89 MM) ABOVE TOP SURFACE
OF FLOOR.
3M COMPANY -- 3M FIRE BARRIER CAST-IN DEVICE 2MCID, 3MCID, 4MCID
2A. FIRESTOP DEVICE - HEIGHT ADAPTER* -- (NOT SHOWN) - FOR USE IN
FLOORS GREATER THAN 8 IN. (203 MM) THICK. ADAPTER SNAPS ONTO TOP OF
FIRESTOP DEVICE (ITEM 2).
3M COMPANY -- 3M FIRE BARRIER CAST-IN DEVICE HEIGHT ADAPTER, 2HA, 3HA,
4HA
3. THROUGH PENETRANTS -- ONE METALLIC PIPE OR TUBING TO BE INSTALLED
CONCENTRICALLY OR ECCENTRICALLY WITHIN OPENING. PENETRANT TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR TUBES MAY BE USED:
A. STEEL PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 5 (OR
HEAVIER) STEEL PIPE.
B. IRON PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) CAST OR DUCTILE
IRON PIPE.
C. COPPER TUBING -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) TYPE L (OR
HEAVIER) COPPER TUBING.
D. COPPER PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) REGULAR (OR
HEAVIER) COPPER PIPE.
4. PIPE COVERING -- THE FOLLOWING TYPES AND SIZES OF PIPE COVERINGS
MAY BE USED WITH THE METALLIC PIPES:
A. PIPE COVERING -- NOM 1-1/2 IN. (38 MM) THICK (OR LESS) HOLLOW
CYLINDRICAL HEAVY DENSITY GLASS FIBER UNITS JACKETED ON THE
OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED
WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP
TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH
BUTT TAPE SUPPLIED WITH PRODUCT. ANNULAR SPACE BETWEEN THE
PIPE COVERING AND PERIPHERY OF OPENING OR SLEEVE SHALL BE MIN
0 IN. (0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM).
SEE PIPE AND EQUIPMENT COVERING - MATERIALS(BRGU) CATEGORY IN
THE BUILDING MATERIALS DIRECTORY FOR NAMES OF
MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE
SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH
A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED
INDEX OF 50 OR LESS MAY BE USED.
B. PVC JACKET++ -- (OPTIONAL, NOT SHOWN) -- AN ADDITIONAL PVC
JACKET, SUPPLIED IN SHEET FORM, SHALL BE TIGHTLY WRAPPED
AROUND THE ALL SERVICE JACKET ON THE PIPE COVERING (ITEM 4A)
WITH THE LONGITUDINAL SEAM CONTINUOUSLY SEALED USING THE
SELF-SEALING LAP TAPE OR ADHESIVE SUPPLIED WITH THE JACKET. THE
JACKET IS TO BE NOM 48 IN. (1.22 M) WIDE BY NOM 20 OR 30 MIL (0.5 OR
0.8 MM) THICK. THE JACKET SHALL EXTEND DOWNWARD INTO AND/OR
THROUGH THE OPENING FROM A POINT 36 TO 40 IN. (0.91 TO 1.02 M)
ABOVE THE TOP SURFACE OF THE FLOOR ASSEMBLY. THE PVC JACKET
MUST BE USED FOR THE W RATING TO APPLY.
SEE PLASTICS (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED
COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY
RECOGNIZED COMPONENT PLASTIC MATERIAL MEETING THE ABOVE
SPECIFICATIONS AND HAVING A UL 94 FLAMMABILITY CLASSIFICATION
OF 94-5VA MAY BE USED.
C. TUBE INSULATION-PLASTICS++ -- NOM 1 IN. (25 MM) THICK (OR LESS)
ACRYLONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE
FOAM FURNISHED IN THE FORM OF TUBING. ANNULAR SPACE BETWEEN
THE INSULATED PENETRATING ITEM AND THE PERIPHERY OF THE
OPENING SHALL BE MIN 0 IN. (0 MM) (POINT CONTACT) TO MAX 1 IN. (25
MM).
SEE PLASTICS (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED
COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY
RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE
ABOVE SPECIFICATIONS AND HAVING A UL 94 FLAMMABILITY
CLASSIFICATION OF 94-5A MAY BE USED.
THE HOURLY T RATINGS ARE DEPENDENT ON THE SIZE OF PIPE OR TUBE
AND THE NOM THICKNESS OF THE PIPE COVERING, AS SHOWN BELOW:
NOM PENETRANT NOM PIPE COVERING T RATING,
SIZE, IN (mm) THICKNESS, IN (mm) HR
1/2 & 3/4 (13 & 19) 1/2 & 3/4 (13 & 19) 1-3/4
1/2 & 3/4 (13 & 19) 1 & 1-1/2 (25 & 38) 3
1 (25) 1/2 & 3/4 (13 & 19) 1/2
1 (25) 1 (25) 2-3/4
1 (25) 1-1/2 (38) 3
1-1/4 TO 2 (32 TO 51) 1/2 (13) 1/4
1-1/4 TO 2 (32 TO 51) 3/4, 1 & 1-1/2 (19, 25 & 38) 1/2
5. PACKING MATERIAL -- NOT REQUIRED IF ANNULAR SPACE IS 1/4 IN. (6 MM) OR
LESS. IF ANNULAR SPACE IS GREATER THAN 1/4 IN. (6 MM), MIN 2 IN. (51 MM)
THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY
PACKED WITHIN ANNULUS, FLUSH WITH THE TOP SURFACE OF FLOOR.
5A. FILL, VOID OR CAVITY MATERIALS - SEALANT, CAULK OR PUTTY* --
(OPTIONAL, NOT SHOWN) - AS AN OPTION, THE PACKING MATERIAL (ITEM 5)
MAY BE REDUCED IN THICKNESS BY 1/4 TO 1/2 IN. (6 MM TO 13 MM) AND
RECESSED FROM THE TOP SURFACE OF FLOOR TO ACCOMMODATE A 1/4 TO
1/2 IN. (6 MM TO 13 MM) THICKNESS OF SEALANT, CAULK OR PUTTY, INSTALLED
WITHIN ANNULUS, FLUSH WITH THE TOP SURFACE OF FLOOR. IF ANNULAR
SPACES ARE LESS THAN 1/4 IN. (6 MM) AND PACKING MATERIAL IS NOT USED,
SEALANT, CAULK OR PUTTY MAY BE INSTALLED WITHIN ANNULUS, FLUSH WITH
THE TOP SURFACE OF FLOOR, BUT IS NOT REQUIRED. FOR W AND L RATINGS,
A MIN 1/4 IN. (6 MM) BEAD OF SEALANT IS REQUIRED AT THE
DEVICE/CONCRETE INTERFACE ON THE TOP SURFACE OF THE FLOOR AND A
MIN 1/4 IN. (6 MM) DEPTH OF SEALANT IS REQUIRED ATOP A MIN 1-3/4 IN. (44
MM) THICKNESS OF…