This document is a statement of work for an electrical installation project at the Island Park Ranger Office of the Caribou-Targhee National Forest. The project includes installing an electrical feeder to a new laundry, shower, and restroom building and coordinating electrical, heating and ventilation installation as the building is constructed. Key details include a start date of September 11, 2023, a contract time of 45 calendar days, and work being measured and paid by lump sum items for the electrical distribution system and building electrical system. The solicitation was issued by the USDA Forest Service Intermountain Region and specifications cover requirements for conduits, boxes, grounding, wiring devices and other electrical systems.

View the file

Other files for this federal contract opportunity

Other files attached to Island Park Laundry Electrical, newest first.
File Type Posted
J.3 Island Park Laundry Drawings.pdf PDF
Island Park Laundry Electrical RFQ 1240LT23Q0128.pdf PDF
J.4 Experience Questionnaire (3 Pages) Island Park Laundry Electrical.pdf PDF
J.1 Wage Determination Fremont County ID20230021 08-04-2023.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION C - DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK 000001-1

Section C - Description/Specifications/Statement of Work

GENERAL SPECIFICATIONS

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

Final – 3/10/2023

1.1 SCOPE OF CONTRACT

A. This project is for the electrical feeder and electrical installation during the construction of the laundry, shower, and restroom building at the Island Park employee RV park in the

Forest Service Island Park Compound.

B. The work includes:

1. The installation of an electrical feeder to the new building site from an existing service.

2. The coordination and installation of electrical, and electric heating and ventilation in the new building as it is being constructed by others.

C. Quantities associated with this contract are identified in the Schedule of Items.

1.2 PROJECT LOCATION

A. The project is located at the Island Park Ranger Office of the Caribou-Targhee National

Forest, 3726 US-20, Island Park, Idaho. It is located approximately 75 miles north of

Idaho Falls, Idaho. The project is behind the office.

1.3 SITE INFORMATION AND LIMITATIONS

A. The following site conditions are considered incidental to the contract and the contractor will not be paid directly for any of the following items:

1. Construction sites are closed to the public during construction. The Contractor will be responsible for signing and limiting access.

2. Contractor will provide all materials and labor necessary to protect streams, wet or dry, during construction activities. The Contractor will be required to submit a stream protection plan and receive approval from the COR, in writing, prior to the beginning of construction.

3. All construction equipment shall be pressure washed before entering National

Forest System lands. The removal of mud and debris from treads, tracks and undercarriage, with emphasis on axles, frame, cross-members, motor mounts, and underneath steps, running boards, and front bumper/brushguard assemblies will be required. The purpose is to reduce or eliminate the transportation of noxious weeds, which is required by Federal and State regulations.

4. Water is available at the site for construction purposes. The Contractor will be responsible for coordinating the installation of temporary power for the site and the cost for the service.

5. The Contractor shall provide temporary toilet facilities (porta-potty) at the site during all construction work.

SECTION C - DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK 000001-2

1.4 TRAFFIC CONTROL AND CONSTRUCTION SIGNING

A. No work that endangers, interferes, or conflicts with traffic or access to work sites shall be performed until a plan for satisfactory warning and handling of traffic has been submitted by the contractor and approved by the COR and Idaho Department of

Transportation. Construction signing for traffic control shall conform to the Manual of

Uniform Traffic Control Devices (MUTCD). All traffic control signs will be placed in areas adequate for a truck pulling a fifth wheel trailer to be turned around. Contractor shall not be paid directly for this item, rather it will be considered incidental to other items of work listed in the Schedule of Items.

1.5 WORK CAMPS, STAGING AND STORAGE AREAS

A. Areas for staging operations and storage of materials shall be approved by the CO. The

Contractor must request in writing for approval from the CO to stage trailers (work) on site.

B. No overnight camping will be allowed on compound without written approval from CO.

1.6 INSPECTION OF WORKSITE

A. The contractor acknowledges they have taken the necessary steps to ascertain the nature and location of work, and have investigated and satisfied themselves as to the general and local conditions that can affect the work or its cost. Any failure of the contractor to take the actions described and acknowledged in this paragraph will not relieve the Contractor from the responsibility of estimating properly the difficulty and cost of successfully performing the work, or for proceeding to successfully perform the work without additional expenses to the government.

1.7 START DATE

A. September 11, 2023

1.8 CONTRACT TIME

A. 45 Calendar Days

1.9 SPECIFICATIONS

A. The following specifications are attached. Some sections in the schedule of items refer to other sections not listed and are subsidiary to, or are included in payment for other pay items in this contract. These items are considered incidental and no additional compensation will be made.

SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND

CABLES

SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

SECTION C - DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK 000001-3

SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION 262726 - WIRING DEVICES

END OF SECTION C

August 2023

COMMON WORK RESULTS FOR ELECTRICAL 260500-1

USDA FOREST SERVICE, R4

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Electrical equipment coordination and installation.

2. Grout.

3. Common electrical installation requirements.

1.2 SUBMITTALS

A. Product Data:

1. For any substitutions for equipment referred to by name in Division 26 specifications or the drawings.

1.3 QUALITY ASSURANCE

A. The installation shall conform to the 2020 Edition of the National Electrical Code (NFPA

70) and to the requirements specified herein.

B. The Contractor shall perform all work necessary and required to accomplish the task as detailed on the drawings and discussed in the installation notes. All work shall be done by a state licensed electrician.

1.4 MEASUREMENT AND PAYMENT

A. The work in this section, including all incidentals in other electrical sections, shall be measured and paid for by one or more of the following methods as shown in the Schedule of Items:

1. Electrical Distribution System - Lump Sum including full compensation for all labor, materials, and incidentals necessary to complete the feeder work as shown on the drawings including all wiring, trenching, bedding, backfill, and all other incidentals necessary for a functional system.

2. Building Electrical System: Lump Sum including full compensation for all labor, materials, and incidentals necessary to complete the work as shown on the drawings including Panel L, grounding, all wiring, devices, and all other incidentals necessary for a functional system.

PART 2 - PRODUCTS

2.1 PRODUCTS REFERRED TO BY NAME

COMMON WORK RESULTS FOR ELECTRICAL 260500-2

A. The materials referred to by trade name, make, or catalog number on the drawings shall be regarded as establishing a minimum standard of quality; substitutions of equal or greater quality can be made by submitting a data sheet of the proposed substituted item to the Contracting Officer, for approval.

2.2 GROUT

A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time.

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to piping systems installed at a required slope.

3.2 RACEWAY AND SIMILAR PENETRATIONS (NON-FIRE RATED, NOT

SLEEVED)

A. Concrete Slabs and Walls: Core-drilled holes.

1. Fill oversized holes with grout to within 1/4-inch (6 mm).

B. Stick-built and Similar Interior-Wall Penetrations: Repair wall to within 1/8-inch (3 mm) to match the surrounding wall finish.

1. Allow for a small gap or flexible fill to allow expansion and contraction to minimize cracking.

C. Aboveground, Exterior-Wall Penetrations: Seal exterior opening around the raceway or cable, using a flexible, waterproofing, joint sealant appropriate for size, depth, and color to closely match the surrounding surface. Finish interior openings, filling opening and matching the exiting surface with appropriate materials and finish quality for the space.

END OF SECTION 260500

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-1

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Copper building wire rated 600 V or less.

2. Connectors, splices, and terminations rated 600 V and less.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 COPPER BUILDING WIRE

A. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.

B. Standards:

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.

C. Conductors: Copper, complying with ASTM B 3 for bare annealed copper and with

ASTM B 8 for stranded conductors.

D. Conductor Insulation:

1. Type THHN/THWN-2: Comply with UL 83.

2. Type XHHW-2: Comply with UL 44.

E. Cable: Comply with NEMA WC 70/ICEA S-95-658 for:

1. Armored cable, Type AC.

2. Metal-clad cable, Type MC.

3. Nonmetallic-sheathed cable, Type NM with ground wire: Comply with UL 83 and

UL 719.

2.2 CONNECTORS AND SPLICES

A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-2

PART 3 - EXECUTION

3.1 CONDUCTOR MATERIAL APPLICATIONS

A. Circuits: Copper; solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

1. Aluminum conductors are prohibited unless specifically called for on the drawings.

3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS

AND WIRING METHODS

A. Feeders: Type THHN/THWN-2 or XHHW, single conductors in raceway.

B. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN/THWN-2, single conductors in raceway; Armored cable, Type AC; Metal-clad cable, Type MC; and

Nonmetallic-sheathed cable, Type NM.

3.3 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls and ceilings.

B. Complete raceway installation between conductor and cable termination points according to Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables.

C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips that will not damage cables or raceway.

3.4 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.

B. Make splices, terminations, and taps that are compatible with conductor material.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches (150 mm) of slack.

END OF SECTION 260519

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-1

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes grounding and bonding systems and equipment.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with UL 467 for grounding and bonding materials and equipment.

2.2 CONDUCTORS

A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.

B. Bare Copper Conductors:

1. Solid Conductors: ASTM B 3.

2.3 CONNECTORS

A. Listed and labeled by a Nationally Recognized Testing Laboratory (NRTL) acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.

B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy.

PART 3 - EXECUTION

3.1 GROUNDING AT THE BUILDING

A. Equipment grounding conductors and grounding electrode conductors shall be connected to the ground bus. Remove main bonding jumper between the neutral and ground buses.

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-2

3.2 EQUIPMENT GROUNDING

A. Install insulated equipment grounding conductors with all feeders and branch circuits.

3.3 INSTALLATION

A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

B. Concrete-Encased Grounding Electrode (Ufer Ground): Fabricate according to NFPA 70;

use bare copper conductor not smaller than No. 4 AWG or as indicated on the drawings, whichever is largest.

1. Bond to all electrically conductive coated steel reinforcing bars or rods in footing.

a. If reinforcing is in multiple pieces, connect footing reinforcing together by the usual steel tie wires (two wraps minimum) and bond to conductor in at least three locations with rebar clamps, or connect together with exothermic welding.

END OF SECTION 260526

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-1

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Metal conduits and fittings.

2. Nonmetallic conduits and fittings.

3. Boxes, enclosures, and cabinets.

4. Handholes and boxes for exterior underground cabling.

1.2 DEFINITIONS

A. GRC: Galvanized rigid steel conduit.

B. IMC: Intermediate metal conduit.

1.3 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 METAL CONDUITS AND FITTINGS

A. Metal Conduit:

1. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. GRC: Comply with ANSI C80.1 and UL 6.

3. IMC: Comply with ANSI C80.6 and UL 1242.

4. PVC-Coated Steel Conduit: PVC-coated rigid steel conduit or IMC.

a. Comply with NEMA RN 1.

b. Coating Thickness: 0.040 inch (1 mm), minimum.

5. EMT: Comply with ANSI C80.3 and UL 797.

B. Metal Fittings:

1. Comply with NEMA FB 1 and UL 514B.

2. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Fittings, General: Listed and labeled for type of conduit, location, and use.

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-2

4. Coating for Fittings for PVC-Coated Conduit: Minimum thickness of 0.040 inch (1 mm), with overlapping sleeves protecting threaded joints.

2.2 NONMETALLIC CONDUITS AND FITTINGS

A. Nonmetallic Conduit:

1. Listing and Labeling: Nonmetallic conduit shall be listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. RNC: Type EPC-40-PVC, complying with NEMA TC 2 and UL 651 unless otherwise indicated.

3. Rigid HDPE: Comply with UL 651A.

4. Continuous HDPE: Comply with UL 651A.

5. RTRC: Comply with UL 2420 BG (Below Ground).

B. Nonmetallic Fittings:

1. Fittings, General: Listed and labeled for type of conduit, location, and use.

2. Fittings for RNC: Comply with NEMA TC 3; match to conduit type and material.

3. Fittings for RTRC: Comply with NEMA TC 14.

4. Solvents and Adhesives: As recommended by conduit manufacturer.

2.3 BOXES, ENCLOSURES, AND CABINETS

A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations.

B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, Type FD, with gasketed cover.

2.4 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING

A. General Requirements for Handholes and Boxes:

1. Boxes and handholes for use in underground systems shall be designed and identified as defined in NFPA 70, for intended location and application.

2. Boxes installed in wet areas shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Standard: Comply with SCTE 77.

4. Configuration: Designed for flush burial with open bottom unless otherwise indicated.

5. Cover: Weatherproof, secured by tamper-resistant locking devices and having structural load rating consistent with enclosure and handhole location.

6. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.

7. Cover Legend: Molded lettering, "ELECTRIC".

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-3

B. Fiberglass Handholes and Boxes: Molded of fiberglass-reinforced polyester resin, with frame and covers of polymer concrete, reinforced concrete, or cast iron.

1. Polymer-concrete units or heavy-duty fiberglass units with polymer-concrete frame and cover, SCTE 77, Tier 8 structural load rating.

PART 3 - EXECUTION

3.1 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed Conduit: GRC or IMC.

a. Feeders and Branch Circuits: EMT allowed with UL listed raintight compression fittings, once the metal raceway is 5-ft (1.5-m) minimum above finished grade.

2. Underground Conduit: GRC or IMC.

a. Once the direct buried conduit extends beyond 5-ft (1.5-m) of initial grade penetration or building foundation penetration, whichever is greater: HDPE, RTRC, or RNC, Type EPC-40-PVC direct buried may be substituted.

3. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R.

B. Indoors: Apply raceway products as specified below unless otherwise indicated:

1. Concealed in Ceilings and Interior Walls and Partitions: Rigid metallic conduit or tubing, or approved cable method, see section 260519.

2. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250.

C. Raceway Fittings: Compatible with raceways and suitable for use and location.

1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB 2.10.

2. PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with this type of conduit. Patch and seal all joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Use sealant recommended by fitting manufacturer and apply in thickness and number of coats recommended by manufacturer.

3. EMT: Comply with NEMA FB 2.10.

3.2 INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter.

B. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.

C. Complete raceway installation before starting conductor installation.

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-4

D. Arrange stub-ups so curved portions of bends are not visible above finished grade.

E. Make bends in raceway using large-radius preformed ells. Field bending shall be according to NFPA 70 minimum radii requirements. Use only equipment specifically designed for material and size involved.

F. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated.

Install conduits parallel or perpendicular to building lines.

G. Coat field-cut threads on PVC-coated raceway with a corrosion-preventing conductive compound prior to assembly.

H. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to 1-1/4-inch (35mm) trade size and insulated throat metal bushings on 1-1/2-inch (41-mm) trade size and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits.

I. Install raceways square to the enclosure and terminate at enclosures with locknuts. Install locknuts hand tight plus 1/4 turn more.

J. Cut conduit perpendicular to the length. For conduits 2-inch (53-mm) trade size and larger, use roll cutter or a guide to make cut straight and perpendicular to the length.

K. Comply with manufacturer's written instructions for solvent welding RNC and fittings.

L. Mount boxes at heights indicated on Drawings. If mounting heights of boxes are not individually indicated, give priority to ADA requirements. Install boxes with height measured to center of box unless otherwise indicated.

M. Locate boxes so that cover or plate will not span different building finishes.

N. Fasten junction and pull boxes to or support from building structure. Do not support boxes by conduits.

3.3 INSTALLATION OF UNDERGROUND CONDUIT

A. Direct-Buried Conduit:

1. Excavate trench bottom to provide firm and uniform support for conduit.

2. All backfill shall be free of materials that may damage the conduit system, such as construction waste, large rocks, sharp rocks, etc. Where natural backfill poses a hazard, alternate backfill material is required.

3. After installing conduit, backfill and compact. Start at tie-in point, and work toward end of conduit run, leaving conduit at end of run free to move with expansion and contraction as temperature changes during this process. Firmly hand tamp backfill around conduit to provide maximum supporting strength. After placing controlled backfill to within 12 inches (300 mm) of finished grade, make final conduit connection at end of run and complete backfilling with normal compaction.

4. Install manufactured rigid steel conduit elbows for stub-ups at poles and equipment.

See 3.1 A.3. this section, for building entrances.

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-5

5. Underground Warning Tape: Comply with requirements in Section 260553

"Identification for Electrical Systems."

3.4 INSTALLATION OF UNDERGROUND HANDHOLES AND BOXES

A. Handholes and Boxes for Underground Wiring are allowed. Keep 2.5-ft (0.5-m) away from roadways and parking areas for nondeliberate loading by vehicles: .

B. Install handholes and boxes level and plumb and with orientation and depth coordinated with connecting conduits to minimize bends and deflections required for proper entrances.

C. Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from 1/2-inch (12.5-mm) sieve to No. 4 (4.75-mm) sieve and compacted to same density as adjacent undisturbed earth.

D. Elevation: Set covers 1 inch (25 mm) above finished grade.

3.5 PROTECTION

A. Protect coatings, finishes, and cabinets from damage and deterioration.

1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

2. Repair damage to PVC coatings or paint finishes with matching touchup coating recommended by manufacturer.

END OF SECTION 260533

IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553-1

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Tapes.

2. Tags.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Comply with ASME A13.1.

B. Comply with NFPA 70.

C. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969.

2.2 TAPES

A. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.

B. Underground-Line Warning Tape:

1. Tape:

a. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical utility lines.

b. Printing on tape shall be permanent and shall not be damaged by burial operations.

c. Tape material and ink shall be chemically inert and not subject to degradation when exposed to acids, alkalis, and other destructive substances commonly found in soils.

d. Width: 3 inches (75 mm).

e. Thickness: 4 mils (0.1 mm).

f. Weight: 18.5 lb/1000 sq. ft. (9.0 kg/100 sq. m).

IDENTIFICATION FOR ELECTRICAL SYSTEMS 260553-2

g. Tensile according to ASTM D 882: 30 lbf (133.4 N) and 2500 psi (17.2

MPa).

2. Color and Printing:

a. Comply with ANSI Z535.1, ANSI Z535.2, ANSI Z535.3, ANSI Z535.4, and

ANSI Z535.5.

b. Inscriptions for Red-Colored Tapes: "ELECTRIC LINE ".

PART 3 - EXECUTION

3.1 PREPARATION

A. Self-Adhesive Identification Products: Before applying electrical identification products, clean substrates of substances that could impair bond, using materials and methods recommended by manufacturer of identification product.

3.2 INSTALLATION

A. Verify identity of each item before installing identification products.

B. Apply identification devices to surfaces that require finish after completing finish work.

C. Marker Tapes: Secure tight to surface at a location with high visibility and accessibility.

D. Underground Line Warning Tape:

1. During backfilling of trenches, install continuous underground-line warning tape directly above cable or raceway at 6 to 8 inches (150 to 200 mm) below finished grade. Use multiple tapes where width of multiple lines installed in a common trench exceeds 16 inches (400 mm) overall.

2. Install underground-line warning tape for direct-buried cables and cables in raceways.

3.3 IDENTIFICATION SCHEDULE

A. Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment. Install access doors or panels to provide view of identifying devices.

B. Identify enclosures and at devices by circuit designation.

C. Locations of Underground Lines: Underground-line warning tape for power, lighting, communication, and control wiring and optical-fiber cable.

D. Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer. Panelboard identification shall be in the form of an engraved, laminated acrylic or melamine label.

END OF SECTION 260553

WIRING DEVICES 262726-1

ISLAND PARK LAUNDRY, SHOWER, AND RESTROOM BUILDING ELECTRICAL

SECTION 262726 - WIRING DEVICES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. GFCI receptacles.

2. Wall switch sensor light switches with passive infrared sensors.

3. Wall plates.

1.2 DEFINITIONS

A. Abbreviations of Manufacturers' Names:

1. Hubbell: Hubbell Incorporated: Wiring Devices-Kellems.

2. Leviton: Leviton Mfg. Company, Inc.

3. Pass & Seymour: Pass& Seymour/Legrand.

B. GFCI: Ground-fault circuit interrupter.

C. Pigtail: Short lead used to connect a device to a branch-circuit conductor.

1.3 SUBMITTALS

A. Product Data: For each type of product.

B. Operation and Maintenance Data: For wiring devices to include in all manufacturers' packing-label warnings and instruction manuals that include labeling conditions.

1.4 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 GENERAL WIRING-DEVICE REQUIREMENTS

A. Wiring Devices, Components, and Accessories: Listed and labeled as defined in

NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NFPA 70.

C. Source Limitations: Obtain each type of wiring device and associated wall plate from single source from single manufacturer.

WIRING DEVICES 262726-2

2.2 GFCI RECEPTACLES

A. General Description:

1. 125 V, 15 A, straight blade, feed-through type.

2. Comply with NEMA WD 1, NEMA WD 6 Configuration 5-15R, UL 498, UL 943

Class A, and FS W-C-596.

3. Include indicator light that shows when the GFCI has malfunctioned and no longer provides proper GFCI protection.

B. Duplex GFCI Convenience Receptacles:

C. Products: Subject to compliance with requirements, provide one of the following:

1. Eaton (Arrow Hart); VGF15.

2. Hubbell Incorporated; Wiring Device-Kellems; GFR5352L.

3. Leviton Manufacturing Co., Inc.; 7590.

4. Pass & Seymour/Legrand (Pass & Seymour); 2095.

2.3 INDOOR OCCUPANCYAND VACANCY SENSORS

A. General Requirements for Sensors:

1. Passive infrared technology (PIR): Ceiling mounted; detect occupants in coverage area by their heat and movement.

a. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum movement of any portion of a human body that presents a target of not less than 36 sq. in. (232 sq. cm).

b. Detection Coverage (Room, Ceiling Mounted): Detect occupancy anywhere in a circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

2. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Occupancy Sensor: Unless otherwise indicated, turn lights on when coverage area is occupied, and turn them off when unoccupied; with a time delay for turning lights off, adjustable over a minimum range of 1 to 15 minutes.

4. Power: Line voltage.

5. Indicator: LED indicator, to show when motion is detected during testing and normal operation of sensor.

2.4 WALL PLATES

A. Shall match corresponding wiring devices.

1. Plate-Securing Screws: Metal with head color to match plate finish.

2. Material for Finished Spaces: 0.035-inch- (1-mm-) thick, satin-finished, Type 302 stainless steel.

http://www.specagent.com/Lookup?ulid=2086 http://www.specagent.com/Lookup?uid=123457066813 http://www.specagent.com/Lookup?uid=123457066814 http://www.specagent.com/Lookup?uid=123457066816 http://www.specagent.com/Lookup?uid=123457066815

WIRING DEVICES 262726-3

B. Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R, extra duty, weather-resistant, die-cast aluminum or thermoplastic with lockable cover.

2.5 FINISHES

A. Device Color:

1. Wiring Devices Connected to Normal Power System: Ivory unless otherwise indicated or required by NFPA 70 or device listing.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with NECA 1, including mounting heights listed in that standard, unless otherwise indicated.

B. Coordination with Other Trades:

1. Protect installed devices and their boxes. Do not place wall finish materials over device boxes and do not cut holes for boxes with routers that are guided by riding against outside of boxes.

2. Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust, paint, and other material that may contaminate the raceway system, conductors, and cables.

3. Install wiring devices after all wall preparation, including painting, is complete.

C. Conductors:

1. Do not strip insulation from conductors until right before they are spliced or terminated on devices.

2. Strip insulation evenly around the conductor using tools designed for the purpose.

Avoid scoring or nicking of solid wire or cutting strands from stranded wire.

3. The length of free conductors at outlets for devices shall meet provisions of

NFPA 70, Article 300, without pigtails.

D. Device Installation:

1. Replace devices that have been in temporary use during construction and that were installed before building finishing operations were complete.

2. Keep each wiring device in its package or otherwise protected until it is time to connect conductors.

3. Do not remove surface protection, such as plastic film and smudge covers, until the last possible moment.

4. Connect devices to branch circuits using pigtails that are not less than 6 inches (152

mm) in length.

5. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid conductor tightly clockwise, two-thirds to three-fourths of the way around terminal screw.

WIRING DEVICES 262726-4

6. Use a torque screwdriver when a torque is recommended or required by manufacturer.

7. When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice No. 12 AWG pigtails for device connections.

8. Tighten unused terminal screws on the device.

9. When mounting into metal boxes, remove the fiber or plastic washers used to hold device-mounting screws in yokes, allowing metal-to-metal contact.

E. Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.

F. Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension vertical

3.2 GFCI RECEPTACLES

A. Install GFCI receptacles at all locations noted on the drawings, non-feed-through unless noted for feed-through protection of downstream receptacles specifically.

3.3 IDENTIFICATION

A. Comply with Section 260553 "Identification for Electrical Systems."

B. Identify each receptacle with panelboard identification and circuit number. Use durable wire markers or tags inside outlet boxes.

END OF SECTION 262726