JCCA_24793-9_OSFM_Approved_Drawings_-_2025-12-05.pdf

PDF 26 MB Posted

Attached to
MSH Central Kitchen Air Conditioning
Solicitation number
0000040196
Issued by
Los Angeles County, Oakland City, East Los Angeles CDP, Lake Los Angeles CDP, Los Angeles City, California

About this file

This is a set of approved construction drawings and specifications for the Department of State Hospitals (DSH) Metropolitan facility in Norwalk, California, prepared by J.C. Chang & Associates, Inc. The project involves the installation of supplemental HVAC (heating, ventilation, and air conditioning) cooling systems for the central kitchen located at Building 517, 11401 Bloomfield Avenue. The scope of work includes two new outdoor air conditioning units with piping and supports, eight new indoor mini-split wall-mounted units, new refrigerant and condensate piping, and all associated electrical infrastructure to power and control the equipment. The project is designated as JCCA #24793-9 with OSFM (Office of the State Fire Marshal) Permit Number 25-1380. The drawings were submitted as a 100% construction document submittal dated November 27, 2024, and approved by the State Fire Marshal on December 4, 2025, for fire and panic safety only. Major project milestones include mobilization, obtaining permits to install HVAC equipment, equipment submittals, and installation completion.

The project utilizes Samsung Variable Refrigerant Flow (VRF) equipment as the basis of design, with the mechanical equipment consisting of one 12-ton outdoor condensing unit (OU1), one 4-ton outdoor unit (OU2), and eight indoor units (IU1-IU8) rated at 24 MBH cooling capacity each. The electrical work requires new circuit breakers and disconnect switches fed from existing panels KP3 and PP1, with conduit and conductor sizing specified per California Electrical Code requirements. All work must comply with 2022 California Building, Mechanical, Electrical, Plumbing, and Fire codes, as well as seismic bracing requirements using pre-approved systems from manufacturers such as B-Line/Tolco, Mason Industries, or ISAT. The contractor is responsible for coordinating with all trades, verifying field conditions, submitting shop drawings for approval, performing acceptance testing, and providing as-built documentation. Fire-rated penetration details using 3M firestop systems are required where piping penetrates fire-rated assemblies, and condensate drainage must include level sensors with automatic system shutdown capabilities in the event of overflow.

View the file

Other files

File Type Posted
MSH_IFB_26-20063_Project_Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T0.1

TITLE SHEET

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :5

A

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 T

V3

SITE PLAN VICINITY MAP

SCOPE OF WORK (NOT LIMITED TO)

11401 BLOOMFIELD AVENUE, NORWALK, CALIFORNIA 90650

DEPARTMENT OF STATE HOSPITALS - METROPOLITAN

OSFM PERMIT NUMBER: 25-1380

DEPARTMENT OF STATE HOSPITALS

1. CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 33 - FIRE SAFETY

DURING CONSTRUCTION OF THE 2022 CALIFORNIA FIRE CODE.

FIRE SAFETY DURING CONSTRUCTION

PROJECT'S MAJOR MILESTONES:

A. PROJECT MOBILIZATION

B. OBTAIN PERMIT TO INSTALL HVAC EQUIPMENT

C. EQUIPMENT SUBMITTALS

D. INSTALLATION OF HVAC EQUIPMENT

PROJECT MILESTONES

REFERENCE: 2022 CALIFORNIA FIRE CODE

1. SEE OVERALL SITE PLAN FOR SITE ACCESS FOR BOTH PUBLIC RIGHT OF WAY AND DSH FIRE

DEPARTMENT.

2. TURNAROUND CAN BE ACCOMPLISHED BY USING EXISTING SITE ROADS. SEE T0.3.

FIRE APPARATUS ACCESS

SEE MECHANICAL SHEETS & T0.2 FOR SEISMIC NOTES.

SEISMIC NOTES

THE SCOPE OF WORK INCLUDES, BUT NOT LIMITED TO:

MECHANICAL SCOPE:

1. PROVIDE AND INSTALL SUPPLEMENTAL COOLING FOR THE CENTRAL KITCHEN.

1.1. TWO (2) NEW OUTDOOR AIR CONDITIONING UNITS WITH PIPING AND SUPPORTS

1.2. EIGHT (8) NEW INDOOR MINI-SPLIT UNITS WALL-MOUNTED OVERHEAD.

1.3. NEW REFRIGERANT AND CONDENSATE PIPING

ELECTRICAL SCOPE:

1. PROVIDE AND INSTALL ALL ELECTRICAL ITEMS REQUIRED TO POWER NEW MECHANICAL

EQUIPMENT.

2. PROVIDE CONDUIT AND CONDUCTORS AS REQUIRED BY MECHANICAL PLANS.

SUPPLEMENTAL HVAC

517 CENTRAL KITCHEN

PROJECT INFORMATION

DRAWING INDEX

1. NO DEFERRED APPROVAL ON THIS PROJECT

DEFERRED APPROVALS

APPLICABLE CODES AND STANDARDS

1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.

2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.

3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.

4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.

5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.

6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.

7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.

8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,

TITLE 24 C.C.R.

9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.

10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

PARTIAL LIST OF APPLICABLE STANDARDS

1. NFPA 13 AUTOMATIC SPRINKLER SYSTEMS (CA AMENDED) 2022 EDITION

2. NFPA 14 STANDPIPE SYSTEM (CA AMENDED) 2022 EDITION

3. NFPA 17a WET CHEMICAL SYSTEMS 2022 EDITION

4. NFPA 20 STATIONARY PUMPS 2022 EDITION

5. NFPA 24 PRIVATE FIRE MAINS (CA AMENDED) 2022 EDITION

6. NFPA 72 NATIONAL FIRE ALARM CODE (CA AMENDED) 2022 EDITION

7. NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2022 EDITION

W/ CA AMENDMENTS

8. NFPA 101 LIFE SAFETY CODE 2022 EDITION

9. REFERENCE CODE SECTION FOR NFPA STANDARDS 2022 CBC (SFM) CHAPTER 35

REFERENCE CODE SECTION FOR NFPA STANDARDS ARE IN 2022 CBC CHAPTER 35 OR 2022 CFC

CHAPTER 80. SEE CHAPTER 35 FOR STATE OF CALIFORNIA AMENDMENTS TO NFPA STANDARDS

PREPARED FOR:

DEPARTMENT OF STATE HOSPITALS

METROPOLITAN (DSH-M)

11401 BLOOMFIELD AVENUE

NORWALK, CA 90650

DEPARTMENT OF STATE HOSPITALS (DSH)

1215 O STREET

SACRAMENTO, CA 95814

SUSANNA PETROVICH

CONSTRUCTION MANAGER

PHONE: (714) 920-0334

OFFICE: SUSANNA.PETROVICH@DSH.CA.GOV

PANG HER

CONSTRUCTION ADMINISTRATOR

CELL: (916) 508-8283

EMAIL: PANG.HER@DSH.CA.GOV

DOUGLAS AZORES

CHIEF OF PLANT OPERATION III

PHONE: (562) 651-4376

CELL: (562) 229-8326

EMAIL: PAUL.SMITH@DSH.CA.GOV

PREPARED BY:

J.C. CHANG & ASSOCIATES, INC.

ENGINEERS, ARCHITECTS AND PLANNERS

385 VAN NESS AVENUE, SUITE 208

TORRANCE, CALIFORNIA 90501

PHONE : (310) 212-7644

MECHANICAL ENGINEER OF RECORD

ROBERT NOLAN

LIC. NO. 31684

385 VAN NESS AVE. #208

TORRANCE, CALIFORNIA 90501

ELECTRICAL ENGINEER OF RECORD

HECTOR LACSA

LIC. NO. E18399

385 VAN NESS AVE. #208

TORRANCE, CALIFORNIA 90501

PROJECT AREA

T E L E G

R A P H

R D

TE

LE

G R A

PH

R D

F L O

R E N C

E A

V E

PIONEER BLVD.

NORWALK BLVD.

BLOOMFIELD AVE.

IM

P E R

IA

L H

W Y

SANTA ANA FW

Y

STUDEBAKER RD.

F

IR

E S T O N E B

LV

D

N O

R W

A L K

R O

S E C

R A N S A

V E

GREENSTONE AVE.

105 605

PROJECT LOCATION

NN

SHEET NO SHEET TITLE

GENERAL

T0.1 TITLE SHEET

T0.2 SEISMIC PROTECTION NOTES

T0.3 FIRE ACCESS SITE PLAN

T0.4 STATE FIRE MARSHAL TRIAGE LIST

T0.5 BUILDING INFORMATION, BLDG. 517 SITE PLAN

MECHANICAL

M0.1 MECHANICAL GENERAL NOTES

M0.2 MECHANICAL EQUIPMENT SCHEDULES

M2.1 MECHANICAL NEW WORK PLAN

M3.1 MECHANICAL DETAILS

M3.2 MECHANICAL DETAILS

M3.3 MECHANICAL REFERENCE PHOTOS

M5.1 TITLE 24 MANDATORY MEASURES

M5.2 TITLE 24

ELECTRICAL

E0.1 ELECTRICAL COVER SHEET

E0.2 ELECTRICAL PANEL SCHEDULES

E2.1 ELECTRICAL NEW WORK PLAN

E3.1 FIRE RATED PENETRATION DETAILS

1. THIS PROJECT IS UNDERTAKEN SOLELY FOR THE PURPOSE OF ADDING SUPPLEMENTAL AIR

CONDITIONING TO THE KITCHEN AREA. THIS PROJECT IS EXEMPT PER ACCESSIBILITY CODE

PROVISION AND DOES NOT REQUIRE DSA ACCESS COMPLIANCE REVIEW OR APPROVAL UNDER

DSA IR 11B-6. THIS PROVISION INCLUDES MECHANICAL ONLY PROJECTS THAT CONTAIN

INCIDENTAL STRUCTURAL UPGRADES REQUIRED SOLELY FOR THE PURPOSE OF PERFORMING

MECHANICAL ONLY WORK. HOWEVER, COMPLIANCE WITH THE CALIFORNIA BUILDING CODE IS

STILL REQUIRED AND PROVIDED.

DSA EXEMPTION NOTES

BUILDING PHOTO

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1380

T0.2

SEISMIC PROTECTION

NOTES

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E M a r :2

A

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 T

V3

SEISMIC PROTECTION NOTES

1. ONLY ONE PRE-APPROVED BRACING SYSTEM SHALL BE USED FOR A RUN OF PIPE, DUCT, OR

CONDUIT. COMPONENTS OF TWO OR MORE BRACING SYSTEMS SHALL NOT BE MIXED. A COPY

OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION GUIDE/MANUAL SHALL BE ON THE

JOBSITE PRIOR TO STARTING THE INSTALLATION OF HANGERS AND/OR BRACES. IT IS THE

CONTRACTOR'S RESPONSIBILITY TO OBTAIN COPIES OF HCAI PEER REVIEW PRE-APPROVALS

AND FURNISH THE OWNER WITH A COPY OF EACH.

2. IF AN HCAI PEER REVIEW PRE-APPROVED BRACING SYSTEM IS UTILIZED, PROVIDE COPIES OF

PRE-APPROVED DETAILS ON JOB SITE PRIOR TO STARTING INSTALLATION OF THE COMPONENT

OR SYSTEM.

3. IN NEW WORK AREAS AND LIMITED NEW WORK AREAS ALL NEW PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC. SHALL BE SEISMICALLY BRACED (SEE NOTE 4 BELOW).

4. SEISMIC ANCHORAGE OF ALL NEW PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC.

SHALL BE BY ONE OF THE FOLLOWING MANUFACTURERS IN ACCORDANCE WITH THE 2022 CBC

AND THE LATEST ISSUE OF "ENGINEERED SEISMIC BRACING OF SUSPENDED UTILITIES" AS

PUBLISHED BY THE INTERNATIONAL SEISMIC APPLICATION TECHNOLOGY (ISAT). APPROVED

MANUFACTURERS INCLUDE: ISAT OPM-0403-13, MASON INDUSTRIES OPM-0043-13,

B-LINE/TOLCO OPM-0052-13, OR EQUAL.

5. DEFERRED APPROVAL - LAYOUT DRAWINGS, SHOWING THE BRACING/SUPPORT LOCATIONS

AND REFERENCES TO DETAILS FROM THE RELEVANT HCAI PEER REVIEW PRE-APPROVALS FOR

PIPING/DUCTS/CONDUITS EXCEPT FIRE SPRINKLERS, NEED TO BE SUBMITTED FOR USE BY THE

INSPECTOR IF RECORD (IOR) (IF APPLICABLE FOR THIS PROJECT) AND OWNER. THE LAYOUT

DRAWINGS, PREPARED PER ASCE 7 CHAPTER 13 AS MODIFIED BY CBC SECTIONS 1613A/1615A, NEED TO BE REVIEWED AND ACCEPTED BY THE OWNER PRIOR TO STARTING INSTALLATION OF

THE BRACING/SUPPORT. IOR (IF APPLICABLE FOR THIS PROJECT) SHALL ENSURE THE ABOVE

REQUIREMENTS ARE SATISFIED.

6. FOR ALL NEW SEISMIC BRACING OF PIPING, CONDUIT, DUCTWORK, EQUIPMENT, PANELS, ETC., A COPY OF EACH BRACING SYSTEM INSTALLATION GUIDE/MANUAL SHALL BE ON THE JOBSITE

PRIOR TO STARTING THE INSTALLATION.

7. CONTRACTOR SHALL PROVIDE CALCULATIONS AND DETAILS FOR THE SUPPORT AND BRACING

OF ALL PIPES, DUCTS, EQUIPMENT AND CONDUITS. SHOP DRAWINGS SHALL INCLUDE ALL

BRACING AND SUPPORT LOCATIONS AND REFERENCES TO DETAILS FROM RELEVANT HCAI

PEER REVIEW PRE-APPROVALS AND SHALL BE SUBMITTED TO THE IOR (IF APPLICABLE FOR

THIS PROJECT) AND OWNER.

8. THE IOR (IF APPLICABLE FOR THIS PROJECT) SHALL ASSURE THAT THE FIELD INSTALLATION

CONFORMS TO APPROVED SUBMITTED DETAILS.

9. ONCE EXACT LOCATIONS OF ALL CONDUIT HAVE BEEN ESTABLISHED, THE ENGINEER OF

RECORD (EOR) MUST CHECK THE ADEQUACY OF THE SUPPORTING STRUCTURE TO ENSURE

THAT THE ORIGINAL DESIGN IS STILL ADEQUATE. THE INSPECTOR OF RECORD SHALL ENSURE

THAT ALL WORK IS PROPERLY INSTALLED PER THE APPLICABLE HCAI PEER REVIEW

PRE-APPROVAL.

10. SPECIAL INSPECTION SHALL BE PERFORMED BY SPECIAL INSPECTOR IN ACCORDANCE WITH

CBC 1705A.12.4 FOR SPECIAL SEISMIC CERTIFICATION.

PRE-APPROVED COMPONENT AND SYSTEM LIMITATIONS:

A. SOME PRE-APPROVALS HAVE LIMITATIONS THAT REQUIRE EITHER A DEFERRED SUBMITTAL

COMMENT ON LAYOUT DRAWINGS AND COMPONENT DESIGN OR A PRE-ENGINEERED DESIGN

THAT IS A PART OF THE CONTRACT DOCUMENTS. ALL OF THE PRE-APPROVED SYSTEMS

REQUIRE THAT THE SEISMIC LATERAL FORCE, Fp, INCLUDING CONSIDERATION OF Ap AND Rp BE

DETERMINED AT EACH LEVEL OF THE BUILDING SO THAT BRACE SPACING AND ANCHORAGE

REQUIREMENTS CAN BE DETERMINED. PROVIDE ALL PARAMETERS REQUIRED TO COMPUTE Fp (e.g. Ap,Rp,Sps,Ip,h AND z AT EACH LEVEL) ON THE SHOP DRAWINGS.

PRE-APPROVED PIPE, DUCT, AND CONDUIT BRACING:

A. SHOP DRAWINGS OF THE SUPPORT AND BRACING SYSTEMS PER THE PRE-APPROVAL SHALL BE

SUBMITTED TO THE DISCIPLINE IN RESPONSIBLE CHARGE OF THE PROJECT FOR REVIEW TO

VERIFY THAT THE DETAILS ARE IN CONFORMANCE WITH ALL CODE REQUIREMENTS. THE SHOP

DRAWINGS SHALL BE IN ACCORDANCE WITH ASCE 7-16 SECTION 13.6.

a) A "SHOP DRAWING STAMP" MAY BE USED TO INDICATE COMPLIANCE WITH THIS

REQUIREMENT.

b) THE REGISTERED DESIGN PROFESSIONAL (OTHER THAN SEOR) MAY PROVIDE THE SHOP

DRAWING STAMP FOR SMALL INSTALLATIONS AT THE DISCRETION OF THE SEOR.

B. THE CONTRACTORS STRUCTURAL ENGINEER SHALL DESIGN ANY SUPPLEMENTARY FRAMING

THAT IS NEEDED TO RESIST THE LOADS, MAINTAIN STABILITY AND/OR IS REQUIRED FOR

INSTALLATION OF PRE-APPROVED SYSTEM. THE SUPPLEMENTARY FRAMING SHALL BE

SUBMITTED TO THE SEOR PRIOR TO CONSTRUCTION FOR REVIEW.

C. THE SHOP DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON THE JOBSITE AND

CAN THEN BE USED FOR INSTALLATION OF THE SUPPORT AND BRACING.

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

X

X X X X X X X X X X

X

X

X X X X X X X X X X X X X X

X XX X X X X X X X X X X XX

X X

X

X X

X X

X X X X X X X X X X X X X X X X X X X X X

X

X

X X X X X X X X X X

X X X X X X XX X X X

XX

X

X X

X X X

X X

X

X

X

X

X

X

X X X X

XX X X XX X

XX

X X X

X X X X X X

X X X XX X X X X X X X X

X

X

X

X

X

X X

X X X

X X

X

X

X

X X X XXX X X X XX X X X X X

X X X

X X X X X X X X X X X X

X

X X X X X X X X X X X X X X

X X X X X XXX XXX X XXX

X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X

X

X X X X X XX

X

X X X X X X X X X

X XX X X X X X X X X X X

X

X X

X

X

X

X

X

X X X X X

X

X X X X X

X

X X X X X X

X X

X X X

X

X X

X

X

X

X

X X

X

X

X X X X X

X

X X X X X X X X X X X X X X X

R-20

R-12

G-12

R-11

G-10

R-10

305/307

GB-5

515 309/311

306/308 516 /2

/2

/2

/2

/2

PW-1

PW-3

EB-1

GB-8

GB-3GB-4

GB-6

R-1

R-5R-6

R-8

R-15

R-13

R-16

R-17

G-16

G-13

G-14

G-15

536542

CEDAR ST

BLOOMFIELD AVE

/2

5T H S

T

T H

S T

NORWALK BLVD

528GB-14

S-1

S-7

S-8

S-6

S-5

564565

S-11 S-12

CS-1 - CS-2

CS-3

S-4

S-3

S-2

MB-1

CS-7 - CS-10

CS-11

S-13

S-9 S-10

S-14

GB-9

GB-11

GB-12

GB-13

MB-3

T H

S T

S O U T H C

IR

C L E D

R

ELM

ST

N O R T H C

IR

C

LE

D R

S-15

S-16

S-19

S-20

S-17

S-18

S-21

S-22

CS-16

CS-5 -

CS-6

CS-15

CS-4

S-24

S-23

MB-4

CTW

CTE SNF

DATE ST

T H

S T

H

S T

T H

S T

T H

S T

R-14

313/315

EB-2

NORTH CIRCLE

DR

R

D

S T

GB-10

BALSAM ST

T H

S T

T H

S

201/203

N

D S

T

CHP FUTURE

LOCATION

FUTURE

SUPPORT

BUILDINGS

HPD

FUTURE

LOCATION

GB-1

R-7

FIR ST

FIR ST

BALSAM ST

CS-13

CS-14

MB-2

DATE

ST

CS-19

S-25

PLOPS

WAREHOUSE

X X

X X

T H S

T

CS-17

CS-18

T H

S T

X

X X X

X X X

T0.3

FIRE ACCESS SITE PLAN

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E J u n

:5

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 T

V3

FIRE ACCESS SITE PLAN

SCALE: N0 24020 FEET120

1" = 120'

SITE ACCESS FROM PUBLIC RIGHT OF WAY AND

FROM FIRE APPARATUS ROUTE USING EXISTING

PAVED ROADS

LEGEND:

FIRE TRUCK ROUTE

(E) FIRE HYDRANT

(E) FIRE HYDRANT

GENERAL NOTE:

1. PROTECT 20FT FIRE LANES DURING CONSTRUCTION.

BUILDING 517

FOR REFERENCE ONLY

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

T0.4

STATE FIRE MARSHAL

TRIAGE LIST

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E J u n

:1

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 T

V3

NOT APPLICABLE

ALL FLOOR PLANS ARE 1/8" SCALE MINIMUM. ALL SITE PLANS ARE 1"=30'

ADOPTED CODE CYCLE LISTINGS ARE INCLUDED ON TITLE SHEET

SITE PLAN IS ORIENTED TO NORTH, INDIVIDUAL DRAWINGS HAVE KEYPLAN

NORTH ORIENTED SITE PLAN IS PROVIDED

SITE KEY PLAN IS PROVIDED

SCOPE OF WORK IS INCLUDED ON TITLE SHEET

ELECTRONIC SIGNATURE PROVIDED ON DOCUMENT

SHEET INDEX IS ON T0.1

NOT APPLICABLE

PROJECT IS NOT PHASED

OSFM NO IS NOTED ON THE TITLE SHEET

NOT APPLICABLE

BUILDING 517: EXISTING TENANT SPACE

BUILDING 517: TENANT IMPROVEMENT

3102 HIGHLAND AVE., PATTON, CA 92369

SHEET SIZE: 42"X30"

TWO (2) PLAN REVIEW APPLICATIONS PROVIDED WITH SUBMITTAL

NOT APPLICABLE

OWNER: DEPARTMENT OF STATE HOSPITALS

OCCUPANT: DEPARTMENT OF STATE HOSPITALS

PROVIDE APPROVED REFERENCE PLANS/DOCUMENTATION

PROVIDE A LEGIBLE SCALE. TYPICALLY 1/8"

PROVIDE ADOPTED CODE CYCLE LISTINGS AND STANDARDS

ORIENTATE ALL SHEETS TO NORTH

PROVIDE A NORTH ORIENTED SITE MAP

PROVIDE A KEY PLAN COORDINATED TO EACH SHEET

SCOPE OF WORK

WET STAMP AND SIGN SHEETS

SHEET INDEX

SLIP SHEETS SHALL BE BOUND TO SET

PROJECT IS A PHASED SUBMITTAL

ADD OSFM FILE NUMBER TO TITLE SHEET

IDENTIFY IF DEFERRED SUBMITTAL

IDENTIFY IF NEW OR EXISTING TENANT SPACE

IDENTIFY IF NEW CONSTRUCTION OR T.I

PROVIDE NAME OF OWNER AND OCCUPANT

PROVIDE SITE ADDRESS

SUBMIT PLANS SUFFICIENT SIZE

PROVIDE A COMPLETE PLAN REVIEW APPLICATION

SEE FOR SPECIFIC SECTION COMMENTS

ALL RELEVANT

SHEETS

T0.1

ALL RELEVANT

SHEETS

T0.3

ALL RELEVANT

SHEETS

T0.1

ALL SHEETS

T0.1

T0.1

T0.1

T0.1

ALL RELEVANT

SHEETS

SUBMITTAL RESPONSE SUBMITTAL REQUIREMENTS REFERENCEITEM

GENERAL

SUBMITTAL RESPONSESUBMITTAL REQUIREMENTS REFERENCEITEM

ACCESS AND WATER SUPPLY

PROVIDE LOCAL FIRE AUTHORITY APPROVAL LETTER

FIRE DEPARTMENT ACCESS

FIRE DEPARTMENT CONNECTION

FIRE HYDRANTS

FIRE ALARM ANNUNCIATOR

FIRE ALARM CONTROL PANEL

KNOX BOX/KEY SWITCH

EMERGENCY RESPONDER RADIO COVERAGE

ELEVATOR GURNEY ACCOMODATION

PROVIDE A COMPLETE FIRE ACCESS PLAN

PROVIDE 6 MO. CURRENT SITE FIRE FLOW INFORMATION

PROVIDED ON FIRE ACCESS SITE PLAN

T0.3

NOT APPLICABLE

NOT APPLICABLE

LOCAL FIRE DEPARTMENT SHOWN ON SITE PLAN

NOT APPLICABLE

ALL BUILDINGS ARE FIRE TRUCK ACCESSIBLE USING EXISTING ROADS

NOT APPLICABLE

T0.3

T0.3

T0.3

PROVIDED ON FIRE ACCESS SITE PLAN

NOT AVAILABLE - USE FIRE HYDRANTS

NOT AVAILABLE

T0.4NOT APPLICABLE

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

X XX X

30' TYP.

T0.5

BUILDING INFORMATION

BLDG. 517 SITE PLAN

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :0

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 T

V3

BUILDING 517 SITE PLAN

SCALE: N0 100 5 FEET50

1" = 50'

BLDG

LEGEND:

SETBACK

(E) FIRE

HYDRANT

(E) FIRE

HYDRANT

(E) FIRE

HYDRANT

BUILDING INFORMATION

BUILDING NAME

CONSTRUCTION

TYPE

NUMBER

OF STORIES

BUILDING

AREA

IN SQ. FT.

SEPARATED /

NONSEPARATED

SPRINKLER

COVERAGE

FIRE ALARM

OTHER

PROTECTION

SYSTEM

SMOKE

CONTROL

SYSTEM

OCCUPANT

LOAD

YEAR BUILDING

CONSTRUCTED

HIGH FIRE

HAZARD

SEVERITY ZONE

SEISMIC JOINT

EMERGENCY

RESPONDER RADIO

COVERAGE

OCCUPANCY

GROUP

BUILDING 517 1 38' 27,232 161 2007 NO NO YES

BUILDING

HEIGHT

NONSEPARATED YES YES NO NO

AREA OF

PROJECT

ALLOWABLE

STOREY

(CBC TABLE

504.4)

USE

KITCHEN

STORAGE

OFFICE

ALLOWABLE

AREA

(CBC TABLE

506.2)

27,000 B

S-2 V-B

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M0.1

MECHANICAL GENERAL

NOTES

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :3

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 M

V3

1. ALL WORK SHALL COMPLY WITH THE 2022 EDITIONS OF THE CALIFORNIA BUILDING, MECHANICAL, PLUMBING, AND OTHER APPLICABLE FEDERAL, STATE AS ADOPTED AND ENFORCED BY THE AUTHORITY HAVING JURISDICTION (AHJ). IN CASE THE PLANS SHOW MORE STRINGENT REQUIREMENTS, THE PLANS SHALL GOVERN THE DESIGN, YET NOTHING ON THE DESIGN DOCUMENTS SHALL BE INTERPRETED AS

AUTHORITY TO VIOLATE CODE(S) OR REGULATION(S).

2. SUBMISSION OF BID IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER HAS EXAMINED THE JOB SITE UNDER WHICH THE CONTRACTOR WILL BE OBLIGATED TO OPERATE UNDER THIS CONTRACT. NO EXTRA CHARGE WILL BE ALLOWED FOR FAILURE OF ANY BIDDER TO EXAMINE THE SITE PRIOR TO BID.

3. WHERE USED, THE TERM "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".

4. CONTRACTOR AND SUBCONTRACTORS SHALL VERIFY ALL DIMENSIONS AT THE JOB SITE PRIOR TO

COMMENCEMENT OF ANY CONSTRUCTION. THE CONSULTANTS AND OWNER SHALL IMMEDIATELY BE

NOTIFIED OF ANY DISCREPANCIES.

5. THE CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE ALL WORK PERFORMED AND ALL EQUIPMENT AND MATERIALS FURNISHED FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE OF THE

WORK BY THE OWNER'S REPRESENTATIVE.

6. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON THE DRAWINGS. TYPICAL DETAILS AND

GENERAL NOTES ARE MINIMUM REQUIREMENTS TO BE USED WHEN CONDITIONS ARE NOT SHOWN

OTHERWISE.

7. NOTES AND DETAILS ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR ON PROJECT.

8. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON DESIGN PLANS WITH

CODE REQUIREMENTS, THE MORE STRINGENT STANDARD SHALL PREVAIL.

9. CONTRACTOR SHALL FURNISH LABOR, MATERIALS, EQUIPMENT, AND TRANSPORTATION AS REQUIRED TO PROPERLY INSTALL ALL NEW HVAC SYSTEMS OR RELATED COMPONENTS AS INDICATED ON PLANS AND

SPECIFIED HEREIN.

10. ALL NEW EQUIPMENT AND MATERIAL TO BE INSTALLED AS PART OF THE RENOVATION SHALL BEAR AN UNDERWRITERS LABORATORIES LABEL (UL), AND INSTALLED IN THE APPROVED MANNER FOR WHICH THEY

ARE DESIGNED.

11. CONTRACTOR SHALL DOCUMENT AND RELAY ANY MAJOR DEVIATIONS FROM THE DESIGN DOCUMENTS, AND ATTAIN APPROVAL FROM THE E.O.R. BEFORE PROCEEDING. AS-BUILT COPIES SHALL BE PROVIDED INDICATING ALL CHANGES AND DEVIATIONS MADE DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE

COMPLETED AS-BUILT DRAWINGS TO E.O.R. FOR RECORD AND PUBLISHING.

12. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARE SHALL BE EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TO OTHER AREAS OF THE BUILDING WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS BY MEANS TO KEEP DUST AND DIRT WITHIN THE

CONSTRUCTION AREA.

13. NO PIPING, EQUIPMENT, ETC. SHALL BE REMOVED, DISCONNECTED OR SHUT DOWN WITHOUT PRIOR REVIEW WITH THE OWNER'S REPRESENTATIVE TO CONFIRM THAT AREAS TO REMAIN IN OPERATION WILL NOT BE AFFECTED. IF ANY AREAS NOT WITHIN THE SCOPE OF WORK SHALL BE AFFECTED BY ANY

SHUTDOWN, REMOVAL OR DISCONNECTION, THE OWNER NEEDS ADVANCE NOTICE PER APPROVAL

SCHEDULE.

14. THE ARRANGEMENT OF EQUIPMENT, DUCTWORK, AND PIPING SHOWN ON THE DRAWINGS IS BASED UPON INFORMATION AVAILABLE TO THE ENGINEER AT THE TIME OF DESIGN AND IS NOT INTENDED TO SHOW

EXACT DIMENSIONS PECULIAR TO A SPECIFIC MANUFACTURER. THE DRAWINGS ARE, IN PART,

DIAGRAMMATIC AND SOME FEATURES OF THE ILLUSTRATED EQUIPMENT INSTALLATION MAY REQUIRE REVISION TO MEET ACTUAL EQUIPMENT INSTALLATION REQUIREMENTS. STRUCTURAL SUPPORTS, FOUNDATIONS, CONNECTED PIPING, VALVES, PIPE SUPPORTS AND ELECTRICAL CONDUIT SPECIFIED MAY

HAVE TO BE ALTERED OR ADDITIONAL ITEMS REQUIRED TO ACCOMMODATE THE EQUIPMENT PROVIDED.

NO ADDITIONAL PAYMENT WILL BE MADE FOR SUCH REVISIONS, ALTERATIONS AND ADDITIONS.

15. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AT THE SITE MAKING FIELD MEASUREMENTS AND SHOP DRAWINGS NECESSARY FOR FABRICATION AND INSTALLATION OF HVAC SYSTEMS. MAKE ALLOWANCE FOR BEAMS, PIPES AND OTHER OBSTRUCTIONS IN BUILDING CONSTRUCTION. CHECK DRAWINGS SHOWING

WORK OF OTHER TRADES AND CONSULT WITH THE STATE'S REPRESENTATIVE IN THE EVENT OF

POTENTIAL INTERFERENCE. SHOP DRAWINGS SHALL BE MINIMUM 1/4"=1'-0" SCALE, INDICATING FITTINGS, SIZES, WELDS AND CONFIGURATIONS AND SUBMITTED TO ENGINEER FOR REVIEW.

16. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES PRIOR TO FABRICATION, PURCHASE AND/OR INSTALLATION OF HIS WORK.

17. BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS, ELEVATIONS, AND CHARACTERISTICS OF ALL UTILITIES.

18. THE CONTRACTOR SHALL SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO THE CONTRACT.

19. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED IN NEW SYSTEMS, EXCEPT WHERE

INDICATED AS BEING RELOCATED.

20. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE MANUFACTURER'S WRITTEN

INSTALLATION INSTRUCTIONS.

21. GALVANIZED SHEET METAL SHALL BE PROVIDED FOR ALL HVAC DUCT SYSTEMS, AND CONSTRUCTED, SUPPORTED AND INSTALLED IN ACCORDANCE WITH THE 2022 CALIFORNIA MECHANICAL CODE AND THE

LATEST SMACNA STANDARDS.

22. ALL PIPING SHALL BE INSTALLED IN A NEAT WORKMANSHIP-LIKE MANNER AND BE SUPPORTED AS REQUIRED BY CODES. PIPING SHALL BE SET UP AND DOWN AND OFFSET AS REQUIRED TO SUIT FIELD CONDITIONS. DIELECTRIC COUPLINGS SHALL BE USED WHERE DISSIMILAR METALS ARE JOINED.

23. CONTRACTOR SHALL PROVIDE ALL NECESSARY SUPPORTS FOR FIXTURES, DUCTWORK, PIPING, AND MECHANICAL EQUIPMENT, IN ORDER TO COMPLY WITH SEISMIC REQUIREMENTS AS OUTLINED BY THE LATEST EDITION(S) OF THE CALIFORNIA BUILDING CODE, SMACNA INSTALLATION STANDARDS.

24. ALL VALVES, UNIONS, ETC. TO BE LINE SIZE UNLESS OTHERWISE INDICATED ON DRAWINGS.

25. UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH THREADED TYPE VALVE AND PRIOR TO

EQUIPMENT CONNECTIONS.

26. ALL BRACING OF DUCTS AND PIPING SHALL BE

A. INSTALLED IN ACCORDANCE WITH SMACNA GUIDELINES, OR AS DETAILED AND SPECIFIED HEREIN.

SEE SEISMIC PROTECTION NOTE SHEET FOR MORE INFORMATION.

B. WHERE BRACING DETAILS ARE NOT SHOWN ON THE DRAWINGS OR IN THE GUIDELINES, THE FIELD

INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER

27. A COPY OF THE GUIDELINES PUBLISHED BY SMACNA SHALL BE PROVIDED BY THE CONTRACTOR AND KEPT

ON THE JOB AT ALL TIMES.

28. CONTRACTOR SHALL NOT BORE, NOTCH, CUT, OR PENETRATE INTO A STRUCTURAL MEMBER WITHOUT

WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD AND STATE'S REPRESENTATIVE.

29. ALL CONDUIT AND WIRE REQUIRED FOR THE DIRECT DIGITAL CONTROL SYSTEM SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. THE CONTROLS CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL

ELECTRICAL ITEMS REQUIRED FOR AN OPERATIONAL CONTROLS SYSTEM.

30. ALL DUCTWORK AND PIPING INSULATION SHALL MEET FIRE AND SMOKE HAZARD RATING AS TESTED UNDER PROCEDURE ASTM E-84, NFPA 255 AND UL 723 AND SHALL NOT EXCEED FLAME SPREAD RATING OF

25 AND MAXIMUM SMOKE DEVELOPED RATING OF 50.

31. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ROUTING OF ALL DUCTWORK AND PIPING AND SUBMIT DETAILED, CLEARLY LEGIBLE, FULL SIZE (MINIMUM 30"x42") DUCT AND PIPING SHOP DRAWINGS IN

AUTOCAD FORMAT FOR APPROVAL FROM THE ENGINEER PRIOR TO FABRICATION, CONSTRUCTION AND

INSTALLATION OF DUCTWORK AND PIPING.

32. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF COMPONENTS AT LEAST TWO WEEKS PRIOR TO

INSTALLATION.

33. OWNER'S REPRESENTATIVE SHALL INSPECT AND APPROVE OF ALL WORK BEFORE COVERING WITH

INSULATION OR INSTALLATION WITHIN CEILING SPACE.

34. APPROVAL OR DISAPPROVAL BY THE INSPECTOR OF RECORD DOES MEAN APPROVAL OR FAILURE TO COMPLY WITH THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. ANY DESIGN WHICH IS NOT CLEAR OR IS AMBIGUOUS SHALL BE REFERRED TO THE EOR AND OWNER FOR INTERPRETATION OR

CLARIFICATION.

35. CONTRACTOR SHALL USE ALL NECESSARY APPROVED MEANS TO PROTECT HIS PORTION OF THE WORK BEFORE, DURING, AND AFTER INSTALLATION, UNTIL ACCEPTED, AND TO PROTECT THE INSTALLED WORK

AND MATERIALS OF OTHER TRADES IN A LIKE MANNER. IN THE EVENT OF ANY DAMAGE, CONTRACTOR SHALL MAKE ALL REQUIRED REPAIRS AND REPLACEMENTS TO THE SATISFACTION OF THE EOR AND

OWNER AND AT NO ADDITIONAL COST TO THE OWNER.

36. NEITHER THE E.O.R. OR OWNER SHALL BE RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES, OR FOR THE SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. ALL SUCH MATTERS ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.

37. A MINIMUM OF 36" CLEAR WORKING SPACE, NOT LESS THAN 30" WIDE, SHALL BE MAINTAINED IN FRONT OF

ALL SWITCHES, OVERCURRENT PROTECTION DEVICES, AND ELECTRICAL CONTROL COMPONENTS.

38. CONTRACTOR SHALL OBTAIN AND FOLLOW ALL REQUIREMENTS, GUIDELINES, RULES, AND PROCEDURES

FOR CONSTRUCTION.

39. DEMOLITION OF ANY EXISTING AC UNITS, DUCTWORK, AND PIPING SHALL BE COORDINATED WITH

FACILITIES AND OPERATIONS. CONTRACTOR SHALL SCHEDULE WORK TO MINIMIZE SHUT-DOWN OF

EXISTING UNITS.

40. EXISTING SURFACES AND AREAS NOT INCLUDED IN THE WORK AREA SHALL BE PROTECTED FROM DAMAGE

BY APPROVED MEANS. IF DAMAGE OCCURS, THE DAMAGE SHALL BE REPAIRED BY THE CONTRACTOR TO

SATISFACTION OF THE E.O.R. AND OWNER AND AT NO ADDITIONAL COST TO THE OWNER.

41. REMOVE ALL SURPLUS MATERIALS, EQUIPMENT AND DEBRIS INCIDENTAL TO THIS PROJECT AND LEAVE

THE PREMISES CLEAN AND ORDERLY UPON COMPLETION OF WORK.

42. UPON COMPLETION OF PIPING, BUT PRIOR TO APPLICATION OF INSULATION, THE CONTRACTOR SHALL TEST THE PIPING SYSTEMS FOR LEAKS. EQUIPMENT WHICH MAY BE DAMAGED BY THE SPECIFIED TEST

CONDITIONS SHALL BE ISOLATED.

43. ON INSULATED PIPING: ALL VALVES HANDLES, AIR VENTS AND PRESSURE/ TEMPERATURE READOUT

PORTS TO BE PROVIDED WITH 2" EXTENSION TO CLEAR PIPING INSULATION.

44. ALL EXISTING DUCTING TO REMAIN SHALL BE CLEANED

45. CONTRACTOR SHALL COORDINATE WITH OWNER TO SCHEDULE INSTALLATION OF INDOOR UNITS DURING

OFF-HOURS. NO HEAVY EQUIPMENT SHALL BE USED DURING INSTALLATION.

46. REFRIGERANT PIPING AND ALL JOINTS INSTALLED ON THE PREMISES SHALL BE LEFT EXPOSED TO VIEW FOR VISUAL INSPECTION AND SHALL NOT BE COVERED OR ENCLOSED UNTIL THE REQUIRED INSPECTION

HAS BEEN COMPLETED AND APPROVED BY THE AUTHORITY HAVING JURISDICTION, IN ACCORDANCE WITH

CMC SECTION 1109.8.

47. PIPING AND TUBING SHALL BE SECURELY FASTENED TO A PERMANENT SUPPORT WITHIN 6 FEET

FOLLOWING THE FIRST BEND IN SUCH TUBING FROM THE COMPRESSOR AND WITHIN 2 FEET OF EACH

SUBSEQUENT BEND OR ANGLE.

48. BASIS OF DESIGN CONTACT:

LENNOX COMMERCIAL

RAMIRO RODRIGUEZ

PH: 951-491-9195

EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM

GENERAL NOTES

AFF ABOVE FINISHED FLOOR

BDD BACKDRAFT DAMPER

BSC BIOSAFETY CABINET

CD CEILING DIFFUSER

CFM CUBIC FEET PER MINUTE

CFSD COMBINATION FIRE/SMOKE DAMPER

CV CONTROL VALVE

(A) EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMP.

°F FAHRENHEIT

FC FAN COIL UNIT

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

FS FIRE SPRINKLER

FT FEET

GPM GALLONS PER MINUTE

HHWS HEATING HOT WATER SUPPLY

HHWR HEATING HOT WATER RETURN

HTS HIGH TEMP. WATER SUPPLY

HTR HIGH TEMP. WATER RETURN

HOA HAND/OFF/AUTO SWITCH

HP HORSEPOWER

HR HOUR

IN INCHES

IN. W.C. INCHES OF WATER COLUMN

KW KILOWATT

L LENGTH

(L) LINER

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LWT LEAVING WATER TEMP.

MAX MAXIMUM

MIN MINIMUM

MUA MAKEUP AIR

(N) NEW

OSA OUTSIDE AIR

dP DIFFERENTIAL PRESSURE

PH PHASE

QTY QUANTITY

RA RETURN AIR

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

SA SUPPLY AIR

SD SMOKE DETECTOR

SF SUPPLY FAN

SR SUPPLY REGISTER

SQFT. SQUARE FEET

TI TEMPERATURE INDICATOR

TT TEMPERATURE TRANSDUCER

TYP TYPICAL

TSP TOTAL STATIC PRESSURE

V VOLTS

VAV VARIABLE AIR VOLUME

VEL VELOOWNER

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VP VELOOWNER PRESSURE

WG WATER GAUGE

WT WEIGHT

LIGHT, THIN LINES INDICATE EXISTING.

HEAVY, THICK LINES INDICATE NEW.

HEAVY, SHORT DASHED INDICATE

DEMOLITION OR REMOVAL.

THIS SYMBOLOGY TO BE USED BY MECHANICAL AND LAYOUT FOR ALL FLOOR PLANS,

EQUIPMENT, DEVICES, UTILITIES, ETC., SHOWN ON DRAWINGS.

ABBREVIATIONS MECHANICAL SYMBOL LIST

TYPICAL PLAN LEGEND

FLEXIBLE DUCT

AIR VOLUME IN CFM

RETURN CEILING GRILLE

EXHAUST CEILING GRILLE

DUCT SIZE IN INCHES

TYPE OF DIFFUSER OR GRILLE

10"ØA

SUPPLY CEILING DIFFUSER

ELBOW W/TURNING VANES

RECTANGULAR TO ROUND TRANSITION

MANUAL VOLUME DAMPER

EXISTING DUCT TO REMAIN

SPLITTER VANES OR MITTERED

SHORT RADIUS ROUND ELBOW W/

EXISTING DUCTWORK TO BE REMOVED

NEW DUCTWORK

"Ø

MOTORIZED DAMPER

VD

FSD FIRE/SMOKE DAMPER

VOLUME DAMPER, MANUAL

SIDE POINTED TO

DUCT SIZE - FIRST DIMENSION IS FOR

SUPPLY AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST AIR DUCT SECTION

ROUND DUCT SECTION

24"x12"

"Ø

HVAC SYMBOLS

DESCRIPTIONDOUBLE LINE SINGLE LINE

SYMBOL

DESCRIPTIONSYMBOL

DESCRIPTION

POINT OF CONNECTION

POINT OF DISCONNECTION

NEW WORK KEYNOTE1

DEMOLITION KEYNOTE

CONTROL PANEL

HUMIDITY SENSOR

THERMOSTAT SENSOR

THERMOSTAT

DUCT SMOKE DECTOR

AIR TIGHT DAMPER

SYMBOL DESCRIPTION

REFRIGERANT: R-410A

ALLOWABLE QUANTITY PER CMC 1102.3: 26-LBS PER1,000 CF OF SPACE

SMALLEST AREA FOR POTENTIAL LEAK

ROOM: 107 - WOMEN'S RESTROOM

DIMENSIONS (LxWxH): 20' 8" X 9' 6" X 9'

VOLUME (CF): 1,767

ALLOWABLE REFRIGERANT QTY: 45.942-LBS

POUNDS (LBS) OF REFRIGERANT IN SYSTEM

LINEAR DENSITY LENGTH QTY

REFRIGERANT LOCATION (LBS/FT) (FT) (LBS)

EQUIPMENT CHARGE: 23.100

PIPE - 1/2" LIQUID 0.098 85 8.345

PIPE - 3/8" LIQUID 0.055 40 2.209

PIPE - 1-1/8" SUCTION 0.002 85 0.153

PIPE - 5/8" SUCTION 0.001 40 0.022

ACCESSORIES/BUFFER 2.000

TOTAL 35.829

SYSTEM OK

REFRIGERANT CONCENTRATION LIMIT

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

M0.2

MECHANICAL EQUIPMENT

SCHEDULES

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :3

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 M

V3

VARIABLE REFRIGERANT FLOW (VRF) INDOOR UNIT SCHEDULE

NOTES:

SELECTION BASED ON EQUIPMENT MANUFACTURED BY SAMSUNG.

SEE OUTDOOR CONDENSING UNIT SCHEDULE FOR DETAILS REGARDING CONNECTION CAPACITY, OUTDOOR CONDITIONS AND OTHER FACTORS ASSOCIATED WITH CORRECTED CAPACITIES.

INDOOR (AIR HANDLING) UNITS SHALL BE OF THE SAME MANUFACTURER AND SHALL BE CERTIFIED FOR USE WITH EACH OTHER. REMOTE CONDENSING UNITS SHALL BE SECURELY MOUNTED AS DETAILED IN THE MANUFACTURERS

INSTALLATION MANUAL.

SIZE REFRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER DESIGN SOFTWARE AFTER ESTIMATED LINE LENGTHS THAT ARE PROVIDED AND INCLUDED IN THE REPORT.

MECHANICAL CONTRACTOR SHALL SIZE REFRIGERANT LINES PER MANUFACTURER'S RECOMMENDATIONS BASED ON ACTUAL ROUTING OF REFRIGERANT LINES.

CORRECTED CAPACITIES ARE BASED ON THE ENTERING AIR CONDITIONS AS NOTED IN THE ABOVE TABLE.

LOCAL ZONE CONTROLLERS ARE NOTED ABOVE IN THE "LOCAL CONTROLLER" COLUMN.

THE SYSTEM SHALL CONNECT TO SAMSUNG CENTRAL CONTROL SOLUTIONS.

NOTE INDOOR UNIT SERIAL NUMBERS ON PLANS DURING INSTALL FOR FUTURE REFERENCE DURING COMMISSIONING. FOR HEAT RECOVERY SYSTEMS, ALSO NOTE WHICH PORT(S) EACH INDOOR IS CONNECTED TO.

UNIT SHALL BE MOUNTED PER MANUFACTURE'S RECOMMENDATION.

PROVIDE WITH LIQUID LEVEL SENSOR / FLOAT SWITCH AND CONTR4OL MODULE FOR UNIT SHUTDOWN IN THE EVENT OF CONDENSATE OVERFLOW.

EQUIPMENT TAG

MANUFACTURER

MODEL NO.

SAMSUNG

AM024TNVDCH/AA

R410A

REFRIGERANT

IU

RATED PERFORMANCE

23,200

IU

MBH

COOLING

(BTU/H)

23,800

HEATING

(BTU/H)

FAN

LOW

(CFM)

MID

(CFM)

HIGH

(CFM)

AIRFLOW

466.20 529.70 593.30 208/230

VOLT

PHASE

HZ

ELECTRICAL

0.50

MCA

15.00

MOP

0.40

FAN

FLA

43.00

NOISE

(dB(A))

REFRIGERANT

3/8

LIQUID

PIPE

(IN.)

5/8

GAS

PIPE

(IN.)

REMARKS

1 2 3 4 5 6 7 8 9

26.46

PRODUCT

WEIGHT

VARIABLE REFRIGERANT FLOW (VRF) OUTDOOR UNIT SCHEDULE

NOTES:

SELECTION BASED ON EQUIPMENT MANUFACTURED BY SAMSUNG.

CORRECTED CAPACITIES ARE BASED ON THE ENTERING AIR CONDITIONS AS NOTED IN THE ABOVE TABLE ALONG WITH PIPE LENGTH AND VERTICAL SEPARATION.

SYSTEM MUST BE CAPABLE OF SIMULTANEOUS HEATING AND COOLING.

REFER TO THE MANUFACTURER'S ENGINEERING TECHNICAL DATA BOOK FOR SOUND RATING DETAILS.

SIZE REFRIGERANT LINES IN ACCORDANCE WITH MANUFACTURER DESIGN SOFTWARE AFTER ESTIMATED LINE LENGTHS ARE PROVIDED AND INCLUDED IN THE REPORT.

AIR SOURCE CONDENSING UNITS SHALL HAVE RATED CAPACITY DATA FROM -13°F - 120°F (-25°C - 48.9°C).

PROVIDE DEDICATED 16/2 STRANDED, SHIELDED COMMUNICATION WIRE BETWEEN CONDENSING UNIT, INDOOR UNIT(S), AND HEAT RECOVERY MODE CONTROL UNIT(S) (MCU).

NOTE OUTDOOR UNIT SERIAL NUMBERS ON PLANS DURING INSTALL FOR FUTURE REFERENCE DURING COMMISSIONING.

THE SYSTEM SHALL CONNECT TO SAMSUNG CENTRAL CONTROL SOLUTIONS. PROVIDE WITH SAMSUNG THERMOSTAT MODEL MWR-WG00UN.

EQUIPMENT

TAG

MANUFACTURER

MODEL NO.

SAMSUNG

AM048TXMDCH/AA

R410A

REFRIGERANT

RATED PERFORMANCE

48,000

OU

TON

COOLING

(BTU/H)

54,000

HEATING

(BTU/H)

FAN

AIRFLOW

(CFM)

3884.76 208/230

VOLT

PHASE

HZ

ELECTRICAL

29.00

MCA

50.00

MOP

SCCR

51.00

NOISE

(dB(A))

REFRIGERANT

3/8

LIQUID

PIPE

(IN.)

3/4

GAS

PIPE

(IN.)

REMARKS

1 2 3 4 5 6 7 8 9

213.85

PRODUCT

WEIGHT

DVM S ECO,

HEAT PUMP

TYPE

SAMSUNG

AM144BXVGFH/AA

R410A 144,000

OU

12 162,000 10170.00 208/230 3 60 52.60 60.00 5 60.00 1/2 1 1/8 612.89

DVM S2, HEAT

PUMP

THRU

1 2 3 4 5 6 7 8 9

INDOOR

TEMP

OUTDOOR

TEMP

47°F DB

43°F WB

NOMINAL HEATING NOMINAL COOLING

INDOOR

TEMP

OUTDOOR

TEMP

70°F DB

60°F WB

95°F DB

75°F WB

80°F DB

67°F WB

BASIS OF DESIGN CONTACT:

LENNOX COMMERCIAL

RAMIRO RODRIGUEZ

PH: 951-491-9195

EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM

BASIS OF DESIGN CONTACT:

LENNOX COMMERCIAL

RAMIRO RODRIGUEZ

PH: 951-491-9195

EMAIL: RAMIRO.RODRIGUEZ@LENNOX.COM

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject

B.4 B.7 C C.2 C.6 D

B.4

B.7 C C.6 D D.6

HALL

RESTROOM

MEN'S

130 131

DISH WASH

UTENSIL/TRAY/

DISPATCH COOLER

INVENTORY

COOLER

MEAT

MEN

CORRIDOR

BREAKROOM

ADMIN

SUPERVISOR II

FOOD SERVICE

DIRECTOR

ASSISTANT

COPY

STORAGE/

HALL

DIRECTOR

ASSISTANT

COOK II

SUPERVISING

OFFICE

OPEN

COOK I

SUPERVISING

DIRECTOR

DIRECTOR

ASSISTANT

ROOM

ELECTRICAL

TELECOM

ROOM

MECHANICAL

FREEZER

BULK

COOLER

BULK

ASSEMBLY

CART STORAGE/

INVENTORY COOLER

FOOD BANK/

INGREDIENT CONTROL

DRY STORAGE/

HOT PREP.

COOKING/

SUPERVISOR I

FOOD SERVICE

LOBBY 102

CONFERENCE

RESTROOM

WOMEN'S

LOCKERS

CORRIDOR

HALL

WOMEN

DIETITIAN

COLD PREP.

T T

12"

MIN.

M

IN

10' MIN

10' MIN

M2.1

MECHANICAL NEW WORK

PLAN

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :3

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 M

V3

0 FEET8

1/8" = 1'-0"

4 16SCALE:

MECHANICAL NEW WORK PLAN

NEW WORK KEYNOTES:

(N) 12 TON VRF OUTDOOR UNIT. SEE DETAIL 1/M3.1 FOR MOUNTING.

(N) 4 TON VRF OUTDOOR UNIT. SEE DETAIL 5/M3.1 FOR WALL MOUNT.

(N) VRF INDOOR UNIT 10' AFF.

(N) REFRIGERANT PIPING. SEE 1/M3.1.

CONNECT CONDENSATE DRAIN TO (E) SEWER. SEE 2/M3.1

(N) CONDENSATE DRAIN PIPING. ROUTE TO NEAREST DRAIN.

CONDENSATE PIPING SHALL NOT SLANT UPWARD. SEE 2/M3.1 AND

3/M3.1

(N) EQUIPMENT PAD. SEE DETAIL 1/M3.1.

(N) THERMOSTAT W/ LOCKING COVER. COVER SHALL BE APPROVED

BY OWNER PRIOR TO INSTALLATION. PROVIDE AND INSTALL ALL

CONDUIT, WIRING, AND CONNECTIONS FOR FULL OPERATION AND

CONTROL OF EQUIPMENT. THERMOSTAT FOR SET-POINT AND

ON/OFF OPERATION. LOCATION SHOWN FOR OFFICE REFERENCE.

CONTRACTOR SHALL COORDINATE EXACT LOCATION WITH OWNER

PRIOR TO INSTALL.

INDIRECT DRAIN TERMINATION AT FLOOR SINK

(N) LEVEL SENSOR IN CONDENSATE LINE AND CONTROL MODULE

INTERLOCKED WITH VRF INDOOR UNIT POWER. VRF SHALL POWER

OFF IN THE EVENT OF CONDENSATE OVERFLOW PER CMC 310.2

N

IU

OU

OU

IU

IU

IU

IU

IU

IU

IU

3 3

1/2" LIQUID

1-1/8" SUCTION

3/8" LIQUID

5/8" SUCTION

3/4" CONDENSATE

(TYP. 8 UNITS)

TYP

6TYP

M3.1

M3.1

M3.2

M3.2

M3.2

A.8 B.4 B.7 C C.2 C.6 D E E.6

7.4

6.7

5.2

4.4

3.6

2.8

A A.8 B B.4

B.7 C C.6 D D.6

6.5

4.4

0.1

2.1

5.6

E E.7

2.4

E.9 F

E.9

7.1

HALL

RESTROOM

MEN'S

130 131

DISH WASH

UTENSIL/TRAY/

JANITOR

WASH

CART

DISPATCH COOLER

INVENTORY

ROOM

BREAD

COOLER

DAIRY/PRODUCE

COOLER

MEAT

RR

UNISEX

DOCK

RECEIVING

MEN

CORRIDOR

BREAKROOM

ADMIN

SUPERVISOR II

FOOD SERVICE

DIRECTOR

ASSISTANT

COPY

STORAGE/

HALL

DIRECTOR

ASSISTANT

COOK II

SUPERVISING

OFFICE

OPEN

COOK I

SUPERVISING

DIRECTOR

DIRECTOR

ASSISTANT

ROOM

ELECTRICAL

TELECOM

ROOM

MECHANICAL

FREEZER

BULK

COOLER

BULK

CHARGING

FORKLIFT

ASSEMBLY

CART STORAGE/

INVENTORY COOLER

FOOD BANK/

INGREDIENT CONTROL

DRY STORAGE/ 137

STORAGE

BULK DRY

HOT PREP.

COOKING/

SUPERVISOR I

FOOD SERVICE

BREAK ROOM

LOBBY 102

CONFERENCE

RESTROOM

WOMEN'S

LOCKERS

CORRIDOR

DOCK

DISPATCH

HALL

WOMEN

DIETITIAN

COLD PREP.

HALL

RESTROOM

MEN'S

130 131

DISH WASH

UTENSIL/TRAY/

JANITOR

WASH

CART

DISPATCH COOLER

INVENTORY

ROOM

BREAD

COOLER

DAIRY/PRODUCE

COOLER

MEAT

RR

UNISEX

DOCK

RECEIVING

MEN

CORRIDOR

BREAKROOM

ADMIN

SUPERVISOR II

FOOD SERVICE

DIRECTOR

ASSISTANT

COPY

STORAGE/

HALL

DIRECTOR

ASSISTANT

COOK II

SUPERVISING

OFFICE

OPEN

COOK I

SUPERVISING

DIRECTOR

DIRECTOR

ASSISTANT

ROOM

ELECTRICAL

TELECOM

ROOM

MECHANICAL

FREEZER

BULK

COOLER

BULK

CHARGING

FORKLIFT

ASSEMBLY

CART STORAGE/

INVENTORY COOLER

FOOD BANK/

INGREDIENT CONTROL

DRY STORAGE/ 137

STORAGE

BULK DRY

HOT PREP.

COOKING/

SUPERVISOR I

FOOD SERVICE

BREAK ROOM

LOBBY

CONFERENCE

RESTROOM

WOMEN'S

LOCKERS

CORRIDOR

DOCK

DISPATCH

HALL

WOMEN

DIETITIAN

COLD PREP.

KEY PLAN

N

CONTROL WIRING

END OF LINE CLEANOUT (TYP)

1/2" LIQUID

1-1/8" SUCTION

1" CONDENSATE

1/2" LIQUID

1-1/8" SUCTION

1" CONDENSATE

1/2" LIQUID

1-1/8" SUCTION

1" CONDENSATE

3/4" CONDENSATE

3/8" LIQUID

5/8" SUCTION

3/8" LIQUID

5/8" SUCTION

1" CONDENSATE

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

12/04/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1380

AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x AutoCAD SHX Text: x

INSULATE SUCTION LINE &

LIQUID LINES WITH 2" THICK

ARMAFLEX

CONTRACTOR TO VAPOR SEAL

PENETRATIONS

DRAIN LINE TO EXIT 45° @ BACK OF COIL.

EXIT FROM FREEZER AT EARLIEST

POSSIBLE DISTANCE.

INSULATED CONDENSATE

DRAIN LINE WITH 1" THICK

ARMAFLEX INSULATION. ALL

INSULATED DRAIN LINES

REQUIRE A MINIMUM 1/4 "

FALL PER FT.

NOTE:

ROUTE EACH CONDENSATE DRAIN

SEPARATELY FROM EVAPORATOR COIL TO

FLOOR SINK

CEILING SPACE

OUTSIDE

AIR FLOW

A F F

INSTALL ELECTRIC HEATER SPIRALED

AND TAPED ON FREEZER INSULATED

CONDENSATE DRAIN LINE BY

CONTRACTOR

(E) LIGHTING

M3.1

MECHANICAL DETAILS

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 24793-9

00000000000XXXX

DEPARTMENT OF STATE

HOSPITALS, METROPOLITAN

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

SUPPLEMENTAL

HVAC - CENTRAL

KITCHEN

11/27/2024

100% SUBMITTAL

DSH

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

JCCA

D A T E T

IM

E O c t :5

P

M

F

IL

E L \2

-9

C e n tr a l K it c h e n A

C D

S H

-M \C

A D

\2 M

V3

OUTDOOR CONDENSING UNIT DETAIL

NO SCALE M3.1

CONDENSATE TO TAILPIECE

M3.1

NO SCALE

CONDENSING UNIT

(E) EXTERIOR WALL

UNISTRUT P1000

ANCHORED TO

EXTERIOR WALL, 48"

OC.

INSULATED REFRIGERANT

PIPING SECURED TO

P1000 UNISTRUT W/PIPE

CLAMP

SEAL PIPE WATER TIGHT AT

SOFFIT PIPE PENETRATION

(E) ROOF

REFRIGERANT PIPING IN CEILING

TO NEW INDOOR UNITS. SEE

PLANS.

PIPE BRACE

SECTION

WALL

TO MATCH PIPE SIZE

3/4" COPPER ELBOW

INSULATE

3/4" COPPER COUPLING

DRAINAGE SYSTEM

WASTE WATER

SINK

X 1" TEE

1 1/2" X 1 1/2"

1 1/2" TAILPIECE

1 1/2" TRAP ARM

1 1/2" 'P' TRAP

1/8"/FT SLOPE

3/4" INSULATED

CONDENSATE DRAIN

FROM FCU

NOTES:

1. GENERAL CONTRACTOR SHALL SUBMIT CUT SHEETS FOR APPROVAL.

2. PROVIDE PIPE SLEEVES WHERE PIPE PENETRATES THROUGH FIRE RATED FLOOR

OR WALLS.

3. PIPING AND TUBING SHALL BE SECURELY FASTENED TO A PERMANENT SUPPORT

WITHIN 6 FEET FOLLOWING THE FIRST BEND IN SUCH TUBING FROM THE

COMPRESSOR AND WITHIN 2 FEET OF EACH SUBSEQUENT BEND OR ANGLE.

TYPICAL CONDENSATE DRAIN LINE

M3.1

NO SCALE

PIPE HANGER DETAIL

M3.1

NO SCALE

ADJUSTABLE

HALF HINGE

PART NO.

B335V-½

B335V-½

B335V-½

B335V-½

B335V-½

B335V-½

B335V-½

B335V-½

RISER

CLAMP

IN.

COPPER

TUBING SIZE

1"

1¼"

1½"

2"

2½"

3"

LONGITUDINAL BRACE

B-LINE CHANNEL

HINGE

ADJUSTABLECLEVIS HANGER

PART NO.

8"B335-2-

N/A

N/A

8"

8"

8"B335-2-

B335-2-

B335-2- 3

B3104CT-½

B3104CT-

B3104CT-1

B3104CT-1¼

B3104CT-1½

B3104CT-2

PART NO.

B3104CTPS-1

B3104CTPS-1¼

B3104CTPS-1½

B3104CTPS-2

PART NO.*

N/A

N/A

PIPE

SLEEVE

ADJUSTABLE HALF HINGE

B355V-BOLT SIZE

4"

B3373CT

4" MAX.

(101 mm)

INSTALL HANGER AT 6' MAX INTERVALS. INSTALL BRACES AT 20' MAX INTERVALS

STRUCTURAL SUPPORT FOR PIPING SEISMIC BRACING SHALL BE IN ACCORDANCE WITH OSHPD

PRE-APPROVAL DETAILS OF B-LINE SEISMIC RESTRAINTS No. OPM-0052-13, OPM-0043-13 OR

APPROVED EQUAL.

RISER CLAMP SERIES

8"

8"

8" B335-2-

B335-2-

B335-2- 3

8B335-2- 3 "

B3104CT-2½

B3104CT-3

B3104CT-3½

B3104CT-4 B3104CTPS-4

B3104CTPS-2½

B3104CTPS-3

B3104CTPS-3½

3½" B3373CT-3½

B3373CT-4

PART NO.

B3373CT-2

B3373CT-2½

B3373CT-3

B3373CT-1

B3373CT-1¼

B3373CT-1½

1"

½"

1¼"

1½"

2"

1 (MIN.)

B-LINE CHANNEL

ROD STIFFENER

3/8", MIN. ALL THREADED ROD

2½"

3"

3½"

4"

B355-2-BOLT SIZE

B3104CTPS PIPE SLEEVE

B3104CT SERIES CLEVIS HANGER

ADJUSTABLE HINGE

TRANSVERSE BRACE

*NOT INCLUDED WHEN ORDERING STANDARD B1304CT SERIES

CLEVIS HANGER.

NOTES:

COPPER

TUBING SIZE

IN.

(E) CEILING

SMOOTH

TROWEL

FINISH

4" CHAMFER TYP.

ALL AROUND

#4 @ 12" O.C.

(N) OUTDOOR

CONDENSING UNIT

PROVIDE SEISMIC

RESTRAINTS FOR

AC. ANCHOR W/

HILTI EPOXY OR

WEDGE ANCHORS

12" MIN

4" MIN

6"

MIN

ALL

AROUND

SAWCUT EXISTING ASPHALT CONCRETE

PAVEMENT. FIELD VERIFY THICKNESS.

BOTTOM

ELEVATION

ANCHOR BOLT LOCATION

(TYP. 6)

1/2" ANCHOR, 3" EMBED

PROVIDE WITH NEOPRENE

ISOLATION PAD

MINIMUM SLEEVE LENGTH OF 2

INCHES AND A MINIMUM OF A 4

INCH ANCHOR IF 3 INCHES IS

EMBEDDED. SEE INSTALLATION

INSTRUCTIONS.

FIRE RATED PIPE PENETRATION

M3.1

NO SCALE

SYSTEM NO. F-A-5028

APRIL 12, 2017

F RATING - 3 HR

T RATING - 1/2, 3/4, 1-3/4, 2-3/4 and 3 Hr (SEE ITEM 4)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 5A)

L RATING AT 400° F - LESS THAN 1 CFM/SQ FT (SEE ITEM 5A)

W RATING - CLASS 1 (SEE ITEMS 4B AND 5A)

1. FLOOR ASSEMBLY -- MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT

OR NORMAL WEIGHT (100-150 PCF OR 1600 - 2400 KG/M3) CONCRETE.

2. FIRESTOP DEVICE* -- CAST IN PLACE FIRESTOP DEVICE PERMANENTLY

EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE

ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION

INSTRUCTIONS. THE DEVICE MAY BE TRIMMED FLUSH WITH TOP SURFACE OF

FLOOR OR MAY PROJECT UP TO MAX 3-1/2 IN. (89 MM) ABOVE TOP SURFACE

OF FLOOR.

3M COMPANY -- 3M FIRE BARRIER CAST-IN DEVICE 2MCID, 3MCID, 4MCID

2A. FIRESTOP DEVICE - HEIGHT ADAPTER* -- (NOT SHOWN) - FOR USE IN

FLOORS GREATER THAN 8 IN. (203 MM) THICK. ADAPTER SNAPS ONTO TOP OF

FIRESTOP DEVICE (ITEM 2).

3M COMPANY -- 3M FIRE BARRIER CAST-IN DEVICE HEIGHT ADAPTER, 2HA, 3HA,

4HA

3. THROUGH PENETRANTS -- ONE METALLIC PIPE OR TUBING TO BE INSTALLED

CONCENTRICALLY OR ECCENTRICALLY WITHIN OPENING. PENETRANT TO BE

RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE

FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR TUBES MAY BE USED:

A. STEEL PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 5 (OR

HEAVIER) STEEL PIPE.

B. IRON PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) CAST OR DUCTILE

IRON PIPE.

C. COPPER TUBING -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) TYPE L (OR

HEAVIER) COPPER TUBING.

D. COPPER PIPE -- NOM 2 IN. (51 MM) DIAM (OR SMALLER) REGULAR (OR

HEAVIER) COPPER PIPE.

4. PIPE COVERING -- THE FOLLOWING TYPES AND SIZES OF PIPE COVERINGS

MAY BE USED WITH THE METALLIC PIPES:

A. PIPE COVERING -- NOM 1-1/2 IN. (38 MM) THICK (OR LESS) HOLLOW

CYLINDRICAL HEAVY DENSITY GLASS FIBER UNITS JACKETED ON THE

OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED

WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP

TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH

BUTT TAPE SUPPLIED WITH PRODUCT. ANNULAR SPACE BETWEEN THE

PIPE COVERING AND PERIPHERY OF OPENING OR SLEEVE SHALL BE MIN

0 IN. (0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM).

SEE PIPE AND EQUIPMENT COVERING - MATERIALS(BRGU) CATEGORY IN

THE BUILDING MATERIALS DIRECTORY FOR NAMES OF

MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE

SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH

A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED

INDEX OF 50 OR LESS MAY BE USED.

B. PVC JACKET++ -- (OPTIONAL, NOT SHOWN) -- AN ADDITIONAL PVC

JACKET, SUPPLIED IN SHEET FORM, SHALL BE TIGHTLY WRAPPED

AROUND THE ALL SERVICE JACKET ON THE PIPE COVERING (ITEM 4A)

WITH THE LONGITUDINAL SEAM CONTINUOUSLY SEALED USING THE

SELF-SEALING LAP TAPE OR ADHESIVE SUPPLIED WITH THE JACKET. THE

JACKET IS TO BE NOM 48 IN. (1.22 M) WIDE BY NOM 20 OR 30 MIL (0.5 OR

0.8 MM) THICK. THE JACKET SHALL EXTEND DOWNWARD INTO AND/OR

THROUGH THE OPENING FROM A POINT 36 TO 40 IN. (0.91 TO 1.02 M)

ABOVE THE TOP SURFACE OF THE FLOOR ASSEMBLY. THE PVC JACKET

MUST BE USED FOR THE W RATING TO APPLY.

SEE PLASTICS (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED

COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY

RECOGNIZED COMPONENT PLASTIC MATERIAL MEETING THE ABOVE

SPECIFICATIONS AND HAVING A UL 94 FLAMMABILITY CLASSIFICATION

OF 94-5VA MAY BE USED.

C. TUBE INSULATION-PLASTICS++ -- NOM 1 IN. (25 MM) THICK (OR LESS)

ACRYLONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE

FOAM FURNISHED IN THE FORM OF TUBING. ANNULAR SPACE BETWEEN

THE INSULATED PENETRATING ITEM AND THE PERIPHERY OF THE

OPENING SHALL BE MIN 0 IN. (0 MM) (POINT CONTACT) TO MAX 1 IN. (25

MM).

SEE PLASTICS (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED

COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY

RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE

ABOVE SPECIFICATIONS AND HAVING A UL 94 FLAMMABILITY

CLASSIFICATION OF 94-5A MAY BE USED.

THE HOURLY T RATINGS ARE DEPENDENT ON THE SIZE OF PIPE OR TUBE

AND THE NOM THICKNESS OF THE PIPE COVERING, AS SHOWN BELOW:

NOM PENETRANT NOM PIPE COVERING T RATING,

SIZE, IN (mm) THICKNESS, IN (mm) HR

1/2 & 3/4 (13 & 19) 1/2 & 3/4 (13 & 19) 1-3/4

1/2 & 3/4 (13 & 19) 1 & 1-1/2 (25 & 38) 3

1 (25) 1/2 & 3/4 (13 & 19) 1/2

1 (25) 1 (25) 2-3/4

1 (25) 1-1/2 (38) 3

1-1/4 TO 2 (32 TO 51) 1/2 (13) 1/4

1-1/4 TO 2 (32 TO 51) 3/4, 1 & 1-1/2 (19, 25 & 38) 1/2

5. PACKING MATERIAL -- NOT REQUIRED IF ANNULAR SPACE IS 1/4 IN. (6 MM) OR

LESS. IF ANNULAR SPACE IS GREATER THAN 1/4 IN. (6 MM), MIN 2 IN. (51 MM)

THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY

PACKED WITHIN ANNULUS, FLUSH WITH THE TOP SURFACE OF FLOOR.

5A. FILL, VOID OR CAVITY MATERIALS - SEALANT, CAULK OR PUTTY* --

(OPTIONAL, NOT SHOWN) - AS AN OPTION, THE PACKING MATERIAL (ITEM 5)

MAY BE REDUCED IN THICKNESS BY 1/4 TO 1/2 IN. (6 MM TO 13 MM) AND

RECESSED FROM THE TOP SURFACE OF FLOOR TO ACCOMMODATE A 1/4 TO

1/2 IN. (6 MM TO 13 MM) THICKNESS OF SEALANT, CAULK OR PUTTY, INSTALLED

WITHIN ANNULUS, FLUSH WITH THE TOP SURFACE OF FLOOR. IF ANNULAR

SPACES ARE LESS THAN 1/4 IN. (6 MM) AND PACKING MATERIAL IS NOT USED,

SEALANT, CAULK OR PUTTY MAY BE INSTALLED WITHIN ANNULUS, FLUSH WITH

THE TOP SURFACE OF FLOOR, BUT IS NOT REQUIRED. FOR W AND L RATINGS,

A MIN 1/4 IN. (6 MM) BEAD OF SEALANT IS REQUIRED AT THE

DEVICE/CONCRETE INTERFACE ON THE TOP SURFACE OF THE FLOOR AND A

MIN 1/4 IN. (6 MM) DEPTH OF SEALANT IS REQUIRED ATOP A MIN 1-3/4 IN. (44

MM) THICKNESS OF…