RVS Electrical and Plumbing Replacement at Tulsa ATCT Federal contract opportunity
Solicitation number
697DCK-23-R-00090
Issued by
Department of Transportation Federal Aviation Administration Southwestern Region

About this file

This solicitation requests proposals for electrical, plumbing, and siding replacement work at an air traffic control tower in Tulsa, Oklahoma. Offerors must be registered in the System for Award Management and submit proposals by the specified due date to be considered. The work includes replacing domestic piping, sanitary sewer lines, water heaters, fixtures, electrical panels and feeders. A site visit is scheduled and attendance is optional. The Federal Aviation Administration seeks these services to upgrade building systems at the tower facility.

View the file

Other files for this federal contract opportunity

Other files attached to RVS Electrical and Plumbing Replacement at Tulsa ATCT, newest first.
File Type Posted
Site Visit Attendee List RVS Project.pdf PDF
Questions and Answers RVS Project 13 Mar 2023.pdf PDF
697DCK-23-R-00090 Amd 3.pdf PDF
697DCK-23-R-00090 Amd 2.pdf PDF
697DCK-23-R-00090 Amend 0001.pdf PDF
J-2 Wage Determinations.pdf PDF
J-1a Drawings RVS ATCT.pdf PDF
J-5 COVID-19 Contractual Requirement Rev 1 8-26-20.pdf PDF
J-6 FAA Certification Vaccination PRAv7_Blank.pdf PDF
J-3 eInvoicing Vendor Notification Letter.pdf PDF
J-4 COVID 19 Memo Contractor_8-17-21.pdf PDF
SIR_697DCK-23-R-00090.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSTRUCTION SPECIFICATIONS

ELECTRICAL SYSTEM REPLACEMENT

PLUMBING REPLACEMENT

SIDING RESEAL

AT

TULSA RIVERSIDE

AIRPORT TRAFFIC CONTROL TOWER

(ATCT) FACILITIES

TULSA, OKLAHOMA

U.S. DEPARTMENT OF TRANSPORTATION FEDERAL

AVIATION ADMINISTRATION

TECHNICAL OPERATIONS (ATO)

CENTRAL SERVICE AREA (CSA)

TERMINAL ENGINEERING CENTER

FORT WORTH, TEXAS

June 2022

JCN – 803971

JCN – 909316

JCN – 1703861

FINAL

FEDERAL AVIATION ADMINISTRATION JUNE 2022

RVS RESEAL, ELECTRICAL & PLUMBING REPLACEMENT

TABLE OF CONTENTS TOC - 1

SECTION 00 01 00 - TABLE OF CONTENTS

DIVISION

NUMBER SECTION NAME

00 01 00 TABLE OF CONTENTS

DIVISION 1 – GENERAL REQUIREMENTS

01 00 00 GENERAL PARAGRAPHS

01 10 00 SUMMARY OF WORK

01 10 12 CONSTRUCTION ADMIN FORMS

01 25 00 SUBSTITUTION PROCEDURES

01 31 00 PROJECT MANAGEMENT & COORDINATION

01 32 00 CONSTRUCTION PROGRESS DOCUMENTATION

01 32 01 PROJECT SCHEDULE

01 33 00 SUBMITTAL PROCEDURES

01 40 00 CONTRACTOR QUALITY CONTROL

01 50 00 TEMPORARY FACILITIES

01 50 10 FAA FIELD REPRESENTATIVE’S OFFICE

01 71 33 PROTECTION OF WORK AND PROPERTY

01 74 13 CONSTRUCTION CLEANING

01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL

01 77 00 CLOSEOUT PROCEDURES

01 77 10 FINAL CLEANING

01 78 23 O&M DATA

01 78 36 WARRANTIES AND GUARANTEES

DIVISION 2 – EXISTING CONDITIONS

02 01 00 INTERIM LIFE SAFEY MEASURES FOR FACILITIES UNDER CONSTRUCTION

02 08 10 ASBESTOS ABATEMENT

02 41 19 SELECTIVE DEMOLITION

DIVISION 3 – CONCRETE

DIVISION 4 MASONRY

DIVISION 5 – METALS

DIVISION 6 – WOOD, PLASTICS, AND COMPOSITES

DIVISION 7 – THERMAL AND MOISTURE PROTECTION

07 92 00 JOINT SEALANT

TABLE OF CONTENTS TOC - 2

DIVISION 8 – OPENINGS

08 11 13 HOLLOW METAL DOORS AND FRAMES

08 53 13 VINYL WINDOWS

08 71 00 DOOR HARDWARE

08 80 00 GLAZING

DIVISION 9 – FINISHES

09 51 13 ACOUSTICAL PANEL CEILINGS

09 65 13 RESILIENT BASE AND ACCESSORIES

09 65 19 RESILIENT TILE FLOORING

09 68 13 TILE CARPETING

09 91 13 EXTERIOR REPAINTING

09 96 53 ELASTOMERIC COATING

DIVISION 22 – PLUMBING

22 05 00 COMMON WORK RESULTS FOR PLUMBING

22 05 19 METERS AND GAUGES FOR PLUMBING PIPING

22 05 23 GENERAL DUTY VALVES FOR PLUMBING PIPING

22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

22 05 48 VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

22 07 00 PLUMBING INSULATION

22 11 16 DOMESTIC WATER PIPING

22 11 19 DOMESTIC WATER SPECIALTIES

22 13 16 SANITARY WASTE AND VENT PIPING

22 13 19 SANITARY WASTE PIPING SPECIALTIES

22 33 00 ELECTRIC DOMESTIC WATER HEATERS

22 40 00 PLUMBING FIXTURES

22 47 13 DRINKING FOUNTAINS & BOTTLE FILLILLING STATION

22 47 23 REMOTE WATER COOLERS

DIVISION 23 – HEATING VENTILATING AND AIR CONDITIONING

23 31 13 METAL DUCTS

23 34 23 HVAC POWER VENTILATORS

23 81 13 PACKED TERMINAL AIR CONDITIONERS, THROUGH WALL UNITS

DIVISION 26 – ELECTRICAL

26 01 00 GENERAL REQUIREMENTS FOR ELECTRICAL WORK

26 05 00 BASIC ELECTRICAL MATERIALS AND METHODS

26 05 74 ARC FLASH HAZARD ANALYSIS

26 06 00 GROUNDING AND BONDING

26 07 50 ELECTRICAL IDENTIFICATION

26 10 00 RACEWAYS, BOXES, AND CABINETS

26 12 00 WIRES AND CABLES

26 19 00 SUPPORTING DEVICES

26 47 00 PANELBOARDS

TABLE OF CONTENTS TOC - 3

26 47 60 DISCONNECT SWITCH AND CIRCUIT BREAKERS

26 51 00 INTERIOR LIGHTING

26 56 00 EXTERIOR LIGHTING

26 60 50 TRANSIENT VOLTAGE SURGE SUPPRESSION

ATTACHMENT NO. 1 FAA-C-1217H

ATTACHMENT NO. 2 FAA-STD-019F

ATTACHMENT NO. 3 SITE SUPPLEMENTAL CONDITIONS

ATTACHMENT NO. 4 EOSH IMPACTS

ATTACHMENT NO. 5 COVID-19 REQUIREMENTS

END OF DOCUMENT 00 01 00

SAT AHU#6 & AHU #7 REPLACEMENT

AND

E/G VENTILATION SYSTEM

THIS PAGE INTENTIONALLY LEFT BLANK

GENERAL PARAGRAPHS 01 00 00 - 1

SECTION 01 00 00 – GENERAL PARAGRAPHS

PART 1 - GENERAL

1.1 DRAWINGS, SPECIFICATIONS, AND OTHER CONTRACT DOCUMENTS

A. Drawings showing general outlines and details necessary for a comprehensive understanding of the work form a part of the Contract Documents. The total number and the titles of the drawings constituting the Drawings are given in the index of the Drawings. All work under the Contract must be performed in all respects in compliance with the requirements of the Contract Documents.

B. The Contract Documents provide for a complete work, and may have been prepared in divisions of various crafts, trades and other categories of work. The Contractor is responsible for the performance of all work under the Contract regardless of any such divisions, and must ensure that all of the work is performed and completed.

C. The FAA will provide the Contractor with one bound copy of the construction drawings and specifications for the Contractor’s use during the execution of the Contract. The Contractor may reproduce these documents for its use during the performance of the work under this Contract.

D. The Contractor must maintain at the Site at all times at least one (1) copy of Drawings, Specifications and all other Contract Documents, together with at least one (1) complete set of approved Shop Drawings and approved samples.

E. The Contract, Drawings, Specifications, and all referenced standards cited are essential parts of the Contract requirements. A requirement occurring in one is as binding as though occurring in all. They are intended to be complementary and to describe and provide for a complete work.

F. On the drawings, calculated or figured dimensions govern over scaled dimensions.

G. Generally the electrical drawings and any drawings relating to piping are schematic only and dimensions shall be followed without regard to scale. Drawings show the general arrangement and the extent of the work. Exact location and equipment arrangement shall be determined by the physical dimensions of the equipment actually furnished, by shop drawings, detailed dimensioned drawings. Submit all necessary shop drawings mentioned in drawings or specifications.

H. In the event of a conflict between commercially available or industry standard documents and specific requirements in FAA Orders and Notices, the more stringent shall apply.

I. The contractor is responsible to provide a certification to FAA that all materials used on this project are free of lead and asbestos

J. The Contractor must not take advantage of any apparent error, omission, discrepancy, or

GENERAL PARAGRAPHS 01 00 00 - 2

ambiguity on the Drawings or Specifications. If any error, omission, discrepancy, or ambiguity is found by the Contractor in the Drawings or Specifications, the Contractor must refer these to the Contracting Officer (CO) prior to beginning work on affected task(s), for interpretation and decision, and such decision must be final.

K. The CO has the right to correct apparent errors or omissions in the Drawings and Specifications and to make such interpretations as he may deem necessary for the proper fulfillment of the Contract Documents. During the course of the work, should any conflicts, ambiguities, or discrepancies be found that are not addressed or any discrepancies between the Drawings and the Specifications to which the Contractor has failed to call attention before submitting the offer, then the CO will interpret the intent of the Drawings and Specifications and the Contractor hereby agrees to abide by the CO’s interpretation and agrees to carry out the work in accordance with the decision of the CO. In such event the Contractor will be held to have included in the offer the most proper material and/or method of construction in order to fulfill the intent of the Contract Documents.

L. When a material, article, or equipment is designated by a brand name, and more than one brand name is listed, it will be understood that the design is based on one of the brand name listed products. The Contractor will be responsible for all coordination necessary to accommodate the material, article, or equipment actually being provided and per the requirements of Section 01 25 00 without additional cost to the government.

M. The organization of the specification into divisions, sections and articles, and the arrangement of Drawings does not restrict or limit the Contractor in dividing the Work among Subcontractors or in establishing the extent of work to be performed by any trade.

N. Product and Reference Standards:

1. When descriptive catalog designations including manufacturer’s name, product brand name, or model number are referred to in the Contract Documents, such designations are considered as being those found in industry publications of current issue on the date of the first advertisement for offers.

2. When standards of the Federal Government, State Department of Transportation, Standards Organization such as ASTM, AASHTO, AWS, or ANSI, trade societies, or trade associations are referred in the Contract Documents by specific date of issue, these are considered a part of this Contract. When such references do not bear a date of issue, the current published edition on the date of the first advertisement for offers are considered as part of the Contract.

3. Where in the Contract Documents an item is identified by a particular manufacturer’s name, model or other code it must be interpreted to include other manufacturers’ product of like and equal quality whether the words “or equal” are included or not unless specifically stated otherwise.

4. Wherever a particular manufacturer’s product is required, to the exclusion of all others, appropriate language is included in the Contract Documents.

5. Wherever the terms, “as directed”, “ordered”, “permitted”, “designate”, “as approved”, “approved equal”, “or equal”, “acceptable” and other words of similar meaning which authorize an exercise of judgement are used in the Contract Documents, such judgment is vested only in the CO or designated representative.

6. When a particular manufacturer’s product is used, the Basis of Design and Section 01 25

GENERAL PARAGRAPHS 01 00 00 - 3

00 shall be follow and be in conformance.

1.2 CONFORMITY WITH DRAWINGS AND SPECIFICATIONS

A. No deviation from the Drawings, Specifications and other Contract Documents will be permitted without the prior written approval of the CO.

1.3 SUPERVISION AND CONSTRUCTION PROCEDURES

A. At all times during performance of this contract, and until the work is completed and accepted, the Contractor must directly superintend the work or assign and have on the worksite a competent superintendent who is an employee of the Contractor and is satisfactory to the CO and has the authority to act for the Contractor.

B. The Contractor must supervise and direct the Work, using the Contractor's best skill and attention. The Contractor is solely responsible for and has control over construction means, methods, techniques, sequences, and procedures and for coordinating all portions of the Work under the Contract including coordination of the duties of all trades, unless the Contract Documents give other specific instructions concerning these matters.

C. The Contractor must control its operations and those of its Subcontractors and Suppliers to assure the least inconvenience to the traveling public. Under all circumstances, safety must be the most important consideration.

D. Contractor must lay out all work well enough in advance to avoid conflicts or interferences with other work in progress so that in case of interference the layout may be altered to suit the conditions, prior to the installation of any work and without additional cost to the FAA. The Contractor must be responsible to coordinate all work and take all action as required to avoid conflicts between trades.

1.4 CORRESPONDENCE

A. Contract correspondence must be directed to the CO with a copy to the COR.

B. Send submittals directly to the COR with a copy of the transmittal letter to the CO.

1.5 LIST OF SUBCONTRACTORS

A. The Contractor must, within 10 calendar days after award, furnish to the CO with a copy to the COR, a list of subcontractors showing the type of work each will perform. If all subcontracts have not been awarded when the initial list is submitted, the Contractor must update the list monthly.

1.6 EXISTING WORK

A. The disassembling, disconnecting, cutting, removal, or altering in any way of existing work must be carried on in such a manner as to prevent injury or damage to all portions of existing work, whether they are to remain in place, be re-used in the new work, or be salvaged and stored.

GENERAL PARAGRAPHS 01 00 00 - 4

B. All portions of existing work which have been cut, damaged, or altered in any way during construction operations must be repaired or replaced in kind in an approved manner to match existing or adjoining work. All work of this nature must be performed by the Contractor at his expense and must be as directed. Existing work must, at the completion of all operations, be left in a condition as good as existed before the new work started.

1.7 MATERIALS AND EQUIPMENT TO BE SALVAGED

A. Except where specifically specified otherwise herein, or designated on the drawings, all existing materials and equipment which are required to be removed or disconnected to perform the work but are not indicated or specified for use in the new work, becomes the property of the Contractor and must be disposed of properly.

1.8 UNCOVERING AND CORRECTION OF WORK

A. Uncovering Work

1. If any portion of the Work is covered contrary to the COR's request or to requirements specifically expressed in the Contract Documents, it must, if required in writing by the COR be uncovered for his observation and be recovered (if corrections are not required) or be corrected, if applicable, at the Contractor's expense without change in the Contract Time.

B. Correction of Work

1. The Contractor must promptly correct Work rejected by the COR that fails to conform to the requirements of the Contract Documents, whether observed before or after Substantial Completion and whether or not fabricated, installed or completed. The Contractor must bear all costs of correcting such rejected Work, including additional testing and inspections and compensation for the COR's services and expenses incurred by the FAA.

2. If, within two years after the date of Substantial Completion of the Work or designated portion thereof, or after the date for commencement of warranties established above, or by terms of an applicable special warranty required by the Contract Documents, any of the work is found to be not in accordance with the requirements of the Contract Documents, the Contractor must correct it promptly after receipt of written notice from the FAA to do so unless the FAA has previously given the Contractor a written acceptance of that specific condition. This period of two years must be extended with respect to portions of Work first performed after Substantial Completion by the period of time between Substantial Completion and the actual performance of the Work. This obligation survives acceptance of the Work under the Contract and termination of the Contract. The FAA must give such notice within a reasonable amount of time after discovery of the condition.

3. The Contractor must remove from the site portions of the Work that are not in accordance with the requirements of the Contract Documents and are neither corrected by the Contractor nor accepted by the FAA.

4. If the Contractor fails to correct nonconforming Work within a reasonable time, the FAA may correct it in accordance with General Provisions. If the Contractor does not proceed with correction of such nonconforming Work within a reasonable time fixed by written

GENERAL PARAGRAPHS 01 00 00 - 5

notice from the COR, the FAA may correct or remove such nonconforming work and all costs for such corrections or removals must be assessed against the Contractor.

5. The Contractor must bear the cost of correcting destroyed or damaged Work, whether completed or partially completed, of the FAA or separate contractors caused by the Contractor's performing correction or removal of Work which is not in accordance with the requirements of the Contract Documents.

6. Nothing contained herein shall be construed to establish a period of limitation with respect to other obligations that the Contractor might have under the Contract Documents. Establishment of the time period of two years as described above relates only to the specific obligation of the Contractor to correct the Work, and has no relationship to the time within which the obligation to comply with the Contract Documents may be sought to be enforced, nor to the time within which proceedings may be commenced to establish the Contractor's liability and damages with respect to the Contractor's obligations other than specifically to correct the Work.

1.9 LOCATION OF SERVICES

A. The FAA does not guarantee the accuracy or the completeness of the location information relating to existing utility services, facilities, or structures that may be shown on the drawings.

Any inaccuracy or omission in such information must not relieve Contractor of its responsibility to protect such existing features from damage or unscheduled interruption of service.

1.10 COOPERATE WITH OTHER ENTITIES

A. Cooperate with the FAA and other public or private utility services, or a utility service of another government agency that may be authorized by the FAA to construct, reconstruct, or maintain such utility services or facilities during the progress of the work. Control operations to prevent the unscheduled interruption of such utility services and facilities.

1.11 DAMAGE TO SERVICES

A. Should Contractor damage or interrupt the operation of a utility service or facility by accident or otherwise, it must immediately notify in writing the FAA/operator, appropriate public safety authorities, and the COR and must take all reasonable measures to prevent further damage or interruption of service. Cooperate with the utility service or facility FAA and the COR continuously until such damage has been repaired and service restored.

1.12 FAILURE TO PROTECT PROPERTY

A. Contractor will not be entitled to any extension of time or compensation on account of Contractor’s failure to protect all facilities, equipment, materials and other property as described herein. All costs in connection with any Improvements or restoration necessary or required by reason of unauthorized obstruction, damage, or use must be borne by Contractor.

1.13 UTILITY CONTRACTOR LICENSING REQUIREMENTS

GENERAL PARAGRAPHS 01 00 00 - 6

A. Contractor must comply with all state and local requirements for construction of utilities.

1.14 ASBESTOS AND LEAD FREE CERTIFICATION

A. FAA policy is to construct all new facilities without asbestos or lead containing products. The Contractor must provide a letter on his company’s standard letter head stating that to the best of his knowledge no product or material used on this project contains asbestos or lead. The statement must include the name of the project and the contract number and must be signed by an officer of the company. The statement must be furnished within 10 calendar days of the Substantial Completion date. Submission of this statement is a condition for final payment under the contract.

B. Verification: If the FAA suspects the presence of asbestos or lead, tests will be performed on the material or product at the FAA’s expense. If it is determined that the product or material does contain asbestos or lead, then the Contractor must remove the product or material and replace at his own expense including the expense of the testing and any retesting that may be necessary.

C. Non – Compliance: If the Contractor fails to provide the above statement, then the FAA may have a complete building survey performed by a qualified testing firm and the costs deducted from the Contractor’s final payment.

1.15 SAFETY DATA SHEETS (SDS):

A. The Contractor must submit to the COR Safety Data Sheets (SDS) for all materials and/or products utilized during the course of the project accomplishment. During the course of the project, both the COR and the Contractor must routinely check products utilized on-site to ensure only products which have had SDS submitted are utilized. Copies of all SDS must be turned over to the local FAA office for their records.

1.16 INITIAL SUBMITTALS

A. The following submittals are required to have FAA approval prior to Notice to Proceed.

1. Section 01 00 00 LIST OF SUBS, CERTIFICATE OF INSURANCE

2. Section 01 32 00 CONSTRUCTION SCHEDULE

3. Section 01 33 00 SUBMITTAL PROCEDURES

4. Section 01 40 00 CONTRACTOR QUALITY CONTROL

5. Section 01 50 10 FAA FIELD REPRESENTATIVE’S OFFICE

6. Section 22 33 00 ELECTRIC DOMESTIC WATER HEATERS

7. Section 22 47 00 DRINKING FOUNTAINS

8. Section 22 47 23 REMOTE WATER COOLERS

9. Section 23 11 13 PACKAGED TERMINAL AIR-CONDITIONERS

10. Section 26 47 00 PANELBOARDS

11. Section 26 47 60 DISCONNECT SWITCH AND CIRCUIT BREAKERS

PART 2 - PRODUCTS

GENERAL PARAGRAPHS 01 00 00 - 7

NOT USED

PART 3 - EXECUTION

END OF SECTION 01 00 00

SUMMARY OF WORK 01 10 00 - 1

SECTION 01 10 00 – SUMMARY OF WORK

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following:

1. Work covered by the Contract Documents.

2. Type of the Contract.

3. Work phases.

4. Work under other contracts.

5. Use of premises.

6. FAA's occupancy requirements.

7. Work restrictions.

8. Specification formats and conventions.

9. Permits and Fees

10. Security Requirements

11. Insurance

1.2 DEFINITIONS

A. Contracting Officer’s Representative (COR): Individual authorized to receive and distribute information on the behalf of the Contracting Officer. Also referred to as the Contracting Officer’s Technical Representative (COTR) and/or Resident Engineer (RE) in some instances.

B. Recycled Content: The recycled content value of a material assembly shall be determined by weight. The recycled fraction of the assembly is then multiplied by the cost of assembly to determine the recycled content value.

1. "Post-consumer" material is defined as waste material generated by households or by commercial, industrial, and institutional facilities in their role as end users of the product, which can no longer be used for its intended purpose.

2. "Pre-consumer" material is defined as material diverted from the waste stream during the manufacturing process. Excluded is reutilization of materials such as rework, regrind, or scrap generated in a process and capable of being reclaimed within the same process that generated it.

C. Recycled Content: The percentage by weight of constituents that have been recovered or otherwise diverted from the solid waste stream, either during the manufacturing process (pre-consumer), or after consumer use (post-consumer).

1. Spills and scraps from the original manufacturing process that are combined with other constituents after a minimal amount of reprocessing for use in further production of the same product are not recycled materials.

SUMMARY OF WORK 01 10 00 - 2

2. Discarded materials from one manufacturing process that are used as constituents in another manufacturing process are pre-consumer recycled materials.

1.3 WORK COVERED BY CONTRACT DOCUMENTS

A. Project Identification: T u l s a Riverside Airport - Airport Traffic Control Tower Electrical, Plumbing, and Exterior Reseal

B. FAA's Lead Project Engineer: Walter Parker III (AJW-2C11C) FAA Central Service Area

C. CO (Contracting Officer): TBD

D. The Work consists of the construction of the following:

Electrical

1. Replace new I-Line Panel DPE-A, 200A, 208V/120V, 3 PH, 4 W and Feeders included Wires & Conduits in the Storage Room fed from Disconnect Switch 2.

Provide and Install new circuit breaker No. 3 from existing I-Line Panel DPN-A included wires and conduits to feed for new Panel DPE-A with new TVSS Box on the first floor.

2. Demolish existing Main Service Entrance/Disconnect Switch 2 with Fuse, 200 Amp, 3 PH, 240V and existing TVSS Box in the Electrical Room.

3. Replace new Panel LPE-A, 100A, 208V/120V, 3 PH, 4 W, in the Storage Room. Fed from Panel DPE-A, Replace new wiring and conduits to new Panel LPE-A. Not Needed TVSS Box on the first floor

4. Replace new Panel Telco, 50A, 208V/120V, 3 PH, 4 W, in the Telco Room. Fed from Panel DPE-A, Replace new wiring and conduits to new Panel Telco. Not Needed TVSS Box on the first floor.

5. Replace new Panel LPN-A, 100A, 208V/120V, 3 PH, 4 W, in the Electrical Room.

Fed from Panel DPN-A, Replace new wiring and conduits to new Panel LPN-A.

Needed TVSS Box on the first floor.

6. Replace new Panel F, 3- 50A MCB, 208V/120V, 3 PH, 4 W, in the Electrical Room.

Fed from ATS, Replace new wiring and conduits to new Panel F. Needed TVSS Box on the first floor.

7. Install new TVSS Box for existing Panel DPHVAC, 225A, 208V/120V, 3 PH, 4 W, in the Storage Room. Fed from Panel DPN-A on the first floor.

8. Replace new Panel LPE-C, 100A, 208V/120V, 3 PH, 4 W, in the UPS Room. Fed from Panel DPE-A, Replace new wiring and conduits to new Panel LPE-C. Needed TVSS Box on the third floor.

9. Replace new Panel LPE-D, 100A, 208V/120V, 3 PH, 4 W, in the Locker Room. Fed from Panel DPE-A, Replace new wiring and conduits to new Panel LPE-D. Not Needed TVSS Box on the fourth floor.

10. Replace new Panel DPE-B, 100A, 208V/120V, 3 PH, 4 W included new feeders on the Junction Level and Fed from Panel DPE-A. Not Needed TVSS Box on the fifth floor.

11. Replace new Panel LPE-B, 100A, 208V/120V, 3 PH, 4 W included new feeders.

Provide and install new 3P-50A circuit breaker No. 9/11/13 from new Panel DPE-B to feed for new Panel LPE-B. Needs TVSS Box on the Fifth Floor.

SUMMARY OF WORK 01 10 00 - 3

12. Replace new Panel DPN-B, 225A, 208V/120V, 3 PH, 4 W Fed from Panel DPN-A on the Junction Level. All circuit breakers from existing Panel LPN-B will be moving to new Panel DPN-B. Needed TVSS Box on the fifth floor.

13. Demolish existing Panel LPN-B, 100A, 208V/120V, 3 PH, 4 W Fed from Panel DPN-B included wires and conduits on the Junction Level.

14. Remove existing Speaker and feeders next to panel DPN-B on the fifth floor.

15. Replace and install Two (2) new 1’X4’ LED Lighting Fixtures in the Electrical Room

Plumbing

1. Replace domestic pipe and sanitary sewer pipe throughout the building

2. Replace the 2nd floor drinking fountain

3. Replace the water closets and lavatories in all bathrooms

4. Replace 1st floor and 4th floor water heaters

5. Remove 4th floor humidifiers

Civil

1. Replace all ATCT joint sealant including Cab Glass sealant

2. Replace ATCT windows (Cab windows to remain)

3. Coat ATCT with elastomeric coating and properly flash applicable penetrations

4. Paint and reseal catwalk and cab level metal panels.

5. Replace two backup PTAC units on 3rd floor

6. Replace 4th floor finishes (Tile, Carpet Tile, Paint walls, Replace ceiling tiles)

7. Replace catwalk access door

8. Add toe board to catwalk roof guard rail in required areas

9. Replace cab roof access ladder

1.2 TYPE OF CONTRACT

A. Project will be constructed under a firm fixed price contract awarded to a single contractor.

1.3 WORK PHASES

A. The Work shall be conducted in one phase. The Contractor will be responsible for determining the sequence of operation to maintain security of the construction site.

B. Before commencing Work, submit a schedule showing the sequence, commencement, and completion dates for all of the Work.

1.4 WORK UNDER OTHER CONTRACTS

A. General: Cooperate fully with separate contractors so work on those contracts may be carried out smoothly, without interfering with or delaying work under this Contract. Coordinate the Work of this Contract with work performed under separate contracts.

B. Experience: Contractor must have experience working at an ATCT/TRACON operational facility. Contractor must show they have completed at least one project at an operational facility in the last 5 years, with a construction cost greater than $500,000.

1.5 USE OF PREMISES

SUMMARY OF WORK 01 10 00 - 4

A. General: Contractor shall have full use of premises for construction operations, including use of

Project site, during construction period. Contractor's use of premises is limited only by FAA's right to perform work or to retain other contractors on portions of Project.

B. Use of Site: Limit use of premises to areas within the Contract limits indicated. Do not disturb portions of Project site beyond areas in which the Work is indicated.

1.6 FAA'S OCCUPANCY REQUIREMENTS

B. Full FAA Occupancy: FAA will occupy Project site and existing building(s) during entire construction period. Cooperate with FAA during construction operations to minimize conflicts and facilitate FAA usage. Perform the Work so as not to interfere with FAA's day-to-day operations.

Maintain existing exits unless otherwise indicated.

1. Maintain access to existing walkways, corridors, and other adjacent occupied or used facilities. Do not close or obstruct walkways, corridors, or other occupied or used facilities without written permission from FAA and approval of authorities having jurisdiction.

2. Notify FAA not less than 14 days in advance of activities that will affect FAA's operations.

1.7 WORK RESTRICTIONS

A. Normal working hours are 0700 to 1700, Monday through Friday (except U.S. Federal holidays). Contractor requests to work outside normal working hours require COR approval.

However, the COR has full discretion to approve or disapprove, or withdraw approval of requests. If the contractor desires to work outside normal hours (including Saturdays, Sundays, and holidays), he shall submit his written request to the COR at least 48 hours in advance.

Some typical constraints on working outside normal working hours are:

1. The Contractor’s request must be made at least two days in advance (e.g., request received by close of business Wednesday for work on following Saturday). Prior to submitting the request, the Contractor must coordinate as needed (such as utility outages) and have all required people and materials for the work that will be performed.

2. A Contractor with quality or safety problems (as determined by the COR) will be restricted to normal working hours. Contractors may also not work time outside of normal working hours if they are not present on the job site during normal working hours.

3. A Contractor who fails to correct deficiencies within a reasonable time (as determined by the COR) will be restricted to normal working hours or may be allowed to work outside normal working hours only to correct those deficiencies.

4. The Contractor shall schedule his work to cause the least amount of interference to normal activities

B. Night work shall be expected for the following tasks (10:00pm – 5:00am)

1. Panel cutovers

2. Work in the cab

3. 4th floor asbestos abatement

4. 4th floor flooring replacement

5. As indicated on drawings

SUMMARY OF WORK 01 10 00 - 5

C. Existing Utility Interruptions: Do not interrupt utilities serving facilities occupied by FAA or others unless permitted under the following conditions and then only after arranging to provide temporary utility services according to requirements indicated:

1. Existing Utility Interruptions: Do not interrupt utilities serving facilities occupied by

FAA or others unless permitted under the following conditions and then only after arranging to provide temporary utility services according to requirements indicated: Notify FAA COR not less than 10 days in advance of proposed utility interruptions.

2. Do not proceed with utility interruptions without FAA and utility company written permission.

D. Nonsmoking Building: Smoking is not permitted inside the buildings or within 25 feet of the building entrances, operable windows or openings, outdoor air intakes throughout the duration of the construction.

E. Limits on Operations: The FAA has established moratorium dates for construction activity at critical facilities. The intent is to minimize the possibility of any activity that may have an adverse impact on the ability of FAA to perform its operational activities. Moratorium dates may change without notice. The moratorium dates are generally:

November – Friday before Thanksgiving through Monday after Thanksgiving December/January – Friday before Christmas through Monday after New Years

All construction activity during moratorium periods must be approved in advance by the FAA.

Submit items of work to be performed during moratorium dates no later than forty-five (45) days prior to the moratorium dates. Activities that have, in the sole opinion of the FAA, potential to negatively impact FAA operations will not be approved. A written waiver will be provided by FAA to the Contractor outlining the allowable work items. No additional time or cost will be allowed for such denial.

1.8 SPECIFICATION FORMATS AND MISCELLANEOUS PROVISIONS

A. Specification Format: The Specifications are organized into Divisions and Sections using the 50-division format and CSI/CSC's "MasterFormat" numbering system.

1. Section Identification: The Specifications use Section numbers and titles to help cross-referencing in the Contract Documents. Sections in these Specifications are in numeric sequence; however, the sequence is incomplete because all available Section numbers are not used. Consult the table of contents at the beginning of the Project Manual to determine numbers and names of Sections in the Contract Documents.

2. Division 01: Sections in Division 01 govern the execution of the Work of all Sections in the Specifications.

A. Specification Content: The Specifications use certain conventions for the style of language and the intended meaning of certain terms, words, and phrases when used in particular situations.

These conventions are as follows:

1. Abbreviated Language: Language used in the Specifications and other Contract

SUMMARY OF WORK 01 10 00 - 6

Documents is abbreviated. Words and meanings shall be interpreted as appropriate.

Words implied, but not stated, shall be inferred as the sense requires. Singular words shall be interpreted as plural and plural words shall be interpreted as singular where applicable as the context of the Contract Documents indicates.

2. Imperative mood and streamlined language are generally used in the Specifications.

Requirements expressed in the imperative mood are to be performed by Contractor.

Occasionally, the indicative or subjunctive mood may be used in the Section Text for clarity to describe responsibilities that must be fulfilled indirectly by Contractor or by others when so noted.

a. The words "shall," "shall be," or "shall comply with," depending on the context, are implied where a colon (:) is used within a sentence or phrase.

1.9 PERMITS AND FEES

A. Listed below are the agencies that govern this project. Unless otherwise noted, Contractor is responsible for applying for utility services, obtaining required permits, and payment for any associated fees. Compliance is required with the conditions of all permits that have been issued.

Additional permits may need to be obtained by the Contractor and all fees must be paid by the Contractor.

1. Air Space– All permanent and temporary work, including cranes, must comply with FAA

Obstruction Evaluation / Airport Airspace Analysis (OE/AAA) requirements. Contractor shall file a Request for Construction for permanent structures on Airport. The Request should be submitted online. The website for more information and to obtain the appropriate forms is https://oeaaa.faa.gov/oeaaa/external/puntal.jsp. Erection of the crane will not be permitted without approval of the form. No claim for delay will be allowed for failure to submit the form in a timely manner. Allow a minimum of sixty (60) days for processing. Contractor is responsible for follow up with the issuing office after submittal.

2. The contractor will be responsible for any additional fees, payments or applications required for the site utilities that have not been identified above.

1.10 INSURANCE

A. Insurance Requirements

The Contractor shall at its sole expense, procure and maintain in effect at all times during the performance of the Work insurance coverage with insurers and under forms of policies satisfactory to the FAA, and with limits not less than those set forth in the contract.

The contractor shall not commence work until he/she has obtained, and the Contracting Officer has approved, all insurance required within the contract, nor shall the contractor allow any subcontractor(s) to commence work on a subcontract until all similar insurance required of the subcontractor has been obtained and approved. The successful contractor shall be required to procure and maintain bodily injury, general liability, and property damage liability insurance in his/her own name as protection against damages to persons or property, including injury or death, which may result from his/her performance of the work.

The insurance required shall be written for not less than the limits of liability specified in the

SUMMARY OF WORK 01 10 00 - 7

contract documents, or required by law, whichever is greater. The proof of insurance shall be furnished within ten (10) days from the date of the Notice of Award to the Contracting Officer for approval.

The insurance limits shall be maintained during the entire performance or contract work. No cancellations of any insurance, whether by the insurer or by the insured, shall be effective unless written notice thereof is given to the Contracting Officer at least thirty (30) days prior to the intended effective date thereof, which date has been expressed in the notice. Prior to the effective date of any such cancellation, the contractor shall take out new insurance to cover the policies so canceled. All insurance policies referred to shall be underwritten by companies authorized to do business in the state of construction. The Certification shall be an “ACCORD” certificate with the Contract number and job location identified.

Workmen's Compensation Insurance This contract shall be void and of no effect unless the contractor secures compensation for the benefit of (and keep insured during the life of this contract) such employees as are required to be insured by the Workmen's Compensation Insurance Law in the state of construction. The contractor hereby agrees to secure such compensation in the manner prescribed by law. The contractor shall require any subcontractors similarly to provide Workmen's Compensation Insurance for all the latter's employees to be engaged in the work unless such employees are covered by the protection afforded by the contractor's Workmen's Compensation Insurance.

The above-indicated insurance shall be maintained during the entire performance of contract work. No cancellation of any insurance, whether by the insurer or by the insured, shall be effective unless written notice thereof is given to the Contracting Officer at least thirty (30) days prior to the intended effective date thereof, which date has been expressed in the notice. Prior to the effective date of any such cancellation, the contractor shall take out new insurance to cover the policies so canceled. All insurance policies referred to shall be underwritten by companies authorized to do business in the state of construction.

B. FAA Furnished Insurance

1. FAA is not maintaining any insurance on behalf of Contractor covering against loss or damage to the Work or to any other property of Contractor. In the event Contractor maintains insurance against physical loss or damage to Contractor’s construction equipment and tools, such insurance shall include an insurer's waiver of rights of subrogation in favor of FAA.

C. Notifications

1. In accordance with the submittal requirements outlined above, Contractor shall deliver the original and two (2) copies of the Certificate(s) of Insurance required by this clause and all subsequent notices of cancellation, termination and alteration of such policies to the CO with a copy to the COR.

D. Certificate of Insurance

1. The scope of coverage shall be shown on the certificate of insurance as “All operations of the Named Insured”.

1.11 SECURITY REQUIREMENTS

A. Personnel List: Contractor shall provide the Resident Engineer with a list of Contractor's

SUMMARY OF WORK 01 10 00 - 8

personnel who will require access to the site. The list shall be kept current during project work.

The Contractor shall provide all personnel with readily identifiable numbered badges during the period their access to the site is required. Badges shall be worn on outer clothes at all times when on airport property and at work in the site.

B. Security Investigation: If contractor needs access to active facility, Contractor's site superintendent shall submit to an FAA security background check and obtain an official FAA contractor ID badge. Other Contractor personnel may be subject to security investigation by FAA. Upon request by the Contracting Officer’s Representative, the Contractor shall promptly complete all security forms provided by FAA.

C. Communication: The Contractor shall request through the COR, a meeting with the Airport Manager and Control Tower personnel to discuss planned Contractor activities in the controlled airport operation area.

D. Airport Requirements: Contractor must also meet all the Airport's security requirements for work at the airport. FAA will not provide escorts, communication, or transportation.

PART 2 - PRODUCTS

PART 3 - EXECUTION

END OF SECTION 01 10 00

RVS ELECTRICAL, PLUMBING, & SIDING REPLACEMENT

CONSTRUCTION ADMINISTRATION FORMS 01 10 12 - 1

SECTION 01 10 12 - CONSTRUCTION ADMINISTRATION FORMS

PART 1 – GENERAL

1.1 INDEX OF CONSTRUCTION ADMINISTRATION FORMS:

RFI Standard Form Transmittals for Contractor’s Materials or Shop Drawings Resident Engineer EOSH Checklist (FAA 3900-19) Pre-Construction and Maintenance Project Safety and Health Checklist (FAA 3900-18) Lock Out/Tag Out Procedure (See Division 26)

SEE DIVISION 2 FOR ADDITIONAL FORMS ASSOCIATED WITH REMOVAL AND DISPOSAL OF

HAZMAT

Contractor shall submit a copy of Airspace Form 7460.1 to COR Contractor shall be responsible to follow up with airport division within 2 weeks of submission to verify receipt and ensure timely processing of the form.

PART 2 - EXECUTION

A. During the administration of the Contract, the Contractor will be required to complete various construction administration forms as a part of the Management System. These forms are identified above and will be issued at the Pre-Construction Conference. These forms may be revised during the construction period and the Contractor will be required to comply with any such revisions.

Federal Aviation Administration

Request For Information No. 000

Title:

From: Project: To:

Contractor Contractor address

Phone:

Fax:

Contact:

JOB TITLE

Job Location

Contract: Phone:

Fax:

RE:

Drawing or Spec:

Attachments? No

Date Started:

Date Required:

Date Completed:

Priority: Normal Potential Cost Impact? Yes No Potential Schedule Impact? Yes No If yes to either, explain below.

Question (Include Potential Impacts):

Response:

By: , FAA Date:

AAPPROVAL OR DISAPPROVAL OF CONTRACTOR’S

MMATERIALS OR SHOP DRAWINGS

DEPARTMENT OF TRANSPORTATION

FEDERAL AVIATION ADMINISTRATION

1. TO: 2. DATE CONTRACTOR’S SUBMITTAL RECEIVED: 3. DATE SUBMITTAL RETURNED:

Contractor Address

Tel: Fax:

4. GOV’T TRANS. NO. 5. CONTRACTOR’S TRANS. NO.

6. PROJECT NAME

7. CONTRACT NUMBER

ATTN:

8. TRANSMITTAL REFERENCE TO CONTRACT DRAWINGS and/or SHOP DRAWINGS

9. TRANSMITTAL REFERENCE TO CONTRACT DRAWINGS AND PARAGRAPH NUMBER and/or CHANGE ORDER NUMBER

10. FACTS:

Gentlemen: We are returning herewith the following Submittal Data:

A. B. C. D. E. APPROVAL F.

ITEM

NO.

NO.

COPIES NAME OF SUPPLIER TYPE OF MATERIAL OR EQUIPMENT AS

SUBMITTED

AS

NOTED*

NOT

APPROVED

REVISE

AND

RESUBMIT

G. REMARKS

H. STIPULATIONS

*Data marked “Approved as Noted” is satisfactory, contingent upon contractor acceptance of corrections and/or notations, and if accepted does not require re-submittal.

†Data marked “Not Approved” does not meet job requirements, and contractor must re-submit on proper basis.

Approval of Data does not obviate Contractor Responsibility for correct take-off or installation clearance.

Carbon Copies Transmitted To: Sincerely, Resident Engineer

FAA Form 3900-19 (03/13) Electronic Version (PDF) Page 1 of 12

This checklist is intended to be used as a tool by the resident engineer (RE) and other personnel overseeing construction to ensure adherence to Environmental and Occupational Safety and Health (EOSH) requirements at a project site. . It must be noted that contractors are responsible for ensuring the safety of their employees. The checklist may be used by the RE as a tool to support their oversight role at the construction site. The checklistmay be completed at the beginning of the project and reviewed and updated as the project proceeds.

This checklist relies on the training and professional judgment of the user. EOSH personnel should be consulted asneeded.

The purpose of this section is to provide a brief description of the construction project and/or specific maintenance tasks, and identify key personnel responsible for project completion. Fill in the requested site-specific information. Indicate if this work will occur in or adjacent to an occupied space.

Note: Provide further explanation of activities on additional sheets if necessary.

The following questions cover the most common EOSH related areas that may be encountered. This list is not inclusive. Consult with your designated EOSH professionals for additional guidance and assistance.

Construction Safety Subject Area Yes No/NA Comment

GENERAL

The project has the budget, work force, and schedule to develop an Accident Prevention Plan.

The accident prevention plan must include procedures for;

Preventing Accidents, Educating Employees and Conducting Accident Investigation.

29 CFR 1926 Subpart C

The construction site will be inspected before, during and after each shift for obvious hazards.

OSHA has the right to enter the work site to conduct an inspection at any time. Conducting routine inspections, correcting potential violations, and maintaining good general housekeeping can minimize possible findings.

29 CFR 1903.3, 29 CFR 1926.3(a), 29 CFR1926.25

A bulletin board will be posted with all required OSHA Notifications, safety literature, copies of accident reports and OSHA 300 Form.

Each employer is required to establish a location for posting of information, including: copies of the OSHA standards, specific safety standards, accident reports, and State specific safety postings.

29 CFR 1903.2(a)(1) and (2)

Concrete and/or masonry construction will take place as part of the project

If yes, complete Concrete and Masonry section below.

29 CFR 1926.700(a)

Structural Steel erection will take place as part of this project.

If yes, complete Steel Erection section below.

29 CFR 1926.750(a), (b) and (c)

The project will require welding, cutting, and/or brazing. If yes, completeWelding, Cutting, and Brazing section below.

29 CFR 1926.350, 1926.351 and 1926.352

This project will involve structural demolition. If yes, complete Demolition section below.

Section C. Construction Safety Subject Areas

Project Name and Description:

Project Location:

Facility:

Planned Start Date:

Expected Completion Date:

Contractor Contact: Name:

Project/Design Representative:Name:

COTR/Specialist:

EOSH Contact:

Facility Representative:

Name:

Name:

Name:

Phone:

Phone:

Phone:

Phone:

Phone:

Section B. Project Summary Information

Section A. Purpose

FAA Form 3900-19 (03/13) Electronic Version (PDF) Page 2 of 12

Construction Safety Subject Area Yes No/NA Comment

CONCRETE andMASONRY

Formwork and shoring must be adequate to support all intended loads during concrete placement.

29 CFR 1926.703(a)(1)

All protruding reinforcing steel will be guarded to eliminate impalement hazards.

29 CFR 1926.701(b)

All forms and shoring shall remain in place until a competent person determines that the concrete can support its weight and the weight of any superimposed loads.

29 CFR 1926.701(a)

Shoring equipment must be inspected immediately prior to, during and immediately after concrete placement.

29 CFR 1926.703(b)(3)

Work conducted over 4 feet above the next lower level shall comply with fall protection requirements.

See Climbing/Walking and WorkSurfaces.

Pre-cast wall units, structural framing, and tilt-up wall panels shall be supported to prevent overturning and collapse until permanent connections aremade.

29 CFR 1926.704(a)

A limited access zone will be established during masonry wall construction.

29 CFR 1926.701(c)

All masonry walls over eight feet in height shall be braced or supported to prevent collapse.

29 CFR 1926.706(b)

STRUCTURAL STEEL ERECTION

The project has the schedule, budget andmanpower needed to ensure the concrete attains 75% of its compressive strength.

Prior to beginning steel erection the prime/controlling contractor must provide written notice to the steel erection firm that the concrete has attained at least 75% of its compressive strength.

29 CFR 1926.751(a)

The project will require development of a site-specific traffic plan and site-specific erection plan.

Qualified person (also defined in § 1926.32) means one who, by possession of a recognized degree, certificate, or professional standing, or who by extensive knowledge, training, and experience, has successfully demonstrated the ability to solve or resolve problems relating to the subject matter, the work, or the project.

The controlling contractor is responsible for traffic control on the site to allow ease of steel delivery and movement of derricks, cranes, etc. Further, to ensure employee safety a site specific erection plan is required to be developed by a “qualified person.”

29 CFR 1926.752(c)(1) and (d)

The project requires inspections of all cranes, derricks, etc. by a qualified person before beginning each shift and of all rigging by a qualified rigger.

The contractor should supply or be able to supply their shift inspection form for equipment being used on the site. 29 CFR 1926.753(c)(1) and (2)

The crane or derrick operators training certificate is on site and copies of the certificates are maintained in the project file.

American National Standards Institute (ANSI) B30.2 through B30.22.

The crane operation is performed by a qualified or certified operator, with appropriate clearance from power lines and appropriate work area control.

OSHA Crane standard was recently revised extensively to cover crane operations, including certifications, operation, and training requirements.

29 CFR 1926.1400

The project requires all decking or roofing holes where an employee could…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .